www.arteche.com 1 2.0 saTECH BCU Automation System and Bay Control Unit APPLICATIONS Substation Automation: Acquisition, monitoring and measurement unit for any bay position. Sequential event logger: It stores input and output change of status with an accuracy of 1 millisecond. Great interoperability capacity among devices through conventional protocols and/or IEC 61850 standard protocols using Ethernet or serial ports. Auxiliary service monitoring and control. KEY BENEFITS IEC 61850 native design. Robust and reliable equipment, allowing its use both in process bus applications and station bus. Interoperability with the main IED manufacturers. Flexibility for the implementation of advanced control strategies to get the most of the communication capacity performance and the IEDs’ current interoperability. IEEE 1588 Synchronization, PRP Network Redundancy and IEC 61850 Test Mode. Modularity, which allows the selection of the most suitable hardware configuration. Visual logical configuration in accordance with IEC 61131 standard. It optimises the implementation of any monitoring system by selecting previously configured single diagram lines and adapting them to your needs through the saTECH CNF configuration software, in an easy and simple way.

Transcript of saTECH BCU

Page 1: saTECH BCU

www.arteche.com 1

2.0

saTECH BCU

Automation System and Bay Control Unit

APPLICATIONS Substation Automation: Acquisition, monitoring and measurement unit for any bay position.

Sequential event logger: It stores input and output change of status with an accuracy of 1 millisecond.

Great interoperability capacity among devices through conventional protocols and/or IEC 61850 standard

protocols using Ethernet or serial ports.

Auxiliary service monitoring and control.

KEY BENEFITS IEC 61850 native design.

Robust and reliable equipment, allowing its use both in process bus applications and station bus.

Interoperability with the main IED manufacturers. Flexibility for the implementation of advanced control strategies to get the most of the communication capacity performance and the IEDs’ current interoperability.

IEEE 1588 Synchronization, PRP Network Redundancy and IEC 61850 Test Mode.

Modularity, which allows the selection of the most suitable hardware configuration.

Visual logical configuration in accordance with IEC 61131 standard.

It optimises the implementation of any monitoring system by selecting previously configured single diagram lines and adapting them to your needs through the saTECH CNF configuration software, in an easy and simple way.

Page 2: saTECH BCU

www.arteche.com 2

2.0

MAIN FEATURES

Protocols Master

Customer

Slave

Server

IEC 61850 MMS Report

IEC 61850 MMS/GOOSE

DNP3 TCP/Series

MODBUS TCP/Series

IEC 60870-5-104

Programmable logical functions for the configuration of monitoring diagrams in accordance with IEC 61131 standard.

High-resolution touch screen which allows the monitoring of local operations with of customizable screens, such as single diagram line, events, alarm lists, real-time measurements or primary device status.

48 programmable LEDs at the front panel.

Opening and close switch push-buttons at the front panel.

Option double power supply and 8 digital outputs type "C".

Confirmation of manual operation protected through password.

Ethernet access via copper and fiber optic cabling. With PRP support and “fail-over”.

Communications through RS-232 and RS-485 isolated serial ports.

Communication with SCADA and with other IEDs using IEC 61850 logical nodes and GOOSE, DNP, Modbus, and IEC 60870-5-104 protocols.

Sequential event log, storing the last 1,400 analogue events and 1,400 digital events in non-volatile memory.

WEB server with I/O simulation functions, real-time display of IEC-61131 logics, historical record, communication trace, and hardware diagnostic.

Several synchronization sources from through IEEE 1588 (PTP IEEE Std C37.228-2011 with power systems profile), SNTP and IRIG-B conventional protocols.

Embedded cybersecurity features, including advanced user authentication encryption, integrated firewall, and secure communication protocols (SFTP, SSH).

Hardware design with no removable parts and a solid-state storage.

Robust design with a wide range of operation temperatures.

TEST mode conforming to IEC 61850.

Data model according to SAS Specification IEC 61850 CFE Transmission DT-CTRL-10.

Page 3: saTECH BCU

www.arteche.com 3

2.0

TECHNICAL SPECIFICATIONS

COMUNICACIONES

Communication Ports

3 10/100 Mbps individual Ethernet ports.

(1 RJ45 front port and 2 rear ports with RJ45 or fiber optics options).

Options:

Dual 100 Base fiber ETH - FX (ST or LC type).

Dual 10/100 Base copper ETH- TX (RJ45 type)..

4 RS232 or RS485 individually isolated serial ports.

2 USB ports at the front.

1 mini USB front port for diagnosis and maintenance jobs.

IRIG-B synchronisation input with regeneration capacity.

Communication protocols

IEC 61850 MMS: Server.

IEC 61850 GOOSE: Client and Server.

DNP3.0 TCP/Series: Master and Slave.

PRP and PTP 1588 V2 PP.

MODBUS TCP/Series: Master.

IEC 60870-5-104: Slave.

INPUT / OUTPUT

Digital Inputs

Up to 128 digital opto-isolated inputs and 48,125 or 250 VDC polarization voltages.

Card models: 16 DI with independent common; 32 DI with one independent common for every 8 inputs.

Nominal voltage Vin OFF Vin ON Vmax Consumption

48V 31V 40V 75V

150V @ 1min 1.85mA

110/125V 71V 90V 190V

300V @ 1min 2.145mA

220/250V 143V 190V 375V

500V @ 1 min 645uA

Digital Outputs

Up to 32 digital outputs with electromechanical relay.

Card models: 16 digital outputs, 4 bistable outputs, and 8 digital outputs.

Relay Outputs

Parameter Value

Maximum voltage 250Vac

Load capacity 16A

30A @ 200ms

Break capacity

(L/R=40ms) 25VA (V = 125Vdc) 1000 operations

Bistable Outputs Maximum voltage 250Vac

Load capacity 8A

Page 4: saTECH BCU

www.arteche.com 4

2.0

DC Analog Inputs

Up to 32 isolated analogue inputs in voltage or current, with configurable input ranges (±1mA, 4÷20mA, 0-10VDC).

Card model: 16 EA (mA, V).

Parameter Nominal Value Range Maximum

Current

Range Input ± 20mA ±10%

Input resistance <500 Ω

Consumption per input <0.2W

Voltage

Range Input ± 10V ±10%

Input resistance <5 kΩ

Consumption per input <0.05W

AC Analog Inputs (VT/TC)

Up to 4 independent isolated analogue inputs with 115 Vn (wide range from 10 to 300 VAC).

Up to 4 independent, isolated analogue inputs with 1 or 5A input current.

Parameter Nominal Value Range Maximum

Current

Phase current

1A 0.02 x In - 20 x In

20mA - 20A

100 x In @ 1s

100A @ 1s

5A 0.02 x In - 20 x In

100mA - 100A

100 x In @ 1s

500A @ 1s

Burden Current <0.25VA

Sn Current 5mA - 5A 20A @ 1s

Burden <0.25VA

Voltage

Phase voltage and synchrony

110V 1V -300V 450V @ 10s

Frequency 50/60Hz 0-70Hz

Burden <0.2VA @ 220V

<0.1VA @ 110V

POWER SUPPLY

48 Vdc Range: 39 VDC at 57 VDC (+/-20%).

125 Vdc/250 Vdc Range: 100-320 VDC / 100-240 VAC 50-60Hz.

ENVIRONMENT

Environmental features Operating temperature range: -40 to 85 ºC.

Storage temperature range: -40 to 85 ºC.

MECHANICAL FEATURES

Size 19” rack mounting.

Modular, from 2U up to 5U depending on the equipment.

Page 5: saTECH BCU

www.arteche.com 5

2.0

COMPLIANCE RULES Compliance Standards

Test Rules and/or

specifications Required severity level

Environmental

Temperature in operation dry heat

IEC 60068-2-2 Test Bd

+85ºC @ 16h operation +70ºC @ 96h operation

+55ºC @ 1000h operation +85ºC @ 96h storage

Temperature in cold operation IEC 60068-2-1 Test Ad -40 ºC @ 96 h storage and operation

Sudden changes in temperature

IEC 60068-2-14 -25 ºC to +55 ºC

5 cycles of 1-hour

Temperature and humidity IEC 60068-2-30

25ºC @ >95%HR 55ºC @ 93%HR

6 cycles (12h+12h)

Transport and storage IEC 60068-2-78 55ºC @ 93%HR

10 days

Mechanical

Vibration IEC 60255-21-1

EN 60068-2-6

1 g @ 10 Hz < F< 150 Hz

1 cycles/axis, energized equipment

Vibration endurance IEC 60255-21-1

EN 60068-2-6

2 g @ 10 Hz < F < 150 Hz

20 cycles/axis, unpowered equipment

Shock response IEC 60255-21-2

EN 600068-2-27 5g 3 cycles/axis, energized equipment

Shock resistance IEC 60255-21-2

EN 600068-2-27 15g 3 cycles/axis, energized equipment

Sinusoidal vibration (Seismic) IEC 60255-21-3

EN 600068-2-6

2g X and Y axes, 1g axis Z

1 cycle per axes, energized equipment

Shakes IEC 60255-21-1

EN 60068-2-27

10g 1000 pulses/axis, energized equipment

Pressure IN 60870-2-2

70 kPa, equivalent to 3000m altitude

Duration 1 hour at 25 ºC, energized equipment

IP degree protection IEC 60529 IP40

Free fall IEC 60068-2-31 500mm 2 falling/packing face

Electromagnetic

compatibility

Radiated emissions EN 55032

CISPR 16-4-2 Class A (30MHz - 6GHz)

Conducted emissions EN 55032

CISPR 16-4-2 Class A (150kHz to 30MHz)

Electrostatic discharge IEC 61000-4-2 ± 8 kV contact

± 15 kV air Class A

Immunity to electromagnetic fields

IEC 61000-4-3

Class A 10 V/m at 1 kHz; 80 to 6000 MHz

Class A 30 V/m at 1 kHz; 80 to 1000 MHz

Fast transients IEC 61000-4-4

Test frequency: 5 and 100 kHz 4kV 5/50ns: Power and I/O. Class A

2kV 5/50ns: Communications and IRIG-B.

Class A

Page 6: saTECH BCU

www.arteche.com 6

2.0

Compliance Standards

Immunity - Shock waves IEC 61000-4-5

Common Mode: ± 4 kV Power supply, I/O

± 2 kV IRIG-B and Communications. Differential mode:

± 2 kV Power supply.

Class A

Conducted immunity IEC 61000-4-6 10 V/m from 150kHz to 80MHz

Immunity to magnetic fields at industrial frequency

IEC 61000-4-8 100 A/m continuous @ 1 minute

1000 A/m transient @ 2s

Immunity to magnetic field impulses

IEC 61000-4-9 1000A/m 30s

Immunity to magnetic fields at industrial frequency

IEC 61000-4-10

100 A/m s 3s

100kHz (40 pulses) and 1MHz (400 pulses)

Ring wave immunity test IEC 61000-4-12

Common Mode: ± 2.5 kV Power supply, I/O

± 1 kV IRIG-B and Communications. Differential mode:

± 1 kV Power supply, I/O

Immunity to disturbances conducted in common mode

IEC 61000-4-16

Common mode 300Vrms Differential mode 150Vrms

50Hz and 60Hz

Ripple on d.c. input power port immunity test

IEC 61000-4-17 20% Vn

50, 60, 100 and 120 Hz

Damped oscillatory wave immunity test

IEC 61000-4-18

Common Mode: ± 2.5 kV Power supply, I/O

± 1 kV IRIG-B and Communications. Differential mode:

± 1 kV Power supply, I/O

Voltage dips, short interruptions and voltage

variations on d.c. input power port

IEC 61000-4-29

Short interruptions: 100% 0V HZ, LZ 100 ms. Class A

Drops: 60% 44V 200 ms. Class A 30% 77V 500 ms. Class A

Cut voltage: 100% 0V 250 cycles/5s. Class B

Gradual on and off:

100% 0V off 60s-5min, on 60S. Class C

Security

Isolation IEC 60255-27 500V

Impulse IEC 60255-27

±5 kV Power supply, I/O

±2 kV IRIG-B and Communications.

Dielectric resistance IEC 60255-27

±5 kV Power supply, I/O

±2 kV IRIG-B and Communications.

Page 7: saTECH BCU

www.arteche.com 7

2.0

FRONT VIEW

Front view with TFT touch screen

Front view without TFT touch screen

REAR VIEW

Example configuration of 2Us

LCD DISPLAY

KEYBOARD

Ground connector

MATRIX LED

IRIG-B

TOUCH SCREEN

MAINTENANCE PORTS

SERIAL PORT INDICATORS

ETHERNET INDICATORS

Power supply input

Ethernet RJ-45 Serial ports

Digital input and output terminals.

Page 8: saTECH BCU

www.arteche.com 8

2.0

Example configuration of 3Us

Example configuration of 5Us

Ground connector

IRIG-B Input Power

supply

Ground connector

IRIG-B Input Power

supply OF Ports

LC. connector Serial ports

Digital input and output terminals

AC voltage input terminals

AC current input terminals

Input and output terminals

AC voltage input terminals

AC current input terminals