technical data Split Sky Air air conditioning systems RXS-F2V1B

Transcript of RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning...

Page 1: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

technical data

SplitSky Air

air cond

itioning

systems

RXS-F2V1B

Page 2: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

Het ISO14001 assures an effective environmental management system in order to help protect human health and the environment from potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

“ The present publication is drawn up by way of informa-tion only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this publication to the best of its knowledge. No express or implied warranty is given for the complete-ness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, In the broadest sense, aris-ing from or related to the use and/or interpretation of this publication. All content is copyrighted by Daikin Europe N.V..”

Split - Sky Air

03/2

007

Prin

ted

in B

elgi

um b

y G

oeki

nt G

raph

ics

Copy

right

© D

aiki

n

EEDEN07

Naamloze VennootschapZandvoordestraat 300B-8400 Oostende, Belgiumwww.daikin.euBTW: BE 0412 120 336RPR Oostende

Page 3: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

technical data

SplitSky Air

air cond

itioning

systems

RXS-F2V1B

Page 4: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Split Sky Air • Outdoor Units 4

• Outdoor Units • R-410A • RXS-F2V1B

TABLE OF CONTENTSRXS-F2V1B

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Nominal Capacity and Nominal Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

3 Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Cooling capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15Cooling/Heating capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

5 Dimensional drawing & centre of gravity . . . . . . . . . . . . . . . . . . . . . . . 27Dimensional drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27Centre of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

6 Piping diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

7 Wiring diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33Wiring diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8 Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35Sound pressure spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

9 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Page 5: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

11

• Split Sky Air • Outdoor Units5

1 Features

Outdoor Uni Split Sky RXS-F2V1B R-410A

Page 6: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

12

• Split Sky Air • Outdoor Units 6

• Outdoor Units • R-410A • RXS-F2V1B

2 Specifications

2-1 NOMINAL CAPACITY AND NOMINAL INPUT RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

For combination indoor units + outdoor units

Indoor Units FVXS25FV1B FVXS35FV1B FTXS50FV1B FTXS60FV1B FTXS71FV1B

Cooling capacity

Minimum kW 1.3 1.4 1.7 1.7 2.3Standard kW 2.5 3.5 5.0 6.0 7.1Maximum kW 3.0 3.8 6.0 6.7 8.5

Heating capacity

Minimum kW 1.3 1.4 1.7 1.7 2.3Standard kW 3.4 4.5 5.8 7.0 8.2Maximum kW 4.5 5.0 7.7 8.0 10.2

Nominal input Cooling Minimum kW 0.30 0.30 0.44 0.44 0.57Standard kW 0.57 1.02 1.55 1.99 2.35Maximum kW 0.92 1.25 2.08 2.40 3.20

Heating Minimum kW 0.29 0.31 0.40 0.40 0.52Standard kW 0.79 1.22 1.60 2.04 2.55Maximum kW 1.39 1.88 2.53 2.81 3.82

For combination indoor units + outdoor units

EER Nominal 4.39 3.43 3.23 3.02 3.02COP Nominal 4.30 3.69 3.63 3.43 3.22Energy Labeling Directive

Cooling A A A B BHeating A A A B C

Annual energy consumption kWh 285 510 775 995 1175Indoor Units FCQ35C7VEB FVXS50FV1B FDXS60CVMB

Cooling capacity

Minimum kW 1.4 1.4 1.7Standard kW 3.4 5.0 6.0Maximum kW 3.7 5.6 6.5

Heating capacity

Minimum kW 1.4 1.4 1.7Standard kW 4.2 5.8 7.0Maximum kW 5.0 8.1 8.0

Nominal input Cooling Minimum kW 0.50 0.44Standard kW 0.95 1.55 2.13Maximum kW 2.00 2.49

Heating Minimum kW 0.50 0.40Standard kW 1.23 1.60 2.32Maximum kW 2.60 3.18

For combination indoor units + outdoor units

EER Nominal 3.58 3.23 2.82COP Nominal 3.41 3.63 3.02Energy Labeling Directive

Cooling A A CHeating B A D

Annual energy consumption kWh 475 775 1065Indoor Units FDXS50CVMB FBQ60B8V1

Cooling capacity

Minimum kW 1.7Standard kW 5.0 5.7Maximum kW 5.3

Heating capacity

Minimum kW 1.7Standard kW 5.8 7.0Maximum kW 6.0

Nominal input Cooling Minimum kW 0.44Standard kW 1.65 2.19Maximum kW 1.93

Heating Minimum kW 0.40Standard kW 1.92 2.50Maximum kW 2.04

Page 7: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

12

• Split Sky Air • Outdoor Units7

2 Specifications

For combination indoor units + outdoor units

EER Nominal 3.03 2.60COP Nominal 3.02 2.80Energy Labeling Directive

Cooling B EHeating D E

Annual energy consumption kWh 825 1095Indoor Units FLXS50BAVMB FCQ60C7VEB

Cooling capacity

Minimum kW 1.7 0.9Standard kW 4.9 5.7Maximum kW 5.3 6.0

Heating capacity

Minimum kW 1.7 0.9Standard kW 6.1 7.0Maximum kW 7.5 8.0

Nominal input Cooling Minimum kW 0.44Standard kW 1.72 1.64Maximum kW 1.95

Heating Minimum kW 0.40Standard kW 1.82 1.99Maximum kW 3.54

For combination indoor units + outdoor units

EER Nominal 2.85 3.48COP Nominal 3.35 3.52Energy Labeling Directive

Cooling C AHeating C B

Annual energy consumption kWh 860 820Indoor Units FTXS50D2V1W FFQ60B8V1B

Cooling capacity

Minimum kW 1.7Standard kW 5.0 5.8Maximum kW 5.2

Heating capacity

Minimum kW 1.7Standard kW 5.8 7.0Maximum kW 6.0

Nominal input Cooling Minimum kW 0.44Standard kW 1.65 2.07Maximum kW 1.82

Heating Minimum kW 0.40Standard kW 2.06 2.49Maximum kW 2.19

For combination indoor units + outdoor units

EER Nominal 3.03 2.80COP Nominal 2.82 2.81Energy Labeling Directive

Cooling B DHeating D D

Annual energy consumption kWh 825 1035Indoor Units FTXS50D2V1L FHQ60BVV1B

Cooling capacity

Minimum kW 1.7 1.7Standard kW 5.0 5.7Maximum kW 5.2 6.0

Heating capacity

Minimum kW 1.7 1.7Standard kW 5.8 7.2Maximum kW 6.0 8.0

Nominal input Cooling Minimum kW 0.44 0.44Standard kW 1.65 2.15Maximum kW 1.82 2.23

Heating Minimum kW 0.40 0.40Standard kW 2.06 2.49Maximum kW 2.19 2.75

2-1 NOMINAL CAPACITY AND NOMINAL INPUT RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Page 8: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

12

• Split Sky Air • Outdoor Units 8

• Outdoor Units • R-410A • RXS-F2V1B

2 Specifications

For combination indoor units + outdoor units

EER Nominal 3.03 2.65COP Nominal 2.82 2.89Energy Labeling Directive

Cooling B DHeating D D

Annual energy consumption kWh 825 1075Indoor Units FCQ50C7VEB

Cooling capacity

Minimum kW 0.9Standard kW 5.0Maximum kW 5.6

Heating capacity

Minimum kW 0.9Standard kW 6.0Maximum kW 7.0

Nominal input Cooling Standard kW 1.41Heating Standard kW 1.62

For combination indoor units + outdoor units

EER Nominal 3.55COP Nominal 3.70Energy Labeling Directive

Cooling AHeating A

Annual energy consumption kWh 705Indoor Units FBQ50B8V1

Cooling capacity

Standard kW 5.0

Heating capacity

Standard kW 6.0

Nominal input Cooling Standard kW 1.92Heating Standard kW 1.87

For combination indoor units + outdoor units

EER Nominal 2.60COP Nominal 3.21Energy Labeling Directive

Cooling EHeating C

Annual energy consumption kWh 960Indoor Units FFQ50B8VMB

Cooling capacity

Standard kW 4.70

Heating capacity

Standard kW 5.50

Nominal input Cooling Standard kW 1.80Heating Standard kW 1.96

For combination indoor units + outdoor units

EER Nominal 2.61COP Nominal 2.81Energy Labeling Directive

Cooling DHeating D

Annual energy consumption kWh 900Indoor Units FHQ50BVV1B

Cooling capacity

Minimum kW 1.7Standard kW 5.0Maximum kW 5.6

Heating capacity

Minimum kW 0.9Standard kW 1.7Maximum kW 7.0

2-1 NOMINAL CAPACITY AND NOMINAL INPUT RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Page 9: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

12

• Split Sky Air • Outdoor Units9

2 Specifications

Nominal input Cooling Minimum kW 0.44Standard kW 1.83Maximum kW 2.02

Heating Minimum kW 0.40Standard kW 2.05Maximum kW 2.45

For combination indoor units + outdoor units

EER Nominal 2.73COP Nominal 2.93Energy Labeling Directive

Cooling DHeating D

Annual energy consumption kWh 915

2-2 TECHNICAL SPECIFICATIONS RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Casing Colour Ivory WhiteDimensions Unit Height mm 550 550 735 735 770

Width mm 765 765 825 825 900Depth mm 285 285 300 300 320

Packing Height mm 617 617 797 797 900Width mm 882 882 960 960 925Depth mm 363 363 390 390 390

Weight Unit kg 34 34 48 48 71Packed Unit kg 40 40 53 53 78

Heat Exchanger

Dimensions Length mm 805 805 845 845 859Nr of Rows 2 2 2 2 2Fin Pitch mm 1.4 1.4 1.8 1.8 1.4Nr of Stages 24 24 32 32 34

Tube type Hi-Xa(7) Hi-Xa(7) Hi-Xa(8) Hi-Xa(8) Hi-Xa(7)Fin Type Waffle fin

Treatment Anti-corrosion treatment (PE)Fan Type Propeller

Quantity 1 1 1 1 1Air Flow Rate (nominal at 230V)

Cooling m³/min 33.5 33.5 48.9 50.9 54.5Heating m³/min 30.2 30.2 45.0 46.3 52.5

Motor Quantity 1 1 1 1 1Model D23B-28 D23B-28 KFD-380-50-8A KFD-380-50-8A KFD-280-66-8A

Motor Speed (nominal)

Cooling rpm 860(H) - 620(L) 860(H) - 620(L) 780 860Heating rpm 860(H) - 810(L) 860(H) - 810(L) 720 830

Fan Motor Output W 23 23 53 53 66Compressor Quantity 1 1 1 1 1

Motor Model 1YC23NXD#C 1YC23NXD#C 2YC36BXD#C 2YC36BXD#C 2YC63BXD#DType Hermetically sealed swing compressorMotor Output

W 600 600 1100 1100 1920

Operation Range

Cooling Min °CDB -10 -10 -10 -10 -10Max °CDB 46 +46 46 46 46

Heating Min °CWB -15 -15 -15 -15 -15Max °CWB 20 +20 18 18 18

Sound Level (nominal)

Cooling Sound Power

dBA 61 62 61 63 66

Sound Pressure

dBA 46(H) - 43(L) 47(H) - 44(L) 47(H)/44(L) 49 52

Heating Sound Pressure

dBA 47(H) - 44(L) 48(H) - 45(L) 48(H)/45(L) 49 52

Sound Level (Night quiet)

Sound Pressure dBA 46 49

Refrigerant Type R-410ACharge kg 1.0 1.0 1.5 1.5 2.3

2-1 NOMINAL CAPACITY AND NOMINAL INPUT RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Page 10: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

12

• Split Sky Air • Outdoor Units 10

• Outdoor Units • R-410A • RXS-F2V1B

2 Specifications

Refrigerant Oil Type FVC50KCharged Volume l 0.375 0.375 0.65 0.65 0.75

Piping connections

Liquid (OD) Quantity 1 1 1Diameter (OD)

mm 6.35 6.35 6.35 6.35 6.35

Gas Quantity 1 1 1Diameter (OD)

mm 9.5 9.5 12.7 12.7 15.9

Drain Quantity 1 1 1Diameter (OD)

mm 20 20 20 18 18

Piping Length Maximum m 20 20 30 30 30Chargeless

m 10 10 10 10

Additional Refrigerant Charge

kg/m 0.02/>10m 0.02/>10m 0.02/>10 0.02/>10m 0.02/>10m

Installation height difference

Maximum m 15 15 20 20 20

Heat Insulation Both liquid and gas pipesStandard Accessories

Item Installation manual Installation manual Installation manual Drain plug Installation manualQuantity 1 1 1 1 1Item Installation manualQuantity 1

Notes Nominal cooling capacities are based

on : indoor temperature :

270CDB, 190CWB, outdoor temperature : 350CDB, equivalent refrigerant piping :

7.5m, level difference : 0m.

Nominal cooling capacities are based

on : indoor temperature :

270CDB, 190CWB, outdoor temperature : 350CDB, equivalent

refrigerant piping : 7.5m, level difference

: 0m.

Nominal cooling capacities are based

on : indoor temperature :

270CDB, 190CWB, outdoor temperature : 350CDB, equivalent

refrigerant piping : 7.5m, level difference

: 0m.

Nominal cooling capacities are based

on : indoor temperature :

270CDB, 190CWB, outdoor temperature : 350CDB, equivalent refrigerant piping :

5m, level difference : 0m.

Nominal cooling capacities are based

on : indoor temperature :

270CDB, 190CWB, outdoor temperature : 350CDB, equivalent

refrigerant piping : 7.5m, level difference

: 0m.Nominal heating

capacities are based on : indoor

temperature : 200CDB, outdoor

temperature : 70CDB, 60CWB

2-3 ELECTRICAL SPECIFICATIONS RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Power Supply Name V1Phase 1 1 1 1 1Frequency Hz 50 50 50 50 50Voltage V 220-240/220-230 220-240/220-230 220-240 220-240/220-230 220-240/220-230

Current Nominal running current (RLA)

Cooling (A)

A 3.2 4.6 6.64 8.62 10.2

Heating (A)

A 4.2 5.5 8.80 10.93

Starting current (cooling/heating)

A 4.5 5.9 7.3 9.4 11.7

Maximum Running Current A 4.4 5.8 7.02 9.19 11.42Wiring connections

For Power Supply

Quantity 3 3 3 3 3

For connection with indoor

Quantity 4 4 4 4 4Remark (including earth wiring)

2-2 TECHNICAL SPECIFICATIONS RXS25F2V1B RXS35F2V1B RXS50F2V1B RXS60F2V1B RXS71FV1B

Page 11: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

13

• Split Sky Air • Outdoor Units11

3 Electrical data

Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA

FVXS25FV1B RXS25F2V1B50 - 22050 - 23050 - 240

Max. 50Hz 264VMin. 50Hz 198V 9.75 10 52

3.023 0.16 48 0.052.8

2.7

3D055010B

SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.

Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA

FVXS35FV1B RXS35F2V1B50 - 22050 - 23050 - 240

Max. 50Hz 264VMin. 50Hz 198V 9.75 10.0 80

4.423 0.16 48 0.054.2

4.0

3D056495

SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.

Page 12: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

13

• Split Sky Air • Outdoor Units 12

• Outdoor Units • R-410A • RXS-F2V1B

3 Electrical data

Representative unit combination Power supply Comp. OFM IFMIndoor unit Outdoor unit Hz-volts Voltage range MCA MFA RHz RLA W FLA W FLA

FTXS50FV1B RXS50F2V1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 19.75 20.0 67

6.753 0.27 43 0.1650 - 230 6.4

50 - 240 6.1

FTXS60FV1B RXS60F2V1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 19.75 20.0 84

8.753 0.32 43 0.1650 - 230 8.3

50 - 240 7.9

FTXS71FV1B RXS71FV1B50 - 220

Max. 50Hz 264VMin. 50Hz 198V 19.75 20.0 57

10.366 0.40 43 0.1950 - 230 9.9

50 - 240 9.4

3D056032A

SYMBOLSMCA : Min. Circuit Amps (A)MFA : Max. Fuse Amps (A)RHz : Rated operating frequency (Hz)RLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load Amps (A)W : Rated motor output (W)

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB

2. Maximum allowable voltage unbalance between phases is 2%3. Select wire size based on the larger value of MCA.4. Instead of fuse, use circuit breaker.5. For more details concerning conditional connections, see

http://extranet.daikineurope.com, select ’’E-Data Books’’. Finally, click onthe document title of your choice.

Page 13: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units13

4 Capacity tables4 - 1 Cooling capacity tablesFBQ50B8V1+RXS50F2V1B

Cooling 220-240V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

3TW25112-1B

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 SHC is based on each EWB and EDBSHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR [m3/min.] x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4 Direct interpolation is permissible.Do not extrapolate.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Model FBQ

35 AFR 11.5BF 0.15

50 AFR 14BF 0.15

60 AFR 19BF 0.11

Page 14: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 14

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 1 Cooling capacity tablesFBQ60B8V1+RXS60F2V1B

Cooling 220-240V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

3TW25112-1B

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 SHC is based on each EWB and EDBSHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR [m3/min.] x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4 Direct interpolation is permissible.Do not extrapolate.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Model FBQ

35 AFR 11.5BF 0.15

50 AFR 14BF 0.15

60 AFR 19BF 0.11

Page 15: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units15

4 Capacity tables4 - 2 Heating capacity tablesFBQ50B8V1+RXS50F2V1B

Heating 220-240V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB -15 -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI TC PI

3TW25112-2B

SYMBOLSAFR: Air flow rate (m3/min)EWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total capacity (kW)PI: Power input (Comp. + indoor + outdoor fan motor). (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 Direct interpolation is permissible.Do not extrapolate.

4 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

5 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Model FBQ35 11.550 1460 19

Page 16: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 16

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 2 Heating capacity tablesFBQ60B8V1+RXS60F2V1B

Heating 220-240V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB -15 -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI TC PI

3TW25112-2B

SYMBOLSAFR: Air flow rate (m3/min)EWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total capacity (kW)PI: Power input (Comp. + indoor + outdoor fan motor). (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 Direct interpolation is permissible.Do not extrapolate.

4 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

5 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Model FBQ35 11.550 1460 19

Page 17: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units17

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFVXS25FV1B+RXS25F2V1B

Cooling 50Hz 220-240VAFR 8.2BF 0.10

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 8.8

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D056491

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 18: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 18

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFVXS35FV1B+RXS35F2V1B

Cooling 50Hz 220-240VAFR 8.5BF 0.11

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 9.4

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D056492

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 19: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units19

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFCQ35C7VEB+RXS35F2V1B

Cooling 50Hz 220-240VAFR 10.5BF 0.28

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 12.5

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D057246

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 20: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 20

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFTXS50FV1B+RXS50F2V1B

Cooling 50Hz 220-240VAFR 14.7BF 0.28

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 16.1

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D051923A

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 TC, PI and SHC must be calculated by interpolation using the figuresin the above tables. (Figures out of the tables should not be used forcalculation.)

4 About SHC which are not mentioned on the table, please calculatethem with around values in direct proportion.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Page 21: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units21

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFVXS50FV1B+RXS50F2V1B

Cooling 50Hz 220-240VAFR 10.7BF 0.13

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 11.8

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D056339

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 22: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 22

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFFQ50B8V1B+RXS50F2V1B

Cooling 50Hz 230VAFR 12.0BF 0.16

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 230V AFR 12.0

Indoor Outdoor temperature (°CWB)EDB -15 -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI TC PI

3D041023

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 TC, PI and SHC must be calculated by interpolation using the figuresin the above tables. (Figures out of the tables should not be used forcalculation.)

4 SHC is based on each EWB and EDBSHC* = SHC correction for other dry bulb=0.02*AFR(m3/min.)*(1-BF)*(DB*-EDB)Add SHC* to SHC.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Page 23: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units23

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFCQ50C7VEB+RXS50F2V1B

Cooling 50Hz 220-240VAFR 12.5BF 0.21

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 12.5

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D057248

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 24: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 24

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFTXS60FV1B+RXS60F2V1B

Cooling 50Hz 220-240VAFR 16.2BF 0.29

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 17.4

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D051924A

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 TC, PI and SHC must be calculated by interpolation using the figuresin the above tables. (Figures out of the tables should not be used forcalculation.)

4 About SHC which are not mentioned on the table, please calculatethem with around values in direct proportion.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Page 25: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units25

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFFQ60B8V1B+RXS60F2V1B

Cooling 50Hz 230VAFR 15.0BF 0.11

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 230V AFR 15.0

Indoor Outdoor temperature (°CWB)EDB -15 -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI TC PI

3D041028

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1 Ratings shown are net capacities which include a deduction for

indoor fan motor heat

2 shows nominal (rated) capacities and power input.

3 TC, PI and SHC must be calculated by interpolation using the figuresin the above tables. (Figures out of the tables should not be used forcalculation.)

4 SHC is based on each EWB and EDBSHC* = SHC correction for other dry bulb=0.02*AFR(m3/min.)*(1-BF)*(DB*-EDB)Add SHC* to SHC.

5 Capacities are based on following conditions:Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6 Air flow rate (AFR) and Bypass factor (BF) are taburated above.

Page 26: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

14

• Split Sky Air • Outdoor Units 26

• Outdoor Units • R-410A • RXS-F2V1B

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFCQ60C7VEB+RXS60F2V1B

Cooling 50Hz 220-240VAFR 13.5BF 0.21

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 13.5

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D057250

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 27: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

14

• Split Sky Air • Outdoor Units27

4 Capacity tables4 - 3 Cooling/Heating capacity tablesFTXS71FV1B+RXS71FV1B

Cooling 50Hz 220-240VAFR 17.4BF 0.30

Indoor Outdoor temperature (°CDB)EWB EDB 20 25 30 32 35 40(°C) (°C) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

Heating 50Hz 220-240V AFR 19.7

Indoor Outdoor temperature (°CWB)EDB -10 -5 0 6 10(°C) TC PI TC PI TC PI TC PI TC PI

3D056030

SYMBOLSAFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°C)EDB: Entering dry bulb temp. (°C)TC: Total capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

NOTES1. Capacities are based on the following conditions:

(1) Corresponding refrigerant piping length: 7.5 m(2) Level difference: 0 m

2. shows nominal (rated) capacities and power input.

Page 28: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

15

• Split Sky Air • Outdoor Units 28

• Outdoor Units • R-410A • RXS-F2V1B

5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing

3D055546

RXS25-35F2V1B unit (mm)

Minimum space for air passage Wall height on air outlet side =less than 1200

Drain outlet(I.D. J15.9 hose for connection)

Handle

Wiring inlet

Gas stop valve(J12.7 CuT)

Liquid stop valve(J6.4 CuT)

Service port

Outdoor air thermistor

Brand name label

4 x holes for anchor bolts(M8 or M10)

Manufacturer’slabel

In case of removingstop valve cover

3D051657D

RXS50-60F2V1B unit (mm)

Minimum space for air passage Wall height on air outlet side =less than 1200

Brand name labelTerminal strip withearth terminal

Outdoor air temperaturethermistorName plate

Drain outlet(I.D. J 15.9 hose for connection)

Wiring inlet

Liquid stop valve(J6.4 CuT)

4 x holes for anchor bolts (M8or M10)

Service port Gas stop valve(J12.7 CuT)

In case of removing stopvalve cover

Page 29: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

15

• Split Sky Air • Outdoor Units29

5 Dimensional drawing & centre of gravity5 - 1 Dimensional drawing

3D054589A

RXS71FV1B unit (mm)

Minimum space for air passage Wall height on air outlet side =less than 1200

Gas stop valve

Liquid stop valve

Outdoor airthermistorName plate

4-cuts for anchor bolts

Terminal strip withearth terminal

Interconnecting pipingand wiring inlet

I.D. J25 hose for connection

Drain outlet

(M12)

Gas pipe(J15.9 single union)

Liquid pipe(J6.4 single union)

Page 30: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

15

• Split Sky Air • Outdoor Units 30

• Outdoor Units • R-410A • RXS-F2V1B

5 Dimensional drawing & centre of gravity5 - 2 Centre of gravity

4D056351

RXS25-35F2V1B

4D051638C

RXS50-60F2V1B

The position of foundation bolt

Page 31: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

15

• Split Sky Air • Outdoor Units31

5 Dimensional drawing & centre of gravity5 - 2 Centre of gravity

4D053630B

RXS71FV1B

Position of anchor bolt

Page 32: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

16

• Split Sky Air • Outdoor Units 32

• Outdoor Units • R-410A • RXS-F2V1B

6 Piping diagram

3D047316E

RXS25-35F2V1B

Outdoor temperature thermistorHeat exchanger

Propeller fan

Liquid stopvalve

Field piping

Field piping

Gas stopvalve

Compressor

Refrigerant flow

Cooling

Heating

Discharge pipethermistor

Heat exchangerthermistor

Muffler withfilter

Motor operatedvalve

Muffler withfilter

Outdoor unit

Muffler

Muffler

Four way valveon: heating

Accumulator

Muffler withfilter

3D051637D

RXS50-60F2V1B

Outdoor temperature thermistorHeat exchanger

Propeller fan

Capillary tube 1

Liquid stopvalve

Field piping

Field piping

Gas stop valve withservice portCompressor

Capillary tube 3

Refrigerant flow

Cooling

Heating

Discharge pipethermistor

Heat exchangerthermistor

Capillary tube 2

Capillary tube 4

Muffler withfilter

Motor operatedvalve

Outdoor unit

Muffler Muffler

Four way valve on :heating

Muffler

Filter

Receiver

Page 33: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

16

• Split Sky Air • Outdoor Units33

6 Piping diagram

3D054593A

RXS71FV1B

Outdoor temperature thermistorHeat exchanger

Propeller fan

Field piping

Field piping

Gas linestop valve

Compressor

Refrigerant flowCooling

Heating

Heat exchanger(condenser) thermistor

Motoroperated

valve

Outdoor unit

Muffler

Accumulator

Four way valveon : heating

Accumulator

DC fan motor

Header

Capillary tube

Distributor Filter Filter

Liquid (6.4 CuT)

Gas (15.9 CuT)

Receiver

Liqu

idlin

est

opva

lve

Discharge pipethermistor

Page 34: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

17

• Split Sky Air • Outdoor Units 34

• Outdoor Units • R-410A • RXS-F2V1B

7 Wiring diagram7 - 1 Wiring diagram

3D046707H

RXS25-35F2V1B

R : Protective earthC74,C75C94,C95,C100 : CapacitorDB1,DB2 : Diode bridgeFU1,FU2,FU3 : FuseIC11 : TriacIPM1 : Intelligent power moduleL : LiveL1 : CoilL1R : ReactorM1C : Compressor motorM1F : Fan motorMRCW,MRM10,MRM20 : Magnetic relay

N : NeutralPCB1,PCB2 : Printed circuit boardQ1L : Overload protectorR1T,R2T,R3T,R12T : ThermistorS10,S11,S20S30,S40,S70S80,S90,S91HC3,HC4,HL3,HN3: Connector

gField wiringIndoor

Outdoor

(outdoor)(Condenser)

(discharge)

SA1 : Surge arresterV1,V2,V3 : VaristorX1M : Terminal stripY1E : Electronic expansion valve coilY1R : Reversing solenoide valve coilZ1C,Z2C : Ferrite core

In case of coolingonly type

In case of heatpump type

NOTE1. Refer to the nameplate for the power requirements.

3D056095

RXS50F2V1B

R : Protective earthZ1C∼Z4C : Ferrite coreX1M,X2M : Terminal stripY1E : Electronic expansion valve coilV2,V3,V5,V6,V11 : VaristorSA2 : Surge arresterF1U,F2U,FU3 : FuseAC1,AC2U,V,W,X11AE1,E2HR1,HR2 : ConnectorMRM10, MRM20,MRC/W : Magnetic relay

R1T∼R3T : ThermistorS2∼S102 : ConnectorLEDA : Pilot lampL : LiveN : NeutralS1W : Forced operation on/off switch (SW1)S4W : Local setting SW (SW4)

gField wiring

Indoor

Power supply

Outdoor

(outdoor)(Condenser)

(discharge)

M1C : Compressor motorsM1F : Fan motorL1R : ReactorQ1L : Overload protectorPM1 : Power modulePCB1, 2 : Printed circuit boardSheet metal : Terminal strip fixed plate

To indoor unit

Sheet metal

Page 35: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

17

• Split Sky Air • Outdoor Units35

7 Wiring diagram7 - 1 Wiring diagram

3D050706F

RXS60F2V1B

R : Protective earthZ1C∼Z4C : Ferrite coreX1M,X2M : Terminal stripY1E : Electronic expansion valve coilV2,V3,V5,V6,V11 : VaristorSA2 : Surge arresterF1U,F2U,FU3 : FuseAC1,AC2U,V,W,X11AE1,E2HR1,HR2 : ConnectorMRM10, MRM20,MRC/W : Magnetic relay

R1T∼R3T : ThermistorS2∼S102 : ConnectorLEDA : Pilot lampL : LiveN : NeutralS1W : Forced operation on/off switch (SW1)S4W : Local setting SW (SW4)

gField wiring

Indoor

Power supply

Outdoor

(outdoor)(Condenser)

(discharge)

M1C : Compressor motorsM1F : Fan motorL1R : ReactorQ1L : Overload protectorPM1 : Power modulePCB1, 2 : Printed circuit boardSheet metal : Terminal strip fixed plate

To indoor unit

Sheet metal

3D053931B

RXS71FV1B

R : Protective earthZ1C∼Z4C : Ferrite coreX1M,X2M : Terminal stripY1E : Electronic expansion valve coilV2,V3,V5,V6,V11 : VaristorSA2 : Surge arresterF1U,F2U,FU3 : FuseAC1,AC2U,V,W,X11AE1,E2HR1,HR2 : ConnectorMRM10, MRM20,MRC/W : Magnetic relay

R1T∼R3T : ThermistorS2∼S102 : ConnectorLEDA : Pilot lampL : LiveN : NeutralS1W : Forced operation on/off switch (SW1)S4W : Local setting SW (SW4)

gField wiring

Indoor

Power supply

Outdoor

(outdoor)(Condenser)

(discharge)

M1C : Compressor motorsM1F : Fan motorL1R : ReactorQ1L : Overload protectorPM1 : Power modulePCB1, 2 : Printed circuit boardSheet metal : Terminal strip fixed plate

To indoor unit

Sheet metal

Page 36: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

18

• Split Sky Air • Outdoor Units 36

• Outdoor Units • R-410A • RXS-F2V1B

8 Sound data8 - 1 Sound pressure spectrum

4D052971C

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS25F2V1B (Cooling)

approximatethreshold hearing for

continuous noise

NOTES1 Measure in anechoic room2 Operation noise differs with operation and

ambient conditions.3 The operation noise measuring method is in

accordance with JISC9612

Legend

50Hz, 220-240V

Location of microphone

3D052971C

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS25F2V1B (Heating)

approximatethreshold hearing for

continuous noise

NOTES1 Measure in anechoic room2 Operation noise differs with operation and

ambient conditions.3 The operation noise measuring method is in

accordance with JISC9612

Legend

50Hz, 220-240V

Location of microphone

4D052972C

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS35F2V1B (Cooling)

approximatethreshold hearing for

continuous noise

NOTES1 Measure in anechoic room2 Operation noise differs with operation and

ambient conditions.3 The operation noise measuring method is in

accordance with JISC9612

Legend

50Hz, 220-240V

Location of microphone

3D052972C

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS35F2V1B (Heating)

approximatethreshold hearing for

continuous noise

NOTES1 Measure in anechoic room2 Operation noise differs with operation and

ambient conditions.3 The operation noise measuring method is in

accordance with JISC9612

Legend

50Hz, 220-240V

Location of microphone

Page 37: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

18

• Split Sky Air • Outdoor Units37

8 Sound data8 - 1 Sound pressure spectrum

4D051717B

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS50F2V1B (Cooling)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an echoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

4D051717B

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS50F2V1B (Heating)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an echoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

4D051716A

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS60F2V1B (Cooling)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an echoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

3D051716A

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS60F2V1B (Heating)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an echoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

Page 38: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

3

18

• Split Sky Air • Outdoor Units 38

• Outdoor Units • R-410A • RXS-F2V1B

8 Sound data8 - 1 Sound pressure spectrum

4D055789

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS71FV1B (Cooling)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an anechoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

3D055789

Oct

ave

band

soun

dpr

essu

rele

vel

Octave band center frequency (Hz)

RXS71FV1B (Heating)

approximatethreshold hearing for

continuous noise

NOTES1 Measured in an anechoic room2 Operation noise differs with operation and ambient

conditions.

Legend

50Hz, 220-240V

Page 39: RXS-F2V1B 07 EN - daikintech.co.uk2)V... · technical data Split Sky Air RXS-F2V1B air conditioning systems

• Outdoor Units • R-410A • RXS-F2V1B

19

• Split Sky Air • Outdoor Units39

9 Operation range

RXS25-35F2V1B

3D039536J

Out

door

tem

p.(°

CDB)

Pull-

dow

npe

riod

Indoor temp. (°CWB)

Notes:The graphs are based on the following conditions:+ Equivalent piping length 7.5 m+ Level difference 0 m+ Air flow rate high

Cooling Heating

Indoor temp. (°CDB)

Out

door

tem

p.(°

CWB)

Cont

inuo

usop

erat

ion

Cont

inuo

usop

erat

ion

(-15 °CDB)

RXS50-71F2V1B

3D028318K

Out

door

tem

p.(°

CDB)

Pull-

dow

npe

riod

Indoor temp. (°CWB)

Notes:The graphs are based on the following conditions:+ Equivalent piping length 7.5 m+ Level difference 0 m+ Air flow rate high

Cooling Heating

Indoor temp. (°CDB)

Out

door

tem

p.(°

CWB)

Cont

inuo

usop

erat

ion

Cont

inuo

usop

erat

ion

(-15 °CDB)