Page 1 of 17
Sample address
Inspection Type: Pre Purchase Builders Report
Name Client
Address [email protected] Phone 027xxxxxx
Date 14th May 2012 Time 130 pm Weather Fine
Persons in Attendance Inspector and Agent
Inspector Grant Bennett Phone: 021775470I hereby certify that I have carried out the inspection of the property site at the above address in accordance withNZS 4306:2005 Residential property inspection – and I am competent to undertake this inspection
Page 2 of 17
Scope: The purpose of the inspection is to identify significant Faults or defects visible at the time of the inspection. Thereporting of any significant Fault or Defect is on an exceptional basis, rather than reporting on items, which are in acceptablecondition for their age. This Inspection is strictly non invasive consisting of the building elements which could be seen easily,and does not include any item that is closed in or concealed (which could include flooring, framing, plumbing, drainage,heating, ventilation, wiring) or which required the moving of anything impeding access or limiting visibility such as (floorcoverings, furniture, appliances, personal property, vehicles, vegetation, debris or soil). The customer agrees to assume allthe risk, for any condition or problems that may be concealed at the time of the inspection. Nothing will be dismantled duringthe inspection, and there will be no destructive testing performed. We do not test appliances, therefore we are unable toreport any such items are free from defect, and no determination of their efficiency will be made. Please note that thisinspection has been conducted at a particular time of day and under those climatic conditions. Whilst we have taken everycare to comment on all aspects of the dwelling, we cannot comment on past or future events that do not occur during ourinspection. There may be some historical evidence present that we have had to make assumptions for, these areas of theproperty will be stated in the report. Any recommendations contained in the report are suggestion only and it shall be theresponsibility of the person carrying out any works to ensure the most appropriate remedy is carried out in conjunction withany further discoveries, warranty’s, manufacturers recommendations and local authority consents. We hope you have foundthe report of this property detailed and informative. The report has been formulated in this way to make for ease of reading,and for quick reference. Some photos supplied can be indicative of multiple occurrences and should not be seen in isolation.If for any reason you have been unhappy with our service, please let us know, as this is the way we can make improvements.If you have any questions after reading this report please contact us and we will be happy to discuss any items with you.
Reasonable Access: As defined by NZS4306-2005, reasonable access is areas where safe, unobstructed access isprovided and the minimum clearances specified in the table below are available, or where these clearances are not available,areas within the inspector’s unobstructed line of sight. Note: It shall be clearly stated if no access was available, or access tolimited areas only was available at the time the inspection was carried out.
Area Accessmanhole
(mm)
Crawl space(mm)
Height
Roof space 450 x 400 600 x 600 Accessible from a 3.6m ladder*
Subfloor 500 x 400 Vertical clearance Timberfloor: 400** Concretefloor: 500
Roof exterior Accessible from a 3.6m ladder*
*Or such other means of access that meet OSH requirements ** From underside of bearer
Exclusions From the Report will Include: Building codes, zoning ordinance violations, geological stability, soil conditions,structural stability, engineering analysis, termites or other infestations, asbestos, formaldehyde, water or air contaminants ofany kind, toxic moulds, rotting(non visual), electromagnetic radiation, environmental hazards, appraisal of property value,repair estimates, detached buildings, sheds, underground condition of pool and spa bodies and related piping, items markedas not inspected within the report, private water systems, septic systems, saunas, specialized electronic controls of any kind,elevators, dumb waiters, water softener and purification systems, solar systems, internal system components, securitysystems, system adequacy or efficiency, prediction of life expectancy of any item or system, minor and/or cosmetic problems,latent or concealed defects.
Disputes and Limitation on Liability: The Customer understands and agrees that any claim against the accuracy of thereport, in the form of errors or omissions is limited to the failure on the part of the inspector to follow the Standards of Practiceas outlined in the New Zealand standard-4306:2005 (a copy is held at our office for viewing if required). The customeragrees to notify the us of any dispute in written form, within ten working days of discovery. The Customer further agrees thatwith the exception of emergency conditions, no repairs, replacements or alterations of the claimed discrepancy shall be madebefore we can re-inspect the said item(s). The Customer understands and agrees that any failure to notify us as stated aboveshall constitute a waiver of any and all claims. Any claims connected with the completion of the Inspection and/or report, ourliability shall be limited to a sum that does not exceed the cost of the Inspection. We will not be liable to you for anyconsequential loss of whatever nature suffered by you or any other person. The content of the report is confidential intendedsolely for the customer and shall not be relied upon by any third parties. We accept no responsibility for anything done or notdone by any third party in reliance, whether wholly or partially, on any of the contents of the report.
Terms of trade: The Customer acknowledges that they are liable for the full cost of the Inspection and agree to payHomeCheck Wellington Ltd in full, upon delivery of the report. Delivery of the report is considered an acceptance of thiscontract. Payment terms are strictly Three(3) days. In the event of the need to recover the debt, this will include any legaland/or collection expenses that may be incurred in the recovery. Interest for the full amount of the inspection will be incurredat the rate 2% per week three(3) days from the date the report was delivered..
Page 3 of 17
MOISTUREThis was a non invasive survey. Areas of typical concern such as around windows, doors,plumbing fittings, and along exterior walls where accessible, have been scanned with an industrystandard “Protimeter” moisture meter from the interior. This is to get an idea of any moistureFluctuations, if any, within the wall framing or linings. Any Fluctuations are assessed with regardto location, level, surroundings and substrate type(s). Results are listed in each subsection in thefollowing pages. This scanning method does not constitute a weathertightness guarantee. Levelswill vary from house to house. Different locations and types of surroundings, as well as currentatmospheric conditions can all affect the moisture level within a wall from time to time.Further invasive investigation is always recommended when elevated fluctuations are found,unless indicated otherwise. An invasive survey may be able to indicate actual levels of moisture tothe timber framing, flooring and some other substrates. Safe and Dry Levels for your more modernhomes timbers are less than older homes that can have a slightly elevated reading without concern.
COUNCIL RECORDS INSPECTIONOften you are advised by your lawyer to obtain a LIM (Land Information Memorandum). This is acomputer generated print out of some of the information the council holds on file, mostlypertaining to the “Land”. If there are any known problems or unusual important features, theseshould show up. For instance the LIM might reveal the property is subject to flooding, or containsa council drain which may not be built over, or a protected tree or building. It should also help youto figure out how the district plan applies to the site. Sometimes the council will also supply pagesof area plans showing the known storm water and sewage drains, zoning and other details.
There is also something called a “Building File” held at council which contains documentsrelating to any buildings on that site. However, the council only has records of works it knowsabout. Frequently alterations have been done to older houses without council knowledge. So it is agood idea to check the council “Building File” as part of due diligence, or we can do this for youfor a small fee. Some council's also have a small fee for accessing these files.
Additions done, check for permitt /consent and compliance documents
MAINTENANCEThe current condition of a home is often only as good as it’s past maintenance. This is the singlemost important factor in a homes lifespan after the initial construction.
Past maintenance on this home appears SatisfactoryFuture maintenance expectations are in line with age and materials used (low)
Overall condition with regard to age, type and expectations of similar properties is - Average
Page 4 of 17
SITE FEATURESGROUNDS
Locale Non Coastal
Wind Zone High
Site wind Protection Reasonable from foliage and landscape
Section Slope/contour Moderate right to left
Driveway Concrete
Paths Concrete
Section Run Off Sloped toward dwelling in areas but swails anddrainage appear efficient
Stairs (External) N/A
Lawns/Gardens Over grown
Retaining Walls No concerns
Fencing N/A
FIXTURES
Garage Free standing concrete construction
Carport None
Shed Various sheds noted
TV Aerial Sky dish noted
Clothes line Extenda line
Letter box Timber type
Other exterior solar panels(not part of inspection)
no concerns
Page 5 of 17
DWELLING ENVELOPE
NZS4306:2005 WEATHERTIGHT RISK ASSESMENT
NZS4306:2005 provides a guide for weather associated moisture risks. This assessment should be considered asinformation only and does not indicate the dwelling has defects unless stated further.
Number of storeys 2 High
Wind Zone High
Roof /Wall junctions Medium
Eave width Very High to areas
Complexity High
Decking Medium
cantilevered deck joists rely onun-viewable flashings andsealants, high risk rating
lack of eaves and angledjunctions raise risk ratings
STRUCTURE
Type Single dwelling house
Design level Subject to NZS3604 and specific engineer design
Living Orientation North/East
Modifications Significant structural remoldelling noted includingupper extention
Compliance some items do not comply check all records.
Page 6 of 17
FRAMINGGenerally the majority of framing cannot be seen due to linings and assumptions are sometimes made based on
experience, any visible or known concerns will be stated
WALL FRAMING
Type Timber assumed for extensions only, majority is formedconcrete
Condition Unknown however no visible concerns
Treatment Both Herbicide and Fungicide expected
Insulation Expected Inspected while being constructed andrefurbished
ROOF FRAMING
Type Timber
Condition Average
Method Pitched roof
Treatment Unknown
Borer No visible signs
Man hole location In hallway and kitchen
Insulation Fiberglass Batts
no concerns
LIMITATIONSFraming not visible , fully lined
RECOMMENDATIONSNone
Page 7 of 17
FOUNDATIONSEXTERIOR
Type Concrete Slab
Condition Generally good
INTERIOR
Access door N/A
Type Concrete foundation as part of slab
Condition Not applicable
Joists/bearer Condition N/a
Borer N/A
Ventilation Not applicable
Ground Condition N/a
FLOORING
Type Concrete to lower level partical board to upper
Condition Appears sound, no concerns
Treatment n/a
Borer N/A
Insulation no able to sight
no view available
LIMITATIONSPercentage unviewable 100%
RECOMMENDATIONSNone
Page 8 of 17
ROOF AND FIXTURESAll roofing materials have a definitive lifespan and this is variable on a number of factors like location, design and
appropriate application as well as regular maintenancePITCHED ROOF
Type Corrugated Colour steel
Condition Average overall
FLAT ROOF
Type none
ConditionFLASHINGS
Type ColourSteel
Condition Average
Design detailing standard level, appears functional
SOFFIT/EAVES
Type and size Cement sheet Differing sizes
Condition Average
FASCIA
Type Timber
Condition Average
CHIMNEY
Type Masonry
Condition Appears sound
tape flashings on skylightconsidered temporary remedy
upper downpipe didcharges ontoflashing
sheets have minimal extensioninto gutter, see interior section
LIMITATIONSNone accessed by ladder
RECOMMENDATIONSconsider re-pitching skylight with more robust flashings and extending upper roof further into gutter.
extend downpipe with spreader past vulnerable flashing.
Page 9 of 17
CLADDINGS
Exterior claddings protect the framework and can also provide the visual appeal of the home. New Zealand homescan be clad in a vast variety of materials and combinations of them. Each cladding system has it’s pro’s and con’s
and it is recommended that you become familiar with the maintenance requirements.
Main Type Concrete walls form cladding system
Other Types Weatherboards , horizontal steel panel system
Condition Appear sound
Finishes Paint
Joinery Aluminium and PVC framed double glazed
Flashings/trims Average condition
Design detailing Weak, could contribute to moisture ingress
Comments multiple complex junctions and flashing systemsemployed make this property hard to assess
retro fitted joinery flashingsappear to rely on sealants for
weathertighness
poorly designed drip edge maypromote moisture ingress into
overhang
angled joinery not fitted withhead flashings, relies on sealant
poor cover from cut fascia fascia detailing not to bestpractice, this design requies
flashings
covered entrance not consideredweathertight
RECOMMENDATIONSkeep vigilant with maintenance especially to sealants. design changes would prove costly
Page 10 of 17
PLUMBING AND DRAINAGE
INTERNAL
Water Pipes (Condition) PVc(Average)
Hot water System (Condition)(Average) appears to be integrated into
home heating boiler
Age Of Cylinder Unknown
Waste pipes (General Condition) PVc(Average for age)
Header Tank N/a
Drainage In Ceiling N/a
EXTERNAL
Waste pipes Under Floor Buried under slab(not sighted)
Gulley Traps All appear to be in good condition
Gulley Trap Lids All appear to be good
Stormwater drains All appears to be working well
Guttering PVc and steel
Downpipes PVc
Driveway/Paving Sump Needs checking regularly
Gas Meter (Position) N/a bottle supply
Toby (Position) At front of property
gutters full drains clogged
LIMITATIONSNo pressure testing or appliance testing was undertaken as part of this visual inspection. The majority of waterpiping is installed behind lined wall cavities. We attempt to locate faulty or non-compliant elements which are
easily visible.
RECOMMENDATIONSNormal and usual maintenance keep all drains and gutters clean
Page 11 of 17
ELECTRICALNo circuit or appliance testing was undertaken. This is not a compliance certificate and can only be undertaken by
a registered electrical inspector. We are attempting to find any significant defects that are clearly visible, pleasenote most wiring is installed behind lined wall cavities and is not visible
Power Connection Overhead
Meter Board Position Inside in hallway
Condition Of Meter Board Average for age
Switch Board Fuse and Breakers on Meter board
Cabling materials Appears to be partially rewired , somerubber coated circuits appear live
rubber coated cables noted
SECURITY
Alarm System None found
Alarm Control Panel Not applicable
Exterior lights No
Security Lights No
Smoke Sensors None sighted
Security Door Locks Yes fitted to some doors
Security Window Locks None sighted
detector not installed
Page 12 of 17
INTERIOR SPACES
Floor coverings Carpet and sealed timber
Majority Walls linings Plaster board , masonry
Majority Ceiling linings Plaster board
Joinery function Good
Trims painted and stained timber
Heating ducted radiators, woodburner
Moisture fluctuations Slightly elevated
General Comments -
minor moisture stains andfluctuations noted under short
cut roofing as above
poor fitting door would suggestminor movement, no significant
concern
RECOMMENDATIONSNormal and usual maintenance
Page 13 of 17
KITCHEN
Floor coverings Cork Tiles
Walls Plaster board
Ceilings Plaster board
Heating Central Heating (radiator)
Rangehood/Extract None
Waste Disposal No waste diposal
Bench Top seals Do not appear functional
Tapware Average for age
Moisture fluctuations Acceptable around fittings
General Comments Wear and Tear in line with age
poor seal at benctop walljunction
RECOMMENDATIONSseal wall/ benchtop junction
Page 14 of 17
BATHROOM
Floor coverings Cork Tiles
Walls cement fibre sheets with timber battens, timberweatherboards
Ceilings cement fibre sheets with timber battens
Heating None
Ventilation Passive only via Window
Shower seals/linings Appear functional
Shower design over bath, relies on wel sealed tiles
Bath seals Appear functional
Vanity seals Appear functional
Toilet seals Appear functional
Tapware Average function for age
Moisture fluctuations Acceptable around fittings
General Comments Wear and Tear in line with age and high usage area
seal to skylight consistent withpast issues, see roofing
swelling around vanity appersdry at time of inspection
RECOMMENDATIONSNormal and usual maintenance , expect higher than normal due to materials used.
Page 15 of 17
LAUNDRY
Floor coverings Tiles
Walls Plaster board
Ceilings none
Ventilation No ventilation noted
Laundry Tub No tub
Tapware Not applicable
Dryer Vent None
Other Fittings cenral heating boiler
Moisture fluctuations Acceptable around fittings
General Comments low celing height noted
no concerns
RECOMMENDATIONSNormal and usual maintenance
Page 16 of 17
DECKING
Types timber and steel framed
Condition Appears sound
Design detailing Weak, could contribute to moisture ingress
Comment see below
no balustade present, does notcomply with regulations
steel structure designed byengineer
RECOMMENDATIONSNormal and usual maintenance , check compliance documentaion and engineering cerificates
Page 17 of 17
APPENDIX GALLERY
cracked glazing noted to entrycover
joinery penetration relies onsealant, however under front
entry cover
excavation around footingsappears to be remedied to good
standard, no concerns
moisture entry to garage noted,see next pic
wek design to flashings allowsmoisture into garage
partially expose vent noted,questions arise as to unviewable
flashing design
skylight installed with minimumpitch, seals under pressure.