S110 Wiring Block Instructions Mount the S110 ® wiring base and legs onto a suit- able mounting surface with the nec- essary screws and hardware. 1 Remove the S110 ® wiring base from the legs by depressing the outer 4 fanning strips of the S110 ® wiring base inward to defeat the leg latches. Pull the wiring base away from the legs. 2 Strip back only as much cable jacket as is necessary to terminate the conductors using the Siemon CPT tool or equivalent. 5 Lace the conductors into the S110 ® wiring base. Pair twist must be maintained to within 12mm (.5") of the point of termination for category 5 installations. Ample channel space is provided to allow jacketed cable to continue close to the point of termination. 6 With the S110 ® base removed, route the cable between the legs. 3 Lace the cables through the appropriate openings in the wiring base and snap the S110 ® wiring base back onto the legs. Push the wiring base onto the legs until the latches “snap” into place. NOTE: For additional security, the assembly can be fastened together using the self-tapping, Phillips-head screws included. 4 Insert a S110C connecting block into the head of a Siemon S788 impact tool. 9 Carefully align the S110C connecting block over the wiring base, with the blue marking to the left side of the block (gray stripe down), and seat the connect- ing block. Note: Side stack connecting blocks starting from left side. 4-pair kit includes one 5-pair connecting block for the end of each row to eliminate extra gap. 10 Seat the conductors and trim off the excess wire with the cutting edge of the Siemon S788 impact tool or equivalent. NOTE: Be sure that the cutting edge is properly oriented prior to trimming the wire. 7 Visually inspect the conduc- tor and cable placement at this point to eliminate any miswires or reversals. 8 (100-pair wall mount shown) INS_1004854_S110 WiringBlck_E_E 2/18/15 3:47 PM Page 1

Transcript of S110 Wiring Block Instructions - The Siemon...

Page 1: S110 Wiring Block Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/110_s110... · S110 Wiring Block Instructions Mount the S110 ... nections

S110 Wiring Block Instructions

Mount the S110® wiringbase and legs onto a suit-

able mounting surface with the nec-essary screws and hardware.

1 Remove the S110® wiringbase from the legs by

depressing the outer 4 fanning stripsof the S110® wiring base inward todefeat the leg latches. Pull the wiringbase away from the legs.

2

Strip back only as muchcable jacket as is necessary

to terminate the conductors usingthe Siemon CPT tool or equivalent.

5 Lace the conductors into theS110® wiring base. Pair twist

must be maintained to within 12mm(.5") of the point of termination forcategory 5 installations. Amplechannel space is provided to allowjacketed cable to continue close tothe point of termination.

6With the S110® baseremoved, route the cable

between the legs.

3 Lace the cables through theappropriate openings in the

wiring base and snap the S110®

wiring base back onto the legs. Pushthe wiring base onto the legs untilthe latches “snap” into place.

NOTE: For additional security, the assembly can be fastened together usingthe self-tapping, Phillips-head screwsincluded.

4

Insert a S110C connectingblock into the head of a

Siemon S788 impact tool.

9 Carefully align the S110Cconnecting block over the

wiring base, with the blue markingto the left side of the block (graystripe down), and seat the connect-ing block.

Note: Side stack connecting blocks startingfrom left side. 4-pair kit includes one 5-pairconnecting block for the end of each row toeliminate extra gap.

10Seat the conductors and trimoff the excess wire with the

cutting edge of the Siemon S788impact tool or equivalent.

NOTE: Be sure that the cutting edge isproperly oriented prior to trimming thewire.

7 Visually inspect the conduc-tor and cable placement at

this point to eliminate any miswiresor reversals.

8

(100-pair wall mount shown)

INS_1004854_S110 WiringBlck_E_E 2/18/15 3:47 PM Page 1

Page 2: S110 Wiring Block Instructions - The Siemon Companyfiles.siemon.com/int-download-installation-instructions/110_s110... · S110 Wiring Block Instructions Mount the S110 ... nections

S110 Wiring Block Instructions

© 2

015

Sie

mon

R

ev.

E 2

/15

100.4

854

Label the circuits then slidethe designation strip into the

S110-HLDR and snap the holder ontothe wiring base. Complete the con-nections using CJ5 series cross-con-nect wire or S110P patch cables.

NOTE: Remove designation strips prior toremoving base from legs.

11The S110C connecting block is a double-ended, insulation

displacement connector. It should be noted that only 22 through 26 AWG (0.64-0.40mm) insulatedwire should be used with this connector.

Once the connecting blocks have been seated and designation strips snapped into place, cross-con-nection wires can be terminated to the top of the S110C connecting blocks. Arrange wires as shownand terminate using Siemon Company P/N S814 or S788 impact tool or equivalent. The Siemon S788impact tool may also be used for both terminating wires to the top of all 110C-type connectingblocks, and for seating connecting blocks. Make sure all conductors have been completely seatedinto the wire slots and trim any excess wire using the cutting edge of either impact tool.

12

R

Global HeadquartersWatertown, Connecticut USA

Tel: (1) 866-548-5814

For a complete listing of our global offices visit our web site www.siemon.com

The Siemon S100A2 verticalwire manager can be ordered

separately and mounted to the legsof the S110 to provide vertical cablemanagement for S110® patch cordsor cross-connect wire.

13

T1 R1 T2 R2 T3 R3 T4 R4 T5 R5

BLUEGREEN STATE

ORANGE BROWN

STRIPED SOLID

To assist safe installations, comply with the following:A. Use caution when installing or modifying telecommunications circuits.

B. Never touch uninsulated wire terminals unless the circuit has been disconnected.

C. Never install this device in a wet location.

D. Never install wiring during a lightning storm.

Lors de l'installation, respectez les consignes de sécuritésuivantes: A. Utiliser avec prudence lors de l'installation ou de la modification circuits de télécommunications.

B. Ne jamais toucher les bornes de fil métallique non isolés sauf si le circuit a étédébranché.

C. Ne jamais installer cet appareil dans un endroit humide.

D. Ne jamais installer pendant un orage.