SACP SECURITY ALARM CONTROL PANEL - pages.uoregon.edupages.uoregon.edu/moxoby/942Olive/942 Olive...

6
* C S S D S S S S S S S S S S D S S S S S R G A V T 1. NOT ALL SYMBOLS & NOTES ARE NECESSARILY USED ON THIS PROJECT. 2. INSTALLATION OF ALL ELECTRICAL EQUIPMENT SHALL MEET STATE AND LOCAL CODES. PROVIDE STRUCTURAL SEISMIC RATINGS/LABELS AND BRACING PER IBC. 3. ALL CONTROL WIRING AND DEVICES SUCH AS OVERLOAD DEVICES, PUSH-BUTTON STATIONS, RELAYS, THERMOSTATS AND CONTROL DEVICES TO BE PROVIDED AND INSTALLED UNDER MECHANICAL CONTROLS. POWER WIRING WILL BE PER ELECTRICAL, AS SHOWN ON DRAWINGS AND WRITTEN SPECIFICATIONS. REFER TO MECHANICAL DRAWINGS AND DATA SHEETS PRIOR TO BID AND INSTALLATION. FUSE DISCONNECTS AND FUSES SHALL BE PROVIDED BY DIVISION 16/26. 4. ALL PENETRATIONS OF WALLS AND CONCRETE SLABS SHALL BE COORDINATED WITH ARCHITECT. SEAL ALL OPENINGS WITH FIRE STOP AS REQUIRED. 5. PROVIDE EQUIPMENT GROUNDING (GREEN WIRE) AND NEUTRAL (WHITE/GRAY WIRE) CONDUCTORS IN ALL RACEWAYS. EQUIPMENT GROUNDING CONDUCTOR IS TO BE BONDED TO ALL RACEWAY BOXES AND ENCLOSURES ENCLOSING THE CIRCUIT CONDUCTORS. 6. FIRE ALARM CABLES SHALL BE PLENUM RATED. RELOCATED SMOKE DETECTORS SHALL INSTALLED AND BE TESTED PER NFPA 72, INTERNATIONAL FIRE CODE, STATE AND LOCAL CODES. PROVIDE ACCEPTANCE TESTING REPORTS WITH OPERATION AND MAINTENANCE MANUALS. 7. ELECTRICAL EQUIPMENT LAYOUT SHOWN IN ENLARGED ELECTRICAL PLANS ARE BASED UPON A BASIS OF DESIGN MANUFACTURER'S EQUIPMENT. COORDINATE EXACT SPACE REQUIREMENTS WITH EQUIPMENT SUPPLIER. MAINTAIN EQUIPMENT CLEARANCES IN COMPLIANCE WITH NEC AND MANUFACTURER RECOMMENDATIONS. 8. COORDINATE ALL ELECTRICAL DEVICE LOCATIONS (SWITCHES, RECEPTACLES, DATA OUTLETS, ETC) WITH ARCHITECT AND CASEWORK SUPPLIER PRIOR TO ROUGH-IN. DO NOT LOCATE ELECTRICAL DEVICES BEHIND MIRRORS, CASEWORK OR BACKSPASHES. 1. FIRE SAFETY NOTE: STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR DEMOLITION OPERATIONS, INCLUDING THOSE IN UNDERGROUND LOCATIONS, SHALL COMPLY WITH NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, AND THIS CHAPTER. 2006 NFPA 1. 2. FIRE SAFETY DURING ALTERATION: 16.4.4.1 WHERE THE BUILDING IS PROTECTED BY FIRE PROTECTION SYSTEMS, SUCH SYSTEMS SHALL BE MAINTAINED OPERATIONAL AT ALL TIMES DURING ALTERATION. 16.4.4.2 WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE SYSTEM SHALL BE KEPT IN SERVICE AND FIRE DEPARTMENT SHALL BE NOTIFIED. 16.4.4.3 WHEN IT IS NECESSARY TO SHUT DOWN THE SYSTEM, THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL HAVE THE AUTHORITY TO REQUIRE ALTERNATE MEASURES OF PROTECTION UNTIL THE SYSTEM IS RETURNED TO SERVICE. 10.8.1.1 AS NECESSARY DURING EMERGENCIES, MAINTENANCE, DRILLS, PRESCRIBED TESTING, ALTERATIONS, OR RENOVATIONS, PORTABLE OR FIXED FIRE-EXTINGUISHING SYSTEMS OR DEVICES OR ANY FIRE-WARINING SYSTEM SHALL BE PERMITTED TO BE MADE INOPERATIVE OR INACCESSIBLE. A FIRE WATCH SHALL BE REQUIRED AS SPECIFIED IN SECTIONS 13.3.4.3.5.2(3), 13.7.1.4.4, 16.5.4, 20.2.3.6, 34.6.3.3, 41.2.2.5, 41.2.2.6, 41.2.4, 41.3.4, 41.4.1, 34.5.4.3, AND 25.1.8 AT NO COST TO THE AHJ. NFPA 1 2006, AS AMENDED. 3. AHJ APPROVAL: 13.1.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE THAT CONSTRUCTION DOCUMENTS FOR ALL FIRE PROTECTION SYSTEMS BE SUBMITTED FOR REVIEW AND APPROVAL AND A PERMIT BE ISSUED PRIOR TO THE INSTALLATION, REHABILITATION, OR MODIFICATIONS. FURTHER, THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE THAT FULL ACCEPTANCE TESTS OF THE SYSTEMS BE PREFORMED IN THE AHJ'S PRESENCE PRIOR TO FINAL SYSTEM CERTIFICATION. FIRE ALARM SYSTEMS; FIRE HYDRANT SYSTEMS; FIR-EXTINGUISHING SYSTEMS; STANDPIPES; AND OTHER FIRE-PROTECTION SYSTEMS AND APPURTENANCES REQUIRED BY THIS CODE SHALL BE APPROVED BY THE AHJ AS TO INSTALLATION AND LOCATION AND SHALL BE SUBJECT TO ACCEPTANCE TESTS REQUIRED BY THE APPROPRIATE COUNTY AGENCY. NFPA 1, CHAPTER 13 AS AMENDED. 4. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS: 13.7.1.1 WHERE BUILDING FIRE ALARM SYSTEMS OR AUTOMATIC FIRE DETECTORS ARE REQUIRED BY OTHER SECTIONS OF THIS CODE, THEY SHALL BE PROVIDED AND INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72, NATIONAL FIRE ALARM CODE, AND SECTION 13.7. 2006 NFPA 1. FIRE ALARM SYSTEM INSTALLATION AND MAINTENANCE SHALL BE IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM CODE, AND 2006 NFPA 1. 13.7.1.4.9.8 AUDIBILITY. THE ALARM SIGNAL SHALL BE A DISTINCTIVE SOUND, WHICH IS NOT USED FOR ANY OTHER PURPOSE OTHER THAN THE FIRE ALARM. ALARM-SIGNALING DEVICES SHALL PRODUCE A SOUND THAT EXCEEDS THE PREVAILING EQUIVALENT SOUND LEVEL IN THE ROOM OR SPACE BY 15 DECIBELS MINIMUM, OR EXCEEDS ANY MAXIMUM SOUND LEVEL WITH A DURATION OF 60 SECONDS MINIMUM BY 5 DECIBELS MINIMUM, WHICHEVER IS LOUDER. SOUND LEVELS FOR ALARM SIGNALS SHALL BE 120 DECIBELS MAXIMUM. 2006 NFPA 1 AS AMENDED. 13.7.3.2.1 APPROVAL AND ACCEPTANCE: 13.7.3.2.1.2 BEFORE REQUESTING FINAL APPROVAL OF THE INSTALLATION, IF REQUIRED BY THE AHJ, THE INSTALLING CONTRACTOR SHALL FURNISH A WRITTEN STATEMENT STATING THAT THE SYSTEM HAS BEEN INSTALLED IN ACCORDANCE WITH APPROVED PLANS AND TESTED IN ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS AND APPROPRIATE NFPA REQUIREMENTS. [72:4.5.1.2]. 13.7.3.2.1.3 THE RECORD OF COMPLETION FORM, FIGURE 4.5.2.1 OF NFPA 72, SHALL BE PERMITTED TO BE PART OF THE WRITTEN STATEMENT REQUIRED IN 13.7.3.2.1.2. WHEN MORE THAN ONE CONTRACTOR HAS BEEN RESPONSIBLE FOR THE INSTALLATION, EACH CONTRACTOR SHALL COMPLETE THE PORTIONS OF THE FORM FOR WHICH THAT CONTRACTOR HAD RESPONSIBILITY. 13.7.3.2.1.4 THE RECORD OF COMPLETION FORM, FIGURE 4.5.2.1 OF NFPA 72, SHALL BE PERMITTED TO BE A PART OF THE DOCUMENTS THAT SUPPORT THE REQUIREMENTS OF 13.7.3.2.1.3. 2006 NFPA 1. ENSURE AUDIBILITY IS MET THROUGH ALL OCCUPIABLE AREAS AND SPACES. THIS WILL BE THOROUGHLY CHECKED AT TIME OF THE ALARM ACCEPTANCE TEST. 5. MANUAL FIRE ALARM BOXES: 13.7.1.4.7.3 A MANUAL FIRE ALARM BOX SHALL BE PROVIDED IN THE NATURAL EXIT ACCESS PATH NEAR EACH REQUIRED EXIT FROM AN AREA, UNLESS MODIFIED BY ANOTHER SECTION OF THIS CODE. 13.7.1.4.7.4 ADDITIONAL MANUAL FIRE ALARM BOXES SHALL BE LOCATED SO THAT, ON ANY GIVEN FLOOR IN ANY PART OF THE BUILDING, NO HORIZONTAL DISTANCE ON THAT FLOOR EXCEEDING 200 FT (6O M) SHALL NEED TO BE TRAVERSED TO REACH A MANUAL FIRE ALARM BOX [9.6.2.4]. 13.7.3.3.6 MANUAL FIRE ALARM BOXES SHALL BE LOCATED WITHIN 5 FT (1.5 M) OF THE EXIT DOORWAY OPENING AT EACH EXIT ON EACH FLOOR. THE LOCATION OF MANUAL FIRE ALARM BOXES MAY BE MODIFIED BY THE AHJ. 2006 NFPA 1 AS AMENDED. 6. PORTABLE FIRE EXTINGUISHERS: 13.6.1 GENERAL REQUIREMENTS: 13.6.1.1 THE INSTALLATION, MAINTENANCE, SELECTION, AND DISTRIBUTION OF PORTABLE FIRE EXTINGUISHERS SHALL BE IN ACCORDANCE WITH NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, AND SECTION 13.6. 2006 NFPA 1. 9. COORDINATE ELECTRICAL CONNECTIONS TO MECHANICAL & PLUMBING EQUIPMENT WITH DIVISION 15/23 PRIOR TO ROUGH-IN. SECURITY ALARM CONTROL PANEL SACP M J J AUDIBLE, BELL EMERGENCY GENERATOR VOLT METER, AMP METER GROUND ROD TRANSFER SWITCH XFSW KILOVOLT AMP KVA ABOVE FINISHED FLOOR AMPERE (AMP) CIRCUIT BREAKER CURRENT TRANSFORMER ARCHITECT / ARCHITECTURAL AUTOMATIC TRANSFER SWITCH CLOSED CIRCUIT TELEVISION EMERGENCY EXPLOSION PROOF EMERGENCY POWER OFF ELECTRIC WATER COOLER FIRE ALARM FULL LOAD AMPS FLUORESCENT ELECTRIC METALLIC TUBING ALTERNATE DOWN CIRCUIT CEILING CONDUIT KILOWATT HOUR KILOWATT KILOVOLT GROUND FAULT INTERRUPTER GROUND FAULT CIRCUIT INTERRUPTER GALVANIZED RIGID CONDUIT HORSEPOWER HIGH PRESSURE SODIUM HIGH VOLTAGE ISOLATED GROUND HERTZ GROUND ATS HP KW KWH KV HV HZ IG HPS GFCI GRC GRD GFI FLUOR FA FLA EP EPO EWC EMERG EMT CLG DN CT CCTV CKT CB C ALT ARCH AFF A POLYVINYL CHLORIDE CONDUIT TELEPHONE TERMINAL BOARD UNINTERRUPTABLE POWER SUPPLY TRANSIENT VOLTAGE SURGE SUPPRESSION TELEPHONE TERMINAL CABINET VAPOR PROOF WEATHER PROOF TRANSFORMER UNDERGROUND TYPICAL VOLT AMPERES VOLTAGE WP XFMR VP W WATTS UPS VA V UG TYP SOLENOID VALVE STARTER TAMPERPROOF TVSS TTC TTB SW TP SV STR SWITCH PANELBOARD SUB-DISTRIBUTION PANEL PUBLIC ADDRESS POWER FACTOR PHOTO ELECTRIC CELL NIGHT LIGHT CIRCUIT PF PWR SDP PNL PVC POWER PA PE NL MAIN LUGS ONLY MECHANICAL MANUAL TRANSFER SWITCH MAIN DISTRIBUTION PANEL MINIMUM CIRCUIT AMPS MAIN CIRCUIT BREAKER MOTOR CONTROL CENTER MECH MTS MLO MDP MCC MCB MCA MASTER ANTENNA TELEVISION LIGHTNING ARRESTOR LIGHTING LOW VOLTAGE KILOVOLT AMPS REACTIVE LTG LV MATV LA KVAR CONDUIT ELL: UP, DN. HOME RUN DESTINATION SHOWN CLOCK HANGER RECEPTACLE CONTACTOR, RELAY, SOLENOID PUSH BUTTON STATION PEDESTAL OUTLET: POWER, SIGNAL, COMBINATION SURFACE OUTLET STRIP: DIMENSION AS SHOWN WIRING CONCEALED IN FLOOR OR UNDERGROUND DISCONNECT SWITCH: FUSED, NON-FUSED MOTOR STARTER: MAGNETIC, COMBINATION WIRING CONCEALED IN CEILING OR WALL TELEPOWER POLE, POWER, COMBINATION FLUSH IN-FLOOR OUTLET: DUPLEX, COMBINATION, SIGNAL SPECIAL PURPOSE OUTLET AS NOTED, EMERGENCY MOTOR CONNECTION JUNCTION BOX CEILING RECEPTACLE: DUPLEX DENOTES RECEPTACLE ABOVE COUNTER WALL RECEPTACLE: SINGLE, DUPLEX, EMERGENCY, 4-PLEX WALL RECEPTACLE: EMERGENCY, 4-PLEX SHEET NOTE EXISTING TO BE RELOCATED NEW EXISTING TO REMAIN EQUIPMENT DESIGNATOR SEE SCHEDULE. EXISTING TO BE REMOVED E NIC NOT IN CONTRACT AIR SAMPLING DETECTOR, AIR SAMPLING DETECTOR CONTROL AIR SAMPLING DETECTION PORT DIGITAL ALARM COMMUNICATOR PR=PHOTOELECTRIC WITH RELAY, 2 AMP SPDT I=IONIZATION P=PHOTOELECTRIC IR=IONIZATION WITH RELAY, 2 AMP SPDT XXXX XXXX XXXX R=RELAY BASE, 2 AMP SPDT P=PHOTOELECTRIC I=IONIZATION AB=PHOTOELECTRIC WITH AUDIBLE BASE X FIRE ALARM SIGNAL ANNUCIATOR FIRE ALARM CONTROL PANEL # VISUAL, # INDICATES CANDELA # DUAL SYNCH MODULE SYNCH MODULE MONITOR MODULE, DUAL INPUT RELAY/CONTROL MODULE F190=190°F FIXED F135=135°F FIXED ROR2=190°F FIXED/RATE OF RISE ROR=135°F FIXED/RATE OF RISE RC=135°F RATE COMPENSATED THERMAL DETECTOR SURGE SUPPRESSER SPRINKLER SYSTEM SWITCH: FLOW, TAMPER FIRE SMOKE DAMPER 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, 2 PORT DATA PHOTOELECTRIC DUCT DETECTOR AUDIBLE/VISUAL, # INDICATES CANDELA SMOKE DETECTOR MANUAL FIRE ALARM STATION NAC POWER SUPPLY CIRCUIT BREAKER BUSS METER AUTOMATIC SWITCH PANEL FEEDER CALLOUT SWITCH, FUSED SWITCH TRANSFORMER EQUIPMENT WITH GROUND ELECTRICAL EQUIPMENT CABINET: SURFACE, RECESSED PANELBOARD: SURFACE, RECESSED CURRENT TRANSFORMER CABLE TRAY CARD READER KEY PAD PIN PAD C PP K CP CARD READER/PIN PAD CONBINATION ELECTRIC/MAGNETIC LOCK CONNECTION L H HIDDEN PUSH BUTTON DOOR MAGNETIC CONTACT CCTV CAMERA: FIXED, PAN/TILT/ZOOM A AUDIO DETECTOR/LISTENING DEVICE C ASD F E X R N 1 123 FS TS P XXXX X FSD ASD ASDC CM DACT DM DSM SM SS X NAC FSD FIRE SMOKE DAMPER BM BEAM SMOKE DETECTOR MAGNETIC DOOR HOLD OPEN M MOTION DETECTOR MD RI WIRING BY CONTRACTOR PUSHBUTTON NORMALLY OPEN CONTACT NORMALLY CLOSED CONTACT RELAY COIL (#14 AWG UNLESS NOTED OTHERWISE) SCHEMATIC SECURITY EQUIPMENT SIGNAL ONE-LINE POWER LIGHTING SYMBOLS ABBREVIATIONS FIRE ALARM NOTES (ALL SHEETS) PROJECT GENERAL NOTES (ALL SHEETS) FIRE ALARM SHEET LIST HA HA WW DIRECTION WW DIRECTION 3c 3A RECESSED 2X4 LUMINAIRE SURFACE MOUNTED 2X4 LUMINAIRE RECESSED 1X4 LUMINAIRE, SURFACE MOUNT SURFACE MOUNTED 2X2 LUMINAIRE, RECESSED SHADING OF ANY LUMINAIRE INDICATES CONNECTION TO ALTERNATE POWER SOURCE (EMERGENCY, UPS, STANDBY, ETC.) PER CIRCUITNG INDICATED SUSPENDED LINEAR LUMINAIRE SUSPENDED PENDANT LUMINAIRE (SIZE VARIES) RECESSED DOWNLIGHT, CEILING MOUNTED SURFACE DOWNLIGHT, CEILING MOUNTED RECESSED WALLWASH SURFACE WALLWASH RECESSED LINEAR WALLWASH SURFACE LINEAR WALLWASH RECESSED WALL MOUNTED LUMINAIRE SURFACE MOUNT FLUORESCENT LUMINAIRE TRACK LIGHTING WITH HEADS AS INDICATED. RECESSED CEILING ADJUSTABLE POINT SOURCE SURFACE CEILING ADJUSTABLE POINT SOURCE WALL MOUNTED LUMINAIRE FLUORESCENT STRIPLIGHT - POWER FEED SECTION, FEED THROUGH SECTION. LENGTH AS SHOWN UNDERCABINET FLUORESCENT STRIPLIGHT CONTINUOUS LINEAR SOURCE (LED, COLD CATHODE, NEON, FIBER OPTIC, ETC...) BATTERY POWER EMERGENCY UNIT EQUIPMENT (SEE LUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) - WALL, CEILING MOUNTED LUMINAIRE SCHEDULE ILLUMINATED EXIT SIGN, SHADED QUADRANT INDICATES FACES, ARROWS AS SHOWN BOLLARD POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD INDICATES ROTATED OPTICS POLE TOP MOUNTED LUMINAIRE IN-GRADE POINT SOURCE GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS LUMINAIRE MARKING CONVENTION LEGEND : HA = LUMINAIRE TYPE IDENTIFICATION. SEE 3c = CIRCUIT NUMBER VIA LOCAL SWITCH (LOWERCASE LETTER) THAT SERVES THE LUMINAIRE SERVES THE LUMINIARE. 3A = CIRCUIT NUMBER/UPPERCASE LETTER COMBINATION INDICATES LOW VOLTAGE RELAY OR LIGHTING CONTACTOR THAT SINGLE POLE SWITCH (SUPERSCRIPT DENOTES SIMILARLY MARKED LUMINAIRES CONTROLLED TOGETHER THREE WAY SWITCH FOUR WAY SWITCH KEY OPERATED SWITCH DIMMER SWITCH DIMMER SWITCH UNDER SEPARATE COVERPLATE SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN SWITCH IS "ON"). SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN SWITCH IS "OFF"). TIMER SWITCH LOW VOLTAGE, 6 BUTTON WALLSTATION, UPPER CASE LETTER SUPERSCRIPT INDICATES CONNECTION TO LOW VOLTAGE RELAY CONTROLLING SIMILARLY MARKED LUMINAIRES. WEATHERPROOF SWITCH LIGHTING CONTROL OVERIDE SWITCH, SEQ. PHOTOCELL TIME CLOCK OCCUPANCY SENSOR - WALL MOUNTED 360 DEGREE OCCUPANCY SENSOR - CEILING - AISLE/CORRIDOR OR 180 DEGREE COMBINATION OCCUPANCY SENSOR & SWITCH LIGHTING CONTROL PANEL AND ASSOCIATED COMPONENTS. PROVIDE 120V OR 277V CONTROL POWER AS REQUIRED OR AS INDICATED. REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSED TRANSFORMER. CONCEAL FROM VIEW. LCP ? OS OS OS OS TC PC OR1 5A,5B WP OS TS 5C 5A 4 PL P K 3 a TX D 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS. 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, 4 PORT DATA 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS. TEL 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS. 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, FLAT SCREEN DISPLAY. SET AT + 50". 1" EMT EXTENDED TO TOP OF BOTTOM FSD CORD OF ROOF TRUSS. ONE 1-1/2" EMT TO 4" SQUARE INPUT INPUT BOX AT +18" 4" SQUARE, 2 DEEP, CIRCULAR DEVICE RING, WI-FI ANTENNA 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, TELEPHONE. BACKBOX, CEILING MOUNTED. SUPPORT FROM CEILING STRUCTURE SYSTEM. SUBSCRIPT INDICATES A SEPARATE COMMUNICAITION NETWORK SYSTEM ACCESS 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS. 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, CARDREADER. 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS. 4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, CAMERA. CR C Tel: (503) 771-1986 Happy Valley, OR 97086 10555 SE 82nd Avenue, Suite 203 ALEX RIDLEY ELECTRICAL DESIGNER:[email protected] ENGINEERING REYES PASSION CREATIVITY SUSTAINABILITY R E V I S I O N S P R O J E C T N O. I S S U E D A T E © MERRYMAN BARNES ARCHITECTS, INC. S H E E T 942 OLIVE STREET 942 OLIVE STREET, EUGENE, OREGON 97401 OWNER: UNIVERSITY OF OREGON CAMPUS PLANNING, DESIGN & CONSTRUCTION CONTACT: MARTINA OXOBY 541.346.5880 15-0309 BID SET 09.25.2015 E0.0 COVER PAGE E0.0 COVER PAGE E0.1 SCHEDULES E1.0 DEMOLITION PLAN E2.0 FLOOR PLAN - LIGHTING E3.0 FLOOR PLAN - POWER E5.0 DIAGRAMS, SCHEDULES AND ENLARGED PLANS W

Transcript of SACP SECURITY ALARM CONTROL PANEL - pages.uoregon.edupages.uoregon.edu/moxoby/942Olive/942 Olive...

*

C

S

S

D

S

S

S

S

S

S

S

S

S

S

D

S

S

S

S

SR

G

AV

T

1. NOT ALL SYMBOLS & NOTES ARE NECESSARILY USED

ON THIS PROJECT.

2. INSTALLATION OF ALL ELECTRICAL EQUIPMENT SHALL

MEET STATE AND LOCAL CODES. PROVIDE

STRUCTURAL SEISMIC RATINGS/LABELS AND BRACING

PER IBC.

3. ALL CONTROL WIRING AND DEVICES SUCH AS

OVERLOAD DEVICES, PUSH-BUTTON STATIONS,

RELAYS, THERMOSTATS AND CONTROL DEVICES TO BE

PROVIDED AND INSTALLED UNDER MECHANICAL

CONTROLS. POWER WIRING WILL BE PER ELECTRICAL,

AS SHOWN ON DRAWINGS AND WRITTEN

SPECIFICATIONS. REFER TO MECHANICAL DRAWINGS

AND DATA SHEETS PRIOR TO BID AND INSTALLATION.

FUSE DISCONNECTS AND FUSES SHALL BE PROVIDED

BY DIVISION 16/26.

4. ALL PENETRATIONS OF WALLS AND CONCRETE SLABS

SHALL BE COORDINATED WITH ARCHITECT. SEAL ALL

OPENINGS WITH FIRE STOP AS REQUIRED.

5. PROVIDE EQUIPMENT GROUNDING (GREEN WIRE) AND

NEUTRAL (WHITE/GRAY WIRE) CONDUCTORS IN ALL

RACEWAYS. EQUIPMENT GROUNDING CONDUCTOR IS TO

BE BONDED TO ALL RACEWAY BOXES AND

ENCLOSURES ENCLOSING THE CIRCUIT CONDUCTORS.

6. FIRE ALARM CABLES SHALL BE PLENUM RATED.

RELOCATED SMOKE DETECTORS SHALL INSTALLED AND

BE TESTED PER NFPA 72, INTERNATIONAL FIRE CODE,

STATE AND LOCAL CODES. PROVIDE ACCEPTANCE

TESTING REPORTS WITH OPERATION AND MAINTENANCE

MANUALS.

7. ELECTRICAL EQUIPMENT LAYOUT SHOWN IN ENLARGED

ELECTRICAL PLANS ARE BASED UPON A BASIS OF

DESIGN MANUFACTURER'S EQUIPMENT. COORDINATE

EXACT SPACE REQUIREMENTS WITH EQUIPMENT

SUPPLIER. MAINTAIN EQUIPMENT CLEARANCES IN

COMPLIANCE WITH NEC AND MANUFACTURER

RECOMMENDATIONS.

8. COORDINATE ALL ELECTRICAL DEVICE LOCATIONS

(SWITCHES, RECEPTACLES, DATA OUTLETS, ETC) WITH

ARCHITECT AND CASEWORK SUPPLIER PRIOR TO

ROUGH-IN. DO NOT LOCATE ELECTRICAL DEVICES

BEHIND MIRRORS, CASEWORK OR BACKSPASHES.

1. FIRE SAFETY NOTE:

STRUCTURES UNDERGOING CONSTRUCTION,

ALTERATION, OR DEMOLITION OPERATIONS,

INCLUDING THOSE IN UNDERGROUND LOCATIONS,

SHALL COMPLY WITH NFPA 241, STANDARD FOR

SAFEGUARDING CONSTRUCTION, ALTERATION, AND

DEMOLITION OPERATIONS, AND THIS CHAPTER. 2006

NFPA 1.

2. FIRE SAFETY DURING ALTERATION:

16.4.4.1 WHERE THE BUILDING IS PROTECTED BY

FIRE PROTECTION SYSTEMS, SUCH SYSTEMS SHALL

BE MAINTAINED OPERATIONAL AT ALL TIMES DURING

ALTERATION.

16.4.4.2 WHERE ALTERATION REQUIRES MODIFICATION

OF A PORTION OF THE FIRE PROTECTION SYSTEM,

THE REMAINDER OF THE SYSTEM SHALL BE KEPT IN

SERVICE AND FIRE DEPARTMENT SHALL BE NOTIFIED.

16.4.4.3 WHEN IT IS NECESSARY TO SHUT DOWN

THE SYSTEM, THE AUTHORITY HAVING JURISDICTION

(AHJ) SHALL HAVE THE AUTHORITY TO REQUIRE

ALTERNATE MEASURES OF PROTECTION UNTIL THE

SYSTEM IS RETURNED TO SERVICE.

10.8.1.1 AS NECESSARY DURING EMERGENCIES,

MAINTENANCE, DRILLS, PRESCRIBED TESTING,

ALTERATIONS, OR RENOVATIONS, PORTABLE OR

FIXED FIRE-EXTINGUISHING SYSTEMS OR DEVICES OR

ANY FIRE-WARINING SYSTEM SHALL BE PERMITTED

TO BE MADE INOPERATIVE OR INACCESSIBLE. A

FIRE WATCH SHALL BE REQUIRED AS SPECIFIED IN

SECTIONS 13.3.4.3.5.2(3), 13.7.1.4.4, 16.5.4,

20.2.3.6, 34.6.3.3, 41.2.2.5, 41.2.2.6, 41.2.4, 41.3.4,

41.4.1, 34.5.4.3, AND 25.1.8 AT NO COST TO THE

AHJ. NFPA 1 2006, AS AMENDED.

3. AHJ APPROVAL:

13.1.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE

THAT CONSTRUCTION DOCUMENTS FOR ALL FIRE PROTECTION

SYSTEMS BE SUBMITTED FOR REVIEW AND APPROVAL AND A

PERMIT BE ISSUED PRIOR TO THE INSTALLATION,

REHABILITATION, OR MODIFICATIONS. FURTHER, THE AHJ

SHALL HAVE THE AUTHORITY TO REQUIRE THAT FULL

ACCEPTANCE TESTS OF THE SYSTEMS BE PREFORMED IN

THE AHJ'S PRESENCE PRIOR TO FINAL SYSTEM CERTIFICATION.

FIRE ALARM SYSTEMS; FIRE HYDRANT SYSTEMS;

FIR-EXTINGUISHING SYSTEMS; STANDPIPES; AND OTHER

FIRE-PROTECTION SYSTEMS AND APPURTENANCES REQUIRED

BY THIS CODE SHALL BE APPROVED BY THE AHJ AS TO

INSTALLATION AND LOCATION AND SHALL BE SUBJECT TO

ACCEPTANCE TESTS REQUIRED BY THE APPROPRIATE

COUNTY AGENCY. NFPA 1, CHAPTER 13 AS AMENDED.

4. DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS:

13.7.1.1 WHERE BUILDING FIRE ALARM SYSTEMS OR

AUTOMATIC FIRE DETECTORS ARE REQUIRED BY OTHER

SECTIONS OF THIS CODE, THEY SHALL BE PROVIDED AND

INSTALLED IN ACCORDANCE WITH NFPA 70, NFPA 72,

NATIONAL FIRE ALARM CODE, AND SECTION 13.7. 2006 NFPA

1.

FIRE ALARM SYSTEM INSTALLATION AND MAINTENANCE SHALL

BE IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE ALARM

CODE, AND 2006 NFPA 1.

13.7.1.4.9.8 AUDIBILITY. THE ALARM SIGNAL SHALL BE A

DISTINCTIVE SOUND, WHICH IS NOT USED FOR ANY OTHER

PURPOSE OTHER THAN THE FIRE ALARM. ALARM-SIGNALING

DEVICES SHALL PRODUCE A SOUND THAT EXCEEDS THE

PREVAILING EQUIVALENT SOUND LEVEL IN THE ROOM OR

SPACE BY 15 DECIBELS MINIMUM, OR EXCEEDS ANY

MAXIMUM SOUND LEVEL WITH A DURATION OF 60 SECONDS

MINIMUM BY 5 DECIBELS MINIMUM, WHICHEVER IS LOUDER.

SOUND LEVELS FOR ALARM SIGNALS SHALL BE 120 DECIBELS

MAXIMUM. 2006 NFPA 1 AS AMENDED.

13.7.3.2.1 APPROVAL AND ACCEPTANCE:

13.7.3.2.1.2 BEFORE REQUESTING FINAL APPROVAL OF THE

INSTALLATION, IF REQUIRED BY THE AHJ, THE INSTALLING

CONTRACTOR SHALL FURNISH A WRITTEN STATEMENT

STATING THAT THE SYSTEM HAS BEEN INSTALLED IN

ACCORDANCE WITH APPROVED PLANS AND TESTED IN

ACCORDANCE WITH THE MANUFACTURER'S SPECIFICATIONS

AND APPROPRIATE NFPA REQUIREMENTS. [72:4.5.1.2].

13.7.3.2.1.3 THE RECORD OF COMPLETION FORM, FIGURE

4.5.2.1 OF NFPA 72, SHALL BE PERMITTED TO BE PART OF

THE WRITTEN STATEMENT REQUIRED IN 13.7.3.2.1.2. WHEN

MORE THAN ONE CONTRACTOR HAS BEEN RESPONSIBLE FOR

THE INSTALLATION, EACH CONTRACTOR SHALL COMPLETE

THE PORTIONS OF THE FORM FOR WHICH THAT CONTRACTOR

HAD RESPONSIBILITY.

13.7.3.2.1.4 THE RECORD OF COMPLETION FORM, FIGURE

4.5.2.1 OF NFPA 72, SHALL BE PERMITTED TO BE A PART

OF THE DOCUMENTS THAT SUPPORT THE REQUIREMENTS OF

13.7.3.2.1.3. 2006 NFPA 1.

ENSURE AUDIBILITY IS MET THROUGH ALL OCCUPIABLE

AREAS AND SPACES. THIS WILL BE THOROUGHLY CHECKED

AT TIME OF THE ALARM ACCEPTANCE TEST.

5. MANUAL FIRE ALARM BOXES:

13.7.1.4.7.3 A MANUAL FIRE ALARM BOX SHALL BE

PROVIDED IN THE NATURAL EXIT ACCESS PATH NEAR EACH

REQUIRED EXIT FROM AN AREA, UNLESS MODIFIED BY

ANOTHER SECTION OF THIS CODE.

13.7.1.4.7.4 ADDITIONAL MANUAL FIRE ALARM BOXES SHALL

BE LOCATED SO THAT, ON ANY GIVEN FLOOR IN ANY PART

OF THE BUILDING, NO HORIZONTAL DISTANCE ON THAT

FLOOR EXCEEDING 200 FT (6O M) SHALL NEED TO BE

TRAVERSED TO REACH A MANUAL FIRE ALARM BOX [9.6.2.4].

13.7.3.3.6 MANUAL FIRE ALARM BOXES SHALL BE

LOCATED WITHIN 5 FT (1.5 M) OF THE EXIT

DOORWAY OPENING AT EACH EXIT ON EACH FLOOR.

THE LOCATION OF MANUAL FIRE ALARM BOXES MAY

BE MODIFIED BY THE AHJ. 2006 NFPA 1 AS

AMENDED.

6. PORTABLE FIRE EXTINGUISHERS:

13.6.1 GENERAL REQUIREMENTS:

13.6.1.1 THE INSTALLATION, MAINTENANCE,

SELECTION, AND DISTRIBUTION OF PORTABLE FIRE

EXTINGUISHERS SHALL BE IN ACCORDANCE WITH

NFPA 10, STANDARD FOR PORTABLE FIRE

EXTINGUISHERS, AND SECTION 13.6. 2006 NFPA 1.

9. COORDINATE ELECTRICAL CONNECTIONS TO

MECHANICAL & PLUMBING EQUIPMENT WITH DIVISION

15/23 PRIOR TO ROUGH-IN.

SECURITY ALARM CONTROL PANELSACP

M

JJ

AUDIBLE, BELL

EMERGENCY GENERATOR

VOLT METER, AMP METER

GROUND ROD

TRANSFER SWITCHXFSW

KILOVOLT AMPKVA

ABOVE FINISHED FLOOR

AMPERE (AMP)

CIRCUIT BREAKER

CURRENT TRANSFORMER

ARCHITECT / ARCHITECTURAL

AUTOMATIC TRANSFER SWITCH

CLOSED CIRCUIT TELEVISION

EMERGENCY

EXPLOSION PROOF

EMERGENCY POWER OFF

ELECTRIC WATER COOLER

FIRE ALARM

FULL LOAD AMPS

FLUORESCENT

ELECTRIC METALLIC TUBING

ALTERNATE

DOWN

CIRCUIT

CEILING

CONDUIT

KILOWATT HOUR

KILOWATT

KILOVOLT

GROUND FAULT INTERRUPTER

GROUND FAULT CIRCUIT INTERRUPTER

GALVANIZED RIGID CONDUIT

HORSEPOWER

HIGH PRESSURE SODIUM

HIGH VOLTAGE

ISOLATED GROUND

HERTZ

GROUND

ATS

HP

KW

KWH

KV

HV

HZ

IG

HPS

GFCI

GRC

GRD

GFI

FLUOR

FA

FLA

EP

EPO

EWC

EMERG

EMT

CLG

DN

CT

CCTV

CKT

CB

C

ALT

ARCH

AFF

A

POLYVINYL CHLORIDE CONDUIT

TELEPHONE TERMINAL BOARD

UNINTERRUPTABLE POWER SUPPLY

TRANSIENT VOLTAGE SURGE SUPPRESSION

TELEPHONE TERMINAL CABINET

VAPOR PROOF

WEATHER PROOF

TRANSFORMER

UNDERGROUND

TYPICAL

VOLT AMPERES

VOLTAGE

WP

XFMR

VP

W WATTS

UPS

VA

V

UG

TYP

SOLENOID VALVE

STARTER

TAMPERPROOF

TVSS

TTC

TTB

SW

TP

SV

STR

SWITCH

PANELBOARD

SUB-DISTRIBUTION PANEL

PUBLIC ADDRESS

POWER FACTOR

PHOTO ELECTRIC CELL

NIGHT LIGHT CIRCUIT

PF

PWR

SDP

PNL

PVC

POWER

PA

PE

NL

MAIN LUGS ONLY

MECHANICAL

MANUAL TRANSFER SWITCH

MAIN DISTRIBUTION PANEL

MINIMUM CIRCUIT AMPS

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MECH

MTS

MLO

MDP

MCC

MCB

MCA

MASTER ANTENNA TELEVISION

LIGHTNING ARRESTOR

LIGHTING

LOW VOLTAGE

KILOVOLT AMPS REACTIVE

LTG

LV

MATV

LA

KVAR

CONDUIT ELL: UP, DN.

HOME RUN DESTINATION SHOWN

CLOCK HANGER RECEPTACLE

CONTACTOR, RELAY, SOLENOID

PUSH BUTTON STATION

PEDESTAL OUTLET: POWER, SIGNAL, COMBINATION

SURFACE OUTLET STRIP: DIMENSION AS SHOWN

WIRING CONCEALED IN FLOOR OR UNDERGROUND

DISCONNECT SWITCH: FUSED, NON-FUSED

MOTOR STARTER: MAGNETIC, COMBINATION

WIRING CONCEALED IN CEILING OR WALL

TELEPOWER POLE, POWER, COMBINATION

FLUSH IN-FLOOR OUTLET: DUPLEX, COMBINATION, SIGNAL

SPECIAL PURPOSE OUTLET AS NOTED, EMERGENCY

MOTOR CONNECTION

JUNCTION BOX

CEILING RECEPTACLE: DUPLEX

DENOTES RECEPTACLE ABOVE COUNTER

WALL RECEPTACLE: SINGLE, DUPLEX, EMERGENCY, 4-PLEX

WALL RECEPTACLE: EMERGENCY, 4-PLEX

SHEET NOTE

EXISTING TO BE RELOCATED

NEW

EXISTING TO REMAIN

EQUIPMENT DESIGNATOR SEE SCHEDULE.

EXISTING TO BE REMOVED

E

NIC NOT IN CONTRACT

AIR SAMPLING DETECTOR, AIR SAMPLING DETECTOR CONTROL

AIR SAMPLING DETECTION PORT

DIGITAL ALARM COMMUNICATOR

PR=PHOTOELECTRIC WITH RELAY, 2 AMP SPDT

I=IONIZATION

P=PHOTOELECTRIC

IR=IONIZATION WITH RELAY, 2 AMP SPDT

XXXX

XXXXXXXX

R=RELAY BASE, 2 AMP SPDT

P=PHOTOELECTRIC

I=IONIZATION

AB=PHOTOELECTRIC WITH AUDIBLE BASE

X

FIRE ALARM SIGNAL ANNUCIATOR

FIRE ALARM CONTROL PANEL

# VISUAL, # INDICATES CANDELA

#

DUAL SYNCH MODULE

SYNCH MODULE

MONITOR MODULE, DUAL INPUT

RELAY/CONTROL MODULE

F190=190°F FIXED

F135=135°F FIXED

ROR2=190°F FIXED/RATE OF RISE

ROR=135°F FIXED/RATE OF RISE

RC=135°F RATE COMPENSATED

THERMAL DETECTOR

SURGE SUPPRESSER

SPRINKLER SYSTEM SWITCH: FLOW, TAMPER

FIRE SMOKE DAMPER

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, 2 PORT DATA

PHOTOELECTRIC DUCT DETECTOR

AUDIBLE/VISUAL, # INDICATES CANDELA

SMOKE DETECTOR

MANUAL FIRE ALARM STATION

NAC POWER SUPPLY

CIRCUIT BREAKER

BUSS

METER

AUTOMATIC SWITCH

PANEL

FEEDER CALLOUT

SWITCH, FUSED SWITCH

TRANSFORMER

EQUIPMENT WITH GROUND

ELECTRICAL EQUIPMENT

CABINET: SURFACE, RECESSED

PANELBOARD: SURFACE, RECESSED

CURRENT TRANSFORMER

CABLE TRAY

CARD READER

KEY PAD

PIN PAD

C

PP

K

CP CARD READER/PIN PAD CONBINATION

ELECTRIC/MAGNETIC LOCK CONNECTIONL

H HIDDEN PUSH BUTTON

DOOR MAGNETIC CONTACT

CCTV CAMERA: FIXED, PAN/TILT/ZOOM

A AUDIO DETECTOR/LISTENING DEVICE

CASD

F

E

X

R

N

1

123

FS TS

P

XXXX

X

FSD

ASD ASDC

CM

DACT

DM

DSM

SM

SS

X

NAC

FSD FIRE SMOKE DAMPER

BM BEAM SMOKE DETECTOR

MAGNETIC DOOR HOLD OPENM

MOTION DETECTORMD

RI

WIRING BY CONTRACTOR

PUSHBUTTON

NORMALLY OPEN CONTACT

NORMALLY CLOSED CONTACT

RELAY COIL

(#14 AWG UNLESS NOTED

OTHERWISE)

SC

HE

MA

TIC

SE

CU

RIT

YE

QU

IPM

EN

T

SIG

NA

L

ON

E-L

INE

PO

WE

R

LIG

HT

ING

SY

MB

OL

S

AB

BR

EV

IAT

ION

S

FIR

E A

LA

RM

NO

TE

S (

AL

L S

HE

ET

S)

PR

OJE

CT

GE

NE

RA

L N

OT

ES

(A

LL

SH

EE

TS

)

FIR

E A

LA

RM

SH

EE

T L

IST

HA

HA

WW DIRECTION

WW DIRECTION

3c

3A

RECESSED 2X4 LUMINAIRE

SURFACE MOUNTED 2X4 LUMINAIRE

RECESSED 1X4 LUMINAIRE, SURFACE MOUNT

SURFACE MOUNTED 2X2 LUMINAIRE, RECESSED

SHADING OF ANY LUMINAIRE INDICATES CONNECTIONTO ALTERNATE POWER SOURCE (EMERGENCY, UPS,STANDBY, ETC.) PER CIRCUITNG INDICATED

SUSPENDED LINEAR LUMINAIRE

SUSPENDED PENDANT LUMINAIRE (SIZE VARIES)

RECESSED DOWNLIGHT, CEILING MOUNTED

SURFACE DOWNLIGHT, CEILING MOUNTED

RECESSED WALLWASH

SURFACE WALLWASH

RECESSED LINEAR WALLWASH

SURFACE LINEAR WALLWASH

RECESSED WALL MOUNTED LUMINAIRE

SURFACE MOUNT FLUORESCENT LUMINAIRE

TRACK LIGHTING WITH HEADS AS INDICATED.

RECESSED CEILING ADJUSTABLE POINT SOURCE

SURFACE CEILING ADJUSTABLE POINT SOURCE

WALL MOUNTED LUMINAIRE

FLUORESCENT STRIPLIGHT - POWER FEEDSECTION, FEED THROUGH SECTION. LENGTH AS SHOWN

UNDERCABINET FLUORESCENT STRIPLIGHT

CONTINUOUS LINEAR SOURCE (LED, COLDCATHODE, NEON, FIBER OPTIC, ETC...)

BATTERY POWER EMERGENCY UNIT EQUIPMENT(SEE LUMINAIRE SCHEDULE FOR QUANTITY OF HEADS) - WALL, CEILING MOUNTEDLUMINAIRE SCHEDULE

ILLUMINATED EXIT SIGN, SHADED QUADRANTINDICATES FACES, ARROWS AS SHOWN

BOLLARD

POLE MOUNTED LUMINAIRE- SINGLE OR DUAL HEAD

INDICATES ROTATED OPTICS

POLE TOP MOUNTED LUMINAIRE

IN-GRADE POINT SOURCE

GARAGE LIGHTING LUMINAIRE WITH CUTOFF LOUVERS

LUMINAIRE MARKING CONVENTION LEGEND:

HA = LUMINAIRE TYPE IDENTIFICATION. SEE

3c = CIRCUIT NUMBER VIA LOCAL SWITCH(LOWERCASE LETTER) THAT SERVES THE LUMINAIRE

SERVES THE LUMINIARE.

3A = CIRCUIT NUMBER/UPPERCASE LETTERCOMBINATION INDICATES LOW VOLTAGERELAY OR LIGHTING CONTACTOR THAT

SINGLE POLE SWITCH (SUPERSCRIPT DENOTESSIMILARLY MARKED LUMINAIRES CONTROLLED TOGETHER

THREE WAY SWITCH

FOUR WAY SWITCH

KEY OPERATED SWITCH

DIMMER SWITCH

DIMMER SWITCH UNDER SEPARATE COVERPLATE

SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN

SWITCH IS "ON").SWITCH WITH PILOT LIGHT (PILOT IS "ON WHEN

SWITCH IS "OFF").

TIMER SWITCH

LOW VOLTAGE, 6 BUTTON WALLSTATION,UPPER CASE LETTER SUPERSCRIPT INDICATES

CONNECTION TO LOW VOLTAGE RELAYCONTROLLING SIMILARLY MARKED LUMINAIRES.

WEATHERPROOF SWITCH

LIGHTING CONTROL OVERIDE SWITCH, SEQ.

PHOTOCELL

TIME CLOCK

OCCUPANCY SENSOR - WALL MOUNTED

360 DEGREE OCCUPANCY SENSOR - CEILING - AISLE/CORRIDOR OR 180 DEGREE

COMBINATION OCCUPANCY SENSOR & SWITCH

LIGHTING CONTROL PANEL AND ASSOCIATEDCOMPONENTS. PROVIDE 120V OR 277VCONTROL POWER AS REQUIRED OR AS INDICATED.

REMOTE MOUNTED LINE TO LOW-VOLTAGE FUSEDTRANSFORMER. CONCEAL FROM VIEW.

LCP ?

OS

OSOS

OS

TC

PC

OR1

5A,5B

WP

OS

TS

5C

5A

4

PL

P

K

3

a

TX

D

1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS.

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, 4 PORT DATA1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS.

TEL 1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS.

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, FLAT SCREENDISPLAY. SET AT + 50". 1" EMT EXTENDED TO TOP OF BOTTOMFSD

CORD OF ROOF TRUSS. ONE 1-1/2" EMT TO 4" SQUARE INPUT

INPUT BOX AT +18"

4" SQUARE, 2 DEEP, CIRCULAR DEVICE RING, WI-FI ANTENNA

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, TELEPHONE.

BACKBOX, CEILING MOUNTED. SUPPORT FROM CEILING

STRUCTURE SYSTEM. SUBSCRIPT INDICATES A SEPARATE

COMMUNICAITION NETWORK SYSTEM ACCESS

1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS.

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, CARDREADER.

1" EMT EXTENDED TO TOP OF BOTTOM CORD OF ROOF TRUSS.

4" SQUARE, 2" DEEP, SINGLE GANG DEVICE RING, CAMERA.

CR

C

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E0.0

COVER PAGE

E0.0 COVER PAGE

E0.1 SCHEDULES

E1.0 DEMOLITION PLAN

E2.0 FLOOR PLAN - LIGHTING

E3.0 FLOOR PLAN - POWER

E5.0 DIAGRAMS, SCHEDULES AND ENLARGED PLANS

W

bklawa
Image

ROOM CONTROLLER SERVICE ZONE/RELAY SERVICE DIMMING PC/DAYLIGHT ZONE OCCUPANCY MODE OCCUPANT CONTROL

1 ENTRY 101 & HALL 101A

1A ENTRY & HALL NO NO OCCUPANCY ON/OFF

1B ENTRY & HALL DAYLIGHT NO YES VACANCY ON/OFF

1C ENTRY & HALL TRACK NO NO VACANCY ON/OFF

2 HOTELING/COWORK SPACE 107

2A HOTELING/COWORK NO NO VACANCY ON/OFF

2B HOTELING/COWORK DAYLIGHT NO YES VACANCY ON/OFF

2C HOTELING/COWORK TRACK NO NO VACANCY ON/OFF

3 WAR ROOM 102

3A WAR ROOM ZONE 1 YES NO VACANCY RAISE/LOWER

3B WAR ROOM ZONE 2 YES YES VACANCY RAISE/LOWER

3C WAR ROOM ZONE 3 YES YES VACANCY RAISE/LOWER

4 MEETING & INVENTION GREEN 103 & 105

4A OPEN MEETING WORK AREA 103 NO NO VACANCY ON/OFF

4B OPEN MEETING 103 NO NO VACANCY ON/OFF

4C INVENTION GREEN 104 YES NO VACANCY RAISE/LOWER

5 DISTANCE CONFERENCE 105

5A DISTANCE CONF ZONE 1 YES NO VACANCY RAISE/LOWER

5B DISTANCE CONF ZONE 2 YES NO VACANCY RAISE/LOWER

5C DISTANCE CONF ZONE 3 YES NO VACANCY RAISE/LOWER

6 CLASSROOM 110

6A CLASSROOM ZONE 1 YES NO VACANCY RAISE/LOWER

6B CLASSROOM ZONE 2 YES NO VACANCY RAISE/LOWER

6C CLASSROOM ZONE 3 YES NO OCCUPANCY RAISE/LOWER

7 FLEX SPACE 117

7A FLEX SPACE ZONE 1 NO NO VACANCY ON/OFF

7B FLEX SPACE ZONE 2 NO NO VACANCY ON/OFF

7C FLEX SPACE TRACK NO NO VACANCY ON/OFF

8 BREAK 112 & HALLWAY 121

8A BREAK & HALLWAY NO NO OCCUPANCY ON/OFF

8B BREAK & HALLWAY DAYLIGHT NO YES OCCUPANCY ON/OFF

8C SPARE - - - -

9 3D PRINTERS 125 & COMP. LAB 126

9A 3D PRINTERS 125 YES NO VACANCY RAISE/LOWER

9B COMPUTER LAB 126 ZONE 1 YES NO VACANCY RAISE/LOWER

9C COMPUTER LAB 126 ZONE 2 YES NO VACANCY RAISE/LOWER

10 DESIGN STUDIO 122

10A DESIGN STUDIO ZONE 1 YES YES VACANCY RAISE/LOWER

10B DESIGN STUDIO ZONE 2 YES YES VACANCY RAISE/LOWER

10C DESIGN STUDIO ZONE 3 YES YES VACANCY RAISE/LOWER

LIGHTING CONTROL SCHEDULE

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E0.1

SCHEDULES

LUMINAIRE SCHEDULEID DESCRIPTION MANUFACTURER MODEL FINISH MOUNTING MOUNTING HEIGHT LIGHT SOURCE POWER SUPPLY VOLTAGE LOAD (VA) COUNT NOTES

DA MAXIMUM 6" ROUND BY 6" HIGH SURFACE LED DOWNLIGHT. SELF FLANGEDSEMI-SPECULAR TRIM. MEDIUM DISTRIBUTION. WITH UL DAMP LOCATIONLISTING. LIGHT ENGINE AND DRIVER ACCESSIBLE FROM BELOW CEILING.

WILASPECTRUM

-

S608GV SERIES

-

SEMI SPECULAR CLEAR TRIM CEILING SURFACE 4000K, NOMINAL 1500 LUMEN LED 0-10V DIMMING DRIVER 120 V 30 VA 9

GA 2'X2' RECESSED LED LUMINAIRE FOR GRID CEILING. FOCAL POINTMETALUXLEDALITE

EQUATIONENCOUNTER

ARCFORM

WHITE GRID CEILING VARIES 4000K, NOMINAL 3500 LUMEN LED 0-10V DIMMING DRIVER 120 V 30 VA 44

HA NOMINAL 4' LONG INDUSTRIAL FLUORESCENT STRIP WITH STEEL HOUSING.PROVIDE WITH WIREGUARD.

METALUXLITHONIA

HE WILLIAMS

SNFC77

WHITE CEILING OR WALLSURFACE

VARIES (2) 4100K, 3100 LUMEN T8 FLUORESCENT PROGRAM RAPID STARTELECTRONIC BALLAST

120 V 60 VA 12

HB NOMINAL 3" HIGH BY 1 1/2" WIDE FLUORESCENT SURFACE STRIP LUMINAIREWITH STEEL HOUSING AND WHITE ACRYLIC LENS. PROVIDE IN CONTINUOUSRUNS AS SHOWN ON DRAWINGS.

PRUDENTIALNULITEPRIMUS

AXIS

HALFSNAP17N

ALX2BOX MINI

AS SELECTED BY ARCHITECT CEILING SURFACE VARIES (1) 4100K, 3100 LUMEN T8 FLUORESCENT PROGRAM RAPID STARTELECTRONIC BALLAST

120 V 30 VA 9 2

LA NOMINAL 3" HIGH BY 1 1/2" WIDE FLUORESCENT PENDANT STRIP LUMINAIREWITH STEEL HOUSING AND WHITE ACRYLIC LENS. PROVIDE IN CONTINUOUSRUNS AS SHOWN ON DRAWINGS. PROVIDE AIRCRAFT CABLE MOUNTINGHARDWARE.

PRUDENTIALNULITEPRIMUS

AXIS

HALFSNAP17N

ALX2BOX MINI

AS SELECTED BY ARCHITECT PENDANT VARIES (1) 4100K, 3100 LUMEN T8 FLUORESCENT PROGRAM RAPID STARTELECTRONIC BALLAST

120 V 30 VA 118 2

LB NOMINAL 4' LONG BY 10" WIDE INDUSTRIAL LED HIGH-BAY LUMINAIRE WITHSTEEL HOUSING. PROVIDE WITH WHITE STRAIGHT BLADE LOUVER, PROVIDE

AIRCRAFT CABLE PENDANT MOUNTING HARDWARE.

LITHONIAMETALUX

-

MSLILED

-

MATTE WHITE PENDANT 13'-0" AFF 4000K, NOMINAL 8000 LUMEN LED 0-10V DIMMING DRIVER 120 V 75 VA 32

SA LOW PROFILE, CAST ALUMINUM WALL MOUNT LED DIRECT/INDIRECTLUMINAIRE WITH UV STABILIZED LENSES AND GASKETS. UL WET LOCATIONLISTING.

PRISMAWE-EF

-

MIMIK620

-

AS SELECTED BY ARCHITECT WALL SURFACE 10'-0" AFF 4000K, NOMINAL 1400 LUMEN DIRECT AND1400 LUMEN INDIRECT LED

0-10V DIMMING DRIVER 120 V 45 VA 7

T1 LOW PROFILE, SINGLE CIRCUIT TRACK WITH 250VA OR 2A CURRENTLIMITING CIRCUIT BREAKER POWER FEED.

BRUCKHALOJUNO

ECO AS SELECTED BY ARCHITECT PENDANT VARIES N/A N/A 120 V 250 VA 9

TA1 EXISTING TRACK HEAD LUMINAIRES TO BE REUSED ---

---

AS SELECTED BY ARCHITECT TRACK VARIES 4000K, NOMINAL 600 LUMEN INTEGRALDRIVER PAR30L LED LAMP WITH 36 DEGREE

MEDIUM FLOOD BEAM

INTEGRAL DRIVER 120 V 15 VA 14 1

TA2 EXISTING TRACK HEAD LUMINAIRES TO BE REUSED ---

---

AS SELECTED BY ARCHITECT TRACK VARIES 4000K, NOMINAL 600 LUMEN INTEGRALDRIVER PAR30L LED LAMP WITH 8-15

DEGREE SPOT BEAM

INTEGRAL DRIVER 120 V 15 VA 8 1

VA NOMINAL 14" HIGH BY 5" WIDE BY MAXIMUM 4" PROJECTION WALL MOUNTCYLINDRICAL VANITY LUMINAIRE. OPAL GLASS AND PLATED STEELCONTSTRUCTION. PROVIDE WITH UL WET LOCATION AND ADA LISTINGS.

WACEUREKA

LIGHTOLIER

ELEMENTUMSILENE WALLVETRO WALL

AS SELECTED BY ARCHITECT WALL SURFACE 5'-6" AFF 4000K, NOMINAL 700 LUMEN LED 0-10V DIMMING DRIVER 120 V 20 VA 4

XA SURFACE OR PENDANT MOUNT, EDGE LIT LED EXIT SIGN LUMINAIRE WITHEXTRUDED ALUMINUM HOUSING AND 90 MINUTE BATTERY BACKUP.PROVIDE SINGLE OR DOUBLE FACE AS REQUIRED

LITHONIASURE LITESCHLORIDENAVILITE

EDGEUX44R

NXESA

AS SELECTED BY ARCHITECT PENDANT ORSURFACE

VARIES GREEN LED THERMALLY PROTECTED LEDDRIVER

120 V 3 VA 8

NOTES

A THIS LUMINAIRE SCHEDULE IS NOT COMPLETE WITHOUT A COPY OF THE PROJECT MANUAL CONTAINING DIVISION 26 SPECIFICATIONS.

B VERIFY LUMINAIRE VOLTAGE WITH BRANCH CIRCUIT PRIOR TO ORDERING.

C PROVIDE MINIMUM 82 CRI, HIGH PERFORMANCE FLUORESCENT LAMPS ONLY. MINIMUM 25,000 HOUR LIFE.

D PROVIDE MINIMUM 70 CRI, METAL HALIDE LAMPS, MINIMUM 25,000 HOUR LIFE.

E COORDINATE ALL LUMINAIRE MOUNTING WITH CEILING TYPES IN ALL LOCATIONS PRIOR TO ROUGH-IN.

F PROVIDE MINIMUM 12" ADJUSTABILITY IN AIRCRAFT CABLE HUNG LUMINAIRES, IF USED. COIL EXCESS CABLE ABOVE CEILING FOR FUTURE ADJUSTMENT.

G ALL FLUORESCENT LAMPS TO COMPLY WITH FEDERAL TOXIC CHARACTERISTIC LEACHING PROCEDURE (TCLP) REQUIREMENTS, WHERE REQUIRED.

H ALL LED LUMINAIRES TO BE SUPPLIED WITH A MINIMUM 5 YEAR WARRANTY.

I ALL ELECTRONIC BALLASTS AND DRIVERS TO COMPLY WITH REDUCTION OF HAZARDOUS SUBSTANCES (ROHS) REQUIREMENTS.

J LIGHT OUTPUT LISTED IN THIS SCHEDULE IS DELIVERED LUMENS.

K LUMINAIRE COUNT IN THIS SCHEDULE FOR REFERENCE ONLY. CONTRACTOR RESPONSIBLE FOR OBTAINING EXACT LUMINAIRE QUANTITIES FROM FLOOR PLANS FOUND IN CONTRACT DOCUMENTS.

L CONFIRM ALL LUMINAIRE FINISHES, MOUNTING AND PENDANT HEIGHTS WITH ARCHITECT.

1 CLEAN AND RELAMP EXISTING "EYEBALL" TRACK HEAD LUMINAIRES. PAINT AS DIRECTED BY ARCHITECT. PROVIDE TRACK ADAPTER IF REQUIRED TO FIT TRACK SELECTED. PROVIDE ELV DIMMABLE, 4000K, 25 DEGREE BEAM, MINIMUM 90CRI, 600 LUMEN PAR30L LED RETROFIT LAMP, PROVIDE SORAASP30L-12-36D-940-03 OR APPROVED EQUAL. REFER TO DEMOLITION PLANS FOR MORE INFORMATION.

2 PROVIDE BID ALTERNATE PRICING INFORMATION TO PROVIDE ALTERNATE LED LUMINAIRES INSTEAD OF BASE BID LINEAR FLUORESCENT SELECTIONS. REFER TO BID ALTERNATE LUMINAIRE SCHEDULE FOR LUMINAIRE SELECTIONS.

BID ALTERNATE LUMINAIRE SCHEDULEID DESCRIPTION MANUFACTURER MODEL FINISH MOUNTING MOUNTING HEIGHT LIGHT SOURCE POWER SUPPLY VOLTAGE LOAD (VA) COUNT NOTES

HB - ALT NOMINAL 3" HIGH BY 1 1/2" WIDE LED SURFACE STRIP LUMINAIRE WITHSTEEL HOUSING AND WHITE ACRYLIC LENS. PROVIDE IN CONTINUOUSRUNS AS SHOWN ON DRAWINGS.

PRUDENTIALNULITEPRIMUS

AXIS

HALFSNAP17N

ALX2BOX MINI

MATTE WHITE CEILING SURFACE VARIES 4000K, 600 LUMEN PER FOOT LED 0-10V DIMMING DRIVER 120 V 60 VA 1

LA - ALT NOMINAL 3" HIGH BY 1 1/2" WIDE LED PENDANT STRIP LUMINAIRE WITHSTEEL HOUSING AND WHITE ACRYLIC LENS. PROVIDE IN CONTINUOUSRUNS AS SHOWN ON DRAWINGS. PROVIDE AIRCRAFT CABLE MOUNTINGHARDWARE.

PRUDENTIALNULITEPRIMUS

AXIS

HALFSNAP17N

ALX2BOX MINI

MATTE WHITE PENDANT VARIES 4000K, 600 LUMEN PER FOOT LED 0-10V DIMMING DRIVER 120 V 30 VA 1

MECHANICAL & PLUMBING EQUIPMENT CONNECTION SCHEDULETAG # DESCRIPTION PANEL CIRCUIT VOLTAGE LOAD (HP) LOAD (FLA) LOAD (MCA) LOAD (VA) POLES BREAKER FEEDER DISCONNECT TYPE DISCONNECT BY STARTER BY

AHU 1 CONDENSING GAS FURFACE 1N2-1 2 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

AHU 2 CONDENSING GAS FURFACE 1N2-1 4 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

AHU 3 CONDENSING GAS FURFACE 1N2-1 6 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

AHU 4 CONDENSING GAS FURFACE 1N2-1 8 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

AHU 5 CONDENSING GAS FURFACE 1N2-1 10 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

AHU 6 CONDENSING GAS FURFACE 1N2-1 12 120 V - 5 A 5 A 1200 VA 1 20/1 20A SWITCH DIV. 26 N/A

CU 1 CONDENSING UNIT 1N2-1 1,3,5 208 V - 25 A 30 A 8000 VA 3 30/3 30A FUSIBLE DIV. 26 N/A

CU 2 CONDENSING UNIT (DUCTLESS SPLIT SYSTEM) 1N2-1 32,34,36 208 V - 25 A 30 A 7200 VA 3 30/3 30A FUSIBLE DIV. 26 N/A

MAU 1 MAKE UP AIR UNIT 1N2-1 38,40,42 208 V 5 30 A 35 A 9600 VA 3 40/3 40A FUSIBLE DIV. 26 N/A

bklawa
Image

OLIV

E S

TR

EE

T

BROADWAY ALLEY

OLIV

E A

LLE

Y

FD

1

2

3

4

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E1.0

DEMOLITION PLAN

1/8" = 1'-0"1

DEMOLITION PLAN - ELECTRICAL

XKEYED NOTES2 ALL LIGHTING, TELECOM, FIRE ALARM AND OTHER

MISC ELECTRICAL INFRASTRUCTURE TO BE

DISCONNECTED AND REMOVED. DEMOLISH ALL

ELECTRICAL SYSTEMS COMPLETE INCLUDING, ALL

J-BOXES, DEVICE, CONDUIT, WIRING, PANELS AND

ASSOCIATED HARDWARE. PATCH, SEAL AND/OR

REPAIR ANY OPENINGS, PENETRATIONS AND/OR

DAMAGE TO EXISTING TO REMAIN ELEMENTS

INCLUDING WALLS FLOORS AND CEILINGS

RESULTING FROM ELECTRICAL DEMOLITION WORK.

3 ALL EXTERIOR LIGHTING, TELECOM, FIRE ALARM AND

OTHER MISC ELECTRICAL INFRASTRUCTURE TO BE

DISCONNECTED AND REMOVED. DEMOLISH ALL

ELECTRICAL SYSTEMS COMPLETE INCLUDING, ALL

J-BOXES, DEVICES, CONDUIT, WIRING, PANELS AND

ASSOCIATED HARDWARE. PATCH AND SEAL ALL

REMAINING PENETRATIONS WATERTIGHT.

4 COORDINATE DISCONNECTION AND DEMOLITION OF

BUILDING ELECTRIC SERVICE METER, CT

ENCLOSURE AND DISCONNECT WITH EUGENE

WATER AND ELECTRIC BOARD.

1 EXISTING 'EYEBALL' TRACK LUMINAIRES TO BE

DISCONNECTED AND REMOVED FOR REUSE DURING

NEW CONSTRUCTION PHASE. REMAINING LIGHTING,

TELECOM, FIRE ALARM AND OTHER MISC

ELECTRICAL INFRASTRUCTURE TO BE

DISCONNECTED AND REMOVED. DEMOLISH ALL

ELECTRICAL SYSTEMS COMPLETE INCLUDING, ALL

J-BOXES, DEVICES, CONDUIT, WIRING, PANELS AND

ASSOCIATED HARDWARE. PATCH, SEAL AND/OR

REPAIR ANY OPENINGS, PENETRATIONS AND/OR

DAMAGE TO EXISTING TO REMAIN ELEMENTS

INCLUDING WALLS FLOORS AND CEILINGS

RESULTING FROM ELECTRICAL DEMOLITION WORK.

SHEET NOTESA DEMOLISHED ELEMENTS ARE SHOWN DASHED.

DEMOLITION OF STRUCTURAL AND ARCHITECTURAL

ELEMENTS AND BUILDING EQUIPMENT BY OTHERS

AND SHOWN FOR REFERENCE ONLY.

B EXISTING ELEMENTS AND WORK TO REMIAN ARE

INDICATED BY POCHE AND/OR SOLID LINES.

bklawa
Image

$O

S

$OS

$OS

$O

S

$OS

$O

S

$O

S RC

RC

RC

RC

OS

OS

OS

OS OS

OS

OS

OS OS

OS

OS

OS

OS OS

OSOS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS OS OS

OSOS

OS

OS

OS

OS

PC

PC

PC

RC

RC

RC

TC

$D$

D

$D$

D

$LV

$LV

$LV

RC

RC

$LV$LV

$LV

$LV $LV

$LV $LV

$LV

$D

$LV

existing overheadgarage door w/new 'knee wall' atbase

1:20 SLOPE

1:20 SLOPE

1:20 SLOPE

OLIV

E S

TR

EE

T

BROADWAY ALLEY

OLIV

E A

LLE

Y

coffeeH₂O

copy/print

VLS6.60laser

uPrintSE

Dimension1200es

uPrintSE

uPrintSE

uP

rint

SE

uPrintSE

uPrintSE

Dimension1200es

Dimension1200es

Dimension1200es

Dimension1200es

Dimension1200es

$O

S

PC

OS

$LV

RC

$LV

$LV

PC

PC

PC

PC

PC

C

C

C

CR

CR

C

C

W

W

WW

W

3

E5.0

DA

HAHA

HA

HAHA

DA DADAVA

DA

DA HA

HA

HA

HA

HB

HB

HB

HB

HBHB

VAVA

VA

T1

T1T1

T1

LB LB

LB

LB LB

LB

LBLBLB

LB

LBLB

LB LB

LBLB

LA LA

HA

LA

LALA

LA LA

LA

LA LA LA

LA

LA LA

LA LA LA

LALA LA

LA

LA LA

DA

LA

LA LA LA LA LA

ba a

b

2A,2B,2C

ROOM CONTROLLER 2

ROOM CONTROLLER 1

ROOM CONTROLLER 8

SA

SA

SA

SA

SASASA

XA

XA

XA

XA

XA

XA

XA

XA

TA1

TA2

TA1

TA2

TA1 TA1 TA1TA2 TA1 TA1

TA1

TA1

TA1

TA1 TA2 TA1

TA1 TA2 TA1

LB LB LB LB

LBLBLBLBLB

LB LB LB LB LB

LA LA

HA

HA

LB

GA GAGAGA

GA GA

GAGA

GA GA

GAGA

GA GA

GA GA

GAGA

GA GA GA

GAGAGA

GAGAGA

GA GA GA

LB

LA LA

LA LA

5C, 45B, 4

5B, 4 5C, 4

5C, 45B, 4

5B, 4 5C, 4

5A, 45A, 4

4C, 4 4C, 4 4C, 4

4C, 44C, 44C, 4

3C, 4 3C, 4

3C, 43A, 4

3A, 4 3B, 4 3B, 4

3B, 43B, 43A, 4

8 8

8

88

a, 8 a, 8C, 8

a, 8 a, 8

6

2

6A

,6B

,6C

6A

,6B

,6C

GA

b, 8 b, 8

GA

2C, 6

2B, 6 2A, 6

2A, 6

2A, 6

2A, 6

12

2A,2B,2C

12

1C, 101C, 10

1212

22

22

GA

GA

GA

GA

GA

GA

GAGA

GA

GA

GA

GA

6C, 8 6C, 8

6C, 8

6A, 8

6A, 8

6A, 8

6A, 86B, 8

6B, 8

6B, 8

6B, 8

6C, 8

2

2

5

5

5

5

2

1

DISTANCE CONFERENCE

105

OPEN MEETING

103

INVENTION GREEN SPACE

104

WAR ROOM

102

ELEC

119MECH

120

IDF

118

FLEX SPACE

117

ENTRY

101

HALLWAY 1

101A

STORAGE

111

JANITOR

116

CLASSROOM

110

HOTELING/ COWORKING

106

COPY/PRINT

107

SMALL CONFERENCE

109

SMALL CONFERENCE

108

DESIGN STUDIO

122

STUDIO STORAGE

123

FIRE SPRINKLER

124

HALLWAY 2

121BREAK AREA

112

UNISEX TOILET

113

WOMEN'S TOILET

115 MEN'S TOILET

114

3D PRINTERS/ POLYMERS SHOP

125

COMPUTER LAB

126

1A, 121A, 121A, 121A, 121A, 121A, 12

1A, 12 1B, 12 1A, 12

1B, 12 1A, 12

1A, 12

1B, 12

1B, 12

1B, 12

4B, 12 4A, 12

33

8A, 18A, 1

3 333

3

3 3

3

3

9A, 3 9A, 3

9A, 3

9A, 3

9A, 39A, 3

9A, 3 9A, 3 9A, 3

9A, 39A, 3

3A

,3B

,3C5

A,6

B,5

C

1A, 12

4C

4A

,4B

4A

,4B

1

2

1 1

1B, 121A, 121A, 12

1B, 12

1A, 12

1B, 12

1A, 12

1B, 12

1A, 12

1A, 12

1B, 12

1A, 12

1B, 12

1A, 12

1B, 12

1A, 12

1B, 12

1B, 12

1A, 121B, 12

2A, 6

2B, 6

2A, 6

2B, 6

2A, 6 2B, 6

2A, 6

2B, 6

2A, 6

2B, 6 2A, 6

2B, 6

2A, 6

2B, 6

2A, 6

2B, 6

2B, 6

2A, 6

2B, 6

2A, 6

2B, 62A, 6

2B, 6

3

4

5

6

81

2

7

7

7

9

7

8B, 1 8B, 1

7A, 17A, 1 7A, 1

7B, 17B, 1

7B, 1

7B, 1 7A

,7B

,7C

7A,7B,7C

9A

9B

,9C

9B, 3 9B, 3

9C, 39C, 3

9C, 3 9C, 3

10A, 710B, 710B, 710C, 710C, 7

10C, 7 10C, 7 10B, 7 10B, 7 10A, 7

10C, 7 10C, 7 10B, 7 10B, 7 10A, 7

3

8A, 18B, 1

8A, 18A, 1

8B, 1

8A, 1

8B, 1

8A, 1

8B, 1

8A, 1

1

8B, 1

8A, 1

8B, 1 8A, 1

8B, 1

8A, 1

8A, 1

8B, 1

10A

,10B

,10C

10A,10B,10C

2

2

222

2

2

22

TA2

T1

TA2 TA2

7C, 5

7C, 5

2

2

DA

DA

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E2.0

FLOOR PLAN - LIGHTING

1/8" = 1'-0"1

FLOOR PLAN - LIGHTING

SHEET NOTESXKEYED NOTES1 PROVIDE WALLBOX DIMMING PIR VACANCY SENSOR,

LUTRON MSCL-VP153M OR EQUIVALENT.

2 PROVIDE LUMINAIRE INDICATED WITH EMERGENCY

BATTERY PACK TO PRODUCE MINIMUM 1000 LUMENS

FOR 90 MINUTES. PROVIDE BATTERY PACKS WITH

SWITCHED AND UNSWITCHED INPUTS - CONNECT SO

THAT EMERGENCY LUMINAIRE CONTROLLED ALONG

WITH ADJACENT LUMINAIRES EXCEPT IN THE EVENT

OF A POWER FAILURE.

3 PROVIDE ASTRONOMICAL TIMECLOCK FOR CONTROL

OF EXTERIOR LIGHTING.

A ALL LIGHITNG ON THIS FLOOR PLAN IS CONNECTED

TO PANEL 1N2-3.

B CONFIRM ALL FIXTURE MOUNTING HEIGHTS WITH

ARCHITECT PRIOR TO ROUGH-IN.

bklawa
Image

existing overheadgarage door w/new 'knee wall' atbase

1:20 SLOPE

1:20 SLOPE

1:20 SLOPE

OLIV

E S

TR

EE

T

BROADWAY ALLEY

OLIV

E A

LLE

Y

coffeeH₂O

copy/print

VLS6.60laser

uPrintSE

Dimension1200es

uPrintSE

uPrintSE

uP

rint

SE

uPrintSE

uPrintSE

Dimension1200es

Dimension1200es

Dimension1200es

Dimension1200es

Dimension1200es

C

C

C

CR

CR

C

C

W

W

WW

W

J

J

W

W

W

W

J

W

J

J

J

J

J

J

J

J

J

J

3

E5.0E5.0

2

PNL-1N2-4

GFI16

GFI16

AB GFI19

AB GFI19

AB GFI19

AB GFI19

AB GFI21

AB GFI21

AB GFI21

WP GFI11

AB2

AB4

AB2

AB4

AB6

AB11

AB11

AB13

AB11

AB9

AB9

9

AB7

AB7

AB5

AB5

AB1

AB3

WP GFI5 WP GFI

8

PJ6

PJ4

PJ9

PJ7

GFI11

P18 P

16P14

P14

P16

P18

PJ10

PM22

PJ18

3

1

CU- 2

5

55

6

6

66

8

10

8

10

12

12

8

AB13

7

AB3

1

AB1

PANEL 1N2-4

7

7

7

7

9

9

9

9

11

GFI11

11

1513

13

17 15 17

11

AB23

AB23

CM27

REF25

4

4

4

4

6 66

6

2

2

2

88

10

10

10

2 8

14 1212

14 14 1412 12

14

16

16

16

16

18

18

18 18

20

20

20

20

20

24 24

2424

24

24

2628

2628

AHU- 5 AHU- 1

AHU- 2

CU- 1

MAU- 1

AHU- 6

AHU- 3

AHU- 4

ENTRY

101

HALLWAY 1

101A

WAR ROOM

102

OPEN MEETING

103

INVENTION GREEN SPACE

104

DISTANCE CONFERENCE

105

ELEC

119

MECH

120

IDF

118

STORAGE

111

JANITOR

116

CLASSROOM

110HOTELING/ COWORKING

106

SMALL CONFERENCE

109COPY/PRINT

107

SMALL CONFERENCE

108

MEN'S TOILET

114

WOMEN'S TOILET

115

3D PRINTERS/ POLYMERS SHOP

125

UNISEX TOILET

113

BREAK AREA

112

COMPUTER LAB

126

HALLWAY 2

121

FLEX SPACE

117

DESIGN STUDIO

122STUDIO STORAGE

123

FIRE SPRINKLER

124

4

1

1

1

1

1

1

2

1

1

1

1

11

1

1

1

3

EWEB VAULT

4

(2) 3" PVC C. 36" COVER - POWER

(1) 3" PVC C. 36" COVER - TCOM

5

6

PEND

PEND

PEND

TEL

FSD

TEL

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

R

7

8

7

98

9

1

R

1

R

1

R

1

1

10

9

7

8

1

R

1

1 1 1

1

1

1

1

PF-114

PF-214

PF-314

PF-414

PF-514

11

11

11

11

1112

1212

12

12

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E3.0

FLOOR PLAN - POWER

1/8" = 1'-0"1

FLOOR PLAN - POWER

SHEET NOTES XKEYED NOTESA REYES ENGINEERING INC. HAS CONDUCTED

PRELIMINARY COORDINATION OF THE ELECTRICPOWER SERVICE WITH EUGENE WATER ANDELECTRIC BOARD. CONTRACTOR RESPONSIBLE FORFINAL COORDINATION OF ELECTRIC SERVICE WITHROBERT WILLIAMS AT EUGENE WATER ANDELECTRIC BOARD - 541-685-7170.

B EXCEPT WHERE NOTED ON PLANS & SCHEDULES,ALL RECEPTACLES AND EQUIPMENT SHOWN ON THISFLOOR PLAN ARE CONNECTED TO PANEL 1N2-2.

4 STUB CONDUIT FOR FIBER OPTIC SERVICE IN IDFCLOSET AS DIRECTED BY OWNER. PROVIDEPULLSTRING.

5 CONTRACTOR TO PROVIDE NEW SERVICE LATERALCONDUIT AND CONDUCTORS. COORDINATETERMINATION OF CONDUITS WITH EWEB AT VAULTAS SHOWN. REFER TO SINGLE LINE DIAGRAM ONSHEET E5.0 FOR CONDUCTOR SIZE AND QUANTITIES.

6 CONTRACTOR TO PROVIDE CONDUIT FORCONNECTION TO DOWNTOWN FIBER LOOP. FIBEROPTIC CABLE TO BE INSTALLED BY OTHERS.COORDINATE TERMINATION OF CONDUIT WITH EWEBAND CITY OF EUGENE AT EWEB VAULT AS SHOWN.

7 PROVIDE POWER CONNECTION TO OVERHEADPROJECTOR,. SET RECEPTACLE IN CEILING.LOCATION OF PROJECTOR TO BE CONFIRMED WITHARCHITECT PRIOR TO ROUGH IN.

8 PROVIDE 4" BY 4" BY 4" CEILING BACKBOX WITH TWOGANG DEVICE RING FOR OVERHEAD PROJECTOR,HDMI AND CATEGORY 6 CABLE CONNECTIONS TOOVERHEAD PROJECTOR.

9 PROVIDE 4" BY 4" BY 4" WALL BACKBOX WITH TWOGANG DEVICE RING FOR OVERHEAD PROJECTOR,HDMI AND CATEGORY 6 CABLE CONNECTIONS TOOVERHEAD PROJECTOR,. PROVIDE 1-1/2 INCH EMT TOTOP OF LOWER CORD OFTRUSS ELEVATION.

10 PROVIDE TWO: 2 INCH EMT SLEEVES WITHCONNECTORS AND FIBER BUSHINGS FORCOMMUNICATIONS CABLES TO PASS THROUGHWALL. FIRE SEAL SLEEVES AFTER CABLEINSTALLATION.

11 PROVIDE 4" BY 4" BY 4" WALL BACKBOX WITH SINGLEGANG DEVICE RING FOR CEILING PADDLE FANMANUAL CONTROLS. PROVIDE 3/4 INCH EMT TOPADDLE FAN BACKBOX.

12 PROVIDE 4" BY 4" BY 4" BACKBOX FOR PADDLE FANCONNECTION AND MOUNTING. PROVIDE WITH DEVICERING AS REQUIRED BY FAN MANUFACTURER.SECURELY SUPPORT TO STRUCTURE TO INERTIALLYANCHOR THE FAN BASE AGAINST FAN VIBRATIONTRANSMISSION.

1 DIV. 26 CONTRACTOR TO PROVIDE RACEWAYS ASREQUIRED TO SERVE SECURITY/TELECOMEQUIPMENT BY OTHERS. COORDINATE EXACTLOCATIONS AND REQUIREMENTS WITH SECURITYCONTRACTOR AND/OR EQUIPMENT SUPPLIER.

2 PROVIDE (1) #6AWG BARE OR GREEN COPPERCONDUCTOR BONDED TO BUILDING EQUIPMENTGROUND. LEAVE 6 FEET OF EXTRA CONDUCTOR FORTERMINATION BY OTHERS.

3 CONTRACTOR TO CONFIRM EXACT CT ENCLOSURESIZE AND CONFIGURATION WITH UTILITY PRIOR TOORDERING.

bklawa
Image
bklawa
Image

MECHANICAL

ELEC.

119

PNL1N2-1

225A MCB

35 kAIC

PNL1N2-2

225A MCB

35 kAIC

PNL1N2-3

100A MCB

35 kAIC

MECHANICAL POWER LIGHTING

PNL1N2-4

225A MLO

22 kAIC

COMPUTER LABPOLYMERS SHOP

6"X6" NEMA 1 BUSSED WIREGUTTER

M600AF600AT

(2) 4" C. ROUTED THRU SOUTHEXTERIOR WALL

ELECTRIC CLOSET (EAST WALL)

CODE TAP LUGS (TYP)

(1) 3" C. ROUTED OVERHEAD

250AF225ATSPD SPD

25.7 kA AVAILABLE

225A-5

225A-5 225A-5 225A-5 100A-5 600A-5

600A-4

600A-4

EWEB VAULT ON OLIVE ST.

600A-4

600A-5 (2) SETS OF (4) 350 kCMIL, (1) #2 GND EACH SET IN 3" C.

(2) SETS OF (3) 350 kCMIL, (1) #2 GND EACH SET IN 3" C.

100A-5

225A-5 (1) SET OF (1) #4/0, (1) #4 GND EACH IN 3" C.

(1) SET OF (1) #2, (1) #8 GND EACH IN 2" C.

FEEDER SCHEDULE

3

E5.0

MAIN BREAKER

SUBFEED BREAKER FOR 1N2-4

PNL-1N2-1

PNL-1N2-2

PNL-1N2-3

PNL-1N2-5 (FUTURE)

CT ENCLOSURE

METER SOCKET

PNL-1N2-3 PNL-1N2-2 PNL-1N2-1

MAIN BREAKER

PNL-1N2-5 (FUTURE)

6"X6" NEMA 1 BUSSED WIREWAY WITH SCREW COVER

METER SOCKET

CT ENCLOSURE

HAHA

SA

ROOMCONTROLLER #X

120V NORMAL PWR

ZONE XA

ZONE XB

ZONE XC

DAYLIGHT SENSOR(S) PC

RCSLVLOW VOLTAGE WALLSTATION

(CONTROLS ZONES SHOWN)

OSOCCUPANCY SENSOR(S)

NOTES:A BASIS OF DESIGN PRODUCT IS GREENGATE RC3D. ACCEPTABLEALTERNATE MANUFACTURERS ARE WATTSTOPPER, LEVITON,NLIGHT AND LUTRON.

B. ALTERNATE SYSTEM MUST MEET INTENT SPECIFIED ONCONTRACT DOCUMENTS.

C. ALL OCCUPANCY SENSORS TO BE DUAL TECHNOLOGY TYPE.

D. NOT ALL COMPONENTS/ZONES USED ALL SPACES - REFER TOFLOOR PLANS FOR EXACT EQUIPMENT REQUIRED IN EACH.

WIRING LEGENDLOW VOLTAGE LIGHTING CONTROL WIRING

120V POWER WIRING

0-10V DIMMING WIRING

BUILDING LOAD SUMMARY208Y/120V, 3PH, 4W + GRD, 600A

CONNECTED LOAD (VA): 165010EST. DEMAND LOAD (VA): 163440

EST. DEMAND LOAD (A): 454

Tel: (

503)

771-1

986

Happy V

alle

y, O

R 97086

10555 S

E 8

2nd A

venue,

Suite 2

03

ALEX R

ID

LEY

ELECTRIC

AL D

ESIG

NER:a

ridle

y@

reyese

ng.c

om

ENGIN

EERIN

GREYES

PASSIO

N

CREATIV

ITY

SU

STAIN

ABIL

ITY

R E V I S I O N S

P R O J E C T N O. I S S U E D A T E

© MERRYMAN BARNES ARCHITECTS, INC.

S H E E T

942 O

LIV

E S

TREET

942 O

LIV

E S

TREET, EU

GEN

E, O

REG

ON

97401

OW

NER:

UN

IVERSIT

Y O

F O

REG

ON

CAM

PU

S P

LAN

NIN

G, D

ESIG

N &

CO

NSTRU

CTIO

NCO

NTACT:

MARTIN

A O

XO

BY 5

41.3

46.5

880

15-0309

BID SET

09.25.2015

E5.0

DIAGRAMS, SCHEDULES ANDENLARGED PLANS

12" = 1'-0"1

SINGLE LINE DIAGRAM

1/4" = 1'-0"2

ENLARGED PLAN - ELECTRIC RM.

1/4" = 1'-0"3

SECTION - MAIN ELECTRICAL EAST

Notes:

Total Est. Demand: 239 A

Total Conn.: 239 A

N 0 VA 0.00% 0 VA Total Est. Demand: 86000 VA

M 32000 VA 100.00% 32000 VA Total Conn. Load: 86000 VA

Spare 54000 VA 100.00% 54000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 239 A 239 A 239 A

Total Load: 28667 VA 28667 VA 28667 VA

41 3 3.2 42

39 3 3.2 40

37

SPARE 30 A 3

3 3.2

3 40 A POLYMER SHOP MAKE-UP AIR

38

35 3 2.4 36

33 3 2.4 34

31

SPARE 30 A 3

3 2.4

3 30 A IDF CLOSET SPLIT SYSTEM

32

29 3 0 1 20 A SPARE 30

27 3 0 1 20 A SPARE 28

25

SPARE 30 A 3

3 0 1 20 A SPARE 26

23 3 0 1 20 A SPARE 24

21 3 0 1 20 A SPARE 22

19

SPARE 30 A 3

3 0 1 20 A SPARE 20

17 3 0 1 20 A SPARE 18

15 3 0 1 20 A SPARE 16

13

SPARE 30 A 3

3 0 1 20 A PADDLE FANS 1 THRU 5 14

11 3 1.2 1 20 A AHU-6 12

9 3 1.2 1 20 A AHU-5 10

7

SPARE 30 A 3

3 1.2 1 20 A AHU-4 8

5 2.67 1.2 1 20 A AHU-3 6

3 2.67 1.2 1 20 A AHU-2 4

1

COMP. LAB CONDENSING UNIT CU-1 30 A 3

2.67 1.2 1 20 A AHU-1 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 225 A

Mounting: SURFACE Wires: 4 Bus Rating: 250 A

Supply From: MAIN BREAKER Phases: 3 Mains Type: MCB

Location: ELEC 119 Volts: 120/208 Wye A.I.C. Rating: 22 kAIC

PANELBOARD: 1N2-1

{1} PROVIDE PANELBOARD WITH INTEGRAL SPD. PROVIDE OVERCURRENT PROTECTION AS DIRECTED BY MANUFACTURER.{2} PROVIDE MEANS TO LOCK BREAKER HANDLE IN THE ON POSITION AND PAINT RED.

Notes:

Total Est. Demand: 51 A

N 2450 VA 100.00% 2450 VA Total Conn.: 69 A

C 4560 VA 125.00% 5700 VA Total Est. Demand: 18290 VA

K 2400 VA 100.00% 2400 VA Total Conn. Load: 24890 VA

R 15480 VA 50.00% 7740 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 70 A 73 A 66 A

Total Load: 8290 VA 8660 VA 7940 VA

41 0 0 1 20 A SPARE 42

39 0 0 1 20 A SPARE 40

37

SPD {1} 30 A 3

0 0 1 20 A SPARE 38

35 SPARE 20 A 1 0 0 1 20 A SPARE 36

33 SPARE 20 A 1 0 0 1 20 A SPARE 34

31 SPARE 20 A 1 0 0 1 20 A SPARE 32

29 FIRE ALARM CONTROL PANEL {2} 20 A 1 0.6 0 1 20 A SPARE 30

27 BREAK AREA COFEE MACHINE 20 A 1 1.2 0.72 1 20 A CO-WORK SPACE WORKSTATIONS 28

25 BREAK AREA REFIGERATOR 20 A 1 1.2 0.72 1 20 A CO-WORK SPACE WORKSTATIONS 26

23 BREAK AREA RECEPTS 20 A 1 0.72 1.08 1 20 A CONF & CO-WORK SPACE RECEPTS 24

21 BREAK AREA RECEPTS 20 A 1 0.54 1.2 1 20 A CO-WORK SPACE PHOTOCOPIER 22

19 RESTROOM RECEPTS 20 A 1 0.72 0.9 1 20 A CONF & CLASSRM RECEPTS 20

17 DESIGN STUDIO RECEPTS 20 A 1 0.72 0.97 1 20 A CLASSRM & HALL RECEPTS 18

15 DESIGN STUDIO RECEPTS 20 A 1 0.72 1.08 1 20 A CLASSRM/STORAGE/JANITOR... 16

13 DESIGN STUDIO RECEPTS 20 A 1 0.72 0.9 1 20 A HALLWAY & PHONE RM RECEPTS 14

11 DESIGN STUDIO CONV RECEPTS 20 A 1 1.08 0.9 1 20 A HALLWAY & CIRC RECEPTS 12

9 FLEX SPACE & STUDIO RECEPTS 20 A 1 0.97 0.72 1 20 A MEETING & WAR ROOM RECEPTS 10

7 FLEX SPACE RECEPTS 20 A 1 0.97 0.9 1 20 A WAR RM. & INVENTION SPACE... 8

5 MECH & ELEC RM RECEPTS 20 A 1 0.72 1.15 1 20 A CONF & INVENTION SPACE RECEPTS 6

3 IDF RECEPTS 20 A 1 0.36 1.15 1 20 A MEETING & CONF RECEPTS 4

1 IDF RECEPTS 20 A 1 0.36 0.9 1 20 A WAR RM. & INVENTION SPACE... 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 225 A

Mounting: SURFACE Wires: 4 Bus Rating: 250 A

Supply From: MAIN BREAKER Phases: 3 Mains Type: MCB

Location: ELEC 119 Volts: 120/208 Wye A.I.C. Rating: 22 kAIC

PANELBOARD: 1N2-2

Notes:

Total Est. Demand: 36 A

Total Conn.: 28 A

Total Est. Demand: 12793 VA

Total Conn. Load: 10234 VA

L 10234 VA 125.00% 12793 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 33 A 24 A 29 A

Total Load: 3879 VA 2935 VA 3420 VA

29 SPARE 20 A 1 0 0 1 20 A SPARE 30

27 SPARE 20 A 1 0 0 1 20 A SPARE 28

25 SPARE 20 A 1 0 0 1 20 A SPARE 26

23 SPARE 20 A 1 0 0 1 20 A SPARE 24

21 SPARE 20 A 1 0 0 1 20 A SPARE 22

19 SPARE 20 A 1 0 0 1 20 A SPARE 20

17 SPARE 20 A 1 0 0 1 20 A SPARE 18

15 SPARE 20 A 1 0 0 1 20 A SPARE 16

13 SPARE 20 A 1 0 0 1 20 A SPARE 14

11 SPARE 20 A 1 0 1.59 1 20 A EAST CIRC LIGHTING 12

9 SPARE 20 A 1 0 0.5 1 20 A EAST CIRC TRACK LIGHTING 10

7 DESIGN STUDIO LIGHTING 20 A 1 1.31 0.87 1 20 A CLASSRM, CONF, STORAGE, JAN LTG 8

5 FLEX SPACE TRACK & MECH/ELEC LTG 20 A 1 0.74 1.09 1 20 A CO WORK SPACE LIGHTING 6

3 COMP. LAB, RESTRM & SHOP LIGHTING 20 A 1 1.66 0.78 1 20 A WAR ROOM, CONF & INVENTION LTG 4

1 WEST CIRC & FLEX SPACE LIGHTING 20 A 1 1.24 0.47 1 20 A OUTDOOR & EXTERIOR LIGHTING 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: 100 A

Mounting: SURFACE Wires: 4 BUS Rating: 100 A

Supply From: MAIN BREAKER Phases: 3 Mains Type: MCB

Location: ELEC 119 Volts: 120/208 Wye A.I.C. Rating: 22 kAIC

PANELBOARD: 1N2-3

{1} PROVIDE PANELBOARD WITH INTEGRAL SPD. PROVIDE OVERCURRENT PROTECTION AS DIRECTED BY MANUFACTURER.

Notes:

Total Est. Demand: 46 A

Total Conn.: 38 A

N 250 VA 100.00% 250 VA Total Est. Demand: 16630 VA

C 12240 VA 125.00% 15300 VA Total Conn. Load: 13570 VA

R 1080 VA 100.00% 1080 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Amps: 42 A 35 A 36 A

Total Load: 5040 VA 4210 VA 4320 VA

41 0 0 1 20 A SPARE 42

39 0 0 1 20 A SPARE 40

37

SPD {1} 30 A 3

0 0 1 20 A SPARE 38

35 SPARE 20 A 1 0 0 1 20 A SPARE 36

33 SPARE 20 A 1 0 0 1 20 A SPARE 34

31 SPARE 20 A 1 0 0 1 20 A SPARE 32

29 SPARE 20 A 1 0 0 1 20 A SPARE 30

27 SPARE 20 A 1 0 0 1 20 A SPARE 28

25 SPARE 20 A 1 0 0 1 20 A SPARE 26

23 SPARE 20 A 1 0 0 1 20 A SPARE 24

21 SPARE 20 A 1 0 0 1 20 A SPARE 22

19 SPARE 20 A 1 0 0 1 20 A SPARE 20

17 SPARE 20 A 1 0 0.72 1 20 A COMP. LAB PENDAND RECEPTS 18

15 SPARE 20 A 1 0 0.72 1 20 A COMP. LAB PENDAND RECEPTS 16

13 POLYMERS BENCH RECEPTS 20 A 1 0.72 0.72 1 20 A COMP. LAB PENDAND RECEPTS 14

11 POLYMERS BENCH RECEPTS 20 A 1 1.08 0.72 1 20 A COMP. LAB WORKSTATIONS 12

9 POLYMERS & LASER BENCH RECEPTS 20 A 1 1.08 0.97 1 20 A COMP. LAB WORKSTATIONS & PJ 10

7 POLYMERS & LASER BENCH RECEPTS 20 A 1 0.9 1.08 1 20 A COMP. LAB WORKSTATIONS 8

5 POLYMERS BENCH RECEPTS 20 A 1 0.72 1.08 1 20 A COMP. LAB CONV. RECEPTS 6

3 POLYMERS BENCH RECEPTS 20 A 1 0.72 0.72 1 20 A COMP. LAB COUNTER CONV. RECEPTS 4

1 POLYMERS BENCH/CONV RECEPTS 20 A 1 0.9 0.72 1 20 A COMP. LAB COUNTER CONV. RECEPTS 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Enclosure: NEMA 1 MCB Rating: N/A

Mounting: RECESSED Wires: 4 Bus Rating: 250 A

Supply From: MAIN BREAKER Phases: 3 Mains Type: MLO

Location: 3D PRINTERS/ POLYME... Volts: 120/208 Wye A.I.C. Rating: 10 kAIC

PANELBOARD: 1N2-4

1/8" = 1'-0"4

LIGHITNG CONTROL DIAGRAMS

PROVIDE 3/4" SHEET OF FIREPROOF PLYWOOD TO MOUNTAMG SECURITY SYSTEM.

bklawa
Image