This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upon therein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com INSPECTION CONDITIONS It is the clients sole responsibility to read this report in its entirety and to research any and all jurisdictional permits required by the local authorities regarding the property in contract before the close of escrow. The client is to personally perform a diligent visual inspection of the property after the seller vacates to insure that no "condition" was concealed by personal property and/or stored items while occupied, or damaged during the seller's evacuation of the building. Should any "condition" be revealed that was not addressed within this report prior to, or after the close of escrow please contact our office immediately for an additional evaluation regarding such "condition." CLIENT & SITE INFORMATION: 101 FILE/DATE/TIME: File # 060321900 Date: Any Date, 2006 Time: 9:00 AM. 102 CLIENT NAME: Any Client. 103 LOCATION: Any Street Any City, CA. 104 BUYER'S AGENT: The Best Agent. CLIMATIC CHARACTERISTICS: 106 WEATHER/SOIL: Weather conditions during the inspection: partly cloudy windy, 50-60 degrees and the ground was dry. BUILDING CHARACTERISTICS: 108 STRUCTURE: Age: 1999, 2 story, 2,400 sq. ft., Single Family Residence. 109 FOUNDATION: Foundation types: raised foundation. UTILITY SERVICES: 113 UTILITIES: Municipal: All utilities on. OTHER INFORMATION: 114 ATTENDING: People present: seller, listing agent, buyers agent and client(s) 115 OCCUPIED: The building was occupied and access to some items such as; electrical outlets/receptacles, windows, wall/floor surfaces, and cabinet interiors may be restricted by furniture or personal belongings. Any such items are excluded from this inspection report.

description

Lugar Inspection Services Sample Home Inspection Report

Transcript of Sample Report

Page 1: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

INSPECTION CONDITIONS

It is the clients sole responsibility to read this report in its entirety and to research any and all jurisdictionalpermits required by the local authorities regarding the property in contract before the close of escrow. Theclient is to personally perform a diligent visual inspection of the property after the seller vacates to insure thatno "condition" was concealed by personal property and/or stored items while occupied, or damaged during theseller's evacuation of the building. Should any "condition" be revealed that was not addressed within this reportprior to, or after the close of escrow please contact our office immediately for an additional evaluation regardingsuch "condition."

CLIENT & SITE INFORMATION:101 FILE/DATE/TIME: File # 060321900 Date: Any Date, 2006 Time: 9:00 AM.

102 CLIENT NAME: Any Client.

103 LOCATION: Any Street Any City, CA.

104 BUYER'S AGENT: The Best Agent.

CLIMATIC CHARACTERISTICS:106 WEATHER/SOIL: Weather conditions during the inspection: partly cloudy windy, 50-60 degrees and the

ground was dry.

BUILDING CHARACTERISTICS:108 STRUCTURE: Age: 1999, 2 story, 2,400 sq. ft., Single Family Residence.

109 FOUNDATION: Foundation types: raised foundation.

UTILITY SERVICES:113 UTILITIES: Municipal: All utilities on.

OTHER INFORMATION:114 ATTENDING: People present: seller, listing agent, buyers agent and client(s)

115 OCCUPIED: The building was occupied and access to some items such as; electricaloutlets/receptacles, windows, wall/floor surfaces, and cabinet interiors may be restrictedby furniture or personal belongings. Any such items are excluded from this inspectionreport.

Page 2: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

116 INSPECTED BY: Bill Lugar, CREIA Certified Inspector.

INTRODUCTORY NOTES:118 IMPORTANTINFORMATION:

[NOTE] Any statements made in the body of this inspection report pertaining to left, right,front or rear are referenced to standing in front of and facing the building. [NOTE] Werecommend obtaining equipment operating manuals and documentation for all warranteditems of the building. [SC] Gas leak and carbon monoxide testing are beyond the scopeof the inspection. We recommend further evaluation of all gas appliance by a specialist inthe appropriate trade. [NOTE] We recommend having the locks on all of the exteriordoors re-keyed after taking possession of the building for security reasons. [NOTE] Photographs when used, are simply a tool to convey our findings, they are not intended toenhance those findings or diminish any findings not photographed. [NOTE] This report issoley produced for the client listed. Reproduction of this report is unauthorized and not tobe used for insurance purposes or any other other matters. [FE] If the interior of thehome has been repainted and/ot there have been flooring changes. Each of these canremove or conceal evidence of any past conditions that may have been present prior tothe work being done. We recommend inquiring the sellers about any past conditions thatmay no longer be visible. [NOTE] We do not note cosmetic conditions. We recommendmaking your own notes or using small removable stickers on the items or areas ofconcern. Window, door and roof leaks may not be identifiable. Shrinkage cracks willdevelop over time and are normal. [NOTE] Buildings built before 1978 may haveproducts in them that contain some amounts asbestos or lead, determining the presenceof these products is beyond the scope of this report. Information related to these productscan be found in the "Homeowners Guide to Earthquake Safety & Environmental Hazards"pamphlet. [FE] We recommend inquiring about any/all permits and inspection recordswith final signatures for any changes or additions that may have been made to thebuilding, and/or any known conditions that may have been inadvertently left out of thedisclosure statements. [NOTE] We are not soil or geotechnical engineers and cannotrender an opinion regarding soil stability or potential soil movement. If desired, qualifiedspecialists should be consulted on these matters.

119 ENVIRONMENTALCONCERNS:

Environmental issues include but are not limited to asbestos, lead paint, leadcontamination, radon, mold/mildew, toxic waste, formaldehyde, electromagnetic radiation,buried fuel oil tanks, ground water contamination and soil contamination. We are nottrained or licensed to recognize or discuss any of these materials. We may makereference to one or more of these materials in this report when we observe one of thecommon forms of these substances. If further study or analysis seems prudent, theadvice and services of the appropriate specialists is recommended. Information relatedto these products can be found in the "Homeowners Guide to Earthquake Safety &Environmental Hazards" pamphlet.

DEFINITIONS:120 SAFETY CONCERNS: [SC] Safety Concerns: Conditions noted that may pose a hazard to humans, the building

or both. These conditions warrant further evaluation and corrections by a specialist in theappropriate trade.

121 FURTHER EVALUATION: [FE] Further Evaluation: Conditions noted that warrant further evaluation by specialists inthe appropriate trades.

Page 3: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

122 CORRECTIONSRECOMMENDED:

[CR] Corrections Recommended: Conditions noted in need of maintenance, repair orreplacement. We recommend that all corrections be made by specialists in theappropriate trades.

123 RECOMMENDEDUPGRADE:

[RU] Recommended Upgrades: Upgrades are systems and/or components that may nothave been available or have been improved since the building was constructed. Thesemay be, but are not limited to safety related items; such as GFCI receptacle and smokedetector locations and the installation of safety glass where subject to human impact.

124 SERVICEABLE: Serviceable; As defined in the Websters Dictionary; "That can be of service; ready foruse; useful; useable". Means that a system and/or component was capable of performingits intended function and/or task. It does not imply that the system and/or component wasin perfect or in like new condition or that it would meet every individuals interpretation ofan acceptable state.

125 FUNCTIONED: Functioned; as defined in the CREIA/ASHI Standards of Practice; "Performing its normal,proper and characteristic action".

126 FAILED: Failed; As defined in Websters Dictionary; "To be deficient or negligent in an obligation,duty, or expectation". If an item did not function, then it was not serviceable and wasconsidered to have failed.

127 SPECIALIST: Specialist; as defined in the Websters Dictionary; "A person who specializes in aparticular field of study, professional work". Any individual schooled, trained and/orotherwise holds a special knowledge of specific systems or components. Trade school orfactory trained individuals in specific fields of expertise may be considered a "Specialist"as well as qualified state licensed contractors in specific occupations.

128 CLOSE OF ESCROW: [SC] Safety Concerns, [FE] Further Evaluation, [CR] Corrections Recommended, [RU] Recommended Upgrades:When the above listed items/abbreviations are stated in the report. We recommend thelisted items be evaluated and/or corrected prior to the close of escrow.

FOUNDATION/UNDER-FLOOR AREAS

Areas of the foundation and/or structural components of the building were inaccessible because they were installed at orbelow grade level, and/or behind walls. Areas concealed from view by any means and assessing the structural integrity ofa building is excluded from this report. The inspectors observations take into account the age of the building and theconstruction standards of that time, older buildings may lack many of the modern framing and seismic connectionspresently being utilized. Foundations may have curing cracks that do not represent a structural problem. All concreteexperiences some degree of cracking due to shrinkage in the drying process. If large cracks are present along withmovement, we recommend further evaluation by a structural engineer, foundation specialist or a geologist. All exteriorgrades should allow for surface and roof water to be diverted away from the foundation system. All maintenance, repairsor corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

Page 4: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

FOUNDATION:201 TYPE: Foundation types observed: Raised foundation with a concrete perimeter and interior

wood beams supported by concrete piers.

202 BOLTS/BRACING: Anchor bolts were observed in the visible and accessible areas of the newer additionareas of the crawl space during the inspection.

[RU] There were no anchor bolts or seismic connections observed between the originalportion of the house framing and the foundation. We recommend the building be boltedand/or fastened to the foundation using the appropriate methods to accommodate theconstruction design of the home as an upgrade for earthquake safety.

CRAWL SPACE:206 ACCESSIBILITY: Accessed from the exterior at the left side of the building. The crawl space was generally

accessible.

207 FOUNDATION: The concrete foundation had hairline cracks. This type of cracking is often a result ofshrinkage of materials, settlement or seismic action and usually does not affect thestrength of the foundation. with exceptions noted.a. [FE] There was a condition known as efflorescence on portions of the foundationwalls. This is a salt deposit left when moisture in the foundation evaporates. It indicatesthat the foundation is experiencing wet and dry cycles. We recommend improvement ofthe exterior grading and drainage.

208 FRAMING: The visible floor framing appeared serviceable. with exceptions noted.a. [CR] Earth-to-Wood contact is present at post in the left section of the crawlspace. Thiscondition is conducive to moisture damage and deterioration. We recommend correctingthe condition(s) noted.b. [CR] There was trash/debris observed in the crawl space area. We recommend thatall trash and debris be removed from the crawl space area. c. [CR] Some of the piers and posts were unsecured/ un-attached or have beenimproperly installed. We recommend correcting the condition(s) noted.

210 VENTILATION: The crawl space ventilation appeared serviceable. Good ventilation is vital for moisturecontrol. The exterior vents should be kept in good repair, clear of vegetation andinspected periodically.

213 DRYER VENT: [CR] The dryer vent exhaust pipe was observed to be flexible plastic in the crawl spaceunder the building. This is an improper installation. We recommend correcting thecondition(s) noted.

214 OBSERVATIONS: [CR] The drain lines had an improper in slope in the crawlspace to provide for adequatedrainage and blockage may result. We recommend correcting the condition(s) noted. [CR] There was improper wiring in the crawlspace in the form of splices in wiring, notcontained in approved boxes. We recommend correcting the condition(s) noted.

Page 5: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

EXTERIORS

The visible exterior surfaces and materials of the building were observed to determine their current condition. Areasconcealed from view by any means are excluded from this report. Moisture intrusion through cracks or openings in theexterior siding, trim, windows and doors are the source of moisture deterioration and damage. We recommend sealing allcracks or openings in, and between the exterior siding and trim materials, especially around windows and doors. Routinemaintenance may extend the service life and minimize deterioration of the exterior surfaces. All maintenance, repairs orcorrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

EXTERIOR INFORMATION:301 SIDING TYPE: Materials: stucco.

303 EXT TRIM TYPE: Materials: wood.

304 EXT DOOR TYPE: Materials: wood.

305 WINDOW TYPE: Type: casement, fixed and vertical sliding, there was a combination of single/non-thermaland double/thermal pane windows present.

306 WINDOW MATRLS: Materials: wood.

EXTERIOR CONDITIONS:308 STUCCO SIDING: The stucco siding appeared

serviceable, with common signs ofaging/wear with exceptions noted.a. [FE] Past repairs were noted on thestucco siding. We recommend inquiringabout the conditionsb. [CR] There were patched/caulkedcracks in the left stucco siding at theaddition. These conditions areconducive to moistureintrusion/deterioration. We recommendfurther evaluation and corrections by aspecialist in the appropriate trade.

317 EXT TRIM: The exterior wood trim appeared serviceable.

Page 6: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

318 EXT DOORS: The doors viewed from the exterior appeared serviceable.

319 WINDOWS: The windows viewed from the exterior appeared serviceable with exceptions noted.a. [CR] The finish on the window(s) was damaged/worn. We recommend they berefinished for better appearance and to maximize their service life. b. [CR] A number of the window screens were damaged and/or missing. Werecommend they be repaired or replaced as needed.

320 BALCONIES: [FE] The balcony(s) had been tiled. We cannot determine what, or if any membraneand/or flashing was installed under the tile. We recommend further evaluation by aspecialist in the appropriate trade.

321 GUARD RAILS: The railings appeared serviceable.

322 EXT ELECTRICAL: The lights and receptacles appeared serviceable.

325 MOIST CONTROL: [FE] Our observations regarding evidence of damaged or deteriorated wood should notbe a substitute for inspection by a licensed pest control operator or exterminator. Wereport current visible conditions only and cannot render an opinion regarding their causeor remediation.

The items listed below were visually observed to determine their current condition during the inspection, areas concealedfrom view by any means are excluded from this report. The permanently installed components or equipment are checkedfor basic operation, with exception to lawn sprinklers and low voltage yard lighting. This inspection is a visual observationand does not attempt to determine site drainage performance or the condition of any underground piping, includingmunicipal water and sewer service piping or concealed cleanouts. This inspection is not intended to address or includeany geological conditions or site stability information, for information in these areas we recommend consulting with ageologist and/or a geotechnical engineer.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

GROUNDS INFORMATION:327 DRIVEWAY: Materials: concrete.

329 WALKWAYS: Materials: concrete and tile on concrete.

330 STEPS & STAIRS: Materials: tile on concrete.

331 MAIN ENTRY: Materials: tile on concrete.

332 PATIOS: Materials: tile on concrete.

336 FENCING & GATES: Materials: stucco chain link, metal and wood.

GROUNDS CONDITION:338 DRIVEWAY: The driveway appeared serviceable There were common cracks in the driveway, no

action is needed at this time.

Page 7: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

340 WALKWAYS: The walkways appeared serviceable There were common cracks noted in the walkways,no action is needed at this time.

343 STEPS & STAIRS: The stairs were serviceable.

344 MAIN ENTRY: The entry/porch appeared serviceable.

350 FENCING & GATES: The yard fencing appeared serviceable with exceptions noted.a. [CR] Vegetation was growing on the fencing. This condition limits the inspection, andis conducive to moisture intrusion/deterioration. We recommend further evaluation andcorrections by a specialist in an appropriate trade.b. [CR] The rear metal fencing had moisture deterioration. We recommend correcting thecondition(s) noted.

The gate(s) were in serviceable condition.

GRADING/DRAINAGE/LANDSCAPING INFORMATION:357 SITE GRADING: Flat site

358 SITE DRAINAGE: Surface and underground drains

359 LAWN SPRNKLRS: NOTE: Yard sprinkler systems are outside of the scope of the inspection agreement andare not inspected.

GRADING/DRAINAGE/LANDSCAPING CONDITION:362 SITE GRADING: [RU] There were areas where, adjustments (removal of top soil and/or vegetation) of the

grading at the foundation would be advised to help excess moisture flow away from thefoundation. [RU] The yard grading at areas around the foundation had inadequate slope.The slope should fall away from the foundation at a rate of 1 inch per foot for at least 6

feet to prevent moisture accumulation next the foundation. We recommend correctingthe condition(s) noted.

363 SITE DRAINAGE: [NOTE] An underground drainagesystem was installed, it was not watertested during the inspection. We makeno representations as to itseffectiveness and recommend itsoperation be noted during adverseweather.[FE] The location of the discharge forthe driveway under ground drain wasnot located. We recommend inquiringabout the condition(s) noted.

[RU] Based on evidence noted aroundthe building. We recommend adrainage system be added to collectand divert surface water and roof runoffan appropriate location.

Page 8: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

364 LANDSCAPING: The vegetation and landscaping appeared manicured with exceptions noted.a. [CR] Tree(s) were planted too close to the building. We recommend considering theremoval, as trees continue to grow in size and damage may occur to the foundationand/or roof

366 SPRNKLR VALVES: [CR] There were visible leaks at the front control valves and anti-siphon devices. Werecommend correcting the condition(s) noted.

ROOF COVERINGS

The visible areas of the roof and components were observed to determine their current condition. Areas concealed fromview by any means are excluded from this report. The inspector cannot and does not offer an opinion or warranty as towhether the roof leaks or may be subject to future leakage. This report is issued in consideration of the foregoingdisclaimer. The testing of gutters, downspouts and underground drain piping is beyond the scope of this report. Allmaintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

ROOF INFORMATION:401 INSPECT METHOD: The inspector walked on the roof and viewed the accessible roofing components.

402 ROOF COVERING: Materials: clay tile and built-up with a cap sheet surface

403 ROOF LAYERS: 1 layer

404 CHIMNEY/FLUE: Materials: stucco chimney with a metal flue

405 ROOF DRAINAGE: Materials: metal rain gutters

ROOF CONDITION:411 CLAY TILE: The visible areas of the roof appeared serviceable with signs of weathering and aging.

Periodic maintenance and inspection is recommended. with exceptions noted.a. [CR] Trees were touching/overhanging the roof. We recommend they be trimmed andthe debris removed to prevent damage to the roof and to prevent animal access.b. [FE] There were a couple cracked tiles throughout the roof. We recommend furtherevaluation and corrections by a specialist in the appropriate trade.

Page 9: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

414 BUILT UP ROOF: Low slope: The visible areas of the roofappeared serviceable with signs ofweathering and aging. Periodicmaintenance and inspection isrecommended. with exceptions noted.a. [CR] There were areas of the roofthat require maintenance (damagedspots in field). We recommendcorrecting the condition(s) noted usingapproved methods.b. [CR] The roofing was improper atthe cricket ends/discharge points. Werecommend correcting the condition(s)noted.

415 PARAPETS: The parapet walls appeared serviceable.

416 FLASHINGS: The visible flashings appeared serviceable. with exceptions noted.a. [CR] The mastic used to seal some of the roof connections and penetrations wascracked. We recommend correcting the condition(s) noted using approved methods.

417 FLUE PIPES: The visible exhaust flue pipes and weather caps appeared serviceable.

1531 ROOF DRAINAGE: [RU] The roof drainage was directed to collect into gutters. They were not installed on alldown sloped roofs. We recommend additional gutters and downspouts be installed.

421 DOWNSPOUTS: [CR] The right cricket downspout was missing. We recommend correcting thecondition(s) noted.[CR] The rear deck downspout was missing. We recommend correcting the condition(s)noted.[CR] Runoff water from the roof discharged next to the building. We recommend thedownspouts be routed sufficiently away from the building to prevent ponding, pooling, andsaturation of the soil at the foundation.

Page 10: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

ATTIC AREAS & ROOF FRAMING

The visible areas of the attic and roof framing were observed to determine their current condition. Areas concealed fromview by any means are excluded from this report. The accessible permanently installed equipment or components arechecked for their basic operation. Thermostatically operated attic vent fans are excluded from the inspection. Allmaintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

ATTIC/FRAMING INFORMATION:501 ATTIC ACCESS: Access's: 1 Second bedroom closet Type: Hatch in the ceiling.

502 FRAMING: Conventional framing

503 SHEATHING: Plywood

504 INSULATION: Fiberglass batts

505 VENTILATION: Vent types: roof

ATTIC/FRAMING CONDITION:506 ACCESS: The inspection of the attic space was conducted from the opening only due to limited

access.

509 INSULATION: The visible attic insulation appeared serviceable.

510 VENTILATION: The attic ventilation appeared to be adequate. Good attic ventilation is beneficial to the longevity of the roofing material and comfort ofthe living spaces. Attic ventilation can be provided by eave, gable, and automatic or winddriven fans.

PLUMBING

The visible areas of the main water line, shutoff valve, water supply & drain lines, gas meter and piping were observed todetermine their current condition. Areas concealed from view by any means are excluded from this report. Theaccessible permanently installed equipment or components are checked for their basic operation. Leakage or corrosionin underground or concealed piping cannot be detected by a visual inspection. Older fixtures or components should bebudgeted for replacement. Fixture shutoffs are not tested, some corrosion is common. We are not equipped to repair a

Page 11: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

leaky shutoff caused by a test, we recommend fixture shutoffs be tested by a specialist in the appropriate trade equippedto repair or replace the shutoffs. All maintenance, repairs or corrections should be made by specialist's in the appropriatetrade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

PLUMBING INFORMATION:601 MAIN WATER LINE: Materials: copper piping where visible

602 WATER SHUTOFF: The main water shutoff valve was located at the left side of the building.

603 WATER PRESSRE: 60-70 PSI

604 WATER PIPING: Materials: copper piping where visible

605 WASTE LINES: Materials: ABS black plastic piping where visible

606 GAS SHUTOFF: The gas meter and shutoff valve are located at the left side of the building

PLUMBING CONDITIONS:607 WATER SHUTOFF: The main water shutoff valve appeared serviceable, no leakage observed. We do not

operate these devices.

608 WATER PRESSRE: The water pressure measured at an exterior hose faucet was within the acceptablerange.

609 WATER PIPING: The visible water supply piping appeared serviceable

610 WATER FLOW: A number of fixtures were operated simultaneously with a serviceable water flow.

611 HOSE FAUCETS: The accessible hose faucets were serviceable.

612 WASTE PIPING: The visible waste piping appeared serviceable. with exceptions noted.a. [CR] The drain lines had an improper in areas in the crawlspace to provide foradequate drainage and blockage may result. We recommend correcting the condition(s)noted. b. [FE] The underground main sewer line is not visible to inspect and no representationsare made about this system. We recommend further evaluation/scope/camera by aspecialist in the appropriate trade.

613 WASTE FLOW: A number of drains were emptied simultaneously and appeared serviceable.

615 VENT PIPING The visible areas of the vent pipes appeared serviceable

616 GAS SHUTOFF: [RU] The supply shutoff appeared serviceable, we do not operate these devices. Thereis no emergency shutoff wrench present. We recommend providing a wrench orinstalling a seismic automatic shut off valve for emergencies. with exceptions noted.a. [SC] There was a gas leak detected at the gas meter (front well). We recommendcontacting the Gas Company immediately to correct the condition(s) noted.

Page 12: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

617 GAS PIPING: The visible areas of the gas piping appeared serviceable.

FIRE SPRINKLER SYSTEM:629 CONTROLS: [FE] This system is outside the scope of the inspection and was not inspected. We

recommend consulting with a specialist regarding the operation and maintenance of thissystem.

WATER HEATER

WATER HEATER INFORMATION:1701 LOCATION: The water heater was located at the exterior

1702 MANUFACTURER: American

1703 MANUFCTR DATE: 2003

1704 SIZE / GALLONS: 50 gallon

1705 ENERGY TYPE: Natural gas

WATER HEATER CONDITIONS:1707 VENTING SYSTEM: The visible areas of the flue vent piping were intact and secured at the connections

1708 WATER PIPES: [CR] The water supply connectors were corroded, no leakage observed. Werecommend further evaluation by a specialist in an appropriate trade

1709 T&P VALVE: [SC] The temperature & pressure relief valve discharge line was routed in a material thatwas not rated for this application. We recommend installing an approved discharge linethat extends to the exterior and terminates close to the ground facing downward.

1710 TANK: The water heater tank appeared serviceable, no leakage noted.

1711 SEISMIC : [SC] The water heater was double strapped, it was not stabilized/blocked to resistmovement as required by the State Architect. We recommend correcting the condition(s)noted.

1712 COMBUSTION AIR: A combustion air supply for the water heater was present. Adequate ventilation for all fuelburning appliances is vital for their safe operation.

Page 13: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1713 ENERGY SUPPLY: The gas shutoff valve and flexible gas connector appeared serviceable.

1714 CONTROLS: The temperature control was set in the "normal range" and the water at the faucets waswarm/hot.

1716 CIRCLING PIPING: [CR] The hot water recirculating pump failed to function. We recommend correcting thecondition(s) noted.[CR] The hot water recirculating pump was corroded. We recommend correcting thecondition(s) noted.

1717 COMMENTS: [CR] The door jamb wasdamaged/rotted. We recommendcorrecting the condition(s) noted. [CR] The door did not latch to thejamb. We recommend correcting thecondition(s) noted.[FE] There was evidence of whatappeared to be mold/mildew present(surface). We recommend furtherevaluation and corrections by aspecialist in the appropriate trade.

ELECTRICAL SYSTEMS

The service entrance, grounding system, main and sub panels were observed to determine their current condition. Areasconcealed from view by any means are excluded from the report. Lights and accessible receptacles were checked forbasic operation. Light fixtures that have missing or dead bulbs were considered non-functioning. The location of GFCIcircuit protection devices will be identified when present. The operation of time control devices was not verified. Thelocation of smoke detectors will be identified when present. All maintenance, repairs or corrections should be made byspecialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

ELECTRICAL SERVICE INFORMATION:801 SERVICE TYPE: Overhead.

802 MAIN PANEL: Located at the left side of the building

803 SERVICE RATING: 120/240 volt system, rated at 100 Amperes

Page 14: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

804 SERVICE WIRING: Material observed: aluminum

805 BRANCH WIRING: Material observed: copper

806 DISCNNCT TYPE: Circuit breakers

807 GROUNDING: Driven rod into the earth

ELECTRICAL SERVICE CONDITIONS:808 SERVICE WIRING: The overhead service wires and weatherhead appeared to be serviceable with exceptions

noted.a. [CR] Tree branches were in contact with the overhead service entrance cables. Werecommend correcting the condition(s) noted.

809 GROUNDING: The visible ground connections appeared serviceable

810 MAIN PANEL: [RU] The circuit breakers were not labeled. We recommend they be accurately labeledto allow individual circuits to be shut off for maintenance or emergency needs.[CR] Screws were missing at the front cover of the panel. We recommend correcting thecondition(s) noted.

811 WORKMANSHIP: The wiring within the panel appeared serviceable

812 BREAKERS/WIRE: The breakers to wire connections appeared compatible where visible within the panel

HOUSEHOLD COMPONENT CONDITIONS:817 DOOR BELL: The door bell functioned when the button was operated

818 SWITCHES: Serviceable overall; deficiencies are identified in the location of the conditions

819 FIXTURES: Serviceable overall; deficiencies are identified in the location of the conditions

820 RECEPTACLES: Serviceable overall; deficiencies are identified in the location of the conditions.

823 ALARM SYSTEM: [FE] These systems are outside the scope of the inspection and are not inspected. Werecommend consulting with a specialist regarding the operation and maintenance of thissystem.

HEATING SYSTEMS

The visible areas of the furnace units, electrical and gas connections, ducting and filters were observed to determine theircurrent condition. Areas concealed from view by any means are excluded from this report. The accessible permanentlyinstalled equipment or components are checked for their basic operation. Determining the condition of heat exchangers

Page 15: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

is beyond the scope of this report. The inspector does not light pilot lights. Thermostats are not checked for calibration ortimed functions. Routine maintenance is recommended per the manufacturers specifications and operating conditions. All maintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

HEATING SYSTEM INFORMATION:901 LOCATION: The unit was located in the attic

902 MANUFACTURER: Amana

904 TYPE & FUEL: Forced air natural gas fired system

905 APPROX. BTU'S: 70-80,000 btu's

906 FILTER TYPE: Disposable

HEATING SYSTEM CONDITIONS:908 VENTING SYSTEM: The visible areas of the flue vent piping were intact and secured at the connections

909 SUPPLY PLENUM: The supply air plenum appeared serviceable

910 HEATING UNIT: The furnace was serviceable

911 COMBUSTION AIR: The combustion air supply for the furnace appeared adequate.

912 ENERGY SUPPLY: The gas shutoff valve and flexible gas connector appeared serviceable

913 BURNERS: The burner flame(s) appeared typical for this type of unit

914 HEAT EXCHANGR: [NOTE] The heat exchanger was not visible to inspect without dismantling the unit, whichis beyond the scope of the inspection.

915 BLOWER / FILTER: The blower and filter appeared serviceable with exceptions noted.a. [CR] The filter was dirty which blocks the air flow. We recommend the filter becleaned or replaced.

916 RETURN PLENUM: The return air ducting appeared serviceable

917 THERMOSTAT: The thermostat was operated and the system responded.

KITCHEN

Page 16: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

The visible areas of the walls, ceilings, floors, cabinets and counters were observed to determine their current condition. Areas concealed from view by any means are excluded from this report. The accessible doors, windows, lights,receptacles, conditioned air vents and permanently installed components or equipment were checked for basic operation. Self or continuous cleaning functions, timing devices and thermostat accuracy are not include in the inspection. Allmaintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

KITCHEN:1101 WALLS/CEILING: The visible areas of the walls and ceiling appeared serviceable

1105 WOOD FLOOR: The visible areas of the wood flooring appeared serviceable

1109 WINDOWS: The accessible window(s) were serviceable with exceptions noted.a. [FE] Condensation/stains were noted between the thermal glass panes in thewindow(s). We recommend having all of the doors and windows evaluated by a specialistin the appropriate trade.

1111 LIGHTS/FIXTURS: The light(s) were serviceable

1112 RECEPTACLES: The accessible receptacles were serviceable and GFCI protected where required

1113 CABINETS/TOPS: The cabinet(s)/ counter(s) were serviceable with exceptions noted.a. [CR] The cabinet/shelf edge tape was damaged in areas (cosmetic). We recommendcorrecting the condition(s) noted.b. [CR] The drawer fronts were loose in areas. We recommend correcting thecondition(s) noted.

1114 SINK/PLUMBING: The faucet, sink and piping were serviceable, no leakage observed

1115 DISPOSAL: The garbage disposal(s) functioned

1116 DISHWASHER: The dishwasher(s) functioned through the "Normal Cycle", no leakage observed

1118 EXHAUST VENT: The exhaust fan(s)/ light(s) functioned

Page 17: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1119 COOKTOP: Freestanding; Gas; The cooktop/rangeburners functioned with exceptionsnoted.a. [CR] The range oven and LEDpanel failed to function. Werecommend correcting the condition(s)noted.

1120 OVEN(S): Electric; The oven functioned

1121 MICROWAVE: The microwave oven functioned and heated a glass of water

1122 FILTRD WATER: [CR] The filtered water system failed to function. We recommend correcting thecondition(s) noted.

1123 INSTA HOT: [CR] The hot water dispenser failed to function during the inspection. We recommendcorrecting this condition.

1124 REFRIGERATOR: [CR] The access cover was missing at the bottom. We recommend correcting thecondition(s) noted.[CR] The refrigerator ice maker was frozen and the interior ice maker switch was in theoff position. We recommend inquiring about the condition(s) noted. We recommendcorrecting this condition.

BUILDING INTERIOR

The visible areas of the walls, ceilings, floors, cabinets and counters were observed to determine their current condition. Areas concealed from view by any means are excluded from this report. The accessible doors, windows, lights,receptacles, conditioned air vents and permanently installed components or equipment are checked for basic operation. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lightingconditions. In general almost all insulated glass window seals will fail and can fail at any time. Fireplaces with gas linesshould have the damper fixed so it will not close and the gas line should be sealed to the wall where it enters the fireplace.All fireplaces should be cleaned and inspected on a regular basis to insure safe operation. Smoke detectors should be

installed within 15 feet of all sleeping rooms, to examine or test is outside the scope of this report. We recommend olderhomes be upgraded to meet the current smoke detector installation standards for added occupant safety. Allmaintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

Page 18: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

INTERIOR ROOMS INFORMATION:1401 ROOMS INSPCTD: Bedrooms # 3, front entry living room dining room hallway and stairwell

1402 WALLS/CEILINGS: Materials: sheetrock

1403 FLOORS: Materials: wood and carpet

1405 FIREPLACES #: 1 manufactured (zero clearance) gas burning appliance

1406 SMOKE DETCTRS: Smoke detectors were noted at; hallways and bedrooms

INTERIOR ROOMS CONDITIONS:1407 COMMENTS: [FE] If the interior or sections of the home has been repainted and/or there have been

flooring changes. Each of these can remove or conceal evidence of any past conditionsthat may have been present prior to the work being done. We recommend inquiring thesellers about any past conditions that may no longer be visible. [FE] Portions of theinterior walls/closets were not visible at this time due to stored personal items, Theseareas are not included as part of this inspection. We recommend checking these areasafter the items have been removed, We recommend inquiring the sellers about any pastconditions that are not visible.

FRONT ENTRY/LIVING ROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1408 WALLS/CEILING: [CR] Moisture stains and damage werenoted on the wall(s)/ceiling at the rearwindow area. The area tested dryduring the inspection. We recommendlocating and correcting the source andany damaged materials.

Page 19: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1412 WOOD FLOOR: [CR] There were moisture stains on the wood flooring at the front window area. The areatested dry during the inspection. We recommend locating and correcting the source andany damaged materials. We recommend inquiring about the condition(s) noted.

1415 EXT DOORS: [CR] The entry push button door lock failed to function properly. We recommendcorrecting the condition(s) noted.[CR] A sight window hardware was loose. We recommend correcting the condition(s)noted.

1416 WINDOWS: [CR] The entry window cranking mechanisms cover was missing. We recommendcorrecting the condition(s) noted.[CR] The driveway side window(s) would not open. We recommend correcting thecondition(s) noted.

1419 RECEPTACLES: [CR] There was no power at the front left receptacle. We recommend correcting thecondition(s) noted.

1428 COMMENTS: [FE] There was evidence of what appeared to be mold/mildew present (rear roof/windowleak area). We recommend further evaluation and corrections by a specialist in theappropriate trade.

Page 20: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

DINING ROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage

BREAKFAST ROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1416 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1422 CABINETS/TOPS: [CR] The drawer fronts were loose in areas. We recommend correcting the condition(s)noted.

FAMILY ROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1415 EXT DOORS: [SC] The deadbolt lock in the exit door was key operated from both sides. This conditionis a safety hazard for emergency exiting. We recommend the lock be replaced with a fliplever type on the inside for emergency exiting.

HALLWAY/STAIRS:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1409 CARPET FLOOR: [CR] The carpet was soiled. We recommend correcting the condition(s) noted.

1428 COMMENTS: [FE] There was evidence of what appeared to be mold/mildew present (surface on lowercloset walls). We recommend further evaluation and corrections by a specialist in theappropriate trade.

FRONT BEDROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

Page 21: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1416 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1419 RECEPTACLES: [CR] A receptacle cover plates was missing. We recommend correcting the condition(s)noted.

1428 COMMENTS: [FE] There was evidence of whatappeared to be mold/mildew present(surface on walls). We recommendfurther evaluation and corrections by aspecialist in the appropriate trade.

Page 22: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

REAR BEDROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1414 INT DOORS: [CR] The door did not latch to the jamb. We recommend correcting the condition(s)noted.

1416 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1420 CLOSET(S): [CR] The door track was damaged/missing parts. We recommend correcting thecondition(s) noted.

MASTER BEDROOM:The visible areas of the walls, floors, doors, windows, heating/cooling, lights,receptacles,closets, smoke detectors, cabinets, sinks, hand/guard rails, stairwells andfireplaces where applicable were serviceable with no significant defects and no visiblemoisture damage with the exceptions listed below.

1408 WALLS/CEILING: [CR] Damage was noted on the entry stairway/cornerbead. We recommend correctingthe condition(s) noted.(Note) Settleing cracks were noted on the ceiling

1409 CARPET FLOOR: [CR] The carpet was soiled. We recommend correcting the condition(s) noted.

Page 23: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1415 EXT DOORS: [CR] The doors had moisturedamage/deterioration. We recommendcorrecting the condition(s) noted.[CR] The deadbolt lock failed tofunction. We recommend correctingthe condition(s) noted.[CR] The door did not latch to thejamb. We recommend correcting thecondition(s) noted.

1416 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.[CR] The front window(s) would not open. We recommend correcting the condition(s)noted.[CR] The closet window cranking mechanisms/handles were missing. We recommendcorrecting the condition(s) noted.

1420 CLOSET(S): [CR] The door knob-set was loose. We recommend correcting the condition(s) noted.[CR] The door did not latch to the jamb. We recommend correcting the condition(s)noted.

BATHROOMS

The visible areas of the walls, ceilings, floors, cabinets and counters were observed to determine their current condition. Areas concealed from view by any means are excluded from this report. The accessible doors, windows, lights,receptacles, conditioned air vents and permanently installed components or equipment are checked for basic operation. All maintenance, repairs or corrections should be made by specialist's in the appropriate trade using approved methods.

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

FRONT HALL BATH:The visible areas of the walls, floors, doors, windows, heating/cooling, lights, receptacles,vents, cabinets, sinks, toilets, tubs, showers and enclosures where applicable wereserviceable with no significant defects and no visible moisture damage with theexceptions listed below.

Page 24: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1309 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1314 CABINETS/TOPS: [CR] The cabinet/shelf edge tape was damaged in areas (cosmetic). We recommendcorrecting the condition(s) noted.

1327 TOWEL BARS: [CR] The toilet paper holder was loose. We recommend correcting the condition(s)noted.

REAR BEDROOM BATH:The visible areas of the walls, floors, doors, windows, heating/cooling, lights, receptacles,vents, cabinets, sinks, toilets, tubs, showers and enclosures where applicable wereserviceable with no significant defects and no visible moisture damage with theexceptions listed below.

1309 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1311 LIGHTS/FIXTURS: [CR] Some of the lights failed to function. We recommend correcting the condition(s)noted.

1312 RECEPTACLES: [CR] The receptacle was loose at the wall. We recommend correcting the condition(s)noted.

1315 SINK/PLUMBING: [CR] The stopper mechanism was defective/missing parts. We recommend correctingthe condition(s) noted.

1319 TUB/SHOWER: [CR] The stopper mechanism was defective. We recommend correcting the condition(s)noted.[CR] The spout was not sealed to the wallz, this is a potential leak source. Werecommend correcting this condition to prevent moisture intrusion into concealed spaces.

MASTER BATH:The visible areas of the walls, floors, doors, windows, heating/cooling, lights, receptacles,vents, cabinets, sinks, toilets, tubs, showers and enclosures where applicable wereserviceable with no significant defects and no visible moisture damage with theexceptions listed below.

Page 25: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1307 INT DOORS: [CR] The toilet room door frame wasrotted from past moisture damage. Werecommend correcting the condition(s)noted.

1309 WINDOWS: [FE] Condensation/stains were noted between the thermal glass panes in the window(s). We recommend having all of the doors and windows evaluated by a specialist in theappropriate trade.

1319 TUB/SHOWER: [SC] The hot and cold water were reversed at the faucet, this condition is a scald hazard.We recommend correcting the condition(s) noted.

1321 SHOWER: [CR] The lower bodywash head failed to function. We recommend correcting thecondition(s) noted.[CR] The handheld showerhead leaked when operated. We recommend correcting thecondition(s) noted.[CR] The grout was cracked, damaged. We recommend correcting this condition toprevent moisture intrusion into concealed spaces.

Page 26: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1322 ENCLOSURE: [SC] The shower door was contactingthe tile jamb and was chipped. Werecommend correcting the condition(s)noted.[CR] The shower enclosure fixed panelwas loose. We recommend correctingthe condition(s) noted.

LAUNDRY ROOM

LAUNDRY:1201 LOCATION: Located in an interior closet

1204 TILE FLOOR: The visible areas of the tile floor appeared serviceable

1208 INT DOORS: The door was serviceable

1217 WASHR SERVICE: [FE] The washer/dryer hookup connections were not visible due to obstructions present . We recommend inquiring about the condition(s) noted.

1218 DRYER SERVICE: [FE] The washer/dryer hookup connections were not visible due to obstructions present. We recommend inquiring about the condition(s) noted.

GARAGE - CARPORT

The visible areas of the walls, ceilings, floors, cabinets and counters were observed to determine their current condition. Areas concealed from view by any means are excluded from this report. The accessible doors, windows, lights,receptacles and permanently installed components or equipment are checked for basic operation. The garage doorbalance and spring tension should be checked regularly by a garage door specialist. All garage door openers shouldhave functional auto-reverse system safety features for child safety. All maintenance, repairs or corrections should bemade by specialist's in the appropriate trade using approved methods.

Page 27: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

[SC] Safety Concerns [FE] Further Evaluation [CR] Corrections Recommended [RU] Recommended Upgrade

GARAGE/CARPORT INFORMATION:1501 TYPE & LOCATN: Garage; detached two car.

1503 ROOF COVERING: Materials observed: built-up with a cap sheet surface

1504 ROOF LAYERS: Unknown

1507 SIDING TYPE: The same as the main structure

1509 EXT TRIM TYPE: The same as the main structure

1513 VEHICLE GARAGEDOOR(S):

Door types: wood tilt-up(s)

1515 INTERIOR WALLS: Materials: sheetrock

1516 INTERIOR FLOOR: Materials: concrete and pressboard

GARAGE/CARPORT CONDITIONS:1525 BUILT UP ROOF: [CR] Trees were touching/overhanging

the roof. We recommend they betrimmed and the debris removed toprevent damage to the roof and toprevent animal access.[CR] There were areas of the roof thatrequire maintenance. We recommendcorrecting the condition(s) noted usingapproved methods.

1527 FLASHINGS: [CR] The mastic used to seal some of the roof connections and penetrations wascracked. We recommend correcting the condition(s) noted using approved methods.

1532 DOWNSPOUTS: [CR] The downspout was missing. We recommend they be repaired and/or replaced asneeded.

Page 28: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1534 STUCCO SIDING: [CR] The stucco siding wasdamaged/improper patch at the exteriordoor. These conditions are conduciveto moisture intrusion/deterioration. Werecommend correcting the condition(s)noted.

1545 EXT DOOR: [CR] There was day light visible around the door. We recommend installing oradjusting/adding the existing weather stripping minimize moisture intrusion. Werecommend correcting the condition(s) noted.

1548 INTERIOR WALLS: [CR] Damage was noted on the officewall(s). We recommend correcting thecondition(s) noted.[CR] Moisture stains and damage werenoted on the office walls and ceiling(roof leak). The stains tested wetduring the inspection. We recommendlocating correcting the source and anydamaged materials.[CR] Moisture stains and damage werenoted on the garage wall (wall/windowleak). The stains tested wet during theinspection. We recommend locatingcorrecting the source and any damagedmaterials.[CR] There was damage/holes in thewalls. We recommend correcting thecondition(s) noted.

Page 29: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1549 GARAGE FLOOR: [FE] There were large cracks present in the slab foundation. This may be the result of movement of the building. We recommend further evaluation and corrective action by astructural and/or geotechnical engineer.

Page 30: Sample Report

This report is prepared for the client listed above in accordance with our written agreement and is subject to the terms and conditions agreed upontherein. A verbal consultation is part of this inspection. If you were not present during the inspection, call our office for a full discussion of the entire

report. Lugar Inspection Services © 2001. Lugar Inspection Services (310) 798-2411 - www.lugarinspections.com

1554 VEHICLE GARAGEDOOR:

The car door was operated and appeared serviceable. with exceptions noted.a. [CR] The car door frame was rotted. We recommend correcting the condition(s)noted.

1555 VEHICLE GARAGEDOOR OPENER:

[CR] The car door opener failed to function. We recommend correcting the condition(s)noted.

1556 LIGHTS/FIXTURS: [CR] Some of the lights failed to function. We recommend correcting the condition(s)noted.[SC] There was improper wiring in the garage/office in the form of splices in wiring thatwere not contained in approved/covered boxes We recommend correcting thecondition(s) noted.

1557 RECEPTACLES: The accessible receptacles were serviceable

1558 COMMENTS: [FE] There was evidence of what appeared to be mold/mildew present (officewalls/ceiling). We recommend further evaluation and corrections by a specialist in theappropriate trade.[FE] There was evidence of what appeared to be mold/mildew present (garage rightwall). We recommend further evaluation and corrections by a specialist in theappropriate trade.[FE] Evidence of rodent activity was observed in the garage. Werecommend a full evaluation by a specialist in the appropriate trade.