SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9...

15
OWNER KISD DR. MARK FOUST 1009 BARNETT ST KERRVILLE, TX 78028 830 - 257 - 2200 P ARCHITECT PBK ARCHITECTS 601 N.W. LOOP 410 SUITE 400 SAN ANTONIO, TX 78216 210 - 829 - 0123 P 210 - 829 - 0578 F MEPT LEAF ENGINEERS 601 N.W. LOOP 410 SUITE 400 SAN ANTONIO, TX 78216 210 - 638 - 7200 P 210 - 829 - 0578 F PRESIDENT DAVID SPROUSE, M.D. VICE PRESIDENT JACK M STEVENS, JR. SECRETARY ROLINDA SCHMIDT TRUSTEE CURTIS FINLEY TRUSTEE PATRICK FREEDLE TRUSTEE ANDREE HAYES TRUSTEE MARTY LENARD SAFETY AND SECURITY IMPROVMENTS - PACKAGE A KISD 3/4/2019 G0.00 B O A R D O F T R U S T E E S

Transcript of SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9...

Page 1: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

OWNER

KISDDR. MARK FOUST 1009 BARNETT STKERRVILLE, TX 78028830-257-2200 P

ARCHITECT

PBK ARCHITECTS601 N.W. LOOP 410SUITE 400SAN ANTONIO, TX 78216210-829-0123 P210-829-0578 F

MEPT

LEAF ENGINEERS601 N.W. LOOP 410SUITE 400SAN ANTONIO, TX 78216210-638-7200 P210-829-0578 F

PRESIDENT

DAVID SPROUSE, M.D.

VICE PRESIDENT

JACK M STEVENS, JR.

SECRETARY

ROLINDA SCHMIDT

TRUSTEE

CURTIS FINLEY

TRUSTEE

PATRICK FREEDLE

TRUSTEE

ANDREE HAYES

TRUSTEE

MARTY LENARD

SAFETY AND SECURITY IMPROVMENTS - PACKAGE A

KISD

3/4/2019

G0.00

B O A R D O F T R U S T E E S

Page 2: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

PLAN NORTH

NORTH

SHEET NUMBER

SHEET DISCIPLINE TYPEDISCIPLINE

A2.01ASEQUENCE (.01 - .99......etc.)

BUILDING AREA

0 GENERAL1 SITE2 FLOOR PLANS (Note: Flip Sheets are Schedules)3 ROOF4 ENLARGED PLANS5 PLAN DETAILS6 ELEVATIONS (Exterior and Interior)7 PARTITION TYPES, WALL SECTIONS8 CASEWORK, MILLWORK9 DOORS, WINDOWS, FRAMES10 CEILINGS

G GENERALC CIVILL LANDSCAPECA SPORTSS STRUCTURALD DEMOLITIONA ARCHITECTURALM MECHANICALE ELECTRICALP PLUMBINGT TECHNOLOGYFS FOOD SERVICEAV ACOUSTICALTH THEATRICAL

TIVY HIGH SCHOOL3250 TX-534 LOOPKERRVILLE, TEXAS 78028

TOM DANIELS ELEMENTARY3250 TX-534 LOOPKERRVILLE, TEXAS 78028

TIVY EDUCATION CENTER1009 BARNETT STREETKERRVILLE, TEXAS 78028

BT WILSON 6TH GRADE305 TIVY STREETKERRVILLE, TEXAS 78028

NIMITZ ELEMENTARY100 N VALLEY VIEW DRIVEKERRVILLE, TEXAS 78028

STARKEY ELEMENTARY 1030 W MAIN STREETKERRVILLE, TEXAS 78028

TALLY ELEMENTARY1840 GOAT CREEK ROADKERRVILLE, TEXAS 78028

DISCRIPTION OF WORK

Work of this proposed Contract comprises the selective demolition of existing Security and Fire protection devices and the furnishing and installation of new and/or salvaged Security System and Fire Protection System devices and cabling in accordance with the Contract Documents.

Other

Architect

ARCHITECT PBK Architects, Inc.

MEPT

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

12:4

9:2

0 P

M

C:\U

se

rs\k

be

navid

ez\D

ocum

ents

\KIS

D_B

T W

ILS

ON

MS

_V

2.4

_A

19_

keith

.be

navid

ez.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VM

EN

TS

-P

AC

KA

GE

A

100%

CD

G0.01

INDEX, GENERAL

INFORMATION

3/4/2019

18397M

KISD

100% CD

Aut

hor

Che

cker

3/4/2019

N.D. NAPKIN DISPOSAL

N.I.C. NOT IN CONTRACT

N.T.S. NOT TO SCALE

N.V. NAPKIN VENDOR

NO. NUMBER

NOM. NOMINAL

O.C. ON CENTER (S)

O.C.E.W. ON CENTER EACH WAY

O.D. OUTSIDE DIAMETER

O.F.C.I. OWNER FURNISHED, CONTRACTORINSTALLED

O.H. OPPOSITE HAND

OPNG. OPENING

OPP. OPPOSITE

P. LAM. /PLAM

PLASTIC LAMINATE

P.C. PRECAST

P.H. PAPER HOLDER

P.L. PROPERTY LINE

P.P. POWER POLE

P.W.B. PREFINISHED WALL BOARD

PL. PLATE

PLUMB. PLUMBING

PLYWD. PLYWOOD

POL. POLISHED

PR. PAIR

PREFIN. PRE-FINISHED

PT PRESSURE-TREATED

PT. POINT

PTD. PAINTED

Q.T. QUARRY TILE

R / RAD RADIUS

R.O. ROUGH OPENING

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RE. , REF. REFER TO / REFERENCE / SEE

RECP. RECEPTACLE

REINF. REINFORCE (D), (ING)

REQ'D. REQUIRED

RES. RESILIENT

REV. REVISION (S), REVISED

RF RECREATIONAL RESILIENTFLOORING

RPG. RELOCATABLE PAINTED GYPSUMBOARD

RSS. ROD STOCK AND SEALANT

S.C. SEALED CONCRETE

S.D. SOAP DISPENSER

S.N.D. SANITARY NAPKIN DISPOSAL

SCHED SCHEDULE

SCPL SOLID CORE PLASTIC LAMINATE

SECT SECTION

SHT SHEET

SIM SIMILAR

SPC SPECIAL COATING SYSTEM

SPEC SPECIFICATION (S)

SQ. SQUARE

SS / SS.STL.

STAINLESS STEEL

STL STEEL

STRUC /STRUCT

STRUCTURAL

SUSP SUSPENDED

SVDF SHEET VINYL DANCE FLOORING

SVF SHEET VINYL FLOORING

T.A.S. TEXAS ACCESSIBLITY STANDARDS(2012)

T.B. TACK BOARD

T.D.R. TOWEL DISPENSER AND RECEPTACL

T.O. TOP OF

T.O.B. TOP OF (WOOD) BLOCKING

T.O.M. TOP OF MASONRY

T.O.P. TOP OF PARAPET

T.O.S. TOP OF STEEL

T.T.D. TOILET TISSUE DISPENSER

TEL TELEPHONE

TERR TERRAZZO

THK THICK (NESS)

TYP TYPICAL

U.N.O. UNLESS NOTED OTHERWISE

UR. URINAL

V VENT

V.C.T. VINYL COMPOSITION TILE

V.I.F. VERIFY IN FIELD

VENT. VENTILATING, VENTILATED

VER. VERIFY

VERT. VERTICAL

VGB (PREFINISHED) VINYL CLAD GYPSUMBOARD

VWC VINYL WALL COVERING

W WASHING MACHINE

W.P. WATER PROOFING

W.S. WEATHERSTRIP

W.W. WATER WELL

W.W.F. WELDED WIRE FABRIC

W.W.M. WOVEN WIRE MESH

W/ WITH

WC WATER CLOSET

WD WOOD

WDW WINDOW

WT WEIGHT

A.D. AREA DRAIN

A.D.A. AMERICANS WITH DISABILITIES ACT

A.D.A. 2010 ADA STANDARDS FORACCESSIBLE DESIGN

A.D.A.A.G. AMERICANS WITH DISABILITIES ACTACCESSIBILITY GUIDELINES

A.F.F. ABOVE FINISH FLOOR

A.F.G. ABOVE FINISH GRADE

A.H.J. ATHORITY HAVING JURISDICTION

A/C AIR CONDITIONING

ACC. ACCESSIBLE, ACCESSIBILITY

ACP. ACOUSTICAL PANEL

ACT. ACOUSTICAL TILE

ADJ. ABADJUSTABLE

ALT. ALTERNATE

ALUM. ALUMINUM

ASPH. ASPHALT

ے ANGLE

B.O.D. BOTTOM OF DECK

B.U.R. BUILT-UP ROOF

BD. BOARD

BLDG. BUILDING

BLK. BLOCK

BM. BEAM

C CHANNEL

C.J. CONTROL JOINT

C.M.U. CONCRETE MASONRY UNIT

C.W. COLD WATER

CAB, CABT CABINET

CFMF COLD-FORMED METAL FRAMING

CFSF COLD-FORMED STEEL FRAMING

CL CENTERLINE

CLG. CEILING

CLR CLEAR

COL. COLUMN

COMP. COMPRESSIBLE

CONC. CONCRETE

COND. CONDITION

CONT. CONTINUOUS

CORR. CORRIDOR

CPT. CARPET (ED)

CT. CERAMIC TILE

CTSK. COUNTER SINK

D DRYER

D.F. DRINKING FOUNTAIN

D.P. DAMPPROOFING

D.S. DOWN SPOUT

DIA. DIAMETER

DIM. DIMENSION

DTL. DETAIL

DWG. DRAWING

E.J. EXPANSION JOINT

E.Q. EQUAL

EA. EACH

EDF ELECTRIC DRINKING FOUNTAIN

EL. ELEVATION (HEIGHT)

ELEC. ELECTRICAL

ELECT. ELECTRICAL

ELEV ELEVATION (DRAWING)

EQUIP EQUIPMENT

EXIST EXISTING

EXP EXPANSION

EXT EXTERIOR

F.E. FIRE EXTINGUISHER

F.E.C. FIRE EXTINGUISHER CABINET

F.H.C. FIRE HOSE CABINET

FB. FACE BRICK

FD. FLOOR DRAIN

FIN. FINISH (ED)

FIXT. FIXTURE

FLR. FLOOR (ING)

FLSHG. FLASHING

FLUOR FLUORESCENT

FRP FIBER REINFORCED PLASTIC

G.B. GRAB BAR

G.I. GALVANIZED IRON

GA. GAUGE

GALV. GALVANIZED

GCMU GLAZED CONCRETE MASONRY UNIT

GEN. GENERAL

GEN. GENERAL

GL. GLASS / GLAZING

GL. GLASS

GR. GRADE

GTP. GLAZED TILE PAVER

GWB GYPSUM WALL BOARD

GYP. GYPSUM

H.W. HOT WATER

HM HOLLOW METAL FRAME

HORIZ. HORIZONTAL

HT. HEIGHT

I.D. INSIDE DIAMETER

I.P.S. IRON PIPE SIZE

INSUL INSULATE (ED), (ION)

INT. INTERIOR

JT. JOINT

L.P. LIGHT POLE

LAM. LAMINATE (D)

LAV. LAVATORY

LT. LIGHT

LT. WT. LIGHTWEIGHT

M.O. MASONRY OPENING

MAS. MASONRY

MATL. MATERIAL (S)

MAX. MAXIMUM

MB. MARKER BOARD

MECH. MECHANICAL

MEM MEMBRANE

MEM. WP. MEMBRANE WATERPROOFING

MEP MECHANICAL, ELECTRICAL,PLUMBING

MEPT MECHANICAL, ELECTRICAL,PLUMBING, TECHNOLOGY

MEZZ. MEZZANINE

MFR. /MANUF.

MANUFACTURE (R)

MH. MANHOLE

MIN. MINIMUM

MISC. MISCELLANEOUS

MOD MODULAR

MTL METAL

MTP. METAL TOILET PARTITION

GENERAL

G0.00 COVER SHEET - TEXAS

G0.01 INDEX, GENERAL INFORMATION

ABBREVIATIONS DRAWING INDEX

SHEET NUMBERING

PROJECT LOCATION

No. Description Date

TECHNOLOGY

T1.01 NIMITZ ELEMENTARY SCHOOL - FIRE SAFETYPLAN

T1.02 STARKEY ELEMENTARY SCHOOL - FIRE SAFETYPLAN

T1.03 TIVY EDUCATION CENTER - FIRE SAFETY PLAN

T1.04 TOM DANIELS ELEMENTARY SCHOOL - FIRESAFETY PLAN

TS1.01 BT WILSON MIDDLE SCHOOL - SECURITY CAMERAPLAN

TS1.02 BT WILSON MIDDLE SCHOOL - SECURITY CAMERAPLAN - GYM

TS1.03 NIMITZ ELEMENTARY SCHOOL - SECURITYCAMERA PLAN

TS1.04 STARKEY ELEMENTARY SCHOOL - SECURITYCAMERA PLAN

TS1.05 TALLY ELEMENTARY SCHOOL - SECURITYCAMERA PLAN

TS1.06 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -FIRST FLOOR - AREA A

TS1.07 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -FIRST FLOOR - AREA B

TS1.08 TIVY HIGH SCHOOL - SECURITY CAMERA PLAN -SECOND FLOOR

TS1.09 TOM DANIELS ELEMENTARY SCHOOL - SECURITYPLAN

Page 3: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

F

F

F

F

F

F

F

F

F

FF

F

F

F F

F

F

F

F

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP S

P

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SPS

P

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SPS

P

SP

SPS

P SP

SP

SP

FA

CP

CO !F

F SP

UPSP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

FFS

P

SP

SP

MDF

IDF

WP

WP

WPWP

WP

WPF5

F3

F2

F1

F4F6

F8 F7

STAIR

D228

CORRIDOR

D229

RECEPTION

D230

OFFICE

D231

Room

D232

OFFICE

D233

OFFICE

D234

OFFICE

D235CONFERENCE

D236

OFFICE

D237

Room

D238

Room

D239

RR

D240

RR

D241 BREAK

D242

Room

D243

OFFICE

D244

VEST

D245

MECH

D246

CLASS

D247

STOR

D248

RR

D249 SHWR

D250

CLASS

D251STOR

D252

STOR

D253

STOR

D254

CLASS

D255

ISO

D256

RR

D257

VEST

D258

CORRIDOR

D259

CORRIDOR

D260

MEDIA CENTER

D261

STAGE

D262

OFFICE

D263

COMP LAB

D264

LOUNGE

D265

CORRIDOR

D266

Room

D267

STOR

D268

STOR

D269RR

D270

RR

D271

OFFICE

D272ART

D273

STOR

D274

STOR

D275

VEST

D276

CAFETERIA

D277STAGE

D278

STOR

D279

STOR

D280

STOR

D281

STOR

D282

PREP

D283

STOR

D284

STOR

D285

PREP

D286

STOR

D287

RISER

D288STOR

D289RR

D290

LOCKER

D291

PREP

D292

SERVING

D293

CORRIDOR

D294

VEST

D295

RR

D296

Room

D297

VEST

D298

RR

D299

VEST

D300

ENCLOSED PLAY AREA

D301

DRESS

D302OFFICE

D303

RR

D304DRESS

D305

JAN

D306

Room

D307

MECH

D308

MENTORING CENTER

M100

IDFIDF F2

F1

F3

F4

CORRIDOR

A201

CLASSROOM

A202

CLASSROOM

A203

CLASSROOM

A204

CLASSROOM

A205

CLASSROOM

A206

CLASSROOM

A207

CLASSROOM

A208

CLASSROOM

A209

CLASSROOM

A210

CLASSROOM

A211

CLASSROOM

A212

CLASSROOM

A213

CORRIDOR

A214

JAN

A215

VEST

A216

RR

A217RR

A218

VEST

A219

FAC

A220

STORAGE

A221

CORRIDOR

B201

CLASSROOM

B202

CLASSROOM

B203

CLASSROOM

B204

CLASSROOM

B205

CLASSROOM

B206

CLASSROOM

B207

CLASSROOM

B208

CLASSROOM

B209

CLASSROOM

B210

CLASSROOM

B211

CORRIDOR

D201

JAN

D202

VEST

D203

RR

D204

FAC

D205

VEST

D206

RR

D207CLASSROOM

D208

CLASSROOM

D209

CLASSROOM

D210

CLASSROOM

D211

CLASSROOM

D212

CLASSROOM

D213

CLASSROOM

D214

CLASSROOM

D215

CLASSROOM

D216

CLASSROOM

D217

CORRIDOR

D218

CLASSROOM

D219

VEST

D220

JAN

D221

VEST

D222

RR

D223

FAC

D224

VEST

D225

RR

D226

STORAGE

D227

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

12:5

0:3

6 P

M

C:\U

sers

\acru

z\D

ocum

ents

\18

397M

- K

ER

RV

ILLE

- N

IMIT

Z_

R19_

acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

T1.01

NIMITZ

ELEMENTARY

SCHOOL - FIRE

SAFETY PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

GENERAL NOTES - FIRE SAFETY PLAN

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.

2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.

2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.

2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.

2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.

3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.

3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.

3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.

3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.

3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.

3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.

3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.

4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.

5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.

6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.

7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.

8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.

9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.

10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.

11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.

12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.

14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.

15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.

16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.

17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.

18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.

19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.

SCALE: 1/16" = 1'-0"

FIRE SAFETY PLAN - FIRST FLOOR1

SCALE: 1/16" = 1'-0"

FIRE SAFETY PLAN - SECOND FLOOR2

KEYED NOTES - FIRE SAFETY PLAN

F1 MANUAL FIRE ALARM PULL STATION.

F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.

F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W"INDICATES WHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATESLOCAL VOICE EVACUATION SPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUMESPEAKER FUNCTIONS, REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/ORHORN APPLICATIONS.

F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISESTANDARD RED COLOR.

F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOFDEVICE. REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORNAPPLICATIONS. A SUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TOVOICE EVAC PANEL SHALL BE PROVIDED FOR ALL LOCATIONS INDICATED.

F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL

F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F"INDICATES FIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C"INDICATES RATE COMPENSATION TYPE.

F8 CARBON MONOXIDE DETECTOR.

No. Description Date

Page 4: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

FA

CP

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

S P

F

F

F

F

F

F

F

F

F

F

FS P

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

F

F

F

F

F

F

F

F

F

!F

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

CO

CO

SP

SP

5' - 0"

MDF

IDF

F1

F2

F3

F4

F5F6

WP

WP

WP

WP

WP

WP

WP

WP

WP

DRESS

A101

RR

A102DRY STO

A103

BULK STO

A104

FOOD PREP

A105OFFICE

A107

JAN

A109

REF / FZR

A106

WAREWASH

A110

SERVERY

A108

CAN WASH

A112

CAFETORIUM

A111

STAGE

A127

MUSIC

A128

RR

A129

VEST

A130

JAN

A131

RR

A132

VEST

A133

OUTSIDE STO

A114

ELEC

A115

STO

A116

MECH

A117

PAPER STO

A118

JAN

A119

RR

A120

RR

A121

DRESS

A122

DRESS

A123

OFFICE / STO

A124

STO

A125

STO

A126

ENCLOSED PLAY AREA

A135

Room

A136

ELEC

B101

STO

B102

RR

B103

RR

B104

JAN

B105WORK AREA

B106

CLASSROOM

B107

CLASSROOM

B108

Room

B109

Room

B110

CLASSROOM

B111

CLASSROOM

B112

Room

B113

Room

B114

CLASSROOM

B115

CORRIDOR

B116

ART

B118

KILN

B119

STO

B120

CORRIDOR

B121

CLASSROOM

B122

CLASSROOM

B123

CLASSROOM

B124

CLASSROOM

B125

CLASSROOM

B126

CLASSROOM

B127

CLASSROOM

B128

CLASSROOM

B129

CORRIDOR

B131

ELEC

B133

RR

B134CLINIC

B135

CORRIDOR

B136

CLASSROOM

B137

CLASSROOM

B139

CLASSROOM

B140

CLASSROOM

B141

VEST

B142

FAC

B143

VEST

B144

RR

B145

RR

B146

VEST

B147

JAN

B148CLASSROOM

B149

CLASSROOM

B150

STO

B151

RR

B152

CLASSROOM

B153 CLASSROOM

B154

CLASSROOM

B155RR

B156

CORRIDOR

B157

TESTING

B158

STORAGE

B159 CLASSROOM

B160

CLASSROOM

B162

CLASSROOM

B163

CLASSROOM

B164

CORRIDOR

C100

OFFICE / RECEP

C101

CORRIDOR

C102

WORK ROOM

C103PRINC

C104

COUNCELOR

C105

FILES / RECORDS

C106MULTI-USE OFFICE

C107

CONFERENCE

C108

FAC WORK ROOM

C109

RR

C110

RR

C111

LOUNGE

C112

TELE

C113

TEXTBOOK STO

C114

TEACHERS LOUNGE

C115

COFFEE

C116

LOBBY

C117COMPUTER LAB

C118

Room

C119

STO

C122

CORRIDOR

C123

Room

C125

MULTI-USE

C126

MEDIA CENTER

C127

LIBRARIANS OFFICE

C128

LIBRARY STO

C129STUDY ROOM

C130

FILM VIEWING

C131

CLASSROOM

C133

CORRIDOR

C132

RR

C134

CLASSROOM

C135

CLASSROOM

C136

CLASSROOM

C137CLASSROOM

C138

CLASSROOM

C139

CLASSROOM

C140

STO

C141

STO

C142

RR

C143

WORKROOM

C144CLASSROOM

C145

CLASSROOM

C146

F5

F7

F8

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 1

2:5

3:2

0 P

M

C:\U

sers

\acru

z\D

ocum

en

ts\1

839

7M

- K

ER

RV

ILLE

- S

TA

RK

EY

_R

19

_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

T1.02

STARKEY

ELEMENTARY

SCHOOL - FIRE

SAFETY PLAN

03/04/2019

18397M

Kerrville Indepenent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

FIRE SAFETY PLAN1

GENERAL NOTES - FIRE SAFETY PLAN

6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.

7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.

8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.

9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.

10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.

11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.

12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.

14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.

15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.

16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.

17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.

18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.

19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.

GENERAL NOTES - FIRE SAFETY PLAN

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.

2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.

2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.

2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.

2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.

3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.

3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.

3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.

3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.

3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.

3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.

3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.

4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.

5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.

KEYED NOTES - FIRE SAFETY PLAN

F1 MANUAL FIRE ALARM PULL STATION.

F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATESPHOTOELECTRIC TYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.

F3 COMBINATION SPEAKER OR HORN AND STROBE IN SINGLE COVER. SUBSCRIPT "W" INDICATESWHITE FINISH; OTHERWISE STANDARD RED COLOR. "V" INDICATES LOCAL VOICE EVACUATIONSPEAKER FUNCTIONS, "H" INDICATES HIGH VOLUME SPEAKER FUNCTIONS, REFERENCE DIV. 28SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS.

F4 VISUAL ALARM STROBE. SUBSCRIPT "W" INDICATES WHITE FINISH; OTHERWISE STANDARDRED COLOR.

F5 FIRE ALARM SPEAKER OR HORN. SUBSCRIPT "WP" INDICATES WEATHER PROOF DEVICE.REFERENCE DIV. 28 SPECIFICATIONS FOR SPEAKER AND/OR HORN APPLICATIONS. ASUBSCRIPT "S" INDICATES THAT A SPEAKER STROBE TIED TO VOICE EVAC PANEL SHALL BEPROVIDED FOR ALL LOCATIONS INDICATED.

F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL

F7 HEAT DETECTOR; COMBINATION RATE OF RISE AND FIXED TEMPERATURE. "F" INDICATESFIXED TEMPERATURE ONLY; "R" INDICATES RATE OF RISE ONLY. "C" INDICATES RATECOMPENSATION TYPE.

F8 CARBON MONOXIDE DETECTOR.

No. Description Date

Page 5: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

SP

SP

SP

SP

SP

SP

CLASS

115

CLASS

116

STOR

117

RR

118

CONFERENCE

119

STOR

120STOR

121

RR

122

RR

123

CORRIDOR

124

F2

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

1:0

8:4

0 P

M

C:\U

sers

\acru

z\D

ocum

ents

\1839

7M

- K

ER

RV

ILLE

- T

IVY

ED

UC

AT

ION

CE

NT

ER

_T

19_a

cru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

T1.03

TIVE EDUCATION

CENTER - FIRE

SAFETY PLAN -

AREA F

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

GENERAL NOTES - FIRE SAFETY PLAN

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.

2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.

2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.

2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.

2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.

3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.

3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.

3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.

3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.

3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.

3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.

3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.

4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.

5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.

6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.

7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.

8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.

9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.

10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.

11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.

12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.

14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.

15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.

16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.

17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.

18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.

19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.

KEYED NOTES - FIRE SAFETY PLAN

F2 SMOKE DETECTOR. NO SUBSCRIPT INDICATES IONIZATION TYPE; "P" INDICATES PHOTOELECTRICTYPE; "D" INDICATES DUCT TYPE AND PHOTOELECTRIC.

SCALE: 1/4" = 1'-0"

FIRE SAFETY PLAN - AREA F1

No. Description Date

Page 6: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

FA

CP

FA

CP

MDF

IDF

IDF

IDF F6

MENTORING CENTER

C001

CORRIDOR

A100

CLASSROOM

A101

CLASSROOM

A102

CLASSROOM

A103

CLASSROOM

A104

CLASSROOM

A105

MEDIA CENTER

A106

WORK ROOM

A107

STORAGE

A108

VEST

A109

JAN

A110

RR

A111

RR

A112

TEXT BOOK STORAGE

A113

COMPUTER LAB

A114

CORRIDOR

B101 LOBBY

B100

GEN OFFICE

B102

CONFERENCE

B103

COUNC

B104OFFICE

B105

RECORDS

B106

NURSE

B107

RR

B108

PRINC

B109

STORAGE

B110

STAIR

B111STORAGE

B112

MECH

B113

CAFETORIUM

B114

STAGE

B125

SERVERY

B115WAREWASH

B116

REF. / FREEZER

B117

DRY STORAGE

B118

MECH

B119OFFICE

B120

FOOD PREP

B121

LOCKER

B122TOILET

B123

JAN

B124

STORAGE

B126

STAIR

B127

JAN

B128

CLASSROOM

B129

STORAGE

B131

TELE

B132

RR

B133

RR

B134

WORK ROOM

B135

WORK ROOM

B136

CLASSROOM

B137

CLASSROOM

B138

CLASSROOM

B139

CLASSROOM

B140

CLASSROOM

B141

CLASSROOM

B142

CLASSROOM

B143

VEST

B144

RAMP

B145

Room

B146

CORRIDOR

B130

CLASSROOM

B147

Room

B148

Room

B149

Room

B150

CLASSROOM

B151

CLASSROOM

B152

CLASSROOM

B153

CLASSROOM

B154

CLASSROOM

B155

CLASSROOM

B156

CLASSROOM

B157

CLASSROOM

B158

CORRIDOR

C100

Room

C101

Room

C102

Room

C103

Room

C104

VEST

C105 FAC

C106

VEST

C107

RR

C108

JAN

C109

VEST

C110

RR

C111

ELEC

C112MECH

C113

PLAY AREA

C114

OFFICE

C115

BOYS DRESS

C116

STORAGE

C117

RR

C118

GIRLS DRESS

C119

RR

C120

STORAGE

C121

VEST

C123

ART CLASSROOM

C124

Room

C125

Room

C126

CLASSROOM

C127

RAMP

C128

VEST

C129

TESTING

C130MUSIC CLASSROOM

C131

STORAGE

C132

RAMP

C133

CORRIDOR

C134

CLASSROOM

C135RESOURCE

C136

CLASSROOM

C137

CLASSROOM

C138

VEST

C139

FAC

C140

VEST

C141 RR

C142

JAN

C143

VEST

C144

RR

C145

CORRIDOR

C146

CLASSROOM

C147

OUTDOOR STORAGE

C148

STORAGE

C149

ELEC

C150

CENTRAL STORAGE

C151

CLASSROOM

C152

CLASSROOM

C153

NEW FACP WITH FIBER COMMUNICATION ABILITIES,

TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.

EXISTING DEVICES TO BE CONNECTED TO NEW FACP.

LOCATIONOF EXISTING FIBER PAIRSTO ANNEX

IDF

F6

CLASSROOM

C154

CLASSROOM

C155

CLASSROOM

C156

CLASSROOM

C157

CLASSROOM

C158

CLASSROOM

C159

CLASSROOM

C160

CLASSROOM

C161

CLASSROOM

C162

CLASSROOM

C163

ELEC / STOR / IDF

C164

RR

C165

RR

C166

ELEC / STOR

C167

CORRIDOR

C168

VEST

C169

NEW FACP WITH FIBER COMMUNICATION ABILITIES,

TO BE INSTALLED AND CONNECTED VIA EXISTING FIBER.

EXISTING DEVICES TO BE CONNECTED TO NEW FACP.

LOCATIONOF EXISTING FIBER PAIRSTO MDF

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 1

:59:1

3 P

M

C:\U

sers

\acru

z\D

ocum

ents

\1839

7M

- K

ER

RV

ILL

E -

DA

NIE

LS

_R

19_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VM

EN

TS

-

PA

CK

AG

E A

100%

CD

T1.04

TOM DANIELS

ELEMENTARY

SCHOOL - FIRE

SAFETY PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

FIRE SAFETY PLAN1

GENERAL NOTES - FIRE SAFETY PLAN

6. ALL EQUIPMENT AND WORK PERFORMED SHALL COMPLY WITH ALL OF THE CURRENT ANDAPPLICABLE CODES, RULES, ORDINANCES, REGULATIONS, AND STANDARDS AS INTERPRETED ANDENFORCED BY THE AUTHORITIES HAVING JURISDICTION.

7. PROVIDE POWER FOR REMOTE BATTERY SUPPLIES AND BOOSTER PANELS AS NEEDED. FIRE ALARMCONTRACTOR TO COORDINATE WITH ELECTRICAL CONTRACTOR FOR CIRCUIT.

8. ALL FIRE ALARM WIRING SHALL ROUTE DOWN CORRIDORS AND WALKWAYS PARALLEL ANDPERPENDICULAR TO BUILDING WALLS.

9. ALL FIRE ALARM CABLING SHALL BE SUPPORTED IN DEDICATED CABLE SUPPORTS. DO NOT ROUTE INOR TIE-WRAP DIRECTOR TO THE BUILDING'S STRUCTURE.

10. ALL NOTIFICATION APPLIANCE CIRCUIT CABLES SHALL HAVE A YELLOW OUTER JACKET. ALL OTHERFIRE ALARM SYSTEM CABLE SHALL HAVE A RED OUTER JACKET.

11. ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ANY CONDUITS AND/OR BOXES REQUIREDFOR THE INSTALLATION FIRE ALARM DEVICES.

12. PROVIDE AND INSTALL PROTECTIVE BUSHINGS ON ALL STUB-OUTS AND SLEEVES TO PREVENTCABLE DAMAGE. BUSHINGS TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHINGAND INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

13. PROVIDE AND INSTALL STOPPER II PROTECTIVE COVERS WITH A LOCAL ALARM FOR ALL MANUALPULL STATIONS ON THE ENTIRE PROJECT.

14. CONTRACTOR TO PROVIDE AND INSTALL DUCT DETECTORS ON ALL AHU AND OAHU AS REQUIRED BYCODE. REFERENCE MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND QUANTITIES.

15. CONTRACTOR TO PROVIDE CEILING MOUNTED LED NOTIFICATION DEVICES FOR ALL DUCTDETECTORS THAT ARE MOUNTED ABOVE CEILING AND/OR IN LOCATIONS NOT VISIBLE FROM THEFLOOR.

16. ALL FIRE ALARM DEVICES ARE NEW UNLESS NOTED OTHERWISE. CONTRACTOR TO CONNECT NEWDEVICES TO NEW FIRE ALARM PANEL AND CONFIGURE PANEL FOR NEW DEVICES AND LAYOUT.

17. TESTING OF THE FIRE ALARM SYSTEM SHALL BE PERFORMED PRIOR TO THE COMMENCEMENT OFANY PHASE OF WORK ON THIS PROJECT. UPON COMPLETION OF THE SYSTEM'S TESTING, THECONTRACTOR SHALL ISSUE A FORMAL DOCUMENT THAT STATES NO ISSUES WERE FOUND. IF ANYPORTION OF ANY SYSTEM WERE FOUND TO BE NON-FUNCTIONAL OR FUNCTIONING IMPROPERLY,THE CONTRACTOR SHALL NOTE EACH ITEM, ITS LOCATION, AND A DETAILED DESCRIPTION OF THEISSUE. IF ANY WORK IS CONDUCTED PRIOR TO THE SYSTEMS' TESTING, THE CONTRACTOR WILLASSUME ALL RESPONSIBILITY FOR ANY SYSTEM REPAIRS, WHERE ISSUES ARE DISCOVERED UPONCOMPLETION OF THE PROJECT, REPLACEMENT AND OR REPAIRS TO WILL BE AT NO ADDITIONALCOST TO THE PROJECT OR THE OWNER.

18. ANY DEVICE WITH A SUBSCRIP (E) INDICATES AND EXISTING DEVICE. DEVICE TO REMAIN UNLESSOTHERWISE NOTED ON PLANS.

19. CONTRACTOR SHALL PROVIDE ALL MATERIALS REQUIRED TO CONNECT EXISTING FIRE ALARMSYSTEM TO NEW FIRE ALARM SYSTEM TO BE INSTALLED.

GENERAL NOTES - FIRE SAFETY PLAN

1. ALL 120V POWER REQUIRED FOR THE FUNCTIONALITY OF THE FIRE ALARM SYSTEMS SHALL BE ADEDICATED CIRCUIT AND 0N EMERGENCY POWER WHEN AVAILABLE. THE INSTALLING CONTRACTOROF EACH SYSTEM SHALL BE RESPONSIBLE FOR PROVIDING THEIR OWN 120V POWER REQUIREMENTSFOR ALL REMOTE POWER SUPPLIES. THE INSTALLING CONTRACTORS LICENSED ELECTRICALSUBCONTRACTOR SHALL COORDINATE ELECTRICAL PANEL LOCATIONS AND AVAILABLE SPACEDEDICATED FOR THE CONTRACTOR'S SYSTEM REQUIREMENTS. (TYPICAL). PROJECTS ELECTRICAL

CONTRACTOR SHALL BE RESPONSIBLE FOR ALL POWER TOMAIN CONTROL PANELS AND ALL HEADEND EQUIPMENT. SYSTEM INSTALLERS SHALL COORDINATE LOCATION AND CONNECTION OFCONTROL PANEL AND HEAD END POWER WITH THE PROJECTS ELECTRICAL CONTRACTOR.

2. UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS OR OTHERWISE INSTRUCTED BY THEARCHITECT, FIRE ALARM DEVICES SHALL HAVE THE FOLLOWING MOUNTING HEIGHTS. VERIFY EXACTHEIGHT WITH ARCHITECT. DIMENSIONS ARE TO CENTER OF BOX UNLESS OTHERWISE NOTED.

2A. MANUAL FIRE PULL STATIONS - MOUNT AT 42" AFF TO THE TOP OF BOX FOR FRONTAL WHEELCHAIRAPPROACH; AND 48" AFF FOR SIDE WHEELCHAIR APPROACH. PULL STATIONS SHALL BE LOCATEDTHROUGHOUT THE PROTECTED AREA SO THAT THEY ARE UNOBSTRUCTED AND ACCESSIBLE;MOUNT WITHIN 5 FT. OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR; MOUNT ONBOTH SIDES OF GROUP OPENINGS OVER 40 FT. IN WIDTH ADDITIONAL.

2B. FIRE ALARM AUDIBLE DEVICES - IF CEILING HEIGHTS ALLOW, WALL-MOUNTED APPLIANCES SHALLHAVE THEIR TOPS ABOVE THE FINISHED FLOORS AT HEIGHTS OF NOT LESS THAN 90 IN. AND BELOWTHE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 6 IN. THIS REQUIREMENT SHALL NOTPRECLUDE CEILING-MOUNTED OR RECESSED APPLIANCES. COMPLY WITH NFPA 72, CHAPTER 4.

2C. SOUND PRESSURE LEVEL SHALL EXCEED THE PREVAILING EQUIVALENT SOUND IN THE ROOM BYAT LEAST 15 dbA OR EXCEED ANY MAX SOUND LEVEL WITH A DURATION OF 60 SECONDS BY 5 dbA,WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL NOT EXCEED 120 dbA.

3. FIRE ALARM VISUAL DEVICES SHALL COMPLY WITH NFPA 72, CHAPTER 4.

3A. VISUAL APPLIANCES CANDELA SHALL BE THE HIGHEST VALUE ALLOWED BY NFPA TABLE IN ORDERTO INSTALL THE FEWEST NUMBER OF STROBES.

3B. THE LAMP SHALL BE XENON STROBE TYPE OR EQUIVALENT.

3C. THE COLOR SHALL BE CLEAR OR NOMINAL WHITE.

3D. THE MAXIMUM PULSE DURATION SHALL BE TWO TENTHS OF ONE SECOND (0.2 SEC) WITH A MAXIMUMDUTY CYCLE OF 40%.

3E. THE PULSE DURATION IS DEFINED AS THE TIME INTERVAL BETWEEN INITIAL AND FINAL POINTS OF10% MAXIMUM SIGNAL.

3F. THE INTENSITY SHALL BE A MINIMUM 0F 75 CANDELA. THE FLASH RATE SHALL BE A MIN. OF 1Hz ANDMAXIMUM OF 3Hz.

4. VISUAL APPLIANCES SHALL BE PLACED 80" ABOVE THE HIGHEST FLOOR LEVEL WITHIN THE SPACEOR 6" BELOW THE CEILING, WHICHEVER IS LOWER. CEILING MOUNTED WERE INDICATED.

5. AT A MIN. VISUAL SIGNALS APPLIANCES SHALL BE PROVIDED IN BUILDING AND FACILITIES IN EACH OFTHE FOLLOWING AREAS: HALLWAYS, LOBBIES, AND ANY OTHER GENERAL USAGE AREAS.

SCALE: 1/16" = 1'-0"

FIRE SAFETY PLAN - ANNEX2

KEYED NOTES - FIRE SAFETY PLAN

F6 INDICATES THE LOCATION FOR A FIRE ALARM CONTROL PANEL

No. Description Date

Page 7: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

MDF

ENTRY

100

LOBBY

100A

CORRIDOR

101

CORRIDOR

102

CORRIDOR

103

CORRIDOR

104

CORRIDOR

105

CORRIDOR

106

SPEECH

107

DIAG

108

RESOURCE

109BEHAVORIAL

110

RR

111

TIME OUT

112

ELEC

113

RR

114

COMPUTER LAB

115

LIBRARY MEDIA CENTER

116

AV STORAGE

117

OFFICE

118

WORK ROOM

119

TECH. CTR.

120

RR

121

CEI / MENTOR

122

Room

123

Room

124

COMPUTER

125RESOURCE

126

CONTENT MASTERY

127

ART

128

STORAGE

129

STORAGE

130

RR

131

RR

132

MUSIC

133

WAITING OFFICE

134

WORK ROOM

135

CONFERENCE

136

PRINC

137

COUNCEL

138

ASST PRINC

139

COOL DOWN

140

RR

141

CORRIDOR

142

EXAM

143 WAITING

144

RR

145 ISO

146

PLAY GYM

300

STORAGE

301

JAN

302

RR

303

RR

304

OFFICE

305

CAFETORIUM

306

STAGE

307

STORAGE

308

CHAIR / TABLE STORAGE

309

KITCHEN

310

JAN

311

OFFICE

312

MECH

313

STORAGE

314

RR

315

CORRIDOR

500

STORAGE

501

BOOK ROOM

502

CLASSROOM

503

CLASSROOM

504

CLASSROOM

505

CLASSROOM

506

CLASSROOM

507

CLASSROOM

508

FAC

509

STORAGE

510 RR

511STORAGE

512

JAN

513

RR

514

CLASSROOM

515

CLASSROOM

516

CLASSROOM

517

CLASSROOM

518

CORRIDOR

400

TEACHER'S BREAK ROOM

401

TEACHER'S WORK ROOM

402CLASSROOM

403

CLASSROOM

404CLASSROOM

405

CLASSROOM

406

CLASSROOM

407

CLASSROOM

408

STORAGE

409

RR

410

JAN

411

FAC

412

RR

413

ELEC

414

CLASSROOM

415

CLASSROOM

416

CLASSROOM

417

CLASSROOM

418

Room

200

READING ROOM

201

ISS

202

CLASSROOM

203

CLASSROOM

204

CLASSROOM

205

CLASSROOM

206

CLASSROOM

207

CLASSROOM

208

STORAGE

209

RR

210JAN

211

FAC

212

RR

213

ELEC

214CLASSROOM

215

CLASSROOM

216

CLASSROOM

217

CLASSROOM

218

S5

S1

PTZ

PTZ

PTZ

S7

S7

S7

S2

S1S2

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 1

:06:3

8 P

M

C:\U

sers

\acru

z\D

ocum

ents

\18

397M

- K

ER

RV

ILLE

- T

ALL

EY

_R

19_

acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VM

EN

TS

-

PA

CK

AG

E A

100%

CD

TS1.05

TALLY

ELEMENTARY

SCHOOL-SECURITY

CAMERA PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

NEW CABLING MUST BE

PULLED TO THIS LOCATION

No. Description Date

Page 8: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

E

E

E

E

IDF

E

E

IDF

E

E

E

E

E

E

E

E

E

E

E

E

E

E

E

RELOCATION M3

S6

REPLACE WITH PTZ

AND RELOCATE TO M1.

REPLACE

REPLACE

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

S4

S3

S3

S1

S5

S2

S3

S1

S1

S1

S1

S5

S5

S3

S1

S3

S4

S1

S1

S1

S5

S1

S1

S3

REPLACE

S5

S3

S3

S1

S3

S1

S1

S4

S1

S3

S4

S1

S5

S5

S7

CORRIDOR

100

CORRIDOR

101

CORRIDOR

103

CORRIDOR

104

TICK

B100

ELEC

B101ENTRY

B102

THEATER

B103

STAGE

B104

COST.

B105

OFFICE

B106

CLASS / DRESS

B107

CLASS / DRESS

B108

RAMP

B109

BOYS

B110

GIRLS

B111JAN

B112

FAC

B113

CORRIDOR

B114

BAND REHERSAL

B115

ENSEM

B116ENSEM

B117OFFICE

B118

LIBR

B119

HALL

B120

PERCUSS

B121

ENSEM

B122

STAGE BAND

B123

COLOR GAURD

B124P

B125

P

B126

UNIF

B127

ENSEM

B128OFFICE

B129

LIBR

B130

UNIF

B131

CHORAL REHERSAL

B132

EQUIP

B133P

B134

P

B135

DARK

B136

STOR

B137

COMP

B138

PHOTO JOURNALISM

B140

OFFICE

B141

P

B142

DARK

B143

ART STUDIO LAB

B144

COMP

B145

STOR

B146

STOR

B147

OFFICE

B148

ART STUDIO LAB

B149

HALL

B150

OFFICE

B151

STOR

B152

KILN

B153

OFFICE

C100

DANCE / DRILL TEAM

C101

DRILL

C102A

DANCE

C102B

CHEER

C103

GIRLS

C104

CONC.

C105

LOBBY

C106

STOR

C107

BOYS

C108

CORRIDOR

C109

CORRIDOR

C110

MAIN GYM

C111

PRACTICE GYM

C112

Room

C113

CLASS

C114

MECH

C115

STAIRS

C116STOR

C117

GIRLS LOCKER

C118

SHWR

C119TLT

C120

STOR

C121

TLT

C122

SHWR

C123

DRY

C123A

BOYS LOCKERS

C124

LAUNDRY

C125

STAIRS

C126

Room

C127

Room

C128

COACHES

C129

OFFICE

C130OFFICE

C131OFFICE

C132 OFFICE

C133

OFFICE

C134

WET

C135

TRAINING

C136STOR

C137

MECH / STOR

C138

WEIGHT RM

C139

CORRIDOR

C140

FOOTBALL

C141

SHWR

C142

DRY

C142A

TLT

C143

COACHES

C144

TLT

C145

A.D.

C146

SEC

C147

RECEP

D100

SEC

D101

ATTEND

D102

HALL

D103

A.P.

D104

A.P.

D105

A.P.

D106

A.P.

D107

SEC

D108

HALL

D109

Room

D110

RECEP

D111

PRINC

D112

LG. CONF

D113

CONF

D114

V

D115

TLT

D116

TLT

D117

I.S.S.

D118

OFFICE

D118A

CORRIDOR

D119

Room

D120

CLASS

D121

CLASS

D122

CORRIDOR

D123

CLASS

D124

CLASS

D125

CLASS

D126

PLANNING

D127

CORRIDOR

D128

PLANNING

D129

CLASS

D130

COMPUTER / KEYBOARDING

D131

COMPUTER / KEYBOARDING

D132

COMPUTER / KEYBOARDING

D133

COMPUTER / KEYBOARDING

D134

COMPUTER / KEYBOARDING

D135

COMPUTER / KEYBOARDING

D136

COMPUTER PLANNING

D137

GIRLS

D138

BOYS

D139

JAN

D140

FAC

D141

CORRIDOR

D142

CLASS

D143

CLASS

D144

Room

D145

RESOURCE COMPUTER LAB

D146

ELC

D148

COPY CENTER

D149

Room

D120ARoom

D120B

FUNCTIONAL LIVING LAB

A100

SEVER & PROFOUND

A101

RR

A102

STOR

A101A

Room

A118

HEALTH COUNC

A119 OFFICE

A120

WORK

A121

RR

A122

COUNS

A123

COUNS

A124

CORRIDOR

A125 REGISTR

A126

WAIT / RECEP

A127

COUNS

A128

COUNS

A129

CORRIDOR

A131

VAULT

A132

BOOK ROOM

A156

RELOCATE

PTZ

S1

PTZ

S7

REPLACE

S6

REPLACE

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

3:1

2:0

1 P

M

C:\U

sers

\she

ivly

\Docum

ents

\18397

M -

KE

RR

VIL

LE

- T

I VY

-HS

_R

19_

sheiv

ly.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.06

TIVY HIGH SCHOOL

SECURITY CAMERA

PLAN - FIRST

FLOOR - AREA A

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - FIRST FLOOR - AREA A1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.

S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.

S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.

S6 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO BE REPLACED.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

No. Description Date

Page 9: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

E

IDF

E

E

E

E

E

E

E

E

E

EE

IDF IDF-(MEZZ.)

E

E

E

MDF

E

E

E

E

RELOCATION M2

RELOCATION M1

S6

S6

S6

REPLACE WITH PTZ AND RELOCATE EXISTING TO M2

RELOCATE EXISTING TO M3 S1

S1

S1

S3

S3

S3

S4

REPLACE

S1

S1

S1

S3

REPLACE

S1

S4

S3

S3

S3

S6

S5

S3

S3

S1

S1

S1

S3

S3

S2

S6

S7

S7

REPLACE

S4S5

CORRIDOR

105

CORRIDOR

106

C.T. DIRECTOR

F100SEC

F101

PLANNING

F102

TLT

F103

STOR

F104P.R.

F105

OFFICE

F106

HEALTH OCCUPATIONS

F107

TLT

F108

STOR

F109

OFFICE

F110

CLASS

F111

COMMERCIAL KITCHEN LAB

F112

Room

F113

Room

F114

CORRIDOR

F115

CORRIDOR

F116

MAIN MECHANICAL BOILER

ROOM

F117

CENTRAL STOR

F118

AUTO MECHANICS

F119

CLASS

F120

OFFICE

F121

TOOLS

F122

STOR

F123

CLASS

F124

OFFICE

F125

STOR

F126

BUILDING TRADES /

CONSTRUCTION MFG.

F127

CLASS

F128

OFFICE

F129

STOR

F130

INDUSTRIAL / MODULAR

TECHNOLOGY

F131

CLASS

F132

OFFICE

F133CLASS

F134

TLT

F135

STOR

F136

VOC. AG / HORTICULTURE

F137

STOR

F138

CORRIDOR

G100

ELEC

G101

Room

G102

CLASS

G103

CLASS

G104

CORRIDOR

G105

CLASS

G106

CLASS

G107

CLASS

G108

CLASS

G109

CORRIDOR

G110

CLASS

G111

CLASS

G112CLASS

G113

Room

G114

CORRIDOR

G115

MARKETING CLASSROOM

G116

STOR

G117

OFFICE

G118

CLASS

G119

Room

G120

Room

G121

Room

G122

Room

G123

COMPUTER / KEYBOARDING

G124

RR

A102ED

A103

ED

A104

ED

A105

ED

A106

ED

A107

ED

A108

CLASS

A109

OFFLINE

A110

STOR

A111

OFFICE

A112

STUDIO

A113

P.E.S.

A114

STUDIO

A115

STUDIO

A116

TECH

A117

COUNS

A129

COUNS

A130

CORRIDOR

A131

VAULT

A132

COUNS

A133

CARRERS LAB

A134

CORRIDOR

A138

ENTRY

A139

COMPUTER RESOURCE LAB

A140

WORK RM

A141

OFFICE

A142

A.V.

A143

LIBRARY MEDIA CENTER

READING ROOM

A144

DISTANCE LEARNING LAB

A145

COMPUTER RESOUCE

A146

D

A147

D

A148

DEBATE

A149

STOR

A150

BOYS

A151

GIRLS

A152

FAC

A153

JAN

A154

TEACHER WORK RM.

A155

TEACHER BREAK / LUNCH

E123

P

E116

TLT

E125

TLT

E124

SCIENCE

E120

STOR

E105

FAMILY & CONSUMER

TECHNOLOGY

E118

STOR

E121

STOR

E122

DINING

E100

KITCHEN

E127

S7

PTZ

PTZ

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

S7

PTZ

REPLACE

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

3:1

2:0

3 P

M

C:\U

sers

\she

ivly

\Docum

ents

\18397

M -

KE

RR

VIL

LE

- T

I VY

-HS

_R

19_

sheiv

ly.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.07

TIVY HIGH SCHOOLSECURITY CAMERA

PLAN - FIRSTFLOOR - AREA B

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - FIRST FLOOR - AREA B1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.

S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.

S5 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO REMAIN.

S6 INDICATES THE LOCATION FOR AN EXISTING OUTDOOR CAMERA TO BE REPLACED.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

No. Description Date

Page 10: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

E

E

E

E

E

E

E

E

IDF(MEZZ.)

IDF

CLASS

K212

PLANNING

K211

CLASS

K210

CLASS

K209

CLASS

K207

CLASS

K206

CLASS

K205

COMPUTER RESOURCE

K203

PHYSICS LAB

K202

SCIENCE EQUIP / PREP

K202A

CLASS

K213

CLASS

K215

CLASS

K216

CLASS

K220

CLASS

K221

CLASS

K222

CLASS

K223

CLASS

K224

GIRLS

K225

JAN

K226

FAC

K227

BOYS

K228

PLANNING

K201

SPEC ED

K200

Room

K234

Room

K233

Room

K232

CLASS

K231

CLASS

K230

MECH MEZZ

K235

REPLACE

S3

S1

S1

S4

S3

S1

S1

S1

S3

S4

REPLACE

REPLACE

REPLACE

S4

S1

S3

S4

S1

S1

S1

S1

INSIDE ELEVATOR,REQUIRES TRAVELING CABLE AND ELEVATOR CONTRACTOR COORDINATION.

CORRIDOR

H200

ELEC

H201

CLASS

H202

CLASS

H203

PLANNING

H204

CLASS

H205

CLASS

H206

CLASS

H207

CLASS

H208

CORRIDOR

H209

CLASS

H210CLASS

H211CLASS

H212

Room

H213

CORRIDOR

H214

PLANNING

H215

CLASS

H216CLASS

H217

CLASS

H218

CLASS

H219

BOYS

H220

TLT

H221

JAN

H222

CORRIDOR

H223

GIRLS

H224

CORRIDOR

J201

ELEV

J202 BIOLOGY CLASS

J203 BIOLOGY LAB

J204

BIOLOGY CLASS

J205

IPC CLASS

J206

IPC LAB

J207

Room

J208

IPC CLASS

J209

Room

J210

IPC CLASS

J211IPC LAB

J212IPC CLASS

J213

CHEMESTRY LAB

J214

CHEMESTRY LAB

J215

STOR

J216

CORRIDOR

K204

CORRIDOR

K208

CORRIDOR

K214

CORRIDOR

K202E

CLASS

K218

CLASS

K219

MECH

J200

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

REPLACE AND RELOCATE TO BE BACK -TO BACK WITH OTHER CORRIDOR CAMERA

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 1

:40:4

9 P

M

C:\U

sers

\acru

z\D

ocum

en

ts\1

839

7M

- K

ER

RV

ILLE

- T

IVY

-HS

_R

19_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.08

TIVY HIGH SCHOOLSECURITY CAMERA

PLAN - SECONDFLOOR

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

SCALE: 1" = 20'-0"

SECURITY CAMERA PLAN - SECOND FLOOR1

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.

S4 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO BE REPLACED.

No. Description Date

Page 11: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

M

M

M

M

M

M

M

M

MM

M

M

IDF

IDF

IDF

MDF

MENTORING CENTER

C001

CORRIDOR

A100

CLASSROOM

A101

CLASSROOM

A102

CLASSROOM

A103

CLASSROOM

A104

CLASSROOM

A105

MEDIA CENTER

A106

WORK ROOM

A107

STORAGE

A108

VEST

A109

JAN

A110

RR

A111

RR

A112

TEXT BOOK STORAGE

A113

COMPUTER LAB

A114

CORRIDOR

B101

LOBBY

B100

GEN OFFICE

B102

CONFERENCE

B103

COUNC

B104OFFICE

B105RECORDS

B106

NURSE

B107

RR

B108

PRINC

B109

STORAGE

B110

STAIR

B111

STORAGE

B112

MECH

B113

CAFETORIUM

B114

STAGE

B125

SERVERY

B115

WAREWASH

B116

REF. / FREEZER

B117

DRY STORAGE

B118

MECH

B119

OFFICE

B120

FOOD PREP

B121

LOCKER

B122TOILET

B123JAN

B124

STORAGE

B126

STAIR

B127

JAN

B128

CLASSROOM

B129

STORAGE

B131

TELE

B132

RR

B133

RR

B134

WORK ROOM

B135

WORK ROOM

B136

CLASSROOM

B137

CLASSROOM

B138

CLASSROOM

B139

CLASSROOM

B140

CLASSROOM

B141

CLASSROOM

B142

CLASSROOM

B143

VEST

B144

RAMP

B145

Room

B146

CORRIDOR

B130

CLASSROOM

B147

Room

B148

Room

B149

Room

B150

CLASSROOM

B151

CLASSROOM

B152

CLASSROOM

B153

CLASSROOM

B154

CLASSROOM

B155

CLASSROOM

B156

CLASSROOM

B157

CLASSROOM

B158

CORRIDOR

C100

Room

C101

Room

C102

Room

C103

Room

C104

VEST

C105 FAC

C106

VEST

C107

RR

C108

JAN

C109

VEST

C110

RR

C111

ELEC

C112 MECH

C113

PLAY AREA

C114

OFFICE

C115

BOYS DRESS

C116

STORAGE

C117

RR

C118

GIRLS DRESS

C119

RR

C120

STORAGE

C121

VEST

C123

ART CLASSROOM

C124

Room

C125

Room

C126

CLASSROOM

C127

RAMP

C128

VEST

C129

TESTING

C130

MUSIC CLASSROOM

C131

STORAGE

C132

RAMP

C133

CORRIDOR

C134

CLASSROOM

C135RESOURCE

C136

CLASSROOM

C137

CLASSROOM

C138

VEST

C139

FAC

C140

VEST

C141

RR

C142

JAN

C143

VEST

C144

RR

C145

CORRIDOR

C146

CLASSROOM

C147

OUTDOOR STORAGE

C148

STORAGE

C149

ELEC

C150

CENTRAL STORAGE

C151

CLASSROOM

C152

CLASSROOM

C153

S2

PTZPTZ

PTZ

KP

KP

KP

E

E

E

E

E

S7

S7S7

S11

S11

S11

S11 S12

S13

S13

S9S8

S8?

S8

S9

S8

S2

CLASSROOM

C154

CLASSROOM

C155

CLASSROOM

C156

CLASSROOM

C157

CLASSROOM

C158

CLASSROOM

C159

CLASSROOM

C160

CLASSROOM

C161

CLASSROOM

C162

CLASSROOM

C163

ELEC / STOR / IDF

C164

RR

C165

RR

C166

ELEC / STOR

C167

CORRIDOR

C168VEST

C169S1

PTZ

S7

KP S13

S10

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 2

:02:3

5 P

M

C:\U

sers

\acru

z\D

ocum

ents

\1839

7M

- K

ER

RV

ILL

E -

DA

NIE

LS

_R

19_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VM

EN

TS

-

PA

CK

AG

E A

100%

CD

TS1.09

TOM DANIELS

ELEMENTARY

SCHOOL -

SECURITY PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY PLAN1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

SCALE: 1/16" = 1'-0"

FIRST FLOOR - SECURITY PLAN - ANNEX2

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

S8 INDICATES THE LOCATION FOR A NEW WALL MOUNTED MOTION DETECTOR.

S9 INDICATES THE LOCATION FOR A NEW CEILING MOUNTED LONG RANGE MOTION DETECTOR.

S10 INDICATES THE LOCATION FOR A NEW CEILING MOUNTED 360-DEGREE LONG RANGE MOTION

DETECTOR.

S11 INDICATES THE LOCATION FOR AN EXISTING MOTION DETECTOR.

S12 INDICATES THE LOCATION FOR AN EXISTING SECURITY KEY PAD.

S13 INDICATES THE LOCATION FOR A NEW SECURITY KEY PAD.

No. Description Date

Page 12: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

E

E

E

RELOCATE TO CENTER

OF CORRIDORR

BACK TO BACK

E

E

IDF

IDFIDF

CORRIDOR

A100

CORRIDOR

A101

CORRIDOR

A102

CORRIDOR

A103

DINING

A104

STAGE

A105

DRESSING

A106

RR

A107

DRESSING

A108

RR

A109

SS RESOURCE

A110

STORAGE

A111

ELEV

A112

MECH

A113

READING

A114

ART

A115

STORAGE

A116

OFFICE

A117

KILN

A118

STOR / ELEC

A119

RR

A120

VEST

A121

JAN

A122VEST

A123

RR

A124

STAIR

A125

STORAGE

A126

SCULLERY

A127

SERVICE

A128

DRY STORAGE

A130

COLD STORAGE

A131

COLD STORAGE

A132 WASH

A133

JAN

A134

VEST

A135

RR

A136

Room

A129

SPEECH

A137

SPEECH

A138SP ED

A139SP ED

A140

SP ED

A141

STORAGE

A142

RR

A143

?

?OFFICE

A146

CORRIDOR

B100

CORRIDOR

B101

CORRIDOR

B102

RESOURCE MATERIAL

B103

RR

B104

RR

B106

JAN

B105

ENGLISH

B107

ENGLISH

B108

ENGLISH

B109

ENGLISH

B110

ENGLISH

B111

GEN OFFICE

B112

ASST PRIN

B113

PRIN

B114

COUNC

B115

RECEPT

B116 CLOSET

B117LOUNGE

B118

CONFERENCE

B119

WORK ROOM

B120

FIRE STORAGE

B121

NURSE

B122RR

B123

LIB STORAGE / MDF

B124

LIB

B125

OFFICE

B126TEACH WORK ROOM

B127

RR

B128

RR

B129BOOK STORAGE

B130

SS

B131SS

B132

SS

B133 SS

B134SS

B135

VEST

B136

BAND HALL

B137

INSTRU. STORAGE

B138

Room

B139

PRAC

B140

PRAC

B141

PRAC

B142

PRAC

B143

PRAC

B144

PRAC

B145

PRAC

B146

PRAC

B147

PRAC

B148

Room

B149

ENSEM

B150

OFFICE

B151

LIB

B152

STAIR

B153

CHOIR HALL

B154

OFFICE

B155

WK RM.

B156

ENG. RES. RM

B157

Room

B158

Room

B159

S3

S3

S3

S3

S3

S3

S1

S7

PTZ

PTZ

S7

S7

S2

S1

PTZ S7

ORCHESTRA O100

RELOCATE TO COVER RESTROOM ENTRANCES

E

E

E

RELOCATE TO COVER ELEVATOR

MDF

Room

A200

VEST

A202

RR

A203

BK RM

A204

CLASSROOM

A205

CLASSROOM

A206

CLASSROOM

A207CLASSROOM

A208

CLASSROOM

A209

CLASSROOM

A210

CLASSROOM

A211

CLASSROOM

A212

CLASSROOM

A213

CLASSROOM

A214

CLASSROOM

A215

CLASSROOM

A216

VEST

A217

RR

A218

ELECTRICAL

A219

JAN

A220

CORRIDOR

B200

Room

B201 MATH CLASSROOM

B202

MATH CLASSROOM

B203

MATH CLASSROOM

B204

MATH CLASSROOM

B205MATH CLASSROOM

B206

MATH CLASSROOM

B207

STORAGE / ELEC

B208SCIENCE

B209PREP

B210SCIENCE

B211

SCIENCE

B212PREP

B213

SCIENCE

B214

S3

S3

S3

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

1:2

0:0

1 P

M

C:\U

sers

\acru

z\D

ocum

ents

\18

397M

- K

ER

RV

ILLE

- B

T W

ILS

ON

_R

19_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.01

BT WILSON MIDDLE

SCHOOL -

SECURITY CAMERA

PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - FIRST FLOOR1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - SECOND FLOOR2

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

No. Description Date

Page 13: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

S1

S2

S2

NOTE: THERE IS ONE OUTDOOR CAMERA TO BE ADDED TO THE OUTSIDE

OF THE STAFF DEVELOPMENT BUILDING TO COVER THE

COURTYARD BEHIND THE GYM.

IDF

LOCKER

118

Room

122

Room

119

VEST

117Room

117A

GYM

120

WEIGHT ROOM

115

Room

114A

VEST

114

LOCKER

113

Room

121

Room

124

Room

125

Room

126

Room

129

Room

130

Room

127

Room

128

Room

131

Room

132

Room

133

Room

134

Room

135Room

139

Room

138

Room

137

Room

136

Room

123

Room

140

Room

141

STAFF DEVELOPMENT

S100

S2

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

1:2

3:0

3 P

M

C:\U

sers

\acru

z\D

ocum

ents

\18

397M

- K

ER

RV

ILLE

- B

T W

ILS

ON

_R

19_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.02

BT WILSON MIDDLE

SCHOOL -

SECURITY CAMERA

PLAN - GYM

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1" = 10'-0"

SECURITY CAMERA PLAN - GYM1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

No. Description Date

Page 14: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

UP

IDF

MDF

PTZ

S7

S1

S2

PTZ

S7

S2

S1

S1

STAIR

D228

CORRIDOR

D229

RECEPTION

D230

OFFICE

D231

Room

D232

OFFICE

D233

OFFICE

D234

OFFICE

D235CONFERENCE

D236

OFFICE

D237

Room

D238

Room

D239

RR

D240

RR

D241 BREAK

D242

Room

D243

OFFICE

D244

VEST

D245

MECH

D246

CLASS

D247

STOR

D248

RR

D249 SHWR

D250

CLASS

D251STOR

D252

STOR

D253

STOR

D254

CLASS

D255

ISO

D256

RR

D257

VEST

D258

CORRIDOR

D259

CORRIDOR

D260

MEDIA CENTER

D261

STAGE

D262

OFFICE

D263

COMP LAB

D264

LOUNGE

D265

CORRIDOR

D266

Room

D267

STOR

D268

STOR

D269RR

D270

RR

D271

OFFICE

D272ART

D273

STOR

D274

STOR

D275

VEST

D276

CAFETERIA

D277STAGE

D278

STOR

D279

STOR

D280

STOR

D281

STOR

D282

PREP

D283

STOR

D284

STOR

D285

PREP

D286

STOR

D287

RISER

D288STOR

D289RR

D290

LOCKER

D291

PREP

D292

SERVING

D293

CORRIDOR

D294

VEST

D295

RR

D296

Room

D297

VEST

D298

RR

D299

VEST

D300

ENCLOSED PLAY AREA

D301

DRESS

D302OFFICE

D303

RR

D304DRESS

D305

JAN

D306

Room

D307

MECH

D308

CORRIDOR

A201

CLASSROOM

A202

CLASSROOM

A203

CLASSROOM

A204

CLASSROOM

A205

CLASSROOM

A206

CLASSROOM

A207

CLASSROOM

A208

CLASSROOM

A209

CLASSROOM

A210

CLASSROOM

A211

CLASSROOM

A212

CLASSROOM

A213

CORRIDOR

A214

JAN

A215

VEST

A216

RR

A217

RR

A218

VEST

A219

FAC

A220

STORAGE

A221

CORRIDOR

B201

CLASSROOM

B202

CLASSROOM

B203

CLASSROOM

B204

CLASSROOM

B205

CLASSROOM

B206

CLASSROOM

B207

CLASSROOM

B208

CLASSROOM

B209

CLASSROOM

B210

CLASSROOM

B211

CORRIDOR

D201

JAN

D202

VEST

D203

RR

D204

FAC

D205

VEST

D206

RR

D207

CLASSROOM

D208

CLASSROOM

D209

CLASSROOM

D210

CLASSROOM

D211

CLASSROOM

D212

CLASSROOM

D213

CLASSROOM

D214

CLASSROOM

D215

CLASSROOM

D216

CLASSROOM

D217

CORRIDOR

D218

CLASSROOM

D219

VEST

D220

JAN

D221

VEST

D222

RR

D223

FAC

D224

VEST

D225

RR

D226

STORAGE

D227

IDF IDF

S7

S1

PTZ

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

3/1

/2019

12:4

4:0

5 P

M

C:\U

sers

\acru

z\D

ocum

ents

\18

397M

- K

ER

RV

ILLE

- N

IMIT

Z_

R19_

acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.03

NIMITZ

ELEMENTARY

SCHOOL-SECURITY

CAMERA PLAN

03/04/2019

18397M

Kerrville Independent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - FIRST FLOOR1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

SCALE: 1/16" = 1'-0"

SECURITY CAMERA PLAN - SECOND FLOOR2

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

No. Description Date

Page 15: SAFETY AND SECURITY IMPROVMENTS -PACKAGE A...7 partition types, wall sections 8 casework, millwork 9 doors, windows, frames 10 ceilings g general c civil l landscape ca sports s structural

E

IDF

MDF

DRESS

A101

RR

A102DRY STO

A103

BULK STO

A104

FOOD PREP

A105OFFICE

A107

JAN

A109

REF / FZR

A106

WAREWASH

A110

SERVERY

A108

CAN WASH

A112

CAFETORIUM

A111

STAGE

A127

MUSIC

A128

RR

A129

VEST

A130

JAN

A131

RR

A132

VEST

A133

OUTSIDE STO

A114

ELEC

A115

STO

A116

MECH

A117

PAPER STO

A118JAN

A119

RR

A120

RR

A121

DRESS

A122

DRESS

A123

OFFICE / STO

A124

STO

A125

STO

A126

ENCLOSED PLAY AREA

A135

Room

A136

ELEC

B101

STO

B102

RR

B103

RR

B104

JAN

B105WORK AREA

B106

CLASSROOM

B107

CLASSROOM

B108

Room

B109

Room

B110

CLASSROOM

B111

CLASSROOM

B112

Room

B113

Room

B114

CLASSROOM

B115

CORRIDOR

B116

ART

B118

KILN

B119

STO

B120

CORRIDOR

B121

CLASSROOM

B122

CLASSROOM

B123

CLASSROOM

B124

CLASSROOM

B125

CLASSROOM

B126

CLASSROOM

B127

CLASSROOM

B128

CLASSROOM

B129

CORRIDOR

B131

ELEC

B133

RR

B134

CLINIC

B135

CORRIDOR

B136

CLASSROOM

B137

CLASSROOM

B139

CLASSROOM

B140

CLASSROOM

B141

VEST

B142

FAC

B143

VEST

B144

RR

B145

RR

B146

VEST

B147

CLASSROOM

B149

CLASSROOM

B150

STO

B151

RR

B152

CLASSROOM

B153 CLASSROOM

B154

CLASSROOM

B155RR

B156

CORRIDOR

B157

TESTING

B158

STORAGE

B159

CLASSROOM

B160

CLASSROOM

B162

CLASSROOM

B163

CLASSROOM

B164

CORRIDOR

C100

OFFICE / RECEP

C101CORRIDOR

C102

WORK ROOM

C103PRINC

C104

COUNCELOR

C105

FILES / RECORDS

C106

MULTI-USE OFFICE

C107

CONFERENCE

C108

FAC WORK ROOM

C109

RR

C110

RR

C111

LOUNGE

C112

TELE

C113

TEXTBOOK STO

C114

TEACHERS LOUNGE

C115

COFFEE

C116

LOBBY

C117COMPUTER LAB

C118

Room

C119

STO

C122

CORRIDOR

C123

Room

C125

MULTI-USE

C126

MEDIA CENTER

C127

LIBRARIANS OFFICE

C128

LIBRARY STO

C129STUDY ROOM

C130

FILM VIEWING

C131

CLASSROOM

C133

CORRIDOR

C132

RR

C134

CLASSROOM

C135

CLASSROOM

C136

CLASSROOM

C137

CLASSROOM

C138

CLASSROOM

C139

CLASSROOM

C140

STO

C141

STO

C142

RR

C143

WORKROOM

C144

CLASSROOM

C145

CLASSROOM

C146

S7

S3

PTZ

PTZ

RELOCATE

BACK-TO-BACK

S7

S1

S2

S2

LICENSED

PRO

FESS IONAL ENGIN

EER

STATE OF TEXAS

F-18672

LEAF ENGINEERS

DONALD C. RICHARDS

61525

Other

Architect

CIVIL

ARCHITECT PBK Architects, Inc.

LANDSCAPE NAME

STRUCTURAL NAME

MEPT

FOOD SERVICE NAME

ACOUSTICAL NAME

THEATRICAL NAME

DATE

PROJECT NUMBER

CLIENT

REVISIONS

SAN ANTONIO601 N.W. Loop 410, Suite 400

San Antonio, TX 78216210-829-0123 P210-829-0578 FTX Firm: F-1608

PBK.com

DR

AW

N B

Y:

CH

EC

KE

D B

Y:

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

ADDRESSADDRESS

012-345-6789 P 012-345-6789 F

601 N.W. Loop 410, Suite 400San Antonio, TX 78216

210-638-7200 P 210-829-0578 FTX Firm: F-18672

LEAFE N G I N E E R S

A COMPANYPBK

2/2

8/2

01

9 1

2:5

3:2

1 P

M

C:\U

sers

\acru

z\D

ocum

en

ts\1

839

7M

- K

ER

RV

ILLE

- S

TA

RK

EY

_R

19

_acru

z.r

vt

100%

CD

SA

FE

TY

AN

D S

EC

UR

ITY

IMP

RO

VE

ME

NT

S -

PA

CK

AG

E A

100%

CD

TS1.04

STARKEY

ELEMENTARY

SCHOOL-SECURITY

CAMERA PLAN

03/04/2019

18397M

Kerrville Indepenent School District

100% CD

AN

TH

ON

Y C

RU

ZG

RE

G G

RIF

FIN

03/04/2019

SCALE: 1/16" = 1'-0"

SECURITY PLAN1

GENERAL NOTES - SECURITY PLAN

1. ALL EXPOSED SECURITY SYSTEMS WIRING OR WIRING ROUTING ACROSS NON ACCESSIBLE CEILINGS

SHALL BE ROUTED IN CONDUIT. SIZE CONDUIT AS REQUIRED TO ROUTE SYSTEMS WITH 40% CABLE

FILL RATIO. MINIMUM CONDUIT SIZE SHALL BE 3/4"

2. SECURITY CONTRACTOR SHALL PROVIDE A 10'-0" SERVICE LOOP AT EACH CAMERA TO PROVIDE

FLEXIBILITY OF CAMERA POSITION AND LOCATION.

3. SECURITY CONTRACTOR TO ENSURE ALL EXTERIOR WALL PENETRATIONS ARE PROPERLY SEALED

TO PREVENT ANY MOISTURE FROM ENTERING BUILDING.

4. NO CONDUITS SHALL BE INSTALLED ON THE EXTERIOR OF THE BUILDING. CONTRACTOR TO

COORDINATE WITH TECHNOLOGY CONSULTANT PRIOR TO INSTALLATION IF ANY EXTERIOR

CONDUITS ARE REQUIRED.

5. ALL CONDUIT STUB OUTS AND SLEEVES SHALL HAVE PROTECTIVE BUSHINGS TO PREVENT CABLE

DAMAGE. BUSHING TO BE INSTALLED PRIOR TO CABLE INSTALLATION. CUTTING BUSHING AND

INSTALLING AFTER CABLE IS INSTALLED WILL NOT BE ACCEPTED.

KEYED NOTES - SECURITY PLAN

S1 INDICATES THE LOCATION FOR A NEW INDOOR CAMERA.

S2 INDICATES THE LOCATION FOR A NEW OUTDOOR CAMERA.

S3 INDICATES THE LOCATION FOR AN EXISTING INDOOR CAMERA TO REMAIN.

S7 INDICATES THE LOCATION FOR A NEW OUTDOOR PAN, TILT, ZOOM CAMERA.

No. Description Date