REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
ADDENDUM NO.: 2 DATE: March 27, 2013 PROJECT: Reynolds Market - Fox Run Retail Sidney, Montana ARCHITECT: CTA ARCHITECTS ENGINEERS 13 North 23rd Street (59101) P.O. Box 1439 Billings, MT 59103-1439 CTA PROJECT REF.: REYNOLDS_FOXRUN TO: ALL PLAN HOLDERS OF RECORD PAGES: 20 (If you did not receive correct # of pages, please notify us immediately) 14 - 8-1/2" x 11" 2 – 11" x 17" 4 - 30" x 42" Acknowledge receipt of this Addendum by inserting its number and date in the Proposal Form. Failure to do so may subject Bidder to disqualification. This Addendum forms a part of the Contract Documents. It modifies them as follows: GENERAL 1. INSTRUCTIONS TO BIDDERS - Modify Article 4, paragraph "c" as follows: Electronic bids (.pdf)
will be accepted so long as bids are received no later than the date and time specified in the Project Manual and as modified by addenda. Bids shall be e-mailed to [email protected]. Electronic bids shall include a facsimile of the bid bond written on AIA Document A310, Bid Bond. Bidders shall also include name of surety underwriter, contact name and phone number. Facsimiles of a certified check, cashier’s check or bank money order will not be acceptable for a bid submitted electronically. Bidders submitting electronic bids do so at their own risk. CTA, Inc. will not be responsible for technological anomalies in regard to electronic bidding.
2. BID FORM: Bid Form has been revised. SPECIFICATIONS 033030 – CAST-IN-PLACE CONCRETE SLABS 1. Refer to Part 1.5.E.: Add 3. "Concrete Polishing Association of America (CPAA) Section 03 3300
Concrete Recommendations with Polished Concrete". The CPAA standards for floor polishing shall be included as integral to these specifications. CPAA standards can be obtained at http://www.concretepolishingassociation.com/specifications.
2. Delete 2.4.B. "Air-entraining Admixture." 3. Refer to 2.6.B. Plasticizing admixtures shall be limited to maximum of 20 percent.
AD2 - 1
REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
033600 – SPECIAL CONCRETE FLOOR SYSTEMS 1. Refer to Part 1.3.D.: Add "Concrete Polishing Association of America (CPAA) Section 03 3543
Diamond Polishing Concrete Floors". The CPAA standards for floor polishing shall be included as integral to these Specifications. CPAA standards can be obtained at http://www.concretepolishingassociation.com/specifications.
2. Refer to Part 3.2.B.5. Paragraph shall be modified to read: Polish to required sheen level: Level 2 – Medium Gloss Appearance: a. Procedure: Not less than 5 step process with full refinement of each diamond pad up to 800 girt
resin bonded pad with on application densifier. b. Gloss reading: Not less than 55 according to ASTM E 430 before polish guard application.
3. Add Part 3.2.B.6: Subparagraph shall read: Polish to required sheen level: Class B- Fine Aggregate (Salt and Pepper). Remove not more than 1/16 inch of concrete surface by grinding and polishing resulting in majority of exposure displaying fine aggregate with no, or small amount of, medium aggregate at random locations.
042000 – UNIT MASONRY 1. Part 2.2.C.2. shall be changed to read: Density Classification: Light Weight. Note: CMU used on
grid line 17 of Retail Shop B shall have a 2 hr. UL rating per G102. 084113 – ALUMINUM –FRAMED ENTRANCES AND STOREFRONTS 1. Refer to Part 2.5.A.1.a.: Remove Thermal Construction. Storefront doors shall not be thermally
broken. 2. Refer to Part 2.10.A: High-Performance Organic Finish shall be three-coat (two coat + clear coat)
and not two-coat as specified. 211313 - FIRE SPRINKLER SYSTEM 1. Change subparagraph 3.1.A.9.a to, "Hydrants located on Third Ave NW. Information provided by
local Sidney Water Department." 2. Change subparagraph 3.1.A.9.c to "43 psi" 3. Change subparagraph 3.1.A.9.d to "1941 gpm" 4 Change subparagraph 3.1.A.9.e to "03/15/2013" 213213 - ELECTRIC DRIVE CENTRIFUGAL FIRE PUMPS 1. Add subparagraph 2.2.C.1.e "SPP Pumps Inc." 237413 - ROOFTOP AIR CONDITIONERS
1. Delete subparagraph 2.1 P.1. "Cold-Weather Kit: Electric heater maintains temperature in gas burner compartment."
DRAWINGS CIVIL (Great Basin Eng.) SHEET C1.1 1. Curbed area directly SW of Reynolds Grocery Store shall receive 4" topsoil, not 2" Gravel Cap as
noted. This area shall receive sod and irrigation system per Landscape documents. 2. Thickened sidewalks adjacent to Reynolds Grocery Store and Retail Shops B shall be installed by GC,
not by civil contractor. GC shall include these in Base Bids A and B respectively.
AD2 - 2
REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
SHEET C1.2 1. Thickened sidewalks adjacent to Retail Shops B shall be installed by GC, not by civil contractor. GC
shall include these in Base Bid B. 2. Thickened sidewalks adjacent to Retail C and D shall not be included in bid. These shall be provided
by others. 3. Truck Dock Ramp for Retail D shall not be included in this scope of work. Retail D dock ramp shall
be by others. SHEET C2.1 1. Building Pads: Civil contractor shall be responsible for over-excavation and placing engineered fill
under building pads for Reynolds Grocery Store and Retail Shops B per geotechnical report. Civil contractor shall bring engineered sub-base to 11 inches below finished slab elevation. GC shall be responsible for 6" base per geotechnical report.
SHEET C2.1 1. Building Pads: Civil contractor shall be responsible for over-excavation and placing engineered fill
under building pads for Retail Shops B, Retail C and Retail D per geotechnical report. Civil contractor shall bring engineered sub-base to 11 inches below finished slab elevation. GC shall be responsible for 6" base per geotechnical report.
LANDSCAPE
SHEET L401, L402, L403, L404 1. Change the irrigation legend call out for sleeves from "Schedule 80" to "Schedule 40 or SDR-11." SHEET L405 1. Detail 1 and Detail 2: Add note to each detail reading "One decoder per station/valve." 2. Detail 3: Change controller call out from "Model IC-3000 Dual 48M" to "Model IC-600-SS-
Dual48M." ARCHITECTURAL SHEET A203 1. Refer to "Exterior Paint Color Schedule". Note shall read: "Exterior Hollow Metal Doors and Frames
shall be painted same color as adjacent wall". Aluminum storefront doors and frames have factory finish as specified.
SHEET A501 (see attached A501-1) 1. Base Finishes: "CB" – Concrete Base added to legend. SHEET A502 (see attached A502-1) 1. Added RB in Rooms B102 and B103. 2. Added Additional Note #3 for FRP in Rooms B102 and B103. SHEET A601 1. Doors B101-1, B106-1, 500-1, 600-1, 700-1, 800-1, 900-1 and 1000-1 shall have Hinge note #2. 2. Doors B101-1 shall have Door and Frame Type "Q" 3. Doors B106-1, 500-1, 600-1, 700-1, 800-1, 900-1 and 1000-1 shall have Hinge note #2; Door and
Frame Type "Z". 4. Doors B105-3, B500-2, B600-2, B700-2, B800-2, B900-2 and B1000-2 shall have Frame Type "B". 5. Doors B102-1, B103-1, B104-1, B106-2, B107-1, B108-2 shall have Frame Type "A".
AD2 - 3
REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
6. Door 105-1 shall have Frame Type "C". 7. Doors B102-1, B103-1 and B104-1 shall have Hinge note #1. 8. Door hardware for Door 103-1 shall be the same as Door 102-1. 9. Door hardware for Door 104-1 shall be the same as Door 139-1. 10. Window Type "B" shall be hollow metal frame with ¼" tempered glass with sliding hardware track at
top and bottom of frame. SHEET A701 (see attached A701-1) 1. Changed mantel to 12" deep, lengthened mantel and added mantel bracket(s). 2. Added Burnished Block base. 3. Added Cultured Stone note. 4. Changed hearth depth. 5. Refer to Details 16 and 17. All millwork will be furnished and installed by others. Blocking for
millwork shall be by GC as shown on 18/A701. SHEET S002 1. Refer to Detail 1/S002. 18" min. zone of engineered fill shall be furnished by civil contractor as
shown on C2.1 and C2.2. GC shall be responsible for installing 6" base per geotechnical report. SHEET S201 1. Refer to Details 2/S201, 3/S201 and Civil Sheets C1.1, C1.2 and Detail 5/C4.1. GC shall be
responsible for installing all thickened sidewalks adjacent to Reynolds Grocery Store and Retail Shops B. GC shall include costs for sidewalks in Base Bids A and B respectively. Thickened sidewalks for Retail C and Retail D shall not be included in this scope of work.
FIRE PROTECTION SHEET FP100 (see attached FP100) 1. Change water supply information to reflect current test performed on 03/15/2013. No further testing
is required. 2. Change note 6 to "Flow hydrants" 3. Add note 13 "Static and residual pressure hydrant" SHEET FP101 (see attached FP101) 1. Change pump test header to 4 outlets. 2. Add FDC pipe routed to riser. 3. Change configuration of riser piping. 4. Change location of Fire Pump Controller. 5. Change denotation of thrust block to Note 4. 6. Change configuration and location of FDC. SHEET FP200 (see attached FP200 1. Delete note 13. 2. Add note 13 "Route FDC to riser room" 3. Change FDC location and routing. 4. Add OH2 hazard classification to storage adjacent to exterior seating. 5. Add note 6 to storage adjacent to exterior seating. 6. Add note 15 "sprinkler protection is required under soffits housing display coolers and racks"
AD2 - 4
REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
SHEET FP200 (see attached FP201) 1. Add section through exit/entry showing limited combustible concealed space. MECHANICAL
SHEET M001 1. Packaged RTU schedule - delete accessory item #7. ELECTRICAL SHEET E001 (see attached E001-E1) 1. Added "LV – Low Voltage" to Device & Power section lf Legend. 2. Modified Luminaire Schedule – A7 fixture should be Lithonia SP8 F 2 28 A12125 GEB10IS. 3. Modified Luminaire Schedule – Removed type A4 and E1 fixtures – not used. 4. Modified Luminaire Schedule – Changed ballast type for fixtures A5 and A6 from BSNP to
GEB10IS. Also added to remarks to include suspension system of fixtures. SHEET E601 1. Changed "no scale" to "scale 1/8" = 1’-0"" on plans 2/E601 and 4/E601. PRIOR APPROVALS Architectural Acceptable manufacturers for prior approvals: Specification 033030 - Cast-In-Place Concrete Slabs Insulation Solutions Viper VaporCheck II 15 Mil "Class A" vapor barrier Specification 074113 - Metal Roof Panels – Field Fabricated Sno-Gem Junior Polycarbonates - Clear UV Stabilized by Sno-Gem, Inc. with the condition that Sno-Gem, Inc. submit engineered shop drawings showing layout of snow guards on applicable roof structures. Final approval is at the sole discretion of CTA. CTA reserves the right of rejection with no additional cost to the owner. Specification 083613 – Sectional Doors Clopay (OH doors) and Liftmaster (Operators) Specification 096723 - Resinous Flooring Sherwin-Williams GP 3745 Series Fast Top S Urethane Slurry system by General Polymers Mechanical Acceptable manufacturers for prior approvals: Specification 233113 - Round Duct and Fittings Lewis and Lambert Specification 233300 - Back Draft Damper, Volume Damper, and Duct Access Door Nailor Industries Specification 233300 - Flexible Duct Work Flexmaster Hart & Cooley
AD2 - 5
REYNOLDS MARKET REYNOLDS_FOX RUN SIDNEY, MONTANA
AD2 - 6
Specification 233423 - HVAC Power Ventilators Aerovent (A Twin City Fan Co.) Captive Aire Specification 237433 - Rooftop MAU Absolute Aire Captive Aire Intake Hood Acme Engineering Cesco Products Electrical Lighting Control Panel – Approved Cooper Controls LK Series, Wattstopper LIA Series Low Voltage Occupancy Sensor – Cooper Controls OAC Series Power Pack – Cooper Controls – OC Series Low Voltage Switch – Cooper Controls GDS Series, Wattstopper DCC2 and LVS series. Generator – Kohler; provide 25A 3-pole and 60A 3-pole breakers and critical muffler as spec’d. Light Fixtures: Northern Rockies Agency - Approved types: A1, A2, A3, A3E, A5, A6, A7, B1, B1E, B2, B3, B4, C1, E3 – LSI E2 – Pathway EM, F1, F2, F3, X1, X2, X4 – Philips. D4, S1, S2, S3, S4, S5, S6 – Gardco Pole for S series fixtures - Hapco (Note that all fluorescent fixtures other than F series fixtures shall have F28T8 Energy saving lamps and compatible ballasts as scheduled) CLR – Approved types: A1, A2, A3, A3E, A5, A6, A7, B1, B1E, B2, B3, B4, C1, EM, E2, E3, F1, F2, F3, X1, X2, X4 – H.E. Williams Inc. D2 – Juno Lighting Group S1, S2, S3, S4, S5, S6 fixtures and poles – Juno Lighting Group AccuLite. Prime West Electrical Group – Approved types: A1, A2, A3, A3E, A5, A6, A7, B1, B1E, B2, B3, B4, F1, F2, F3 – Columbia Lighting E2, E3 – Prescolite EM, X1, X2, X4 – Dual-Lite (Note that all fluorescent fixtures other than F series fixtures shall have F28T8 Energy saving lamps and compatible ballasts as scheduled) Illumination Systems Inc. – Approved types: A1, A2, A3, A3E, A5, A6, A7, B1, B1E, B2, B3, B4, C1, F1, F2, F3 – Metalux D1, D3 – Bock Lighting EM, X1, X2, X4 – Surelites (X1 and X2 approval on change to AC power) D2 – Lumark. END OF ADDENDUM
REYNOLDS MARKET REYNOLDS_FOX RUN 100% CONSTRUCTION DOCUMENTS 03/01/2013 SIDNEY, MONTANA
BID FORM AD2 1
BID FORM PROJECT: REYNOLDS MARKET - FOX RUN RETAIL SIDNEY, MONTANA
CTA Project No. REYNOLDS_FOXRUN TO: John Reynolds
C/O CTA Architects Engineers 13 N. 23rd Street Billings, MT 59101
BID FROM: _________________________________________________________________________ I have familiarized myself with the conditions of the Work and Contract Documents, as prepared by CTA Architects Engineers, Billings, Montana; Great Basin Engineering, Salt Lake City, Utah; and Interstate Engineering, Sidney, Montana; and agree to furnish all labor, materials, equipment and services necessary to complete all Work, as bid herein, for Reynolds Market - Fox Run Retail Space, Sidney, Montana, in accordance with the Contract Documents, including all Addenda. Addendum No. Dated Addendum No. Dated Addendum No. Dated I have examined both the Documents and the site and submit the following Bid: In submitting this Bid, I agree:
1. To hold my Bid open thirty (30) consecutive calendar days from the date of Receipt of Bids. 2. To accept the provisions of the Instructions to Bidders regarding disposition of Bid Security. 3. To enter into and execute a Contract, if awarded on the basis of this Bid and to furnish all bonds
and insurance required by the Bidding Documents. 4. To accomplish the Work not later than stipulated in Invitation to Bid to accomplish the Work in
accordance with the Contract Documents. I agree to complete all Construction for the sum(s) as delineated by the following: Grand Total Base Bid (Sum of Base Bids A, B, C, D, E, and F): __________________________________________________________dollars ($__________). Total of "Grand Total Base Bids" Written in Words
REYNOLDS MARKET REYNOLDS_FOX RUN 100% CONSTRUCTION DOCUMENTS 03/01/2013 SIDNEY, MONTANA
BID FORM AD2 2
Base Bid "A" - Reynolds Market, 47,500 Sq. Ft. Grocery Store including Connecting Wall at Easement and Patio (CTA Documents):
__________________________________________________________dollars ($__________). Total Base Bid "A" Written in Words Base Bid "B" - 12,000 Sq Ft. Fox Run Retail Space (CTA Documents): __________________________________________________________dollars ($__________). Total Base Bid "B" Written in Words Base Bid "C" - Subdivision Water and Sewer Improvements (Interstate Engineering
Documents): __________________________________________________________dollars ($__________). Total Base Bid "C" Written in Words (Total of Unit Pricing below)
BASE BID "C" - AUGUSTUS VAUX SUBDIVISION WATER & SEWER IMPROVEMENTS
ITEM No.
ITEM UNIT No. OF UNITS
UNIT PRICE L & M
EXTENDED PRICE L & M
1 Mobilization, Taxes, Bonds and Insurance L.S. 1
2 12” Water Main L.F. 1,482
3 12” Water Main Replacement L.F. 572
4 12” Gate Valve w/ Riser EA 10
5 10” Water Main L.F. 2,298
6 10” Gate Valve w/ Riser EA 7
7 Fire Hydrant Assembly w/ Valves EA 11
8 New 1” Water Service Connection EA 8
9 New 2” Water Service Connection EA 5
10 Water Service Reconnection EA 4
11 12” Water Main Highway Bore (Cased) L.F. 100
12 21” (nominal) SDR 35 PVC Sewer Main L.F. 805
13 12” (nominal) SDR 35 PVC Sewer Main L.F. 1,078
14 10” (nominal) SDR 35 PVC Sewer Main L.F. 592
15 Standard Manhole EA 12
16 Additional Manhole V.F. 26
17 Sewer Manhole Tie-in EA 3
18 4” Sanitary Sewer Service EA 7
19 6” Sanitary Sewer Service EA 5
REYNOLDS MARKET REYNOLDS_FOX RUN 100% CONSTRUCTION DOCUMENTS 03/01/2013 SIDNEY, MONTANA
BID FORM AD2 3
20 Imported Backfill C.Y. 1,000
21 Type II Bedding C.Y. 2,000
22 Exploratory Excavation Hours 15
Base Bid "D" - Street and Drainage Improvements (Interstate Engineering Documents): __________________________________________________________dollars ($__________). Total Base Bid "D" Written in Words (Total of Unit Pricing below) BASE BID "D" - AUGUSTUS VAUX STREET & DRAINAGE IMPROVEMENTS
ITEM No.
ITEM UNIT No. OF UNITS
UNIT PRICE L & M
EXTENDED PRICE L & M
1 Mobilization, Taxes, Bonds and Insurance L.S. 1
2 Remove & Stockpile Topsoil C.Y. 1,200
3 Embankment In-Place C.Y. 4,400
4 Subgrade Preparation S.Y. 5,450
5 Geotextile Fabric S.Y. 5,450
6 12” Depth – 2” Minus Uncrushed Sub Base S.Y. 5,450
7 6” Depth – 1” Minus Crushed Base Course S.Y. 5,450
8 3” Hot Bituminous Pavement S.Y. 5,450
9 Curb & Gutter L.F. 2,570
10 Concrete Curb Turn Fillet EA 8
11 Concrete Valley Gutter S.F. 1,412
12 Asphalt Surface Restoration L.F. 575
13 Curb & Gutter Remove & Replace L.F. 20
14 MDT Highway Approaches L.S. 2
15 Storm Sewer Inlet & RCP Pipe L.S. 1
16 Testing Laboratory Services L.S. 1 $9,500.00 $9,500.00
Base Bid "E" - Earthwork, site concrete, asphalt and striping (Great Basin Documents): __________________________________________________________dollars ($__________). Total Base Bid "E" Written in Words
REYNOLDS MARKET REYNOLDS_FOX RUN 100% CONSTRUCTION DOCUMENTS 03/01/2013 SIDNEY, MONTANA
BID FORM AD2 4
Base Bid "F" - Landscaping (CTA Documents L101 through L405): __________________________________________________________dollars ($__________). Total Base Bid "E" Written in Words
Alternate Bid No. 1: Add Moisture Retaining Cover (General Sales Floor Only). __________________________________________________________dollars ($__________). Total Alternate Bid No. 1 Written in Words
Alternate Bid No. 2: Add Remote Generator Manual Transfer Switch. __________________________________________________________dollars ($__________). Total Alternate Bid No. 2 Written in Words
Alternate Bid No. 3: Add Performance Bond and Payment Bond - Site/Civil Work Only. __________________________________________________________dollars ($__________). Total Alternate Bid No. 3 Written in Words
Alternate Bid No. 4: Finish Retail Space B-700. __________________________________________________________dollars ($__________). Total Alternate Bid No. 4 Written in Words
Alternate Bid No. 5: Two (2) Houses to Remain. __________________________________________________________dollars ($__________). Total Alternate Bid No. 5 Written in Words
Alternate Bid No. 6: Demo two (2) Houses. __________________________________________________________dollars ($__________). Total Alternate Bid No. 6 Written in Words
Alternate Bid No. 7: 15-Second Delay Panic Hardware. __________________________________________________________dollars ($__________). Total Alternate Bid No. 7 Written in Words
Unit Price No. 1: Electrical - Provide Duplex Receptacle. __________________________________________________________dollars ($__________).
REYNOLDS MARKET REYNOLDS_FOX RUN 100% CONSTRUCTION DOCUMENTS 03/01/2013 SIDNEY, MONTANA
BID FORM AD2 5
Total Unit Price No. 1 Written in Words
Unit Price No. 2: Electrical - Provide Drop Cord Receptacle. __________________________________________________________dollars ($__________). Total Unit Price No. 2 Written in Words
Unit Price No. 3: Single-user Restroom. __________________________________________________________dollars ($__________). Total Unit Price No. 3 Written in Words I have attached the required Bid Security to this Bid. I understand that if I do not answer the above questions and complete all blank spaces provided, my Bid may be rejected as an incomplete Bid. Respectfully Submitted: Date: By: Contractor
Signature
Title
Business Address
(Seal - if by a Corporation) Montana Public Contractor’s License No.
FLOOR FINISHES
SC SEALED CONCRETE
CC COLORED CONCRETE (WITHOUT SPECIAL FINISH)
EPX EPOXY
T TILE
PT PROTECTAL (4X8 SHEETS GLUED & WELDED W/ INTEGRAL BASE)
SPC SPECIAL COLORED CONCRETE WITH ADDITIONAL FLOOR FINISH
BASE FINISHESCB CONCRETE BASE (COOLER) SEE 7/A131 & 8/A131RB RUBBER BASET 6" TILE BASE
WALL FINISHESCP COOLER PANELWT WALL TILEFRP FIBERGLASS REINFORCED PANELP PAINT
MISC. FINISHESXX XXXX
ADDITIONAL NOTES1. EXISTING COOLER/FREEZER2. 5/8" DENSGLASS TO BE USED AT ALL TILE AND FRP LOCATIONS UP TO 48" A.F.F.ABOVE 48" USE 5/8" WATER RESISTANT G.W.B.3. FRP WAINSCOT TO 48" A.F.F.
BILLINGS, MT(406)248-7455
Fax (406)248-3779
DRAWN BY
CHECKED BY
CTA #
REF SHEET #
SHEET#
R
SIDNEY MONTANA
TK
SS
REYNOLDS
A501
A501-1
REYNOLD'S MARKET
AT FOX RUN
TAG # REVISION DATE1 ADD02 3-26-13
1
1
FFF
E.8 E.8
12
ELECTRICLANDB100
WOMEN'SB103
MEN'SB102
MECHB104
3
RBFRP
FRP
FRP
FRP
3
RBFRP
FRP
FRP
FRP
BASE FINISHESCB CONCRETE BASE (COOLER) SEE 7/A131 & 8/A131RB RUBBER BASET 6" TILE BASE
WALL FINISHESCP COOLER PANELWT WALL TILEFRP FIBERGLASS REINFORCED PANELP PAINT
MISC. FINISHESXX XXXX
ADDITIONAL NOTES1. EXISTING COOLER/FREEZER2. 5/8" DENSGLASS TO BE USED AT ALL TILE AND FRP LOCATIONS UP TO 48" A.F.F.ABOVE 48" USE 5/8" WATER RESISTANT G.W.B.3. FRP WAINSCOT TO 48" A.F.F.
BIL
LIN
GS
, MT
(406
)248
-745
5F
ax (4
06)2
48-3
779
DR
AW
N B
Y
CH
EC
KE
D B
Y
CT
A #
RE
F S
HE
ET
#
SH
EE
T#
R
\\ys0
30\U
sers
_Fol
ders
\todd
k\D
ocum
ents
\RE
DS
Arc
h_C
entra
l_to
ddk.
rvt
SID
NE
Y M
ON
TA
NA
TK
SS
RE
YN
OLD
S
A50
2
A50
2-1
RE
YN
OLD
'S M
AR
KE
T
AT
FO
X R
UN
TA
G #
RE
VIS
ION
DA
TE
1A
DD
023-
26-1
3
3/32" = 1'-0"A502-1
2 FINISH PLAN - TENANT B
1
1
1
G
9
G
A701
22
A701-1
22
7'-0 1/4" 2'-0 1/4"
7'-0
1/4
"
2'-0"
HEAT & GLOTRU-50 GAS FIREPLACENEW BRONZE FIRESCREEN;STRATFORD REFRACTORY;INTELLIFIRE PLUS
FIREPLACE WALL:3-5/8" METAL STUDS,5/8" CEMENT BACKER BOARD,AND CULTURED STONE.
1'-0 3/4"
1'-0
3/4
"
APPROX T.V. OUTLINE
OMIT STONE TO PROVIDE SPACEFOR MOUNTING BRACKET.PROVIDE BLOCKING IN WALL FORBRACKET.
1'-6"1'-6"
3'-0"
2'-0
"8'
-9"
6"5'
-6"
8"1'
-4"
HEAVY TIMBER MANTEL12" DEEP
HEAT & GLOTRU-50 GAS FIREPLACENEW BRONZE FIRESCREEN;STRATFORD REFRACTORY;INTELLIFIRE PLUS
4" BURNISHED BLOCK
CULTURED STONE
PRECAST CONCRETE HEARTH
6"6"
1'-0
"
1'-0"
1'-0
"
4"
MANTELBRACKET
HEAVY TIMBERMANTEL BRACKET
POWER AND CABLE (SEE ELECTRICAL)
3"3"
9 1/4"9 1/4"
BIL
LIN
GS
, MT
(406
)248
-745
5F
ax (4
06)2
48-3
779
DR
AW
N B
Y
CH
EC
KE
D B
Y
CT
A #
RE
F S
HE
ET
#
SH
EE
T#
R
\\ys0
30\U
sers
_Fol
ders
\todd
k\D
ocum
ents
\RE
DS
Arc
h_C
entra
l_to
ddk.
rvt
SID
NE
Y M
ON
TA
NA
TK
SS
RE
YN
OLD
S
A70
1
A70
1-1
RE
YN
OLD
'S M
AR
KE
T
AT
FO
X R
UN
1/4" = 1'-0"A701-1
21 FIREPLACE PLAN
TA
G #
RE
VIS
ION
DA
TE
1A
DD
023-
26-1
3
1/4" = 1'-0"A701-1
22 FIREPLACE
1
6" CI
6" AC
4" A
C
6" AC
12" P
VC
12" P
VC
10" PVC
Fast
Food
2,8
90
Sq. ft.
Bank4,000 Sq. ft.
6,500 Sq. ft.
Retail
Fast Food4,540 Sq. ft.
12,800 Sq. ft.
Retail E
MO
NT
AN
A S
TA
TE
HIG
HW
AY
NO
. 16
MIL
LE
R S
TR
EE
T
FRONTAGE ROAD
9
4 4 2
19
7
Future
Future
FutureFutureFuture
C e n t r a l A v e n u e( S t a t e R o a d 2 0 0 )
P r
o p
o s
e d
8 t
h
S t
r e
e t N
W
4th
Stre
et
NW
Desig
n b
y I
nte
rsta
te E
ngin
eering
Improvements to Central Avenue by Interstate Engineering
Retail C8,040 Sq. ft.
Expansion15,000 Sq. ft.
Retail D25,540 Sq. ft.
Future
Drive Approach, Paint Striping,and Signage. See Design by
Interstate Engineering
Drive Approach, Paint Striping,and Signage. See Design by
Interstate Engineering
Drive Approach, Paint Striping,and Signage. See Design by
Interstate EngineeringDrive Approach, Paint Striping,
and Signage. See Design by
Interstate Engineering
Design byInterstate Engineering
D
FIRE PROTECTION LEGEND
FLANGEDFL
GROOVEDGR
GALVANIZEDGALV
MECHANICAL JOINTMJ
THREADEDTH
SYMBOL DESCRIPTION
UNDERGROUND FIRE SERVICE
FIRE SPRINKLER PIPING, WET SYSTEM
FIRE SPRINKLER PIPING, DRY SYSTEM
FIRE SPRINKLER DRAIN LINE
ELBOW DOWN
ELBOW UP
TAMPER SWITCH
FLOW SWITCH
FIRE DEPARTMENT CONNECTION, SIAMESE
HORN/STROBE ASSEMBLY
FIRE HYDRANT
TEE DOWN
TEE UP
SQUARE FEETSF
FIRE DEPARTMENT CONNECTIONFDC
FIRE SPRINKLER FDC LINE
FIRE PROTECTION ABBREVIATIONS
F
F-D
F
FDC
TS
FS
FIRE SPRINKLER RISER
CONNECT TO EXISTING
WATER SUPPLY INFORMATION
32/35
STATIC PRESSURE:
PITOT PRESSURE:
59
GPM FLOWING
PSI
PSI WITH 1941
JASON ELLETSONBY: 03/15/2013DATE:
NOTE: TWO HYDRANTS WERE FLOWED SIMULTANEOUSLY.
RESIDUAL PRESSURE: PSI43
3RD AVENUE SOUTHWEST ANDWEST HOLLY
TEST HYDRANT LOCATION:
2
1/FP100 NOTES#
1. 8" FIRE SERVICE TO WITHIN 5'-0" OF BUILDING BY OTHERS. SEESITE UTILITY PLAN.
2. 8" TRANSITION COUPLING.3. 8" CLASS 52 CEMENT LINED DUCTILE IRON FIRE SERVICE UNDER
BUILDING FOOTING AND THROUGH FLOOR SLAB. SEE DETAIL2/FP101.
4. FIRE SERVICE ENTRANCE AND RISER. SEE DETAIL 1 &2/FP101.5. FDC AND HORN/STROBE ASSEMBLY.6. LOCATION OF FLOW HYDRANTS.7. APPLY HOSE ALLOWANCE AT THIS FIRE HYDRANT.8. 6" FIRE SERVICE TO WITHIN 5'-0" OF BUILDING BY OTHERS. SEE
SITE UTILITY PLAN.9. 6" TRANSITION COUPLING.10. 6" CLASS 52 CEMENT LINED DUCTILE IRON FIRE SERVICE UNDER
BUILDING FOOTING AND THROUGH FLOOR SLAB. SEE DETAIL5/FP202.
11. FIRE SERVICE ENTRANCE AND RISER. SEE DETAILS 4,5,&6/FP202.12. CO-LOCATE KNOX BOX WITH FDC.13. LOCATION OF STATIC AND RESIDUAL HYDRANT.
2
2
12"
CO
OLE
R2
4"
FR
EE
ZE
R
SHEET METAL SLEEVE
RIGID FOAM SPRAYED INPLACE OR CELLULARFOAM
SUPPORTS, PIPING,CONDUIT, ETC
SEALANT
COOLER/FREEZER CEILING PANEL
DRY TYPE PENDENTSPRINKLER(LENGTH PER MFG'SRECOMMENDATIONS)MINIMUM 18"
EXTEND FROMSPRINKLER SYSTEM
NOTE:TYCO DRY SPRINKLERBOOT MAY BE SUBSTITUTEDIF INSTALLED PERMANUFACTURERSRECOMMENDATIONS
CEILING PLATE
FILL CLEARANCE SPACE (AS PERMANUFACTURERS RECOMMENDATIONS)
INTERMEDIATETEMPERATUREDRY SPRINKLER
NOTE: ALL FREEZERS/COOLERS ARE TO BE PROTECTED WITHINTERMEDIATE TEMPERATURE DRY PENDENT SPRINKLERS.
6
7
1
2
3
5
F
4
FF
5
8
9
10
11
12
REYNOLDS MARKETCONSTRUCTION TYPE: IIBIFC FIRE FLOW CALCULATION AREA: 48,948 SFIFC REQUIRED FIRE FLOW: 1500 GPM @ 20 PSI FOR 4 HOURSAVAILABLE FIRE FLOW: 3140 GPM @ 20 PSIFINISH FLOOR ELEVATION: 1938' (100'-0")WATER SUPPLY INFORMATION ELEVATION: 1940'
TENANT SPACE BCONSTRUCTION TYPE: IIBIFC FIRE FLOW CALCULATION AREA: 12,000 SFIFC REQUIRED FIRE FLOW: 1500 GPM @ 20 PSI FOR 2 HOURSAVAILABLE FIRE FLOW: 3140 GPM @ 20 PSIFINISH FLOOR ELEVATION: 1938' (100'-0")WATER SUPPLY INFORMATION ELEVATION: 1940'
REYNOLDS MARKET
TENANT SPACE B
12
6
13
2
2
2
2
BEAM CLAMP W/RESTRAININGSTRAP
STEELBEAM OR
STEELBAR JOIST
BEAM CLAMP W/RESTRAININGSTRAP
THREADED ROD
STEEL BARJOIST
THREADEDROD
ERICO HANGERRING OR EQUAL
THREADEDROD
STEELBEAM
BEAM CLAMP W/RESTRAININGSTRAP
THREADED ROD
ERICO HANGERRING OR EQUAL
ERICO HANGERRING OR EQUAL
ANGLE IRON, UNISTRUTOR EQUAL
BEAM CLAMP W/RESTRAININGSTRAP
THREADED ROD
STRUTCLAMP
CHANNEL/STRUT
MAXIMUM PIPE/TUBING SUPPORT SPACING, FEET
151515
4" 6" 8"
151515151212N.A.STEEL
THRU 3/4"NOM. SIZE 1-1/2"1-1/4"1" 2-1/2"2" 3"
1. UNSUPPORTED LENGTHS BETWEEN THE END SPRINKLER ON A BRANCH AND THE LAST HANGER SHALL
NOT BE GREATER THAN 12".
2. THE LENGTH OF AN UNSUPPORTED ARM OVER MUST NOT BE GREATER THAN 12".
3. ALL HANGERS LOCATED WITHIN 12" OF THE LAST SPRINKLER ON A BRANCH LINE OR ARMOVER MUST
BE FITTED WITH A SURGE SUPPRESSOR OR EQUIVALENT.
NOTES
STEELBEAM OR
STEELBAR JOIST
3/FP100 NOTES
1. GYPSUM WALL ASSEMBLY
2. SLEEVE
3. PENETRATING PIPE
4. FORMING MATERIAL TIGHTLY PACKED
5. INTUMESCENT FIRESTOP SEALANT
6. MINIMUM 1/2" BEAD INTUEMSCENT FIRESTOP SEALANT AT POINT OF CONTACT
NOTE: PROVIDE PIPE STOPPING SYSTEMS IN SUBMITTALS
METAL PIPE THROUGH A FIRE RATED GYPSUM WALL ASSEMBLY
2
41
3
6
#
5
METAL PIPE THROUGHA CMU WALL
2
5
3
7. CMU WALL ASSEMBLY
7
1. DESIGN AND INSTALLATION SHALL CONFORM TO NFPA 13, 2007 EDITION, LOCAL FIRE AND BUILDING DEPARTMENTS.2. THE SPRINKLER SYSTEM SHOWN IS CONCEPTUAL ONLY. THE CONTRACTOR SHALL PROVIDE A COMPLETE SPRINKLER
SYSTEM SHOWING ALL REQUIRED PIPING, OFFSETS, SPRINKLERS, RISERS AND DROPS.3. CONTRACTOR SHALL SECURE ALL PERMITS AND PAY ALL FEES REQUIRED BY THE LOCAL AUTHORITY HAVING
JURISDICTION AND BUILDING DEPARTMENTS.4. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND
OPERABLE FIRE PROTECTION SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED AND COMPLYING WITH THESTANDARDS OF THE NATIONAL FIRE PROTECTION ASSOCIATION, INDUSTRIAL RISK INSURERS, AND ALL STATE ANDLOCAL REGULATIONS.
5. APPROVAL OF THE COMPLETE SYSTEM SHALL BE OBTAINED FROM THE AUTHORITIES HAVING JURISDICTION, AND ACOPY OF SAME SHALL BE DELIVERED TO THE OWNER'S REPRESENTATIVE FOR DELIVERY TO THE OWNER. PROVIDETHE AUTHORITY HAVING JURISDICTION PLANS AS WELL AS A COST ESTIMATE. THE CONTRACTOR IS RESPONSIBLEFOR PAYING ASSOCIATED PLAN REVIEW FEES.
6. RESTORE ALL DEVICES, FINISHES, ETC. DAMAGED OR ALTERED DURING CONSTRUCTION TO AN ACCEPTABLECONDITION AS DETERMINED BY THE OWNER, ARCHITECT AND/OR ENGINEER.
7. CONTRACTOR SHALL SCHEDULE ALL SHUTDOWNS THAT AFFECT UTILITIES AND PORTIONS OF THE BUILDING THATMUST REMAIN IN OPERATION WITH THE OWNER.
8. PROVIDE AND INSTALL SPRINKLERS OF THE PROPER TEMPERATURE RATING AND TYPE PER NFPA 13.9. PROVIDE AND INSTALL VALVES OF THE PROPER TYPE, UL LISTED, AND PRESSURE RATING PER NFPA 13.10. PROVIDE AND INSTALL SPARE SPRINKLERS, WRENCH AND CABINET PER NFPA 13.11. COORDINATE INSTALLATION OF ALL ELECTRICALLY SUPERVISED VALVES, HORN/STROBE, ETC. WITH THE ELECTRICAL
CONTRACTOR.12. PROVIDE AND INSTALL A HYDRAULIC PLACARD WITH THE HYDRAULIC DESIGN DATA FOR EACH ZONE RISER OR
SYSTEM CALCULATED.13. PROVIDE AND INSTALL A SIGN WITH RAISED LETTERS FOR THE FDC PER NFPA 13.14. PROVIDE AND INSTALL AUX. DRAINS AND VALVES AS REQUIRED FOR PROPER DRAINING OF THE SYSTEM.15. COORDINATE SPRINKLER PIPING AND HEAD LOCATIONS WITH DUCTWORK, PIPING, LIGHTING FIXTURES, DIFFUSERS,
ETC. AS REQUIRED.16. ISOLATE, DRAIN AND REFILL EXISTING PIPING SYSTEM AS REQUIRED TO ACCOMMODATE INSTALLATION OF NEW
WORK.17. HANGER INSTALLATION AND SPACING SHALL BE IN ACCORDANCE WITH NFPA 13.18. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CORING AND DRILLING AS REQUIRED.19. THE CONTRACTOR SHALL SUBMIT SIZE AND LOCATION OF ALL BEAM PENETRATIONS TO THE STRUCTURAL ENGINEER
FOR REVIEW AND DETAIL.20. WHERE PIPING PASSES THROUGH FIRE RATED FLOORS OR WALLS, SLEEVES SHALL BE COMPLETELY SEALED WITH A
FIRE STOP MATERIAL THAT IS UL LISTED AND ACCEPTED BY THE BUILDING DEPARTMENT AND FIRE DEPARTMENT.THIS MATERIAL SHALL BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER TOMAINTAIN THE FIRE RATING OF THE PENETRATED WALL OR FLOOR.
21. SLEEVES THROUGH WALL AND FLOOR SHALL BE SCH. 10 GALVANIZED AND PACKED WITH NONCOMBUSTIBLE,SMOKEPROOF, AND WATERPROOF FIRE SEALANT.
22. DESIGN AND INSTALL FIRE PUMP TO NFPA 20.23. ALL SHUTOFF VALVES IN SPRINKLER, STANDPIPE, AND COMBINED SYSTEMS SHALL BE APPROVED INDICATING TYPE.24. COORDINATE SPRINKLER HEAD LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS, LIGHTING, AND
OTHER CEILING ITEMS AND MAKE MODIFICATIONS TO SUIT.25. SPRINKLERS INSTALLED IN CEILINGS OF FINISHED AREAS SHALL BE SYMMETRICAL IN RELATION TO CEILING SYSTEM
COMPONENTS AND CENTERED IN THE CEILING TILE.26. THIS LOCATION IS A SEISMIC DESIGN CATEGORY "A". NO SEISMIC BRACING REQUIRED.27. ALL PIPING 2" AND SMALLER SHALL BE SCHEDULE 40 PIPE. PIPING 2 1/2" AND LARGER SHALL BE SCHEDULE 10 PIPE
WITH GROOVED FITTINGS.28. ALL DRY SYSTEM PIPING ABOVE GROUND SHALL BE GALVANIZED THREADED FITTINGS AND SCHEDULE 40 PIPE FOR
SIZES 2" AND SMALLER. SIZES 2 1/2" AND LARGER SHALL BE SCHEDULE 10 GALVANIZED PIPE AND HOT DIPPEDGALVANIZED OR PAINTED DUCTILE IRON FITTINGS. GROOVED PIPE COUPLINGS SHALL BE GALVANIZED OR PAINTED.
GENERAL NOTES
FIRE PUMP CURVE FOR AURORA 6-481-11, 1000 GPM, 40 TO 50 PSI, 912 SERIES PUMP.HYDRAULIC CALCULATIONS REQUIRED:
HYDRAULICALLY CALCULATE THE MOST DEMANDING LIGHT HAZARD ; 1500 SF AT .10 GPM/SFAND 100 GPM OUTSIDE HOSE ALLOWANCE.
HYDRAULICALLY CALCULATE THE MOST DEMANDING ORDINARY GROUP 1 ; 1500 SF AT .15 GPM/SFAND 250 GPM OUTSIDE HOSE ALLOWANCE.
HYDRAULICALLY CALCULATE THE MOST DEMANDING ORDINARY GROUP 2 ; 1500 SF AT .20 GPM/SFAND 250 GPM OUTSIDE HOSE ALLOWANCE.
NOTES:
1. CALCULATED DEMAND INCLUDING HOSE STREAM REQUIREMENTS SHALL FALL NO LESS THAN 10
PSI BELOW THE AVAILABLE WATER SUPPLY CURVE.
2. NO REDUCTIONS FOR QUICK RESPONSE SPRINKLERS WILL BE ALLOWED.
3. PERFORM ADDITIONAL SUPPLY CALCULATIONS FOR EACH STORAGE DESIGN AREA TOCONFIRM THAT CITY WATER PRESSURE IS MAINTAINED ABOVE 20 PSI AT SOURCE.
4. SPRINKLER CONTRACTOR TO COORDINATE WITH OTHER TRADES TO PREVENT CONFLICT WITH
OTHER BUILDING SYSTEMS. ANY INSTALLATION WITHOUT PRIOR COORDINATION IS SUBJECT TO
REMOVAL AND REINSTALLATION AT THE INSTALLING CONTRACTOR'S EXPENSE.
5. NO EXTENDED COVERAGE SPRINKLERS WILL BE ALLOWED UNLESS NOTED OTHERWISE.
HYDRAULICALLY CALCULATE THE MOST DEMANDING RACK STORAGE AREA 1 ; 2000 SF AT .37 GPM/SFAND 500 GPM OUTSIDE HOSE ALLOWANCE.
HYDRAULICALLY CALCULATE THE MOST DEMANDING FREEZER/COOLER AREA 1 ; 2000 SF AT .30 GPM/SFAND 500 GPM OUTSIDE HOSE ALLOWANCE.
ALL SPRINKLERS SHALL BE CENTERED WITH 1" +/- OF CENTER POINTS OFCEILING TILES. (QUARTER POINTS ARE ACCEPTABLE AS SHOWN ON PLANS)
1'-0" 1'-0" 1'-0" 1"-0"
1"-
0"
1'-0"
1"-
0"
1'-0"
1'-0" 1"-0"
R
SHEET
CHECKED BY:
CTA #
DATE:
DRAWN BY:
COPYRIGHT 2013
CTA, INC.ALL RIGHTS RESERVED
SID
NE
Y,
MO
NT
AN
A\\ys0
30
\Use
rs_F
old
ers
\will
s\D
ocum
en
ts\R
evit20
12
\RE
YN
OLD
S_
FO
X\R
ED
SM
EP
_w
ills.r
vt
FP100
FIREPROTECTION
SITE PLAN,LEGEND, AND
DETAILS
100%
CO
NS
TR
UC
TIO
ND
OC
UM
EN
TS
RE
YN
OL
D'S
MA
RK
ET
AT
FO
X R
UN
WS
DH/DK
REYNOLDS
03/01/13
NOT TO SCALEFP100
4 WALK IN BOX FREEZER/COOLER FIRE SPRINKLER ASSEMBLY
1" = 100'-0"FP100
1 FIRE PROTECTION SITE PLAN 0'
1" = 100'-0"
25' 100' 200'
NOT TO SCALEFP100
2 FIRE SPRINKLER PIPE HANGER DETAILS
NOT TO SCALEFP100
3 FIRE STOPPING PIPE PENETRATION DETAILS
NOT TO SCALEFP100
5 FIRE PROTECTION PUMP CURVE
N
12111 P.E.
KOPPDANIEL J.
OIS
S
EF
OR
P
RE
ENI
GNELA
ANAMONT
REG I STER
DE
~
/ / / / / / / / / //
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
///////////////////
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
/ / / / / / / /
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~~~~~~~~
~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~~~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
NOT TO SCALEFP100
6 SPRINKLER HEAD IN CENTER PLACEMENT
RE
VIS
ION
S
23
/20/2
013
AD
DE
ND
UM
#2
A
6 7
A
6 7
2
FP101
3
FP101
OH2
4
FP101
125
RISER
1
2
3
6
7
8
TS
TS
9
TS
8
8
FP-1
18
20 13
21
8
6
22
17
24
11
12
TS
15
TS
18
TS
19
TS
19
TS
19
4" TO FDC
6" TO WETSYSTEM
2
TEST HEADERLINE
BYPASS LINE
TS
FP-1
18
24
13
TS
26 26
123
6
3
5
4
TS
TS TS
7
24
24
17
24
19 19
24
20
2124 24 23
14
125
RISER
2614
TS
19
24
2
15
TS
19
BYPASS LINE
TEST HEADERLINE
PLANCODE
MODEL NO REMARKSMFGR GPM RPM POWER
5
FIRE PUMP SCHEDULE
FP-1
JP-1
AURORA
RATED PRES.PSI
460/3Ø1750
AURORA -
HP ULRATED
FIRE PUMP DESIGN AND BUILDING NOTES:
1
HP(BHP)
PVMX2 69
6-481-11 1,000 40 30
-
34
PROVIDE WITH METRON FULL SERVICE FIRE PUMP CONTROLLER WITH SOFT START.
PROVIDE WITH METRON JOCKEY PUMP CONTROLLER.
COORDINATE ELECTRICAL REQUIREMENTS WITH ELECTRICAL CONTRACTOR.
1
2
3
1 3
2460/3Ø 3
14 2626
18
TS
24
22
TS
19
19
TS
2
BYPASS LINE
TEST HEADERLINE
15
24
1112
9
TS
26
CROSSMAIN (TYPICAL)
BRANCHLINE(TYPICAL)
6" RISER
26
TS
1919
TS
26
4" TO FDC
2
FUTURE BUILDING EXPANSION IS POSSIBLE.SAVE SPACE FOR FUTURE RISER IF NEEDED.
19
24
TEST HEADERLINE
BYPASS LINE
UNION (TYPICAL)
1-1/4" PIPINGANDSCREWEDFITTINGS
1/2" COPPER TUBING
1/2 " BRONZE CHECKW/ 3/32" ORIFICE(TYPICAL)
JP-1
TSTS
JOCKEY PUMPCONTROLLER
1, 2, 3 & 4/FP101 DETAIL NOTES#
1. 8" FIRE SERVICE TO WITHIN 5'-0" OF BUILDING BY OTHERS.2. 8" TRANSITION COUPLING.3. 8" CLASS 52 CEMENT LINED DUCTILE IRON FIRE SERVICE UNDER
BUILDING FOOTING AND THROUGH FLOOR SLAB BY FIRE SPRINKLERCONTRACTOR.
4. CONCRETE THRUST BLOCK WITH MEGA-LUG RESTRAINT.5. 12" SCH. 40 STEEL SLEEVE THRU CONCRETE. SEAL ANNULAR
SPACE WITH WATERTIGHT MASTIC.6. 8" FL ELBOW.7. 8" DOUBLE CHECK VALVE ASSEMBLY WITH OS&Y VALVES AND
TAMPER SWITCHES.8. 8" FL PIPE.9. 6" COMMERCIAL RISER MANIFOLD WITH PRESSURE RELIEF.10. CENTRAL SPARE HEAD CABINET WITH WRENCH.11. JOCK PUMP CONTROLLER.12. FIRE PUMP CONTROLLER.13. FIRE PUMP, FP-1.14. JOCKEY PUMP SUPPLY AND DISCHARGE LINES TO JP-1. SEE
JOCKEY PUMP DETAIL, 5/FP101.15. PUMP TEST HEADER ( 4) 2 1/2" OUTLETS WITH VALVES.16. 6" GR GALV PIPING.17. FLOW METER, 6" MINIMUM.18. 8" FL OS&Y VALVE WITH TAMPER SWITCH.19. 8" GR BUTTERFLY VALVE WITH TAMPER SWITCH.20. ECCENTRIC INCREASER.21. CONCENTRIC INCREASER.22. 8" FL CHECK VALVE.23. PRESSURE GUAGE.24. 8" GR PIPE.25. 6" GR PIPE.26. 2" PIPE STAND.27. 6" GR FEED MAIN.28. 4" GR PIPE.29. 4" GR CHECK VALVE. MAINTAIN A MINIMUM OF 4'-0" PIPING IN
CONDITIONED SPACE UPSTREAM.30. 4" GR GALV PIPE.31. 4" x 1" GR DRAIN ELBOW WITH BALL DRIP. ROUTE GALV DRAIN
PIPING TO BUILDING EXTERIOR.32. 4" x 2 1/2" x 2 1/2" ROUGH BRASS FDC WITH "AUTO SPKR" WALL
PLATE, BRASS PLUGS WITH CHAINS. FDC IS TO BE LOCATED NOTLESS THAN 18" AND NOT MORE THAN 48" ABOVE GRADE.
33. HORN/STROBE ASSEMBLY. COORDINATE INSTALLATION WITHELECTRICAL CONTRACTOR
2
LH
28
29
30
31
32
33
28
TO FIRE RISERROOM
102
CART STORAGE
CHECK VALVE INSTALLEDIN HEATED SPACE,CART STORAGE 101
DRY PIPE TO EXTERIOREXITS THROUGH COLD SPACE,EXTERIOR STORAGE 147
2
R
SHEET
CHECKED BY:
CTA #
DATE:
DRAWN BY:
COPYRIGHT 2013
CTA, INC.ALL RIGHTS RESERVED
SID
NE
Y,
MO
NT
AN
A\\ys0
30
\Use
rs_F
old
ers
\will
s\D
ocum
en
ts\R
evit20
12
\RE
YN
OLD
S_
FO
X\R
ED
SM
EP
_w
ills.r
vt
FP101
FIREPROTECTION
PUMP ANDRISER DETAILS
100%
CO
NS
TR
UC
TIO
ND
OC
UM
EN
TS
RE
YN
OL
D'S
MA
RK
ET
AT
FO
X R
UN
WS
DH/DK
REYNOLDS
03/01/13
3/8" = 1'-0"FP101
1 ENLARGED FIRE RISER ROOM PLAN 3/8" = 1'-0"FP101
2 FIRE RISER ROOM SECTION 1PLAN
NORTHTRUE
NORTH
0'
SCALE: 3/8" = 1'-0"
1'-4"' 2'-8" 5'-4"' 0'
SCALE: 3/8" = 1'-0"
1'-4"' 2'-8" 5'-4"'
3/8" = 1'-0"FP101
3 FIRE RISER ROOM SECTION 2
0'
SCALE: 3/8" = 1'-0"
1'-4"' 2'-8" 5'-4"'
3/8" = 1'-0"FP101
4 FIRE RISER ROOM SECTION 3NOT TO SCALEFP101
5 JOCKEY PUMP DETAIL 3/8" = 1'-0"FP101
6 FDC DETAIL - REYNOLDS0'
SCALE: 3/8" = 1'-0"
1'-4"' 2'-8" 5'-4"'
N
12111 P.E.
KOPPDANIEL J.
OIS
S
EF
OR
P
RE
ENI
GNELA
ANAMONT
REG I STERDE
~
/ / / / / / / / / //
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
//
///////////////////
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
//
/ / / / / / / /
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~~~~~~~~
~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
RE
VIS
ION
S
23
/20/2
013
AD
DE
ND
UM
#2
H
G
F
E
D
B
A
1 2 9 10 11
C
3 5 6 7 84
IH
G
F
E
D
B
A
1 2 3 5 6 7 8 9 10 11
C
4
I
EMPLOYEEBREAKROOM
131
CONFERENCEROOM
130
GROCERYFREEZER
127
DAIRY DELICOOLER
128
DOCK
124
MEATFREEZER
122OFFICE
123
MEATCOOLER
121
MEAT CUT &WRAP ROOM
119
PRODUCECOOLER
117
PRODUCEWORK AREA
116
BAKERYPRODUCTION
114
BAKERYDISPLAY
AREA
115
BAKERYFREEZER
112
BAKERYCOOLER
113
SERVICEDELI COOLER
110
PRODUCE
109
DELI
107
NEW DELIFREEZER
108
INTERIORSEATING
106CHECKOUT
135
EXIT/ENTRY
101CART
STORAGE
102
EXTERIORSEATING
146
GUESTSERVICE
144
CASH COUNT
145
BOOKEEPINGOFFICE
143
SCANNINGOFFICE
142
MANAGEROFFICE
141
DEPT.MANAGERS
140DATA
139
JANITOR
138
MEN'S
137
WOMEN'S
136
NEW BEERCAVE
133
GENERALSALES
134
FROZEN
132
DAIRY
129
FLORAL
103
FLORALCOOLER
104
MEAT
118
DOCK
124
RISER
125
OH2
OH2
OH2
OH2
OH2LH
OH2
OH2
OH2
OH2
LH LH
LH LHLH LH
LH
LH LH
LH
LH
LHOH2
OH2
OH2
OH2
LH
OH2OH
2
OH2
OH1
126
TOILET
MEAT DEPT.OFFICE
120
LH
OH2
2
FP201
OH2
S-1
F/C
F/C
F/C
10
10 F/C 10
6
9
8
F/C 10
9
F/C 10
F/C 10
F/C 10
F/C 10
56
FP101
2
FP101
10 10
10
10
1010
10
DOCK
1247
10
8
8
8
8
8
4"
F
4" F
4"
F
4" F
4"
F
1 1/2" F
1 1/2" F
1 1/2" F
1 1/2" F
1 1/2" F
1 1/2" F
4"
F
4" F
1 1/4" F
1 1/4" F
1 1/4" F
9
1
G
F
S-1 S-1
7
2
3
4
12
12 12 12
4"
F
99
6
9
11
13
14
2
2
2
2
3
FP201
OH2
6
7
2
2
EXTERIORSTORAGE
147
15 15 15
15
15
15
SYMBOL HAZARD DES. DENSITY-GPM/SF
LIGHT 0.10
ORDINARYGROUP 1
0.15
NOTE:
0.20ORDINARYGROUP 2
0.00NO AUTOMATICSPRINKLERS
HAZARD SYMBOLS AT ROOM NAMES INDICATE NEWSPRINKLER AND PIPE AS REQUIRED FOR THESE AREAS.
HAZARD CLASSIFICATION SCHEDULE
LH
OH1
OH2
NAS
0.30FREEZER/COOLER
0.37RACK STORAGES-1
F/C
Commodity: Rack storage of class IV commodity & Randomlydisperse 10 pallet loads of higher commodity.
Storage Height on racks: 17-0” max
NFPA 13 Figure 16.2.1.3.2(d), curve E & apply figure 16.2.1.3.4.1:0.37 gpm over 2000 sf, 500 gpm outside hose allowance.
Use K8 or greater & 100 sf/sprinkler max.
Commodity: Group A Plastics
Ceiling Height: 10’-0”
Storage Height on Racks, Shelves, and Piles : 8’-0”
Maximum ceiling height allowed: 15’-0” with limits (5’-0” above top of storagemaximum).
Reinforced & Unreinforced plastic pallets.
NFPA 13 Figure17.2.1.2(a), 0.3 gpm over 2000 sf, 500 gpm outside hoseallowance.
NFPA 13 Section 15.2.6 allows rack storage protection schemes to protectpalletized, solid piled, bin-box, and shelf storage.
Use K8 or greater & 100 sf/sprinkler maximum. Coordinate installation withelectrical contractor.
OH2 (GENERAL SALES): MISCELLANEOUS STORAGE OF CLASS IVCOMMODITIES ON SHELVES LESS THAN OR EQUAL TO 10'-0". SEENFPA 13 14.2.3 AND TABLE 13.2.1.
2
1/FP200 NOTES#
1. 8" FIRE SERVICE TO WITHIN 5'-0" OF BUILDING BY OTHERS. SEE SITEUTILITY PLAN.
2. 8" TRANSITION COUPLING.3. 8" CLASS 52 CEMENT LINED DUCTILE IRON FIRE SERVICE UNDER
BUILDING FOOTING AND THROUGH FLOOR SLAB. SEE DETAIL 2/FP101.4. FIRE SERVICE ENTRANCE AND RISER. SEE DETAIL 1 &2/FP101.5. FDC AND HORN/STROBE ASSEMBLY. SEE DETAIL 7/FP1016. PROTECTION WITH EXTENDED COVERAGE DRY SIDEWALL
SPRINKLERS.7. TYPICAL CROSS MAIN AND BRANCH LINE LAYOUT.8. REQUIRED DESIGN AREAS.9. EXTEND S-1 HAZARD CLASS 15'-0" FROM STORAGE.10. AREA ABOVE LOW CEILING IS LIGHT HAZARD.11. IT IS THE RESPONSIBILITY OF THE OWNER TO ENSURE THAT THE
TEMPERATURE REMAINS ABOVE 40° F IN THE EXIT/ENTRY VESTIBULE.12. HIGH TEMPERATURE SPRINKLER HEADS ARE TO BE USED IN S-1 AREAS
AND ADJACENT PORTIONS OF THE BUILDING WHICH ARE OPEN TO S-1AREAS.
13. ROUTE FDC TO RISER ROOM.14. PROVIDE INDICATING VALVE WITH TAMPER SWITCH TO ISOLATE
SPRINKLER PIPING SERVING INFORMATION TECHNOLOGY EQUIPMENTAREAS PER NFPA 13, 21.15.
15. PROTECT UNDER SOFFITS HOUSING DISPLAY COOLERS AND RACKS.
2
2
4"-
6"
SPRINKLERCROSS MAIN
SPRINKLERBRANCHLINE
OVERHEADGARAGEDOOR
UPRIGHT SPRINKLERABOVE GARAGE DOOR
SIDEWALL SPRINKLERBELOW GARAGE DOOR
GARAGE DOORTRACK SUPPORT
GARAGEDOOR TRACK
SPRINKLER DRAIN
R
SHEET
CHECKED BY:
CTA #
DATE:
DRAWN BY:
COPYRIGHT 2013
CTA, INC.ALL RIGHTS RESERVED
SID
NE
Y,
MO
NT
AN
A\\ys0
30
\Use
rs_F
old
ers
\will
s\D
ocum
en
ts\R
evit20
12
\RE
YN
OLD
S_
FO
X\R
ED
SM
EP
_w
ills.r
vt
FP200
FIREPROTECTIONFIRST FLOOR
PLAN
100%
CO
NS
TR
UC
TIO
ND
OC
UM
EN
TS
RE
YN
OL
D'S
MA
RK
ET
AT
FO
X R
UN
WS
DH/DK
REYNOLDS
03/0113
3/32" = 1'-0"FP200
1 FIRE PROTECTION FIRST FLOOR PLAN 0'
3/32" = 1'-0"
5'-4" 10'-8" 21'-4"
PLANNORTH
TRUENORTH
N
12111 P.E.
KOPPDANIEL J.
OIS
S
EF
OR
P
RE
ENI
GNELA
ANAMONT
REG I STER
DE
~
/ / / / / / / / / //
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
//
///////////////////
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
//
/ / / / / / / /
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~~~~~~~~
~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
NOT TO SCALEFP200
2 TYPICAL SPRINKLER AT OVERHEAD DOOR
RE
VIS
ION
S
23
/20/2
013
AD
DE
ND
UM
#2
D
C
3 5 6 74
D
3 5 6 7
C
4
201
MEZZANINE
OH2
FIRST FLOOR100' - 0"
MEZZANINE114' - 0"
A
T.O. MASONRY124' - 0"
H G F E D B ACI
OH2
OH2
LH
OH2
124
DOCK
201
MEZZANINE
134
GENERAL SALES
135
CHECKOUT
OH2
118
MEAT
OH2
121
MEAT COOLER
F/C S-1
BOOKEEPINGOFFICE
143
G F
SYMBOL HAZARD DES. DENSITY-GPM/SF
LIGHT 0.10
ORDINARYGROUP 1
0.15
NOTE:
0.20ORDINARYGROUP 2
0.00NO AUTOMATICSPRINKLERS
HAZARD SYMBOLS AT ROOM NAMES INDICATE NEWSPRINKLER AND PIPE AS REQUIRED FOR THESE AREAS.
HAZARD CLASSIFICATION SCHEDULE
LH
OH1
OH2
NAS
0.30FREEZER/COOLER
0.37RACK STORAGES-1
F/C
Commodity: Rack storage of class IV commodity & Randomlydisperse 10 pallet loads of higher commodity.
Storage Height on racks: 17-0” max
NFPA 13 Figure 16.2.1.3.2(d), curve E & apply figure 16.2.1.3.4.1:0.37 gpm over 2000 sf, 500 gpm outside hose allowance.
Use K8 or greater & 100 sf/sprinkler max.
Commodity: Group A Plastics
Ceiling Height: 10’-0”
Storage Height on Racks, Shelves, and Piles : 8’-0”
Maximum ceiling height allowed: 15’-0” with limits (5’-0” above top of storagemaximum).
Reinforced & Unreinforced plastic pallets.
NFPA 13 Figure17.2.1.2(a), 0.3 gpm over 2000 sf, 500 gpm outside hoseallowance.
NFPA 13 Section 15.2.6 allows rack storage protection schemes to protectpalletized, solid piled, bin-box, and shelf storage.
Use K8 or greater & 100 sf/sprinkler maximum. Coordinate installation withelectrical contractor.
OH2 (GENERAL SALES): MISCELLANEOUS STORAGE OF CLASS IVCOMMODITIES ON SHELVES LESS THAN OR EQUAL TO 10'-0". SEENFPA 13 14.2.3 AND TABLE 13.2.1.
2
FIRST FLOOR100' - 0"
MEZZANINE114' - 0"
HG I
101
EXIT/ENTRY
135
CHECKOUT
NAS
LHLH
LH
1
2
1
2
3/FP201 NOTES#
1. IT IS THE RESPONSIBILITY OF THE OWNER TO ENSURE THAT THETEMPERATURE REMAINS ABOVE 40° F IN THE EXIT/ENTRY VESTIBULE.
2. LIMITED-ACCESS LIMITED- OR NON-COMBUSTIBLE CONCEALEDSPACE. SPRINKLERS NOT REQUIRED PER NFPA 13 8.15.1.2.2.
2
R
SHEET
CHECKED BY:
CTA #
DATE:
DRAWN BY:
COPYRIGHT 2013
CTA, INC.ALL RIGHTS RESERVED
SID
NE
Y,
MO
NT
AN
A\\ys0
30
\Use
rs_F
old
ers
\will
s\D
ocum
en
ts\R
evit20
12
\RE
YN
OLD
S_
FO
X\R
ED
SM
EP
_w
ills.r
vt
FP201
FIREPROTECTIONMEZZANINE
AND SECTION
100%
CO
NS
TR
UC
TIO
ND
OC
UM
EN
TS
RE
YN
OL
D'S
MA
RK
ET
AT
FO
X R
UN
WS
DH/DK
REYNOLDS
03/0113
1/8" = 1'-0"FP201
1 FIRE PROTECTION PLAN - MEZZANINE
3/32" = 1'-0"FP201
2 FIRE PROTECTION SECTION
0'
1/8" = 1'-0"
4' 8' 16'
0'
3/32" = 1'-0"
5'-4" 10'-8" 21'-4"
N
12111 P.E.
KOPPDANIEL J.
OIS
S
EF
OR
P
RE
ENI
GNELA
ANAMONT
REG I STERDE
~
/ / / / / / / / // /
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
///////////////////
///
//
//
//
//
/
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
//
/
//
//
//
//
//
//
//
// /
/ / / / / / /
~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~~~~~~~
~~~
~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
~~~~~~~~~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~ ~
RE
VIS
ION
S
23
/20/2
013
AD
DE
ND
UM
#2
3/32" = 1'-0"FP201
3 EXIT/ENTRY 101 SECTION 0'
3/32" = 1'-0"
5'-4" 10'-8" 21'-4"