SAFETY AND SECURITY IMPROVMENTS - PACKAGE A
KISD
3/4/2019
G0.00
B O A R D O F T R U S T E E S
PLAN NORTH
NORTH
SHEET NUMBER
SHEET DISCIPLINE TYPEDISCIPLINE
A2.01ASEQUENCE (.01 - .99......etc.)
BUILDING AREA
0 GENERAL1 SITE2 FLOOR PLANS (Note: Flip Sheets are Schedules)3 ROOF4 ENLARGED PLANS5 PLAN DETAILS6 ELEVATIONS (Exterior and Interior)7 PARTITION TYPES, WALL SECTIONS8 CASEWORK, MILLWORK9 DOORS, WINDOWS, FRAMES10 CEILINGS
G GENERALC CIVILL LANDSCAPECA SPORTSS STRUCTURALD DEMOLITIONA ARCHITECTURALM MECHANICALE ELECTRICALP PLUMBINGT TECHNOLOGYFS FOOD SERVICEAV ACOUSTICALTH THEATRICAL
TIVY HIGH SCHOOL3250 TX-534 LOOPKERRVILLE, TEXAS 78028
TOM DANIELS ELEMENTARY3250 TX-534 LOOPKERRVILLE, TEXAS 78028
TIVY EDUCATION CENTER1009 BARNETT STREETKERRVILLE, TEXAS 78028
BT WILSON 6TH GRADE305 TIVY STREETKERRVILLE, TEXAS 78028
NIMITZ ELEMENTARY100 N VALLEY VIEW DRIVEKERRVILLE, TEXAS 78028
STARKEY ELEMENTARY 1030 W MAIN STREETKERRVILLE, TEXAS 78028
TALLY ELEMENTARY1840 GOAT CREEK ROADKERRVILLE, TEXAS 78028
DISCRIPTION OF WORK
Work of this proposed Contract comprises the selective demolition of existing Security and Fire protection devices and the furnishing and installation of new and/or salvaged Security System and Fire Protection System devices and cabling in accordance with the Contract Documents.
Other
Architect
ARCHITECT PBK Architects, Inc.
MEPT
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
12:4
9:2
0 P
M
C:\U
se
rs\k
be
navid
ez\D
ocum
ents
\KIS
D_B
T W
ILS
ON
MS
_V
2.4
_A
19_
keith
.be
navid
ez.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-P
AC
KA
GE
A
100%
CD
G0.01
INDEX, GENERAL
INFORMATION
3/4/2019
18397M
KISD
100% CD
Aut
hor
Che
cker
3/4/2019
N.D. NAPKIN DISPOSAL
N.I.C. NOT IN CONTRACT
N.T.S. NOT TO SCALE
N.V. NAPKIN VENDOR
NO. NUMBER
NOM. NOMINAL
O.C. ON CENTER (S)
O.C.E.W. ON CENTER EACH WAY
O.D. OUTSIDE DIAMETER
O.F.C.I. OWNER FURNISHED, CONTRACTORINSTALLED
O.H. OPPOSITE HAND
OPNG. OPENING
OPP. OPPOSITE
P. LAM. /PLAM
PLASTIC LAMINATE
P.C. PRECAST
P.H. PAPER HOLDER
P.L. PROPERTY LINE
P.P. POWER POLE
P.W.B. PREFINISHED WALL BOARD
PL. PLATE
PLUMB. PLUMBING
PLYWD. PLYWOOD
POL. POLISHED
PR. PAIR
PREFIN. PRE-FINISHED
PT PRESSURE-TREATED
PT. POINT
PTD. PAINTED
Q.T. QUARRY TILE
R / RAD RADIUS
R.O. ROUGH OPENING
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RE. , REF. REFER TO / REFERENCE / SEE
RECP. RECEPTACLE
REINF. REINFORCE (D), (ING)
REQ'D. REQUIRED
RES. RESILIENT
REV. REVISION (S), REVISED
RF RECREATIONAL RESILIENTFLOORING
RPG. RELOCATABLE PAINTED GYPSUMBOARD
RSS. ROD STOCK AND SEALANT
S.C. SEALED CONCRETE
S.D. SOAP DISPENSER
S.N.D. SANITARY NAPKIN DISPOSAL
SCHED SCHEDULE
SCPL SOLID CORE PLASTIC LAMINATE
SECT SECTION
SHT SHEET
SIM SIMILAR
SPC SPECIAL COATING SYSTEM
SPEC SPECIFICATION (S)
SQ. SQUARE
SS / SS.STL.
STAINLESS STEEL
STL STEEL
STRUC /STRUCT
STRUCTURAL
SUSP SUSPENDED
SVDF SHEET VINYL DANCE FLOORING
SVF SHEET VINYL FLOORING
T.A.S. TEXAS ACCESSIBLITY STANDARDS(2012)
T.B. TACK BOARD
T.D.R. TOWEL DISPENSER AND RECEPTACL
T.O. TOP OF
T.O.B. TOP OF (WOOD) BLOCKING
T.O.M. TOP OF MASONRY
T.O.P. TOP OF PARAPET
T.O.S. TOP OF STEEL
T.T.D. TOILET TISSUE DISPENSER
TEL TELEPHONE
TERR TERRAZZO
THK THICK (NESS)
TYP TYPICAL
U.N.O. UNLESS NOTED OTHERWISE
UR. URINAL
V VENT
V.C.T. VINYL COMPOSITION TILE
V.I.F. VERIFY IN FIELD
VENT. VENTILATING, VENTILATED
VER. VERIFY
VERT. VERTICAL
VGB (PREFINISHED) VINYL CLAD GYPSUMBOARD
VWC VINYL WALL COVERING
W WASHING MACHINE
W.P. WATER PROOFING
W.S. WEATHERSTRIP
W.W. WATER WELL
W.W.F. WELDED WIRE FABRIC
W.W.M. WOVEN WIRE MESH
W/ WITH
WC WATER CLOSET
WD WOOD
WDW WINDOW
WT WEIGHT
A.D. AREA DRAIN
A.D.A. AMERICANS WITH DISABILITIES ACT
A.D.A. 2010 ADA STANDARDS FORACCESSIBLE DESIGN
A.D.A.A.G. AMERICANS WITH DISABILITIES ACTACCESSIBILITY GUIDELINES
A.F.F. ABOVE FINISH FLOOR
A.F.G. ABOVE FINISH GRADE
A.H.J. ATHORITY HAVING JURISDICTION
A/C AIR CONDITIONING
ACC. ACCESSIBLE, ACCESSIBILITY
ACP. ACOUSTICAL PANEL
ACT. ACOUSTICAL TILE
ADJ. ABADJUSTABLE
ALT. ALTERNATE
ALUM. ALUMINUM
ASPH. ASPHALT
ے ANGLE
B.O.D. BOTTOM OF DECK
B.U.R. BUILT-UP ROOF
BD. BOARD
BLDG. BUILDING
BLK. BLOCK
BM. BEAM
C CHANNEL
C.J. CONTROL JOINT
C.M.U. CONCRETE MASONRY UNIT
C.W. COLD WATER
CAB, CABT CABINET
CFMF COLD-FORMED METAL FRAMING
CFSF COLD-FORMED STEEL FRAMING
CL CENTERLINE
CLG. CEILING
CLR CLEAR
COL. COLUMN
COMP. COMPRESSIBLE
CONC. CONCRETE
COND. CONDITION
CONT. CONTINUOUS
CORR. CORRIDOR
CPT. CARPET (ED)
CT. CERAMIC TILE
CTSK. COUNTER SINK
D DRYER
D.F. DRINKING FOUNTAIN
D.P. DAMPPROOFING
D.S. DOWN SPOUT
DIA. DIAMETER
DIM. DIMENSION
DTL. DETAIL
DWG. DRAWING
E.J. EXPANSION JOINT
E.Q. EQUAL
EA. EACH
EDF ELECTRIC DRINKING FOUNTAIN
EL. ELEVATION (HEIGHT)
ELEC. ELECTRICAL
ELECT. ELECTRICAL
ELEV ELEVATION (DRAWING)
EQUIP EQUIPMENT
EXIST EXISTING
EXP EXPANSION
EXT EXTERIOR
F.E. FIRE EXTINGUISHER
F.E.C. FIRE EXTINGUISHER CABINET
F.H.C. FIRE HOSE CABINET
FB. FACE BRICK
FD. FLOOR DRAIN
FIN. FINISH (ED)
FIXT. FIXTURE
FLR. FLOOR (ING)
FLSHG. FLASHING
FLUOR FLUORESCENT
FRP FIBER REINFORCED PLASTIC
G.B. GRAB BAR
G.I. GALVANIZED IRON
GA. GAUGE
GALV. GALVANIZED
GCMU GLAZED CONCRETE MASONRY UNIT
GEN. GENERAL
GEN. GENERAL
GL. GLASS / GLAZING
GL. GLASS
GR. GRADE
GTP. GLAZED TILE PAVER
GWB GYPSUM WALL BOARD
GYP. GYPSUM
H.W. HOT WATER
HM HOLLOW METAL FRAME
HORIZ. HORIZONTAL
HT. HEIGHT
I.D. INSIDE DIAMETER
I.P.S. IRON PIPE SIZE
INSUL INSULATE (ED), (ION)
INT. INTERIOR
JT. JOINT
L.P. LIGHT POLE
LAM. LAMINATE (D)
LAV. LAVATORY
LT. LIGHT
LT. WT. LIGHTWEIGHT
M.O. MASONRY OPENING
MAS. MASONRY
MATL. MATERIAL (S)
MAX. MAXIMUM
MB. MARKER BOARD
MECH. MECHANICAL
MEM MEMBRANE
MEM. WP. MEMBRANE WATERPROOFING
MEP MECHANICAL, ELECTRICAL,PLUMBING
MEPT MECHANICAL, ELECTRICAL,PLUMBING, TECHNOLOGY
MEZZ. MEZZANINE
MFR. /MANUF.
MANUFACTURE (R)
MH. MANHOLE
MIN. MINIMUM
MISC. MISCELLANEOUS
MOD MODULAR
MTL METAL
MTP. METAL TOILET PARTITION
GENERAL
G0.00 COVER SHEET - TEXAS
G0.01 INDEX, GENERAL INFORMATION
ABBREVIATIONS DRAWING INDEX
SHEET NUMBERING
PROJECT LOCATION
No. Description Date
TECHNOLOGY
T1.01 NIMITZ ELEMENTARY SCHOOL - FIRE SAFETYPLAN
T1.02 STARKEY ELEMENTARY SCHOOL - FIRE SAFETYPLAN
T1.03 TIVY EDUCATION CENTER - FIRE SAFETY PLAN
T1.04 TOM DANIELS ELEMENTARY SCHOOL - FIRESAFETY PLAN
TS1.01 BT WILSON MIDDLE SCHOOL - SECURITY CAMERAPLAN
TS1.02 BT WILSON MIDDLE SCHOOL - SECURITY CAMERAPLAN - GYM
TS1.03 NIMITZ ELEMENTARY SCHOOL - SECURITYCAMERA PLAN
TS1.04 STARKEY ELEMENTARY SCHOOL - SECURITYCAMERA PLAN
TS1.05 TALLY ELEMENTARY SCHOOL - SECURITYCAMERA PLAN
TS1.06 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -FIRST FLOOR - AREA A
TS1.07 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -FIRST FLOOR - AREA B
TS1.08 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -SECOND FLOOR
TS1.09 TOM DANIELS ELEMENTARY SCHOOL - SECURITYPLAN
F
F
F
F
F
F
F
F
F
FF
F
F
F F
F
F
F
F
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP S
P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SPS
P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SPS
P
SP
SPS
P SP
SP
SP
FA
CP
CO !F
F SP
UPSP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
FFS
P
SP
SP
MDF
IDF
WP
WP
WPWP
WP
WPF5
F3
F2
F1
F4F6
F8 F7
STAIR
D228
CORRIDOR
D229
RECEPTION
D230
OFFICE
D231
Room
D232
OFFICE
D233
OFFICE
D234
OFFICE
D235CONFERENCE
D236
OFFICE
D237
Room
D238
Room
D239
RR
D240
RR
D241 BREAK
D242
Room
D243
OFFICE
D244
VEST
D245
MECH
D246
CLASS
D247
STOR
D248
RR
D249 SHWR
D250
CLASS
D251STOR
D252
STOR
D253
STOR
D254
CLASS
D255
ISO
D256
RR
D257
VEST
D258
CORRIDOR
D259
CORRIDOR
D260
MEDIA CENTER
D261
STAGE
D262
OFFICE
D263
COMP LAB
D264
LOUNGE
D265
CORRIDOR
D266
Room
D267
STOR
D268
STOR
D269RR
D270
RR
D271
OFFICE
D272ART
D273
STOR
D274
STOR
D275
VEST
D276
CAFETERIA
D277STAGE
D278
STOR
D279
STOR
D280
STOR
D281
STOR
D282
PREP
D283
STOR
D284
STOR
D285
PREP
D286
STOR
D287
RISER
D288STOR
D289RR
D290
LOCKER
D291
PREP
D292
SERVING
D293
CORRIDOR
D294
VEST
D295
RR
D296
Room
D297
VEST
D298
RR
D299
VEST
D300
ENCLOSED PLAY AREA
D301
DRESS
D302OFFICE
D303
RR
D304DRESS
D305
JAN
D306
Room
D307
MECH
D308
MENTORING CENTER
M100
IDFIDF F2
F1
F3
F4
CORRIDOR
A201
CLASSROOM
A202
CLASSROOM
A203
CLASSROOM
A204
CLASSROOM
A205
CLASSROOM
A206
CLASSROOM
A207
CLASSROOM
A208
CLASSROOM
A209
CLASSROOM
A210
CLASSROOM
A211
CLASSROOM
A212
CLASSROOM
A213
CORRIDOR
A214
JAN
A215
VEST
A216
RR
A217RR
A218
VEST
A219
FAC
A220
STORAGE
A221
CORRIDOR
B201
CLASSROOM
B202
CLASSROOM
B203
CLASSROOM
B204
CLASSROOM
B205
CLASSROOM
B206
CLASSROOM
B207
CLASSROOM
B208
CLASSROOM
B209
CLASSROOM
B210
CLASSROOM
B211
CORRIDOR
D201
JAN
D202
VEST
D203
RR
D204
FAC
D205
VEST
D206
RR
D207CLASSROOM
D208
CLASSROOM
D209
CLASSROOM
D210
CLASSROOM
D211
CLASSROOM
D212
CLASSROOM
D213
CLASSROOM
D214
CLASSROOM
D215
CLASSROOM
D216
CLASSROOM
D217
CORRIDOR
D218
CLASSROOM
D219
VEST
D220
JAN
D221
VEST
D222
RR
D223
FAC
D224
VEST
D225
RR
D226
STORAGE
D227
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
12:5
0:3
6 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- N
IMIT
Z_
R19_
acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.01
NIMITZ
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - FIRST FLOOR1
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - SECOND FLOOR2
KEYED NOTES - FIRE SAFETY PLAN
F1 MANUAL FIRE ALARM PULL STATION.
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W"INDICATES WHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATESLOCAL VOICE EVACUATION SPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUMESPEAKER FUNCTIONS, REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/ORHORN APPLICATIONS.
F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISESTANDARD RED COLOR.
F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOFDEVICE. REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORNAPPLICATIONS. A SUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TOVOICE EVAC PANEL SHALL BE PROVIDED FOR ALL LOCATIONS INDICATED.
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F"INDICATES FIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C"INDICATES RATE COMPENSATION TYPE.
F8 CARBON MONOXIDE DETECTOR.
No. Description Date
FA
CP
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
S P
F
F
F
F
F
F
F
F
F
F
FS P
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
F
F
F
F
F
F
F
F
F
!F
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
SP
CO
CO
SP
SP
5' - 0"
MDF
IDF
F1
F2
F3
F4
F5F6
WP
WP
WP
WP
WP
WP
WP
WP
WP
DRESS
A101
RR
A102DRY STO
A103
BULK STO
A104
FOOD PREP
A105OFFICE
A107
JAN
A109
REF / FZR
A106
WAREWASH
A110
SERVERY
A108
CAN WASH
A112
CAFETORIUM
A111
STAGE
A127
MUSIC
A128
RR
A129
VEST
A130
JAN
A131
RR
A132
VEST
A133
OUTSIDE STO
A114
ELEC
A115
STO
A116
MECH
A117
PAPER STO
A118
JAN
A119
RR
A120
RR
A121
DRESS
A122
DRESS
A123
OFFICE / STO
A124
STO
A125
STO
A126
ENCLOSED PLAY AREA
A135
Room
A136
ELEC
B101
STO
B102
RR
B103
RR
B104
JAN
B105WORK AREA
B106
CLASSROOM
B107
CLASSROOM
B108
Room
B109
Room
B110
CLASSROOM
B111
CLASSROOM
B112
Room
B113
Room
B114
CLASSROOM
B115
CORRIDOR
B116
ART
B118
KILN
B119
STO
B120
CORRIDOR
B121
CLASSROOM
B122
CLASSROOM
B123
CLASSROOM
B124
CLASSROOM
B125
CLASSROOM
B126
CLASSROOM
B127
CLASSROOM
B128
CLASSROOM
B129
CORRIDOR
B131
ELEC
B133
RR
B134CLINIC
B135
CORRIDOR
B136
CLASSROOM
B137
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
VEST
B142
FAC
B143
VEST
B144
RR
B145
RR
B146
VEST
B147
JAN
B148CLASSROOM
B149
CLASSROOM
B150
STO
B151
RR
B152
CLASSROOM
B153 CLASSROOM
B154
CLASSROOM
B155RR
B156
CORRIDOR
B157
TESTING
B158
STORAGE
B159 CLASSROOM
B160
CLASSROOM
B162
CLASSROOM
B163
CLASSROOM
B164
CORRIDOR
C100
OFFICE / RECEP
C101
CORRIDOR
C102
WORK ROOM
C103PRINC
C104
COUNCELOR
C105
FILES / RECORDS
C106MULTI-USE OFFICE
C107
CONFERENCE
C108
FAC WORK ROOM
C109
RR
C110
RR
C111
LOUNGE
C112
TELE
C113
TEXTBOOK STO
C114
TEACHERS LOUNGE
C115
COFFEE
C116
LOBBY
C117COMPUTER LAB
C118
Room
C119
STO
C122
CORRIDOR
C123
Room
C125
MULTI-USE
C126
MEDIA CENTER
C127
LIBRARIANS OFFICE
C128
LIBRARY STO
C129STUDY ROOM
C130
FILM VIEWING
C131
CLASSROOM
C133
CORRIDOR
C132
RR
C134
CLASSROOM
C135
CLASSROOM
C136
CLASSROOM
C137CLASSROOM
C138
CLASSROOM
C139
CLASSROOM
C140
STO
C141
STO
C142
RR
C143
WORKROOM
C144CLASSROOM
C145
CLASSROOM
C146
F5
F7
F8
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 1
2:5
3:2
0 P
M
C:\U
sers
\acru
z\D
ocum
en
ts\1
839
7M
- K
ER
RV
ILLE
- S
TA
RK
EY
_R
19
_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.02
STARKEY
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Indepenent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN1
GENERAL NOTES - FIRE SAFETY PLAN
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
KEYED NOTES - FIRE SAFETY PLAN
F1 MANUAL FIRE ALARM PULL STATION.
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W" INDICATESWHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATES LOCAL VOICE EVACUATIONSPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUME SPEAKER FUNCTIONS, REFERENCE DIV. 28SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS.
F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISE STANDARDRED COLOR.
F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOF DEVICE.REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS. ASUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TO VOICE EVAC PANEL SHALL BEPROVIDED FOR ALL LOCATIONS INDICATED.
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F" INDICATESFIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C" INDICATES RATECOMPENSATION TYPE.
F8 CARBON MONOXIDE DETECTOR.
No. Description Date
SP
SP
SP
SP
SP
SP
CLASS
115
CLASS
116
STOR
117
RR
118
CONFERENCE
119
STOR
120STOR
121
RR
122
RR
123
CORRIDOR
124
F2
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
1:0
8:4
0 P
M
C:\U
sers
\acru
z\D
ocum
ents
\1839
7M
- K
ER
RV
ILLE
- T
IVY
ED
UC
AT
ION
CE
NT
ER
_T
19_a
cru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
T1.03
TIVE EDUCATION
CENTER - FIRE
SAFETY PLAN -
AREA F
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
KEYED NOTES - FIRE SAFETY PLAN
F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATES PHOTOELECTRICTYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.
SCALE: 1/4" = 1'-0"
FIRE SAFETY PLAN - AREA F1
No. Description Date
FA
CP
FA
CP
MDF
IDF
IDF
IDF F6
MENTORING CENTER
C001
CORRIDOR
A100
CLASSROOM
A101
CLASSROOM
A102
CLASSROOM
A103
CLASSROOM
A104
CLASSROOM
A105
MEDIA CENTER
A106
WORK ROOM
A107
STORAGE
A108
VEST
A109
JAN
A110
RR
A111
RR
A112
TEXT BOOK STORAGE
A113
COMPUTER LAB
A114
CORRIDOR
B101 LOBBY
B100
GEN OFFICE
B102
CONFERENCE
B103
COUNC
B104OFFICE
B105
RECORDS
B106
NURSE
B107
RR
B108
PRINC
B109
STORAGE
B110
STAIR
B111STORAGE
B112
MECH
B113
CAFETORIUM
B114
STAGE
B125
SERVERY
B115WAREWASH
B116
REF. / FREEZER
B117
DRY STORAGE
B118
MECH
B119OFFICE
B120
FOOD PREP
B121
LOCKER
B122TOILET
B123
JAN
B124
STORAGE
B126
STAIR
B127
JAN
B128
CLASSROOM
B129
STORAGE
B131
TELE
B132
RR
B133
RR
B134
WORK ROOM
B135
WORK ROOM
B136
CLASSROOM
B137
CLASSROOM
B138
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
CLASSROOM
B142
CLASSROOM
B143
VEST
B144
RAMP
B145
Room
B146
CORRIDOR
B130
CLASSROOM
B147
Room
B148
Room
B149
Room
B150
CLASSROOM
B151
CLASSROOM
B152
CLASSROOM
B153
CLASSROOM
B154
CLASSROOM
B155
CLASSROOM
B156
CLASSROOM
B157
CLASSROOM
B158
CORRIDOR
C100
Room
C101
Room
C102
Room
C103
Room
C104
VEST
C105 FAC
C106
VEST
C107
RR
C108
JAN
C109
VEST
C110
RR
C111
ELEC
C112MECH
C113
PLAY AREA
C114
OFFICE
C115
BOYS DRESS
C116
STORAGE
C117
RR
C118
GIRLS DRESS
C119
RR
C120
STORAGE
C121
VEST
C123
ART CLASSROOM
C124
Room
C125
Room
C126
CLASSROOM
C127
RAMP
C128
VEST
C129
TESTING
C130MUSIC CLASSROOM
C131
STORAGE
C132
RAMP
C133
CORRIDOR
C134
CLASSROOM
C135RESOURCE
C136
CLASSROOM
C137
CLASSROOM
C138
VEST
C139
FAC
C140
VEST
C141 RR
C142
JAN
C143
VEST
C144
RR
C145
CORRIDOR
C146
CLASSROOM
C147
OUTDOOR STORAGE
C148
STORAGE
C149
ELEC
C150
CENTRAL STORAGE
C151
CLASSROOM
C152
CLASSROOM
C153
NEW FACP WITH FIBER COMMUNICATION ABILITIES,
TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.
EXISTING DEVICES TO BE CONNECTED TO NEW FACP.
LOCATIONOF EXISTING FIBER PAIRSTO ANNEX
IDF
F6
CLASSROOM
C154
CLASSROOM
C155
CLASSROOM
C156
CLASSROOM
C157
CLASSROOM
C158
CLASSROOM
C159
CLASSROOM
C160
CLASSROOM
C161
CLASSROOM
C162
CLASSROOM
C163
ELEC / STOR / IDF
C164
RR
C165
RR
C166
ELEC / STOR
C167
CORRIDOR
C168
VEST
C169
NEW FACP WITH FIBER COMMUNICATION ABILITIES,
TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.
EXISTING DEVICES TO BE CONNECTED TO NEW FACP.
LOCATIONOF EXISTING FIBER PAIRSTO MDF
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 1
:59:1
3 P
M
C:\U
sers
\acru
z\D
ocum
ents
\1839
7M
- K
ER
RV
ILL
E -
DA
NIE
LS
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-
PA
CK
AG
E A
100%
CD
T1.04
TOM DANIELS
ELEMENTARY
SCHOOL - FIRE
SAFETY PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN1
GENERAL NOTES - FIRE SAFETY PLAN
6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.
8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.
9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.
10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.
11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.
12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.
14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.
15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.
16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.
17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.
18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.
19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.
GENERAL NOTES - FIRE SAFETY PLAN
1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.
2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.
2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.
2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.
2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.
3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.
3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.
3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.
3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.
3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.
3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.
3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.
4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.
5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.
SCALE: 1/16" = 1'-0"
FIRE SAFETY PLAN - ANNEX2
KEYED NOTES - FIRE SAFETY PLAN
F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL
No. Description Date
E
MDF
ENTRY
100
LOBBY
100A
CORRIDOR
101
CORRIDOR
102
CORRIDOR
103
CORRIDOR
104
CORRIDOR
105
CORRIDOR
106
SPEECH
107
DIAG
108
RESOURCE
109BEHAVORIAL
110
RR
111
TIME OUT
112
ELEC
113
RR
114
COMPUTER LAB
115
LIBRARY MEDIA CENTER
116
AV STORAGE
117
OFFICE
118
WORK ROOM
119
TECH. CTR.
120
RR
121
CEI / MENTOR
122
Room
123
Room
124
COMPUTER
125RESOURCE
126
CONTENT MASTERY
127
ART
128
STORAGE
129
STORAGE
130
RR
131
RR
132
MUSIC
133
WAITING OFFICE
134
WORK ROOM
135
CONFERENCE
136
PRINC
137
COUNCEL
138
ASST PRINC
139
COOL DOWN
140
RR
141
CORRIDOR
142
EXAM
143 WAITING
144
RR
145 ISO
146
PLAY GYM
300
STORAGE
301
JAN
302
RR
303
RR
304
OFFICE
305
CAFETORIUM
306
STAGE
307
STORAGE
308
CHAIR / TABLE STORAGE
309
KITCHEN
310
JAN
311
OFFICE
312
MECH
313
STORAGE
314
RR
315
CORRIDOR
500
STORAGE
501
BOOK ROOM
502
CLASSROOM
503
CLASSROOM
504
CLASSROOM
505
CLASSROOM
506
CLASSROOM
507
CLASSROOM
508
FAC
509
STORAGE
510 RR
511STORAGE
512
JAN
513
RR
514
CLASSROOM
515
CLASSROOM
516
CLASSROOM
517
CLASSROOM
518
CORRIDOR
400
TEACHER'S BREAK ROOM
401
TEACHER'S WORK ROOM
402CLASSROOM
403
CLASSROOM
404CLASSROOM
405
CLASSROOM
406
CLASSROOM
407
CLASSROOM
408
STORAGE
409
RR
410
JAN
411
FAC
412
RR
413
ELEC
414
CLASSROOM
415
CLASSROOM
416
CLASSROOM
417
CLASSROOM
418
Room
200
READING ROOM
201
ISS
202
CLASSROOM
203
CLASSROOM
204
CLASSROOM
205
CLASSROOM
206
CLASSROOM
207
CLASSROOM
208
STORAGE
209
RR
210JAN
211
FAC
212
RR
213
ELEC
214CLASSROOM
215
CLASSROOM
216
CLASSROOM
217
CLASSROOM
218
S5
S1
PTZ
PTZ
PTZ
S7
S7
S7
S2
S1S2
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 1
:06:3
8 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- T
ALL
EY
_R
19_
acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-
PA
CK
AG
E A
100%
CD
TS1.05
TALLY
ELEMENTARY
SCHOOL-SECURITY
CAMERA PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
NEW CABLING MUST BE
PULLED TO THIS LOCATION
No. Description Date
E
E
E
E
E
IDF
E
E
IDF
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
RELOCATION M3
S6
REPLACE WITH PTZ
AND RELOCATE TO M1.
REPLACE
REPLACE
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
S4
S3
S3
S1
S5
S2
S3
S1
S1
S1
S1
S5
S5
S3
S1
S3
S4
S1
S1
S1
S5
S1
S1
S3
REPLACE
S5
S3
S3
S1
S3
S1
S1
S4
S1
S3
S4
S1
S5
S5
S7
CORRIDOR
100
CORRIDOR
101
CORRIDOR
103
CORRIDOR
104
TICK
B100
ELEC
B101ENTRY
B102
THEATER
B103
STAGE
B104
COST.
B105
OFFICE
B106
CLASS / DRESS
B107
CLASS / DRESS
B108
RAMP
B109
BOYS
B110
GIRLS
B111JAN
B112
FAC
B113
CORRIDOR
B114
BAND REHERSAL
B115
ENSEM
B116ENSEM
B117OFFICE
B118
LIBR
B119
HALL
B120
PERCUSS
B121
ENSEM
B122
STAGE BAND
B123
COLOR GAURD
B124P
B125
P
B126
UNIF
B127
ENSEM
B128OFFICE
B129
LIBR
B130
UNIF
B131
CHORAL REHERSAL
B132
EQUIP
B133P
B134
P
B135
DARK
B136
STOR
B137
COMP
B138
PHOTO JOURNALISM
B140
OFFICE
B141
P
B142
DARK
B143
ART STUDIO LAB
B144
COMP
B145
STOR
B146
STOR
B147
OFFICE
B148
ART STUDIO LAB
B149
HALL
B150
OFFICE
B151
STOR
B152
KILN
B153
OFFICE
C100
DANCE / DRILL TEAM
C101
DRILL
C102A
DANCE
C102B
CHEER
C103
GIRLS
C104
CONC.
C105
LOBBY
C106
STOR
C107
BOYS
C108
CORRIDOR
C109
CORRIDOR
C110
MAIN GYM
C111
PRACTICE GYM
C112
Room
C113
CLASS
C114
MECH
C115
STAIRS
C116STOR
C117
GIRLS LOCKER
C118
SHWR
C119TLT
C120
STOR
C121
TLT
C122
SHWR
C123
DRY
C123A
BOYS LOCKERS
C124
LAUNDRY
C125
STAIRS
C126
Room
C127
Room
C128
COACHES
C129
OFFICE
C130OFFICE
C131OFFICE
C132 OFFICE
C133
OFFICE
C134
WET
C135
TRAINING
C136STOR
C137
MECH / STOR
C138
WEIGHT RM
C139
CORRIDOR
C140
FOOTBALL
C141
SHWR
C142
DRY
C142A
TLT
C143
COACHES
C144
TLT
C145
A.D.
C146
SEC
C147
RECEP
D100
SEC
D101
ATTEND
D102
HALL
D103
A.P.
D104
A.P.
D105
A.P.
D106
A.P.
D107
SEC
D108
HALL
D109
Room
D110
RECEP
D111
PRINC
D112
LG. CONF
D113
CONF
D114
V
D115
TLT
D116
TLT
D117
I.S.S.
D118
OFFICE
D118A
CORRIDOR
D119
Room
D120
CLASS
D121
CLASS
D122
CORRIDOR
D123
CLASS
D124
CLASS
D125
CLASS
D126
PLANNING
D127
CORRIDOR
D128
PLANNING
D129
CLASS
D130
COMPUTER / KEYBOARDING
D131
COMPUTER / KEYBOARDING
D132
COMPUTER / KEYBOARDING
D133
COMPUTER / KEYBOARDING
D134
COMPUTER / KEYBOARDING
D135
COMPUTER / KEYBOARDING
D136
COMPUTER PLANNING
D137
GIRLS
D138
BOYS
D139
JAN
D140
FAC
D141
CORRIDOR
D142
CLASS
D143
CLASS
D144
Room
D145
RESOURCE COMPUTER LAB
D146
ELC
D148
COPY CENTER
D149
Room
D120ARoom
D120B
FUNCTIONAL LIVING LAB
A100
SEVER & PROFOUND
A101
RR
A102
STOR
A101A
Room
A118
HEALTH COUNC
A119 OFFICE
A120
WORK
A121
RR
A122
COUNS
A123
COUNS
A124
CORRIDOR
A125 REGISTR
A126
WAIT / RECEP
A127
COUNS
A128
COUNS
A129
CORRIDOR
A131
VAULT
A132
BOOK ROOM
A156
RELOCATE
PTZ
S1
PTZ
S7
REPLACE
S6
REPLACE
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
3:1
2:0
1 P
M
C:\U
sers
\she
ivly
\Docum
ents
\18397
M -
KE
RR
VIL
LE
- T
I VY
-HS
_R
19_
sheiv
ly.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.06
TIVY HIGH SCHOOL
SECURITY CAMERA
PLAN - FIRST
FLOOR - AREA A
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - FIRST FLOOR - AREA A1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.
S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.
S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.
S6 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO BE REPLACED.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
No. Description Date
E
E
IDF
E
E
E
E
E
E
E
E
E
EE
IDF IDF-(MEZZ.)
E
E
E
MDF
E
E
E
E
RELOCATION M2
RELOCATION M1
S6
S6
S6
REPLACE WITH PTZ AND RELOCATE EXISTING TO M2
RELOCATE EXISTING TO M3 S1
S1
S1
S3
S3
S3
S4
REPLACE
S1
S1
S1
S3
REPLACE
S1
S4
S3
S3
S3
S6
S5
S3
S3
S1
S1
S1
S3
S3
S2
S6
S7
S7
REPLACE
S4S5
CORRIDOR
105
CORRIDOR
106
C.T. DIRECTOR
F100SEC
F101
PLANNING
F102
TLT
F103
STOR
F104P.R.
F105
OFFICE
F106
HEALTH OCCUPATIONS
F107
TLT
F108
STOR
F109
OFFICE
F110
CLASS
F111
COMMERCIAL KITCHEN LAB
F112
Room
F113
Room
F114
CORRIDOR
F115
CORRIDOR
F116
MAIN MECHANICAL BOILER
ROOM
F117
CENTRAL STOR
F118
AUTO MECHANICS
F119
CLASS
F120
OFFICE
F121
TOOLS
F122
STOR
F123
CLASS
F124
OFFICE
F125
STOR
F126
BUILDING TRADES /
CONSTRUCTION MFG.
F127
CLASS
F128
OFFICE
F129
STOR
F130
INDUSTRIAL / MODULAR
TECHNOLOGY
F131
CLASS
F132
OFFICE
F133CLASS
F134
TLT
F135
STOR
F136
VOC. AG / HORTICULTURE
F137
STOR
F138
CORRIDOR
G100
ELEC
G101
Room
G102
CLASS
G103
CLASS
G104
CORRIDOR
G105
CLASS
G106
CLASS
G107
CLASS
G108
CLASS
G109
CORRIDOR
G110
CLASS
G111
CLASS
G112CLASS
G113
Room
G114
CORRIDOR
G115
MARKETING CLASSROOM
G116
STOR
G117
OFFICE
G118
CLASS
G119
Room
G120
Room
G121
Room
G122
Room
G123
COMPUTER / KEYBOARDING
G124
RR
A102ED
A103
ED
A104
ED
A105
ED
A106
ED
A107
ED
A108
CLASS
A109
OFFLINE
A110
STOR
A111
OFFICE
A112
STUDIO
A113
P.E.S.
A114
STUDIO
A115
STUDIO
A116
TECH
A117
COUNS
A129
COUNS
A130
CORRIDOR
A131
VAULT
A132
COUNS
A133
CARRERS LAB
A134
CORRIDOR
A138
ENTRY
A139
COMPUTER RESOURCE LAB
A140
WORK RM
A141
OFFICE
A142
A.V.
A143
LIBRARY MEDIA CENTER
READING ROOM
A144
DISTANCE LEARNING LAB
A145
COMPUTER RESOUCE
A146
D
A147
D
A148
DEBATE
A149
STOR
A150
BOYS
A151
GIRLS
A152
FAC
A153
JAN
A154
TEACHER WORK RM.
A155
TEACHER BREAK / LUNCH
E123
P
E116
TLT
E125
TLT
E124
SCIENCE
E120
STOR
E105
FAMILY & CONSUMER
TECHNOLOGY
E118
STOR
E121
STOR
E122
DINING
E100
KITCHEN
E127
S7
PTZ
PTZ
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
S7
PTZ
REPLACE
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
3:1
2:0
3 P
M
C:\U
sers
\she
ivly
\Docum
ents
\18397
M -
KE
RR
VIL
LE
- T
I VY
-HS
_R
19_
sheiv
ly.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.07
TIVY HIGH SCHOOLSECURITY CAMERA
PLAN - FIRSTFLOOR - AREA B
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - FIRST FLOOR - AREA B1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.
S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.
S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.
S6 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO BE REPLACED.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
No. Description Date
E
E
E
E
E
E
E
E
E
IDF(MEZZ.)
IDF
CLASS
K212
PLANNING
K211
CLASS
K210
CLASS
K209
CLASS
K207
CLASS
K206
CLASS
K205
COMPUTER RESOURCE
K203
PHYSICS LAB
K202
SCIENCE EQUIP / PREP
K202A
CLASS
K213
CLASS
K215
CLASS
K216
CLASS
K220
CLASS
K221
CLASS
K222
CLASS
K223
CLASS
K224
GIRLS
K225
JAN
K226
FAC
K227
BOYS
K228
PLANNING
K201
SPEC ED
K200
Room
K234
Room
K233
Room
K232
CLASS
K231
CLASS
K230
MECH MEZZ
K235
REPLACE
S3
S1
S1
S4
S3
S1
S1
S1
S3
S4
REPLACE
REPLACE
REPLACE
S4
S1
S3
S4
S1
S1
S1
S1
INSIDE ELEVATOR,REQUIRES TRAVELING CABLE AND ELEVATOR CONTRACTOR COORDINATION.
CORRIDOR
H200
ELEC
H201
CLASS
H202
CLASS
H203
PLANNING
H204
CLASS
H205
CLASS
H206
CLASS
H207
CLASS
H208
CORRIDOR
H209
CLASS
H210CLASS
H211CLASS
H212
Room
H213
CORRIDOR
H214
PLANNING
H215
CLASS
H216CLASS
H217
CLASS
H218
CLASS
H219
BOYS
H220
TLT
H221
JAN
H222
CORRIDOR
H223
GIRLS
H224
CORRIDOR
J201
ELEV
J202 BIOLOGY CLASS
J203 BIOLOGY LAB
J204
BIOLOGY CLASS
J205
IPC CLASS
J206
IPC LAB
J207
Room
J208
IPC CLASS
J209
Room
J210
IPC CLASS
J211IPC LAB
J212IPC CLASS
J213
CHEMESTRY LAB
J214
CHEMESTRY LAB
J215
STOR
J216
CORRIDOR
K204
CORRIDOR
K208
CORRIDOR
K214
CORRIDOR
K202E
CLASS
K218
CLASS
K219
MECH
J200
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 1
:40:4
9 P
M
C:\U
sers
\acru
z\D
ocum
en
ts\1
839
7M
- K
ER
RV
ILLE
- T
IVY
-HS
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.08
TIVY HIGH SCHOOLSECURITY CAMERA
PLAN - SECONDFLOOR
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
SCALE: 1" = 20'-0"
SECURITY CAMERA PLAN - SECOND FLOOR1
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.
S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.
No. Description Date
M
M
M
M
M
M
M
M
MM
M
M
IDF
IDF
IDF
MDF
MENTORING CENTER
C001
CORRIDOR
A100
CLASSROOM
A101
CLASSROOM
A102
CLASSROOM
A103
CLASSROOM
A104
CLASSROOM
A105
MEDIA CENTER
A106
WORK ROOM
A107
STORAGE
A108
VEST
A109
JAN
A110
RR
A111
RR
A112
TEXT BOOK STORAGE
A113
COMPUTER LAB
A114
CORRIDOR
B101
LOBBY
B100
GEN OFFICE
B102
CONFERENCE
B103
COUNC
B104OFFICE
B105RECORDS
B106
NURSE
B107
RR
B108
PRINC
B109
STORAGE
B110
STAIR
B111
STORAGE
B112
MECH
B113
CAFETORIUM
B114
STAGE
B125
SERVERY
B115
WAREWASH
B116
REF. / FREEZER
B117
DRY STORAGE
B118
MECH
B119
OFFICE
B120
FOOD PREP
B121
LOCKER
B122TOILET
B123JAN
B124
STORAGE
B126
STAIR
B127
JAN
B128
CLASSROOM
B129
STORAGE
B131
TELE
B132
RR
B133
RR
B134
WORK ROOM
B135
WORK ROOM
B136
CLASSROOM
B137
CLASSROOM
B138
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
CLASSROOM
B142
CLASSROOM
B143
VEST
B144
RAMP
B145
Room
B146
CORRIDOR
B130
CLASSROOM
B147
Room
B148
Room
B149
Room
B150
CLASSROOM
B151
CLASSROOM
B152
CLASSROOM
B153
CLASSROOM
B154
CLASSROOM
B155
CLASSROOM
B156
CLASSROOM
B157
CLASSROOM
B158
CORRIDOR
C100
Room
C101
Room
C102
Room
C103
Room
C104
VEST
C105 FAC
C106
VEST
C107
RR
C108
JAN
C109
VEST
C110
RR
C111
ELEC
C112 MECH
C113
PLAY AREA
C114
OFFICE
C115
BOYS DRESS
C116
STORAGE
C117
RR
C118
GIRLS DRESS
C119
RR
C120
STORAGE
C121
VEST
C123
ART CLASSROOM
C124
Room
C125
Room
C126
CLASSROOM
C127
RAMP
C128
VEST
C129
TESTING
C130
MUSIC CLASSROOM
C131
STORAGE
C132
RAMP
C133
CORRIDOR
C134
CLASSROOM
C135RESOURCE
C136
CLASSROOM
C137
CLASSROOM
C138
VEST
C139
FAC
C140
VEST
C141
RR
C142
JAN
C143
VEST
C144
RR
C145
CORRIDOR
C146
CLASSROOM
C147
OUTDOOR STORAGE
C148
STORAGE
C149
ELEC
C150
CENTRAL STORAGE
C151
CLASSROOM
C152
CLASSROOM
C153
S2
PTZPTZ
PTZ
KP
KP
KP
E
E
E
E
E
S7
S7S7
S11
S11
S11
S11 S12
S13
S13
S9S8
S8?
S8
S9
S8
S2
CLASSROOM
C154
CLASSROOM
C155
CLASSROOM
C156
CLASSROOM
C157
CLASSROOM
C158
CLASSROOM
C159
CLASSROOM
C160
CLASSROOM
C161
CLASSROOM
C162
CLASSROOM
C163
ELEC / STOR / IDF
C164
RR
C165
RR
C166
ELEC / STOR
C167
CORRIDOR
C168VEST
C169S1
PTZ
S7
KP S13
S10
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 2
:02:3
5 P
M
C:\U
sers
\acru
z\D
ocum
ents
\1839
7M
- K
ER
RV
ILL
E -
DA
NIE
LS
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VM
EN
TS
-
PA
CK
AG
E A
100%
CD
TS1.09
TOM DANIELS
ELEMENTARY
SCHOOL -
SECURITY PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY PLAN1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
SCALE: 1/16" = 1'-0"
FIRST FLOOR - SECURITY PLAN - ANNEX2
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
S8 INDICATES THE LOCATION FOR A NEW WALL MOUNTED MOTION DETECTOR.
S9 INDICATES THE LOCATION FOR A NEW CEILING MOUNTED LONG RANGE MOTION DETECTOR.
S10 INDICATES THE LOCATION FOR A NEW CEILING MOUNTED 360-DEGREE LONG RANGE MOTION
DETECTOR.
S11 INDICATES THE LOCATION FOR AN EXISTING MOTION DETECTOR.
S12 INDICATES THE LOCATION FOR AN EXISTING SECURITY KEY PAD.
S13 INDICATES THE LOCATION FOR A NEW SECURITY KEY PAD.
No. Description Date
E
E
E
E
RELOCATE TO CENTER
OF CORRIDORR
BACK TO BACK
E
E
IDF
IDFIDF
CORRIDOR
A100
CORRIDOR
A101
CORRIDOR
A102
CORRIDOR
A103
DINING
A104
STAGE
A105
DRESSING
A106
RR
A107
DRESSING
A108
RR
A109
SS RESOURCE
A110
STORAGE
A111
ELEV
A112
MECH
A113
READING
A114
ART
A115
STORAGE
A116
OFFICE
A117
KILN
A118
STOR / ELEC
A119
RR
A120
VEST
A121
JAN
A122VEST
A123
RR
A124
STAIR
A125
STORAGE
A126
SCULLERY
A127
SERVICE
A128
DRY STORAGE
A130
COLD STORAGE
A131
COLD STORAGE
A132 WASH
A133
JAN
A134
VEST
A135
RR
A136
Room
A129
SPEECH
A137
SPEECH
A138SP ED
A139SP ED
A140
SP ED
A141
STORAGE
A142
RR
A143
?
?OFFICE
A146
CORRIDOR
B100
CORRIDOR
B101
CORRIDOR
B102
RESOURCE MATERIAL
B103
RR
B104
RR
B106
JAN
B105
ENGLISH
B107
ENGLISH
B108
ENGLISH
B109
ENGLISH
B110
ENGLISH
B111
GEN OFFICE
B112
ASST PRIN
B113
PRIN
B114
COUNC
B115
RECEPT
B116 CLOSET
B117LOUNGE
B118
CONFERENCE
B119
WORK ROOM
B120
FIRE STORAGE
B121
NURSE
B122RR
B123
LIB STORAGE / MDF
B124
LIB
B125
OFFICE
B126TEACH WORK ROOM
B127
RR
B128
RR
B129BOOK STORAGE
B130
SS
B131SS
B132
SS
B133 SS
B134SS
B135
VEST
B136
BAND HALL
B137
INSTRU. STORAGE
B138
Room
B139
PRAC
B140
PRAC
B141
PRAC
B142
PRAC
B143
PRAC
B144
PRAC
B145
PRAC
B146
PRAC
B147
PRAC
B148
Room
B149
ENSEM
B150
OFFICE
B151
LIB
B152
STAIR
B153
CHOIR HALL
B154
OFFICE
B155
WK RM.
B156
ENG. RES. RM
B157
Room
B158
Room
B159
S3
S3
S3
S3
S3
S3
S1
S7
PTZ
PTZ
S7
S7
S2
S1
PTZ S7
ORCHESTRA O100
RELOCATE TO COVER RESTROOM ENTRANCES
E
E
E
RELOCATE TO COVER ELEVATOR
MDF
Room
A200
VEST
A202
RR
A203
BK RM
A204
CLASSROOM
A205
CLASSROOM
A206
CLASSROOM
A207CLASSROOM
A208
CLASSROOM
A209
CLASSROOM
A210
CLASSROOM
A211
CLASSROOM
A212
CLASSROOM
A213
CLASSROOM
A214
CLASSROOM
A215
CLASSROOM
A216
VEST
A217
RR
A218
ELECTRICAL
A219
JAN
A220
CORRIDOR
B200
Room
B201 MATH CLASSROOM
B202
MATH CLASSROOM
B203
MATH CLASSROOM
B204
MATH CLASSROOM
B205MATH CLASSROOM
B206
MATH CLASSROOM
B207
STORAGE / ELEC
B208SCIENCE
B209PREP
B210SCIENCE
B211
SCIENCE
B212PREP
B213
SCIENCE
B214
S3
S3
S3
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
1:2
0:0
1 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- B
T W
ILS
ON
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.01
BT WILSON MIDDLE
SCHOOL -
SECURITY CAMERA
PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - FIRST FLOOR1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - SECOND FLOOR2
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
No. Description Date
S1
S2
S2
NOTE: THERE IS ONE OUTDOOR CAMERA TO BE ADDED TO THE OUTSIDE
OF THE STAFF DEVELOPMENT BUILDING TO COVER THE
COURTYARD BEHIND THE GYM.
IDF
LOCKER
118
Room
122
Room
119
VEST
117Room
117A
GYM
120
WEIGHT ROOM
115
Room
114A
VEST
114
LOCKER
113
Room
121
Room
124
Room
125
Room
126
Room
129
Room
130
Room
127
Room
128
Room
131
Room
132
Room
133
Room
134
Room
135Room
139
Room
138
Room
137
Room
136
Room
123
Room
140
Room
141
STAFF DEVELOPMENT
S100
S2
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
1:2
3:0
3 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- B
T W
ILS
ON
_R
19_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.02
BT WILSON MIDDLE
SCHOOL -
SECURITY CAMERA
PLAN - GYM
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1" = 10'-0"
SECURITY CAMERA PLAN - GYM1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
No. Description Date
UP
IDF
MDF
PTZ
S7
S1
S2
PTZ
S7
S2
S1
S1
STAIR
D228
CORRIDOR
D229
RECEPTION
D230
OFFICE
D231
Room
D232
OFFICE
D233
OFFICE
D234
OFFICE
D235CONFERENCE
D236
OFFICE
D237
Room
D238
Room
D239
RR
D240
RR
D241 BREAK
D242
Room
D243
OFFICE
D244
VEST
D245
MECH
D246
CLASS
D247
STOR
D248
RR
D249 SHWR
D250
CLASS
D251STOR
D252
STOR
D253
STOR
D254
CLASS
D255
ISO
D256
RR
D257
VEST
D258
CORRIDOR
D259
CORRIDOR
D260
MEDIA CENTER
D261
STAGE
D262
OFFICE
D263
COMP LAB
D264
LOUNGE
D265
CORRIDOR
D266
Room
D267
STOR
D268
STOR
D269RR
D270
RR
D271
OFFICE
D272ART
D273
STOR
D274
STOR
D275
VEST
D276
CAFETERIA
D277STAGE
D278
STOR
D279
STOR
D280
STOR
D281
STOR
D282
PREP
D283
STOR
D284
STOR
D285
PREP
D286
STOR
D287
RISER
D288STOR
D289RR
D290
LOCKER
D291
PREP
D292
SERVING
D293
CORRIDOR
D294
VEST
D295
RR
D296
Room
D297
VEST
D298
RR
D299
VEST
D300
ENCLOSED PLAY AREA
D301
DRESS
D302OFFICE
D303
RR
D304DRESS
D305
JAN
D306
Room
D307
MECH
D308
CORRIDOR
A201
CLASSROOM
A202
CLASSROOM
A203
CLASSROOM
A204
CLASSROOM
A205
CLASSROOM
A206
CLASSROOM
A207
CLASSROOM
A208
CLASSROOM
A209
CLASSROOM
A210
CLASSROOM
A211
CLASSROOM
A212
CLASSROOM
A213
CORRIDOR
A214
JAN
A215
VEST
A216
RR
A217
RR
A218
VEST
A219
FAC
A220
STORAGE
A221
CORRIDOR
B201
CLASSROOM
B202
CLASSROOM
B203
CLASSROOM
B204
CLASSROOM
B205
CLASSROOM
B206
CLASSROOM
B207
CLASSROOM
B208
CLASSROOM
B209
CLASSROOM
B210
CLASSROOM
B211
CORRIDOR
D201
JAN
D202
VEST
D203
RR
D204
FAC
D205
VEST
D206
RR
D207
CLASSROOM
D208
CLASSROOM
D209
CLASSROOM
D210
CLASSROOM
D211
CLASSROOM
D212
CLASSROOM
D213
CLASSROOM
D214
CLASSROOM
D215
CLASSROOM
D216
CLASSROOM
D217
CORRIDOR
D218
CLASSROOM
D219
VEST
D220
JAN
D221
VEST
D222
RR
D223
FAC
D224
VEST
D225
RR
D226
STORAGE
D227
IDF IDF
S7
S1
PTZ
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
3/1
/2019
12:4
4:0
5 P
M
C:\U
sers
\acru
z\D
ocum
ents
\18
397M
- K
ER
RV
ILLE
- N
IMIT
Z_
R19_
acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.03
NIMITZ
ELEMENTARY
SCHOOL-SECURITY
CAMERA PLAN
03/04/2019
18397M
Kerrville Independent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - FIRST FLOOR1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
SCALE: 1/16" = 1'-0"
SECURITY CAMERA PLAN - SECOND FLOOR2
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
No. Description Date
E
IDF
MDF
DRESS
A101
RR
A102DRY STO
A103
BULK STO
A104
FOOD PREP
A105OFFICE
A107
JAN
A109
REF / FZR
A106
WAREWASH
A110
SERVERY
A108
CAN WASH
A112
CAFETORIUM
A111
STAGE
A127
MUSIC
A128
RR
A129
VEST
A130
JAN
A131
RR
A132
VEST
A133
OUTSIDE STO
A114
ELEC
A115
STO
A116
MECH
A117
PAPER STO
A118JAN
A119
RR
A120
RR
A121
DRESS
A122
DRESS
A123
OFFICE / STO
A124
STO
A125
STO
A126
ENCLOSED PLAY AREA
A135
Room
A136
ELEC
B101
STO
B102
RR
B103
RR
B104
JAN
B105WORK AREA
B106
CLASSROOM
B107
CLASSROOM
B108
Room
B109
Room
B110
CLASSROOM
B111
CLASSROOM
B112
Room
B113
Room
B114
CLASSROOM
B115
CORRIDOR
B116
ART
B118
KILN
B119
STO
B120
CORRIDOR
B121
CLASSROOM
B122
CLASSROOM
B123
CLASSROOM
B124
CLASSROOM
B125
CLASSROOM
B126
CLASSROOM
B127
CLASSROOM
B128
CLASSROOM
B129
CORRIDOR
B131
ELEC
B133
RR
B134
CLINIC
B135
CORRIDOR
B136
CLASSROOM
B137
CLASSROOM
B139
CLASSROOM
B140
CLASSROOM
B141
VEST
B142
FAC
B143
VEST
B144
RR
B145
RR
B146
VEST
B147
CLASSROOM
B149
CLASSROOM
B150
STO
B151
RR
B152
CLASSROOM
B153 CLASSROOM
B154
CLASSROOM
B155RR
B156
CORRIDOR
B157
TESTING
B158
STORAGE
B159
CLASSROOM
B160
CLASSROOM
B162
CLASSROOM
B163
CLASSROOM
B164
CORRIDOR
C100
OFFICE / RECEP
C101CORRIDOR
C102
WORK ROOM
C103PRINC
C104
COUNCELOR
C105
FILES / RECORDS
C106
MULTI-USE OFFICE
C107
CONFERENCE
C108
FAC WORK ROOM
C109
RR
C110
RR
C111
LOUNGE
C112
TELE
C113
TEXTBOOK STO
C114
TEACHERS LOUNGE
C115
COFFEE
C116
LOBBY
C117COMPUTER LAB
C118
Room
C119
STO
C122
CORRIDOR
C123
Room
C125
MULTI-USE
C126
MEDIA CENTER
C127
LIBRARIANS OFFICE
C128
LIBRARY STO
C129STUDY ROOM
C130
FILM VIEWING
C131
CLASSROOM
C133
CORRIDOR
C132
RR
C134
CLASSROOM
C135
CLASSROOM
C136
CLASSROOM
C137
CLASSROOM
C138
CLASSROOM
C139
CLASSROOM
C140
STO
C141
STO
C142
RR
C143
WORKROOM
C144
CLASSROOM
C145
CLASSROOM
C146
S7
S3
PTZ
PTZ
RELOCATE
BACK-TO-BACK
S7
S1
S2
S2
LICENSED
PRO
FESS IONAL ENGIN
EER
STATE OF TEXAS
F-18672
LEAF ENGINEERS
DONALD C. RICHARDS
61525
Other
Architect
CIVIL
ARCHITECT PBK Architects, Inc.
LANDSCAPE NAME
STRUCTURAL NAME
MEPT
FOOD SERVICE NAME
ACOUSTICAL NAME
THEATRICAL NAME
DATE
PROJECT NUMBER
CLIENT
REVISIONS
SAN ANTONIO601 N.W. Loop 410, Suite 400
San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608
PBK.com
DR
AW
N B
Y:
CH
EC
KE
D B
Y:
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
ADDRESSADDRESS
012-345-6789 P 012-345-6789 F
601 N.W. Loop 410, Suite 400San Antonio, TX 78216
210-638-7200 P 210-829-0578 FTX Firm: F-18672
LEAFE N G I N E E R S
A COMPANYPBK
2/2
8/2
01
9 1
2:5
3:2
1 P
M
C:\U
sers
\acru
z\D
ocum
en
ts\1
839
7M
- K
ER
RV
ILLE
- S
TA
RK
EY
_R
19
_acru
z.r
vt
100%
CD
SA
FE
TY
AN
D S
EC
UR
ITY
IMP
RO
VE
ME
NT
S -
PA
CK
AG
E A
100%
CD
TS1.04
STARKEY
ELEMENTARY
SCHOOL-SECURITY
CAMERA PLAN
03/04/2019
18397M
Kerrville Indepenent School District
100% CD
AN
TH
ON
Y C
RU
ZG
RE
G G
RIF
FIN
03/04/2019
SCALE: 1/16" = 1'-0"
SECURITY PLAN1
GENERAL NOTES - SECURITY PLAN
1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS
SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE
FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"
2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE
FLEXIBILITY OF CAMERA POSITION AND LOCATION.
3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED
TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.
4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO
COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR
CONDUITS ARE REQUIRED.
5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE
DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND
INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.
KEYED NOTES - SECURITY PLAN
S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.
S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.
S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.
S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.
No. Description Date