Seasonal Equipment Operational Considerations

39
e People and ideas you can trust. TM ©2014 Daikin Applied Seasonal Equipment Operational Considerations Joe Leichner, Daikin Applied Strategic Sales Project Developer September 9, 2014

description

Seasonal Equipment Operational Considerations. Joe Leichner, Daikin Applied Strategic Sales Project Developer. September 9, 2014. Agenda. “Seasonal” – Means not full load heating or cooling! Controls settings to save energy and optimize comfort - PowerPoint PPT Presentation

Transcript of Seasonal Equipment Operational Considerations

Page 1: Seasonal Equipment Operational Considerations

ePeople and ideas you can trust.TM©2014 Daikin Applied

Seasonal Equipment Operational ConsiderationsJoe Leichner, Daikin Applied Strategic Sales Project Developer

September 9, 2014

Page 2: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Agenda

1. “Seasonal” – Means not full load heating or cooling!

2. Controls settings to save energy and optimize comfort

3. Designing/selecting new systems for replaced equipment

Page 2

Page 3: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal = 99.9% of the Year

Page 3

Historical data and choosing weather criteria for a hospital:

1. If there is a “worst-case scenario”, your hospital will see it.2. Seems to not account for north winds through north-facing outside

air dampers!3. Does not account for 100 and -10 degree F. days.4. When designing a new building, help guide your design team.5. Systems and equipment degrade in performance and capacity.6. Bigger equipment will help handle “peak” loads, but affect efficiency

at part-load.7. Diversity is tough to estimate, but it very important to equipment

selection and operation.

Page 4: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Heating Design Temperatures

Page 4

Page 5: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Cooling Design Temperatures

Page 5

Page 6: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal = 99.9% of the Year

Page 6

Page 7: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Weather and Internal Loads

Page 7

Not only is the weather dynamic, your internal loads are dynamic as well.

• Surgery suite loading• Emergency room usage• Patient flow and overnights• Conference rooms/meetings• Others

Page 8: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Weather and Internal Loads

Page 8

The use of your building affects your support systems:

• Food service• Laundry• Housekeeping• Many others

Page 9: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Weather, Internal Loads, and Comfort

Page 9

Human comfort is both physical and mental. Physical aspects are:• Airflow

• RH%

• Air Temperature

• Odor

• CO2

• and more!

HOW DO YOU KEEP EVERY OCCUPANT AND PATIENT COMFORTABLE?

Page 10: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings

Page 10

Controls settings for patient comfort

Controls settings for medical staff comfort

Controls settings for safety

Page 11: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings

Page 11

Controls settings for patient comfort• Patient satisfaction surveys and reimbursements• Healing rate improvement if person is comfortable?

Controls settings for medical staff comfort• Physician and nursing staff retention• Job satisfaction improved if environment of care is comfortable• Productivity enhanced if conditions are maintained

Page 12: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Safety

Page 12

• Air pressurization maintenance for critical environments

• Airflow for biological safety cabinets, fume hoods

• Airflow for surgery suites and burn treatment areas (and others)

• Food storage and food preparation areas

IT IS NOT JUST ABOUT THE TEMPERATURE; FLOWS AND PRESSURES MATTER AS WELL.

Page 13: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Occupant Safety

Page 13

First Priority – Airflow and pressure maintenance

In ante rooms, isolation rooms, and other specialized areas, the difference in room pressures must be maintained.

How many of you fight with negative air pressure in the building especially in the winter?

Load and ventilation analysis – Not expensive, but very worthwhile for comfort and energy.

Page 14: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Load and Ventilation Analysis

Page 14

• Optimizes recirculation requirements based upon space type determination

• Defines exact minimum outside air requirement by zone

• Defines inflow and exhaust flow for each zone

• Identifies lighting, people, computer, medical equipment loads (by room or zone)

• Measures current AHU peak airflow and pressure delivery

Page 15: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Load and Ventilation Analysis

Page 15

• Measures current outside air intake quantity, zone temps and settings

• Identifies needs for fan/coil cleaning, damper repairs, etc.

• Provides information for optimizing comfort in the occupied spaces through air/water bal.

• Creates awareness of concern by your staff for patient outcomes, staff satisfaction, etc.

• Can assure of proper AHU ventilation control throughout facilities

Page 16: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Occupant Comfort

Page 16

Second Priority – Occupant Comfort

Page 17: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Occupant Comfort

Page 17

Second Priority – Occupant Comfort

Page 18: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Occupant Comfort

Page 18

Many other considerations for occupant comfort:

• Physical health of the individual• Use of clothing (sweaters, thin shirts, etc.)• Density and length of hair (traps heat from head)• Air velocity across the skin• Noise of the air and within the rooms• Lighting (% of natural lighting, color of lighting, etc.)• Wall and room aesthetics (white, shiny painted walls vs. calm colors and artwork, etc.)• Sensitivity to temperature swings (heating dead-band and cooling dead-band)

Page 19: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Occupant Comfort

Page 19

Second Priority – Occupant Comfort

Energy Policy – Temperature settings by functional space

Given all of this information, where should you set the room temperature?

74 Degrees is the mid-point between heating and cooling. Expensive.

76 for Cooling is most common; 78 may be too high (Dehumidification <50%)

72 for Heating is most common; 68 may be too low (Humidity at 30%/35%)

Page 20: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Ventilation Quantities

Page 20

• Set outside air quantities as required to meet minimum volumes (periodically check the damper positions to ensure these are set in the proper position during occupancy and un-occupied conditions)

• Maintain annual certifications for FHs/BSCs and space pressurization controls

• Test and adjust kitchen, laundry, and other exhaust systems periodically as renovations happen (adjust sheaves as needed) – Turn on only when needed

• Maintain and calibrate building static pressure controls and relief systems

Page 21: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Ventilation Quantities

Page 21

• Check economizer sequences of operation for AHUs that vary outside air quantity

• Check and calibrate CO2 sensors/transmitters/controllers (Ambient air 350 ppm CO2 – adjust to control less than 800 ppm appx. – above this, people can sense the air is “stuffy” and can begin to feel tired.) (If set lower than 800 ppm, energy cost increases significantly.)

Page 22: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Ventilation Quantities

Page 22

Normal CO2 Levels*

The effects of increased CO2 levels on adults at good health can be summarized:

• normal outdoor level: 350 - 450 ppm• acceptable levels: < 600 ppm• complaints of stiffness and odors: 600 - 1000 ppm• ASHRAE and OSHA standards: 1000 ppm• general drowsiness: 1000 - 2500 ppm• adverse health effects expected: 2500 - 5000 ppm• maximum allowed concentration within a 8 hour working period: 5000 ppm

* Source: EngineeringToolbox.com

Page 23: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for AHUs

Page 23

Mixed air temperature and economizer control – 55 degrees +/- with reset from OAT (Minimize chilled water cooling as much as possible.)

Supply air temperature• Low temp systems – 40 degrees (maintains fan

efficiency)• Normal systems – 55 degrees (VAV systems reset from

zone average to limit)• Minimize fan energy as much as possible

Page 24: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for AHUs

Page 24

Supply air pressure – Duct static to maintain +/- 0.5” at furthest outlet (dumping and throw/noise concerns can happen if static too low or too high) (minimize fan motor energy)

Hot deck temperature – reset 180 to 120 from OAT 0 to 60 degrees (minimize hot water pump energy)

Cold deck temperature – maintain at 52 to 55 degrees depending upon fan size (heat from fan motor) and duct heat absorption (long runs of duct) (minimize chilled water pump energy)

Building pressure (Return air fan or relief air damper) – +0.1” normal (can vary by zone)

Page 25: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Heating Plants

Page 25

Deaerator pressure – 3 to 5 psig (for aeration efficiency and feed water heating)

Boiler feedwater pressure – 10 psig over generation pressure (reduce pump energy)

Steam pressure – minimum pressure for loads served – distribution pressure losses (Autoclaves, sterilizers, linen presses, cooking, humidification, etc.) (Can reset pressure setting on a schedule when high pressure loads are not in operation – do not set too low as condensate volume increases drastically on large campus systems)

Page 26: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for Heating Plants

Page 26

Hot water supply temperature – 180 reset to 120 from outside air at 0 to 60 degrees

Re-heat loop supply temperature – 140 reset to 120 from outside air at 0 to 60 degrees

Perimeter heating system supply temp – 180 to 120 reset. Cycle off pump at OAT>60.

Hot water pumping system pressure – minimum to maintain sufficient circulation and not below 25% flow (surging and cavitation)

Page 27: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for CHW Plants

Page 27

Constant flow pumping system – reset chilled water supply temperature to highest temp to satisfy all zones (one valve at 100% open)

Variable flow pumping system – maintain 42/43 degree chilled water supply temp to minimize pumping energy – may reset chilled water supply temp up if chiller efficiency gain is more efficient than pumping energy spent by pumping more flow.

Page 28: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for CHW Plants

Page 28

Chilled water supply temperature – maintain 42 to 45 degrees for variable water pumping systems or chillers with VFDs. For constant pumping systems and chillers without VFDs, reset the chilled water supply temperature as high as possible while maintaining space temperature and relative humidity.

Page 29: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Seasonal Control Settings for CHW Plants

Page 29

Condenser water supply temperature – maintain lowest inlet temperature to chiller to reduce chiller lift requirement to minimum input temperature permitted by chiller design. Outdoor air wet-bulb temperature reset of condenser water supply temperature based upon your load and equipment. Fan speed control given constant condenser water flow. (Sorry, not a definitive answer.)

Page 30: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 30

Chiller Replacement• Evaluate chillers based upon the Integrated Part Load Value (IPLV) (This is intended to show the part load performance/efficiency and is weighted based upon some assumed capacities and hours of use.) (The IPLV is an ARI/ASHRAE Standard that all manufacturers must use and will clearly indicate which chiller is the most efficient given the stated parameters.)

• Consider redundancy; low load operation needs (Mutt chillers, plant configuration, VF pumping conversion, etc.); and future load additions (remodels, additions, expansions, etc.)

Page 31: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 31

Cooling Tower Replacement• Evaluate towers based upon chiller installed capacity and free-cooling needs/wants• Consider redundancy, fan speed control type and drive, and future load additions

Page 32: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 32

Pump Replacement• If you are replacing your chiller or tower, you should also replace your pump and motor. Choosing the new pump in the highest efficiency portion of the curve can save lots of money every hour the pump runs. • Consider conversion to variable flow systems on hot water and chilled water systems; but be very cautious on condenser water and water source heat pump loops. (Requires pressure control and 3-way to 2-way control valve replacement.)

Page 33: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 33

Boiler Replacement• Consider the boiler efficiency at part load, once sizing is confirmed.• Consider redundancy, low load operation needs (Mutt boilers, etc.)• Consider future load additions (remodels, additions, expansions, etc.)• Consider redundant fuel supply (fuel oil, propane, and required storage)• Consider cost for alternative fuels

Page 34: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 34

RTU Replacement• Consider overall cost for energy, repairs and maintenance given unit life time. Much higher efficiency units are available.

AHU Replacement/Refurbish• Consider conversion of constant volume to VAV system for supply fan motors greater than 20 hp. (See table on next page.) Best seasonal performance versus constant volume.

Page 35: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 35

Existing AHU System Type Recommended System Conversion Ideas Advantages Disadvantages

Single Zone, Constant VolumeSimple VAV Conversion - variable flow based

upon average space temperature; add economizer if not existing

Lower cost than other retrofits.

Less energy savings as still have over ventilation of spaces without sensors.

Single Zone, Constant VolumeVariable air volume diffusers; add economizer if

not existingLower cost than adding boxes.

Less energy savings as still have potential for over-

ventilation of spaces due to accuracy of damper

operation.

Single Zone, Constant VolumeAdd VAV boxes with reheat; add economizer if

not existing

Most energy effi cient retrofit.

Will result in highest comfort.

Most costly of conversions.

Single Zone, Terminal Reheat, Constant Volume

Variable air volume diffusers; add economizer if not existing

Lower cost than adding boxes.

Less energy savings as still have potential for over-

ventilation of spaces due to accuracy of damper

operation.

Single Zone, Terminal Reheat, Constant Volume

Add VAV boxes upstream of reheat coils; add economizer if not existing

Most energy effi cient retrofit.

Will result in highest comfort.

Most costly of conversions.

Multizone, Constant VolumeVariable air volume diffusers; add economizer if

not existing

Lower cost than isolating decks and adding boxes. May

increase comfort over existing.

Less energy savings as still have potential for over-

ventilation of spaces due to accuracy of damper

operation.

Page 36: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Designing New Systems for Replaced Equipment

Page 36

Single Zone, Terminal Reheat, Constant Volume

Add VAV boxes upstream of reheat coils; add economizer if not existing

Most energy effi cient retrofit.

Will result in highest comfort.

Most costly of conversions.

Multizone, Constant VolumeVariable air volume diffusers; add economizer if

not existing

Lower cost than isolating decks and adding boxes. May

increase comfort over existing.

Less energy savings as still have potential for over-

ventilation of spaces due to accuracy of damper

operation.

Multizone, Constant Volume

Simple VAV Conversion - isolate decks and install individual deck and zone dampers.

Variable flow based upon zone with highest demand temperature OR can operate on deck static pressure; add economizer if not existing

Lower cost than VAV box retrofit.

Less energy savings as still have over ventilation of spaces without sensors. May still have comfort

issues.

Multizone, Constant VolumeAdd VAV boxes with reheat; add economizer if

not existing

Most energy effi cient retrofit.

Will result in highest comfort.

Most costly of conversions. Highest energy savings and best system conversion for

comfort.

Dual Duct, Constant VolumeRetrofit existing dual duct boxes with new VAV

controls. Fix faulty dampers and seals.

Lower cost than dual duct VAV box replacement.

Less reliable and accurate than new boxes.

Dual Duct, Constant VolumeReplace existing dual duct boxes with new VAV

boxes and controls.

Most energy effi cient retrofit.

Will result in highest comfort.

Most costly of conversions. Highest energy savings and best system conversion for

comfort.

Induction System, Constant Volume

Reset discharge static pressure based upon added zone temperature sensors or feedback

from automation system.

Will save some energy, but may result in some

complaints about excessive humidity

in space (lack of dehumidification)

Costly conversions. May still have comfort

complaints.

Existing AHU System Type Recommended System Conversion Ideas Advantages Disadvantages

Page 37: Seasonal Equipment Operational Considerations

©2014 Daikin Applied

Take Aways

Page 37

1. Ensure your design team uses seasonal weather data to properly size HVAC systems.

2. Periodically check your controls settings to ensure they are set for the best mix of comfort and efficiency.

3. If it has been a while since you have had a loads analysis and ventilation study, it can be money well spent as energy savings can result from minimizing and controlling ventilation rates.

4. When equipment replacement is needed, ensure that HVAC capacities for its zone/service needs are identified, choose the most efficient equipment available, and control the equipment/system in the most efficient manner that compliments occupant comfort.

Page 38: Seasonal Equipment Operational Considerations

ePeople and ideas you can trust.TM

Questions?

©2014 Daikin Applied Page 38

Page 39: Seasonal Equipment Operational Considerations

ePeople and ideas you can trust.TM

Thank You!

©2014 Daikin Applied Page 39