![Page 1: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/1.jpg)
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S00.01
GENERAL NOTES
N.T.S.
No of batches supplied:
1
2 to 5
6 to 10
11 to 30
For Each additional 10 batches
Compressive Strength.
Sample, test, and assess to AS 1379. All testing to be conducted by a NATA registered laboratory.
The minimum frequency of sampling of the concrete at each stage shall be in accordance with the following:
No. of samples taken:
1
2
3
4
1
Minimum clear concrete cover to reinforcement including ties and stirrups shall be as follows uno.
12 N 20 - 200
No of bars group
Nominal bar size in
mm
Bar grade and
type
Spacing in mm
Top
All Other Bars
N12
600
500
N16
800
650
N20
1000
800
N24
1200
950
N28
1440
1150
N32
1600
1300
* - Denotes horizontal bars with 300mm or more concrete cast below.
Laps in Fabric shall be U.N.O.
Do not lap over
slab supports.
Fabric cross rod to be located at cover distance from form edges.
Dotted lines thus indicate possible bending of
bars to suit concrete profile.
Development measured along bar.
All re-entrant corners at penetrations for sumps, pits, column blockouts and the like, to have N16 trimmer
bars place at 45 degrees to corner or in each direction at corners unless noted in a different arrangement on
plan.
TRIMMER BARS IN SLAB:
TOP REINFORCEMENT BOTTOM REINFORCEMENT
x
xx
x
1-N16 x 1200 LG
Placed on centre of
incoming joint
1-N16 x 1200 LG
Placed at 45° to
column face
OR
Trimmer bars to be tied to U/S of slab mesh.
Provide sub-floor drainage to hydraulic engineers details.
Prior to placement of slab, subgrade shall be compacted to a minimum of 98% standard compaction in
accordance with test 'E1.1' of AS 1289 for the top 300mm. Any soft spots shall be removed and replaced with
site won material to the engineers approval.
GENERAL
G1 These drawings shall be read in conjunction with all architectural and other consultants drawings and
specifications and with such other written instructions and sketches as may be issued during the course of
the Contract. Any discrepancies shall be referred to the Superintendent before proceeding with any related
works. Construction from these drawings, and their associated consultants drawings is not to commence until
approved by the Local Authorities.
All materials and workmanship shall be in accordance with the relevant and current Standards Australia
codes and with the By-Laws and Ordinances of the relevant building authorities except where varied by the
project specification.
All set out dimensions shall be obtained from Architect's and Engineer's details. All discrepancies shall be
referred to the Architect and Engineer for decision before proceeding with related work.
During construction the structure shall be maintained in a stable condition and no part shall be overstressed.
Temporary bracing shall be provided by the builder/subcontractor to keep the works and excavations stable
at all times.
Unless noted otherwise levels are in metres and dimensions are in millimetres.
The structural components detailed on these drawings have been designed in accordance with the relevant
Standards Australia codes and Local Government Ordinances for the following loadings. Refer to the
Architectural drawings for proposed floor usage. Refer to drawings for live loads and superimposed dead
loads.
Any substitution of materials shall be approved by the Engineer and included in any tender.
During Construction a minimum of one (1) floor shall remain fully backpropped at all times. At no time shall
concrete be poured unless the floor below is fully backpropped.
G2
G3
G4
G5
G6
G7
G8
FOUNDATION
Footings to be constructed and backfilled as soon as possible following excavation to avoid softening or
drying out by exposure. Refer to drawings for backfill requirements.
Do not backfill retaining walls (other than cantilever walls) until floor construction at top and bottom is
completed. Ensure free draining backfill and drainage is in place.
Do not exceed a rise of 1 in a run of 2 for the line of slope between adjacent footings or excavations.
Footings shall be located centrally under walls/columns unless noted otherwise.
Refer to Geotechnical Report prepared by:
Refer to the notes on the foundation drawing for minimum allowable bearing capacity. The foundation
material shall be approved by the Geotechnical Engineer for this bearing capacity before placing membrane,
reinforcement or concrete.
F1
F2
F3
F4
F5
F6
REINFORCED CONCRETE
Minimum concrete quality noted on relevant drawings. All the requirements of the ACSE Concrete
Specification Document 1 (latest edition) shall apply to the formwork, reinforcement and concrete unless
noted otherwise.
Readymix concrete supply shall comply with AS 1379.
All workmanship and materials shall be in accordance with AS 3600 current edition with amendments,
except where varied by the contract documents.
RC1
RC2
RC3
A sample shall consist of four cylinders, two of which shall be tested at 28 days, one at 7 days and one at 4
days. If the contractor requires early strength results, additional cylinders shall be taken in the sample as
required and at the cost of the contractor.
Other quality parameters
Sample: Test and assess to AS 1379 Section 5.
Slump: Test not less than one sample for each batch before placing concrete from that batch in the work.
Take the samples at the point of discharge on site.
Drying Shrinkage: The maximum total drying shrinkage limit for the concrete shall be an average of 0.070%
at 56 days and no single result shall exceed 0.075%. Measurement shall be in accordance with AS1012 Part
13 and be conducted by a NATA registered laboratory.
Rejection: Remove the concrete from the site.
No admixtures shall be used in concrete unless approved in writing.
Depth of beams are given first and include slab thicknesses. Slabs and beams shall be cast together
unless noted otherwise.
Construction support propping is to be left in place where needed to avoid overstressing the structure due to
construction loading. No brickwork or partition walls are to be constructed on suspended levels until all
propping is removed and the slab has absorbed its dead load deflection..
Curing of all concrete is to be achieved by keeping surfaces continuously wet for a period of 3 days, and
prevention of loss of moisture for a total of 7 days followed by a gradual drying out. Approved sprayed on
curing compounds that comply with AS 3799 may be used where floor finishes will not be affected. (refer
Manufacturers Specification). Polythene sheeting or wet hession may be used to retain moisture where
protected from wind and traffic.
Slabs and beams shall be constructed to bear only on the beams, columns, walls etc. shown on the
drawings. All other building elements shall be kept 12mm minimum clear from soffits of structure.
The finished concrete shall be a dense homogeneous mass, completely filling the formwork thoroughly
embedding the reinforcement and free of stone pockets. All concrete including slabs on ground and footings
shall be compacted with mechanical vibrators.
Provide upward camber to formwork of reinforced concrete cantilevers of L/200 where L is the projection
beyond column or wall face, and to formwork of slabs where noted on plans. Maintain slab and beam depths
as shown. Provide 0mm precumber to post tensioned slabs U.N.O. on plans.
Conduits and pipes when cast in slabs or walls are to be placed between the reinforcement layers. Where
there is only one layer of reinforcement, provide 50mm cover to conduit minimum.
Construction joints shall be located to the satisfaction of the Project Engineer. The Builder shall allow for all
necessary construction joints.
Concrete shall be kept free of supporting masonry with a pre-greased galvanised steel slip joint, vertical
faces shall be separated by 10mm Jointex (or equal).
No holes, chases or embedments other than those shown on the drawings shall be made in concrete
elements without the Project Engineers approval.
Concrete sizes do not include thicknesses of applied finishes.
RC4
RC5
RC6
RC7
RC8
RC9
RC10
RC11
RC12
RC13
RC14
RC15
REINFORCEMENT
R1
Laps in reinforcement shall be U.N.O.
The figures following the symbol "F" is the reference no. for fabric to AS 1304.
Reinforcement Notation.
T - Denotes top reinforcement.
B - Denotes bottom reinforcement.
NF - Denotes near face.
FF - Denotes far face.
EF - Denotes each face.
R2
Reinforcement Symbols:
S - Denotes Grade 230 S Hot Rolled Deformed Bars to AS 1302
Y - Denotes Grade 410 Y Bars to AS 1302 Grade Y
N - Denotes Grade 500 N Bars to AS 1302
R - Denotes Grade 230 R Hot Rolled Plain Bars to AS 1302
F - Denotes Grade 450 F Hard-Drawn Wire Reinforcing Fabric to AS 1304
W - Denotes Grade 450 W Hard-Drawn Plain Wire to AS 1303
Reinforcement is shown diagrammatically and is not necessarily in true projection. Splices to reinforcement
shall be made only at the locations shown, or otherwise approved by the Project Engineer.
The Engineer shall be given 24 hours notice for reinforcement inspection.
All reinforcement shall be firmly supported on mild steel plastic tipped chairs, plastic chairs or concrete chairs
at not more than 1 metre centre both ways. Bars shall be tied at alternate intersections. In exposure
conditions greater than B1 use only plastic chairs.
R3
R4
R5
R6
Typical reinforcement lapping at steps. Refer to note R6 for development past intersection measured along
bar.
Reinforcement crossing penetrations shall be displaced as necessary, no reinf't shall be cut without the prior
written approval of the Project Engineer.
Distribution reinforcement and tying steel shall be N12-400 minimum for conventional slabs, or N12-500
minimum for post tensioned slabs where necessary unless noted otherwise on plan. Lap with main bars
400mm U.N.O.
Joggles to bars shall be 1 bar diameter over a length of 12 bar diameters.
Welding of reinforcement shall not be permitted unless shown on the structural drawings or approved by the
Project Engineer.
Site bending of deformed reinforcing bars shall be done without heating using mechanical bending tools.
Slab reinforcement shall extend minimum 65mm onto masonry support walls and minimum 50 percent of
bottom reinforcement to be cogged, to achieve anchorage at simply supported ends. Terminate all top bars
with standard cogs at form edges.
R7
R8
R9
R10
R11
R12
R13
MASONRY
All cavity construction to have 316 grade stainless steel wall ties installed as per Clause 3.4 in AS 3700.
Refer project specification and local authorities requirements. Refer note G2.
Do not construct masonry walls on suspended concrete slabs until slab has been stripped and de-propped.
Backfill to retaining walls to be free draining granular material unless noted otherwise. Provide subsoil drain
to weep holes.
Provide vertical control joints at 10m. max. centres, and 5m max. from corners in all masonry walls, unless
noted otherwise.
All masonry walls and piers supporting slabs and beams shall have a pre-greased galvanised steel slip joint
between concrete soffit and the top of the masonry element unless noted otherwise.
No cavity or core shall be filled to a height greater than 1200mm without suitable shoring.
All walls shall be tied or bonded at their intersections.
All ties and reinforcement shall have a minimum clear cover of 50mm to external face of masonry.
Hollow blockwork openings greater than 600mm vertically or horizontally shall be trimmed at the sides and
bottom by filling one core and reinforce with 1N12 extending 600mm past opening. The top of the opening
shall have a reinforced lintel beam, arch bar or steel angle support as required.
Fully bed face shells and cross webs in hollow block walls.
Horizontal joint reinforcement shall be provided at max. 600 vertical spacing for all concrete blockwork,
concrete brickwork, and calcium silicate brickwork.
Grout used to fill cavities and cores in reinforced masonry shall have a min. 28 day compressive strength of
32 MPa and a slump of 225mm (+/-25mm) Maximum aggregate size of 10mm rounded gravel. Nominal
proportions shall be 1 : 0.3 : 3 : 2 of cement, lime, sand, aggregate and with a minimum cement content of
300 kg/cm. Provide clean out holes at base of pilasters and every core of reinforced walls.
Mortar shall be full bed and unless noted otherwise, the nominal proportions by volume shall be as follows:
Mortar admixtures shall not be used without the written approval of the Superintendent.
No chases or recesses are permitted in load bearing masonry without the approval of the Structural
Engineer.
Non loadbearing walls shall be separated from concrete above by 12mm thick close cell polyethelene strips.
All masonry supporting or supported by concrete floors shall be provided with vertical joints to match any
control joints in the concrete.
All blockwork walls shall be constructed in Grade 16 blocks (15 MPa) according to AS/NZ 4455. All bricks
shall have a minimum compressive strength of 30 MPa according to AS/NZ 4455. The maximum unrestrained
five year expansion of bricks shall be in accordance with NATA Test B01.
All workmanship and materials shall be in accordance with AS 3700.M1
M2
M3
M4
M5
M6
M7
M8
M9
M10
M11
M12
M13
M14
M15
M16
M17
M18
M19
STRUCTURAL STEEL
SLABS ON GRADE
SOG1
SS1
Provide seal plates to the plates to the ends of all hollow sections, with "breather' holes if members to be hot
dip galvanised.
Unless noted otherwise camber shall be provided to all roof beams, trusses, portals etc. At 5mm per 2000mmof span. No member shall be erected with negative camber.
The builder shall provide all cleats and drill all holes necessary for fixing steel to steel and timber and other
elements to steel whether or not detailed in the drawings.
Steelwork not to be concrete encased shall be given one shop coat of an approved primer unless noted
otherwise. Faces of friction grip connections shall not be painted. Refer to architectural specifications for
coatings schedule.
All steelwork below ground shall be encased by 75mm of concrete, steel wrapped with FGW41 placed 25mmclear of steel. Provide 50mm minimum encasing.
Steelwork intending to be concrete encased shall be unpainted. Encasing concrete to be grade N25
providing cover adequate to suit fire rating or exposure conditions. Concrete encasement shall be centrally
reinforced with 5mm wire to AS 1303 or 6mm structural grade bars to AS 1302 at 150mm pitch.
Where connection forces (in Kilonewtons) are shown on the drawings, connections shall be provided to
transmit these forces. Connections shall provide for a minimum force of 25 kN.
Fabrication shall comply with AS 4100 - Section 14, Erection shall comply with AS 4100 - Section 15. /TB
and /TF bolts to be installed in accordance with AS 4100 - Section 15, using either the part-turn method or
the direct-tension indicator method.
Unless noted otherwise all fillet welds shall be 6mm continuous category SP using E41XX electrodes. All butt
welds shall be complete penetration butt welds SP to AS 1554.1. All gusset plates shall be 12 mm thick, all
bolts shall be M20 8.8/S in 22mm diameter holes, minimum 2 bolts to each connection. All washers and bolts
shall be galvanised.
The bolting procedure is designated as follows: 4.6/S Commercial bolts of grade 4.6 to AS 1111 - snug
tightened 8.8/S High strength bolts of grade 8.8 to AS 1252 - snug tightened 8.8/TB High strength bolts of
grade 8.8 to AS 1252 fully tensioned to AS 4100 as a bearing type joint 8.8/TF High strength bolts of grade
8.8 to AS 1252 fully tensioned to AS 4100 as a friction type joint with facing surfaces left uncoated.
Three (3) copies or 1 transparency of workshop drawings shall be submitted to the Engineer for review at
least 7 days prior to commencement of fabrication. Fabrication shall not commence without Engineers
approval of workshop drawings. All dimensions and setouts to be obtained from the Architects drawings
where not indicated on the Structural drawings.
Unless noted otherwise, all steel shall be in accordance with AS 3678 Grade 250 or AS 3679 Grade 300, or
AS 1163 Grade 350 as appropriate.
All workmanship and materials shall be in accordance with AS 4100 except where varied by the contract
documents.
SS2
SS3
SS4
SS5
SS6
SS7
SS8
SS9
SS10
SS11
SS12
SS13
Surface finishes for all structural steelwork to be in accordance with the Architectural specification.
The fabrication and erection of the structural steel work shall be supervised by a qualified engineer,
experienced in such supervision, to ensure that all requirements of the design are met.
All galvanising of structural steelwork to AS 1650. The continuous average zinc coating mass to be 600 g/m2
(550 g/m2 minimum)
Unless noted otherwise all material to be: Grade 250-Hot Rolled Plates, Flats, Angles (100 x 100 or 125 x 75
and smaller) Grade 300-All WB's and WC's Grade 300 Plus-All UB's, UC's, PFC's and larger angles. Grade
350-All RHS's, and CHS's
Minimum one washer shall be used under the nut in all situations. If tightening is carried out at the head, and
additional washer is to be used under the head. For slotted holes use hardened washer under the nut and
bolt head.
All bolts shall be of such length that at least one full thread is exposed beyond the nut after the nut has been
tightened.
All steelwork shall be securely temporarily braced by the erector as necessary to stabilise the structure
during erection. Design of all temporary bracing is the responsibility of the erector. Specific design details are
to be forwarded onto the project engineer upon request.
SS14
SS15
SS16
SS17
SS18
SS19
SS20
FORMWORK
The contractor shall develop a written construction procedure for the placing of concrete in tall members.
This may require the provision of inspection and pouring openings in formwork, or construction joints at
locations approved by the architect. The construction procedure shall be submitted to the engineer for
acceptance with respect to compliance with the design intent.FW14All slabs, beams, columns, walls etc have
been designed for their final design loads when acting as a part of a total structure. Propping and temporary
supports that may be required to maintain the temporary structural adequacy during construction shall be the
responsibility of the contractor.
Provide independent third party certification of adequacy of all formwork prior to pouring any concrete.
Certification shall be by a suitably qualified structural engineer registered on the National Professional
Engineers register.
Formwork and scaffolding shall be extended beyond tendon anchorage point to provide space for stressing
operations where required. Safety hoarding for stressing shall be provided as necessary.
Refer to Architects drawings for test panel details. Reinforcement for test panels shall be similar to that in the
permanent structure being represented.
Design information concerning the foundation formwork shall be determined from the conditions existing on
site at the time of construction. Also refer Geotechnical Report where available for further details.
Do not place permanent loads, including masonry walls and the like, on the concrete structure until after the
formwork and backpropping has been removed. Refer to note RC15.
Concrete formed surfaces shall have finishes in accordance with AS 3610, as specified by the Project
Architect.
The formwork shall be designed to accommodate movements and load redistribution due to post tensioning.
The formwork shall not be designed to rely on restraint or support from the permanent structure without prior
approval from the Project Structural Engineer.
Stripping of formwork and backpropping details shall be in accordance with AS 3600 clause 17.6 , and shall
be carried out by a suitably qualified and experienced person. Refer to the project engineer for any specific
requirements which may be specified. Refer to note G6.
During construction, support propping will be required where loads from stacked materials, formwork and
other supported slabs induce loads in a slab or beam which exceed the design load for strength or
serviceability at that age. Once the nominated 28 day strength has been attained, these loads shall not
exceed the design superimposed loads set out in the general notes.
Formwork design, construction tolerances and stripping times shall comply with AS 3610 and AS 3600
unless otherwise approved by the Project Structural Engineer.
The design certification, construction and performance of the formwork and false work shall be the
responsibility of the builder/subcontractor, unless specific design requirements are shown on the engineering
drawing.
FW1
FW2
FW3
FW4
FW5
FW6
FW7
FW8
FW9
FW10
FW11
FW12
FW13
P1
FOUNDATION PILING
STRUCTURAL TIMBER
AT 21 BARKER ROAD, STRATHFIELD
T1
Surface finishes for all structural timber shall be in accordance with the Architectural specification.
At the practical completion of the contract, and again at the end of the maintenance period and if necessary
during that period, the contractor shall re-tighten all bolts to approval. Bolts that will be inaccessible after
completion of the project, shall be re-tightened, immediately prior to being built in.
Timber dimensions on the finished width and thickness to be: Seasoned Softwood +5mm, -0mm Unseasoned
Softwood >F7 +3mm, -3mm ≤F7 +2mm, -4mm Seasoned Hardwood +2mm, -0mm Unseasoned Hardwood
+3mm, -3mm (see also clause 1.6.2 in AS 2082)
All timber joints and notches are to be 100mm minimum away from loose knots, severe sloping grain, gum
veins or other minor defects.
Specialised timber fasteners such as Gang-Nail plates, Trip-L-Grip etc. shall be of proven type and shall
have had working loads determined in accordance with the procedure specified in AS 1849.
Shank and thread of bolts shall be thoroughly coated with a heavy waterproof grease before inserting into
the timber.
All bolts in timber construction to be minimum M16 unless noted otherwise. Bolt holes to be drilled exact
size. Washers under heads and nuts to be at least 2.5 times the bolt diameter. Edge distances for fasteners
in timber (from ends and sides) shall be in accordance with AS 1720.
Timber trusses to be precambered an amount equal to dead load deflection. Three (3) copies of shop
drawings are to be submitted to the engineer for approval clearly showing the design loads on the roof and
ceiling and truss node point loads and precamber. Drawings shall be submitted minimum 14 days prior to
commencement of fabrication. Fabrication shall not commence unless permission to do so has been given.
Design of trusses shall only be done by a qualified Structural Engineer experienced in timber design.
External timber to be either Hardwood durability as per AS1702.2 or impregnated pine Grade F7, pressure
treated to AS 1604 and re-dried prior to use. Supplementary treatment shall be applied to all cut surfaces.
Supply supporting documentation for preservative treatment. AS1702.2
Softwood to be minimum Grade F7, Hardwood to be minimum grade F14 unless noted otherwise.
All timber used shall have been stress graded by visual or mechanical means in accordance with the
appropriate Australian Standards.
AS 1684 shall be applied to domestic construction.
All timber design, construction and material to be to AS 1720.1 and AS 1720.2 unless noted otherwise.
T2
T3
T4
T5
T6
T8
T7
T9
T10
T11
T12
T13
Min 1 wire
Spacing plus 25mm
Refer note R6
Refer note R6
Refer to Geotechnical Report prepared by:
Any additional investigation required by the contractor shall be at the contractor's expense.
P2 Class 4 rock shall be as defined in the Geotechnical report. The Class 4 rock levels for determining pile toe
levels shall be agreed in writing with the engaged Geotechnical engineer prior to commencement of drilling.
P3 The tender is to be based on conditions as found on site. Changes in conditions, or obstructions will not form
a basis for a variation.
P4 All piles are to be installed by the contractor to AS2159-1995 piling design and installations code and any
other relevant codes.
P5 Piles shall be placed to a plan tolerance of 50mm maximum at any point along their length, and a gap
between piles along their length of 10mm. If any piles are installed out of tolerance the contractor shall be
responsible and liable for the design and installation costs of additional piles or rectifying elements or the
complete removal and replacement of the piles as instructed by the superintendent.
P6 Contractor shall provide for all surveying requirements to construct piling. This includes, but is not limited to
setting out piles, before and during drilling and for the provision of as-built survey.
P7 At the completion of piling, the contractor shall provide an as-built survey and certification that all piles are
within specified tolerances.
P8 The contractor is to make themselves familiar with the site and to assess the likely issues associated with
noise, vibration, groundwater, trafficability and any other issues which may require risk assessment.
P9 All piles are to be cut down to level such that they protrude 75mm into the base of capping beams and
reinforcement protrudes in capping beams as shown on details. The piling contractor shall progressively
remove and dispose of any soil if any from the work areas. This includes grout/concrete spillage if any. The
piling contractor shall allow for the supply of all equipment such as trucks and loaders and any approvals for
disposal as required.
P10 A construction program will be provided with the tender documentation to the contractor. The contractor is to
provide a critique of the program with the tender submission.
P11 Testing as required for certification of the Australian Standards shall be provided by the contractor.
Pile grout testing - Test grout in accordance with AS2159 clause 7.5.6.2 and note RC3. Min 28 day strength
F'c = 40MPa - Test 10% of piles in accordance with AS2159 clause 8.5. Location of test piles to
be confirmed by structural engineer.
P12 Refer to architectural drawings for all reduced levels.
P13 Place reinforcement in piles in accordance with AS3600 and notes R1 to R14.
M3
M4 1
0
1
0
0
0
1
1
0.5
0.25
1
1
5
4.5
2.25
4
Exposure
Classification
Portland
Cement (GP)
Blended
Cement (GB)
Building Lime
Sand
M3 - Denotes areas with moderate exposure greater than 1km from surf coastal areas
M4 - Denotes areas with extreme exposure with 1km from a surf coast or an industry where chemical
pollutants are produced.
Refer to AS3700 for further detail
Exposure
Classification
Minimum Cover (mm)
A1
A2
B1
B2
C
Concrete Strength (f'c)
20 MPa 25 MPa 32 MPa 40 MPa > 50 MPa
20
(50)
-
-
-
20
30
(60)
-
-
20
25
40
(65)
-
20
20
30
45
(70)
20
20
25
35
50
Site soil classification : Assumed Class H
(refer note below)
Site wind classification : N2 (W33)
Earthquake design category: H1
Construction type: Articulated Masonry Veneer
(Masonry shall be articulated in accordance with technical note 61
from the cement and concrete association of australia)
Roof framing: As noted on plan
Note: The superintendent shall have the site soil classification
confirmed (by inspection of test pier hole
1500 min deep or to auger refusal, whichever is less) by the
engineer prior to commencing construction.
Where the clay extends for 1500 or more the superintendent shall
have the site classification confirmed by a suitably qualified
geotechnical engineer prior to commencing construction.
DESIGN CRITERIA
PROPOSED RESIDENCE
Geotech Name: N/A
Report No: N/A
Report Date: N/A
Geotech Name: N/A
Report No: N/A
Report Date: N/A
![Page 2: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/2.jpg)
1:100
BASEMENT RAFT SLAB LAYOUT PLAN
BEB1 + CW1
BEB1 + CW1
BE
B1
+
C
W1
BE
B1
+
C
W1
BIB
1B
IB
1
BIB1 BIB1
DENOTES OUTLINE OF
GROUND SLAB OVER
RW1
DENOTES
TEMPORARY
BATTER
TEMPORARY SHORING SUBJECT
TO SITE INVESTIGATION OR
GEOTECH ENGINEER ADVICE
CW1 200 THICK N16-200 32REFER TO PLAN
WALL No. THICKNESS
HORIZONTAL WALL
LENGTH
VERTICAL
REINFORCEMENT
HORIZONTAL
REINFORCEMENT
CONC. STRENGTH
F'c
N16-400
RITEK XL WALL SYSTEM SCHEDULE
CORE FILLED
COMMENTS
NOTE:
ALL RITEK XL WALLS ARE TO BE INSTALLED IN ACCORDANCE WITH RITEK XL WALL
SYSTEMS INSTALLATION MANUAL & MANUFACTURERS SPECIFICATIONS
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S01.01
BASEMENT SLAB LAYOUT PLAN
1:100, 1:20 U.N.O.
100 THICK SLAB REINFORCED WITH SL82 MESH TOP
CONTINUOUS THROUGHOUT INCLUDING ANY EXTRAS AS
NOTED ON PLAN OR IN DETAILS.
2-N12 (75 SPACING 1200 LONG) TRIMMERS TOP SHALL BE
LOCATED 50 FROM ALL RE-ENTRANT CORNERS, TYPICAL.
SITE PREPARATION SHALL BE CARRIED OUT IN ACCORDANCE
WITH THE GENERAL NOTES & CURRENT EDITION OF AS2870 -
RESIDENTIAL SLABS & FOOTING CODE.
REFER TO GENERAL NOTES FOR CONCRETE COVERS
RAFT SLAB NOTES
FOUNDATION NOTE
REFER TO GENERAL NOTES FOR REINFORCEMENT COVER
25
STRENGTH
f'c
MAX SIZE
AGG. mm
CEMENT
TYPE
ADMIXTURE
RAFT SLAB GP -20
ELEMENT
CONCRETE QUALITY
80
SLUMP
mm
THE FOOTINGS SHALL BE FOUNDED ON STIFF CLAY
MATERIAL WITH A MINIMUM SAFE BEARING CAPACITY
OF 150 kPa.
IF SLAB IS FOUNDED PARTLY ON STIFF CLAY, THEN BORED
PIERS SHALL BE USED IN ACCORDANCE WITH THE
FOLLOWING:
o FOUNDED OFF STIFF CLAY THAT IS UNIFORM & STABLE
THROUGHOUT.
o MINIMUM SAFE END BEARING OF 250 kPa. GEOTECH TO
VERIFY ON SITE.
o LOCATED AT CORNERS & INTERSECTION POINTS OF
BEAMS.
o LOCATED UNDER STEEL OR BRICK COLUMNS OVER
o MAXIMUM 1800 SPACING FOR EDGE BEAMS OR STRIP
FOOTINGS.
o MAXIMUM 2000 SPACING FOR INTERNAL BEAMS.
o WHERE ROCK IS ENCOUNTERED, ALL PIER TO BE
FOUNDED OFF ROCK THAT IS UNIFORM & STABLE WITH
A MINIMUM OF 700 kPa BEARING CAPACITY.
REFER TO GENERAL NOTES FOR DESIGN CRITERIA
CONCRETE :
INTERIOR SURFACES : A1
EXTERIOR SURFACES : B1
MASONRY :
MASONRY DURABILITY REQUIREMENTS : M2
BORED PIER NOTE
DESIGN CRITERIA
EXPOSURE CLASSIFICATION
![Page 3: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/3.jpg)
30
50
0
400
4-L11TM BOT.
R6-600 TIES
1N12 BARS TOP EXTRA
LAP 600 MIN. AS REQUIRED
DAMP PROOF
MEMBRANE ON
50 MIN SAND BED
TOP MESH
STARTER BARS TO MATCH
VERTICAL REINFORCEMENT
MIN. (ØBAR x 40) LAP
FREE
DRAINAGE
BACKFILL
10
0
80 x 100 FLO-PIPE SURROUNDED BY
FREE DRAINING GRAVEL. DRAIN TO BE
CONNECTED TO STORMWATER
55
TYPICAL EDGE BEAM 'BEB1' DETAIL
1:20
50
0
300
TYPICAL INTERNAL BEAM 'BIB1' DETAIL
3-L11TM BOT.
R6-600 TIES
DAMP PROOF MEMBRANE
ON 50 MIN SAND BED
2N12 BARS TOP EXTRA
LAP 600 MIN. AS REQUIREDTOP MESH
1:20
MIN.
150
20
0
G.L.
55 COVER
90
0
2300
700
TYPICAL RETAINING WALL 'RW1' DETAIL
COMPACTED GRANULAR
BACKFILL TYPICAL
1:20
SL82 MESH TOP
TYPICAL
80 x 100 FLO-PIPE SURROUNDED BY
FREE DRAINING GRAVEL. DRAIN TO
BE CONNECTED TO STORMWATER
MAXIMUM 5kPa
SURCHARGE
N16-400
N16-200 VERTICAL
N16-400 HORIZONTAL
N16-200 STARTER BARS
MIN. (ØBAR x 40) LAP
Y
29
0 B
LO
CK
X
19
0 B
LO
CK
MA
X. 2
80
0
FOOTING CONCRETE
STRENGTH f'c = 32 MPa
CLAY SEAL
BUILDER TO TEMPORARILY PROP
RETAINING WALL UNTIL GROUND
SLAB IS POURED & CURED
ATLANTIS DRAINAGE CELL
TANKING - REFER
TO BLOCKWORK
TYPICAL DETAILS
ATLANTIS DRAINAGE CELL
CW
200 THICK RITEK COREFILLED
WALL TO MANUFACTURERS
SPECIFICATION
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S01.02
BASEMENT DETAILS SHEET
1:20 U.N.O.
![Page 4: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/4.jpg)
1:100
GROUND SLAB LAYOUT PLAN
150
100
100200
200
30
0
FO
LD
EB4
EB1 EB1EB2
EB
2
EB2
EB
1
EB1 EB1 EB1
EB
1
EB4
EB3
EB
1
EB3
EB6
EB
2
EB
2
EB1EB1
EB4
EB
5
SF1
SF
1
IB
2
IB2
IB
3
IB
3
IB
3
1
S02.04
1
SIM.
3
SIM.
HOBHOB
3
S02.04
2
S02.04
C
7
(
o
)
C
2
(
o
)
C
4
(
o
)
C
4
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
LOCAL THICKENING
TYPICAL
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
7
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
C
1
(
o
)
P
O
O
L
B
Y
O
T
H
E
R
S
NOTE:
BORED PIERS WITHIN 1.8m RADIUS OF POOL
TO BE FOUNDED MIN. 400mm BELOW ZONE
OF INFLUENCE OF POOL. REFER TO BORED
PIER NOTES FOR MIN. BEARING CAPACITY.
EB
4
SF1
4
S02.04
R
B
P
1
R
B
P
1
MW1
MW1MW1
MW1 190 BLOCK N16-400 CORE FILLEDREFER TO PLAN
NOTE:
REFER TO MASONRY WALL DETAILS ON THIS DWG.
WALL No. THICKNESS
HORIZONTAL WALL
LENGTH
VERTICAL
REINFORCEMENT
HORIZONTAL
REINFORCEMENT
COMMENTS
N12-400
MASONRY WALL SCHEDULE
4 x C6
C
5
(
o
)
C
5
(
o
)
PROVIDE LOCAL THICKENING
TO ACCOMMODATE BASE
PLATE. REFER TO DETAIL.
TYPICAL.
C
1
(
o
)
CORNER BAR TO MATCH
HORIZONTAL REINFORCEMENT.
EACH LEG 1000 LONG.
TYPICAL REINFORCED
MASONRY CORNER DETAIL
1:20
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.01
GROUND SLAB LAYOUT PLAN
1:100, 1:20 U.N.O.
DENOTES LOCATION OF 300 DEEP PODS.
POD SIZE: 1090 x 1090 (CUT PODS AS REQUIRED)
85 THICK SLAB REINFORCED WITH SL82 MESH TOP
CONTINUOUS THROUGHOUT INCLUDING ANY EXTRAS
AS NOTED ON PLAN OR IN DETAILS.
THE FOOTINGS SHALL BE FOUNDED ON STIFF CLAY
MATERIAL WITH A MINIMUM SAFE BEARING CAPACITY
OF 150 kPa.
BORED PIERS SHALL BE USED IN ACCORDANCE WITH
THE FOLLOWING:
o SET OUT AS PER THE ADJACENT PLAN.
o FOUNDED OFF VERY STIFF CLAY THAT IS UNIFORM
& STABLE THROUGHOUT.
o CONC. PIERS TO BE FOUNDED TO A MINIMUM OF
250 kPa BEARING CAPACITY. GEOTECH TO VERIFY
ON SITE.
o WHERE ROCK IS ENCOUNTERED, ALL PIER TO BE
FOUNDED OFF ROCK THAT IS UNIFORM & STABLE
WITH A MINIMUM OF 700 kPa BEARING CAPACITY
REFER TO GENERAL NOTES FOR DESIGN CRITERIA
CONCRETE :
INTERIOR SURFACES : A1
EXTERIOR SURFACES : B1
MASONRY :
MASONRY DURABILITY REQUIREMENTS : M2
WAFFLE SLAB NOTES
FOUNDATION NOTE
BORED PIER NOTE
DESIGN CRITERIA
EXPOSURE CLASSIFICATION
LEGEND
DENOTES Ø400 CONC. PIERS. REFER
TO BORED PIER NOTES ON THIS DWG &
TO BORED PIER DETAIL ON DWG S01.02.
DENOTES 2-N12 (75 SPACING 1200 LONG)
TRIMMERS TOP LOCATED 50 FROM ALL
RE-ENTRANT CORNERS, TYPICAL
REFER TO GENERAL NOTES FOR REINFORCEMENT COVER
25
STRENGTH
f'c
MAX SIZE
AGG. mm
CEMENT
TYPE
ADMIXTURE
WAFFLE SLAB GP -20
ELEMENT
CONCRETE QUALITY
80
SLUMP
mm
POD LAYOUT STARTING POINT
DENOTES BRICK WALL OVER
DENOTES STUD FRAMED WALL OVER
20CONC. PIERS GP -20 80
SITE PREPARATION SHALL BE CARRIED OUT IN
ACCORDANCE WITH THE GENERAL NOTES &
CURRENT EDITION OF AS2870 - RESIDENTIAL SLABS &
FOOTING CODE.
REFER TO GENERAL NOTES FOR CONCRETE COVERS
DENOTES LOCATION OF 225 DEEP PODS.
POD SIZE: 1090 x 1090 (CUT PODS AS REQUIRED)
85 THICK SLAB REINFORCED WITH SL82 MESH TOP
CONTINUOUS THROUGHOUT INCLUDING ANY EXTRAS
AS NOTED ON PLAN OR IN DETAILS.
DENOTES LOCATION OF 225 DEEP PODS.
POD SIZE: 1090 x 1090 (CUT PODS AS REQUIRED)
160 THICK SLAB REINFORCED WITH SL82 MESH TOP
& BOT. CONTINUOUS THROUGHOUT INCLUDING ANY
EXTRAS AS NOTED ON PLAN OR IN DETAILS.
DENOTES LOAD BEARING MASONRY WALL UNDER
DENOTES SLAB PENETRATION
XX
???DENOTES MINIMUM SLAB THICKNESS, UNO
DENOTES SLAB STEP DEPTH
32SUSPENDED GP -20 80
DENOTES Ø400 REINFORCED CONC. PIERS.
REINFORCE WITH 3-N16 BARS (FULL LENGTH)
WITH R6-300 TIES. REFER TO BORED PIER
NOTES ON THIS DWG FOR MIN. BEARING
CAPACITY.
![Page 5: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/5.jpg)
1:100
GROUND SLAB BOTTOM REINFORCEMENT LAYOUT PLAN
N1
2-2
00
N12-200
1:100
GROUND SLAB TOP REINFORCEMENT LAYOUT PLAN
N1
2-2
00
N12-200
MIN.
1000
MIN.
1000
4N16
x3000
4N
16
x3
00
0
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.02
GROUND SLAB REO PLANS
1:100 U.N.O.
4N20-200
SPACING OF BARS
SIZE OF BARS
NUMBER OF BARS
LAID
2nd & 3rd
LA
ID
1st &
4th
BAR DIA.
N12
N16
N20
N24
N28
N32
N36 800
700
600
500
400
300
200
A B
600
800
1000
1200
1400
1600
1800
TYPICAL REINFORCEMENT
BAR LAP AT STEPS
N20
N24
N28
N32
N36
390
340
295
245
N16
CO
G
STANDARD COG
SCHEDULE
BAR
440
COG (mm)
200
N24
N28
N32
N36
1280
1120
960
640N16
SLAB REINFORCEMENT
MIN. SPLICE SCHEDULE
BAR
1440
LAP (mm)
N20 800
480UP TO N12
A B
TOP OF
SLAB STEP
BOTTOM
SOFFIT STEP
AB
TOP OF SLAB STEP
BOTTOM OF SLAB STEP
R1.ALL SLABS TO BE REINFORCED AS NOTED ON PLAN U.N.O.
IN DETAILS.
REINFORCEMENT NOTES
R2.FOR REINFORCEMENT TO HOBS, STAIRS, ETC REFER TO
DETAILS AND STAIR SCHEDULE.
R3.REINFORCEMENT CROSSING PENETRATIONS IS TO BE
DISPLACED, NOT CUT.
R4.BAR TAG NOTATION:
PROVIDE SL82 MESH THROUGHOUT
AREA SHOWN THUS:
R6.
SLAB PENETRATION TRIMMER
2N16-1200 LONG (75 SPACING)
TRIMMERS BARS AT ALL RE-ENTRANT
CORNERS, TIED TO UNDERSIDE OF
TOP REINFORCEMENT.
SLAB RE-ENTRANT CORNER TRIMMER
SLAB CORNER TRIMMER
UP TO N12 200
TYPICAL SLAB TRIMMER DETAILS
ALL SLAB REINFORCEMENT TO BE LAID IN SEQUENCE
INDICATED BELOW:
R5.
SIDES
EXTERNALINTERNAL
BEAMS
BANDS
BTM
TOP
SLAB
30mm
45mm
30mm
45mm
30mm
45mm
30mm
BTM
TOP
SIDES
BTM
TOP
SIDES
30mm
45mm
45mm
45mm
30mm
45mm
30mm
REINFORCEMENT COVERS
30mm 45mm
30mm 45mm
1N16 L-BARS TOP IN CORNER
OF SLAB, 1000 LEGS.
PROVIDE 2N16 BARS TOP
EXTEND 600 MIN. PAST EACH
EDGE OF THE PENETRATION.
![Page 6: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/6.jpg)
1.5 x "D"
17
0 M
AX
.
ST
EP
SLO
PE
TO
BE
LE
SS
TH
AN
1 IN
10
"D
"
80
0 M
AX
.
ST
EP
300 LAP MIN
TYPICAL STRIP FOOTING STEP DETAIL
75
45
0
400
4L12TM TOP & BTM
R6-600 TIES
1:20
STRIP FOOTING 'SF1' DETAIL
1:20
RE
FE
R
TO
A
RC
H.
(M
AX
. 1
72
)
BORED PIER TO BE
FOUNDED ON MATERIAL
TO ENGINEER'S APPROVAL
AS PER
SLAB PLAN
BORED PIER:
MASS CONCRETE PIERS TYPICAL UNLESS
THROUGH FILL GREATER THAN 1000mm DEEP.
CLASS P SITES THEN REINFORCE WITH 3-N16
BARS (FULL LENGTH) WITH R6-300 TIES.
TYPICAL EDGE BEAM - 'EB1' INTERNAL BEAM - 'IB1'
300
150
110 300
150
STIFFENING RIB EDGE BEAM - 'EB3'
300
AS
P
ER
SL
AB
P
LA
N
300
15
0
MIN
.
(4
00
MA
X.)
300
INTERNAL BEAM - 'IB2' EDGE BEAM - 'EB2'
75
M
AX
.
ST
EP
WET AREA - STEP DETAIL
OPTIONAL
450
MIN.
AS
P
ER
SL
AB
P
LA
N
AS
P
ER
SL
AB
P
LA
N
AS
P
ER
SL
AB
P
LA
N
AS
P
ER
SL
AB
P
LA
N
TOP MESH
TOP MESH
TOP MESH
AS
P
ER
SL
AB
P
LA
N
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
1N12
DAMP-PROOF
MEMBRANE
3N12 (OR EQUIV.)
DAMP-PROOF
MEMBRANE
3N12 (OR EQUIV.)
TOP MESH
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
3N12 (OR EQUIV.)
TOP MESH
3N12 (OR EQUIV.)
TOP MESH
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
GARAGE DOOR REBATE
280 WIDE x 15mm DEEP
(OPTIONAL)
WALL BEYOND
DAMP-PROOF
MEMBRANE
3N12 (OR EQUIV.)
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
TOP MESH
1N12
DAMP-PROOF
MEMBRANE
DAMP-PROOF
MEMBRANE
DRIVEWAY TO THE
DETAIL OF OTHERS
DAMP-PROOF
MEMBRANE
DAMP-PROOF
MEMBRANE
600 LAP
500 LAP
50
0 L
AP
N12 BARS TO
FULLY OVERLAP
1-N12 BOTTOM EXTRA
FOR NON-PIERED SLABS
PIPE PENETRATION
THROUGH RIB
500 MIN. LAPEXTRA 1N12 TOP &
BOTTOM EXTRA
10
0
MIN
500 MIN. LAP
N12 BARS TO
FULLY OVERLAP
WAFFLE POD LAP DETAILS
WAFFLE POD DETAILS AT PENETRATION
AS
P
ER
SL
AB
P
LA
N
2N12 BARS TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
BORED PIER DETAIL
N12 AT RIB
LOCATIONS
1200 LONG
1:20 1:20 1:20 1:20 1:20
1:20
G.L.
1:20
1:20
1:201:20
STEM WIDTH
BEAM WIDTH STEM WIDTH
300 TO 399
110 TO 199
200 TO 299
400 TO 499 3
2
1
0
ADDITIONAL STEEL FOR
EDGE & INTERNAL BEAMS
STEM WIDTH OR
BEAM WIDTH
4
3
2
1
TOP STEEL
(No. N12 BARS)
BTM STEEL
(No. N12 BARS)
500 TO 599 4 5
10
0 M
IN
.
60
0 M
IN
.
60
0 M
IN
.
20
0
MIN
.
100 kPa NATURAL
FOUNDATION
MATERIAL
CONTROLLED
FILL TYPICAL
NOTE:
- FOR ALL SLAB & EDGE BEAM DETAILS
REFER TO TYPICAL DETAILS
- FOR BORED PIER REFER TO BORED
PIER DETAIL
ADDITIONAL PIERS AS
DIRECTED BY ENGINEER AT
TIME OF CONSTRUCTION OR
DEEPEN EDGE BEAM
SERVICES
TRENCH
60
0 M
IN
.
TYPICAL BEAM FOUNDATION DETAILS
1:20
EDGE & INTERNAL BEAMS
1:20
ADDITIONAL STEEL FOR
1N12 TOP AT PIERED
LOCATIONS ONLY
1N12 TOP AT PIERED
LOCATIONS ONLY
1N12 TOP AT PIERED
LOCATIONS ONLY
1N12 BAR TOP EXTRA
LAP 600 MIN. AS REQUIRED
1N12 TOP AT PIERED
LOCATIONS ONLY
1N12 BAR TOP EXTRA
LAP 600 MIN. AS REQUIRED
1N12 BAR TOP EXTRA
LAP 600 MIN. AS REQUIRED
BORED PIER
BORED PIER
BORED PIER
RE
FE
R
TO
A
RC
H.
(M
AX
. 1
72
)
TYPICAL EDGE BEAM - 'EB4'
300
150
110
150
STIFFENING RIB
300
15
0
MIN
.
(4
00
MA
X.)
300
INTERNAL BEAM - 'IB3' EDGE BEAM - 'EB5'
AS
P
ER
SL
AB
P
LA
N
AS
P
ER
SL
AB
P
LA
N
TOP & BOT. MESH
TOP & BOT.
MESH
AS
P
ER
SL
AB
P
LA
N
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
1N12
DAMP-PROOF
MEMBRANE
3N12 (OR EQUIV.)
TOP & BOT.
MESH
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
3N12 (OR EQUIV.)
DAMP-PROOF
MEMBRANE
3N12 (OR EQUIV.)
1N12 BAR TOP EXTRA
FOR PIERED SLABS
LAP 600 MIN. AS REQUIRED
TOP & BOT.
MESH
DAMP-PROOF
MEMBRANE
DAMP-PROOF
MEMBRANE
600 LAP
N12 AT RIB
LOCATIONS
1200 LONG
1:20 1:20 1:20 1:20
G.L.
1N12 TOP AT PIERED
LOCATIONS ONLY
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.03
GROUND DETAILS SHEET 1
1:20 U.N.O.
![Page 7: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/7.jpg)
300
TOP & BOT.
MESH
3N12 (OR EQUIV.)
DAMP-PROOF
MEMBRANE
2N12 TOP
FREE
DRAINAGE
BACKFILL
L-BARS TO MATCH
VERTICAL REO
MIN. (ØBAR x 40) LAP
55
1:20
SECTION
1
S02.01
1:20
SECTION
2
S02.01
TANKING - REFER
TO BLOCKWORK
TYPICAL DETAILS
FREE
DRAINAGE
BACKFILL
L-BARS TO MATCH
VERTICAL REO
MIN. (ØBAR x 40) LAP
55
1:20
SECTION
3
S02.01
CLAY SEAL
30
RE
BA
TE
ATLANTIS DRAINAGE CELL
TANKING - REFER
TO BLOCKWORK
TYPICAL DETAILS
ATLANTIS DRAINAGE CELL
TANKING - REFER
TO BLOCKWORK
TYPICAL DETAILS
FREE
DRAINAGE
BACKFILL
55
1:20
SECTION
4
S02.01
CLAY SEAL
ATLANTIS DRAINAGE CELL
GLAZING
BY OTHERS
10
30
350
1:20
TYPICAL REINFORCED BRICK PIER 'RBP1' DETAIL
3N20 FOR FULL HEIGHT
OF BRICK PIER
R10-300 TIES
GROUT FILL CORE
STARTER BAR TO
MATCH VERTICAL BAR
MIN. (ØBAR x 40) LAP
PLAN
4/ HILTI HVU CHEMICAL CAPSULE
WITH HAS-E M16 ROD (ZINC PLATED).
STANDARD 125mm EMBEDMENT
PROVIDE RECESS IN SLAB AS
REQUIRED TO SUIT BASE PLATE
THEN INFILL WITH NON-SHRINK
GROUT AFTER INSTALLATION
Cx
22
0
12mm THICK BASE PLATE
6 CFW/480/SP TO COLUMN
1:20
TYPICAL COLUMN 'C2, C4 & C7' BASE DETAIL
BASE PLATE PLAN VIEW
MIN.
140
220
290
29
0
LOCALLY THICKENING AROUND
COLUMN TO ACCOMMODATE
BASE PLATE DETAIL
MIN.
150
BASE PLATE PLAN VIEW
ORIENTATE BASE PLATE
TO SUIT WALL LOCATION
30
50
10mm THICK BASE PLATE
6 CFW/480/SP TO COLUMN
TYPICAL COLUMN 'C1, C5 & C7' BASE DETAIL
2/ HILTI HVU M12 CHEMICAL CAPSULE
WITH HAS-E M12 ROD (ZINC PLATED).
STANDARD 110mm EMBEDMENT
1:20
22
0
12mm THICK BASE PLATE
6 CFW/480/SP TO COLUMN
BASE PLATE PLAN VIEW
220
290
29
0
PROVIDE RECESS IN SLAB AS
REQUIRED TO SUIT BASE PLATE
THEN INFILL WITH NON-SHRINK
GROUT AFTER INSTALLATION
4/ HILTI HVU CHEMICAL CAPSULE
WITH HAS-E M16 ROD (ZINC PLATED).
STANDARD 125mm EMBEDMENT
MIN.
150
LOCALLY THICKENING AROUND
COLUMN TO ACCOMMODATE
BASE PLATE DETAIL
Cx
Cx
CW
1
CW
1
RW
1
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.04
GROUND DETAILS SHEET 2
1:20 U.N.O.
![Page 8: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/8.jpg)
1:100
GROUND WALL BRACING PLAN
WB1
MARK SIZE
STRAP BRACING - REFER TO DETAIL 'A' ON THIS DWG
DESCRIPTION
WALL BRACING
STRUCTURAL MEMBER SCHEDULE
WB2 PLY BRACING - REFER TO DETAIL 'B' ON THIS DWGWALL BRACING
WB2
WB
2
WB
2W
B2
WB2
WB2
WB2 WB2
WB
2
WB2 WB2
WB2
WB
2
WB2
WB
2
WB2 WB2
WB
2
WB
1W
B1
WB
1
WB
1
WB1
WB1
WB2
WB2
WB2 WB2
WB
1
WB
1W
B1
WB1 WB1
WB
2W
B2
NAIL SPACING - EDGE
PANEL LENGTH
NAIL SPACING - INTERMEDIATE
VERTICAL EDGES TO BE
SUPPORTED BY STUDS
HORIZONTAL JOINTS IN SHEETS TO OCCUR
OVER NOGGING AND NAILED AS PER TOP
AND BOTTOM PLATE
1.8m (MIN) TO 2.7M (MAX)
TENSION STRAPS TO BE PAIRED
AND OPPOSING
30° (MIN) TO
60° (MAX)
GALVANISED METAL STRAP 30 x 0.8mm LOOPED
OVER PLATE AND FIXED WITH FOUR GALVANISED
FLAT HEAD NAILS 30 x Ø2.8mm EACH END
PRODUCT
AUSTRALIAN
STANDARD
TYPE/
GRADE
MINIMUM THICKNESS (mm)FOR STUD SPACING (mm)
PANEL
LENGTH
(mm)
NAIL
SIZE
(mm)
NAIL SPACING (mm)
EDGE INTERMEDIATE
SPECIAL REQUIREMENTS
450 600
F8
F11
F14
F27
AS 2269PLYWOOD
7
6
4
4
9
7
6
4.5
900
2.8 x 30
(GALVANISED)
50 TO PLATES
150 TO EDGE
STUDS
300
NO NOGGING REQUIRED EXCEPT
AT SHEET ENDS. NAILS SHALL BE
7mm FROM ALL EDGES
HARDBOARD
(MASONITE)
AS 2458
GP 6.4 6.4 900
2.8 x 25
(GALVANISED)
50 300
NAILS TO BE 10mm FROM VERTICAL
EDGES AND 20mm FROM HORIZONTAL
EDGES. NO NOGGING REQUIRED
EXCEPT AT SHEET ENDS
NOTE: PANEL LENGTHS GREATER THAN THOSE LISTED ABOVE CAN BE CONSIDERED AS A NUMBER OF BRACING UNITS DIRECTLY PROPORTIONED
TO THEIR INSTALLED LENGTH, I.E. A 1200mm PANEL OF PLYWOOD EQUALS
1200
900
= 1.33 TYPE B BRACING UNITS.
TYPE OF
DIAGONAL
BRACE
MATERIAL & SIZE
NAILING REQUIREMENTS
SPECIAL REQUIREMENTS
EACH STUD EACH PLATE
GALVANISED
FLAT METAL
TENSION STRAP
NOMINAL SIZE
30 x 0.8mm AND
MINIMUM
SECTION 24mm
TENSION
STRAP
2-30 x Ø3.15mmGALVANISEDFLAT HEAD NAILS
4-30 x Ø3.15mmGALVANISED FLAT
HEAD NAILS
STRAPS MUST BE PROPERLY TENSIONED
AND MUST RETURN OVER TOP PLATE AND
UNDER BOTTOM PLATE.
THE STUD NEAREST TO EACH END OF EACH
DIAGONAL STRAP SHALL BE FIXED TO THE
PLATES WITH STRAPS OR FRAMING
ANCHORS 4-30 x Ø2.8mm NAILS EACH END
1:20
WALL BRACING 'DETAIL B'
1:20
WALL BRACING 'DETAIL A'
HILTI HIT-RE500 CHEMICAL INJECTION WITH
M10 GRADE4.6 GALV. THREADED ROD.
EMBED 160mm. INSTALL AS PER
MANUFACTURERS RECOMMENDATIONS. MIN
DISTANCE FROM SLAB EDGE TO BE 45mm.
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.11
GROUND WALL BRACING PLAN
1:100 U.N.O.
TIMBER FRAMING NOTES
ALL DESIGN, WORKMANSHIP & MATERIALS SHALL BE IN
ACCORDANCE WITH NATIONAL TIMBER FRAMING CODE
AS1684 CURRENT EDITION WITH AMENDMENTS, EXCEPT
WHERE VARIED BY THE CONTRACT DOCUMENTS.
TIMBER SIZES, CONNECTIONS AND BRACING WALL SHALL
BE TO FRAME MANUFACTURER'S DETAILS &
SPECIFICATIONS & SHALL BE IN ACCORDANCE WITH
AS1684. TIMBER FRAMING OUTSIDE THE SCOPE OF
AS1684 SHALL BE REFERED TO THE SUPERINTENDENT
FOR A DECISION BEFORE PROCEEDING.
ROOF BRACING & ANCHOR DETAILS WHERE NOT SHOWN
ON DRAWINGS SHALL BE IN ACCORDANCE WITH AS1684.
TF3.
TF2.
TF1.
![Page 9: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/9.jpg)
1:100
FENCE FOOTING LAYOUT PLAN
M
W
1
+
S
F
1
M
W
1
+
S
F
1
M
W
1
+
P
F
1
ADJOINING WALLS
ARE TO BE 200mm
WIDE. TYPICAL.
LOCAL THICKENING AT
BRICK PIER LOCATION.
REFER TO SECTION 1.
1
-
BW1 190 BLOCK N12-400 CORE FILLEDREFER TO PLAN
NOTE:
REFER TO MASONRY WALL DETAILS ON THIS DWG.
WALL No. THICKNESS
HORIZONTAL WALL
LENGTH
VERTICAL
REINFORCEMENT
HORIZONTAL
REINFORCEMENT
COMMENTS
N12-400
MASONRY WALL SCHEDULE
M
P
1
M
P
1
M
P
1
M
P
1
M
P
1
M
P
1
M
P
1
M
P
1
M
P
1
1.5 x "D"
170 M
AX
.
ST
EP
SLO
PE
TO
BE
LE
SS
TH
AN
1 IN
10
"D
"
800 M
AX
.
ST
EP
300 LAP MIN
TYPICAL STRIP FOOTING STEP DETAIL
1:20
SF1
700
STARTER BAR TO MATCH
VERTICAL REINFORCEMENT
MIN. (ØBAR x 40) LAP
GROUT FILL CAVITY
4N12 BARS FOR FULL
HEIGHT OF PIER
MA
X. 1800 H
IG
H
X X
4N12 U-BARS
SECTION X-X
600 x 600
CORE-FILLED
BLOCKWORK PIER
75
450
400
4L12TM TOP & BOT.
R6-600 TIES
1000 H
IG
H
1:20
TYPICAL STRIP FOOTING 'SF1' DETAIL
BW
1
BW
1
BW
1
700 x 700
STARTER BAR TO MATCH
VERTICAL REINFORCEMENT
MIN. (ØBAR x 40) LAP
MASS
CONCRETE.
BW
1
BW
1
450
1:20
SECTION
1
-
1:20
TYPICAL PAD FOOTING 'PF1' DETAIL
N12-400 TIES
MASONARY PIER 'MP1' DETAIL
NOTE: ALL MASONRY WALLS REQUIRE
VERTICAL CONTROL JOINTS AT 8000 CTS
FOR FULL HEIGHT OF WALL BUILT UP IN
NORMAL MORTAR. RAKE JOINT AND THEN
APPLY SEALANTS AS SPECIFIED TO EACH
FACE OF BLOCKWORK
GROUT FILLED
CORES
GALVANISED R20-600
300 LONG GREASE
AND CAP ONE END
SEALANT AS SPECIFIED
CONTROL JOINT DETAIL
TREAT AS PER 'BLOCKWALL
CONTROL JOINT'
10
BLOCKWALL
"T" JUNCTION CONTROL JOINT (C.J.)
1:20
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S02.21
FENCE FOOTING LAYOUT PLAN
1:100, 1:20 U.N.O.
THE FOOTINGS SHALL BE FOUNDED ON STIFF CLAY
MATERIAL WITH A MINIMUM SAFE BEARING CAPACITY
OF 150 kPa.
IF SLAB IS FOUNDED PARTLY ON STIFF CLAY, THEN
BORED PIERS SHALL BE USED IN ACCORDANCE WITH
THE FOLLOWING:
o FOUNDED OFF STIFF CLAY THAT IS UNIFORM &
STABLE THROUGHOUT.
o MINIMUM SAFE END BEARING OF 250 kPa.
GEOTECH TO VERIFY ON SITE.
o LOCATED AT CORNERS & INTERSECTION POINTS
OF BEAMS.
o LOCATED UNDER STEEL OR BRICK COLUMNS
OVER
o MAXIMUM 1800 SPACING FOR EDGE BEAMS OR
STRIP FOOTINGS.
o WHERE ROCK IS ENCOUNTERED, ALL PIER TO BE
FOUNDED OFF ROCK THAT IS UNIFORM & STABLE
WITH A MINIMUM OF 700 kPa BEARING CAPACITY.
REFER TO GENERAL NOTES FOR DESIGN CRITERIA
CONCRETE :
INTERIOR SURFACES : A1
EXTERIOR SURFACES : B1
MASONRY :
MASONRY DURABILITY REQUIREMENTS : M2
FOUNDATION NOTE
BORED PIER NOTE
DESIGN CRITERIA
EXPOSURE CLASSIFICATION
LEGEND
REFER TO GENERAL NOTES FOR REINFORCEMENT COVER
20
STRENGTH
f'c
MAX SIZE
AGG. mm
CEMENT
TYPE
ADMIXTURE
CONC. FOOTINGS GP -20
ELEMENT
CONCRETE QUALITY
80
SLUMP
mm
DENOTES BRICK WALL OVER
DENOTES STUD FRAMED WALL OVER
![Page 10: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/10.jpg)
1:100
FIRST FLOOR MARKING PLAN
C
3
(
o
)
C
2
C
7
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
7
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
4
(
u
)
GRADE C350SB1
TB BY OTHER'S
MARK SIZE COMMENTS
200 x 100 x 6.0 RHS
-TIMBER BEAM
DESCRIPTION
STEEL BEAM
STRUCTURAL MEMBER SCHEDULE
GRADE C350SB2 200 x 100 x 6.0 RHSSTEEL BEAM
GRADE 300 PLUSSB3 180 PFC + 10 PL.STEEL BEAM
SB4 STEEL BEAM
SB5 STEEL BEAM
GRADE C350C1 89 x 89 x 3.5 SHSSTEEL COLUMN
TP1 90 x 90 F7 -TIMBER POST
GRADE 300 PLUSSB6 250 UC 72.9STEEL BEAM
GRADE 300 PLUSSB7 180 PFC + 10PL.STEEL BEAM
GRADE 300 PLUSSB8 250 UB 37.3STEEL BEAM
GRADE 300 PLUS180 PFC + 10PL.
GRADE 300 PLUS180 PFC
0 - 1800 100 x 100 x 6.0 GALINTEL ANGLE BAR
1801 - 3000 150 x 100 x 6.0 GALINTEL ANGLE BAR
2401 - 3000
SPAN LINTEL SIZE
150 x 90 x 16 UA
NON LOAD BEARING STEEL LINTEL SCHEDULE
0 - 900
901 - 1800 90 x 90 x 8.0 EA
75 x 75 x 6.0 EA
1801 - 2400 150 x 90 x 8.0 UA
1000 150
150
110
150
150
MIN. END
BEARING
MAX. HEIGHT
OF BRICKWORK
OVER LINTEL
1501000
3000
3000
3000
3000
NOTE: MINIMUM 3 COURSES OF BRICK OVER LINTEL
FJ
FJ
TB
TB
FJ
FJ
FJ
FJ
FJ
FJ
FJ
FJ
TB
FJ
FJ
TB
FJ
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
FJ
RF
RF
RF
FJ
RF
RF
RF
FJ
SB4 SB7 SB10
SB
1
SB3
SB
5
SB2
SB6
SB
9
SB8 SB11
SB
12
SB13
SB
14
(B
PF
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
C
1
(
u
)
SB15 SB16
SB17 SB18 SB19
SB
28
SB
20
SB
21
SB22
SB
26
RF
RF
SB23
TB
C
1
(
u
)
SB25
SB27SB24
C
1
(
u
)
GRADE 300 PLUSSB9 250 UC 72.9STEEL BEAM
GRADE 300 PLUSSB10 180 PFC + 10PL.STEEL BEAM
GRADE 300 PLUSSB11 360 UB 56.7STEEL BEAM
SB12 STEEL BEAM
SB13 STEEL BEAM
GRADE 300 PLUSSB14 200 PFCSTEEL BEAM
GRADE 300 PLUSSB15 180 PFC + 10PL.STEEL BEAM
GRADE 300 PLUSSB16 180 PFC + 10PL.STEEL BEAM
GRADE 300 PLUS230 PFC + 10 PL.
GRADE 300 PLUS250 UC 72.9
GRADE 300 PLUSSB17 200 UB 18.2STEEL BEAM
GRADE 300 PLUSSB18 360 UB 56.7STEEL BEAM
GRADE 300 PLUSSB19 250 PFC + 10 PL.STEEL BEAM
SB20 STEEL BEAM
SB21 STEEL BEAM
GRADE 300 PLUSSB22 250 PFCSTEEL BEAM
GRADE 300 PLUSSB23 180 PFC + 10PL.STEEL BEAM
GRADE 300 PLUSSB24 250 PFC + 10PL.STEEL BEAM
GRADE 300 PLUS250 UC 72.9
GRADE 300 PLUS200 PFC + 10 PL.
GRADE 300 PLUSSB25 250 PFCSTEEL BEAM
GRADE 300 PLUSSB26 250 PFCSTEEL BEAM
GRADE 300 PLUSSB27 150 x 100 x 10 UASTEEL BEAM
GRADE G250SB28 200 x 200 x 9 GALINTEL T-BARSTEEL BEAM
C
5
GRADE C350C2 125 x 125 x 6.0 SHSSTEEL COLUMN
LIGHTWEIGHT
BLADE WALL OVER
TO BUILDERS DETAIL
5
S03.02
1
S03.02
1
SIM.
4
S03.02
3
S03.02
2
S03.02
5
SIM.
6
S03.02
7
S03.02
8
S03.02
9
S03.02
12
S03.02
11
S03.02
10
S03.02
LIGHTWEIGHT
BLADE WALL OVER
TO BUILDERS DETAIL
13
S03.03
'C'
REFER TO BEAM
OVER BEAM DETAIL
REFER TO BEAM
OVER BEAM DETAIL
GRADE C350C3 89 x 89 x 3.5 SHSSTEEL COLUMN
C
3
(
o
)
C
3
(
o
)
C
3
(
o
)
C
3
(
o
)
C
4
(
u
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
T
P
1
(
o
)
GRADE C350C4 150 x 100 x 6.0 RHSSTEEL COLUMN
C
5
BPF - DENOTES BRACED PORTAL FRAME
E1
S03.04
REFER TO 'SB3 - SB4, SB7
& SB8' TO BLOCKWALL
CONNECTION DETAIL
MW1
MW1
MW1MW1
GRADE C350C5 150 x 50 x 6.0 RHSSTEEL COLUMN
GRADE C350C6 150 x 50 x 4.0 RHSSTEEL COLUMN
GRADE C350C7 150 x 100 x 6.0 RHSSTEEL COLUMN
4 x C6
R
B
P
1
R
B
P
1
10mm THICK END PLATE
6 CFW/480/SP TO BEAM
SECURE TO BLOCKWALL USING 2/ HILTI HVU
M16 CHEMICAL CAPSULE WITH HAS-E M16 ROD
(ZINC PLATED). STANDARD 125mm EMDEMENT.
'SB3 - SB5, SB7 & SB8' TO BLOCKWALL CONNECTION DETAIL
1:20
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S03.01
FIRST FLOOR MARKING PLAN
1:100 U.N.O.
TIMBER FRAMING NOTES
ALL DESIGN, WORKMANSHIP & MATERIALS SHALL BE IN
ACCORDANCE WITH NATIONAL TIMBER FRAMING CODE
AS1684 CURRENT EDITION WITH AMENDMENTS, EXCEPT
WHERE VARIED BY THE CONTRACT DOCUMENTS.
TIMBER SIZES, CONNECTIONS AND BRACING WALL SHALL
BE TO FRAME MANUFACTURER'S DETAILS &
SPECIFICATIONS & SHALL BE IN ACCORDANCE WITH
AS1684. TIMBER FRAMING OUTSIDE THE SCOPE OF
AS1684 SHALL BE REFERED TO THE SUPERINTENDENT
FOR A DECISION BEFORE PROCEEDING.
ROOF BRACING & ANCHOR DETAILS WHERE NOT SHOWN
ON DRAWINGS SHALL BE IN ACCORDANCE WITH AS1684.
TF3.
TF2.
TF1.
LEGEND
DENOTES LOAD BEARING WALLS UNDER
DENOTES BRICK WALLS OVER
DENOTES STUD FRAMED WALLS OVER
DENOTES PENETRATION
DENOTES FLOOR JOIST SPAN DIRECTION
DENOTES ROOF FRAMING SPAN DIRECTION (BY OTHERS)
DENOTES BEARING PLATE - REFER TO DETAILS
DENOTES 100 END BEARING
DENOTES 150 END BEARING
DENOTES 200 END BEARING
DENOTES 300 END BEARING
FJ
'BP' -
'A' -
'B' -
'C' -
'D' -
RF
![Page 11: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/11.jpg)
ROOF FRAMING
BY OTHERS
S
B
8
FJ
1:20
SECTION
1
S03.01
S
B
7
PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
GLAZING BY
OTHERS
GLAZING BY
OTHERS
S
B
1
1:20
SECTION
2
S03.01
GLAZING BY
OTHERS
GLAZING BY
OTHERS
S
B
1
4
1:20
SECTION
3
S03.01
FJFJ
1:20
SECTION
4
S03.01
S
B
6
F
J
F
J
2
/
F
J
F
J
S
B
1
6
F
J
1:20
SECTION
5
S03.01
PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
FJ
1:20
SECTION
6
S03.01
BLOCKING
DOOR HARDWARE
BY OTHERS
S
B
2
6
SECURE TIMBER WALING PLATE TO WALL
USING HILTI HIT-HY70 CHEMICAL INJECTION
WITH HIT-V M12 ROD (ZINC PLATED) USING
HIT SC COMPOSITE SLEEVE AT 690 CTS.
STANDARD 85mm EMBEDMENT.
FJ
1:20
SECTION
7
S03.01
LIGHTWEIGHT
BALUSTRADE
BY OTHERS
2
/
F
J
F
J
F
J
NON LOAD BEARING
LINTEL. REFER TO
SCHEDULE
TIMBER BEAM
TO DETAILS OF
OTHERS
1:20
SECTION
8
S03.01
ROOF FRAMING
BY OTHERS
S
B
2
4PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
FJ
S
B
2
5
BOX GUTTER
BY OTHERS
BLOCKING
1:20
SECTION
9
S03.01
ROOF FRAMING
BY OTHERS
S
B
2
3PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
S
B
2
5
BOX GUTTER
BY OTHERS
2
/
F
J
F
J
F
J
LIGHTWEIGHT
BALUSTRADE
BY OTHERS
S
B
2
2
DOOR HARDWARE
BY OTHERS
FJ
1:20
SECTION
10
S03.01
LIGHTWEIGHT
BALUSTRADE
BY OTHERS
S
B
2
0
F
J
F
J
S
B
2
1PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
END PLATE
ROOF FRAMING
BY OTHERS
S
B
1
9
1:20
SECTION
11
S03.01
2
/
F
J
F
J
S
B
1
8
FJ
ROOF FRAMING
BY OTHERS
1:20
SECTION
12
S03.01
PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
SECURE USING
M12 AT 900 CTS
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S03.02
FIRST FLOOR DETAILS SHEET 1
1:20 U.N.O.
![Page 12: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/12.jpg)
10
10mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
10mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
BEAMS TO BE LOCATED CENTRALLY OVER COLUMN TYPICAL
PFCUB
ST
EE
L C
OL
UM
N
TYPICAL COLUMN 'C1 & C7' CAP DETAILS
1:20
ST
EE
L C
OL
UM
N
12mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
4M16 8.8/S BOLTS
UB
ST
EE
L C
OL
UM
N
UB
NOTE:
SIMILAR DETAIL FOR PFC
TO PFC. 2M16 8.8/S BOLTS
EACH SIDE OF POST
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
2
/
F
J
F
J
S
B
1
2
F
J
1:20
SECTION
13
S03.01
PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
12mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
4M16 8.8/S BOLTS
ST
EE
L C
OL
UM
N
UB
NOTE:
SIMILAR DETAIL FOR PFC
TO PFC. 2M16 8.8/S BOLTS
EACH SIDE OF POST
10mm THICK STIFFENER PLATE
EACH SIDE OF WEB
6 CFW/480/SP TO BEAM
10mm THICK STIFFENER PLATE
EACH SIDE OF WEB
6 CFW/480/SP TO BEAM
10mm THICK STIFFENER PLATE
EACH SIDE OF WEB
6 CFW/480/SP TO BEAM
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
'SB5' TO 'SB6' CONNECTION DETAIL
(CONNECTION CAPACITY 55 kN ULTIMATE)
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
2M16 8.8/S BOLTS
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
SB5
S
B
6
1:20
'SB8/ SB11' TO 'SB9' CONNECTION DETAIL
(CONNECTION CAPACITY 100 kN ULTIMATE)
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M16 8.8/S BOLTS
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
SB8
S
B
9
1:20
SB11
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M20 8.8/S BOLTS
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M20 8.8/S BOLTS
S
B
9
'SB6/ SB13' TO 'SB9' CONNECTION DETAIL
(CONNECTION CAPACITY 100 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
SB6
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M16 8.8/S BOLTS
SB25
'SB25' TO 'SB26' CONNECTION DETAIL
(CONNECTION CAPACITY 100 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
S
B
2
6
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M20 8.8/S BOLTS
SB20
'SB20' TO 'SB25' CONNECTION DETAIL
(CONNECTION CAPACITY 100 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
S
B
2
5
'SB23 & SB24' TO 'C1' CONNECTION DETAIL
10mm THICK CLEAT PLATE
SLOTTED THROUGH
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
1:20
3M16 8.8/S BOLTS
SB24 SB23
C1
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M16 8.8/S BOLTS
SB22
S
B
2
0
'SB22' TO 'SB20' CONNECTION DETAIL
1:20
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M16 8.8/S BOLTS
SB19
S
B
2
0
'SB18 & SB19' TO 'SB20' CONNECTION DETAIL
1:20
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M20 8.8/S BOLTS
SB18
'SB28' TO 'SB19' CONNECTION DETAIL
1:20
SB28
S
B
1
9
10mm THICK CLEAT PLATE
6 CFW/480/SP TO BEAM
2M16 8.8/S BOLTS
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
3M20 8.8/S BOLTS
SB13
'SB21' TO 'C1' CONNECTION DETAIL
10mm THICK CLEAT PLATE
SLOTTED THROUGH
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
1:20
SB21C1
10mm THICK CLEAT PLATE
6 CFW/480/SP TO END PLATE
2M16 8.8/S BOLTS
10mm THICK END PLATE
6 CFW/480/SP TO BEAM
SB1
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
S
B
3
'SB1' TO 'SB3' CONNECTION DETAIL
(CONNECTION CAPACITY 55 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
10mm THICK CLEAT PLATE
6 CFW/480/SP TO END PLATE
2M16 8.8/S BOLTS
10mm THICK END PLATE
6 CFW/480/SP TO BEAM
SB1
80 WIDE x 10mm THICK
CLEAT PLATE
6 CFW/480/SP TO COLUMN
10mm THICK CLEAT PLATE
6 CFW/480/SP TO CLEAT PLATE
C2
'SB1' TO 'C2' CONNECTION DETAIL
(CONNECTION CAPACITY 55 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
10mm THICK CLEAT PLATE
6 CFW/480/SP TO END PLATE
2M16 8.8/S BOLTS
10mm THICK END PLATE
6 CFW/480/SP TO BEAM
SB2
10mm THICK CLEAT PLATE
SLOTTED THROUGH
6 CFW/480/SP TO COLUMN
C2
'SB2' TO 'C2' CONNECTION DETAIL
(CONNECTION CAPACITY 55 kN ULTIMATE)
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
1:20
10
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S03.03
FIRST FLOOR DETAILS SHEET 2
1:20 U.N.O.
![Page 13: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/13.jpg)
SB14
R
B
1
S
B
3
S
B
4
C4
C4
C3
SB5 (BEYOND)
S
B
2
R
1
RF
R
B
5
1:50
ELEVATION
E1
S03.01
B
-
A
-
300 x 100 x 16 BEARING PLATE
6 CFW/480/SP ALL ROUND
ON 20 MORTAR BED. (FOR
ORIENTATION OF PLATE
REFER PLAN).
STEEL BEAM
REFER TO
SCHEDULE
TYPICAL BEARING PLATE DETAIL
1:20
5 B
RIC
K
CO
UR
SE
M
IN
.
ROOF FRAMING
BY OTHERS
SB
NOTE:
GALINTEL T-BAR DESIGNED BASED ON UNIFORMLY
DISTRIBUTED LOADING TO T-BAR. IF POINT LOADS ARE
TO BE APPLIED, THE ENGINEER IS TO BE INFORMED
PRIOR TO LOADING.
1:20
TYPICAL GALINTEL T-BAR DETAIL
ROOF FRAMING
BY OTHERS
1:20
TYPICAL LINTEL DETAIL
NON LOAD BEARING
LINTEL. REFER TO
SCHEDULE
TIMBER BEAM
TO DETAILS OF
OTHERS
'A' = 110
'B' = 150
'C' = 200
'D' = 300
20 MORTAR
BED
1:20
BEAM END BEARING DETAIL
STEEL BEAM
1:20
BEAM OVER BEAM DETAIL
TO
S
UIT
CE
IL
IN
G
HE
IG
HT
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
10mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
65 x 65 x 4.0 SHS STUB
SB
S
B
S
B
1:20
TYPICAL PFC LINTEL DETAIL
PLATE STITCH WELDED TO
BEAM USING 6mm FILLET
WELD (WELD 150, MISS 150)
STEEL BEAM
REFER TO TYPICAL
COLUMN CAP DETAILS
MIN
.
D/3
250
ST
EE
L C
OL
UM
N
10mm THICK PLATE
6 CFW/480/SP TO
SIDE OF WEB
TRIM TOP FLANGE & WEB AS
REQUIRED TO SUIT ROOF STRUCTURE
WELD FLANGE PLATE TO MATCH BEAM
FLANGE THICKNESS
TRIMMED BEAM END DETAIL
1:20
D
6 CFW/480/SP
ALL ROUND
SB14SB14
500
6mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
F.P.B.W. 'V'-PREP OR SIMILAR TO
AS1554 TO ACHIEVE BUTT WELD.
2/ 20mm THICK END PLATES
6 CFW/480/SP TO BEAM
4M20 8.8/TB BOLTS
A2
SIM.
DETAIL B
-
1:20
SB14 SB14
500
6mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
F.P.B.W. 'V'-PREP OR SIMILAR TO
AS1554 TO ACHIEVE BUTT WELD.
2/ 20mm THICK END PLATES
6 CFW/480/SP TO BEAM
4M20 8.8/TB BOLTS
A2
-
DETAIL A
-
1:20
A1
-
10mm THICK CLEAT PLATE
6 CFW/480/SP TO END PLATE
2M16 8.8/S BOLTS
10mm THICK END PLATE
6 CFW/480/SP TO BEAM
10mm THICK CLEAT PLATE
SLOTTED THROUGH
6 CFW/480/SP TO BEAM
3M16 8.8/S BOLTS
1:20
SECTION
A1
-
SB2
SB6
S
B
2
S
B
1
4
1:20
SECTION
A2
-
BEAMS TO BE LOCATED CENTRALLY OVER COLUMN TYPICAL
TYPICAL COLUMN 'C3' CAP DETAILS
1:20
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
12mm THICK BASE PLATE
6 CFW/480/SP TO COLUMN
4M16 8.8/S BOLTS
C3
UB/ UC
10mm THICK STIFFENER PLATE
EACH SIDE OF WEB
6 CFW/480/SP TO BEAM
12mm THICK BASE PLATE
6 CFW/480/SP TO COLUMN
2M20 8.8/S BOLTS
C3
PFC
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S03.04
FIRST FLOOR DETAILS SHEET 3
1:20 U.N.O.
![Page 14: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/14.jpg)
1:100
FIRST FLOOR WALL BRACING PLAN
WB1
MARK SIZE
STRAP BRACING - REFER TO DETAIL 'A' ON THIS DWG
DESCRIPTION
WALL BRACING
STRUCTURAL MEMBER SCHEDULE
WB2 PLY BRACING - REFER TO DETAIL 'B' ON THIS DWGWALL BRACING
WB
1
WB2
WB
1
WB
1
WB2
WB
1
WB
2
WB
2W
B2
WB2
WB2WB1WB2
WB
2
WB
1
WB
1
WB
2
WB
1
WB
1W
B1
WB
1W
B1
WB
1
WB1
WB1
WB
2
WB1
WB1WB2
WB
2
WB2
WB
2
NAIL SPACING - EDGE
PANEL LENGTH
NAIL SPACING - INTERMEDIATE
VERTICAL EDGES TO BE
SUPPORTED BY STUDS
HORIZONTAL JOINTS IN SHEETS TO OCCUR
OVER NOGGING AND NAILED AS PER TOP
AND BOTTOM PLATE
1.8m (MIN) TO 2.7M (MAX)
TENSION STRAPS TO BE PAIRED
AND OPPOSING
30° (MIN) TO
60° (MAX)
GALVANISED METAL STRAP 30 x 0.8mm LOOPED
OVER PLATE AND FIXED WITH FOUR GALVANISED
FLAT HEAD NAILS 30 x Ø2.8mm EACH END
PRODUCT
AUSTRALIAN
STANDARD
TYPE/
GRADE
MINIMUM THICKNESS (mm)FOR STUD SPACING (mm)
PANEL
LENGTH
(mm)
NAIL
SIZE
(mm)
NAIL SPACING (mm)
EDGE INTERMEDIATE
SPECIAL REQUIREMENTS
450 600
F8
F11
F14
F27
AS 2269PLYWOOD
7
6
4
4
9
7
6
4.5
900
2.8 x 30
(GALVANISED)
50 TO PLATES
150 TO EDGE
STUDS
300
NO NOGGING REQUIRED EXCEPT
AT SHEET ENDS. NAILS SHALL BE
7mm FROM ALL EDGES
HARDBOARD
(MASONITE)
AS 2458
GP 6.4 6.4 900
2.8 x 25
(GALVANISED)
50 300
NAILS TO BE 10mm FROM VERTICAL
EDGES AND 20mm FROM HORIZONTAL
EDGES. NO NOGGING REQUIRED
EXCEPT AT SHEET ENDS
NOTE: PANEL LENGTHS GREATER THAN THOSE LISTED ABOVE CAN BE CONSIDERED AS A NUMBER OF BRACING UNITS DIRECTLY PROPORTIONED
TO THEIR INSTALLED LENGTH, I.E. A 1200mm PANEL OF PLYWOOD EQUALS
1200
900
= 1.33 TYPE B BRACING UNITS.
TYPE OF
DIAGONAL
BRACE
MATERIAL & SIZE
NAILING REQUIREMENTS
SPECIAL REQUIREMENTS
EACH STUD EACH PLATE
GALVANISED
FLAT METAL
TENSION STRAP
NOMINAL SIZE
30 x 0.8mm AND
MINIMUM
SECTION 24mm
TENSION
STRAP
2-30 x Ø3.15mmGALVANISEDFLAT HEAD NAILS
4-30 x Ø3.15mmGALVANISED FLAT
HEAD NAILS
STRAPS MUST BE PROPERLY TENSIONED
AND MUST RETURN OVER TOP PLATE AND
UNDER BOTTOM PLATE.
THE STUD NEAREST TO EACH END OF EACH
DIAGONAL STRAP SHALL BE FIXED TO THE
PLATES WITH STRAPS OR FRAMING
ANCHORS 4-30 x Ø2.8mm NAILS EACH END
1:20
WALL BRACING 'DETAIL B'
1:20
WALL BRACING 'DETAIL A'
HILTI HIT-RE500 CHEMICAL INJECTION WITH
M10 GRADE4.6 GALV. THREADED ROD.
EMBED 160mm. INSTALL AS PER
MANUFACTURERS RECOMMENDATIONS. MIN
DISTANCE FROM SLAB EDGE TO BE 45mm.
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S03.11
FIRST FLOOR WALL BRACING PLAN
1:100 U.N.O.
TIMBER FRAMING NOTES
ALL DESIGN, WORKMANSHIP & MATERIALS SHALL BE IN
ACCORDANCE WITH NATIONAL TIMBER FRAMING CODE
AS1684 CURRENT EDITION WITH AMENDMENTS, EXCEPT
WHERE VARIED BY THE CONTRACT DOCUMENTS.
TIMBER SIZES, CONNECTIONS AND BRACING WALL SHALL
BE TO FRAME MANUFACTURER'S DETAILS &
SPECIFICATIONS & SHALL BE IN ACCORDANCE WITH
AS1684. TIMBER FRAMING OUTSIDE THE SCOPE OF
AS1684 SHALL BE REFERED TO THE SUPERINTENDENT
FOR A DECISION BEFORE PROCEEDING.
ROOF BRACING & ANCHOR DETAILS WHERE NOT SHOWN
ON DRAWINGS SHALL BE IN ACCORDANCE WITH AS1684.
TF3.
TF2.
TF1.
![Page 15: S04.01 Roof Marking Plan - Strathfield Council · plan. TRIMMER BARS IN SLAB: TOP REINFORCEMENT BOTTOM REINFORCEMENT x x x x 1-N16 x 1200 LG Placed on centre of incoming joint 3ODFHG](https://reader030.fdocuments.net/reader030/viewer/2022041123/5d206e1788c993e9188c2026/html5/thumbnails/15.jpg)
1:100
ROOF MARKING PLAN
LAMINATED VENEERRB1
TB BY OTHER'S
MARK SIZE COMMENTS
300 x 45 HYSPAN LVL 13
-TIMBER BEAM
DESCRIPTION
STEEL BEAM
STRUCTURAL MEMBER SCHEDULE
LAMINATED VENEERRB2 300 x 45 HYSPAN LVL 13STEEL BEAM
LAMINATED VENEERRB3 300 x 45 HYSPAN LVL 13STEEL BEAM
RB4 STEEL BEAM
RB5 STEEL BEAM
TP BY OTHER'S -TIMBER POST
LAMINATED VENEERRB6 2/ 300 x 45 HYSPAN LVL 13STEEL BEAM
GRADE 300 PLUSRB7 200 UB 18.2STEEL BEAM
LAMINATED VENEERRB8 300 x 45 HYSPAN LVL 13STEEL BEAM
LAMINATED VENEER300 x 45 HYSPAN LVL 13
GRADE 300 PLUS200 UB 18.2
RF
RF
RF
RF
RF
RF
RF
TB (u)RB6
R1
T
P
1
(
u
)
C
2
(
u
)
RB1 RB2
T
P
1
(
u
)
'
T
D
'
'
T
D
' RB3
T
P
1
(
u
)
T
P
1
(
u
)
RB
4
C
3
(
u
)
RB5
(CONTINUOUS)
C
5
(
u
)
T
P
1
(
u
)
T
P
1
(
u
)
C
3
(
u
)
'
T
D
'
'
T
D
'
RB7
TB TB TB TB TB
TB
TB
RB8
T
P
1
(
u
)
T
P
1
(
u
)
TB
TB
C
3
(
u
)
RB10
'
T
D
'
C
3
(
u
)
C
3
(
u
)
RB
9
SB
11
RB12
'
T
D
'
'
T
D
'
RB9 STEEL BEAM
RB10 STEEL BEAM
LAMINATED VENEERRB11 300 x 45 HYSPAN LVL 13STEEL BEAM
LAMINATED VENEERRB12 300 x 45 HYSPAN LVL 13STEEL BEAM
GRADE 300 PLUSRB13 200 UB 18.2STEEL BEAM
GRADE G250180 DEEP CAVI-T-BAR
LAMINATED VENEER300 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
2/ 240 x 45 HYSPAN LVL 13
ALT. 180 UB 16.1
ALT. 2/ 240 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
ALT. 2/ 240 x 45 HYSPAN LVL 13
GRADE 300 PLUS
1
-
-R1 300 x 45 HYSPAN AT 600 CTSRAFTERS
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
R
F
1
-RF1 30 x 0.8 G.I. STRAPROOF BRACING
C
5
(
u
)
C
5
(
u
)
C
5
(
u
)
C
5
(
u
)
C
5
(
u
)
GRADE C350C2 125 x 125 x 6.0 SHSSTEEL COLUMN
GRADE C350C3 89 x 89 x 3.5 SHSSTEEL COLUMN
GRADE C350C4 150 x 100 x 6.0 RHSSTEEL COLUMN
GRADE C350C5 150 x 50 x 6.0 RHSSTEEL COLUMN
GRADE C350C6 150 x 50 x 4.0 RHSSTEEL COLUMN
R
1
ROOF FRAMING
BY OTHERS
T
B
GLAZING
BY OTHERS
GLAZING BY OTHERS.
PROVIDE TIMPBER POST
BETWEEN GLAZING TO SUPPORT
TIMBER BEAMS (BY OTHERS)
T
B
REFER TO TYPICAL
EAVES OVERHANG
DETAIL
1:20
SECTION
1
-
TYPICAL EAVES OVERHANG DETAIL
R
B
BLOCKING TO
BUILDER'S DETAIL
GI MINI GRIP CONNECTORS
MIN 5 No Ø28 NAILS TO EACH FACE
32 x 1.2 BUILDER'S STRAP
6 x Ø3.15 NAILS EACH
SIDE
STRUCTURAL FASCIA
TYPICAL
500 500
1:20
R1 R1
30x1.0 HOOP IRON
STRAP
SECURE STRAP WITH 4 SUPER
TEC SERIES 500 FASTENERS, 12
GUAGE 5.43mm THREAD DIA.
SCREWS OR EQUIV.) PRE-DRILL
8mm DIA. HOLES AS REQUIRED.
SB/ TB
MIN
. 1
00
0
1:20
TIE DOWN 'TD' DETAIL
10mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
10mm THICK CAP PLATE
6 CFW/480/SP TO COLUMN
2M16 8.8/S BOLTS
BEAMS TO BE LOCATED CENTRALLY OVER COLUMN TYPICAL
PFC/ T-BARUB
ST
EE
L C
OL
UM
N
TYPICAL COLUMN 'C2, C3, C5 & C6' CAP DETAILS
1:20
ST
EE
L C
OL
UM
N
ALTERNATIVELY SITE WELD USING 6 CFW/480/SP ALL ROUND
10mm THICK STIFFENER PLATE
EACH SIDE OF WEB
6 CFW/480/SP TO BEAM
10mm THICK STIFFENER PLATE
6 CFW/480/SP TO BEAM
COPYRIGHT
All rights reserved.
These drawings, plans and specifications and the copyright are
the property of Engineering Studio and must not be used,
reproduced or copied wholly or in part without the written
permission of Engineering Studio.
SCALE:
JOB NUMBER:
DRAWN BY:
DWG NUMBER: ORIGINAL SIZE:
A2
DATE:DESIGNED BY:
NOTE: DO NOT SCALE OFF DRAWINGS. REFER TO
ARCHITECTURAL PLANS. VERIFY DIMENSIONS ON SITE
DESCRIPTIONDATEREV BY
13060
FOR NKT ARCHITECTURE
AT 21 BARKER ROAD, STRATHFIELD
PROPOSED RESIDENCE
10.02.14 PRELIMINARY ISSUEP1 H.L.
JANUARY 204T.I.
H.L.
05.03.14 ISSUED FOR C.CA H.L.
19.05.14 GENERALLY REVISEDB H.L.
03.07.14 GENERALLY REVISEDC H.L.
16.10.15 FENCE DETAILS ADDEDD F.I.
S04.01
ROOF MARKING PLAN
1:100, 1:50 U.N.O.
TIMBER FRAMING NOTES
ALL DESIGN, WORKMANSHIP & MATERIALS SHALL BE IN
ACCORDANCE WITH NATIONAL TIMBER FRAMING CODE
AS1684 CURRENT EDITION WITH AMENDMENTS, EXCEPT
WHERE VARIED BY THE CONTRACT DOCUMENTS.
TIMBER SIZES, CONNECTIONS AND BRACING WALL SHALL
BE TO FRAME MANUFACTURER'S DETAILS &
SPECIFICATIONS & SHALL BE IN ACCORDANCE WITH
AS1684. TIMBER FRAMING OUTSIDE THE SCOPE OF
AS1684 SHALL BE REFERED TO THE SUPERINTENDENT
FOR A DECISION BEFORE PROCEEDING.
ROOF BRACING & ANCHOR DETAILS WHERE NOT SHOWN
ON DRAWINGS SHALL BE IN ACCORDANCE WITH AS1684.
TF3.
TF2.
TF1.
LEGEND
DENOTES LOAD BEARING WALLS UNDER
DENOTES OUTLINE OF NON LOAD BEARING WALLS
UNDER
DENOTES ROOF FRAMING SPAN DIRECTION (BY OTHERS)
RF