CHAPTER12iapmo.org/UPC Report On Comments/2012 Uniform... ·...
Transcript of CHAPTER12iapmo.org/UPC Report On Comments/2012 Uniform... ·...
1201.0 Scope of Gas Piping.1201.1 (A) Coverage of Piping System. Coverageof piping systems shall extend from the point of deliv-ery to the appliance connections with each gas utiliza-tion device. For other than undiluted liquefied petroleumgas systems, the point of delivery shall be considered theoutlet of the service meter assembly, or the outlet of theservice regulator or service shutoff valve where no meteris provided. For undiluted liquefied petroleum gas sys-tems, the point of delivery shall be considered the outletof the final pressure regulator, exclusive of the line gas reg-ulators, in the system where no meter is installed. Wherea meter is installed the point of delivery shall be the out-let of the meter. [NFPA54-12:1.1.1.1(A)]1201.2 (B) Piping System Requirements. Pipingsystems requirements shall include design, materials,components, fabrications, assembly, installation, testing,inspection, operation, and maintenance. [NFPA54:1.1.1.1(C)]1201.3 (C) Application. This code shall not apply tothe following (reference standards for some of which ap-pear in Chapter 14 [NFPA 54-12:1.1.1.2]:(1) Portable LP-Gas appliances of all types that are not
connected to a fixed fuel piping system.(2) Installation of farm appliances and equipment such
as brooders, dehydrators, dryers, and irrigationequipment used for agricultural purposes.
(3) Raw material (feedstock) applications, except forpiping to special atmosphere generators.
(4) Oxygen-fuel gas cutting and welding systems.(5) Industrial gas applications using gases such as acety-
lene and acetylenic compounds, hydrogen, ammo-nia, carbon monoxide, oxygen, and nitrogen.
(6) Petroleum refineries, pipeline compressor or pump-ing stations, loading terminals, compounding plants,refinery tank farms, and natural gas processingplants.
(7) Large integrated chemical plants or portions of suchplants where flammable or combustible liquids orgases are produced by chemical reactions or used inchemical reactions.
(8) LP-Gas installations at utility gas plants.(9) Liquefied natural gas (LNG) installations.(10)Fuel gas piping in electric utility power plants.
[NFPA 54-09:1.1.1.2(10)](11) Proprietary items of equipment, apparatus, or in-
struments such as gas-generating sets, compressors,and calorimeters.
(12) LP-Gas appliances for vaporization, gas mixing, andgas manufacturing.
(13) LP-Gas piping for buildings under construction orrenovations that are not to become part of the per-manent building piping system—that is, temporaryfixed piping for building heat.
(14) Installation of LP-Gas systems for railroad switchheating.
(15) Installation of LP-Gas and compressed natural gassystems on vehicles.
(16) Gas piping, meters, gas-pressure regulators, and otherappurtenances used by the serving gas supplier in dis-tribution of gas, other than undiluted LP-Gas.
1202.0 General.The regulations of this chapter shall govern the installationof fuel gas piping in or in connection with any a building,structure or within the property lines of any premises up tofive (5) psi (34.5 kPa), other than service pipe. Fuel oil pip-ing systems shall be installed in accordance with NFPA 31.
1203.0 Definitions.For the purposes of this code, these definitions shall apply tothis chapter. Certain terms, phrases, words, and their deriva-tives shall be interpreted as set forth in this section, provided,however, that whenever the words “gas meters” appear, theyshall be construed to also mean valves and those devices re-quired for the regulation of pressure and the measurement ofnatural gas being dispensed for any building, structure, orpremises.1203.1 Appliance Fuel Connector – An assembly oflisted semi-rigid or flexible tubing and fittings to carry fuelbetween a fuel-piping outlet and a fuel-burning appliance.1203.2 Bonding Jumper –A reliable conductor to ensurethe required electrical conductivity between metal parts re-quired to be electrically connected. [NFPA 70:100.1]1203.3 Fuel Gas – Natural, manufactured, liquefied petro-leum, or a mixture of these.1203.4 Gas Piping – Any installation of pipe, valves, orfittings that is used to convey fuel gas, installed on any prem-ises or in any building, but shall not include:(1) Any portion of the service piping.(2) Any approved piping connection six (6) feet (1,829 mm)
or less in length between an existing gas outlet and a gasappliance in the same room with the outlet.
1203.5 Gas-Piping System –Any arrangement of gas pip-ing or regulators after the point of delivery and each arrange-ment of gas piping serving a building, structure, or premises,whether individually metered or not.1203.6 Grounding Electrode – A device that establishesan electrical connection to the earth.
CHAPTER 12FUEL PIPING
UNIFORM PLUMBING CODE 171
UNIFORM PLUMBING CODE172
1203.7 Liquefied Petroleum Gas (LPG) Facilities –Liquefied petroleum gas (LPG) facilities means tanks, con-tainers, container valves, regulating equipment, meters,and/or appurtenances for the storage and supply of liquefiedpetroleum gas for any building, structure, or premises.1203.8 Provision for Location of Point of Delivery –The location of the point of delivery shall be acceptable tothe serving gas supplier. [NFPA 54:5.2]1203.9 Quick-Disconnect Device –Ahand-operated de-vice that provides a means for connecting and disconnectingan appliance or an appliance connector to a gas supply andthat is equipped with an automatic means to shut off the gassupply when the device is disconnected.1203.10 Service Piping – The piping and equipment be-tween the street gas main and the gas piping system inlet thatis installed by, and is under the control and maintenance of,the serving gas supplier.1203.11 Transition Gas Riser – Any listed or approvedsection or sections of pipe and fittings used to convey fuelgas and installed in a gas piping system for the purpose ofproviding a transition from below ground to above ground.
12043.0 Inspection.12043.1 Inspection Notification.Upon completion of theinstallation, alteration, or repair of any gas piping, and priorto the use thereof, the Authority Having Jurisdiction shall benotified that such gas piping is ready for inspection.12043.2 Excavation. All eExcavations required for the in-stallation of underground piping shall be kept open until suchtime as the piping has been inspected and approved. If anyWhere such piping is covered or concealed before such ap-proval, it shall be exposed upon the direction of the Author-ity Having Jurisdiction.12043.3 Type of Inspections. The Authority Having Ju-risdiction shall make the following inspections and eithershall approve that portion of the work as completed or shallnotify the permit holder wherein the same fails to comply bein accordance with this code.
12043.3.1 Rough Piping Inspection. This inspec-tion shall be made after all gas piping authorized by thepermit has been installed and before any such piping hasbeen covered or concealed or any fixture or appliancehas been attached thereto. This inspection shall include adetermination that the gas-piping size, material, and in-stallation meet the requirements of this code.12043.3.2 Final Piping Inspection. This inspectionshall be made after all piping authorized by the permithas been installed and after all portions thereof that are tobe covered or concealed are so concealed and before anyfixtures, appliance, or shutoff valve has been attachedthereto. This inspection shall be in accordance with Sec-tion 12143.1. Test gauges used in conducting tests shallcomply be in accordance with Section 319.0, TestGauges.
12043.4 Inspection Waived In cases where the work au-thorized by the permit consists of a minor installation of ad-ditional piping to piping already connected to a gas meter, the
foregoing inspections shall be permitted to be waived at thediscretion of theAuthority Having Jurisdiction. In this event,theAuthority Having Jurisdiction shall make such inspectionas deemed advisable in order to be assured that the work hasbeen performed in accordance with the intent of this code.
12054.0 Certificate of Inspection.12054.1 Issuance. If, Where upon final piping inspection,the installation is found to comply be in accordance with theprovisions of this code, a certificate of inspection shall be per-mitted to be issued by the Authority Having Jurisdiction.12054.2 Gas Supplier. A copy of the certificate of suchfinal piping inspection shall be issued to the serving gas sup-plier supplying gas to the premises.12054.3 Unlawful. It shall be unlawful for any a servinggas supplier, or person furnishing gas, to turn on or cause tobe turned on, any a fuel gas or any a gas meter or meters, untilsuch certificate of final inspection, as herein provided, hasbeen issued.
12065.0 Authority to Render Gas Service.12065.1 Authorized Personnel. It shall be unlawful forany a person, firm, or corporation, excepting an authorizedagent or employee of a person, firm, or corporation engagedin the business of furnishing or supplying gas and whose serv-ice pipes supply or connect with the particular premises, toturn on or reconnect gas service in or on any a premises whereand when gas service is, at the time, not being rendered.12065.2 Outlets. It shall be unlawful to turn on or connectgas in or on any a premises unless all outlets are properly andsecurely connected to gas appliances or capped or pluggedwith screw joint fittings.
12076.0 Authority to Disconnect.12076.1 Disconnection. The Authority Having Jurisdic-tion or the serving gas supplier is hereby authorized to dis-connect any gas piping or appliance or both that shall befound not to conform to comply the requirements of this codeor that are found defective and in such condition as to en-danger life or property.12076.2 Notice.Where such disconnection has been made,a notice shall be attached to such gas piping or appliance orboth that shall state the same has been disconnected, togetherwith the reasons thereof.12076.3 Capped Outlets. It shall be unlawful to removeor disconnect any gas piping or gas appliance without cap-ping or plugging with a screw joint fitting, the outlet fromwhich said pipe or appliance was removed. Outlets to whichgas appliances are not connected shall be left capped, gas-tight on any a piping system that has been installed, altered,or repaired.Exception: When Where an approved listed quick- discon-nect device is used.
FUEL PIPING
12087.0 Temporary Use of Gas.1207.1 General.Where temporary use of gas is desired andtheAuthority Having Jurisdiction deems the use necessary, apermit shall be permitted to be issued for such use for a pe-riod of time not to exceed that designated by the AuthorityHaving Jurisdiction, provided that such gas-piping systemotherwise conforms to is in accordance with the requirementsof this code regarding material, sizing, and safety.
12098.0 Gas-Piping System Design, Materials, andComponents.12098.1 Piping Plan.
12098.1.1 Installation of Piping System. Whererequired by the Authority Having Jurisdiction, a pipingsketch or plan shall be prepared before proceeding withthe installation. This plan shall show the proposed loca-tion of piping, the size of different branches, the variousload demands, and the location of the point of delivery.[NFPA 54:5.1.1]12098.1.2 Addition to Existing System. WhenWhere an additional gas utilization appliance is being con-nected to a gas-piping system, the existing piping shall bechecked to determine whether it has adequate capacity (seeSection 1209.4.3). If Where inadequate, the existing sys-tem shall be enlarged as required, or separate gas piping ofadequate capacity shall be provided. [NFPA 54:5.1.2]
12098.2 Provision for Location of Point of Delivery.The location of the point of delivery shall be acceptable tothe serving gas supplier. [NFPA 54:5.2]12098.3 Interconnections Between Gas-Piping Sys-tems. [NFPA 54:5.3]
12098.3.1 Interconnections Supplying SeparateUsers.Where two (2) or more meters, or two (2) or moreservice regulators where meters are not provided, are lo-cated on the same premises and supply separate users, thegas-piping systems shall not be interconnected on the out-let side of themeters or service regulators. [NFPA54:5.3.1]12098.3.2 Interconnections for Standby Fuels.Where a supplementary gas for standby use is connecteddownstream from a meter or a service regulator where ameter is not provided, a device to prevent backflow shallbe installed. A three-way valve installed to admit thestandby supply and, at the same time, shut off the regu-lar supply, shall be permitted to be used for this purpose.[NFPA 54:5.3.2]
12098.4 Sizing of Gas-Piping Systems. [NFPA 54:5.4]12098.4.1 General Considerations. Gas-piping sys-tems shall be of such size and so installed as to providea supply of gas sufficient to meet the maximum demandand supply gas to each appliance inlet at not less than theminimum supply pressure required by the appliance.[NFPA 54-09:5.4.1]12098.4.2 MaximumGas Demand. The volume vol-umetric flow rate of gas to be provided (in cubic feet perhour) shall be determined directly from calculated usingthe manufacturer's input ratings of the gas utilization ap-pliance served. Where the input rating is not indicated,
the gas supplier, appliance manufacturer, or a qualifiedagency shall be contacted or the rating from Table 12-11208.4.2 shall be used for estimating the volume volu-metric flow rate of gas to be supplied. The total con-nected hourly load shall be used as the basis for pipingsizing, assuming the appliance is operating at full capac-ity simultaneously. [NFPA 54-12:5.4.2]Exception: Sizing shall be permitted to be based uponestablished load diversity factors. [NFPA 54:5.4.2.2]
UNIFORM PLUMBING CODE 173
FUEL PIPING
APPLIANCEINPUT Btu/h.(Approx.)
Space Heating UnitsWarm air furnaceSingle familyMultifamily, per unitHydronic boilerSingle familyMultifamily, per unit
100,00060,000
100,00060,000
Space-and Water-Heating UnitsHydronic boilerSingle familyMultifamily, per unit
120,00075,000
Water-Heating AppliancesWater heater, automatic storage30 to 40 gal. tankWater heater, automatic storage50 gal. tankWater heater, automatic instantaneousCapacity at 2 gal./minuteCapacity at 4 gal./minuteCapacity at 6 gal./minuteWater heater, domestic, circulating orside-arm
35,000
50,000
142,800285,000428,400
35,000Cooking AppliancesRange, freestanding, domesticBuilt-in oven or broiler unit, domesticBuilt-in top unit, domestic
65,00025,00040,000
OtherAppliancesRefrigeratorClothes dryer, Type 1 (domestic)Gas fireplace direct ventGas logBarbecueGaslight
3,00035,00040,00080,00040,0002,500
TABLE 12-1 1208.4.2APPROXIMATE GAS INPUT FOR
TYPICAL APPLIANCES[NFPA 54: TABLE 5.4.2.1]
For SI units: 1 Btu 1000 British thermal units per hour = 0.293 kW
UNIFORM PLUMBING CODE174
12098.4.3 Sizing Methods.Gas piping shall be sizedin accordance with one of the following :(1) Pipe sizing tables or sizing equations in this chap-
ter.(2) Other approved engineering methods acceptable to
the Authority Having Jurisdiction.(3) Sizing tables included in a listed piping system man-
ufacturer's installation instructions. [NFPA54:5.4.3]12098.4.4 Allowable Pressure Drop. The designpressure loss in any a piping system under maximumprobable flow conditions, from the point of delivery tothe inlet connection of the appliance, shall be such thatthe supply pressure at the appliance exceeds is greaterthan or is equal to the minimum pressure required by theappliance. [NFPA 54-09:5.4.4]
12098.5 Acceptable Piping Materials and JoiningMethods.
12098.5.1 General.12098.5.1.1 Acceptable Materials. Materialsused for piping systems shall comply with the re-quirements of this chapter or shall be acceptable tothe Authority Having Jurisdiction. [NFPA54:5.6.1.1]12098.5.1.2 Used Materials. Pipe, fittings,valves, or other materials shall not be used again un-less they are free of foreign materials and have beenascertained to be adequate approved for the serviceintended. [NFPA 54:5.6.1.2]12098.5.1.3 Other Materials. Material not cov-ered by the standards specifications listed hereinshall be investigated and tested to determine that itis safe and suitable for the proposed service and, inaddition, shall be recommended for that service bythe manufacturer and shall be acceptable to the Au-thority Having Jurisdiction. [NFPA 54:5.6.1.3]
12098.5.2 Metallic Pipe.12098.5.2.1 Cast-Iron. Cast-iron pipe shall not beused. [NFPA 54:5.6.2.1]12098.5.2.2 Steel and Wrought-Iron. Steel andwrought-iron pipe shall be not less than standardweight (Schedule 40) and shall comply with one ofthe following standards(1) ASME B36.10,Welded and Seamless Wrought-
Steel Pipe.(2) ASTM A 53, Standard Specification for Pipe,
Steel, Black and Hot-Dipped, Zinc-CoatedWelded and Seamless.
(3) ASTMA106, Standard Specification for Seam-less Carbon Steel Pipe for High-TemperatureService [NFPA 54:5.6.2.2]:.
12098.5.2.3 Copper and Brass. Copper andbrass pipe shall not be used if the gas contains morethan an average of 0.3 grains of hydrogen sulfide perone-hundred (100) standard cubic feet (scf) of gas(0.7 mg/100 L). [NFPA 54:5.6.2.3]
Threaded copper, brass, or aluminum alloy pipeshall not be used with gases corrosive to such mate-rial. [NFPA 54:5.6.2.4]12098.5.2.4 Aluminum Alloy. Aluminum alloypipe shall comply with ASTM B 241, StandardSpecification for Aluminum-Alloy Seamless Pipeand Seamless Extruded Tube (except that the use ofalloy 5456 is prohibited) and shall be marked at eachend of each length indicating compliance. Alu-minum alloy pipe shall be coated to protect againstexternal corrosion where it is in contact with ma-sonry, plaster, insulation or is subject to repeatedwettings by such liquids as water, detergents, orsewage. [NFPA 54:5.6.2.5] Aluminum alloy pipeshall not be used in exterior locations or under-ground. [NFPA 54:5.6.2.6]
12098.5.3 Metallic Tubing. Seamless copper, alu-minum alloy, or steel tubing shall not be used with gasescorrosive to such material. [NFPA 54:5.6.3]
12098.5.3.1 Steel. Steel tubing shall comply withASTM A 254, Standard Specification for CopperBrazed Steel Tubing. [NFPA 54-09:5.6.3.1]12098.5.3.2 Copper and Brass. Copper andbrass tubing shall not be used if where the gas con-tains more than an average of 0.3 grains of hydrogensulfide per one-hundred (100) scf of gas (0.7 mg/100L). Copper tubing shall comply with standard TypeK or L of ASTM B 88, Standard Specification forSeamless Copper Water Tube, or ASTM B 280,Specification for Seamless Copper Tube for Air-Conditioning and Refrigeration Field Service.[NFPA 54:5.6.3.2]12098.5.3.3 Aluminum Alloy. Aluminum alloytubing shall comply with ASTM B 210, StandardSpecification for Aluminum-Alloy Drawn SeamlessTubes, or ASTM B 241, Standard Specification forAluminum Alloy Seamless Pipe and Seamless Ex-truded Tube.Aluminum alloy tubing shall be coated toprotect against external corrosionwhere it is in contactwith masonry, plaster, insulation or is subject to re-peated wettings by liquids such as water, detergent, orsewage. Aluminum alloy tubing shall not be used inexterior locations or underground. [NFPA54:5.6.3.3]12098.5.3.4 Corrugated Stainless Steel. Cor-rugated stainless steel tubing shall be tested andlisted in compliance accordance with the construc-tion, installation, and performance requirements ofCSA LC-1, Standard for Fuel Gas Piping SystemsUsing Corrugated Stainless Steel Tubing. [NFPA54:5.6.3.4]
12098.5.4 Plastic Pipe, Tubing, and Fittings. Plas-tic pipe, tubing, and fittings used to supply fuel gas shallconform be in accordance withASTMD 2513, StandardSpecification for Thermoplastic Gas Pressure Pipe, Tub-ing, and Fittings. Pipe to be used shall be marked "gas"and "ASTM D 2513.” [NFPA 54:5.6.4.1]
Anodeless risers shall comply with the followingsections. [NFPA 54:5.6.4.3]:
FUEL PIPING
12098.5.4.1 Regulator Vent Piping. Plasticpipe, tubing, and fittings used to connect regulatorvents to remote vent terminations shall be PVC con-forming to in accordance withANSI/UL 651, Sched-ule 40 and 80 Rigid PVC Conduit and Fittings. PVCvent piping shall not be installed indoors. [NFPA54-1209:5.6.4.2]12098.5.4.2 Factory-Assembled AnodelessRisers. Factory-assembled anodeless risers shall berecommended by the manufacturer for the gas usedand shall be leak-tested by the manufacturer in ac-cordance with written procedures. [NFPA54:5.6.4.3(1)]12098.5.4.3 Service Head Adapters andField-Assembled Anodeless Risers. Servicehead adapters and field-assembled anodeless risersincorporating service head adapters shall be recom-mended by the manufacturer for the gas used by themanufacturer and shall be design-certified to meetbe in accordance with the requirements of CategoryI of ASTM D 2513, Standard Specification for Ther-mostatic Gas Pressure Pipe, Tubing, and Fittings andthe code of Federal Regulations, Title 49, Part192.281(e). The manufacturer shall provide the userwith qualified installation instructions. as prescribedby the code of Federal Regulations, Title 49, Part192.283(b). [NFPA 54:5.6.4.3(2)]12098.5.4.4 Undiluted Liquefied PetroleumGas Piping. The use of plastic pipe, tubing, and fit-tings in undiluted liquefied petroleum gas-piping sys-tems shall be in accordance comply with NFPA 58,Liquefied Petroleum Gas Code. [NFPA54:5.6.4.3(3)]
12098.5.5 Workmanship and Defects. Gas pipe ortubing and fittings shall be clear and free from cuttingburrs and defects in structure or threading, and shall bethoroughly brushed and chip and scale blown. Defects inpipe, tubing, and fittings shall not be repaired. Defectivepipe, tubing, and fittings shall be replaced. [NFPA54:5.6.5]12098.5.6 Protective Coating.Where in contact withmaterial or atmosphere exerting a corrosive action,metallic piping and fittings coated with a corrosion-re-sistant material shall be used. External or internal coat-ings or linings used on piping or components shall notbe considered as adding strength. [NFPA 54:5.6.6]12098.5.7 Metallic Pipe Threads.
1208.5.7.1 (A) Specifications for PipeThreads.Metallic pipe and fitting threads shall betaper pipe threads and shall comply with ASMEB1.20.1, Standard for Pipe Threads, General Pur-pose (Inch). [NFPA 54:5.6.7.1]1208.5.7.2 (B) Damaged Threads. Pipe withthreads that are stripped, chipped, corroded, or oth-erwise damaged shall not be used. Where a weldopens during the operation of cutting or threading,that portion of the pipe shall not be used. [NFPA54:5.6.7.2]
1208.5.7.3 (C) Number of Threads. Fieldthreading of metallic pipe shall be in accordancecomply with Table 12-2 1208.5.7.3. [NFPA54:5.6.7.3]
1208.5.7.4 (D) Thread Joint Compounds.Thread (joint) compounds (pipe dope) shall be re-sistant to the action of liquefied petroleum gas or toany other chemical constituents of the gases to beconducted through the piping. [NFPA54-12:5.6.7.4]
12098.5.8 Metallic Piping Joints and Fittings. Thetype of piping joint used shall be suitable approved forthe pressure-temperature conditions and shall be selectedgiving consideration to joint tightness and mechanicalstrength under the service conditions. The joint shall beable to sustain the maximum end force due to the inter-nal pressure and any additional forces due to tempera-ture expansion or contraction, vibration, fatigue, or to theweight of the pipe and its contents. [NFPA 54:5.6.8]
12098.5.8.1 Pipe Joints. Pipe joints shall bethreaded, flanged, brazed, or welded. Where non-ferrous pipe is brazed, the brazing materials shallhave a melting point in excess of 1,000°F (538°C).Brazing alloys shall not contain more than 0.05 per-cent phosphorus. [NFPA 54:5.6.8.1]12098.5.8.2 Tubing Joints. Tubing joints shalleither be made with approved gas tubing fittings, bebrazed with a material having a melting point in ex-cess of 1,000°F (538°C), or made by press-connectfittings complying in accordance with CSA ANSILC-4. Brazing alloys shall not contain more than0.05 percent phosphorus. [NFPA 54:5.6.8.2]12098.5.8.3 Flared Joints. Flared joints shall beused only in systems constructed from nonferrouspipe and tubing where experience or tests havedemonstrated that the joint is suitable approved forthe conditions and where provisions are made in thedesign to prevent separation of the joints. [NFPA54:5.6.8.3]
UNIFORM PLUMBING CODE 175
FUEL PIPING
NOMINAL IRONPIPE SIZE(inches)
APPROXIMATE LENGTH OFTHREADED PORTION
(inches)APPROXIMATE NO. OFTHREADS TO BE CUT
1⁄2 3⁄4 103⁄4 3⁄4 101 7⁄8 1011⁄4 1 1111⁄2 1 112 1 1121⁄2 11⁄2 123 11⁄2 124 15⁄8 13
TABLE 12-2 1208.5.7.3SPECIFICATIONS FOR THREADING METALLIC PIPE
[NFPA 54: TABLE 5.6.7.3]
For SI units, 1 inch = 25.4 mm
UNIFORM PLUMBING CODE176
12098.5.8.4 Metallic Fittings (IncludingValves, Strainers, Filters).Metallic fittings shallcomply with the following:(1) Threaded fittings in sizes exceeding four (4)
inches (100 mm) shall not be used unless ac-ceptable to the Authority Having Jurisdiction.
(2) Fittings used with steel or wrought-iron pipeshall be steel, brass, bronze, malleable iron, orcast-iron.
(3) Fittings used with copper or brass pipe shall becopper, brass, or bronze.
(4) Fittings used with aluminum alloy pipe shall beof aluminum alloy.
(5) Cast-Iron Fittings.(a) Flanges shall be permitted.(b) Bushings shall not be used.(c) Fittings shall not be used in systems con-
taining flammable gas-air mixtures.(d) Fittings in sizes four (4) inches (100 mm)
and larger shall not be used indoors unlessapproved by the Authority Having Juris-diction.
(e) Fittings in sizes six (6) inches (150 mm)and larger shall not be used unless ap-proved by the Authority Having Jurisdic-tion.
(6) Aluminum Alloy Fittings. Threads shall notform the joint seal.
(7) Zinc-Aluminum Alloy Fittings. Fittings shallnot be used in systems containing flammablegas-air mixtures.
(8) Special Fittings. Fittings such as couplings; pro-prietary-type joints; saddle tees; gland-typecompression fittings; and flared, flareless, orcompression-type tubing fittings shall be:(1a) uUsed within the fitting manufacturers'
pressure-temperature recommendations;.(2b) uUsed within the service conditions antic-
ipated with respect to vibration, fatigue,thermal expansion, or contraction;.
(3c) iInstalled or braced to prevent separationof the joint by gas pressure or externalphysical damage;. and
(4d) aAcceptable to the Authority Having Ju-risdiction. [NFPA 54:5.6.8.4]
12098.5.9 Plastic Piping, Joints, and Fittings.Plastic pipe, tubing, and fittings shall be joined in accor-dance with the manufacturers' instructions. The follow-ing sections shall be observed when where making suchjoints. [NFPA 54:5.6.9]:
1208.5.9.1 Joint Design (A) The joint shall bedesigned and installed so that the longitudinal pull-out resistance of the joint shall be equal to the ten-sile strength of the plastic piping material. [NFPA54:5.6.9(1)]
1208.5.9.2 Heat-Fusion Joint (B) Heat-fusionjoints shall be made in accordance with AWS B2.4Specification for Welding Procedure and Perform-ance Qualification for Thermoplastics. Joints shallbe made with the joining method recommended bythe pipe manufacturer. Heat-fusion fittings shall bemarked "ASTM D 2513." [NFPA 54:5.6.9(2)]1208.5.9.3 Compression Type MechanicalJoints. (C) Where compression-type mechanicaljoints are used, the gasket material in the fitting shallbe compatible with the plastic piping and with thegas distributed by the system. An internal tubularrigid stiffener shall be used in conjunction with thefitting. The stiffener shall be flush with the end ofthe pipe or tubing, shall extend not less than the out-side end of the pipe or tubing and shall extend notless than to the outside end of the compression fit-ting when where installed. The stiffener shall be freeof rough or sharp edges and shall not be a forced fitin the plastic. Split tubular stiffeners shall not beused. [NFPA 54:5.6.9(3)]1208.5.9.4 (D) Liquefied Petroleum Gas Pip-ing Systems. Plastic piping joints and fittings foruse in liquefied petroleum gas-piping systems shallbe in accordance with NFPA 58, Liquefied Petro-leum Gas Code. [NFPA 54:5.6.9(4)]
12098.5.10 Flanges. Flanges shall comply withASME B16.1, Standard for Cast-Iron Pipe Flanges andFlanged Fittings; ASME B16.20, Standard for Ring-Joint Gaskets and Grooves for Steel Pipe Flanges; orMSS SP-6, Standard Finishes for Contact Faces of PipeFlanges and Connecting-End Flanges of Valves and Fit-tings. The pressure-temperature ratings shall equal or ex-ceed that required by the application. [NFPA 54:5.6.10]
1208.5.10.1 (A) Flange Facings. Standard fac-ings shall be permitted for use under this code.Where one-hundred and fifty (150) psi (1,090 1034kPa) steel flanges are bolted to Class 125 cast-ironflanges, the raised face on the steel flange shall beremoved. [NFPA54:5.6.10.1]1208.5.10.2 (B) Lapped Flanges.Lapped flangesshall be used only above ground or in exposed loca-tions accessible for inspection. [NFPA54:5.6.10.2]
12098.5.11 Flange Gaskets. The material for gasketsshall be capable of withstanding the design temperatureand pressure of the piping system and the chemical con-stituents of the gas being conducted without change toits chemical and physical properties. The effects of fireexposure to the joint shall be considered in choosing thematerial. [NFPA 54:5.6.11] Flange gaskets shall complywith the following requirements:(1) Acceptable materials include the following [NFPA
54-12:5.6.11.1]:(a) Metal or metal-jacketed asbestos (plain or corru-
gated).(b) Asbestos Composition.(c) Aluminum "O" rings and spiral-wound metal
gaskets.
FUEL PIPING
(2) When Where a flanged joint is opened, the gasketshall be replaced. [NFPA54:5.6.11.2]
(3) Full-face gaskets shall be used with all bronze andcast-iron flanges. [NFPA 54:5.6.11.3]
12098.6 Gas Meters.12098.6.1 Capacity. Gas meters shall be selected forthe maximum expected pressure and permissible pres-sure drop. [NFPA54:5.7.1]12098.6.2 Location.
1208.6.2.1 Ventilated Spaces. (A) Gas metersshall be located in ventilated spaces readily accessi-ble for examination, reading, replacement, or neces-sary maintenance. [NFPA 54:5.7.2.1]1208.6.2.2 Subject to Damage. (B) Gas metersshall not be placed where they will be subjected todamage, such as adjacent to a driveway; under a fireescape; in public passages, halls, or coal bins; orwhere they will be subject to excessive corrosion orvibration. [NFPA54:5.7.2.2]1208.6.2.3 Extreme Temperatures. (C) Gasmeters shall not be located where they will be sub-jected to extreme temperatures or sudden extremechanges in temperature. Meters shall not be locatedin areas where they are subjected to temperatures be-yond those recommended by the manufacturer.[NFPA 54:5.7.2.4]
12098.6.3 Supports. Gas meters shall be supported orconnected to rigid piping so as not to exert a strain on themeters. Where flexible connectors are used to connect agas meter to downstream piping at mobile homes in mo-bile home parks, the meter shall be supported by a post orbracket placed in a firm footing or by other means pro-viding equivalent support. [NFPA 54:5.7.3]12098.6.4 Meter Protection.Meters shall be protectedagainst overpressure, back-pressure, and vacuum wheresuch conditions are anticipated. [NFPA 54-12:5.7.4]12098.6.5 Identification. Gas piping at multiple meterinstallations shall be marked by a metal tag or other per-manent means attached by the installing agency, desig-nating the building or the part of the building beingsupplied. [NFPA 54:5.7.5]
12098.7 Gas Pressure Regulators.12098.7.1 Where Required. A line gas pressure reg-ulator or gas appliance pressure regulator, as applicable,shall be installed where the gas supply pressure exceedsthat at which the branch supply line or gas utilization ap-pliance is designed to operate or varies beyond designpressure limits. [NFPA 54-12:5.8.1]
1208.7.1.1Where the gas supply pressure in pipingsystems located indoors exceeds 2 psi (14 kPa) andline pressure regulators are installed to reduce thesupply pressure to 14 inches water column (3.5 kPa)or less, the following shall apply:(1) Regulators shall be provided with factory in-
stalled overpressure protection devices.
(2) Overpressure protection devices shall limit thepressure downstream of the line pressure regu-lator to 2 psi (14 kPa) in the event of failure ofthe line pressure regulator.
12098.7.2 Listing. The line gas pressure regulator shallbe listed in accordance with CSA Z21.80. [NFPA54:5.8.2]12098.7.3 Location. The gas pressure regulator shallbe accessible for servicing. [NFPA 54:5.8.3]12098.7.4 Regulator Protection. Pressure regulatorsshall be protected against physical damage. [NFPA54:5.8.4]12098.7.5 Venting.
1208.7.5.1 (A) Line Gas Pressure Regula-tors. Line gas pressure regulators shall be installedin accordance with the following requirements:(1) An independent vent to the outside exterior of
the building, sized in accordance with the regu-lator manufacturer's instructions, shall be pro-vided where the location of a regulator is suchthat a ruptured diaphragm will cause a hazard.Where there is more than one (1) regulator is ata location, each regulator shall have a separatevent to the outside outdoors, or, if where ap-proved by the Authority Having Jurisdiction,the vent lines shall be permitted to be mani-folded in accordance with accepted engineeringpractices to minimize back-pressure in the eventof diaphragm failure. (See NFPA 54:5.9.7 forinformation on properly locating the vent.) Ma-terials for vent piping shall be in accordancecomply with Section 12098.5.Exception:Aregulator and vent limiting meanscombination listed as complying in accordancewith CSAZ21.80, Standard for Line Pressure Reg-ulators, shall be permitted to be used without avent to the outdoors.
(2) The vent shall be designed to prevent the entryof water, insects, or other foreign materials thatcould cause blockage.
(3) The regulator vent shall terminate not less than3 feet (914 mm) from a source of ignition.
(34)At locations where regulators might be will sub-merged during floods, a special antiflood-typebreather vent fitting shall be installed, or thevent line shall be extended above the height ofthe expected flood waters.
(45)A regulator shall not be vented to the gas appli-ance flue or exhaust system. [NFPA54:5.8.5.1]
1208.7.5.2 (B) Venting of Gas AppliancePressure Regulators. Venting of gas appliancepressure regulators shall comply with the followingrequirements:(1) Gas aAppliance pressure regulators requiring
access to the atmosphere for successful opera-tion shall be equipped with vent piping leading
UNIFORM PLUMBING CODE 177
FUEL PIPING
UNIFORM PLUMBING CODE178
outdoors, or, if where the regulator vent is anintegral part of the appliance, into the combus-tion chamber adjacent to a continuous pilot, un-less constructed or equipped with avent-limiting means to limit the escape of gasfrom the vent opening in the event of diaphragmfailure.
(2) Vent-limiting means shall be employed on listedgas appliance pressure regulators only.
(3) In the case of vents leading outdoors, means shallbe employed to prevent water from entering thispiping and also to prevent blockage of vents byinsects and foreign matter.
(4) Under no circumstances shall a regulator bevented to the gas utilization appliance flue orexhaust system.
(5) In the case of vents entering the combustionchamber, the vent shall be located so the escap-ing gas will be readily ignited by the pilot andthe heat liberated thereby will not adversely af-fect the normal operation of the safety shutoffsystem. The terminus of the vent shall be se-curely held in a fixed position relative to thepilot. For manufactured gas, the need for aflame arrester in the vent piping shall be deter-mined.
(6) Vent lines from a gas appliance pressure regu-lator and bleed lines from a diaphragm-typevalve shall not be connected to a common man-ifold terminating in a combustion chamber. Ventlines shall not terminate in positive-pressure-type combustion chambers. [NFPA 54:9.1.19]
1208.7.5.3 (C) Discharge of Vents. Dischargeof vents shall be in accordance with the followingrequirements:(1) The discharge stacks, vents, or outlet parts of all
pressure-relieving and pressure-limiting devicesshall be located so that gas is safely dischargedinto the outside atmosphere outdoors.
(2) Discharge stacks or vents shall be designed toprevent the entry of water, insects, or any otherforeign material that could cause blockage. Thedischarge stack or vent line shall be not less thanthe same size as the outlet of the pressure-re-lieving device. [NFPA 54:5.9.7]
12098.7.6 Bypass Piping. Valved and regulated by-passes shall be permitted to be placed around gas linepressure regulators where continuity of service is imper-ative. [NFPA 54:5.8.6]12098.7.7 Identification. Line pressure regulators atmultiple regulator installations shall be marked by ametal tag or other permanent means designating thebuilding or the part of the building being supplied.[NFPA 54:5.8.7]
12098.8 Back-Pressure Protection.12098.8.1 Where to Install. Protective devices shallbe installed as close to the utilization appliance as prac-
tical, where the design of utilization appliances con-nected are such that air, oxygen, or standby gases couldbe are capable of being forced into the gas supply sys-tem. [NFPA 54:5.10.1.1] Gas and air combustion mixersincorporating double diaphragm "zero" or "atmosphere"governors or regulators shall require no further protectionunless connected directly to compressed air or oxygen atpressures of five (5) psi (34 kPa) or more. [NFPA54:5.10.1.2]12098.8.2 Protective Devices. Protective devicesshall include but not be limited to the following:(1) Check valves.(2) Three-way valves (of the type that completely closes
one side before starting to open the other side).(3) Reverse flow indicators controlling positive shutoff
valves.(4) Normally closed air-actuated positive shutoff pres-
sure regulators. [NFPA 54:5.10.2]12098.9 Low-Pressure Protection. A protective deviceshall be installed between the meter and the gas utilizationappliance or equipment if where the operation of the appli-ance or equipment (i.e., gas compressors) is such that it couldproduce is capable of producing a vacuum or a dangerous re-duction in gas pressure at the meter. Such protective devicesinclude, but are not limited to, mechanical, diaphragm-oper-ated, or electrically operated low-pressure shutoff valves.[NFPA 54-12:5.11]12098.10 Shutoff Valves. Shutoff valves shall be approvedand shall be selected giving consideration to pressure drop,service involved, emergency use, and reliability of operation.Shutoff valves of size one (1) inch (25 mm) National PipeThread and smaller shall be listed. [NFPA 54:5.12]12098.11 Expansion and Flexibility.
12098.11.1 Design. Piping systems shall be designedto have sufficient flexibility to prevent failure from ther-mal expansion or contraction. from causing excessivestresses in the piping material, excessive bending orloads at joints, or undesirable forces or moments at pointsof connections to equipment and at anchorage or guidepoints. Formal calculations or model tests shall be re-quired only where reasonable doubt exists as to the ade-quate flexibility of the system. [NFPA 54-12:5.134.1]
Flexibility shall be provided by the use of bends,loops, offsets, or couplings of the slip type. Provisionshall be made to absorb thermal changes by the use ofexpansion joints of the bellows type, or by the use of"ball" or "swivel" joints. Expansion joints of the slip typeshall not be used inside buildings or for thermal expan-sion. Where expansion joints are used, anchors or ties ofsufficient strength and rigidity shall be installed to providefor end forces due to fluid pressure and other causes.[NFPA 54:5.13.1.1]
Pipe alignment guides shall be used with expansionjoints according to the recommended practice of the jointmanufacturer. [NFPA 54:5.13.1.2]
FUEL PIPING
UNIFORM PLUMBING CODE 179
12098.11.2 Special Local Conditions.Where localconditions include earthquake, tornado, unstable ground,or flood hazards, special consideration shall be given toincreased strength and flexibility of piping supports andconnections. [NFPA 54:5.13.2]
12109.0 Excess Flow Valve.1209.1 General. Where automatic excess flow gas valvesare installed, they shall be listed, sized, and installed in ac-cordance with the manufacturer’s instructions. [NFPA 54-09:5.13]
12110.0 Gas Piping Installation.12110.1 Piping Underground.
12110.1.1 Clearances. Underground gas piping shallbe installed with sufficient approved clearance from anyother underground structures to avoid contact therewith,to allow maintenance, and to protect against damagefrom proximity to other structures. In addition, under-ground plastic piping shall be installed with sufficientapproved clearance or shall be insulated from any asources of heat so as to prevent the heat from impairingthe serviceability of the pipe. [NFPA 54:7.1.1]12110.1.2 Protection Against Damage.
1210.1.2.1 (A) Cover Requirements. Under-ground piping systems shall be installed with a min-imum cover not less than of eighteen (18) inches (460457mm) of cover.Where external damage to the pipeis not likely to result, the cover shall be a minimumnot less than of twelve (12) inches (3005 mm).Where a minimum of cover not less than twelve (12)inches (3005 mm) of cover cannot be provided, thepipe shall be installed in conduit or bridged(shielded). [NFPA 54:7.1.2.1]1210.1.2.2 (B) Trenches. The trench shall begraded so that the pipe has a firm, substantially con-tinuous bearing on the bottom of the trench. [NFPA54:7.1.2.2]1210.1.2.3 (C) Backfilling.Where flooding of thetrench is done to consolidate the backfill, care shallbe exercised to see that the pipe is not floated from itsfirm bearing on the trench bottom. [NFPA54:7.1.2.3]
12110.1.3 Protection Against Corrosion.Gas pip-ing in contact with earth or other material that could cor-rode is capable of corroding the piping shall be protectedagainst corrosion in an approved manner. When Wheredissimilar metals are joined underground, an insulatingcoupling or fitting shall be used. Piping shall not be laidin contact with cinders. Uncoated threaded or socket-welded joints shall not be used in piping in contact withsoil or where internal or external crevice corrosion isknown to occur. [NFPA 54:7.1.3]12110.1.4 Protection Against Freezing.Where theformation of hydrates or ice is known to occur, pipingshall be protected against freezing. [NFPA 54:7.1.4]
12110.1.5 Piping Through FoundationWall.Under-ground piping, where installed through the outer foundationor basement wall of a building, shall be encased in a pro-tective sleeve or protected by an approved device ormethod. The space between the gas piping and the buildingor sleeve and between the sleeve and thewall shall be sealedto prevent entry of gas and water. [NFPA54-12:7.1.5]12110.1.6 PipingUndergroundBeneath Buildings.Where the installation of gas piping is installed under-ground beneath buildings is unavoidable, the piping shallbe either:(1) eEncased in an approved conduit designed to with-
stand the superimposed loads and installed in accor-dance with Section 1210.1.6.1 or Section 1210.1.6.2,or. [NFPA 54:7.1.6]
(2) Apiping or encasement system listed for installationbeneath buildings.12110.1.6.1 Conduit with One End Terminat-ing Outdoors. The conduit shall extend into a nor-mally usable and accessible portion of the buildingand, at the point where the conduit terminates in thebuilding, the space between the conduit and the gaspiping shall be sealed to prevent the possible entranceof any a gas leakage.Where the end sealing is of a typethat will retain the full pressure of the pipe, the conduitshall be designed for the same pressure as the pipe.The conduit shall extend not less than (4) inches (1002mm) outside the building, be vented outdoors abovefinished ground level grade to the outside, and be in-stalled so as to prevent the entrance of water and in-sects. [NFPA 54:7.1.6.1]12110.1.6.2 Conduit with Both Ends Termi-nating Indoors.Where the conduit originates andterminates within the same building, the conduitshall originate and terminate in an accessible por-tion of the building and shall not be sealed. [NFPA54:7.1.6.2]
12110.1.7 Plastic Pipe.1210.1.7.1 (A) Connection of Plastic Piping.Plastic pipe shall be installed outside, undergroundonly. [NFPA 54:7.1.7.1]Exceptions:(1) Exception No. 1: Plastic pipe shall be permit-
ted to terminate above ground where an anode-less riser is used.
(2) Exception No. 2: Plastic pipe shall be permittedto terminate with a wall head adapter aboveground in buildings, including basements, wherethe plastic pipe is inserted in a piping materialpermitted for use in buildings.
1210.1.7.2 (B) Connections Between Metallicand Plastic Piping. Connections made betweenmetallic and plastic piping shall be made only withfittings conforming to that are in accordance withone of the following:
FUEL PIPING
UNIFORM PLUMBING CODE180
(1) ASTMD2513, Standard Specification for Ther-moplastic Gas Pressure Pipe, Tubing, and Fit-tings, Category I transition fittings.
(2) ASTM F1973, Standard Specification for Fac-tory Assembled Anodeless Risers and TransitionFittings in Polyethylene (PE) and Polyamide 11(PA11) Fuel Gas Distribution Systems.
(3) ASTM F2509, Standard Specification for Field-Assembled Anodeless Riser Kits for Use on Out-side Diameter Controlled Polyethylene GasDistribution Pipe and Tubing. [NFPA 54-09:7.1.7.2]
1210.1.7.3 (C) Tracer Wire.An electrically con-tinuous corrosion-resistant tracer wire (minimumnot less than AWG 14) or tape shall be buried withthe plastic pipe to facilitate locating. One (1) endshall be brought above ground at a building wall orriser. [NFPA 54:7.1.7.3]
12110.2 Installation of Piping.12110.2.1 Protection. Piping installed above groundshall be securely supported and located where it will beprotected from physical damage (also see 1211.1.4).Where passing through an outside wall, the piping shallalso be protected against corrosion by coating or wrap-ping with an inert material approved for such applica-tions. The piping shall be sealed around its circumferenceat the point of the exterior penetration to prevent theentry of water, insects, and rodents. Where piping is en-cased in a protective pipe sleeve, the annular spaces be-tween the gas piping and the sleeve and between thesleeve and the wall opening shall be sealed at the exteriorwall to prevent the entry of water, insects, or rodents.[NFPA 54-12:7.2.1]12110.2.2 Building Structure.
1210.2.2.1 Installation. (1) The installation of gaspiping shall not cause structural stresses withinbuilding components to exceed allowable designlimits. [NFPA 54:7.2.2.1]1210.2.2.2 Approval. (2) Approval shall be ob-tained before any beams or joists are cut or notched.[NFPA 54:7.2.2.2] Permission shall be obtainedfrom the Authority Having Jurisdiction.
1211.2.3 Other than Dry Gas. Drips, sloping, pro-tection from freezing, and branch pipe connections, asprovided for in Section 1211.1.4, 1211.8.1, and Section1211.10, shall be provided when other than dry gas isdistributed and climactic conditions make such provi-sions necessary. [NFPA 54:7.2.3]12110.2.43 Gas Piping to be Sloped. Piping forother than dry gas conditions shall be sloped not less thanone-fourth (1⁄4) inch in fifteen (15) feet (8 mm in 4,572mm) (1.4 mm/m) to prevent traps. [NFPA 54:7.2.4]
12110.2.43.1 Ceiling Locations. Gas pipingshall be permitted to be installed in accessible spaces
between a fixed ceiling and a dropped ceiling,whether or not such spaces are used as a plenum.Valves shall not be located in such spaces.Exception: Appliance shutoff valves required bythis code shall be permitted to be installed in acces-sible spaces containing vented gas utilization appli-ances.
12110.2.54 Prohibited Locations. Gas piping insideany a building shall not be installed in or through a cir-culating air duct, clothes chute, chimney or gas vent, ven-tilating duct, dumbwaiter, or elevator shaft, or air duct,other than combustion air ducts. [NFPA 54:7.2.5]Exception: This provision shall not apply to dDucts usedto provide combustion and ventilation air in accordancewith Section 5076.0 or to above-ceiling spaces as cov-ered in Section 121110.2.4.1.12110.2.65 Hangers, Supports, and Anchors.
1210.2.5.1 General Requirements. (A) Pipingshall be supported with metal pipe hooks, metal pipestraps, metal bands, metal brackets, metal hangers,or building structural components, suitable approvedfor the size of piping, of adequate strength and qual-ity; and located at intervals so as to prevent or dampout excessive vibration. Piping shall be anchored toprevent undue strains on connected appliances andequipment and shall not be supported by other pip-ing. Pipe hangers and supports shall conform tocomply with the requirements of MSS SP-58, PipeHangers and Supports Materials, Design and Man-ufacture. [NFPA 54:7.2.6.1]1210.2.5.2 Spacing. (B) Spacings of supports ingas-piping installations shall not exceed as the dis-tance shown in Table 12-3 1210.2.5.2. Spacing ofsupports for CSST shall be in accordance with theCSSTmanufacturer's instruction. [NFPA54:7.2.6.2]1210.2.5.3 Expansion and Contraction. (C)Supports, hangers, and anchors shall be installed soas not to interfere with the free expansion and con-traction of the piping between anchors. All pParts ofthe supporting equipment system shall be designedand installed so they will are not be disengaged bymovement of the supported piping. [NFPA54:7.2.6.3]
FUEL PIPING
STEEL PIPE,NOMINAL SIZE
OF PIPE(inches.)
SPACING OFSUPPORTS
(feet.)
NOMINAL SIZE OFTUBING SMOOTH-
WALL(Iinches. O.D.)
SPACING OFSUPPORTS
(feet.)
1⁄2 6 1⁄2 43⁄4 or 1 8 5⁄8 or 3⁄4 6
11⁄4 or larger(horizontal)
10 7⁄8 or 1(horizontal)
8
11⁄4 or larger(vertical)
every floorlevel
1 or larger(vertical)
every floorlevel
TABLE 12-3 1210.2.5.2SUPPORT OF PIPING[NFPA 54: Table 7.2.6.2]
For SI units: 1 inch = 25 mm, 1 foot. = 0.305 m 304.8 mm.
UNIFORM PLUMBING CODE 181
12110.2.76 Removal of Pipe Piping.Where pipingcontaining gas is to be removed, the line shall be firstdisconnected from sources of gas and then thoroughlypurged with air, water, or inert gas before any cutting orwelding is done. (See Section 1214.6.) [NFPA 54:7.2.7]
12110.3 Concealed Piping in Buildings.12110.3.1 General. Gas piping in concealed locationsshall be installed in accordance with this section. [NFPA54:7.3.1]12110.3.2 Connections. Where gas piping is to beconcealed, unions, tubing fittings, right and left cou-plings, bushings, swing joints, and compression cou-plings made by combinations of fittings shall not be used.Cconnections shall be of the following type:(1) Pipe fittings such as elbows, tees, and couplings, and
right/left nipple/couplings.(2) Joining tubing by brazing (See Section 12098.5.8.2).(3) Fittings listed for use in concealed spaces or that
have been demonstrated to sustain, without leakage,any forces due to temperature expansion or contrac-tion, vibration, or fatigue based on their geographiclocation, application, or operation.
(4) Where necessary to insert fittings in gas pipe thathas been installed in a concealed location, the pipeshall be reconnected by welding, flanges, or the useof a ground joint union with the nut center-punchedto prevent loosening by vibration right/left nip-ple/coupling. [NFPA 54:7.3.2]
12110.3.3 Piping in Partitions. Concealed gas pipingshall not be located in solid partitions. [NFPA 54:7.3.3]12110.3.4 Tubing in Partitions. This provision shallnot apply to tubing that pierces walls, floors, or partitionsor to tubing installed vertically and horizontally insidehollow walls or partitions without protection along itsentire concealed length where both of the following re-quirements are met:(1) A steel striker barrier not less than 0.0508 inches
(1.3 mm) thick, or equivalent, is installed betweenthe tubing, the finished wall and extends at least notless than 4 inches (1002 mm) beyond concealed pen-etrations of plates, fire stops, wall studs, and so on.
(2) The tubing is installed in single runs and is notrigidly secured. [NFPA 54:7.3.4]
12110.3.5 Piping in Floors. In industrial occupan-cies, gas piping in solid floors such as concrete shall belaid in channels in the floor and covered to permit accessto the piping with minimum damage to the building.Where piping in floor channels could be is capable ofbeing exposed to excessive moisture or corrosive sub-stances, the piping shall be protected in an approvedmanner. [NFPA 54:7.3.5.1]Exception: In other than industrial occupancies andwhere approved by the Authority Having Jurisdiction,gas piping embedded in concrete floor slabs constructedwith portland cement shall be surrounded with a mini-
mum not less than of one and one half (11⁄2) inches (38mm) of concrete and shall not be in physical contact withother metallic structures such as reinforcing rods or elec-trically neutral conductors. Piping, fittings, and risersshall be protected against corrosion in accordance withSection 12098.5.6. Piping shall not be embedded in con-crete slabs containing quick-set additives or cinder ag-gregate. [NFPA 54:7.3.5.2]
12110.4 Piping in Vertical Chases. (See Section 1202.0.)Where gas piping exceeding five (5) psi (34 kPa) is locatedwithin vertical chases in accordance with Section 12110.5,the requirements of Sections 12110.5.1 through Section12110.5.3 shall apply. [NFPA 54:7.4]12110.5 Maximum Design Operating Pressure. Themaximum design operating pressure for piping systems lo-cated inside buildings shall not exceed five (5) psi (34 kPa)unless one (1) or more of the following conditions are met:(1) The piping system is welded.(2) The piping is located in a ventilated chase or otherwise
enclosed for protection against accidental gas accumula-tion.
(3) The piping is located inside buildings or separate areas ofbuildings used exclusively for one of the following:(a) Industrial processing or heating.(b) Research.(c) Warehousing.(d) Boiler or mechanical equipment rooms.
(4) The piping is a temporary installation for buildings underconstruction.
(5) The piping serves appliances or equipment used for agri-cultural purposes.
(6) The piping system is an LP-Gas piping system with a de-sign operating pressure greater than exceeding 20 psi(138 kPa) and complies in accordance with NFPA 5854:5.5.2. Liquefied Petroleum Gas Systems LP-Gas sys-tems designed to operate below -5ºF (-21ºC) or with bu-tane or a propane-butane mix shall be designed to eitheraccommodate liquid LP-Gas or to prevent LP-Gas vaporfrom condensing back into liquid. [NFPA 54-09:5.5.1and 5.5.2]12110.5.1 Pressure Reduction. (See Section1202.0.) Where pressure reduction is required in branchconnections for compliance in accordance with Section12110.5, such reduction shall take place either inside thechase or immediately adjacent to the outside wall of thechase. Regulator venting and downstream overpressureprotection shall comply with Section 12098.7.5 and NFPASection 5.9. The regulator shall be accessible for serviceand repair, and vented in accordance with one (1) of thefollowing:(1) Where the fuel gas is lighter than air, regulators
equipped with a vent-limiting means shall be per-mitted to be vented into the chase. Regulators notequipped with a vent-limiting means shall be per-
FUEL PIPING
mitted to be vented either directly to the outdoors orto a point within the top one (1) foot (0.305mm) of thechase.
(2) Where the fuel gas is heavier than air, the regulatorvent shall be vented only directly to the outdoors.[NFPA 54:7.4.1]
12110.5.2 Liquefied Petroleum Gas Systems. Themaximum operating pressure of LP-Gas piping systemsshall be:(1) In accordance with Section 12110.5.1;(2) In accordance with NFPA58, where the pressure ex-
ceeds twenty (20) psi (138 kPa) and;(3) Designed to either accommodate liquid LP-Gas or
prevent LP-Gas vapor from condensing back into a liq-uid in buildings having systems designed to operatebelow -5ºF (-21ºC) or with butane or a propane–butanemix.
12110.5.3 Construction. Chase construction shallcomply with local building codes with respect to fire re-sistance and protection of horizontal and vertical open-ings. [NFPA 54:7.4.2]12110.5.4 Ventilation. A chase shall be ventilated tothe outdoors and only at the top. The openings shall havea minimum free area (in square inches) equal to the prod-uct of one-half (1⁄2) of the maximum pressure in the pip-ing (in psi) times the largest nominal diameter of thatpiping (in inches), or the cross-sectional area of thechase, whichever is smaller. Where more than one (1)fuel gas piping system is present, the free area for eachsystem shall be calculated and the largest area used.[NFPA 54:7.4.3]
12110.6 Appliance Over Pressure Protection. Themaximum operating pressure for piping systems serving ap-pliances designed to operate at fourteen (14) inches w.c. watercolumn (3.5 kPa) inlet pressure or less shall be two (2) psig 14kPa) unless an over-pressure protection device designed tolimit pressure at the appliance to two (2) psig (14 kPa) uponfailure of the line gas pressure regulator is installed.12110.7 Gas Pipe Turns. Changes in direction of gas pipeshall be made by the use of fittings, or factory bends, or fieldbends. [NFPA 54:7.5]
12110.7.1 Metallic Pipe. Metallic pipe bends shallcomply with the following:(1) Bends shall be made only with bending equipment
and procedures intended for that purpose.(2) Bends shall be smooth and free from buckling,
cracks, or other evidence of mechanical damage.(3) The longitudinal weld of the pipe shall be near the
neutral axis of the bend.(4) The pipe shall not be bent through an arc of more
than 90 degrees (1.57 rad).(5) The inside radius of a bend shall be not less than six
(6) times the outside diameter of the pipe. [NFPA54:7.5.1]
12110.7.2 Plastic Pipe. Plastic pipe bends shall com-ply with the following:(1) The pipe shall not be damaged and the internal di-
ameter of the pipe shall not be effectively reduced.(2) Joints shall not be located in pipe bends.(3) The radius of the inner curve of such bends shall be
not less than twenty-five (25) times the inside di-ameter of the pipe.
(4) Where the piping manufacturer specifies the use ofspecial bending equipment or procedures, suchequipment or procedures shall be used. [NFPA54:7.5.2]
12110.7.3 Elbows. Factory-made welding elbows ortransverse segments cut therefrom shall have an arclength measured along the crotch of at least not less thanone (1) inch (25.4 mm) for pipe sizes two (2) inches (50mm) and larger. [NFPA 54:7.5.3]
12110.8 Drips and Sediment Traps.12110.8.1 Provide Drips Where Necessary. Forother than dry gas conditions, a drip shall be provided atany a point in the line of pipe where condensate is capa-ble of collecting could collect.Where required by theAu-thority Having Jurisdiction or the serving gas supplier, adrip shall also be provided at the outlet of the meter. Thisdrip shall be so installed as to constitute a trap wherein anaccumulation of condensate will shut off the flow of gasbefore it will run back into the meter. [NFPA 54:7.6.1]12110.8.2 Location of Drips. Drips shall be installedonly in such locations that they will be readily accessibleto permit cleaning or emptying. A drip shall not be lo-cated where the condensate is likely to freeze. [NFPA54:7.6.2]12110.8.3 Sediment Traps. (See Section 1212.7.)The installation of sediment traps shall comply with Sec-tion 1211.7.
12110.9 Outlets.12110.9.1 Location and Installation. Outlets shallbe located and installed in accordance with the follow-ing requirements:(1) The outlet fittings or piping shall be securely fas-
tened in place. [NFPA 54:7.7.1.1](2) Outlets shall not be located behind doors. [NFPA
54:7.7.1.2](3) Outlets shall be located far enough from floors,
walls, patios, slabs, and ceilings to permit the use ofwrenches without straining, bending, or damagingthe piping. [NFPA 54:7.7.1.3]
(4) The unthreaded portion of gas piping outlets shallextend not less than one (1) inch (25.4 mm) throughfinished ceilings or indoor or outdoor walls. [NFPA54:7.7.1.4]
(5) The unthreaded portion of gas piping outlets shallextend not less than two (2) inches (501 mm) abovethe surface of floors or outdoor patios or slabs.[NFPA 54:7.7.1.5]
UNIFORM PLUMBING CODE182
FUEL PIPING
UNIFORM PLUMBING CODE 183
(6) The provisions of Sections 12110.79.1(4) and Sec-tion 1210.9.1(5) shall not apply to listed quick-dis-connect devices of the flush-mounted type or listedgas convenience outlets. Such devices shall be in-stalled in accordance with the manufacturer’s in-stallation instructions. [NFPA 54:7.7.1.6]
12110.9.2 Cap Outlets.1210.9.2.1 Gas-Tight. (A) Each outlet, includinga valve, shall be closed gas-tight with a threadedplug or cap immediately after installation and shallbe left closed until the gas utilization appliance isconnected thereto. WhenWhere an appliance is dis-connected from an outlet and the outlet is not to beused again immediately, it shall be closed gas-tight.[NFPA 54:7.7.2.1]Exceptions:(1) Exception No. 1: Laboratory equipment in-
stalled in accordance with Section 12121.2(A1)shall be permitted.
(2) Exception No. 2: The use of a listed quick-dis-connect device with integral shutoff or listedgas convenience outlet shall be permitted.
1210.9.2.2 Appliance Shutoff Valves (B) Ap-pliance shutoff valves installed in fireplaces shall beremoved and the piping capped gas-tight where thefireplace is used for solid-fuel burning. [NFPA54:7.7.2.2]
12110.10 Branch Pipe Connection. When Where abranch outlet is placed on a main supply line before it isknown what size pipe will be connected to it, the outlet shallbe of the same size as the line that supplies it. [NFPA 54:7.8]12110.11 Manual Gas Shutoff Valves. (Also see Sec-tion 1212.5)
12110.11.1 Valves at Regulators. An accessible gasshutoff valve shall be provided upstream of each gaspressure regulator. Where two (2) gas pressure regula-tors are installed in series in a single gas line, a manualvalve shall not be required at the second regulator. [NFPA54:7.9.1]12110.11.2 Valves Controlling Multiple Systems.
1210.11.2.1 (A) Accessibility of Gas Valves.Main gas shutoff valves controlling several gas pip-ing systems shall be readily accessible for operationand installed so as to be protected from physicaldamage. They shall be marked with a metal tag orother permanent means attached by the installingagency so that the gas piping systems suppliedthrough them can be are readily identified. [NFPA54:7.9.2.1]1210.11.2.2 (B) Shutoff Valves for MultipleHouse Lines. In multiple-tenant buildings sup-plied through a master meter, or through one (1)service regulator where a meter is not provided, orwhere meters or service regulators are not readily
accessible from the equipment location, an individ-ual shutoff valve for each apartment or tenant lineshall be provided at a convenient point of generalaccessibility.
In a common system serving a number of indi-vidual buildings, shutoff valves shall be installed ateach building. [NFPA 54:7.9.2.2]
12110.11.3 Emergency Shutoff Valves. An exte-rior shutoff valve to permit turning off the gas supply toeach building in an emergency shall be provided. Theemergency shutoff valves shall be plainly marked as suchand their locations posted as required by the AuthorityHaving Jurisdiction. [NFPA 54:7.9.2.3]12110.11.4 Shutoff Valve For Laboratories. Eachlaboratory space containing two (2) or more gas outletsinstalled on tables, benches, or in hoods in educational,research, commercial and industrial occupancies shallhave a single shutoff valve through which such gas out-lets are supplied. The shutoff valve shall be accessibleand shall be located within the laboratory or located ad-jacent to the laboratory’s egress door and shall be iden-tified. [NFPA 54-09:7.9.2.4]
12110.12 Prohibited Devices. No device shall be placedinside the gas piping or fittings that will reduce the cross-sec-tional area or otherwise obstruct the free flow of gas, exceptwhere proper an allowance in the piping system design hasbeen made for such a device and where approved by the Au-thority Having Jurisdiction. [NFPA 54:7.10]12110.13 Systems Containing Gas-Air Mixtures Out-side the Flammable Range. Where gas-air mixing ma-chines are employed to produce mixtures above or below theflammable range, they shall be provided with stops to pre-vent adjustment of the mixture to within or approaching theflammable range. [NFPA 54:7.11]12110.14 Systems Containing Flammable Gas-AirMixtures. Systems containing flammable gas-air mixturesshall be in accordance with NFPA 54.12110.15 Electrical Bonding and Grounding.
12110.15.1 Pipe and Tubing other than CSST.Each above ground portion of a gas piping system otherthan CSST that is likely to become energized shall beelectrically continuous and bonded to an effectiveground-fault current path. Gas piping, other than CSSTshall be considered to be bonded when where it is con-nected to appliances that are connected to the appliancegrounding conductor of the circuit supplying that appli-ance. [NFPA 54-09:7.13.1]12110.15.2 Bonding of CSST Gas Piping. CSSTgas piping systems shall be bonded to the electrical serv-ice grounding electrode system at the point where the gasservice enters the building. The bonding jumper shallconnect to a metallic pipe or fitting between the point ofdelivery and the first downstream CSST fitting. Thebonding jumper shall be not smaller than six (6) AWGcopper wire or equivalent. Gas piping systems that con-tain one or more segments of CSST shall be bonded inaccordance with this section. [NFPA 54-0912:7.13.2]
FUEL PIPING
UNIFORM PLUMBING CODE184
12110.15.3 Grounding Conductor or Electrode.Gas piping shall not be used as a grounding conductoror electrode. This does not preclude the bonding ofmetallic piping to a grounding system. [NFPA 54-0912:7.13.3]12110.15.4 Lighting Protection System. Where alightning protection system is installed, the bonding ofthe gas piping system shall be in accordance with NFPA780, Standard for Installation of Lightning ProtectionSystems. [NFPA 54-09:7.13.4]
12110.16 Electrical Circuits. Electrical circuits shall notutilize gas piping or components as conductors. [NFPA54:7.14]Exception: Low-voltage (50V or less) control circuits, igni-tion circuits, and electronic flame detection device circuitsshall be permitted to make use of piping or components as apart of an electric circuit.12110.17 Electrical Connections.
1210.17.1 Connections. (A) Electrical connectionsbetween wiring and electrically operated control devicesin a piping system shall conform to comply with the re-quirements of NFPA 70, National Electrical Code. (SeeSection 1211.14) [NFPA 54:7.15.1]1210.17.2 Safety Control. (B) Any An essentialsafety control depending on electric current as the oper-ating medium shall be of a type that will shut off (failsafe) the flow of gas in the event of current failure.[NFPA 54:7.15.2]
12121.0 Appliance Connections to Building Piping.12121.1 Connecting Gas Appliances. Gas utilizationaAppliances shall be connected to the building piping in com-pliance accordance with Sections 12121.5 and Section12121.6 by one of the following [NFPA 54:9.6.1]:(1) Rigid metallic pipe and fittings. [NFPA 54:9.6.1(1)](2) Semirigid metallic tubing and metallic fittings. Alu-
minum alloy tubing shall not be used in exterior loca-tions. [NFPA 54:9.6.1(2)]
(3) ALlisted flexible gas connectors installed in complianceaccordance with CSAANSI Z21.24/CSA6.10, Standardfor Connectors for Gas Appliances. The connector shallbe used in accordance with the terms of their listing thatare completely manufacturer’s installation instructionsand shall be in the same room as the appliance. One con-nector shall be used per appliance. [NFPA 54:9.6.1(3)]
(4) CSST where installed in accordance with the manufac-turer's installation instructions. [NFPA 54:9.6.1(5)]
(5) Listed nonmetallic gas hose connectors installed in ac-cordance with Section 12121.3. [NFPA 54:9.6.1(6)]
(6) Gas-fired food service (cCommercial cooking) applianceslisted for use with casters or otherwise subject to move-ment that are moved for cleaning and sanitation purposes,and other large and heavy gas utilization appliances thatcan be moved, shall be connected in accordance with the
connector manufacturer's installation instructions using alisted appliance connector complying that is in accor-dance with CSAANSI Z21.69/CSA 6.22, Standard forConnectors for Movable Gas Appliances. The commer-cial cooking appliance connector installation shall be con-figured in accordance with the manufacturer’s installationinstructions. (NFPA 54:9.6.1.1)
(7) Movement of appliances with casters shall be limited bya restraining device installed in accordance with the con-nector and appliance manufacturer's installation instruc-tions. [NFPA 54-09:9.6.1.2]
(8) In Sections 12121.1(2), 1211.1(3), and 1211.1(5), theconnector or tubing shall be installed so as to be pro-tected against physical and thermal damage. Aluminumalloy tubing and connectors shall be coated to protectagainst external corrosion where they are in contact withmasonry, plaster, insulation, or are subject to repeatedwettings by such liquids as water (except rainwater), de-tergents, or sewage.[NFPA 54:9.6.1(7)]
12121.2 Suspended Low-Intensity Infrared TubeHeaters. Suspended low-intensity infrared tube heaters shallbe connected to the building piping system with a connectorlisted for the application in accordance with CSA ANSIZ21.24/CGA 6.10, Connectors for Gas Appliances and thefollowing requirements. [NFPA 54-09:9.6.1.3](A1) The connector shall be installed in accordance with the
tube heater installation instructions, and shall be in thesame room as the appliance.
(B2) Only oOne connector shall be used per appliance.12121.3 Use of Nonmetallic Gas Hose Connectors.Listed nonmetallic gas hose connectors shall be used in ac-cordance with the terms of their listing manufacturer’s in-stallation instructions and as follows indicated in thefollowing sections. [NFPA 54:9.6.2]:
1211.3.1 (A) Indoor. Indoor gas hose connectors shallbe used only to connect laboratory, shop, and ironingequipment requiring mobility during operation. Anequipment appliance shutoff valve shall be installedwhere the connector is attached to the building piping.The connector shall be of minimum length and shall notexceed six (6) feet (1,829 mm). The connector shall notbe concealed and shall not extend from one (1) room toanother or pass through wall partitions, ceilings, orfloors.1211.3.2 (B) Outdoor.Where Ooutdoor gas hose con-nectors are permitted used to connect portable outdoorgas-fired appliances, the connector shall be listed in ac-cordance with CSAZ21.54b.An appliance shutoff valve,a listed quick-disconnect device, or a listed gas conven-ience outlet shall be installed where the connector is at-tached to the supply piping and in such a manner toprevent the accumulation of water or foreign matter. Thisconnection shall be made only in the outdoor area wherethe appliance is to be used. The connector length shallnot exceed fifteen (15) feet (4,572 mm).
FUEL PIPING
UNIFORM PLUMBING CODE 185
12121.4 Connection of Portable and Mobile Indus-trial Gas Appliance.
1211.4.1 Flexible Hose (A)Where portable industrialgas utilization appliances, or appliances requiring mo-bility or subject to vibration, are connected to the build-ing gas piping system by the use of a flexible hose, thehose shall be suitable approved and safe for the condi-tions under which it can be is used. [NFPA 54:9.6.3.1]1211.4.2 Swivel Joints or Couplings. (B) Whereindustrial gas utilization appliances requiring mobility areconnected to the rigid piping by the use of swivel joints orcouplings, the swivel joints or couplings shall be suitableapproved for the service required, and only the minimumnumber required shall be installed. [NFPA 54:9.6.3.2]1211.4.3 All-Metal Flexible Connectors. (C)Whereindustrial gas utilization appliances subject to vibrationare connected to the building piping system by the useof all-metal flexible connectors, the connectors shall besuitable approved for the service required. [NFPA54:9.6.3.3]1211.4.4 Flexible Connectors. (D) Where flexibleconnections are used, they shall be of the minimum prac-tical length and shall not extend from one (1) room to an-other or pass through any walls, partitions, ceilings, orfloors. Flexible connections shall not be used in any a con-cealed location. They shall be protected against physical orthermal damage and shall be provided with gas shutoffvalves in readily accessible locations in rigid piping up-stream from the flexible connections. [NFPA 54:9.6.3.4]
12121.5 Appliance Shutoff Valves and Connections.Gas utilization aAppliance connected to a piping system shallhave an accessible, approved manual shutoff valve with anondisplaceable valve member, or a listed gas convenienceoutlet installed within six (6) feet (1.8 1829 mm) of the ap-pliance it serves. Where a connector is used, the valve shallbe installed upstream of the connector. A union or flangedconnection shall be provided downstream from this valve topermit removal of controls. Shutoff valves serving decorativegas appliances shall be permitted to be installed in fireplacesif where listed for such use. [NFPA 54:9.6.4]12121.6 Quick-Disconnect Devices. Quick-disconnectdevices used to connect appliances to the building piping shallbe listed.Where they are installed indoors, an approved man-ual shutoff valve with a nondisplaceable valve member shallbe installed upstream of the quick-disconnect device. [NFPA54:9.6.5]12121.7 Sediment Trap.Where a sediment trap is not in-corporated as a part of the gas utilization appliance, a sedi-ment trap shall be installed downstream of the applianceshutoff valve as close to the inlet of the appliance as practi-cal at the time of appliance installation. The sediment trapshall be either a tee fitting with a capped nipple in the bottomoutlet, as illustrated in Figure 12-1 1211.7, or other devicerecognized as an effective sediment trap. Illuminating appli-ances, ranges, clothes dryers, decorative vented appliancesfor installation in vented fireplaces, gas fireplaces, and out-door grills shall not be required to be so equipped. [NFPA54-09:9.6.7]
12121.8 Installation of Piping. Piping shall be installedin a manner not to interfere with inspection, maintenance, orservicing of the gas utilization equipment appliance. [NFPA54:9.6.8]
12132.0 Liquefied Petroleum Gas Facilities and Pip-ing.1212.1 General. Liquefied petroleum gas facilities shallcomply with NFPA 58, Liquefied Petroleum Gas Code.
12143.0 Pressure Testing and Inspection.12143.1 General.
12143.1.1 Inspection and Testing. Prior to accept-ance and initial operation, piping installations shall bevisually inspected and pressure-tested to determine thatthe materials, design, fabrication, and installation prac-tices comply are in accordance with the requirements ofthis code. [NFPA 54-12:8.1.1.1]12143.1.2 Inspection Requirements. Inspectionshall consist of visual examination during or after man-ufacture, fabrication, assembly, or pressure tests., as ap-propriate. Supplementary types of non-destructiveinspection techniques, such as magnetic-particle, radi-ographic, and ultrasonic, shall not be required unlessspecifically listed herein or in the engineering design.[NFPA 54-12:8.1.1.2]12143.1.3 Repairs and Additions.Where repairs oradditions are made following the pressure test, the af-fected piping shall be tested. Minor repairs and additionsare not required to be pressure-tested provided that thework is inspected and connections are tested with a non-corrosive leak-detecting fluid or other leak-detectingmethods approved by theAuthority Having Jurisdiction.[NFPA 54:8.1.1.3]12143.1.4 New Branches. Where new branches areinstalled from the point of delivery to new appliances,only the newly installed branches shall be required to bepressure-tested. Connections between the new piping and
FUEL PIPING
For SI units: 1 inch = 25.4 mm
FIGURE 12-1 1211.7 METHOD OF INSTALLING ATEE FITTING SEDIMENT TRAP.
the existing piping shall be tested with a noncorrosiveleak-detecting fluid or approved leak-detecting methods.[NFPA 54:8.1.1.4]12143.1.5 Testing. A piping system shall be tested asa complete unit or in sections. Under no circumstancesshall a valve in a line be used as a bulkhead between gasin one (1) section of the piping system and test mediumin an adjacent section, unless two (2) valves are installedin series with a valved "telltale" located between thesevalves.A valve shall not be subjected to the test pressureunless it can be is determined that the valve, includingthe valve-closing mechanism, is designed to safely with-stand the pressure. [NFPA 54:8.1.1.5]12143.1.6 Regulators and Valves. Regulator andvalve assemblies fabricated independently of the pipingsystem in which they are to be installed shall be permit-ted to be tested with inert gas or air at the time of fabri-cation. [NFPA 54:8.1.1.6]12143.1.7 Test Medium. The test medium shall be air,nitrogen, carbon dioxide, or an inert gas. OXYGENSHALL NEVER BE USED. [NFPA 54:8.1.2]
12143.2 Test Preparation.12143.2.1 Pipe Joints. Pipe joints, including welds,shall be left exposed for examination during the test.[NFPA 54:8.1.3.1]Exception: Covered or concealed pipe end joints thathave been previously tested in accordance with this code.12143.2.2 Expansion Joints. Expansion joints shallbe provided with temporary restraints, if where requiredfor the additional thrust load under test. [NFPA54:8.1.3.2]12143.2.3 Appliances and Equipment. Appliancesand equipment that are not to be included in the test shallbe either disconnected from the piping or isolated byblanks, blind flanges, or caps. Flanged joints at whichblinds are inserted to blank off other equipment duringthe test shall not be required to be tested. [NFPA54:8.1.3.3]12143.2.4 Designed for (less than) OperatingPressures. Where the piping system is connected toappliances, equipment, or equipment components de-signed for operating pressures of less than the test pres-sure, such appliances, equipment, or equipmentcomponents shall be isolated from the piping system bydisconnecting them and capping the outlets. [NFPA54:8.1.3.4]12143.2.5 Designed for (equal to or more than)Operating Pressures. Where the piping system isconnected to appliances, equipment, or equipment com-ponents designed for operating pressures equal to orgreater than exceeding the test pressure, such appliancesand equipment shall be isolated from the piping systemby closing the individual appliance or equipment shutoffvalve(s). [NFPA 54:8.1.3.5]12143.2.6 Safety. Testing of piping systems shall bedone with due regard for the safety of employees and thepublic during the test. Bulkheads, anchorage, and bracing
suitably designed to resist test pressures shall be installedif where necessary. Prior to testing, the interior of the pipeshall be cleared of foreign material. [NFPA 54:8.1.3.6]
12143.3 Test Pressure.12143.3.1 General. Test pressure shall be measuredwith a manometer or with a pressure-measuring devicedesigned and calibrated to read, record, or indicate apressure loss due to leakage during the pressure test pe-riod. The source of pressure shall be isolated before thepressure tests are made. Mechanical gauges used tomeasure test pressures shall have a range such that thehighest end of the scale does not exceed five (5) timesthe test pressure. [NFPA 54:8.1.4.1]1214.3.2 The test pressure to be used shall be not lessthan one and one half (1-1⁄2) times the proposed maxi-mum working pressure, but not less than three (3) psi (20kPa), irrespective of design pressure. [NFPA 54:8.1.4.2]1214.3.3 Test duration shall be not less than one-half(1⁄2) hour for each five-hundred (500) cubic feet (14 m3)of pipe volume or fraction thereof.When testing a systemhaving a volume less than ten (10) cubic feet (0.28 m3)or a system in a single-family dwelling, the test durationshall be not less than ten (10) minutes. The duration ofthe test shall not be required to exceed twenty-four (24)hours. [NFPA 54:8.1.4.3] This inspection shall includean air, CO2, or nitrogen pressure test, at which time thegas piping shall stand a pressure of not less than 10 psi(69 kPa) gauge pressure. Test pressures shall be held fora length of time satisfactory to the Authority Having Ju-risdiction, but in no case less than 15 minutes with noperceptible drop in pressure. For welded piping, and forpiping carrying gas at pressures in excess of 14 incheswater column pressure (3.5 kPa), the test pressure shallbe not less than 60 psi (414 kPa) and shall be continuedfor a length of time satisfactory to the Authority HavingJurisdiction, but in no case for less than 30 minutes.These tests shall be made using air, CO2, or nitrogenpressure and shall be made in the presence of the Au-thority Having Jurisdiction. Necessary apparatus for con-ducting tests shall be furnished by the permit holder. Testgauges used in conducting tests shall be in accordancewith Section 317.0.
12143.4 Detection of Leaks and Defects.12143.4.1 Indication of Leaks. The piping systemshall withstand the test pressure specified without show-ing any evidence of leakage or other defects. Any rRe-duction of test pressures as indicated by pressure gaugesshall be deemed to indicate the presence of a leak unlesssuch reduction can be is readily attributed to some othercause. [NFPA 54:8.1.5.1]12143.4.2 Detecting Leaks. The leakage shall be lo-cated by means of an approved gas detector, a noncorro-sive leak detection fluid, or other approved leak detectionmethods. Matches, candles, open flames, or other meth-ods that provide a source of ignition shall not be used.[NFPA 54:8.1.5.2]
UNIFORM PLUMBING CODE186
FUEL PIPING
UNIFORM PLUMBING CODE 187
12143.4.3 Repair or Replace. Where leakage orother defects are located, the affected portion of the pip-ing system shall be repaired or replaced and retested.[(See Section 1214.1.3).] [NFPA 54:8.1.5.3]
12143.5 Piping Systems Leak Check.12143.5.1 Test Gases. Leak checks using fuel gasshall be permitted in piping systems that have been pres-sure-tested in accordance with Section 12143.0. [NFPA54:8.2.1]12143.5.2 Turning Gas On. During the process ofturning gas on into a system of new gas piping, the entiresystem shall be inspected to determine that there are noopen fittings or ends and that valves at unused outlets areclosed and plugged or capped. [NFPA 54-09:8.2.2]12143.5.3 Leak Check. Immediately after the gas isturned on into a new system or into a system that hasbeen initially restored after an interruption of service, thepiping system shall be checked for leakage. Where leak-age is indicated, the gas supply shall be shut off until thenecessary repairs have been made. [NFPA 54:8.2.3]12143.5.4 Placing Appliances and Equipment inOperation. Gas utilization aAppliances and equipmentshall not be placed in operation until after the piping sys-tem has been tested checked in accordance with Section12143.5.3, connections to the appliance are checked forleakage, and purged in accordance with Section 12143.6.2.[NFPA54-12:8.2.4]
1214.6 Purging.1214.6.1 Removal From Service.When gas pipingis to be opened for servicing, addition, or modification,the section to be worked on shall be turned off from thegas supply at the nearest convenient point and the linepressure vented to the outdoors or to ventilated areas ofsufficient size to prevent accumulation of flammablemixtures. The remaining gas in this section of pipe shallbe displaced with an inert gas as required by Table 12-5.[NFPA 54:8.3.1]1214.6.2 Placing in Operation.When piping full ofair is placed in operation, the air in the piping shall be dis-placed with fuel gas, except where such piping is requiredby Table 12-6 to be purged with an inert gas prior to in-troduction of fuel gas. The air can be safely displaced withfuel gas provided that a moderately rapid and continuousflow of fuel gas is introduced at one (1) end of the lineand air is vented out at the other end. The fuel gas flowshall be continued without interruption until the ventedgas is free of air. The point of discharge shall not be leftunattended during purging. After purging, the vent shallthen be closed. Where required by Table 12-6, the air inthe piping shall first be displaced with an inert gas, andthe inert gas shall then be displaced with fuel gas. [NFPA54:8.3.2]1214.6.3 Discharge of Purged Gases. The openend of piping systems being purged shall not dischargeinto confined spaces or areas where there are sources ofignition unless precautions are taken to perform this op-
eration in a safe manner by ventilation of the space, con-trol of purging rate, and elimination of hazardous condi-tions. [NFPA 54:8.3.3]1214.6.4 Placing Appliances in Operation. Afterthe piping has been placed in operation, appliances shallbe purged and then placed in operation, as necessary.[NFPA 54:8.3.4]
1213.6 Purging. Purging shall comply with Section1213.6.1 and Section 1213.6.4.
1213.6.1 Where Required.1213.6.1.1 Conditions. The purging of pipingsystems shall be in accordance with Section1213.6.2 through Section 1213.6.4 where the pipingsystem meets either of the following:(1) The designed operating gas pressure is greater
than 2 psig (14 kPa).(2) The piping being purged contains pipe sizes
greater than 2 inches (50 mm).1213.6.1.2 Monitored.Where piping systems notcovered under Section 1213.6.1.1 are purged withfuel gas the discharge point, whether indoor or out-door, shall be attended and monitored with a com-bustible gas indicator and purging stopped wherefuel gas is indicated at the discharge point.
1213.6.2 Removal From Service. Where existinggas piping meeting Section 1213.6.1 is to be opened foran addition, or modification, or service, the section to beworked on shall be isolated from the gas supply and theline pressure vented in accordance with Section 1213.6.4.Where gas piping meeting the criteria of Table 1213.6.2is removed from service the residual fuel gas in the pip-ing shall be displaced with an inert gas.
1213.6.3 Placing in Operation. Where gas pipingmeeting the criteria of Table 1213.6.2, containing air, isplaced in operation the air in the piping shall first be dis-placed with an inert gas. The inert gas shall then be dis-placed with fuel gas in accordance with Section 1213.6.4.1213.6.4 Outdoor Discharge of Purged Gases.The open end of piping systems being pressure ventedor purged shall discharge directly to an outdoor locationin accordance with the following requirements:
FUEL PIPING
NOMINAL PIPE SIZE(inch.)
LENGTH OF PIPINGREQUIRING PURGING
(feet.)21⁄2 > 503 > 304 > 156 > 10
8 or larger Any length
TABLE 12-5 1213.6.2LENGTH OF PIPING REQUIRING PURGING WITH INERT GAS
FOR SERVICING OR MODIFICATION[NFPA 54: TABLE 8.3.1]
For SI units: 1 inch = 25 mm, 1 foot. = 0.305 304.8 mm.
(1) The point of discharge shall be controlled with ashutoff valve.
(2) The discharge point shall be not less than 10 feet(3048 mm) from sources of ignition, located not lessthan 10 feet (3048 mm) from building openings, andnot less than 25 feet (7620 mm) from mechanical airintake openings.
(3) During discharge, the open discharge point shall becontinuously attended and monitored with a com-bustible gas indicator.
12154.0 Interconnections Between Gas Piping Sys-tems. [NFPA 54:5.3]12154.1 Interconnections Supplying SeparateUsers. Where two (2) or more meters, or two (2) or moreservice regulators where meters are not provided, are locatedon the same premises and supply separate users, the gas-pip-ing systems shall not be interconnected on the outlet side ofthe meters or service regulators. [NFPA 54:5.3.1]12154.2 Interconnections for Standby Fuels. Wheresupplementary gas for standby use is connected downstreamfrom a meter or a service regulator where a meter is not pro-vided, a device to prevent backflow shall be installed. [NFPA54:5.3.2.1] A three-way valve installed to admit the standbysupply and at the same time shut off the regular supply shallbe permitted to be used for this purpose. [NFPA 54:5.3.2.2]
12165.0 Required Gas Supply.12165.1 General. The following regulations, as set forth inthis section and in Section 12176.0, Required Gas PipingSize, shall be the standard for the installation of gas piping.Natural gas regulations and tables are based on the use of gashaving a specific gravity of sixty-hundredths (0.60), suppliedat six (6) to eight (8) inches (152 to 203 mm) water column(1.5 kPa to 1.9 kPa) pressure at the outlet of the meter or reg-ulator. For undiluted liquefied petroleum gas, gas piping shallbe permitted to be sized at eleven (11) inches (279 mm) watercolumn (2.7 kPa) pressure at the outlet of the meter or regu-lator and specific gravity of one and fifty-hundredths (1.50).Note:Where gas of a different specific gravity is to be deliv-ered, the serving gas supplier should be contacted for specificgravity conversion factors to use provided by the serving gassupplier shall be used in sizing piping systems from the pipesizing tables in this chapter.12165.2 Volume. The hourly volume of gas required ateach piping outlet shall be taken as not less than the maxi-
mum hourly rating as specified by the manufacturer of theappliance or appliances to be connected to each such outlet.12165.3 Gas Appliances.Where the gas appliances to beinstalled have not been definitely specified, Table 12-11208.4.2 shall be permitted to be used as a reference to esti-mate requirements of typical appliances.
To obtain the cubic feet per hour (L/sec.) of gas required,divide input of appliances by the average Btu (Watt-hour kW)heating value per cubic foot (L) of the gas. The average Btu(Watt-hour kW) per cubic foot (L) of the gas in the area ofthe installation shall be permitted to be obtained from theserving gas supplier.12165.4 Size of Piping Outlets. The size of the supplypiping outlet for any a gas appliance shall not be less thanone-half (1⁄2) of an inch (15 mm).
Theminimum size of any a piping outlet for amobile homeshall be not less than three-quarters (3⁄4) of an inch (20 mm).
12176.0 Required Gas Piping Size.12176.1 Pipe Sizing Methods. Where the pipe size is tobe determined using any a of the methods in Sections12176.1.1 through Section 12176.1.3, the diameter of eachpipe segment shall be obtained from the pipe-sizing tables inSection 12176.2 or from the sizing equations in Section12176.3. [NFPA 54:6.1]
12176.1.1 Longest Length Method. The pipe size ofeach section of gas piping shall be determined using thelongest length of piping from the point of delivery to themost remote outlet and the load of the section (sSee calcu-lation example in Figure 12-2 1216.1.1). [NFPA54:6.1.1]12176.1.2 Branch Length Method. Pipe shall besized as follows [NFPA 54:6.1.2]:(1) (A) Pipe size of each section of the longest pipe run
from the point of delivery to the most remote outletshall be determined using the longest run of pipingand the load of the section.
(2) (B)The pipe size of each section of branch piping notpreviously sized shall be determined using the lengthof piping from the point of delivery to the most re-mote outlet in each branch and the load of the section.
12176.1.3 Hybrid Pressure.The pipe size for each sec-tion of higher-pressure gas piping shall be determined usingthe longest length of piping from the point of delivery to themost remote line pressure regulator. The pipe size from theline pressure regulator to each outlet shall be determinedusing the length of piping from the regulator to the mostremote outlet served by the regulator. [NFPA54:6.1.3]
12176.2 Tables for Sizing Gas-Piping Systems. Ta-bles 12-8 1216.2(1) through Table 12-41 1216.2(36) shall beused to size gas piping in conjunction with one (1) of themethods described in Sections 12176.1.1 through Section12176.1.3. [NFPA 54:6.2]12176.3 Sizing Equations. The inside diameter ofsmooth-wall pipe or tubing shall be determined by the sizingeEquations 12-1 1216.3(1) or Equation 12-2 1216.3(2), usingthe equivalent pipe length determined by Sections 12176.1.1through Section 12176.1.3. [NFPA 54:6.4]
UNIFORM PLUMBING CODE188
FUEL PIPING
NOMINAL PIPE SIZE (in.) LENGTH OF PIPING REQUIRINGPURGING (ft.)
3 > 304 > 156 > 10
8 or larger Any length
TABLE 12-6Length of Piping Requiring Purging with Inert Gas Before
Placing in Operation[NFPA 54: Table 8.3.2]
For SI units: 1 ft. = 0.305 m.
Equation 12-1 1216.3(1) Low-Pressure Gas Formula (Lessthan 1.5 psi [10.3 kPa]): [NFPA 54:6.4.1]
where:D = inside diameter of pipe, inchesQ = input rate appliance(s), cubic feet per hour at 60˚F
(16ºC) and 30 inch (759 mm) mercury columnP1 = upstream pressure, psia (P1 + 14.7)P2 = downstream pressure, psia (P2 + 14.7)L = equivalent length of pipe, feet∆H =pressure drop, inches water column (27.7 in. H2O=1 psi)Cr and Y in accordance with with Table 1216.3For SI units: 1 inch = 25 mm, 1 pound-force per square inch = 6.894 kPa, t/°C= (t/°F-32)/1.8, 1 inch mercury column = 3.39 kPa, 1 inch water column =0.249 kPa.
Equation 12-2 1216.3(2) High-Pressure Gas Formula (1.5psi [10.3 kPa] and above): [NFPA 54:6.4.2]
where:D = inside diameter of pipe, inchesQ = input rate appliance(s), cubic feet per hour at 60ºF
(16ºC) and 30 inch (759 mm) mercury columnP1 = upstream pressure, psia (P1 + 14.7)P2 = downstream pressure, psia (P2 + 14.7)L = equivalent length of pipe, feet.∆H= pressure drop, inches water column (27.7 in. H2O=1 psi)Cr and Y in accordance with with Table 1216.3For SI units: 1 inch = 25 mm, 1 pound-force per square inch = 6.894 kPa, t/°C= (t/°F-32)/1.8, 1 inch mercury column = 3.39 kPa, 1 inch water column =0.249 kPa.
12176.4 Sizing of Piping Sections. To determine the sizeof each section of pipe in any a system within the range ofthe Table 1216.2(1) through Table 1216.2(36), proceed as fol-lows:(1) (A) Measure the length of the pipe from the gas
meter location to the most remote outlet on the system.(2) (B) Select the length in feet column and row showing the
distance, or the next longer distance if where the tabledoes not give the exact length.
(3) (C) Starting at the most remote outlet, find in the rowjust selected the gas demand for that outlet. If Where theexact figure of demand is not shown, choose the nextlarger figure in the row.
(4) (D) At the top of this column will be found the correctsize of pipe.
(5) (E) Using this same row, proceed in a similar manner foreach section of pipe serving this outlet. For each sectionof pipe, determine the total gas demand supplied by thatsection. Where gas piping sections serve both heatingand cooling appliances and the installation prevents bothunits from operating simultaneously, only the larger ofthe two (2) demand loads needs be used in sizing thesesections.
(6) (F) Size each section of branch piping not previouslysized by measuring the distance from the gas meter lo-cation to the most remote outlet in that branch and followthe procedures of steps B, C, D, and E 2, 3, 4, and 5above.Note: Size branch piping in the order of their dis-tance from the meter location, beginning with the mostdistant outlet not previously sized.
12176.5 Engineering Methods. For conditions other thanthose covered by Section 12176.1, such as longer runs orgreater gas demands, the size of each gas piping system shallbe determined by standard engineering methods acceptableto the Authority Having Jurisdiction, and each such systemshall be so designed that the total pressure drop between themeter or other point of supply and any an outlet when wherefull demand is being supplied to all outlets, shall comply bein accordance with the requirements of Section 12098.4.12176.6 Variable Gas Pressure.Where the gas pressureexceeds fourteen (14) inches (356 mm 3.5 kPa) or less thansix (6) inches (152 mm 1.5 kPa) of water column, or whenwhere diversity demand factors are used, the design, pipe, siz-ing, materials, location, and use of such systems first shall beapproved by the Authority Having Jurisdiction. Piping sys-tems designed for pressures exceeding the serving gas sup-plier's standard delivery pressure shall have prior verificationfrom the gas supplier of the availability of the design pressure.
UNIFORM PLUMBING CODE 189
FUEL PIPING
D =( )∆H
Cr x L
Q0.381
0.20619.17
D = Q0.381
0.20618.93[ ](P1
2 – P22) • Y
Cr x L
FORMULA FACTORS GAS Cr YNatural Gas 0.6094 0.9992Undiluted Propane 1.2462 0.9910
TABLE 12-4 1216.3Cr AND Y FOR NATURAL GAS AND UNDILUTED PROPANE AT
STANDARD CONDITIONS [NFPA 54: TABLE 6.4.2]
For SI units: 1 ft.3 cubic foot = 0.0283 m3, 1 foot = 0.3054.8mm, 1 inch watercolumn = 0.249 kPa, 1 psi pound-force per square inch = 6.894 kPa, 1,000Btu/h British thermal units per hour = 0.293 kW.
190 UNIFORM PLUMBING CODE
FUEL PIPING
FIGURE 12-2 1216.1.1 EXAMPLE ILLUSTRATING USE OF TABLES 12-1 1208.4.2 AND 12-8 1216.2(1)Problem: Determine the required pipe size of each section and outlet of the piping system shown in Figure 12-2 1216.1.1. Gasto be used has a specific gravity of sixty-hundredths (0.60) and eleven-hundred (1,100) British thermal units (Btu) per cubicfoot (11.4 0.0114 Watt-hour/L kW/L), delivered at eight (8) inch (203 mm 1.9 kPa) water column pressure.
Solution:(1) Maximum gas demand of outlet A—
32 cubic feet per hour (0.215 L/sec.) (from Table 12-1 1208.4.2).Maximum gas demand of outlet B —3 cubic feet per hour (0.02 L/sec.) (from Table 12-1 1208.4.2).
Maximum gas demand of outlet C —59 cubic feet per hour (0.46 L/sec.) (from Table 12-1 1208.4.2).
Maximum gas demand of outlet D —136 cubic feet per hour (1.1 L/sec.) (150,000 Btu/hour [43,950 kW])divided by 1,100 Btu per cubic foot (11.4 Watt-hour/L 0.0114 kW/L)
(2) The length of pipe from the gas meter to the most remote outlet (outlet A) is 60 feet (18,288 mm).(3) Using the length in feet column row marked 60 feet (18,288 mm) in Table 12-8 1216.2(1):OutletA, supplying 32 cubic feet per hour (0.215 L/sec.), requires one-half (1⁄2) of an inch (15 mm) pipe. Section 1, supplyingoutlets A and B, or 35 cubic feet per hour (ft3/h)(0.27 L/s) (0.24 L/sec.) requires one-half (1⁄2) of an inch (15 mm) pipe.Section 2, supplying outlets A, B, and C, or 94 cubic feet per hour (0.74 L/sec.) requires three-quarters (3⁄4) of an inch (20mm) pipe.Section 3, supplying outlets A, B, C, and D, or 230 cubic feet per hour (1.809 L/sec.), requires one (1) inch (25 mm) pipe.
(4) Using the column marked 60 feet (18,288 mm) in Table 12-8 1216.2(1) (no column for actual length of 55 feet [16,764mm]:Outlet B supplying 3 cubic feet per hour (0.02 L/sec.), requires one-half (1⁄2) of an inch (15 mm) pipe.Outlet C, supplying 59 cubic feet per hour (0.46 L/sec.), requires one-half (1⁄2) of an inch (15 mm) pipe.
(5) Using the column marked 60 feet (18,288 mm) in Table 12-8 1216.2(1):Outlet D, supplying 136 cubic feet per hour (1.107 L/sec.), requires (3⁄4) of an inch (20 mm) pipe.
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 cubic foot per hour = 0.00787 L/s
191UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-8 1216.2(1)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2(b)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPaNotes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.5 in w.c.
SPECIFIC GRAVITY: 0.60
PIPE SIZE (inch)NOMINAL: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4 5 6 8 10 12
ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026 5.047 6.065 7.981 10.020 11.938
LENGTH(feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
172118958172
360247199170151
678466374320284
1390957768657583
209014301150985873
40202760222019001680
64004400353030202680
11 3007780625053504740
23 10015 90012 70010 9009660
41 80028 70023 00019 70017 500
67 60046 50037 30031 90028 300
139 00095 50076 70065 60058 200
252 000173 000139 000119 000106 000
399 000275 000220 000189 000167 000
60708090100
6560565250
137126117110104
257237220207195
528486452424400
791728677635600
15201400130012201160
24302230208019501840
42903950367034503260
87608050749070306640
15 80014 60013 60012 70012 000
25 60023 60022 00020 60019 500
52 70048 50045 10042 30040 000
95 70088 10081 90076 90072 600
152 000139 000130 000122 000115 000
125150175200250
4440373430
9283777163
173157144134119
355322296275244
532482443412366
1020928854794704
16301480136012701120
28902610241022401980
58905330491045604050
10 6009650888082607320
17 20015 60014 40013 40011 900
35 40032 10029 50027 50024 300
64 30058 30053 60049 90044 200
102 00092 30084 90079 00070 000
300350400450500
2725232221
5753494643
10899928682
221203189177168
331305283266251
638587546512484
1020935870816771
18001650154014401360
36703370314029402780
66306100568053305030
10 7009880919086208150
22 10020 30018 90017 70016 700
40 10036 90034 30032 20030 400
63 40058 40054 30050 90048 100
550600650700750
2019181717
4139383635
7874716866
159152145140135
239228218209202
459438420403389
732699669643619
12901240118011401090
26402520241023202230
47804560436041904040
77407380707067906540
15 90015 20014 50014 00013 400
28 90027 50026 40025 30024 400
45 70043 60041 80040 10038 600
8008509009501000
1616151514
3433323130
6361595856
130126122118115
195189183178173
375363352342333
598579561545530
10601020992963937
21602090202019601910
39003780366035503460
63206110593057605600
13 00012 60012 20011 80011 500
23 60022 80022 10021 50020 900
37 30036 10035 00034 00033 100
11001200130014001500
1413121211
2827262524
5351494745
1091041009693
164156150144139
316301289277267
503480460442426
890849813781752
18101730166015901530
32803130300028802780
53205070486046704500
10 90010 400998095909240
19 80018 90018 10017 40016 800
31 40030 00028 70027 60026 600
16001700180019002000
11111010NA
2322222120
4442414039
8986848179
134130126122119
258250242235229
411398386375364
727703682662644
14801430139013501310
26802590252024402380
43404200407039603850
89208630837081307910
16 20015 70015 20014 80014 400
25 60024 80024 10023 40022 700
192 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 1216.2(2)SCHEDULE 40 METALLIC PIPE [NFPA 54-12: TABLE 6.2(c)]
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 3.0 in. w.c.SPECIFIC GRAVITY: 0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0 IN. W.C. OR GREATERPIPE SIZE (inch)
NOMINAL 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4ACTUAL ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH(feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
10 454 949 1787 3669 5497 10 588 16 875 29 832 43 67820 312 652 1228 2522 3778 7277 11 598 20 503 30 02030 250 524 986 2025 3034 5844 9314 16 465 24 10740 214 448 844 1733 2597 5001 7971 14 092 20 63250 190 397 748 1536 2302 4433 7065 12 489 18 28660 172 360 678 1392 2085 4016 6401 11 316 16 56970 158 331 624 1280 1919 3695 5889 10 411 15 24380 147 308 580 1191 1785 3437 5479 9685 14 18190 138 289 544 1118 1675 3225 5140 9087 13 305100 131 273 514 1056 1582 3046 4856 8584 12 568125 116 242 456 936 1402 2700 4303 7608 11 139150 105 219 413 848 1270 2446 3899 6893 10 093175 96 202 380 780 1169 2251 3587 6342 9285200 90 188 353 726 1087 2094 3337 5900 8638250 80 166 313 643 964 1856 2958 5229 7656300 72 151 284 583 873 1681 2680 4738 6937350 66 139 261 536 803 1547 2465 4359 6382400 62 129 243 499 747 1439 2294 4055 5937450 58 121 228 468 701 1350 2152 3804 5570500 55 114 215 442 662 1275 2033 3594 5262550 52 109 204 420 629 1211 1931 3413 4997600 50 104 195 400 600 1156 1842 3256 4767650 47 99 187 384 575 1107 1764 3118 4565700 46 95 179 368 552 1063 1695 2996 4386750 44 92 173 355 532 1024 1632 2886 4225800 42 89 167 343 514 989 1576 2787 4080850 41 86 162 332 497 957 1526 2697 3949900 40 83 157 322 482 928 1479 2615 3828950 39 81 152 312 468 901 1436 2539 37181000 38 79 148 304 455 877 1397 2470 36161100 36 75 141 289 432 833 1327 2346 34351200 34 71 134 275 412 794 1266 2238 32771300 33 68 128 264 395 761 1212 2143 31381400 31 65 123 253 379 731 1165 2059 30141500 30 63 119 244 366 704 1122 1983 29041600 29 61 115 236 353 680 1083 1915 28041700 28 59 111 228 342 658 1048 1854 27141800 27 57 108 221 331 638 1017 1797 26311900 27 56 105 215 322 619 987 1745 25552000 26 54 102 209 313 602 960 1698 2485
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249kPaNote: Table entries are rounded to 3 significant digits.
193UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 6.0 in. w.c.SPECIFIC GRAVITY: 0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0 IN. W.C. OR GREATERPIPE SIZE (inch)
NOMINAL 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4ACTUAL ID 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH(feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
10 660 1380 2600 5338 7999 15 405 24 553 43 405 63 55120 454 949 1787 3669 5497 10 588 16 875 29 832 43 67830 364 762 1435 2946 4415 8502 13 551 23 956 35 07540 312 652 1228 2522 3778 7277 11 598 20 503 30 02050 276 578 1089 2235 3349 6449 10 279 18 172 26 60660 250 524 986 2025 3034 5844 9314 16 465 24 10770 230 482 907 1863 2791 5376 8568 15 147 22 17880 214 448 844 1733 2597 5001 7971 14 092 20 63290 201 420 792 1626 2437 4693 7479 13 222 19 359100 190 397 748 1536 2302 4433 7065 12 489 18 286125 168 352 663 1361 2040 3928 6261 11 069 16 207150 153 319 601 1234 1848 3559 5673 10 029 14 684175 140 293 553 1135 1700 3275 5219 9227 13 509200 131 273 514 1056 1582 3046 4856 8584 12 568250 116 242 456 936 1402 2700 4303 7608 11 139300 105 219 413 848 1270 2446 3899 6893 10 093350 96 202 380 780 1169 2251 3587 6342 9285400 90 188 353 726 1087 2094 3337 5900 8638450 84 176 332 681 1020 1965 3131 5535 8105500 80 166 313 643 964 1856 2958 5229 7656550 76 158 297 611 915 1762 2809 4966 7271600 72 151 284 583 873 1681 2680 4738 6937650 69 144 272 558 836 1610 2566 4537 6643700 66 139 261 536 803 1547 2465 4359 6382750 64 134 252 516 774 1490 2375 4199 6148800 62 129 243 499 747 1439 2294 4055 5937850 60 125 235 483 723 1393 2220 3924 5745900 58 121 228 468 701 1350 2152 3804 5570950 56 118 221 454 681 1311 2090 3695 54101000 55 114 215 442 662 1275 2033 3594 52621100 52 109 204 420 629 1211 1931 3413 49971200 50 104 195 400 600 1156 1842 3256 47671300 47 99 187 384 575 1107 1764 3118 45651400 46 95 179 368 552 1063 1695 2996 43861500 44 92 173 355 532 1024 1632 2886 42251600 42 89 167 343 514 989 1576 2787 40801700 41 86 162 332 497 957 1526 2697 39491800 40 83 157 322 482 928 1479 2615 38281900 39 81 152 312 468 901 1436 2539 37182000 38 79 148 304 455 877 1 397 2 470 3616
TABLE 1216.2(3)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2(d)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPaNote: Table entries are rounded to 3 significant digits.
194 UNIFORM PLUMBING CODE
FUEL PIPING
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
TABLE 12-9 1216.2(4)SCHEDULE 40 METALLIC PIPE [NFPA 54-12: TABLE 6.2(ce)]
GAS: NATURALINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 0.60
PIPE SIZE (inch)NOMINAL: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH(feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
15101070869753673
30402150176015201360
55603930321027802490
11 4008070659057105110
17 10012 100988085507650
32 90023 30019 00016 50014 700
52 50037 10030 30026 30023 500
92 80065 60053 60046 40041 500
189 000134 000109 00094 70084 700
60708090100
615569532502462
1240115010801010934
22702100197018501710
46604320404038103510
69806470605057005260
13 50012 50011 70011 00010 100
21 40019 90018 60017 50016 100
37 90035 10032 80030 90028 500
77 30071 60067 00063 10058,200
125150175200250
414372344318279
836751695642583
15301370127011701040
31402820260124102140
47004220391036103210
90608130753069606180
14 40013 00012 00011 1009850
25 50022 90021 20019 60017 400
52 10046 70043 30040 00035 500
300350400450500
253232216203192
528486452424401
945869809759717
19401790166015601470
29102670249023302210
56005150479045004250
89208210764071706770
15 80014 50013 50012 70012 000
32 20029 60027 50025 80024 400
550600650700750
182174166160154
381363348334322
681650622598576
14001330128012301180
20902000191018401770
40303850368035403410
64306130587056405440
11 40010 80010 40099709610
23 20022 10021 20020 30019 600
8008509009501000
149144139135132
311301292283275
556538522507493
11401100107010401010
17101650160015601520
32903190309030002920
52505080493047804650
92808980871084608220
18 90018 30017 80017 20016 800
11001200130014001500
125119114110106
262250239230221
468446427411396
960917878843812
14401370132012601220
27702640253024302340
44204220404038803740
78107450714068606600
15 90015 20014 60014 00013 500
16001700180019002000
10299969391
214207200195189
382370358348339
784759736715695
11801140110010701040
22602190212020602010
36103490339032903200
63806170598058105650
13 00012 60012 20011 90011 500
195UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-10 1216.2(5)SCHEDULE 40 METALLIC PIPE [NFPA 54-12: TABLE 6.2(df)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: 3.0 psiPRESSURE DROP: 2.0 psiSPECIFIC GRAVITY: 0.60
PIPE SIZE (inch)NOMINAL: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH(feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
2350162013001110985
49203380272023202060
92706370511043803880
19 00013 10010 50089907970
28 50019 60015 70013 50011 900
54 90037 70030 30025 90023 000
87 50060 10048 30041 30036 600
155 000106 00085 40073 10064 800
316 000217 000174 000149 000132 000
60708090100
892821764717677
18701720160015001420
35203230301028202670
72206640618058005470
10 8009950926086808200
20 80019 20017 80016 70015 800
33 20030 50028 40026 70025 200
58 70054 00050 20047 10044 500
120 000110 00010200096 10090 800
125150175200250
600544500465412
125011401050973862
23602140197018301620
48504400404037603330
72706590606056405000
14 00012 70011 70010 9009620
22 30020 20018 60017 30015 300
39 50035 70032 90030 60027 100
80 50072 90067 10062 40055 300
300350400450500
374344320300283
781719669627593
14701350126011801120
30202780259024302290
45304170387036403430
87208020746070006610
13 90012 80011 90011 20010 500
24 60022 60021 00019 70018 600
50 10046 10042 90040 20038 000
550600650700750
269257246236228
563537514494476
10601010969931897
21802080199019101840
32603110298028602760
62805990574055105310
10 0009550915087908470
17 70016 90016 20015 50015 000
36 10034 40033 00031 70030 500
8008509009501000
220213206200195
460445431419407
866838812789767
17801720167016201580
26602580250024302360
51304960481046704550
81807910767074507240
14 50014 00013 60013 20012 800
29 50028 50027 70026 90026 100
11001200130014001500
185177169162156
387369353340327
729695666640616
15001430137013101270
22402140205019701900
43204120394037903650
68906570629060405820
12 20011 60011 10010 70010 300
24 80023 70022 70021 80021 000
16001700180019002000
151146142138134
316306296288280
595576558542527
12201180115011101080
18301770172016701620
35303410331032103120
56205440527051204980
10 0009610932090508800
20 30019 60019 00018 40018 000
196 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-11 1216.2(6)SCHEDULE 40 METALLIC PIPE [NFPA 54-12: TABLE 6.2(eg)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: 5.0 psiPRESSURE DROP: 3.5 psiSPECIFIC GRAVITY: 0.60
PIPE SIZE (inch)NOMINAL: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH(feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
31902250184015901430
64304550372032202880
11 8008320679058805260
24 20017 10014 00012 10010 800
36 20025 60020 90018 10016 200
69 70049 30040 30034 90031 200
111 00078 60064 20055 60049 700
196 000139 000113 00098 20087 900
401 000283 000231 000200 000179 000
60708090100
1300120011501060979
26302430233021501980
48004450426039203620
98609130854080507430
14 80013 70012 80012 10011 100
28 50026 40024 70023 20021 400
45 40042 00039 30037 00034 200
80 20074 30069 50065 50060 400
164 000151 000142 000134 000123 000
125150175200250
876786728673558
17701590147013601170
32402910269024902200
66405960552051004510
99508940827076506760
19 20017 20015 90014 70013 000
30 60027 40025 40023 50020 800
54 00048 50044 90041 50036 700
110 00098 90091 60084 70074 900
300350400450500
506465433406384
1060973905849802
19901830171016001510
40903760350032903100
61305640525049204650
11 80010 90010 10094808950
18 80017 30016 10015 10014 300
33 30030 60028 50026 70025 200
67 80062 40058 10054 50051 500
550600650700750
364348333320308
762727696669644
14401370131012601210
29502810269025902490
44204210403038803730
85008110777074607190
13 60012 90012 40011 90011 500
24 00022 90021 90021 00020 300
48 90046 60044 60042 90041 300
8008509009501000
298288279271264
622602584567551
11701130110010701040
24102330226021902130
36103490338032903200
69406720652063306150
11 10010 70010 40010 1009810
19 60018 90018 40017 80017 300
39 90038 60037 40036 40035 400
11001200130014001500
250239229220212
524500478460443
987941901866834
20301930185017801710
30302900277026602570
58405580534051304940
93208890851081807880
16 50015 70015 00014 50013 900
33 60032 00030 70029 50028 400
16001700180019002000
205198192186181
428414401390379
806780756734714
16501600155015101470
24802400233022602200
47704620448043504230
76107360714069306740
13 40013 00012 60012 30011 900
27 40026 50025 70025 00024 300
197UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-12 1216.2(7)SEMI-RIGID COPPER TUBING [NFPA 54-12: TABLE 6.2(fh)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Notes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.3 in. w.c.SPECIFIC GRAVITY: 0.60
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
20141110NA
4229232017
8558474035
148102827062
2101441169988
448308247211187
806554445381337
1270873701600532
26501820146012501110
60708090100
NANANANANA
1614131312
3229272624
5652484543
7973686460
170156145136129
306281262245232
482443413387366
1000924859806761
125150175200250
NANANANANA
1110NANANA
2220181715
3834312926
5348454137
114103958978
206186171159141
324294270251223
675612563523464
300350400450500
NANANANANA
NANANANANA
1312111110
2322201918
3331282725
7165615754
12811811010397
202186173162153
420387360338319
550600650700750
NANANANANA
NANANANANA
NANANANANA
1716151514
2423222120
5149474543
9288848178
145139133128123
303289277266256
8008509009501000
NANANANANA
NANANANANA
NANANANANA
1413131312
2019181817
4240393837
7573716967
119115111108105
247239232225219
11001200130014001500
NANANANANA
NANANANANA
NANANANANA
12111110NA
1616151414
3534323130
6360585654
10095918884
208199190183176
16001700180019002000
NANANANANA
NANANANANA
NANANANANA
NANANANANA
1313131212
2928272625
5250494746
8279777472
170164159155151
198 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-13 1216.2(8)SEMI-RIGID COPPER TUBING [NFPA 54-12: TABLE 6.2(gi)]
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 0.60
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
2718151311
5538302623
11177615347
1951341079282
276190152131116
590406326279247
1060730586502445
16801150925791701
34902400193016501460
60708090100
10NANANANA
2119181716
4239363432
7468635956
10596908479
224206192180170
403371345324306
635585544510482
13201220113010601000
125150175200250
NANANANANA
14131211NA
2826242220
5045413934
7064595548
151136125117103
271245226210186
427387356331294
890806742690612
300350400450500
NANANANANA
NANANANANA
1816151413
3128262523
4440383533
9486807571
169155144135128
266245228214202
554510474445420
550600650700750
NANANANANA
NANANANANA
1312121111
2221202019
3230292827
6864625957
122116111107103
192183175168162
399381365350338
8008509009501000
NANANANANA
NANANANANA
1010NANANA
1818171716
2625242423
5553525049
9996939088
156151147143139
326315306297289
11001200130014001500
NANANANANA
NANANANANA
NANANANANA
1515141313
2221201918
4644424139
8480767371
132126120116111
274262251241232
16001700180019002000
NANANANANA
NANANANANA
NANANANANA
1312121111
1817171616
3837363534
6866646260
1081041019895
224217210204199
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Notes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
199UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-14 1216.2(9)SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2(hj)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Notes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 1.0 in. w.c.SPECIFIC GRAVITY: 0.60
INTENDED USE: TUBE SIZING BETWEEN HOUSE LINE REGULATOR AND THE APPLIANCE.TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
3927211816
8055443833
162111897768
283195156134119
402276222190168
859590474406359
15501060853730647
24401680135011501020
50803490280024002130
60708090100
1513131211
3028262423
6157534947
10799928682
152140131122116
326300279262247
586539502471445
925851791742701
19301770165015501460
125150175200250
NANANANANA
2018171614
4137343228
7265605650
10393857970
219198183170151
394357329306271
622563518482427
1290117010801000890
300350400450500
NANANANANA
13121110NA
2624222120
4541393634
6459555148
136125117110103
245226210197186
387356331311294
806742690647612
550600650700750
NANANANANA
NANANANANA
1918171616
3231302827
4644424039
9894908683
177169162155150
279266255245236
581554531510491
8008509009501000
NANANANANA
NANANANANA
1515141413
2626252423
3836353433
8078757371
144140135132128
228220214207202
474459445432420
11001200130014001500
NANANANANA
NANANANANA
1312121111
2221202019
3230292827
6864625957
122116111107103
192183175168162
399381365350338
16001700180019002000
NANANANANA
NANANANANA
1010NANANA
1818171716
2625242423
5553525049
9996939088
156151147143139
326315306297289
200 UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 17.0 in. w.c.SPECIFIC GRAVITY: 0.60
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
1901301059079
391269216185164
796547439376333
1390956768657582
197013601090932826
42202900233019901770
75905220419035903180
12 0008230661056505010
24 90017 10013 80011 80010 400
60708090100
7266625855
148137127119113
302278258243229
528486452424400
749689641601568
16001470137012801210
28802650246023102180
45404180389036503440
94608700809075907170
125150175200250
4844403833
10090837769
203184169157140
355321296275244
503456420390346
1080974896834739
19401750161015001330
30502770254023702100
63605760530049304370
300350400450500
3028262423
6257535047
12611610810296
221203189177168
313288268252238
670616573538508
121011101030968914
19001750163015301440
39603640339031803000
550600650700750
2221201918
4543413938
9187838077
159152145140135
226215206198191
482460441423408
868829793762734
13701310125012001160
28502720261025002410
8008509009501000
1817171616
3735343332
7472706866
130126122118115
184178173168163
394381370359349
709686665646628
1120108010501020991
23302250218021202060
11001200130014001500
1514141313
3129282726
6360575553
1091041009693
155148142136131
332316303291280
597569545524505
941898860826796
19601870179017201660
16001700180019002000
1212111111
2524242322
5149484745
8986848179
127123119115112
271262254247240
487472457444432
768744721700681
16001550150014601420
TABLE 12-15 1216.2(10)SEMI-RIGID COPPER TUBING [NFPA 54-12: TABLE 6.2(ik)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column =0.249 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note:All tTable entries are rounded to 3 significant digits.
201UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-16 1216.2(11)SEMI-RIGID COPPER TUBING [NFPA 54-12: TABLE 6.2(jl)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note:All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 0.60
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
245169135116103
506348279239212
1030708568486431
18001240993850754
25501760141012101070
54503750301025802280
98206750542046404110
15 50010 600855073106480
32 20022 20017 80015 20013 500
60708090100
9386807571
192177164154146
391359334314296
683628584548518
969891829778735
20701900177016601570
37303430319029902830
58705400503047204450
12 20011 30010 50098209280
125150175200250
6357524943
12911710810089
263238219204181
459416383356315
651590543505448
1390126011601080956
25002270209019401720
39503580329030602710
82207450685063805650
300350400450500
3936333130
8074696561
164150140131124
286263245230217
406373347326308
866797741696657
15601430133012501180
24602260210019701870
51204710438041103880
550600650700750
2827262524
5855535149
118112108103100
206196188181174
292279267256247
624595570548528
112010701030986950
17701690162015501500
36903520337032403120
8008509009501000
2322222120
4746444342
9693908885
168163158153149
239231224217211
510493478464452
917888861836813
14501400136013201280
30102920283027402670
11001200130014001500
1918181716
4038363534
8177747168
142135129124120
201192183176170
429409392376363
772737705678653
12201160111010701030
25402420232022302140
16001700180019002000
1615151414
3331303029
6664626059
116112108105102
164159154149145
350339329319310
630610592575559
994962933906881
20702000194018901830
202 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-17 1216.2(12)SEMI-RIGID COPPER TUBING [NFPA 54: TABLE 6.2(km)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa*1 Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.†2 WhenWhere this table is used to size the tubing upstream of a line pressure regulator, the pipe or tubing downstream of the line pressure regulator shall besized using a pressure drop no greater than 1 in. w.c. inch water column (0.249 kPa)
Note: All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.5 psiSPECIFIC GRAVITY: 0.60
INTENDED USE: PIPE SIZING BETWEEN POINT OF DELIVERY AND THE HOUSE LINE REGULATOR. TOTAL LOAD SUPPLIED BY ASINGLE HOUSE LINE REGULATOR NOT EXCEEDING 150 CUBIC FEET PER HOUR.†2
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125
INSIDE:*1 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
303208167143127
625430345295262
1270874702601532
2220153012301050931
31502170174014901320
67404630372031802820
12 1008330669057305080
19 10013 10010 60090308000
39 80027 40022 00018 80016 700
60708090100
115106989287
237218203190180
482444413387366
843776722677640
120011001020961907
25602350219020501940
46004230394036903490
72506670621058205500
15 10013 90012 90012 10011 500
125150175200250
7770646053
159144133124110
324294270252223
567514472440390
804729670624553
17201560143013301180
30902800258024002130
48804420406037803350
10 2009200846078706980
300350400450500
4844413936
9991858075
202186173162153
353325302283268
501461429402380
1070984916859811
19301770165015501460
30402790260024402300
63205820541050804800
550600650700750
3533323029
7268656360
146139133128123
254243232223215
361344330317305
771735704676652
13901320127012201170
21902090200019201850
45604350416040003850
8008509009501000
2827272625
5857555352
119115111108105
208201195189184
295285276268261
629609590573558
11301100106010301000
17901730168016301580
37203600349033903300
11001200130014001500
2423222120
4947454342
10095918885
175167160153148
248237227218210
530505484465448
954910871837806
15001430137013201270
31302990286027502650
16001700180019002000
1919181817
4039383736
8279777472
143138134130126
202196190184179
432419406394383
779753731709690
12301190115011201090
25602470240023302270
203UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: 5.0 psiPRESSURE DROP: 3.5 psiSPECIFIC GRAVITY: 0.60
TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN CUBIC FEET OF GAS PER HOUR1020304050
511351282241214
1050724582498441
2140147011801010898
37502580207017701570
53203650293025102230
11 4007800627053604750
20 40014 00011 30096608560
32 20022 20017 80015 20013 500
67 10046 10037 00031 70028 100
60708090100
194178166156147
400368342321303
813748696653617
14201310122011401080
20201860173016201530
43103960369034603270
77507130664062305880
12 20011 20010 50098209270
25 50023 40021 80020 40019 300
125150175200250
13011810910190
269243224208185
547495456424376
955866796741657
1360123011301050932
29002620241022501990
52104720435040403580
82207450685063705650
17 10015 50014 30013 30011 800
300350400450500
8175696562
167154143134127
340313291273258
595547509478451
844777722678640
18001660154014501370
32502990278026102460
51204710438041103880
10 7009810912085608090
550600650700750
5856535149
121115110106102
245234224215207
429409392376362
608580556534514
13001240119011401100
23402230214020501980
36903520337032403120
76807330702067406490
8008509009501000
4846454342
9895929087
200194188182177
350339328319310
497481466452440
106010301000967940
19101850179017401690
30102910282027402670
62706070588057105560
11001200130014001500
4038373534
8379767370
169161154148143
295281269259249
418399382367353
893852816784755
16101530147014101360
25302420232022202140
52805040482046304460
16001700180019002000
3332313029
6865636260
138133129125122
241233226219213
341330320311302
729705684664646
13101270123012001160
20702000194018901830
43104170404039303820
TABLE 12-18 1216.2(13)SEMI-RIGID COPPER TUBING [NFPA 54-12: TABLE 6.2(ln)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note: All tTable entries are rounded to 3 significant digits.
204 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-19 1216.2(14)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-12: TABLE 6.2(mo)]
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be in-creased by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fit-tings, and/or bends, or both.
(2) All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 0.60
TUBE SIZE (EHD)*FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR510152025
4632252219
6344353127
11582665852
13495776760
225161132116104
270192157137122
471330267231206
546383310269240
895639524456409
1037746615536482
179012601030888793
2070147012001050936
36602600214018501660
41402930240020801860
30405060
18151312
25211917
47413734
55474238
96837568
112978780
188162144131
218188168153
374325292267
442386347318
723625559509
856742665608
1520132011801080
1700147013201200
708090100
1110109
16151413
31292826
36333230
63605754
74696562
121113107101
141132125118
248232219208
295277262249
471440415393
563527498472
1000940887843
11101040983933
150200250300
7655
10987
20181615
23211917
42383432
48443936
78716357
91827467
17114813395
205179161148
320277247226
387336301275
691600538492
762661591540
205UNIFORM PLUMBING CODE
FUEL PIPING
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be in-creased by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fit-tings, and/or bends, or both.
(2) All tTable entries are rounded to 3 significant digits.
TABLE 12-20 1216.2(15)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-12: TABLE 6.2(np)]
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 3.0 in. w.c.SPECIFIC GRAVITY: 0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 8.0 INCH WATER COLUMN OR GREATER.TUBE SIZE (EHD)*
FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 46 48 60 62LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
510152025
12083675751
160112907869
277197161140125
327231189164147
529380313273245
649462379329295
1180828673580518
1370958778672599
2140153012501090978
44303200254022001960
50103560291025302270
88006270514044604000
10 1007160585050704540
30405060
46393532
63544844
1151008982
13411610495
225196176161
270234210192
471407363330
546471421383
895778698639
1790155013801260
2070180016101470
3660318028502600
4140359032102930
708090100
29272624
41383634
76716763
88827773
150141133126
178167157149
306285268254
355331311295
593555524498
117010901030974
1360128012001140
2420226021402030
2720254024002280
150200250300
19171513
27232119
52454037
60524642
104918275
1221069587
206178159144
240207184168
409355319234
793686613559
936812728665
1660144012901180
1860161014401320
206 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-21 1216.2(16)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-12: TABLE 6.2(oq)]
For SI units: 1 foot = 304.8 mm 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD,the greater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be in-
creased by an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additionalfittings, and/or bends, or both.
(2) All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 6.0 in. w.c.SPECIFIC GRAVITY: 0.60
INTENDED USE: INITIAL SUPPLY PRESSURE OF 11.0 INCH WATER COLUMN OR GREATER.TUBE SIZE (EHD)*
FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 46 48 60 62LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
510152025
173120968374
22916013011299
389277227197176
461327267231207
737529436380342
911649532462414
16901180960828739
195013701110958855
30002140176015301370
62804430361031202790
70505010410035603190
12 4008800721062705620
14 26010 100826071606400
30405060
67575146
90786963
161140125115
189164147134
313273245225
379329295270
673580518471
778672599546
12501090978895
2540220019601790
2910253022702070
5140446040003660
5850507045404140
708090100
42393735
58545148
1061009489
124116109104
209196185176
250234221210
435407383363
505471444421
830778735698
1660155014601380
1920180017001610
3390318030002850
3840359033903210
150200250300
28242119
39343027
73635752
85736660
145126114104
172149134122
294254226206
342295263240
573498447409
1130974870793
132011401020936
2340203018201660
2630228020401860
207UNIFORM PLUMBING CODE
FUEL PIPING
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 3⁄4 0.75 psi (5.17 kPa), do not use this table. Consult with
regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary are capable of varying with flow rate.(2) CAUTION: Capacities shown in table may exceed are capable of exceeding the maximum capacity for a selected regulator. Consult with regulator or tubing
manufacturer for guidance.(3) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be increased
by an equivalent length of tubing according to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fit-tings, and/or bends, or both.
(4) All tTable entries are rounded to 3 significant digits.
TABLE 12-22 1216.2(17)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-12: TABLE 6.2(pr)]
GAS: NATURALINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 0.60
TUBE SIZE (EHD)*FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR1025304050
270166151129115
353220200172154
587374342297266
700444405351314
1100709650567510
1370876801696624
25901620148012701140
29901870170014701310
45102890264023002060
50373258298726052343
96006040551047604260
10 7006780620053804820
18 60011 90010 90094408470
21 60013 70012 50010 9009720
7580100150200
9389796455
1241201078775
218211189155135
257249222182157
420407366302263
512496445364317
922892795646557
10701030920748645
16901640147012101050
19321874168513891212
34703360300024402110
39503820342028002430
69406730603049404290
79407690688056204870
250300400500
49443834
67615246
1211109686
141129111100
236217189170
284260225202
497453390348
576525453404
941862749552
1090999871783
1890172014901330
2180199017301550
3850352030602740
4360398034503090
208 UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: 5.0 psiPRESSURE DROP: 3.5 psiSPECIFIC GRAVITY: 0.60
TUBE SIZE (EHD)*FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR1025304050
523322292251223
674420382329293
1080691632549492
1300827755654586
2000129011801030926
25301620148012801150
49203080280024202160
56603540323027902490
83005310486042303790
91405911542047274251
18 10011 4001040089708020
19 80012 60011 50010 0008930
34 40022 00020 10017 40015 600
40 40025 60023 40020 20018 100
7580100150200
180174154124107
238230205166143
403391350287249
479463415339294
763740665548478
944915820672584
17501690151012301060
20201960174014201220
31103020271022201930
35063400305725212199
65306320565046003980
73207090635052004510
12 80012 40011 10091307930
14 80014 30012 80010 5009090
250300400500
95867466
12811610089
223204177159
263240208186
430394343309
524479416373
945860742662
1090995858766
1730159013801040
1977181315811422
3550324028002500
4040369032102870
7110650056505060
8140743064405760
For SI units: 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi (6.89 kPa), do not use this table. Consult with regu-lator manufacturer for pressure drops and capacity factors. Pressure drops across regulator may vary are capable of varying with the flow rate.
(2) CAUTION: Capacities shown in table may exceed are capable of exceeding the maximum capacity of selected regulator. Consult tubing manufacturer for guid-ance.
(3) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be increasedby an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittings, and/orbends, or both.
(4) All tTable entries are rounded to 3 significant digits.
TABLE 12-23 1216.2(18)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-12: TABLE 6.2(qs)]
209UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.3 in. w.c.SPECIFIC GRAVITY: 0.60
PIPE SIZE (inch)NOMINAL OD: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 3 4DESIGNATION: SDR 9.33 SDR 11.00 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 SDR 11 SDR 11ACTUAL ID: 0.660 0.860 1.077 1.328 1.554 1.943 2.864 3.682LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
153105847264
305210169144128
551379304260231
955656527451400
1440991796681604
25901780143012201080
71704920395033803000
13 9009520764065405800
60708090100
5853504644
116107999388
209192179168159
362333310291275
547503468439415
983904841789745
27202500233021802060
52504830450042203990
125150175200250
3935323027
7871656054
14112711710997
243221203189167
368333306285253
661598551512454
18301660152014201260
35303200294027402430
300350400450500
2422211918
4845423937
8881757066
152139130122115
229211196184174
411378352330312
11401050974914863
22002020188017701670
TABLE 12-24 1216.2(19)POLYETHYLENE PLASTIC PIPE [NFPA 54-12: TABLE 6.2(rt)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249 kPaNote: All tTable entries are rounded to 3 significant digits.
210 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-25 1216.2(20)POLYETHYLENE PLASTIC PIPE [NFPA 54-12: TABLE 6.2(su)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water column = 0.249 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: NATURALINLET PRESSURE: LESS THAN 2 psiPRESSURE DROP: 0.5 in. w.c.SPECIFICGRAVITY: 0.60
PIPE SIZE (inch)NOMINAL OD: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 3 4DESIGNATION: SDR 9.33 SDR 11.00 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 SDR 11 SDR 11ACTUAL ID: 0.660 0.860 1.077 1.328 1.554 1.943 2.864 3.682LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
2011381119584
403277222190169
726499401343304
1260865695594527
190013101050898796
34102350188016101430
94506490521044603950
18 26012 55010 08086307640
60708090100
7670656158
153140131123116
276254236221209
477439409383362
721663617579547
1300119011101040983
35803300307028802720
69306370593055605250
125150175200250
5146434035
10393868071
185168154144127
321291268249221
485439404376333
871789726675598
24102180201018701660
46604220388036103200
300350400450500
3229272624
6459555148
115106999388
200184171160152
302278258242229
542499464435411
15001380128012001140
29002670248023302200
211UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFICGRAVITY: 0.60
PIPE SIZE (inch)NOMINAL OD: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 3 4DESIGNATION: SDR 9.33 SDR 11.00 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 SDR 11 SDR 11ACTUAL ID: 0.660 0.860 1.077 1.328 1.554 1.943 2.864 3.682LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
186012801030878778
37202560205017601560
67104610371031702810
11 6007990642054904870
17 60012 100969083007350
31 60021 70017 40014 90013 200
87 30060 00048 20041 20036 600
169 000116 00093 20079 70070 700
60708090100
705649603566535
4101300121011301070
25502340218020501930
44104060378035403350
66606130570053505050
12 00011 00010 20096109080
33 10030 50028 30026 60025 100
64 00058 90054 80051 40048 600
125150175200250
474429395368326
949860791736652
17101550143013301180
29702690247023002040
44804060373034703080
80507290671062405530
22 30020 20018 60017 30015 300
43 00039 00035 90033 40029 600
300350400450500
295272253237224
591544506475448
1070981913856809
18501700158014801400
27902570239022402120
50104610429040203800
13 90012 80011 90011 10010 500
26 80024 70022 90021 50020 300
550600650700750
213203194187180
426406389374360
768733702674649
13301270122011701130
20101920184017601700
36103440330031703050
99909530913087708450
19 30018 40017 60016 90016 300
8008509009501000
174168163158154
348336326317308
627607588572556
109010501020990963
16401590154015001450
29502850277026902610
81607890765074307230
15 80015 30014 80014 40014 000
11001200130014001500
146139134128124
293279267257247
528504482463446
915873836803773
13801320126012101170
24802370227021802100
68706550627060305810
13 30012 70012 10011 60011 200
16001700180019002000
119115112109106
239231224218212
431417404393382
747723701680662
11301090106010301000
20301960190018501800
56105430526051104970
10 80010 50010 20099009600
TABLE 12-26 1216.2(21)POLYETHYLENE PLASTIC PIPE [NFPA 54-12: TABLE 6.2(tv)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour = 0.00787 L/s, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
212 UNIFORM PLUMBING CODE
FUEL PIPING
GAS: NATURALINLET PRESSURE: LESS THAN 2.0 psiPRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 0.60PLASTIC TUBING SIZE (CTS)* (inch)
NOMINAL OD: 1⁄2 3⁄4DESIGNATION: SDR 7.00 SDR 11.00ACTUAL ID: 0.445 0.927LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
7249393430
490337271232205
60708090100
2725232221
186171159149141
125150175200
18171514
12511310497
225250275300
13121111
91868278
350400450500
10NANANA
72676359
TABLE 12-27 1216.2(22)POLYETHYLENE PLASTIC TUBING [NFPA 54-12: TABLE 6.2(uw)]
TABLE 12-28 1216.2(23)POLYETHYLENE PLASTIC TUBING [NFPA 54-12: TABLE 6.2(vx)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour =0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water col-umn = 0.249 kPa* CTS = Copper tube size.Notes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1 cubic foot per hour =0.00787 L/s, 1 pound-force per square inch = 6.894 kPa, 1 inch water col-umn = 0.249 kPa* CTS = Copper tube size.Notes:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10 cfh ft3/h (0.08 L/s).
GAS: NATURALINLET PRESSURE: LESS THAN 2.0 psiPRESSURE DROP: 0.3 in. w.c.SPECIFIC GRAVITY: 0.60PLASTIC TUBING SIZE (CTS)* (inch)
NOMINAL OD: 1⁄2 3⁄4DESIGNATION: SDR 7.00 SDR 11.00ACTUAL ID: 0.445 0.927LENGTH (feet) CAPACITY IN CUBIC FEET OF GAS PER HOUR
1020304050
5437302623
372256205176156
60708090100
2119181716
141130121113107
125150175200
14131211
95867974
225250275300
10NANANA
69656259
350400450500
NANANANA
54514745
213UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-29 1216.2(24)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3(a)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 10.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: PIPE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE REGULATOR) AND SECOND STAGE (LOW PRESSURE REGULATOR).PIPE SIZE (inch)
NOMINALINSIDE:
1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4
ACTUAL: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
33202280183015701390
69504780384032802910
13 1009000722061805480
26 90018 50014 80012 70011 300
40 30027 70022 20019 00016 900
77 60053 30042 80036 60032 500
124 00085 00068 20058 40051 700
219 000150 000121 000103 00091 500
446 000306 000246 000211 000187 000
60708090100
1260116010801010956
26402430226021202000
49704570425039903770
10 2009380873081907730
15 30014 10013 10012 30011 600
29 40027 10025 20023 60022 300
46 90043 10040 10037 70035 600
82 90076 30070 90066 60062 900
169 000156 000145 000136 000128 000
125150175200250
848768706657582
17701610148013701220
33403020278025902290
68506210571053204710
10 3009300856079607060
19 80017 90016 50015 30013 600
31 50028 60026 30024 40021 700
55 70050 50046 50043 20038 300
114 000103 00094 70088 10078 100
300350400450500
528486452424400
11001020945886837
20801910178016701580
42703930365034303240
64005880547051404850
12 30011 30010 50098909340
19 60018 10016 80015 80014 900
34 70031 90029 70027 90026 300
70 80065 10060 60056 80053 700
550600650700750
380363347334321
795759726698672
15001430137013101270
30702930281027002600
46104400421040403900
88708460811077907500
14 10013 50012 90012 40012 000
25 00023 90022 80021 90021 100
51 00048 60046 60044 80043 100
8008509009501000
310300291283275
649628609592575
12201180115011101080
25102430236022902230
37603640353034303330
72407010680066006420
11 50011 20010 80010 50010 200
20 40019 80019 20018 60018 100
41 60040 30039 10037 90036 900
11001200130014001500
261249239229221
546521499480462
1030982940903870
21102020193018501790
31703020289027802680
61005820557053505160
97209270888085308220
17 20016 40015 70015 10014 500
35 00033 40032 00030 80029 600
16001700180019002000
213206200194189
446432419407395
840813789766745
17301670162015701530
25902500243023602290
49804820467045404410
79407680745072307030
14 00013 60013 20012 80012 400
28 60027 70026 90026 10025 400
214 UNIFORM PLUMBING CODE
FUEL PIPING
GAS: UNDILUTED PROPANEINLET PRESSURE: 10.0 psiPRESSURE DROP: 3.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: PIPE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE REGULATOR) AND SECOND STAGE (LOW PRESSURE REGULATOR).PIPE SIZE (inch)
NOMINALINSIDE:
1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4
ACTUAL: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
58904050325027802460
12 3008460679058105150
23 20015 90012 80011 0009710
47 60032 70026 30022 50019 900
71 30049 00039 40033 70029 900
137 00094 40075 80064 90057 500
219 000150 000121 000103 00091 600
387 000266 000214 000183 000162 000
789 000543 000436 000373 000330 000
60708090100
22302050191017901690
46704300400037503540
87908090753070606670
18 10016 60015 50014 50013 700
27 10024 90023 20021 70020 500
52 10047 90044 60041 80039 500
83 00076 40071 10066 70063 000
147 000135 000126 000118 000111 000
299 000275 000256 000240 000227 000
125150175200250
15001360125011601030
31402840262024302160
59105360493045804060
12 10011 00010 10094108340
18 20016 50015 20014 10012 500
35 00031 70029 20027 20024 100
55 80050 60046 50043 30038 400
98 70089 40082 30076 50067 800
201 000182 000167 800156 100138 400
300350400450500
935860800751709
19501800167015701480
36803390315029602790
75606950647060705730
11 30010 400969090908590
21 80020 10018 70017 50016 500
34 80032 00029 80027 90026 400
61 50056 50052 60049 40046 600
125 400115 300107 300100 70095 100
550600650700750
673642615591569
14101340129012401190
26502530242023302240
54505200498047804600
81607780745071606900
15 70015 00014 40013 80013 300
25 00023 90022 90022 00021 200
44 30042 20040 50038 90037 400
90 30086 20082 50079 30076 400
8008509009501000
550532516501487
11501110108010501020
21702100203019701920
44504300417040503940
66606450625060705900
12 80012 40012 00011 70011 400
20 50019 80019 20018 60018 100
36 20035 00033 90032 90032 000
73 70071 40069 20067 20065 400
11001200130014001500
463442423406391
968923884849818
18201740167016001540
37403570342032803160
56105350512049204740
10 80010 300987094809130
17 20016 40015 70015 10014 600
30 40029 00027 80026 70025 700
62 10059 20056 70054 50052 500
16001700180019002000
378366355344335
790765741720700
14901440140013601320
30602960287027802710
45804430430041704060
88208530827080407820
14 10013 60013 20012 80012 500
24 80024 00023 30022 60022 000
50 70049 00047 60046 20044 900
TABLE 12-30 1216.2(25)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3(b)]
For SI units:1 inch = 25 mm 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
215UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-31 1216.2(26)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3(c)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: PIPE SIZING BETWEEN 2 PSI SERVICE AND LINE PRESSURE REGULATORPIPE SIZE (inch)
NOMINAL 1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4
ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
26801840148012601120
55903850309026402340
10 5007240582049804410
21 60014 90011 90010 2009060
32 40022 30017 90015 30013 600
62 40042 90034 50029 50026 100
99 50068 40054 90047 00041 700
176 000121 00097 10083 10073 700
359 000247 000198 000170 000150 000
60708090100
1010934869815770
21201950182017001610
40003680342032103030
82107550702065906230
12 30011 30010 50098809330
23 70021 80020 30019 00018 000
37 70034 70032 30030 30028 600
66 70061 40057 10053 60050 600
136 000125 000116 000109 000103 000
125150175200250
682618569529469
1430129011901110981
26902440224020801850
55205000460042803790
82707490689064105680
15 90014 40013 30012 30010 900
25 40023 00021 20019 70017 400
44 90040 70037 40034 80030 800
91 50082 90076 30071 00062 900
300350400450500
425391364341322
889817760714674
16701540143013401270
34403160294027602610
51504740441041303910
99209120849079607520
15 80014 50013 50012 70012 000
27 90025 70023 90022 40021 200
57 00052 40048 80045 80043 200
550600650700750
306292280269259
640611585562541
12101150110010601020
24802360226021702090
37103540339032603140
71406820653062706040
11 40010 90010 40099909630
20 10019 20018 40017 70017 000
41 10039 20037 50036 00034 700
8008509009501000
250242235228222
523506490476463
985953924897873
20201960190018401790
30302930284027602680
58305640547053105170
93009000872084708240
16 40015 90015 40015 00014 600
33 50032 40031 50030 50029 700
11001200130014001500
210201192185178
440420402386372
829791757727701
17001620155014901440
25502430233022402160
49104680449043104150
78307470715068706620
13 80013 20012 60012 10011 700
28 20026 90025 80024 80023 900
16001700180019002000
172166161157152
359348337327318
677655635617600
13901340130012701230
20802010195019001840
40103880376036503550
63906180600058205660
11 30010 90010 60010 30010 000
23 00022 30021 60021 00020 400
216 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-32 1216.2(27)SCHEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.3(d)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPaNote: All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 11.0 in. w.c.PRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 1.50
INTENDED USE: PIPE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE REGULATOR) AND APPLIANCEPIPE SIZE (inch)
NOMINALINSIDE:
1⁄2 3⁄4 1 11⁄4 11⁄2 2 21⁄2 3 4
ACTUAL ID: 0.622 0.824 1.049 1.380 1.610 2.067 2.469 3.068 4.026LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
291200160137122
608418336287255
1150787632541480
2350162013001110985
35202420194016601480
67904660375032102840
10 8007430597051104530
19 1001310010 60090308000
39 00026 80021 50018 40016 300
6080100125150
110101948984
231212197185175
434400372349330
892821763716677
13401230114010701010
25702370220020701950
41003770351032903110
72506670621058205500
14 80013 60012 70011 90011 200
175200250300350
7467625851
155140129120107
292265243227201
600543500465412
899814749697618
17301570144013401190
27602500230021401900
48804420406037803350
99509010829077106840
400450500550600
4642403735
9789837873
182167156146138
373344320300283
560515479449424
1080991922865817
17201580147013801300
30402790260024402300
61905700530049704700
650700750800850
3332302928
7066646159
131125120115111
269257246236227
403385368354341
776741709681656
12401180113010901050
21902090200019201850
44604260408039203770
900950100011001200
2726252524
5755535250
1071041009795
220213206200195
329319309300292
634613595578562
1010978948921895
17901730168016301580
36403530342033203230
13001400150016001700
2322212019
4846444240
9086827976
185176169162156
277264253243234
534509487468451
850811777746719
15001430137013201270
30702930280026902590
180019002000
191818
393837
747169
151146142
226219212
436422409
694672652
123011901150
250024202350
217UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-33 1216.2(28)SEMI-RIGID COPPER TUBING [NFPA 54-09: TABLE 6.3(e)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note: All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 10.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: TUBE SIZING BETWEEN FIRST STAGE (HIGH PRESSURE) REGULATORAND SECOND STAGE (LOW PRESSURE) REGULATOR.TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR1020304050
513352283242215
1060727584500443
2150148011901020901
37602580208017801570
53303670294025202230
11 4007830629053804770
20 50014 10011 30096908590
32 30022 20017 90015 30013 500
67 40046 30037 20031 80028 200
60708090100
194179166156147
401369343322304
816751699655619
14301310122011501080
20201860173016301540
43203980370034703280
77807160666062505900
12 30011 30010 50098509310
25 60023 50021 90020 50019 400
125150175200250
13111810910190
270244225209185
549497457426377
959869799744659
1360123011301060935
29102630242022502000
52304740436040603600
82507470688064005670
17 20015 60014 30013 30011 800
300350400450500
8175706562
168155144135127
342314292274259
597549511480453
847779725680643
18101660155014501370
32603000279026202470
51404730440041303900
10 7009840916085908120
550600650700750
5956545150
121115111106102
246235225216208
430410393378364
610582558536516
13001240119011401100
23502240214020601980
37003530338032503130
77107350704067706520
8008509009501000
4846454442
9996939088
201195189183178
351340330320311
498482468454442
106010301000970944
19201850180017501700
30202920284027502680
62906090591057305580
11001200130014001500
4038373534
8379767370
169161155148143
296282270260250
420400383368355
896855819787758
16101540147014201360
25402430232022302150
53005050484046504480
16001700180019002000
3332313029
6866646260
138134130126122
241234227220214
343331321312304
732708687667648
13201270124012001170
20802010195018901840
43304190406039403830
218 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-34 1216.2(29)SEMI-RIGID COPPER TUBING [NFPA 54-09: TABLE 6.3(f)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note:(1) All tTable entries are rounded to 3 significant digits.(2) NAmeans a flow of less than 10,000 Btu/hr. (2.90 kW)
GAS: UNDILUTED PROPANEINLET PRESSURE: 11.0 in. w.c.PRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 1.50
INTENDED USE: TUBE SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE REGULATOR) AND APPLIANCE.TUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR1020304050
4531252119
9364514439
1881291048979
329226182155138
467321258220195
997685550471417
18001230991848752
28301950156013401180
58904050325027802470
60708090100
1716151413
3532302827
7166615754
12511510710095
177163152142134
378348324304287
681626583547517
1070988919862814
22402060191018001700
125150175200250
1110NANANA
2421201816
4844403733
8476706558
119108999282
254230212197175
458415382355315
722654602560496
15001360125011701030
300350400450500
NANANANANA
1514131211
3028262423
5248454240
7468636056
158146136127120
285262244229216
449414385361341
936861801752710
550600650700750
NANANANANA
1110NANANA
2221201918
3836343332
5351494745
11410910410096
205196188180174
324309296284274
674643616592570
8008509009501000
NANANANANA
NANANANANA
1817171616
3130292827
4442414039
9390878583
168162157153149
264256248241234
551533517502488
11001200130014001500
NANANANANA
NANANANANA
1514141313
2625242322
3735343231
7875726966
141135129124119
223212203195188
464442423407392
16001700180019002000
NANANANANA
NANANANANA
1212111111
2120201919
3029282727
6462605857
115112108105102
182176170166161
378366355345335
219UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-35 1216.2(30)SEMI-RIGID COPPER TUBING [NFPA 54-09: TABLE 6.3(g)]
For SI units:1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPa*Table capacities are based on Type K copper tubing inside diameter (shown), which has the smallest inside diameter of the copper tubing products.Note: All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: TUBE SIZING BETWEEN 2 PSIG SERVICE AND LINE PRESSURE REGULATORTUBE SIZE (inch)
NOMINAL:K & L: 1⁄4 3⁄8 1⁄2 5⁄8 3⁄4 1 11⁄4 11⁄2 2ACR: 3⁄8 1⁄2 5⁄8 3⁄4 7⁄8 11⁄8 13⁄8 – –
OUTSIDE: 0.375 0.500 0.625 0.750 0.875 1.125 1.375 1.625 2.125INSIDE:* 0.305 0.402 0.527 0.652 0.745 0.995 1.245 1.481 1.959
LENGTH (feet.) CAPACITY IN THOUSANDS OF BTU PER HOUR1020304050
413284228195173
852585470402356
17301190956818725
30302080167014301270
43002950237020301800
91706310506043303840
16 50011 400912078006920
26 00017 90014 40012 30010 900
54 20037 30029 90025 60022 700
60708090100
157144134126119
323297276259245
657605562528498
11501060983922871
16301500139013101240
34803200298027902640
62705760536050304750
98809090845079307490
20 60018 90017 60016 50015 600
125150175200250
10595888272
217197181168149
442400368343304
772700644599531
1100992913849753
23402120195018101610
42103820351032702900
66406020554051504560
13 80012 50011 50010 7009510
300350400450500
6660565350
135124116109103
275253235221209
481442411386365
682628584548517
14601340125011701110
26202410225021101990
41403800354033203140
86107920737069206530
550600650700750
4745434140
9793898682
198189181174168
346330316304293
491469449431415
10501000959921888
18901800173016601600
29802840272026202520
62105920567054505250
8008509009501000
3937363534
8077757271
162157152147143
283274265258251
401388376366356
857829804781760
15401490145014101370
24302350228022202160
50704900475046204490
11001200130014001500
3231302827
6764615957
136130124120115
238227217209201
338322309296286
721688659633610
13001240119011401100
20501950187018001730
42704070390037403610
16001700180019002000
2626252423
5553515048
11110810410199
194188182177172
276267259251244
589570553537522
106010301000966940
16701620157015201480
34803370327031703090
220 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-36 1216.2(31)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-09: TABLE 6.3(h)]
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be increasedby an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittings, and/orbends, or both.
(2) All tTable entries are rounded to 3 significant digits.
GAS: UNDILUTED PROPANEINLET PRESSURE: 11.0 in. w.c.PRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 1.50
INTENDED USE: CSST SIZING BETWEEN SINGLE OR SECOND STAGE (LOW PRESSURE) REGULATOR AND APPLIANCE SHUTOFF VALVETUBE SIZE (EHD)*
FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR
5101520
72503934
99695549
18112910491
211150121106
355254208183
426303248216
744521422365
863605490425
1420971775661
16381179972847
2830199016201400
3270232019001650
5780411033702930
6550464037903290
25304050
30282320
42393330
82746458
94877466
164151131118
192177153137
325297256227
379344297265
583528449397
762698610548
12501140988884
1480135011701050
2630240020901870
2940268023302080
60708090
19171515
26252322
53494544
60575250
107999490
126117109102
207191178169
241222208197
359330307286
502466438414
805745696656
961890833787
1710159014901400
1900176016501550
100150200250300
1411988
2015141211
4131282523
4736333026
8566605350
9875696157
1591231129990
186143129117107
270217183163147
393324283254234
621506438390357
746611531476434
13301090948850777
148012101050934854
221UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-37 1216.2(32)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-09: TABLE 6.3(i)]
GAS: UNDILUTED PROPANEINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: CSST SIZING BETWEEN 2 PSI SERVICE AND LINE PRESSURE REGULATORTUBE SIZE (EHD)*
FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR
1025304050
426262238203181
558347316271243
927591540469420
1110701640554496
174011201030896806
2170138012701100986
41002560233020101790
47202950269023202070
71304560418036303260
79585147471941163702
15 2009550871075306730
16 80010 700979085007610
29 40018 80017 20014 90013 400
34 20021 70019 80017 20015 400
7580100150200
14714012410186
196189169137118
344333298245213
406393350287248
663643578477415
809768703575501
1460141012601020880
16901630145011801020
26802590233019101660
30532961266221951915
54805300474038603340
62306040541044303840
11 00010 600953078106780
12 60012 20010 90088907710
250300400500
77696053
105968272
191173151135
222203175158
373343298268
448411355319
785716616550
910829716638
1490136011601030
1722157813761237
2980272023502100
3440315027302450
6080556048304330
6900630054604880
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi (6.89 kPa), do not use this table. Consult with regu-lator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary are capable of varying with flow rate.
(2) CAUTION: Capacities shown in table may exceed are capable of exceeding the maximum capacity for a selected regulator. Consult with regulator or tubingmanufacturer for guidance.
(3) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be increasedby an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittings, and/orbends, or both.
(4) All tTable entries are rounded to 3 significant digits.
222 UNIFORM PLUMBING CODE
FUEL PIPING
TABLE 12-38 1216.2(33)CORRUGATED STAINLESS STEEL TUBING (CSST) [NFPA 54-09: TABLE 6.3(j)]
GAS: UNDILUTED PROPANEINLET PRESSURE: 5.0 psiPRESSURE DROP: 3.5 psiSPECIFIC GRAVITY: 1.50
TUBE SIZE (EHD)*FLOW DESIGNATION: 13 15 18 19 23 25 30 31 37 39 46 48 60 62
LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR1025304050
826509461396352
1070664603520463
17101090999867777
2060131011901030926
31502040187016301460
40002550234020301820
78304860443038203410
89505600510044003930
131008400768066805990
14 4449339856474696717
28 60018 00016 40014 20012 700
31 20019 90018 20015 80014 100
54 40034 70031 70027 60024 700
6380040 40036 90032 00028 600
7580100150200
284275243196169
376363324262226
637618553453393
757731656535464
121011701050866755
1490145013001060923
27702680239019401680
31903090276022401930
49204770428035103050
55395372483039833474
103009990893072706290
11 60011 20010 00082107130
20 30019 60017 60014 40012 500
2340022 70020 30016 60014 400
250300400500
150136117104
202183158140
352322279251
415379328294
679622542488
828757657589
1490136011701050
1730157013601210
2740251021801950
3124286524982247
5620512044303960
6390584050704540
11 20010 30089208000
12 90011 70010 2009110
For SI units: 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPa*EHD = Equivalent Hydraulic Diameter, which is a measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, thegreater the gas capacity of the tubing.Notes:(1) Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1 psi (6.89 kPa), do not use this table. Consult with regu-lator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary are capable of varying with flow rate.
(2) CAUTION: Capacities shown in table may exceed are capable of exceeding the maximum capacity for a selected regulator. Consult with regulator or tubingmanufacturer for guidance.
(3) Table includes losses for four 90 degree (1.57 rad) bends and two end fittings. Tubing runs with larger numbers of bends, and/or fittings, or both shall be increasedby an equivalent length of tubing to the following equation: L = 1.3n, where L is additional length (ft) of tubing and n is the number of additional fittings, and/orbends, or both.
(4) All tTable entries are rounded to 3 significant digits.
223UNIFORM PLUMBING CODE
FUEL PIPING
GAS: UNDILUTED PROPANEINLET PRESSURE: 11.0 in. w.c.PRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 1.50
INTENDED USE: PE SIZING BETWEEN INTEGRAL 2-STAGE REGULATOR AT TANK OR 2ND STAGE (LOW PRESSURE REGULATOR) AND BUILDINGPIPE SIZE (inch)
NOMINAL OD: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 3 4DESIGNATION: SDR 9.33 SDR 11.00 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 SDR 11 SDR 11ACTUAL ID: 0.660 0.860 1.077 1.328 1.554 1.943 2.864 3.682LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
340233187160142
680468375321285
1230844677580514
2130146011701000890
32102210177015201340
57703970318027302420
16 00011 000881075406680
30 90021 20017 00014 60012 900
60708090100
12911911010398
258237221207196
466428398374353
807742690648612
122011201040978924
21902010187017601660
60505570518048604590
11 70010 80010 00094008900
125150175200250
8778726760
173157145135119
313284261243215
542491452420373
819742683635563
14701330123011401010
40703690339031602800
79007130656061005410
300350400450500
5450464341
10899928782
195179167157148
338311289271256
510469436409387
916843784736695
25302330217020401920
49004510419039303720
TABLE 12-39 1216.2(34)POLYETHYLENE PLASTIC PIPE [NFPA 54-12: TABLE 6.3(k)]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 inch water column = 0.249 kPaNote: All tTable entries are rounded to 3 significant digits.
224 UNIFORM PLUMBING CODE
FUEL PIPING
GAS: UNDILUTED PROPANEINLET PRESSURE: 2.0 psiPRESSURE DROP: 1.0 psiSPECIFIC GRAVITY: 1.50
INTENDED USE: PE PIPE SIZING BETWEEN 2 PSI SERVICE REGULATOR AND LINE PRESSURE REGULATORPIPE SIZE (inch)
NOMINAL OD: 1⁄2 3⁄4 1 11⁄4 11⁄2 2 3 4DESIGNATION: SDR 9.33 SDR 11.00 SDR 11.00 SDR 10.00 SDR 11.00 SDR 11.00 SDR 11 SDR 11ACTUAL ID: 0.660 0.860 1.077 1.328 1.554 1.943 2.864 3.682LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
31302150173014801310
62604300345029602620
11 3007760623053304730
19 60013 40010 80092408190
29 50020 30016 30014 00012 400
5310036 50029 30025 10022 200
147 000101 00081 10069 40061 500
284 000195 000157 000134 100119 000
60708090100
119010901010952899
23702180203019101800
42803940367034403250
74206830635059605630
11 20010 300959090008500
20 10018 50017 20016 20015 300
55 70051 30047 70044 70042 300
108 00099 10092 20086 50081 700
125150175200250
797722664618548
16001450133012401100
28802610240022301980
49904520416038703430
75306830628058405180
13 50012 30011 30010 5009300
37 50033 90031 20029 00025 700
72 40065 60060 30056 10049 800
300350400450500
496457425399377
994914851798754
17901650153014401360
31102860266025002360
46904320402037703560
84307760722067706390
23 30021 50012 00018 70017 700
45100415003860036 20034 200
550600650700750
358341327314302
716683654628605
12901230118011301090
22402140204019601890
33803220309029702860
60705790555053305140
16 80016 00015 40014 70014 200
32 50031 00029 70028 50027 500
8008509009501000
292283274266259
585566549533518
10501020990961935
18301770171016701620
27602670259025202450
49604800465045204400
13 70013 30012 90012 50012 200
26 50025 70024 90024 20023 500
11001200130014001500
246234225216208
492470450432416
888847811779751
15401470141013501300
23202220212020401960
41703980381036603530
11 50011 00010 60010 1009760
22 30021 30020 40019 60018 900
16001700180019002000
201194188183178
402389377366356
725702680661643
12601220118011401110
19001840178017301680
34103300320031103020
94309130885085908360
18 20017 60017 10016 60016 200
TABLE 12-40 1216.2(35)POLYETHYLENE PLASTIC PIPE [NFPA 54-12: TABLE 6.3(l)]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal units per hour = 0.293 kW, 1 pound-force per square inch = 6.894 kPaNote: All tTable entries are rounded to 3 significant digits.
225UNIFORM PLUMBING CODE
FUEL PIPING
GAS: UNDILUTED PROPANEINLET PRESSURE: 11.0 in. w.c.PRESSURE DROP: 0.5 in. w.c.SPECIFIC GRAVITY: 1.50
INTENDED USE: PE TUBE SIZING BETWEEN INTEGRAL2-STAGE REGULATOR AT TANK OR SECOND STAGE (LOW PRESSURE
REGULATOR) AND BUILDING.PLASTIC TUBING SIZE (CTS) (inch)
NOMINAL OD: 1⁄2 3⁄4DESIGNATION: SDR 7.00 SDR 11.00ACTUAL ID: 0.445 0.927LENGTH (feet) CAPACITY IN THOUSANDS OF BTU PER HOUR
1020304050
12183675751
828569457391347
60708090100
4642393735
314289269252238
125150175200
31282624
211191176164
225250275300
22212019
154145138132
350400450500
18161515
121113106100
TABLE 12-41 1216.2(36)POLYETHYLENE PLASTIC TUBING [NFPA 54-12: TABLE 6.3(m)]
For SI units: 1 inch = 25 mm, 1 foot = 304.8 mm, 1000 British thermal unitsper hour = 0.293kW, 1 inch water column = 0.249 kPaNote: All tTable entries are rounded to 3 significant digits.
226 UNIFORM PLUMBING CODE