© ABB Group January 4, 2015| Slide 1 Improving Power System Stability Through Integrated Power System Stabilizers Rudolf Wieser, Matthias Baechle, Valerijs Knazkins – ATPE

Transcript of Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE...

Page 1: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 1

Improving Power System Stability Through Integrated Power System Stabilizers

Rudolf Wieser, Matthias Baechle, Valerijs Knazkins – ATPE

Page 2: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 2

OUTLINE

Controlled Generator on Grid

� The main functions of an Automatic Voltage Regulator (AVR)

� The main functions of a

Power System Stabilizer (PSS)

How to test an AVR system

� Introduction to Real time Simulator

Grid Code compliance testing

� UNITROL built in compliance test functions

Page 3: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 3

The main functions of an AVRAutomatic Voltage Regulator

State-of-the-art excitation systems are equipped with fast

acting voltage regulators:

� Advantages:

� Fast acting voltage control and reactive power

support

� Providing synchronizing torque component

� Disadvantage:

� Introducing negative damping torque component

� Solution to the reduced damping torque problem

� Power System Stabilizers

Page 4: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 4

Model of a single Generator connected to Grid

Turbine and Generator Mechanics

� Turbine driving torque Tm

� Generator braking torque Te

� Mechanical rotational speed ω

GeneratorTurbine

ω

Tm

Te

Page 5: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 5

Model of a single Generator connected to Grid

Turbine and Generator Connection to Grid

� Turbine + Generator

� Generator breaker

� Step-up transformer

� Transmission line

� Infinite bus (constant voltage)

Page 6: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 6

Model of a single Generator connected to Grid

Turbine and Generator connected to Grid

� A single generator connected to a large grid can be

represented by the Phillips-Heffron model

(assuming constant field voltage and mechanical torque)

Page 7: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 7

Model of a single Generator connected to Grid

Linearized Model at certain Operating Point

� A single generator connected to a large grid can be

represented by the Phillips-Heffron model

(assuming constant field voltage and mechanical torque)

Page 8: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 8

Model of a single Generator connected to Grid

Torque Disturbance Impact

� Harmonic Phasor Representation

� Torque equilibrium disturbance

� Electric torque produces natural positive damping

Page 9: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 9

Model of a single Generator connected to Grid

Fast Voltage Control Impact

� Harmonic Phasor Representation Generator plus AVR

� Electric torque form AVR function produces negative damping torque

Page 10: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 10

Model of a single Generator connected to Grid

Power System Stabilizer Function

� Power System Stabilizer (PSS)

� Band limited damping torque contribution

� Speed estimator from electrical voltage and current signals

Page 11: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 11

OUTLINE

Controlled Generator on Grid

� The main functions of an Automatic Voltage Regulator (AVR)

� The main functions of a

Power System Stabilizer (PSS)

How to test an AVR system

� Introduction to Real Time Simulator

Grid Code compliance testing

� UNITROL built in compliance test functions

Page 12: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 12

Synchronous Machine Transient Simulator Turbine, Generator, Transformer, Line to infinite Bus

� Typical turbine - generator arrangement in a power plant

� Automatic Voltage Regulator (AVR)

Page 13: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 13

Synchronous Machine Transient Simulator Turbine, Generator, Transformer, Line to infinite Grid

SMTS-RT

� Real Time Simulation of

� Turbine and governor (simplified)

� Generator

� Breaker and step-up transformer

� Grid representation with infinite Bus Voltage

Page 14: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 14

Synchronous Machine Transient Simulator Turbine, Generator, Transformer, Line to infinite Grid

SMTS-RT

� AVR hardware

in the loop

Real Time Simulation

Page 15: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 15

Synchronous Machine Transient Simulator Turbine, Generator, Transformer, Line to infinite Grid

SMTS-RT 6000

UNITROL 6000

Page 16: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 16

Synchronous Machine Transient Simulator SMTS-RT 6000; User Interface

Page 17: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 17

OUTLINE

Controlled Generator on Grid

� The main functions of an Automatic Voltage Regulator (AVR)

� The main functions of a

Power System Stabilizer (PSS)

How to test an AVR system

� Introduction to Real Time Simulator

Grid Code compliance testing

� UNITROL built in compliance test functions

Page 18: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 18

AVR Grid Code ComplianceGrid Code Example

Excerpt from of a local grid code:

“Overall Excitation System Control Characteristic

�The frequency domain tuning of the Power System

Stabilizer shall also be demonstrated by injecting a

0.2Hz-2Hz band limited random noise signal into the Automatic Voltage Regulator reference� while the

Generating Unit is operating at a typical load level...

�The damping contribution of the Power System Stabilizer shall improve the system-stability within the

frequency-band of interest (compared to the system

response without a stabilizer):

i.e., 0.2Hz - 2Hz”

Page 19: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 19

Grid Code Compliance Testing

Test scheme for

the measurement

of the

corresponding

transfer function

Page 20: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 20

Grid Code Compliance Testing

Time domain-

response of the

system without

the stabilizer,

while injecting

noise signals:

ExpertDays09

Page 21: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 21

Grid Code Compliance Testing

Time domain-

response of the

system with the

stabilizer, while

injecting noise

signals:

8%

ExpertDays09

Page 22: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 22

Grid Code Compliance Testing

Time domain-

response of the

system with the

stabilizer, while

injecting noise

signals:

ExpertDays09

Page 23: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 23

Grid Code Compliance Testing

Frequency domain

response of the

system with

(greenline) and

without (blue line)

the stabilizer

connected:

( )( )

( )

e

ref

P jF j

V j

ωω

ω

∆=∆

-20

-15

-10

-5

0

5

10

15

20

25

Magnitude [d

B]

Frequency [Hz]

10.2 5

Page 24: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 24

Grid Code Compliance Testing

Time domain

response of the

system with

(using different

gains) and

without (blue line)

the stabilizer

connected:

time [s]0 2 4 6 8

0.83

0.84

0.85

0.86

0.87P

e [p

.u.]

w /o PSS

w ith PSS, KS1=2

w ith PSS, KS1=3

w ith PSS, KS1=4

w ith PSS, KS1=10

Page 25: Rudolf Wieser, Matthias Baechle, Valerijs Knazkins –ATPE ...libvolume3.xyz/electrical/btech/semester8/powersystemoperationand... · © ABB Group January 4, 2015| Slide 1 ... SMTS-RT

© ABB Group January 4, 2015 | Slide 25