Rev: 6 Apr 18 - Unifrax · 2018. 8. 7. · or located in close proximity to other building...
Transcript of Rev: 6 Apr 18 - Unifrax · 2018. 8. 7. · or located in close proximity to other building...
FyreWrap® Elite® 1.5 - Duct Insulation
FyreWrap® Elite® 1.5 Duct insulation from Unifrax is a flexible insulation wrap
designed for creating fire protection enclosures for building ductwork
systems.
Thin, lightweight and easy to install, FyreWrap Elite 1.5 systems offer
significant savings in installation time and overall system weight. The flexible
product form facilitates efficient installation where access to the duct is limited
or located in close proximity to other building services.
FyreWrap Elite has been tested and approved for use in a number of different
countries and approvals cover a range of duct types including HVAC,
pressurisation and kitchen extraction systems. Approvals include ASTM, BS,
ISO, EN and AS.
PRODUCT COMPONENTS
Core Material: Insulfrax Low Bio-persistence wool. Totally inorganic and
exonerated from classification under Nota Q of EU Directive 97/69/EC.
Encapsulation Scrim: Full encapsulation with an aluminium foil/glass fibre
reinforced aluminised polyester scrim. The scrim provides additional handling
strength in addition to providing protection against moisture absorption.
TYPICAL PRODUCT PARAMETERS
Thickness 38mm (1.5 inches)
Nominal Density 96kg/m³ (6pcf)
EN13501-1 Non-combustibility A1
EN 1608 Parallel Tensile Strength 180 kPa
EN 826 Compressive Stress (at 10%) 2.4 kPa
EN 12667 Thermal Resistance (at 10°C) R-Value 1.14
ASTM D6329-03 Microbial Resistance Resistant to mould growth
DESCRIPTION
Fire Protection with Integrity and Trust
Contact your local sales office Unifrax Ltd.
T:+44 (0)1744 88 7600 www.unifrax.com
U-714 EN Rev: 6 Apr 18 Page 1 of 2
EN 1366 listings
Supplied by:
FyreWrap® Elite® 1.5 - Duct Insulation
SYSTEM APPROVALS AVAILABILITY
HANDLING INFORMATION
A Material Safety Data Sheet has been issued
describing the health, safety and environmental
properties of this product, identifying the
potential hazards and giving advice on handling
precautions and emergency procedures. This
must be consulted and fully understood before
handling, storage or use.
Information contained in this publication is for illustrative purposes only and is not intended to create any contractual obligation. Further information and advice on specific details of the products described should be obtained in writing from a Unifrax Corporation company
(Unifrax España, Unifrax France, Unifrax GmbH, Unifrax Italia, Unifrax Limited, Unifrax s.r.o.). Unifrax maintains a continuous programme of product development and reserves the right to change product specifications without prior notice. Therefore, it maintains at all times the respon-
sibility of the customer to ensure that Unifrax materials are suitable for the particular purpose intended. Similarly, insofar as materials not manufactured nor supplied by Unifrax are used in conjunction with or instead of Unifrax materials, the customer should ensure that all technical data
and other information relating to such materials has been obtained from the manufacturer or supplier. Unifrax accepts no liability arising from the use of such materials. All sales made by a Unifrax Corporation company are subject to that company's Terms and Conditions of Sale, copies
of which are available on request.
U-714 EN Rev: 6 Apr 18 Page 2 of 2
EN 1366-1 Integrity Insulation Smoke Leakage No. of Layers Classification to EN13501-3
Rectangular Type A: Vertical 120mins 120mins 120mins 2 EI 120 (ve-ho o→i) S
Rectangular Type A: Horizontal 120mins 120mins 120mins 2 EI 120 (ve-ho o→i) S
Rectangular Type B: Vertical 120mins 90mins - 2 EI 90 (ve i→o )
Rectangular Type B: Horizontal 120mins 60mins - 2 EI 60 (ve-ho o↔i)
Round Type A: Vertical 120mins 120mins 120mins 2 EI 120 (ve o→i) S
Round Type A: Horizontal 90mins 120mins 90mins 2 EI 90 (ho o→i) S
Round Type B: Vertical 90mins 60mins - 2 EI 60 (ve-ho o↔i)
Round Type B: Horizontal 120mins 60mins - 2 EI 60 (ve-ho o↔i)
EN 1366-1 (Kitchen Extract) Insulation for combustible internal lining No. of Layers
Rectangular Kitchen Extract 30mins 1
Rectangular Kitchen Extract 2 60mins
Round Kitchen Extract 45mins 2
EN 1366-8 (Smoke Extract) Integrity Insulation Smoke Leakage No. of Layers Classification to EN13501-4
Rectangular Type C: Vertical 120mins 90mins n/a 2 EI 90 (ve) S1500multi
Rectangular Type C: Horizontal 90mins 60mins 120mins 2 EI 60 (ve-ho) S1500multi
Round Type C: Vertical 120mins 60mins n/a 2 EI 60 (ve-ho) S1500multi
Round Type C: Horizontal 120mins 60mins 120mins 2 EI 60 (ve-ho) S1500multi
Thickness Width Length
38mm 610mm 5.0m
38mm 1220mm 5.0m
38mm 610mm 7.62m
38mm 1220mm 7.62m
EN 1366 listings