Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-1 #1492 11 40 00/1 FOODSERVICE EQUIPMENT SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections, apply to this section. 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN OTHER SECTIONS A. Slab depressions, reinforced concrete wearing bed and interior finished floor at Walk In Refrigerator/Freezer. B. Concrete or masonry platforms with coved base at perimeter, for equipment. C. Slab depressions for stainless steel drain trench liner/grate assemblies. D. Corner guards. E. Supply and exhaust fans for foodservice exhaust/supply hoods. F. Roughing in and final connection of mechanical, electrical, and plumbing except indirect wastes built in to fabricated equipment. 1.4 QUALITY ASSURANCE A. In addition to complying with applicable laws, statues, building codes and regulations of public authorities, comply with the following: 01 National Sanitation Foundation (to bear label) 02 National Electric Code 03 Underwriters' Laboratories, Inc. 04 American Gas Association Laboratories 05 National Fire Protection Association 06 American Disabilities Act 1.5 SUBSTITUTIONS A. Equipment items or components specified are intended to be the Basis of Bid. All other brands, including additional names listed as "Approved Equal" must conform with the specifications, size, accessories, etc. of the first- named brand and be subject to Paragraph C-03 of this Article. B. Proposed Substitutions: 01 Submitted no less than 14 calendar days prior to Bid Date. 02. Submit with catalog data and/or manufacturer's shop details indicating all modifications required to conform with specified brand. C. Substitutions with Prior Approval: 01 Submitted on Bidder's letterhead attached to Proposal Form with each additive/deductive amount stipulated.

Transcript of SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified,...

Page 1: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-1

#1492 11 40 00/1 FOODSERVICE EQUIPMENT

SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections, apply to this section.

1.2 WORK

A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment.

1.3 RELATED WORK IN OTHER SECTIONS

A. Slab depressions, reinforced concrete wearing bed and interior finished floor at Walk In Refrigerator/Freezer.

B. Concrete or masonry platforms with coved base at perimeter, for equipment.

C. Slab depressions for stainless steel drain trench liner/grate assemblies.

D. Corner guards.

E. Supply and exhaust fans for foodservice exhaust/supply hoods.

F. Roughing in and final connection of mechanical, electrical, and plumbing except indirect

wastes built in to fabricated equipment.

1.4 QUALITY ASSURANCE

A. In addition to complying with applicable laws, statues, building codes and regulations of public authorities, comply with the following: 01 National Sanitation Foundation (to bear label) 02 National Electric Code 03 Underwriters' Laboratories, Inc. 04 American Gas Association Laboratories 05 National Fire Protection Association 06 American Disabilities Act

1.5 SUBSTITUTIONS

A. Equipment items or components specified are intended to be the Basis of Bid. All other brands, including additional names listed as "Approved Equal" must conform with the specifications, size, accessories, etc. of the first- named brand and be subject to Paragraph C-03 of this Article.

B. Proposed Substitutions:

01 Submitted no less than 14 calendar days prior to Bid Date. 02. Submit with catalog data and/or manufacturer's shop details indicating all

modifications required to conform with specified brand.

C. Substitutions with Prior Approval: 01 Submitted on Bidder's letterhead attached to Proposal Form with each

additive/deductive amount stipulated.

Page 2: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-2

#1492 11 40 00/2 FOODSERVICE EQUIPMENT

02 Owner reserves the right to accept or reject any or all substitution proposals before execution of contract.

03 Provide all engineering services required to make adjustments in space, utilities, etc. and pay all additional costs of utilities or construction that may occur due to the requirements of the accepted substitutions.

1.6 WARRANTY

A. Provide a written warranty for a period of one year from the date of Substantial Completion, including extended four year replacement warranty on compressor bodies.

B. Components of equipment subject to replacement prior to one-year's use (such as steam

cooker door gaskets) and those items which may fail due to improper or inadequate maintenance by the Owner/Operator (such as an uncleaned refrigeration system condenser) are not intended to be included within the scope of the Warranty.

C. Refrigeration systems/equipment: One year free service available within twenty-four

hours of notification.

1.7 INSTRUCTIONS TO BIDDERS A. During Bidding: Contractor's or vendor's questions and comments pertaining to document

clarity or intent will be responded to with addendum. 1.8 SUBMITTAL DATA

A. Special Requirements: The following are in addition to any general requirements given elsewhere in the Documents.

B. Procedures: Submit to the consultant (through the Architect) for preliminary review, one (1) electronic copy and/or at least two (2) prints/hardcopies, within four weeks after award of contract. Upon return of one (1) copy of data, submit the required number of copies to the Architect for processing. Partial submittals will not be accepted or processed.

C. Brochure: 01 Front and rear covers with labeled project name. 02 A separate flysheet for each component or item of equipment, indicating: item

number, name, quantity, manufacturer, optional equipment, modifications, and utility requirements. An item of equipment or assembly containing more than one buy out sub assembly or component shall have the secondary item listed in parenthesis beside the primary item name, i.e, Dishtable (Disposer).

03 Catalog specification sheet and/or manufacturer's drawing.

D. Plan and Rough in Drawings: 01 1/4" scale drawing of fixed/non fixed Foodservice Equipment with itemized

schedules. 02 Separate drawing sheets of same size as contract drawings (Contract Drawings

are not to be traced or reproduced). 03 Electrical roughing in drawing. 04 Plumbing/mechanical rough in drawing. 05 Critical dimension drawings, sizing and locating the following conditions:

a. Slab depressions or block outs. b. Concrete or masonry platforms. c. Pipe sleeves or roof jacks.

06 Required information: a. All fixed and movable Foodservice Equipment shown on Contract

Drawings.

Page 3: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-3

#1492 11 40 00/3 FOODSERVICE EQUIPMENT

b. All general use and convenience utilities or services indicated, including those required or connected to equipment or devices not in this Section.

c. All roughing in drawings fully dimensioned from finished room surface and/or established column lines to point of stub up through floor and stub out through wall or ceiling for all mechanical, electrical and plumbing services.

E. Shop Drawings: 01 Sheet Size: Identical to Contract Drawings drawn at 3/4" scale for plan view and

elevations, and 1-1/2" scale for sections and construction details. 02 Included information: Item Number, name and quantity 03 Construction details, sections and elevations to reflect requirements of the

specifications and drawings. 04 Adjacent walls, columns and equipment. 05 Plumbing and electrical schematic drawings for equipment such as; conveyors,

self-cleaning exhaust hood, exhaust hood fire protection systems, and fabricated fixtures with single electrical and/or plumbing connection.

1.09 OPERATIONS & MAINTENANCE MANUAL

A. Three copies bound in 1-1/2" hardback, three ring binders (as many volumes as required by scope of project) with same data as brochure at completion of installation.

B. Catalog specification sheet and/or manufacturer's shop drawings.

C. Manufacturer's operating/maintenance data including replacement parts information and

price list. Provide the name, title and address of personnel at each respective manufacturer to be contacted for spare of replacement parts after guarantee period.

D. Furnish a list of all equipment and their respective local service agencies, indicating the

address, telephone number and name of person to contact. Whenever possible, the service agencies selected shall be factory authorized for the equipment assigned.

1.10 VERIFICATION AND COORDINATION OF PROJECT/DATA

A. Refrigerated and Dry Storage Areas: Verify and coordinate dimensions to accommodate modular shelf sections. Notify Architect of variance between the Contract Documents and actual conditions.

B. Rough-In Drawings: Review for accuracy and completeness and notify Architect of

deficiencies. Field-check locations. Cooperate and coordinate work with other sub-contractors.

C. Dimension Responsibility: Obtain actual or guaranteed measurements for proper fit of

equipment. All dimensions given are approximate and are as accurate as can be determined at this time. Field check all measurements and conditions at the building prior to fabrication or delivery of equipment and notify the Consultant of any deviation from the dimensions shown.

D. Scheduling to Fit Openings: Should it become necessary to schedule construction of

walls or partitions prior to delivery of fixed equipment, the equipment must be fabricated for passage through finished openings. Maintain close contact with the project and be cognizant of all conditions.

E. Existing Equipment: Foodservice Contractor is responsible for verifying mechanical,

electrical and plumbing characteristic of any existing equipment scheduled for re-use prior to submitting rough-in drawings. Foodservice Contractor to perform all tasks

Page 4: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-4

#1492 11 40 00/4 FOODSERVICE EQUIPMENT

required to integrate/complete any new items with existing equipment and field conditions.

PART 2 - PRODUCTS 2.1 MATERIAL/COMPONENTS

A. Stainless steel sheets and/or shapes: 18-8, Type 304, polished to 180 grit No. 3 finish. 01 Stainless steel joints and seams: heli-arc welded, free of pits and flaws, ground

smooth and polished to No. 4 finish. 02 The "grain" direction of horizontal stainless steel surfaces: longitudinal, including

the back splash. The polishing procedure at right angle corners of fixtures shall provide a mitered appearance.

B. Galvanized Iron Sheets: Armco copper bearing Zinc Grip or Zinc Grip/ Paint Grip.

01 Galvanized iron joint and seams: arc welded, free of pits and flaws and ground smooth.

02 Galvanized sheets and/or shapes: washed with mineral spirits and primed with Rustoleum enamel in color selected by Architect.

C. Sound Deadening: Schnee Butyl Sealant 1/2" wide rope positioned continuously

between all frame members and underside of stainless steel tabletops, overshelves and undershelves. Tighten stud bolts for maximum compression of sealant.

D. Plastic Laminates/Corian: color/pattern selected by Architect, in 1/16" thickness for flat

surfaces; 1/32" thickness for radiused surfaces. Plastic laminates and adhesives must be approved by N.S.F. (Standard No. 35).

E. Identification Plates, Labels, Tags:

01 Prohibited Information: Names of suppliers, fabricators and contractors. 02 Required Information: function or purpose of such things as display light

switches, food warmer controls, etc. 03 Plate Construction: engraved phenolic plastic, secure to equipment with epoxy

cement or stainless steel screws. Furnish samples. 2.2 PLUMBING/MECHANICAL REQUIREMENTS

A. Plumbing fittings and components: furnished under this Section as follows. Components which are provided loose under this Section for field installation and connection by Division 22 are indicated by asterisk* or as indicated on details. 01* Control valves, water pressure regulators, vacuum breakers and chrome plated

90º elbows and nipples (no copper piping above splash) wherever required on Foodservice Equipment.

02* Faucets and drain fittings with connected overflows for all sinks. 03* Specialty Foodservice water fill faucets or hose assemblies indicated in

drawings/specifications. 04* Wade No. W-10 Shock Stop shock absorbers for all Foodservice Equipment with

quick opening or solenoid operated water valves. 05 Extensions of indirect waste originating with-in fabricated counters and/or

equipment to open site drains. Drains: 1" minimum, Type "K" copper. All material and labor for final connection from equipment/sink tail pieces and anklets to open-sight drain over building floor sink or drain by Division 22.

06 All drainlines furnished with equipment: 1" thick insulation. 07 Piping brackets and/or supports beneath/within fabricated equipment.

Page 5: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-5

#1492 11 40 00/5 FOODSERVICE EQUIPMENT

B. Final Plumbing Connections Provisions: 01 Fabricated equipment containing components, fittings and/or devices indicated

on Foodservice Connections Drawings to be connected to the building systems shall have each component, fitting or group thereof prepiped to a utility compartment for final connection by Division 22. Refer to drawings for capacities.

02 Division 22 to supply all required piping/nipples, etc. to make complete installation. All gas lines connected to equipment with flexible hoses with quick connection action. (Quick-connects and steel reinforced supply hoses, by K.E.C.) Installed by Division 22.

03 Field assembled equipment (i.e., conveyor systems, exhaust hoods, conveyor type dishware machines, convection ovens, etc.) shall have plumbing components completely interconnected under this Section for final connection by Division 22 in arrangements indicated on Utility Connection Drawings by Division 22.

04 Back flow preventers, when required by local code, to be provided by Division 22.

C. Ducts and Vents: 01 Exhaust hoods, which are furred in to ceiling: 2" high duct collar for final

connection to duct system. 02 Dishwash machine equipped with integral vent cowls or extended hoods:

furnished with 18 gauge stainless steel seamless duct risers to 6" above finish ceiling for final connection. The duct: trimmed at ceiling with 16-gauge stainless steel angle flange with all corners welded.

2.3 FOODSERVICE EQUIPMENT REFRIGERATION SYSTEMS

A. Install complete with all refrigerant, oil, dials, dehydrators, gauges, controls as required for the proper operation of the system.

B. Self contained or factory installed compressors: check and adjust to proper operating

temperature.

C. Refrigeration Components: 01 Unit coolers: specified quantity and model, ceiling hung by 1/2" o.d. nylon bolts

with stainless steel washers and nuts. Insert hanger bolts through plastic sleeve and seal penetration airtight. a. Unit cooler drain fittings: positioned as indicated on drawings. Install

cast tee fitting on drain-pan outlet with union, clean out plug and extend 1" copper drain-line through wall panel to air gap fitting or floor drain.

b. Slope drain-line 1/2" per foot, trap at exterior of assembly and turn down into drain. Manifold drainlines of adjacent compartments wherever possible.

c. Install plastic sleeve through compartment wall, seal around drain-line and install stainless steel escutcheon with setscrew.

d. Heat exchanger: on all unit coolers; in proper size. e. Electric drain-line heater cable: on all unit coolers operating below 36

degrees F, installed from drain-line fitting to wall penetration. Heater cables: minimum rating of 30 watts/ lineal foot, 120 volt. Wrap drain-line with maximum spacing of 2" loop spacing. Interwire to unit cooler for continuous operation.

D. Refrigerant System Installation:

01 Refrigerant lines: Type "L" hard copper tubing. Fittings: wrought copper or brass designed for use with high temperature solder. Piping joints: made with silver solder (Sil-Fos). Piping: properly suspended from and anchored to the

Page 6: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-6

#1492 11 40 00/6 FOODSERVICE EQUIPMENT

structure with adjustable hangers 6' o.c. maximum. Suction lines: sized to have maximum pressure drop of two pounds in medium temperature systems; one pound in low temperature systems. Liquid lines: sized to give maximum pressure to prevent trapping of oil. Rigid insulation: 1" thick Armstrong Accotherm (1-1/2" thick at low-temp) with factory applied fire retardant jacket and vapor barrier on all suction lines.

02 Cover exterior refrigeration lines with aluminum jacketing. Seal any openings where lines pass thru exterior walls with expanding foam. Paint silver to match aluminum jacketing.

E. Evacuation and Charging:

01 After completion of the pressure test, the system shall be evacuated using an approved auxiliary vacuum pump. Connections for evacuation in accordance with manufacturer's recommendations.

02 Charging subsequent to the initial charge, which is contained in the condensing unit: given through the charging valve in the high side passing all the liquid refrigerant through a charging dehydrator. All charging lines and gauges: purged of air prior to connection with system. After the system is fully charged: started and placed in full operation.

F. Refrigerant Leak Detection Systems

01 In the City of Houston and any other jurisdiction with similar requirements, when the quantity of refrigerant in the system dictates the necessity for a refrigerant leak detection system, this system shall become the responsibility of the foodservice contractor.

2.4 ELECTRICAL REQUIREMENTS

A. Electrical fittings and components: furnished under this Section as follows. Components provided loose under this Section for field installation and connection under Division 26 are indicated with, by asterisk * or as indicated on detail. Coordinate foodservice equipment voltage and phase with building system. 01* Ceiling lights, pre-wired with pigtails and mounting hardware consisting of F.S.

J/box with cover and G.I. or plastic nipple to fasten to walk-in box ceiling panels. K.E.C. to provide all lights and drill holes in walk-in boxes ceiling, Division 26 will install lights and loop wire to electrical roughing-in J/box above walk-in boxes door panel and seal all holes in panels. All wiring to be above ceiling panels in code acceptable conduits.

02 Division 26 to connect all control wiring for walk-in box evaporators from remote compressor panel to walk-in box evaporators and provide disconnect switch on evaporator, all wiring rigid metal conduit, to code requirements. K.E.C. to supply remote outdoor refrigeration racks, pre-wired to master control panel. Division 26 to connect power lines from roughing-in points to master control panel.

B. Cord and caps: 01 Coordinate all Foodservice Equipment cord/caps with related receptacles. 02 All 120 volts "plug in" equipment shall have Type SO or SJO cord and plug with

ground wire fastened to frame/body of item. 03 Cord lengths for fixed equipment: adjusted to eliminate loose-hanging excess. 04 All non-fixed plug in "buy-out" equipment shall have Hubbell configuration,

ratings as required.

C. Switches and Controls: 01 Each motor driven appliance or electrically heated unit: equipped with control

switch or starter as per Underwriters' Laboratories, Inc. with low voltage and overload protection.

Page 7: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-7

#1492 11 40 00/7 FOODSERVICE EQUIPMENT

D. Motors:

01 120-volt motors; manual tumbler type starter with thermal overload protection and interchangeable heating elements.

02 208 volt and 480 volt motors; magnetic starter with low voltage protection and one interchangeable overload relay per phase.

E. Receptacles and Switches:

01 Receptacles installed in/on-fabricated equipment: Hubbell, Inc. assemblies mounted in a metal box with stainless steel cover plate.

02 Load centers installed in/on fabricated equipment to have all fixture components pre-wired to load center with balanced phase loading. Load center ready for final connection by Division 26.

F. Final Electrical Connection Provisions:

01 Fabricated equipment containing electrically operated components and/or fittings indicated on Utility Connections Drawings to be direct connected, shall have each component, fitting or group thereof pre-wired to a junction box for final connection by Division 26. Refer to drawings for circuit loading.

02 Fabricated equipment containing electrically operated components and/or devices indicated to have a circuit breaker load center shall have each component or device pre-wired to a separate circuit breaker for balanced phase loading and single final connection by Division 26.

03 Field assembled equipment (i.e., prefabricated walk in refrigerator/freezers, exhaust hoods), shall have electrical components completely interconnected in this Section for final connection arrangements as indicated on Utility Connection Drawing.

2.5 CUSTOM FABRICATED/ASSEMBLED UNITS

All fixtures within this Section are to be constructed by one manufacturer, of uniform design and finish.

A. Counter/Tabletops:

01 14-gauge stainless steel; all free edges turned down 180° on 1 5/8" radius. Free corners: rounded on 3/4" radius.

02 Marine edges: turned up 1/2" on 45° angle and turned down 2" with 3/4" tight hem at bottom.

03 Tops abutting high fixtures or walls: cove up 6" and slope back 1-1/2" at top on

45°angle; 2-1/2" where piping occurs. Turndown 1" at rear of splash and close ends to bottom of top turndown. Secure splash turndown to wall with 4" long 14 gauge Stainless Steel "zee" clip anchored to wall, 36" o.c.

04 Freestanding tables and all serving counter splash risers: turned back on 90° angles with 1" turndown at rear.

05 Brace tops with rigid-welded 1-1/2" x 1-1/2" x 1/8" galvanized steel angle frame at perimeter with cross bracing 2'-0" o.c. maximum. Provide 4" x 4" x 12 gauge steel triangular pads where leg socket welds to gusset. Paint entire frame with Rustoleum Primer. Angle frames: secured to underside of top surfaces with 1/4" studs welded 9" o.c. maximum with chrome-plated washer, lock washer, and cap nut. Studs: such length that cap nuts can be made-up tight, bringing top down snugly on an angle frame eliminating all vibrations or "oil-cannings."

06 All tops: 1-1/2" overhang at free sides of underframe or Closed Base Body. 07 All openings in tops shall have raised die formed edges, 3/16" high. 08 Reinforce all "built-in" counter equipment with framing members at perimeter of

opening.

Page 8: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-8

#1492 11 40 00/8 FOODSERVICE EQUIPMENT

B. Food Wells: 01 Food warmer controls: remote mounted in sloping recessed apron panel.

Control panel is recessed with 2-1/2" from bodyline at top of 60° slope, 1" at lower edge. Terminate slope angle 2-1/2" below under counter top.

02 Manifold all warmer drains and extend to within utility compartment for indirect waste connection. Install valve in drain-line and extend handle through compartment door. Provide individual P.O. plugs for each warmer.

C. Sinks:

01 14-gauge stainless steel, all corners coved on 3/4" radius. Provide 1-1/2" wide double walled partitions with flat tops between compartments.

02 Exposed exterior panels of multiple compartment sinks are to be continuous. All gaps between compartments must have 14-gauge stainless steel filler panel welded, ground and polished.

03 Score and slope sink bottom 1/2" to drain. Set overflow centerline 1" below drainboard.

04 Fabricator may use at his option die stamped sink inserts of size and gauge specified.

D. Warewash Assembly:

01 Dishtable: a. 14 gauge stainless steel; all free edges coved up 3" with 1-1/2" diameter

rolled rim and bullnosed corners. Two full length 1/8" high die-formed inverted "vee" ridges 10" o.c. at longitudinal centerline of top, with tapered ridge ends.

b. Edge of dishtables next to high fixtures or walls: coved up 10" and sloped back 1-1/2" on 45 degree angle; 2-1/2" where piping occurs. Turn down 1" at rear of splash and close ends to bottom of rolled rim. Secure splash turndown to wall with 4" long 14 gauge stainless steel "zee" clips anchored to wall, 36" o.c.

c. Slope tables 1/8" per foot, maintaining level crown and cove all corners on 3/4" radius.

d. Brace dishtables with 1" x 4" x 12 gauge stainless steel channels down centerline of top and between each pair of legs, with closed ends. Bracing: secured to underside of dishtable with 1/4" studs welded 6" o.c. maximum, with chrome plated washer, lock washer and cap nut. Studs: such length that the cap nuts can be made up tight, bringing the dishtable down in the channel members, eliminating all vibration and "oil-cannings."

E. Closed Base Bodies:

01 Frame: rigid welded 1-1/2" x 1-1/2" x 1/8" galvanized steel angle forming a continuous structure around the top and bottom perimeters of the fixture, a post at each corner, studs spaced 48" o.c. maximum and shelf stringers. Top of frame is cross braced with 1-1/2" angles, 2'-0" o.c. maximum.

02 Panel and trim with 18-gauge stainless steel, having concealed attachment with all seams being welded, ground and polished.

03 Exposed vertical corners rounded on 3/4" radius. Closed Base Bodies adjacent to walls or fixtures have square corners.

04 Close and seal vertical and horizontal channel at shelf interiors or drawer enclosures, such as corners and center mullions.

05 Closed Base Bodies set on masonry platforms: closed and caulked at underside of equipment overhang and bolted to platform. Bodies overhang platform 1" at free ends; 2" at front and exposed rear sides.

Page 9: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-9

#1492 11 40 00/9 FOODSERVICE EQUIPMENT

F. Utility Compartments: 01 Closed Base bodies: fitted with utility compartments wherever piping or wiring is

required in/on the fixture. 02 Same material as Closed Base bodies with back and end partitions. Omit

bottoms only. 03 Access doors: 18 gauge stainless steel double pan type with channel formed

horizontal recessed pull full length of top (similar profile to Garcy No. R-1060) with closed ends. Offset the lower horizontal framing member of the Closed Base fixture to permit flush alignment of door with face and bottom edge of body. Door hardware: two Component Hardware No. M74-3078 stainless steel hinges and one Component Hardware No. M27-2470 catch. The recess on plumbing compartment door is to be constructed using an APW stainless steel bowl with the bottom removed to allow the handle to be accessible.

04 No shelves of Closed Base fixtures are to be penetrated.

G. Serving Counters: 01 Exterior body panels: 3/4" thick hardwood plywood with plastic laminate in

Architect's selection of color/pattern at all exposed surfaces; backing sheet where concealed.

02 Position and finish horizontal and/or vertical reveal as directed by Architect. 03 Secure laminated panels to counter body framing in concealed manner. Install

removable panels with "zee" clips overlapping body-framing members. 04 Rear side and interior of serving counters: closed base bodies. Vertical juncture

of plastic laminate and stainless steel at rear corners of body: a 1/2" wrap around of stainless steel for flush joint with plastic laminate.

H. Open Base Structures:

01 1-5/8" o.d. x 16 gauge seamless stainless steel tubing legs beveled at bottom. Fully weld 1-1/4" o.d. crossrails to legs.

02 Top of leg: inserted in Component Hardware No. A20-0206 socket fully welded to table frame or sink bottom gusset.

03 Round foot: Component Hardware No. A10-0852. 04 Table bases: maximum leg spacing of 5'-0" o.c.; dishtable and utensil wash

counter bases at 5'-0" o.c.

I. Overshelves: 01 16 gauge stainless steel with free edges turned down 1" with 1/2" tight hem at

bottom. ¾” radius at free corners. 02 Turn up 2" raw at walls or adjoining high fixtures with horizontal coved corner at

rear. Round front corners of turnup on 3/4" radius. 03 Where shelf width exceeds 12" width, reinforce with 1/2" x 4" x 14 gauge stainless

steel closed hat channel full length of shelf. 04 Wall mounted shelves: Keil Model No. 1508-1010-1251 or equal brackets 48"

o.c. maximum set in 6" from ends. Coordinate wall backing with General Contractor at gypsum board walls or as required.

05 Freestanding shelves: Where turnup is required at free overshelves, the shelf is to be turned up 2" at ends, coved up at rear and hemmed tight to bottom of front turndown. Weld exposed corners.

06 Freestanding overshelves: Keil or equal cantilevered brackets at rear of table; Keil double cantilevered brackets at center of table. Posts for cantilevered overshelves are 1-5/8" o.d. x 16 gauge stainless steel secured to underframe, 4'-0" o.c. to underframe, 4'-0" o.c. Ends of shelves: Secured to adjacent wall/fixture or mounted on 1-1/4" diameter stainless steel posts.

07 Freestanding overshelves not on cantilevered brackets: 1-1/4" o.d. x 16 gauge stainless steel posts, each pair at 4'-0" o.c., maximum.

Page 10: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-10

#1492 11 40 00/10 FOODSERVICE EQUIPMENT

J Undershelves: 01 Open Base Structures: 16-gauge stainless steel turned down 1-1/2" tight hem at

bottom. Notch all corners to fit tubular legs and weld from underside to completely fill gap; grind and polish. Cove up 2" at rear and/or ends adjacent to wall, columns, refrigerators, etc. The turnup is to be hemmed tight to bottom of turndown when turnup is specified for freestanding fixtures. Brace undershelf with 1" x 4" x 14 gauge stainless steel channel at longitudinal centerline and at each intermediate pair of legs.

02 Closed Base Fixtures: 16 gauge stainless steel turned down 1-1/2" at front. Front edge of bottom shelf: turned back and sealed to masonry platform or boxed for leg application. Center shelf has 3/4" tight hem. a. Shelves: turn up square at ends (coved up at rear only) to the shelf

above or counter top flanged out for attachment with no open spaces at interior.

b. All shelf partitions at exposed ends of cabinet bodies or interiors: free of exposed framing members.

c. Reinforce shelves with full-length 1" x 4" x 14 gauge stainless steel closed hat channel.

d. Unless otherwise noted, all undershelves are to be 22" deep, clear. e. Weld the vertical seam of shelf turndown/turnup with face of body

partition.

K. Shop/Field Joints: 01 Stainless steel tops: welded, ground and polished to No. 4 finish.

PART 3 - EXECUTION 3.1 DELIVERY AND INSTALLATION

A. Supervision: Provide a competent foreman or supervisor who shall remain on the job during the entire installation.

B. Delivery: Foodservice Equipment excluding exhaust hoods, trench liners and walk-in

coolers/freezers are not to be delivered and/or set in place until the following construction has been completed: kitchen floors prepped and cleaned, walls painted, ceiling installed and wiring pulled to junction boxes. (note 1. acid floor washes are not to be used on or near stainless or aluminum surfaces. 2. Walk-in doors are to remain open during concrete cure). 01 Assemble, square, level and make ready items for the final utilities connections. 02 Scribing: cut neatly around obstructions to provide sanitary conditions. 03 Where gaps occur between equipment, apply General Electric silicone

construction sealant Series SE-1200 mastic or stainless steel trim molding of proper shape with concealed attachment. Use epoxy cement and/or "zee" clips wherever possible to secure trim.

3.2 CLEAN AND ADJUST

A. Clean up and remove from the job site, all debris resulting from the work as the installation progresses.

B. Thoroughly clean and polish all Foodservice Equipment, in and out, ready for Owner's

use prior to demonstration and final inspection.

C. Lubricate and adjust drawer slides, hinges, casters.

D. Clean and replace faucet aerators, water strainers.

Page 11: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-11

#1492 11 40 00/11 FOODSERVICE EQUIPMENT

E. Touch up damage to painted finishes.

F. Start up and check all refrigeration systems for at least 72 hours prior to acceptance.

3.3 EQUIPMENT START UP/DEMONSTRATION

A. Carefully test, adjust and regulate all equipment in accordance with the manufacturer's instructions and certify in writing to the Owner that the installation, adjustments and performance are in full compliance.

B. Provide the Owner and/or Operators with a thorough operational demonstration of all

equipment and furnish instructions for general and specific care and maintenance. 3.4 FINAL INSPECTION

A. Final inspection will be made when the contractor will certify that he has completed his work; made a thorough review of the installation/operation of each item in the contract and found it to be in compliance with the construction documents.

B. The Foodservice Consultant's repetitive final inspection and all costs associated thereto,

incurred due to the Contractor's failure to comply with the requirements of this Article, will be invoiced to this Contractor.

4.0 EQUIPMENT SCHEDULE

A. Provide regularly manufactured equipment components included in this Section with standard finishes and accessories unless specifically deleted or superseded by the Contract Documents.

LEVEL 1 Item No. 01 - Refrigeration System Quantity One (1)

A. One (1) Refrigerated Design of Texas Model No. IRW1-2, indoor water cooled

refrigeration rack. System to have the following units: Refrigerator 01. One (1) Model No. ZS13KAE, 1.8 h.p., 208 volt, three phase, condensing unit. 02. One (1) Model No. LET-120, 208 volt, single-phase evaporator coil. 03. Refrigerant R-404A. 04. Adjust thermostat to 34ºF. Freezer 01. One (1) Model No. ZF15K4E, 5.0 h.p., 208 volt, three phase condensing unit. 02. One (1) Model No. LET-160, 208 volt, single-phase evaporator coil. 03. Refrigerant R-404A. 04. Adjust thermostat to -10ºF.

Item No. 02 - Walk-In Cooler/Freezer Assembly Quantity One (1) Lot

A. One (1) Thermo-Kool or Thermalrite two (2) compartment assembly. Assembly panels to

be the nearest nominal size to attain a height of 8’-6” to 8'-8" from top of exterior walk in panels to finished floor. Set in floor recess per Detail C, Sheet F-1.2. 01. 20 gauge stainless steel exterior where exposed, .040" stucco embossed

aluminum interior. Galvalume exterior finish where not exposed. 02. Self closing doors with heated view windows.

Page 12: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-12

#1492 11 40 00/12 FOODSERVICE EQUIPMENT

03. Full perimeter high wattage door heaters. 04. Heated thresholds. 05. Heated pressure relief port at freezer. 06. Dial type thermometer. 07. Foot treadle. 08. Matching closure panels to finished ceiling. 09. Stainless steel trim strips at gaps between building walls and walk-in assembly. 10. Provide one (1) Kason Model No. 1806LED000, LED light fixture and optic globe

above each door at the interior of the walk-in. 11. Twelve (12) Kason Model No. 1810L21248LB, LED light fixtures with lamps.

Pre-wire fixtures to J-Box mounted above each compartment no exposed conduit inside walk-in.

12. 36” high 18 gauge stainless steel kick plate at interior and exterior of doors. 13. Provide wall mounted door bumpers on walk-in exterior. 14. Provide two-piece strip curtain swinging doors with mounting hardware at cooler

and freezer.

Item No. 03 - Walk-In Cooler/Freezer Shelving Quantity One (1) Lot

A. One (1) Lot InterMetro "Metro Max Q" shelving, four (4) tiers high, each section with four (4) MQ74PE, posts. Sections as follows: Refrigerator 01. Three (3) MQ1848G shelf sections. 02. Two (2) MQ2436G shelf sections. 03. Two (2) MQ2442G shelf sections. 04. Eight (8) MQ2448G shelf sections. Freezer 01. Three (3) MQ1848G shelf sections. 02. Two (2) MQ2436G shelf sections. 03. One (1) MQ2442G shelf section. 04. Eight (8) MQ2448G shelf sections.

Item No. 04 - Dry Storage Shelving Quantity One (1) Lot

A. One (1) Lot InterMetro "Metro Max Q" shelving, five (5) tiers high, each section with four (4) MQ74PE, posts. Sections as follows: 01. Four (4) MQ1848G shelf sections. 02 Two (2) MQ2436G shelf sections. 03. One (1) MQ2442G shelf sections. 04. Seven (7) MQ2448G shelf sections.

Item No. 05 - Number Not Used Item No. 06 - Preparation Sink Quantity One (1)

A. One (1) preparation sink assembly; size and shape as indicated on drawings. B. ½” marine edge at front; 10" high splash at wall. C. Two (2) 2'-0" x 2'-2" x 1'-3" deep sink compartments. Weld ¼” stainless steel rods into

sink corners for sink cover holders. D. Two (2) Read Products “Richlite” ½” thick removable sink covers (with finger holes) at

each sink. One (1)14 gauge stainless steel vertical sink cover rack mounted per drawings; refer to Elevation , Sheet FS-.

Page 13: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-13

#1492 11 40 00/13 FOODSERVICE EQUIPMENT

E. Two (2) Component Hardware Model No. D53-7215, rotary waste drains with connected overflow and tailpiece.

F. One (1) T & S Model No. B-0231, splash mount faucet.

G. One (1) T & S Model No. B-0163, pre-rinse with Model No. B-0107-C, spray valve unit

with low flow spray head with B-0109, wall bracket and two (2) Model No. BCVH ½” check valves.

H. One (1) T & S Model No. B-0669-POL, hose bibb faucet. Garden hose provided by

owner. Mount on 14 gauge stainless steel bracket; refer to Detail , Sheet FS-.

I. Open base construction.

J. Provide undershelf as indicated on drawings.

K. Install disposer and control panel where indicated. Provide stainless steel bracket for control panel.

L. One (1) wall mounted overshelf; length as indicated on drawings.

Item No. 07 - Disposer Quantity One (1)

A. One (1) Salvajor Model No. 200-CA-18, disposer with 18" diameter cone assembly. Red Goat is an approved alternate manufacturer. 01. One (1) Model No. ARSS-LD, control panel. 02. One (1) Model No. 980105 stainless steel mounting bracket for control panel.

Mount control panel and bracket where indicated on drawings. 03. One (1) dejamming prong.

B. Mount in Item No. 06 - Preparation Sink. Item No. 08 - Chemical Storage Shelving Quantity One (1) Lot

A. One (1) Lot InterMetro "Metro Max Q" shelving, five (5) tiers high, each section with four (4) MQ74PE, posts. Sections as follows: 01. Six (6) MQ1848G shelf sections. 02. One (1) MQ2448G shelf section.

Item No. 09 - Food Processor Quantity One (1)

A. One (1) Berkel Model No. M2000, food processor. Robot Coupe is an approved alternate manufacturer. 01. "S2" slicer. 02. "S3" slicer. 03. "S5" slicer. 04. “S11” slicer. 05. "D11" dicing grid. 06. "SH3" shredder plate. 07. "SH7" shredder plate. 08. "J6 x 6" julienne slicer.

B. Set on Item No. 17 - Worktable as indicated on drawings.

Item No. 10 - Number Not Used

Page 14: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-14

#1492 11 40 00/14 FOODSERVICE EQUIPMENT

Item No. 11 - Fire Protection System Quantity One (1)

A. One (1) Ansul Model No. R-102, automatic liquid chemical system with all components required by NFPA Pamphlet No. 96, installed in hood in accordance with manufacturer's recommendation. Provide duct and plenum protection to Item No. 22 - Exhaust Hood, and surface protection as required to cooking equipment below.

B. Remote manual release in path of egress from protected exhaust hood area. Provide trim ring around pull.

C. Locate top of chemical cylinders as indicated on the drawings at ceiling level and install

piping to hoods in a totally concealed manner. Any exposed piping and fittings shall be chrome plated or sleeved with stainless steel tubing. Exposed pipe threads in/above food zone are not acceptable.

D. Mechanical gas shut-off valve (installed in line by plumber).

Item No. 12 - Fill Faucet Quantity One (1)

A. One (1) T & S Model No. B-0610, wall mount fill faucet. Mounted on wall 44” A.F.F. with stainless steel bracket where indicated on drawings. Refer to Detail N, Sheet FS-1.6.

Item No. 13 - 40-Quart Mixer Quantity One (1)

A. One (1) Hobart Model No. HL400, 40 quart mixer.

01. Stainless steel 30 quart bowl, beater, whip and adaptor. 02. 9" vegetable slicer with slicer plate, grater and shredder. 03. Protective rubber feet. 04. 40 Quart Stainless Steel bowl 05. 40 Quart "B" Beater 06. 40 Quart "D" Wire Whip 07. 40 Quart "ED" Dough Hook 08. 40 Quart Bowl Scraper 09. 40 Quart Bowl Truck 10. 40 Quart Ingredient Chute.

Item No. 14 - Slicer w/Stand Quantity One (1)

A. One (1) Berkel Model No. 829A-PLUS, slicer. Secure slicer to stand.

B. One (1) Piper Model No. 705-1, slicer stand or fabricated equal.

Item No. 15 - Baker’s Table w/Ingredient Bins Quantity One (1)

A. One (1) baker's table assembly; size and shape as indicated on drawings.

B. 14 gauge stainless steel top with 6” high integral coved risers at rear and end; turn front down 2” square.

C. Four (4) Cambro Model No. IB36-148 ingredient bins.

D. One (1) 16-gauge stainless steel flour trough on front of table. E. Omit front crossrails to accommodate ingredient bins.

Page 15: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-15

#1492 11 40 00/15 FOODSERVICE EQUIPMENT

F. Open base construction.

G. One (1) full-length table mounted overshelf. Item No. 16 - Worktable Quantity Two (2)

A. Two (2) worktable assemblies; size and shape as indicated on drawings.

B. Turn free sides down 2" square; ¾” radius corners.

C. One (1) drawer assembly.

D. Open base construction.

E. Undershelf as indicated on drawings. Item No. 17 - Worktable Quantity Two (2)

A. Two (2) worktable assemblies; size and shape as indicated on drawings.

B. Turn free sides down 2" square; 6” high splash at wall.

C. One (1) drawer assembly.

D. Open base construction.

E. Undershelf as indicated on drawings. Item No. 18 - Mobile Utensil Rack Quantity Two (2)

A. Two (2) InterMetro "Super Erecta" Model No. 2448LS stainless louvered embossed mobile utensil racksm, four (4) tiers high each section with four (4) 63UPS, posts for use with stem casters. Mount shelving on Model No. 6MPB casters with brakes.

Item No. 19 - Three-Compartment Sink Quantity One (1)

A. One (1) three compartment sink assembly; size and shape as indicated on drawings. B. 1-1/2" rolled rim at front and ends; 10" high splash where adjacent to walls.

C. Three (3) 2'-0" x 2'-2" x 1'-3" deep sink compartments. D. Three (3) Component Hardware Model No. D53-7215, rotary drains with connected

overflows and tailpiece.

E. Two (2) T & S Model No. B-0290, splash mount faucets.

F. Open base construction. G. Undershelves below drainboard where indicated.

H. One (1) wall mounted overshelf as indicated on drawings.

Item No. 20 - Number Not Used Item No. 21 - Number Not Used

Page 16: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-16

#1492 11 40 00/16 FOODSERVICE EQUIPMENT

Item No. 22 - Exhaust Hood Quantity One (1)

A. One (1) Mod-u-Serve Air Systems Model No. W-IM, 5'-0" deep exhaust hood. All welded 18-gauge stainless steel construction with insulated supply air plenum. 01. Stainless steel baffle filters. 02. Four (4) 48” recessed LED light fixtures with two (2) factory supplied 22 watt T8

lamps per fixture, to provide 50-foot candles on cooking surface. 03. Provide Mod-u-Serve Model No. ASTS-90 pre-set temperature sensor for

automatic start of exhaust fan when the condition exists where the exhaust fan is not initiated at the wall switch and the temperature in the exhaust canopy reaches 90º F.

04. Suspend from structure above ceiling, trim to ceiling with stainless steel closure panels.

05. Exhaust hood components and accessories shall be UL rated. Exhaust hood shall be fabricated in accordance with NSF requirements.

06. Stainless steel where exposed. 07. Continuous air plenum. 08. Provide double layer fire blanket. 09. Clearance requirement: Where any exterior surface of the hood is installed less

than 18” from a combustible surface or penetrates a lay-in tile ceiling, provide where required the U-shaped 3” high S/S air space and also provide, where required, a double layer of an approved Fire Barrier Duct Wrap in a manner as prescribed by the manufacturer.

B. Install at 6'-10" A.F.F. C. 18 gauge insulated stainless steel wall panel, full height from bottom of hood to top of

coved base. Top of panel to be secured under hood. Item No. 23 - Double Deck Convection Oven Quantity One (1)

A. One (1) Vulcan Model No. VC44GD, double deck convection oven. Duke is an approved

alternate manufacturer. 01. Natural gas. 02. Provide stainless steel back panels. 03. Door with dual pane windows. 04. Two speed motor. 05. Mount on casters with brakes. 06. Two (2) T & S Model No. HG-4D-48KS, 48" long quick disconnects with swivels

at each end with restraining device (installed in line by plumber). 07. Solid state temperature controls.

Item No. 24 - Range Quantity One (1)

A. One (1) Vulcan Model No. 60SS-6B24GN, range with two (2) standard ovens. 01. Natural gas. 02. Stainless steel front top rail. 03. 10” stainless steel stub back. 04. 1” rear gas connection. 05. Cap and trim ends and manifold. 06. Gas pressure regulator. 07. One (1) T & S Model No. HG-4E-48KS, 48" long quick disconnect with swivels at

each end with restraining device (installed in line by plumber).

Page 17: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-17

#1492 11 40 00/17 FOODSERVICE EQUIPMENT

Item No. 25 - Convection Steamer Quantity One (1)

A. One (1) Vulcan Model No. C24GA10DLX, convection steamer. 01. Natural gas. 02. Door hinged as indicated. 03. Heat shield. 04. One (1) T & S Model No. HG-4C-48KS, 48" long quick disconnect with swivels at

each end with restraining device (installed in line by plumber). 05. One (1) Scaleblocker water treatment system per manufacturer’s

recommendation. Item No 26 - Char Broiler Quantity One (1)

A. One (1) Southbend Model No. P32D-CC, char broiler with standard oven. Vulcan is an approved alternate manufacturer. 01. Natural gas. 02. Stainless steel front. 03. Stainless steel flue riser. 04. 1” pressure regulator with rear gas connection. 05. Cap and cover manifold connections. 06. One (1) T & S Model No. HG-4E-48KS, 48" long quick disconnect with swivels at

each end with restraining device (install in line by plumber).

Item No. 27 - Fryer Battery Assembly Quantity One (1) Lot

A. One (1) Vulcan fryer battery consisting of the following components from right to left. Pitco and Frymaster are approved alternate manufacturer.

B. One (1) spreader cabinet with filter, stainless steel door and cabinet.

C. Two (2) Model No. 2TR45AF, fryers with Kleenscreen Plus filtration system.

01. Natural gas. 02. Stainless steel covers for fryers. 03. One (1) T & S Model No. HG-4E-48KS, 48" long quick disconnect (per fryer) with

swivels at each end with restraining device (installed in line by plumber).

D. Mount battery on casters with brakes. Item No. 28 - Number Not Used Item No. 29 - Mobile Warming Cabinet Quantity One (1)

A. One (1) Alto Shaam Model No. 1000-UP, mobile warming cabinet. 01. Separately controlled compartments. 02. Electronic control. 03. Cord and plug. 04. Door swing as indicated. 05. Water reservoir with cover.

Item No. 30 - Number Not Used Item No. 31 - Roll-Thru Refrigerator Quantity One (1)

A. One (1) Traulsen Model No. RHT232WPUT-HHS, roll-thru refrigerator. 01. Full height doors on cooking side, half height doors on serving side. 02. Controls to be mounted on cooking side.

Page 18: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-18

#1492 11 40 00/18 FOODSERVICE EQUIPMENT

03. Door swing as indicated. Item No. 32 - Refrigerator Quantity One (1)

A. One (1) Delfield Model No. 4432N-12M, sandwich refrigerator. Mount under Item No. 35 - Preparation Counter as indicated on drawings. 01. Provide twenty-four (24) Cambro Model No. 66CW-110, inset pans. 02. Provide door lock. 03. Stainless steel finish on back. 04. Flat lift off covers.

Item No. 33 - Refrigerator Quantity One (1)

A. One (1) Delfield Model No. UC4427N, undercounter refrigerator. Mount under Item No. 35 - Preparation Counter as indicated on drawings. 01. Provide door lock.

Item No. 34 - Microwave Oven Quantity One (1)

A. One (1) Amana Model No. HDC182, microwave oven. Set in place on overshelf at Item No. 35 - Preparation Counter as indicated on drawings. 01. Cord and plug.

Item No. 35 - Preparation Counter Quantity One (1) Lot

A. One (1) preparation counter assembly; size and shape as indicated on drawings.

B. Turn edges down 2" square; ¾” radius corners.

C. Full-length stainless steel trayslide, per Detail I, Sheet FS-6. Mount tray slide at 32-½” A.F.F.

D. One (1) Wells Model No. MOD500TDM, hot food well with thermostat and drain. Install

where indicated.

E. One (1) T & S Model No. B-0208 deck mount faucet, install where indicated on drawings.

F. Provide ½” thick cutting board set in ½” deep recess as indicated on drawings.

G. One (1) two (2) tier breath protector/serving shelf per Detail S, Sheet FS-6. Provide three (3) Hatco Model No. GRH, heat lamps below each shelf with remote infinite controls. Display lights with lamps and shields.

H. One (1) 1'-6" x 1'-3" x 10" deep sink compartment.

I. One (1) Component Hardware Model No. D53-7215, rotary drain with tailpiece and

connected overflow.

J. One (1) T & S Model No. B-0301, deck mount faucet.

K. Provide recesses to accommodate Item No. 32 & Item No. 33 - Refrigerators. Receptacles in counter body to provide power.

L. Three (3) Serv-o-lift Model No. AT-5, self-leveling plate dispensers. Install as indicated

on drawings. 01. Verify plate size with owner.

Page 19: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-19

#1492 11 40 00/19 FOODSERVICE EQUIPMENT

M. Closed base construction.

N. Open shelf sections.

O. Plate shelf with control panel.

P. Plumbing compartment.

Q. Load center compartment. R. One (1) Square D Model No. 120/208 volt, three phase, 4 wire, QO320L125G, load

center with Model No. QOC24UF, cover and PK4GTA, ground bar kit with visi trip breaker. Load centers installed in/on fabricated equipment to have all fixture components pre-wired to load center with balanced phase loading.

S. Load center to be ready for final connection by Electrician and flush-mounted within utility

compartment stainless steel rear panel, set back 8" from access door. All breaker/device information: typewritten on circuit schedule in load center door (number corresponding breaker/device) with enclosed schematic wiring diagram of fixture components.

T. Mount counter on 6” high stainless steel legs.

U. Provide receptacle at overshelf as indicated for on drawings Item No. 34 - Microwave

Oven.

V. Provide recessed receptacle at end of counter as indicated for Item No. 29 - Mobile Warming Cabinet.

Item No. 36 - Mobile Pan Rack Quantity Four (4)

A. Four (4) New Age Model No. 1635, mobile pan racks. 01. Universal slides.

Item No. 37 - Conveyor Toaster Quantity One (1)

A. One (1) Hatco Model No. TRH-60, conveyor toaster. Set in place on Item No. 35 - Preparation Counter as indicated on drawings. 01. Cord and plug with receptacle in counter body.

Item No. 38 - Ice Transport Cart Quantity One (1)

A. One (1) Cambro Model No. ICS175 LB, ice transport cart. Color as selected by Architect. 01. Ice leveler.

Item No. 39 - Ice Machine/Bin Quantity One (1)

A. One (1) Scotsman Model No. C0630MA-32A, ice machine mounted on a Model No. B948S, stainless steel bin with 6” stainless steel adjustable legs. 01. Stainless steel scoop holder.

B. One (1) Scotsman AquaPatrol Model No. ADS-AP2, water filter for icemaker. Provide

two (2) additional cartridges, for a total of three (3). Mount on wall adjacent to equipment. C. Insulate drain lines with 1” thick insulation.

Page 20: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-20

#1492 11 40 00/20 FOODSERVICE EQUIPMENT

Item No. 40 - Number Not Used

Item No. 41 - Trench Liner/Grate Quantity Three (3)

A. Three (3) trench liner/grate assemblies; construct per Detail D, Sheet FS-1.2. Item No. 42 - Ice Cream Dispenser Quantity One (1)

A. One (1) Master Bilt Model No. DC-4D, ice cream dispenser. 01. Lid locking device. 02. Stainless steel exterior.

Item No. 43 - Tea Brewer Quantity One (1)

A. By Purveyor. Item No. 44 - Refrigerator Quantity One (1)

A. One (1) Delfield Model No. UC4427N, undercounter refrigerator. Mount under Item No. 46 - Beverage Counter as indicated on drawings. 01. Provide door lock.

Item No. 45 - Number Not Used Item No. 46 - Beverage Counter Quantity One (1)

A. One (1) beverage counter assembly; size and shape as indicated on drawing.

B. Turn front down 2" square; 12" high splash at walls.

C. Provide stainless steel chase to enclose beverage lines. Extend from counter top to 6” above ceiling. Locate as indicated on drawings.

D. One (1) Atlas Model No. WB-15, drop in ice chest, provide cut out in top to

accommodate.

E. One (1) T & S Model No. B-1230, glass filler, provide cut out in top to accommodate.

F. Open shelf sections.

G. Plumbing compartment.

H. Closed base construction.

I. Mount counter on 6" high stainless steel legs. Item No. 47 - Coffee Brewer Quantity One (1)

A. By Purveyor.

Item No. 48 - Number Not Used Item No. 49 - Number Not Used

Item No. 50 - Number Not Used

Page 21: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-21

#1492 11 40 00/21 FOODSERVICE EQUIPMENT

Item No. 51 - Soiled Dishtable Quantity One (1)

A. One (1) “ell” shaped soiled dishtable assembly; size and shape as indicated on drawings.

B. 1-½” rolled rim at front; 10" high splash where adjacent to walls.

C. One (1) 1'-9" x 1'-9" x 7" deep disposer sink. Provide stainless steel removable rack guide.

D. One (1) T & S Model No. B-0163, pre-rinse with Model No. B-0107-C, spray valve unit

with low flow spray head with B-0109, wall bracket and two (2) Model No. BCVH ½” check valves.

E. Install disposer and control panel where indicated. Provide stainless steel bracket for

control panel. F. Provide stainless steel sill and window frame. Extend soiled dishtable top through pass

window and turn down 2” on drop off side. G. One (1) Piper Model No. 337-3474, soak sink (less chute). H. One (1) 16-gauge stainless steel silver chute per Section C, Sheet FS-1.6.

I. Open base construction. J. One (1) wall mounted, slanted glass rack shelf as indicated on drawings. Provide 18-

gauge stainless steel wall panel as indicated on Detail O, Sheet FS-1.6. Item No. 52 - Disposer Quantity One (1)

A. One (1) Salvajor Model No. 200-SA, disposer with 6-1/2" diameter sink collar. Red Goat

is an approved alternate manufacturer. 01. One (1) Model No. ARSS-LD, control panel. 02. One (1) Model No. 980105 stainless steel mounting bracket for control panel.

Mount control panel and bracket where indicated on drawings. 03. One (1) dejamming prong.

B. Install in Item No. 51 - Soiled Dishtable.

Item No. 53 - Vent Duct Quantity Two (2)

A. Two (2) 18-gauge stainless steel fully welded vent ducts with stainless steel angle collar at ceiling. Extend 6" above finished ceiling.

Item No. 54 - Dishmachine Quantity One (1)

A. One (1) Champion Model No. 44DR, dishmachine with 1” shorter stainless steel legs. Meiko is an approved alternate manufacturer. 01. Direction of operation per drawings. 02. Single point connection. 03. Electric tank heat. 04. Stainless steel front panel. 05. Vent hoods. 06. Vent fan control. 07. Auto fill. 08. Stainless steel splash guards.

Page 22: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-22

#1492 11 40 00/22 FOODSERVICE EQUIPMENT

09. Four (4) PEG racks, four (4) COM racks. 10. 6" taller chamber.

Item No. 55 - Booster Heater Quantity One (1)

A. One (1) Hatco Model No. S-54, booster heater. 01. Stainless steel body and base. 02. Adjustable stainless steel legs. 03. Shock absorber.

Item No. 56 - Clean Dishtable Quantity One (1)

A. One (1) clean dishtable assembly; size and shape as indicated on drawings.

B. 1-1/2" rolled rim at free sides; 10" high splash where adjacent walls.

C. One (1) T & S Model No. B-0669-POL, hose bibb faucet. Garden hose provided by owner. Mount on 14 gauge stainless steel bracket; refer to Detail N, Sheet FS-1.6.

D. Open base construction. E. Undershelf.

Item No. 57 - Number Not Used Item No. 58 - Trench Liner/Grate Quantity Two (2)

A. Two (2) trench liner/grate assemblies; construct per Detail D, Sheet FS-1.2. Item No. 59 - Number Not Used Item No. 60 - Number Not Used Item No. 61 - Glass Rack Dollies Quantity Three (3)

A. Three (3) New Age Model No. 1176A, glass rack dollies.

01. Full perimeter vinyl wrap around bumper. Item No. 62 - Can Rack Quantity Two (2)

A. Two (2) New Age Model No. 1250CK, can racks.

Item No. 63 - Beverage System/Beverage Dispenser Quantity One (1)

A. Beverage system including beverage dispenser by purveyor.

LEVEL 3 Item No. 01 - Millwork Counter Quantity One (1)

A. Not in 11 40 00. B. Provide cutout for Item No. 09 - Drop-In Designated Hand Lavatory.

C. Provide recess for Item No. 02 - Ice Machine/Bin.

Page 23: SECTION 11 40 00 - FOODSERVICE EQUIPMENT PART 1 - … · 1.2 WORK A. Include the work specified, shown or reasonably inferable as part of Foodservice Equipment. 1.3 RELATED WORK IN

Foodservice Equipment Specifications 01/22/2016 DD The Village on Triangle Avenue Page-23

#1492 11 40 00/23 FOODSERVICE EQUIPMENT

Item No. 02 - Ice Machine/Bin Quantity One (1)

A. One (1) Scotsman Ice Model No. CU0415, ice machine. Set in place where indicated on drawings. Coordinate installation with Millwork Contractor. 01. Stainless steel scoop holder.

B. One (1) Scotsman AquaPatrol Model No. ADS-AP1, water filter for icemaker. Provide

two (2) additional cartridges, for a total of three (3). Mount in cabinet next to equipment. C. Insulate drain lines with 1” thick insulation. D. Provide one (1) Scotsman Model No. KUFM15, floor mount kit,

Item No. 03 - Beverage Dispenser Quantity One (1)

A. By Purveyor.

Item No. 04 - Conveyor Toaster Quantity One (1)

A. One (1) Hatco Model No. TRH-60, conveyor toaster. Set in place on Item No. 01 - Millwork Counter as indicated on drawings. 01. Cord and plug with receptacle in counter body.

Item No. 05 - Microwave Oven Quantity One (1)

A. One (1) Amana Model No. HDC182, microwave oven. Set in place on Item No. 01 - Millwork Counter as indicated on drawings. 01. Cord and plug.

Item No. 06 - Heated Holding Cabinet Quantity One (1)

A. One (1) Cres Cor Model No. H-339-12-188C, heated holding cabinet. 01. Corner bumpers. 02. Cord and plug.

Item No. 07 - Enclosed Utility Cabinet Quantity One (1)

A. One (1) Lakeside Model No. 6540, enclosed utility cabinet. 01. Casters, two (2) with brakes.

Item No. 08 - Refrigerator Quantity One (1)

A. Not in 11 40 00.

Item No. 09 - Drop-In Designated Hand Lavatory Quantity One (1)

A. One (1) Eagle Model No, SR10-14-5-1, drop in designated hand lavatory. Install in Item

No. 01 - Millwork Counter where indicated on drawings. Coordinate sink cut out size and location with Millwork Contractor.

B. Provide one (1) T & S Model No. 313306, deck mount faucet.

END SECTION 11 40 00