KUTAI ELECTRONICS INDUSTRY CO., LTD. TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN ADVR-08 Universal Hybrid Analog-Digital Voltage Regulator Operation Manual An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic + Auxiliary Winding, PMG and SHUNT. Compatible with Leroy Somer* R438, R448, R449 and more. Use with KUTAI IVT-1260 / IVT-2460 add-on module can boost generator motor starting capacity.

Transcript of SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with...

Page 1: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

KUTAI ELECTRONICS INDUSTRY CO., LTD.

TEL : +886-7-8121771 FAX : +886-7-8121775 Website : www.kutai.com.tw

Headquarters : No.3, Lane 201, Chien Fu St., Chyan Jenn Dist., Kaohsiung 80664, TAIWAN

ADVR-08

Universal Hybrid Analog-Digital Voltage Regulator Operation Manual

An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic + Auxiliary Winding, PMG and SHUNT. Compatible with Leroy Somer* R438, R448, R449 and more. Use with KUTAI IVT-1260 / IVT-2460 add-on module can boost generator motor starting capacity.

Page 2: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

___________________________________________________________________________________________

2 ADVR-08

SECTION 1 : SPECIFICATION

Sensing Input (E1, E2) Static Power Dissipation

Voltage 110 480 Vac, 1 phase Max.6 watts

90 130 Vac @ 110 Vac

180 260 Vac @ 220 Vac Burden in SHUNT & PMG Wiring

340 520 Vac @ 380 Vac 880 VA @ power input 110 Vac

Frequency 50/60 Hz, DIP switch setting 1760 VA @ power input 220 Vac

Power Input (X1, X2, Aux1) Quadrature Droop Input (S1, S2, S3)

Voltage 40 300 Vac, 1 phase / 3 phase CT 5A (S1-S2) or 1A (S2-S3) greater than 5VA

Frequency 50 500 Hz Max. +/- 5% @ P.F +/- 0.7

1 phase (X1、X2) / 3 phase (X1、X2、Aux1)

Analogue Voltage Input (A1, A2)

Auxiliary Input (Aux1, Aux2) Input resistance greater than 2K ohms

Voltage 40 300 Vac, 1 phase Max. Input +/- 5 Vdc

Frequency 50 500 Hz Sensitivity +/- 25% Generator Volts (adjustable)

Excitation Output (F+, F-) Under Frequency Protection (Factory Presets)

Voltage Max. 63 Vdc @ power input 110 Vac 50 Hz system presets knee point at 45 Hz

Max. 125 Vdc @ power input 220 Vac 60 Hz system presets knee point at 55 Hz

Current Continuous 8A

Intermittent 12A for 10 secs. Over Excitation Protection

Resistance ≧ 8 ohms @ power input 110 Vac Set point 170 Vdc +/- 5 % @ power input 220 Vac

≧ 16 ohms @ power input 220 Vac

Fuse Spec. Slow blow 5 x 20mm S505-10A Voltage Thermal Drift

Less than 3% at temperature range -40 to +70 ˚C

External Voltage Adjustment (VR1, VR2)

Max. +/- 4% @ 500 ohms 1 watt potentiometer Under-Frequency Knee Point Thermal Drift

Max. +/- 8% @ 1K ohm 1 watt potentiometer Less than +/- 0.1 Hz at -40 to +70 ˚C

Voltage Regulation Environment

Less than +/- 0.5% ( with 4% engine governing ) Operating Temperature -40 to +70 ˚C

Storage Temperature -40 to +85 ˚C

Build Up Voltage Relative Humidity Max. 95%

6 Vac 25 Hz residual volts at power input terminal Vibration 3 Gs @ 100 2K Hz

Soft Start Ramp Time Dimensions

4 seconds +/- 10% 171.0 (L) x 120.0 (W) x 50.0 (H) mm

Typical System Response Weight

Less than 20 milliseconds 820 g +/- 2%

EMI Suppression

Internal electromagnetic interference filtering

ATTENTION

Carefully set the AVR sensing voltage from 110 to 480 Vac using DIP Switch SW 4 & 5.

Page 3: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

___________________________________________________________________________________________

ADVR-08 3

SECTION 2 : OUTLINE / SIZE / INSTALLATION REFERENCE

ATTENTION

1. All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test equipment must not be used. Use of such equipment could damage the AVR.

2. Improper setting of under-frequency protection could cause the output voltage of the unit to drop or

become unstable under with changes in load. Avoid making any changes to the U/F setting unless necessary.

Figure 1 Outline Drawing

Terminal : “Fast-On” terminals 6.35 mm (1/4 inch)

Flag Terminal (“Fast-On” terminal)

Page 4: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

___________________________________________________________________________________________

4 ADVR-08

SECTION 3 : DIP SWITCH PROGRAMMING & VR ADJUSTMENTS

Auxiliary Input

Power Input

Sensing Voltage

Field Voltage

U/F LED

Under-Frequency Indicator

O/E LED

Over-Excitation Indicator

TRIM Adjustment (for paralleling)

Set fully clockwise for 10% output voltage

change via analog (Bias) input A1 & A2.

Set fully counter-clockwise no effect on

output voltage.(Used only in paralleling)

VOLT Voltage AdjustmentAccording to DIP switch setting SW 4 & 5

DROOP

Current Compensation Droop Adjustment

Used only in paralleling

U/F UFRO Adjustment

Under Frequency knee point setting

50 Hz System : 40 to 51 Hz (Lowest position)

60 Hz System : 50 to 61 Hz (Lowest position)

Quadrature Droop Input (for paralleling)

5A CT (S1-S2)1A CT (S2-S3)

External VR(Shorted when not in use)

Analogue Input (See TRIM)Used for PF control when

paralleling

STAB Stability Adjustment

Set under no load operation, adjust STAB

potentiometer counter-clockwise until the

voltage becomes unstable and turn back

1/5 turn.

DIP Adjustment

This adjustment allows some control over

the generator voltage dip when applying

load.

It is typically used to compensate for

turbo lag, leaving the generator to

operate below the UFRO knee point

setting. The voltage droop ratio can be

set using the DIP adjustment.

The range is 10 to 3 V/Hz.

- +

- +

51(61) 40(50)

HZ HZ

- +

3 10

ON1

23

45

6

SW <90

2

3

OFF

KW 90~500 >500

ON

OFF ON

90~130

4

5

OFF

OFF

V 180~260 340~520

ON ON

OFF ONSW

OFF ON

SW OFF ON

6 O/E ON O/E OFF

SW OFF ON

1 60Hz 50Hz

To IVT Sensing Input (S1,S2) Note1

ATTENTION

For more detail about “ IVT Generator Auxiliary Excitation Booster ” please visit KUTAI website.

Page 5: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

___________________________________________________________________________________________

ADVR-08 5

SECTION 4 : WIRING CONNECTIONS

Armature

Exciter field

C.T

20

0V

AC

m

ax

50~

50

0H

Z

Stator windings

S

T

R

PMG

N:5Aor1A

S2-S3 N:1A

S1-S2 N:5A

ADVR-08

S 2 - S 3 N : 1 A

S 1 - S 2 N : 5 A

A U X . w i r e s

( H a r m o n i )

A D V R - 0 8

Armature

S

T

R

C.TN:5Aor1A

Exciter field

Stator windings

S2-S3 N:1A

S1-S2 N:5A

AUX. wires

Harmoni wires

ADVR-08

Armature

S

T

R

Exciter field

C.TN:5Aor1AStator windings

S2-S3 N:1A

S1-S2 N:5A

ADVR-08

Armature

S

T

R

C.TN:5Aor1A

Exciter field

N

Stator windings

Figure 2 Single & Three Phase PMG Figure 3 Three Phase Auxiliary Winding (Full Harmonic)

Figure 4 Auxiliary & Harmonic Figure 5 Self-Excited (SHUNT)

Page 6: SECTION 1: INTRODUCTION · An Universal Hybrid Analog/Digital 2 lines sensing 8 Amp AVR with multiple power input capability such as Full Harmonic (Compound Windings), Harmonic +

___________________________________________________________________________________________

6 ADVR-08

+

OU

T1

OU

T2

+

B B

IVT

S2

S1

Fuse

Time

Test

Output

Ready

Test

Batt-Volt

OVLD

ON

Droop%

Armature

Exciter field

C.T

N:5Aor1A

S2-S3 N:1AS1-S2 N:5A

ADVR-08

S

T

R

Stator windings

Figure 6 ADVR-08 & IVT-1260 / IVT-2460 Wiring Connection

ATTENTION

1. All AC voltage readings are average value only.

2. Use a remote 500 ohms 1 watt external VR for +/- 4% adjustment range. (keep shorted if not used)

3. Use a remote 1K ohm 1 watt external VR for +/- 8% adjustment range.

4. If your PMG is not working you can also power the AVR in shunt using terminals X1 & X2 connected to the output of the generator as long as it’s less than 300 Vac.

※ Use only the replacement fuses specified in this user manual.

※ Appearance and specifications of products are subject to change for improvement without prior notice.