4
Time started: Discharge temperature 1 2 1 2 1 2 30 minutes 45 minutes 1 hour 1.5 hour 2 hours 2.5 hours 3 hours 4 hours NOTE: Time Completed: Heat Cool Outside ambient temperature (°F): Indoor temperature (°F): THIS DOCUMENT IS FOR REFERENCE ONLY. THIS IS NOT AN INSTRUCTION MANUAL. PLEASE REFER TO SAMSUNG INSTALLATION MANUALS FOR PROPER INSTALLATION METHODS, PROCEDURES, AND DATA. ALL INSTALLING COMPANIES MUST ATTEND DVM TRAINING BEFORE INSTALLATION OF SAMSUNG DVM EQUIPMENT. ONLY BASIC INSTALLATION POINTS ARE NOTED WITHIN THIS DOCUMENT. EVERY STEP OF THE INSTALLATION PROCESS OF SAMSUNG DVM SYSTEMS IS NOT COVERED BY THIS SIMPLE CHECKLIST. LOCAL AND STATE CODES IN YOUR AREA WILL TAKE PRIORITY OVER INFROMATION IN THIS CHECKLIST. NOT ALL EQUIPMENT DISCUSSED IN THIS DOCUMENT WILL APPLY TO YOUR PROJECT. Date:___________________________________________________________ Jobsite Name:___________________________________________________ Company Name:_________________________________________________ Heating trial operation discharge temperature: (Discharge temperature - high pressure saturated temperature) 54˚ F. If this condition is not satisfied Compressor Compressor Compressor Discharge temperatures should be between 140° F - 221° F during normal operation. If over 221° F, check for low refrigerant and verify liquid service valve is open. Compressor will stop if discharge temperature reaches 248° F. If below 140° F for long periods, the system is most likely overcharged. ** NOTE: Operation data must be obtained using SNET Pro 2 service software and MIM-C02N communication converter. ** MAIN unit SUB1 unit SUB2 unit NOTES Auto-trial mode completed (hold K1 for 5 seconds) Pipe check mode operation complete (mandatory for heat recovery systems) Refrigerant amount check completed (K2, 5 times) Test operation mode Employee Name:_________________________________________________ Jobsite Address:_________________________________________________ For reference only. This is not an instruction manual. www.SamsungHVAC.com 1 the system may be overcharged. Check refrigerant volume, outdoor EEV, outdoor liquid bypass valve, and EVI_EEV. (more on following page) Samsung DVM S System Startup Checklist, Operation Log, and Operation Reference QS_DVMS_112016A

Transcript of Samsung DVM S System Startup Checklist, Operation … DVM S System Startup Checklist, Operation Log,...

Page 1: Samsung DVM S System Startup Checklist, Operation … DVM S System Startup Checklist, Operation Log, and Operation Reference High/Low Pressure (PSI) High Low High Low High Low 30 minutes

Time started:

Discharge temperature

1 2 1 2 1 230 minutes

45 minutes

1 hour

1.5 hour

2 hours

2.5 hours

3 hours

4 hours

NOTE:

Time Completed:Heat Cool

Outside ambient temperature (°F): Indoor temperature (°F):

THIS DOCUMENT IS FOR REFERENCE ONLY. THIS IS NOT AN INSTRUCTION MANUAL. PLEASE REFER TO SAMSUNG INSTALLATION MANUALS FOR PROPER INSTALLATION METHODS, PROCEDURES, AND DATA. ALL INSTALLING COMPANIES MUST ATTEND DVM TRAINING BEFORE INSTALLATION OF SAMSUNG DVM EQUIPMENT. ONLY BASIC INSTALLATION POINTS ARE NOTED WITHIN THIS DOCUMENT. EVERY STEP OF THE INSTALLATION PROCESS OF SAMSUNG DVM SYSTEMS IS NOT COVEREDBY THIS SIMPLE CHECKLIST. LOCAL AND STATE CODES IN YOUR AREA WILL TAKE PRIORITY OVER INFROMATION IN THIS CHECKLIST. NOT ALL EQUIPMENT DISCUSSED IN THIS DOCUMENT WILL APPLY TO YOUR PROJECT.

Date:___________________________________________________________

Jobsite Name:___________________________________________________

Company Name:_________________________________________________

• Heating trial operation discharge temperature: (Discharge temperature - high pressure saturated temperature) ≥ 54˚ F. If this condition is not satisfied

Compressor Compressor Compressor

• Discharge temperatures should be between 140° F - 221° F during normal operation. If over 221° F, check for low refrigerant and verify liquid service valve isopen.• Compressor will stop if discharge temperature reaches 248° F. If below 140° F for long periods, the system is most likely overcharged.

** NOTE: Operation data must be obtained using SNET Pro 2 service software and MIM-C02N communication converter. **

MAIN unit SUB1 unit SUB2 unit NOTES

Auto-trial mode completed (hold K1 for 5 seconds)

Pipe check mode operation complete (mandatory for heat recovery systems)

Refrigerant amount check completed (K2, 5 times)

Test operation mode

Employee Name:_________________________________________________

Jobsite Address:_________________________________________________

For reference only. This is not an instruction manual.www.SamsungHVAC.com 1

the system may be overcharged. Check refrigerant volume, outdoor EEV, outdoor liquid bypass valve, and EVI_EEV.

(more on following page)

Samsung DVM S System Startup Checklist, Operation Log, and Operation Reference

QS_DVMS_112016A

Page 2: Samsung DVM S System Startup Checklist, Operation … DVM S System Startup Checklist, Operation Log, and Operation Reference High/Low Pressure (PSI) High Low High Low High Low 30 minutes

Samsung DVM S System Startup Checklist, Operation Log, and Operation Reference

Condenser coil outlet temperature / subcooler outlet temperature

MAIN unit SUB1 unit SUB2 unit MAIN unit SUB1 unit SUB2 unit

30 minutes1 hour

1.5 hour

2 hours

2.5 hours

3 hours

4 hours

NOTE:

• Cooling CondOut should be between 5° F ~ 36° F greater than outside ambient temperature.• Heating CondOut: should be at least 2° F lower than outside ambient temperature.• (Suction temp - Suction saturated temp) = 0 ~ 12.6° F• Liquid tube temp: 68° F ~ 122° F under standard conditions and normal operation. Low or high ambient temperatures can extend this range down or up.

Compressor current (A)

1 2 1 2 1 230 minutes

45 minutes

1 hour

1.5 hour

2 hours

2.5 hours

3 hours

4 hours

NOTE:

NOTE: • Outdoor MAIN EEV should be at 0 steps during cooling operation mode.

• Compressor 1 current read from SNET Pro 2 Software or outdoor unit PCB also includes fan current.

Outdoor EEV position

Cooling test mode: Heating test mode:

MAIN unit SUB1 unit SUB2 unit NOTESCompressor Compressor Compressor

CondOut Liquid Tube Temp NOTES

• CondOut range: 86° F ~ 131° F under standard conditions and normal operation. Low or high ambient temperatures can extend this range down or up.

For reference only. This is not an instruction manual.www.SamsungHVAC.com 2

(more on following page)

Page 3: Samsung DVM S System Startup Checklist, Operation … DVM S System Startup Checklist, Operation Log, and Operation Reference High/Low Pressure (PSI) High Low High Low High Low 30 minutes

Samsung DVM S System Startup Checklist, Operation Log, and Operation Reference

High/Low Pressure (PSI)

High Low High Low High Low30 minutes

45 minutes

1 hour

1.5 hour

2 hours

2.5 hours

3 hours

4 hours

NOTE:

IPM Temperature (inverter PCB temperature)

IPM 1 IPM 2 IPM 1 IPM 2 IPM 1 IPM 230 minutes

45 minutes

1 hour

1.5 hour

2 hours

2.5 hours

3 hours

4 hours

NOTE:

Indoor Unit DataCooling trial operation

Average indoor SH (EVA_OUT - EVA_IN):

• Indoor EEV steps will range between 0 ~ 2,000. Under normal operation and conditions the indoor unit EEV(s) should stay within 250 ~1400 steps.

• If more than 50% of indoor unit EEV's SH ((EVA_OUT) - (EVA_IN)) > 11° F and EEV step of those units > 1400, the system maybeundercharged.• If a small percentage of indoor unit EEV steps are > 1400 under standard operating and space conditions, verify the distance from the first Y-

(EVA_OUT - EVA_IN) should equal approximately 0 ~ 7 after sufficient system operation times. This value will vary initially based on outdoor conditions and indoor conditions.

MAIN unit SUB1 unit SUB2 unit NOTES

• When IPM board temperatures ≥ 194° F the system will modify operation to prevent overheating. No errors will occur until temperatures reach 212° F.Capacity can decrease during protection without any visual indication of protection occurring if below 212° F.

NOTES

• Low pressure range during cooling test operation: 85 ~ 128 PSI. When outdoor temperatures and indoor loads are high, this value may be higher.• Low pressure range during heating test operation: 71 ~ 106 PSI. This is a basic reference as ambient temperatures will change this value.• High pressure range during cooling test operation: 355 ~ 469 PSI. This value can increase with ambient temperatures (max. 512 PSI)• High pressure range during heating test operation: 355 ~ 455 PSI. This value can decrease when outside ambient temperature is below 32° F or indoortemperature is below 68° F.

MAIN unit SUB1 unit SUB2 unit

For reference only. This is not an instruction manual.www.SamsungHVAC.com 3

joint to each unit is within Samsung pipe limitations.

(more on following page)

• Under normal operation and conditions, EVA_IN temperature should be between 45° F - 57° F for all indoor units• Under normal operation and conditions, EVA_OUT temperature should be between 45° F - 57° F for all indoor units

Page 4: Samsung DVM S System Startup Checklist, Operation … DVM S System Startup Checklist, Operation Log, and Operation Reference High/Low Pressure (PSI) High Low High Low High Low 30 minutes

Samsung DVM S System Startup Checklist, Operation Log, and Operation Reference

Indoor Unit Data (continued)Heating trial operation

• Under normal operation and conditions, EVA_OUT temperature should be between 113° F - 194° F for all indoor units.• Under normal operation and conditions, EVA_IN temperature should be between 91° F - 122° F for all indoor units.• Under normal operation and conditions, diffuser temperatures should be 105°F or greater.• EEV position will vary based on indoor and outdoor conditions.

Average EVA_IN temperature:

• If only a small number of indoor unit EVA_IN and EVA_OUT temperatures are lower than normal under standard operating and spaceconditions, verify the distance from the first Y-joint to each unit is within Samsung pipe limitations.• If all indoor unit EVA_IN temperatures are lower than 91.4 ° F, outside ambient temperature is below 41° F, and high pressure is below 356PSI, the system maybe oversized or overcharged.

Average EVA_OUT temperature:

For reference only. This is not an instruction manual.

QS_DVMS_122013A

www.SamsungHVAC.com 4