saTECH BCU
Transcript of saTECH BCU
www.arteche.com 1
2.0
saTECH BCU
Automation System and Bay Control Unit
APPLICATIONS Substation Automation: Acquisition, monitoring and measurement unit for any bay position.
Sequential event logger: It stores input and output change of status with an accuracy of 1 millisecond.
Great interoperability capacity among devices through conventional protocols and/or IEC 61850 standard
protocols using Ethernet or serial ports.
Auxiliary service monitoring and control.
KEY BENEFITS IEC 61850 native design.
Robust and reliable equipment, allowing its use both in process bus applications and station bus.
Interoperability with the main IED manufacturers. Flexibility for the implementation of advanced control strategies to get the most of the communication capacity performance and the IEDs’ current interoperability.
IEEE 1588 Synchronization, PRP Network Redundancy and IEC 61850 Test Mode.
Modularity, which allows the selection of the most suitable hardware configuration.
Visual logical configuration in accordance with IEC 61131 standard.
It optimises the implementation of any monitoring system by selecting previously configured single diagram lines and adapting them to your needs through the saTECH CNF configuration software, in an easy and simple way.
www.arteche.com 2
2.0
MAIN FEATURES
Protocols Master
Customer
Slave
Server
IEC 61850 MMS Report
IEC 61850 MMS/GOOSE
DNP3 TCP/Series
MODBUS TCP/Series
IEC 60870-5-104
Programmable logical functions for the configuration of monitoring diagrams in accordance with IEC 61131 standard.
High-resolution touch screen which allows the monitoring of local operations with of customizable screens, such as single diagram line, events, alarm lists, real-time measurements or primary device status.
48 programmable LEDs at the front panel.
Opening and close switch push-buttons at the front panel.
Option double power supply and 8 digital outputs type "C".
Confirmation of manual operation protected through password.
Ethernet access via copper and fiber optic cabling. With PRP support and “fail-over”.
Communications through RS-232 and RS-485 isolated serial ports.
Communication with SCADA and with other IEDs using IEC 61850 logical nodes and GOOSE, DNP, Modbus, and IEC 60870-5-104 protocols.
Sequential event log, storing the last 1,400 analogue events and 1,400 digital events in non-volatile memory.
WEB server with I/O simulation functions, real-time display of IEC-61131 logics, historical record, communication trace, and hardware diagnostic.
Several synchronization sources from through IEEE 1588 (PTP IEEE Std C37.228-2011 with power systems profile), SNTP and IRIG-B conventional protocols.
Embedded cybersecurity features, including advanced user authentication encryption, integrated firewall, and secure communication protocols (SFTP, SSH).
Hardware design with no removable parts and a solid-state storage.
Robust design with a wide range of operation temperatures.
TEST mode conforming to IEC 61850.
Data model according to SAS Specification IEC 61850 CFE Transmission DT-CTRL-10.
www.arteche.com 3
2.0
TECHNICAL SPECIFICATIONS
COMUNICACIONES
Communication Ports
3 10/100 Mbps individual Ethernet ports.
(1 RJ45 front port and 2 rear ports with RJ45 or fiber optics options).
Options:
Dual 100 Base fiber ETH - FX (ST or LC type).
Dual 10/100 Base copper ETH- TX (RJ45 type)..
4 RS232 or RS485 individually isolated serial ports.
2 USB ports at the front.
1 mini USB front port for diagnosis and maintenance jobs.
IRIG-B synchronisation input with regeneration capacity.
Communication protocols
IEC 61850 MMS: Server.
IEC 61850 GOOSE: Client and Server.
DNP3.0 TCP/Series: Master and Slave.
PRP and PTP 1588 V2 PP.
MODBUS TCP/Series: Master.
IEC 60870-5-104: Slave.
INPUT / OUTPUT
Digital Inputs
Up to 128 digital opto-isolated inputs and 48,125 or 250 VDC polarization voltages.
Card models: 16 DI with independent common; 32 DI with one independent common for every 8 inputs.
Nominal voltage Vin OFF Vin ON Vmax Consumption
48V 31V 40V 75V
150V @ 1min 1.85mA
110/125V 71V 90V 190V
300V @ 1min 2.145mA
220/250V 143V 190V 375V
500V @ 1 min 645uA
Digital Outputs
Up to 32 digital outputs with electromechanical relay.
Card models: 16 digital outputs, 4 bistable outputs, and 8 digital outputs.
Relay Outputs
Parameter Value
Maximum voltage 250Vac
Load capacity 16A
30A @ 200ms
Break capacity
(L/R=40ms) 25VA (V = 125Vdc) 1000 operations
Bistable Outputs Maximum voltage 250Vac
Load capacity 8A
www.arteche.com 4
2.0
DC Analog Inputs
Up to 32 isolated analogue inputs in voltage or current, with configurable input ranges (±1mA, 4÷20mA, 0-10VDC).
Card model: 16 EA (mA, V).
Parameter Nominal Value Range Maximum
Current
Range Input ± 20mA ±10%
Input resistance <500 Ω
Consumption per input <0.2W
Voltage
Range Input ± 10V ±10%
Input resistance <5 kΩ
Consumption per input <0.05W
AC Analog Inputs (VT/TC)
Up to 4 independent isolated analogue inputs with 115 Vn (wide range from 10 to 300 VAC).
Up to 4 independent, isolated analogue inputs with 1 or 5A input current.
Parameter Nominal Value Range Maximum
Current
Phase current
1A 0.02 x In - 20 x In
20mA - 20A
100 x In @ 1s
100A @ 1s
5A 0.02 x In - 20 x In
100mA - 100A
100 x In @ 1s
500A @ 1s
Burden Current <0.25VA
Sn Current 5mA - 5A 20A @ 1s
Burden <0.25VA
Voltage
Phase voltage and synchrony
110V 1V -300V 450V @ 10s
Frequency 50/60Hz 0-70Hz
Burden <0.2VA @ 220V
<0.1VA @ 110V
POWER SUPPLY
48 Vdc Range: 39 VDC at 57 VDC (+/-20%).
125 Vdc/250 Vdc Range: 100-320 VDC / 100-240 VAC 50-60Hz.
ENVIRONMENT
Environmental features Operating temperature range: -40 to 85 ºC.
Storage temperature range: -40 to 85 ºC.
MECHANICAL FEATURES
Size 19” rack mounting.
Modular, from 2U up to 5U depending on the equipment.
www.arteche.com 5
2.0
COMPLIANCE RULES Compliance Standards
Test Rules and/or
specifications Required severity level
Environmental
Temperature in operation dry heat
IEC 60068-2-2 Test Bd
+85ºC @ 16h operation +70ºC @ 96h operation
+55ºC @ 1000h operation +85ºC @ 96h storage
Temperature in cold operation IEC 60068-2-1 Test Ad -40 ºC @ 96 h storage and operation
Sudden changes in temperature
IEC 60068-2-14 -25 ºC to +55 ºC
5 cycles of 1-hour
Temperature and humidity IEC 60068-2-30
25ºC @ >95%HR 55ºC @ 93%HR
6 cycles (12h+12h)
Transport and storage IEC 60068-2-78 55ºC @ 93%HR
10 days
Mechanical
Vibration IEC 60255-21-1
EN 60068-2-6
1 g @ 10 Hz < F< 150 Hz
1 cycles/axis, energized equipment
Vibration endurance IEC 60255-21-1
EN 60068-2-6
2 g @ 10 Hz < F < 150 Hz
20 cycles/axis, unpowered equipment
Shock response IEC 60255-21-2
EN 600068-2-27 5g 3 cycles/axis, energized equipment
Shock resistance IEC 60255-21-2
EN 600068-2-27 15g 3 cycles/axis, energized equipment
Sinusoidal vibration (Seismic) IEC 60255-21-3
EN 600068-2-6
2g X and Y axes, 1g axis Z
1 cycle per axes, energized equipment
Shakes IEC 60255-21-1
EN 60068-2-27
10g 1000 pulses/axis, energized equipment
Pressure IN 60870-2-2
70 kPa, equivalent to 3000m altitude
Duration 1 hour at 25 ºC, energized equipment
IP degree protection IEC 60529 IP40
Free fall IEC 60068-2-31 500mm 2 falling/packing face
Electromagnetic
compatibility
Radiated emissions EN 55032
CISPR 16-4-2 Class A (30MHz - 6GHz)
Conducted emissions EN 55032
CISPR 16-4-2 Class A (150kHz to 30MHz)
Electrostatic discharge IEC 61000-4-2 ± 8 kV contact
± 15 kV air Class A
Immunity to electromagnetic fields
IEC 61000-4-3
Class A 10 V/m at 1 kHz; 80 to 6000 MHz
Class A 30 V/m at 1 kHz; 80 to 1000 MHz
Fast transients IEC 61000-4-4
Test frequency: 5 and 100 kHz 4kV 5/50ns: Power and I/O. Class A
2kV 5/50ns: Communications and IRIG-B.
Class A
www.arteche.com 6
2.0
Compliance Standards
Immunity - Shock waves IEC 61000-4-5
Common Mode: ± 4 kV Power supply, I/O
± 2 kV IRIG-B and Communications. Differential mode:
± 2 kV Power supply.
Class A
Conducted immunity IEC 61000-4-6 10 V/m from 150kHz to 80MHz
Immunity to magnetic fields at industrial frequency
IEC 61000-4-8 100 A/m continuous @ 1 minute
1000 A/m transient @ 2s
Immunity to magnetic field impulses
IEC 61000-4-9 1000A/m 30s
Immunity to magnetic fields at industrial frequency
IEC 61000-4-10
100 A/m s 3s
100kHz (40 pulses) and 1MHz (400 pulses)
Ring wave immunity test IEC 61000-4-12
Common Mode: ± 2.5 kV Power supply, I/O
± 1 kV IRIG-B and Communications. Differential mode:
± 1 kV Power supply, I/O
Immunity to disturbances conducted in common mode
IEC 61000-4-16
Common mode 300Vrms Differential mode 150Vrms
50Hz and 60Hz
Ripple on d.c. input power port immunity test
IEC 61000-4-17 20% Vn
50, 60, 100 and 120 Hz
Damped oscillatory wave immunity test
IEC 61000-4-18
Common Mode: ± 2.5 kV Power supply, I/O
± 1 kV IRIG-B and Communications. Differential mode:
± 1 kV Power supply, I/O
Voltage dips, short interruptions and voltage
variations on d.c. input power port
IEC 61000-4-29
Short interruptions: 100% 0V HZ, LZ 100 ms. Class A
Drops: 60% 44V 200 ms. Class A 30% 77V 500 ms. Class A
Cut voltage: 100% 0V 250 cycles/5s. Class B
Gradual on and off:
100% 0V off 60s-5min, on 60S. Class C
Security
Isolation IEC 60255-27 500V
Impulse IEC 60255-27
±5 kV Power supply, I/O
±2 kV IRIG-B and Communications.
Dielectric resistance IEC 60255-27
±5 kV Power supply, I/O
±2 kV IRIG-B and Communications.
www.arteche.com 7
2.0
FRONT VIEW
Front view with TFT touch screen
Front view without TFT touch screen
REAR VIEW
Example configuration of 2Us
LCD DISPLAY
KEYBOARD
Ground connector
MATRIX LED
IRIG-B
TOUCH SCREEN
MAINTENANCE PORTS
SERIAL PORT INDICATORS
ETHERNET INDICATORS
Power supply input
Ethernet RJ-45 Serial ports
Digital input and output terminals.
www.arteche.com 8
2.0
Example configuration of 3Us
Example configuration of 5Us
Ground connector
IRIG-B Input Power
supply
Ground connector
IRIG-B Input Power
supply OF Ports
LC. connector Serial ports
Digital input and output terminals
AC voltage input terminals
AC current input terminals
Input and output terminals
AC voltage input terminals
AC current input terminals
OF Ports LC. connector Serial ports