2
SERIES 4000RP FIRE ALARM REPEATER PANEL FEATURES * Multi - Panel network by RS485 * Fibre– Optic Link Option Available * Local Programming * Zonal LED’s * Full Control Operation * Back-Lit LCD—4 x 40 Characters * Internal Power Supply Option * Flush Bezel Available * Complies with BS5839 PT4 1988 and EN 54 PT2 1999 GENERAL DESCRIPTION Designed for connection to our Series 4000MP analogue addressable Main Fire Alarm control panel . The Repeater Receives and Displays the information generated by the Analogue addressable panel . The information displayed And system controls are in the same format as the Main Control Panel. The Information is received and transmitted by a 4 core Data RS485 Link . This can be part of a Distributed system which can also include Sub Panels And Loop Panels . The Repeater is comes fitted with the Plug– in RS485/CB communication board . A Fibre - Optic RS485 Communication Link is also available. The panel is housed in an attractive metal enclosure with a glazed hinged lockable door . All indications and controls Together with user instructions are provided on the inner facia . A bezel can be fitted to the back Box to enable the control panel to be Flush Mounted . Special colours or non standard finishes are available to special order . The 4000RP can be supplied either with or without an Internal Power supply. A back-lit 4 x 40 Character LCD display provides Status and programmable location of each event . Zonal Fire RED LED indications ( available up to 160 Zones as standard ) will be as the Main Control panel . A Loss of Data link will be indicated as a “ Communication Fault “. Local programming is achieved by using Main Control panel Infrared controller or via the AT keyboard socket. AVAILABLE OPTIONS * Flush Mounting Bezel * Company name and Logo * Extra Zone LED’s in 32 Way Groups * Special Colours & Finishes * Internal Power Supply 64/40RP/PS

description

REPEATER PANEL

Transcript of Repeater Panel

Page 1: Repeater Panel

SERIES 4000RP FIRE ALARM REPEATER PANEL

FEATURES * Multi - Panel network by RS485

* Fibre– Optic Link Option Available

* Local Programming

* Zonal LED’s

* Full Control Operation

* Back-Lit LCD—4 x 40 Characters

* Internal Power Supply Option

* Flush Bezel Available

* Complies with BS5839 PT4 1988 and EN 54 PT2 1999

GENERAL DESCRIPTION Designed for connection to our Series 4000MP analogue addressable Main Fire Alarm control panel . The Repeater Receives and Displays the information generated by the Analogue addressable panel . The information displayed And system controls are in the same format as the Main Control Panel. The Information is received and transmitted by a 4 core Data RS485 Link . This can be part of a Distributed system which can also include Sub Panels And Loop Panels . The Repeater is comes fitted with the Plug– in RS485/CB communication board . A Fibre - Optic RS485 Communication Link is also available. The panel is housed in an attractive metal enclosure with a glazed hinged lockable door . All indications and controls Together with user instructions are provided on the inner facia . A bezel can be fitted to the back Box to enable the control panel to be Flush Mounted . Special colours or non standard finishes are available to special order . The 4000RP can be supplied either with or without an Internal Power supply. A back-lit 4 x 40 Character LCD display provides Status and programmable location of each event . Zonal Fire RED LED indications ( available up to 160 Zones as standard ) will be as the Main Control panel . A Loss of Data link will be indicated as a “ Communication Fault “. Local programming is achieved by using Main Control panel Infrared controller or via the AT keyboard socket.

AVAILABLE OPTIONS

* Flush Mounting Bezel * Company name and Logo

* Extra Zone LED’s in 32 Way Groups * Special Colours & Finishes

* Internal Power Supply

64/40RP/PS

Page 2: Repeater Panel

ENCLOSURE SIZES AND WEIGHTS (less standby batteries ) NUMBER OF ZONES WIDTH HEIGHT DEPTH ENCLOSURE REF WEIGHT

Up to 64 405 mm 300 mm 125 mm 00 8.0 Kg Up to 160 500 mm 400 mm 150 mm 01 13.0 Kg

TECHNICAL SPECIFICATION

Mains Input( with internal power supply ) ——– 240v AC 50/60 Hz ( other voltages to order )

Nominal panel Input voltage ——– 24v DC

Supply rating / type( when fitted ) ——– 1.25 amp Constant voltage with current limit & thermal shutdown

Standby current ——– 75 mA

Alarm current ——– 110 mA

Data Loop Output ——– Multi-panel network by RS485 fully redundant Loop or Fibre - Optic Cable Link via Fibre Optic Interface Board

Construction ——– 18 gauge sheet steel , Epoxy powder coated semi-gloss Grey - White with hinged lockable glazed door and Blue screen printed lettering

Cable entry ——– Top entry with 20 mm diameter knockouts

Standby battery space ——– Accepts up to 2 off 12v 7 Amp/hr (00 Enclosure) or 12 Amp/hr (01 Enclosure ) Sealed Lead Acid Batteries

Alarmtronic Ltd

Unit 4 , Tait Road , Croydon , Surrey , CRO 2DP Tel : 020 8665 6500 Fax : 020 8684 6511

MEMBER OF THE BRITISH STANDARDS INSTITUTE

ORDER CODE DETAILS

64 / 40 00 / RP / PS ( Typical Code ) Number of Zone LED’s / 40 Enclosure Ref / RP / Power supply Option

TYPICALWIRING

SCHEMATIC

TX 1 RX2 RX1 TX 2

MAIN PAN EL

OU T IN

A

A

B

B

A

A

B

B

A

A

B

B

A

A

B

B

TX 1

TX 1

RX2

RX2

RX1

RX1

TX 2

TX 2

SU B- PAN EL ( TYP.)

OU T IN

NL E

4000 SERIESREPEATER PANEL

240v AC IN PU T

OU T IN

FR O M MA IN P A N E L, S U B -P A N E L OR R E P E A TE R

TO MA IN P A N E L, S U B -P A N E L OR R E P E A TE R

4 CORE

OU

T0V

C LA S SC H A N G E

24VA U X 1

24VA U X 2

MP XZON E

+ - + - A B A B A B A B A B A B A B A B

TX 1 RX2 RX1 TX 2

R EPEATER ( TYP.)

OU T IN