Remote inspection system for impact damage in large ...Remote inspection system for impact damage in...

20
Remote inspection system for impact damage in large composite structure By C. H. Zhong * , A. J. Croxford and P. D. Wilcox Department of Mechanical Engineering,University of Bristol,Queens Building, University Walk, Bristol, BS8 1TR, UK ABSTRACT A significant opportunity for reducing the weight of composite aircraft is through the development of an economically-efficient method to detect barely-visible or invisible impact damage sustained in service. In this paper, a structurally-integrated, inert, wireless system for rapid, large-area impact damage detection in compos- ite is demonstrated. Large-area inspection from single sensors using ultrasonic guided waves is achieved with a baseline-subtraction technique. The wireless interface uses electromagnetic coupling between coils in the em- bedded sensor and inspection wand. Compact encapsulated sensor units are built and successfully embedded into composite panels at manufacture. Chirp-based excitation is used to enable single-shot measurements with high signal-to-random-noise ratio to be obtained. Signal processing to compensate for variability in inspection wand alignment is developed and shown to be necessary to obtain adequate baseline subtraction performance for damage detection. Results from sensors embedded in both glass fibre and carbon fibre reinforced composite panels are presented. Successful detection of a 10 J impact damage in the former is demonstrated at a range of 125 mm. Quantitative extrapolation of this result suggests that the same level of impact damage would be detectable at a range of up to 1000 mm with an inspection wand alignment tolerance of 4 mm. Keywords: Wireless, Embedded sensor, Composites, NDE 1. INTRODUCTION Composite materials are susceptible to barely visible impact damage (BVID) caused by low-velocity impacts (energy level of 10-30 J) such as tool drops, bird strikes and hailstones. 1, 2 By definition, BVID is hard to detect through routine visual inspection. Although ultrasonic bulk wave and thermal imaging non-destructive testing (NDT) techniques are able to detect BVID, neither are ideal for performing rapid in-service inspections. For example, ultrasonic inspection requires water coupling and the ultrasonic transducer must be scanned over * Author for correspondence C.H.Zhong (E-mail: [email protected]) www.ndt.net/?id=17809 Vol.20 No.5 (May 2015) - The e-Journal of Nondestructive Testing - ISSN 1435-4934

Transcript of Remote inspection system for impact damage in large ...Remote inspection system for impact damage in...

  • Remote inspection system for impact damage in largecomposite structure

    By C. H. Zhong*, A. J. Croxford and P. D. Wilcox

    Department of Mechanical Engineering,University of Bristol,Queens Building,

    University Walk, Bristol, BS8 1TR, UK

    ABSTRACT

    A significant opportunity for reducing the weight of composite aircraft is through the development of an

    economically-efficient method to detect barely-visible or invisible impact damage sustained in service. In this

    paper, a structurally-integrated, inert, wireless system for rapid, large-area impact damage detection in compos-

    ite is demonstrated. Large-area inspection from single sensors using ultrasonic guided waves is achieved with

    a baseline-subtraction technique. The wireless interface uses electromagnetic coupling between coils in the em-

    bedded sensor and inspection wand. Compact encapsulated sensor units are built and successfully embedded

    into composite panels at manufacture. Chirp-based excitation is used to enable single-shot measurements with

    high signal-to-random-noise ratio to be obtained. Signal processing to compensate for variability in inspection

    wand alignment is developed and shown to be necessary to obtain adequate baseline subtraction performance

    for damage detection. Results from sensors embedded in both glass fibre and carbon fibre reinforced composite

    panels are presented. Successful detection of a 10 J impact damage in the former is demonstrated at a range

    of 125 mm. Quantitative extrapolation of this result suggests that the same level of impact damage would be

    detectable at a range of up to 1000 mm with an inspection wand alignment tolerance of 4 mm.

    Keywords: Wireless, Embedded sensor, Composites, NDE

    1. INTRODUCTION

    Composite materials are susceptible to barely visible impact damage (BVID) caused by low-velocity impacts

    (energy level of 10-30 J) such as tool drops, bird strikes and hailstones.1,2 By definition, BVID is hard to

    detect through routine visual inspection. Although ultrasonic bulk wave and thermal imaging non-destructive

    testing (NDT) techniques are able to detect BVID, neither are ideal for performing rapid in-service inspections.

    For example, ultrasonic inspection requires water coupling and the ultrasonic transducer must be scanned over

    * Author for correspondence C.H.Zhong (E-mail: [email protected])

    www.ndt.net/?id=17809Vol.20 No.5 (May 2015) - The e-Journal of Nondestructive Testing - ISSN 1435-4934

  • the complete surface to be inspected. Thermography is an inherently large-area technique, but due to the low

    thermal diffusivity of composite, thermographic methods are primarily limited to near-surface damage.3

    The current approach adopted by most of the aerospace industry is to over-design composite structures so

    that they can tolerate the existence of BVID4 (more serious impact damage is assumed to be detectable during

    routine visual inspections between flights). Consequently, there is a real opportunity for reducing the weight of

    composite aircraft by developing an efficient method of detecting BVID between flights. The potential weight

    reductions would also help to meet the new environmental targets set for the aerospace industry.5 Conceptually,

    a fully-integrated structural health monitoring (SHM) system using permanently-installed sensors is the ideal

    solution to provide rapid BVID detection. Such a system could either detect impacts directly (e.g. via acoustic

    emission) or the damage resulting from an impact.6–9 Such SHM systems have been widely demonstrated in the

    laboratory and in some cases trialled on actual aircraft. However, there are two major challenges preventing the

    widespread deployment of such SHM systems in the aerospace industry.

    The first challenge is the fundamental problem of making the necessary physical measurements with suitable

    levels of reliability, sensitivity and selectivity. For large-area monitoring with a limited number of sensors,

    ultrasonic guided waves provide arguably the only generally-applicable physical measurement mechanism. In a

    structure with any degree of complexity, some form of baseline signal comparison approach becomes necessary

    when guided waves are used in order to discriminate between benign structural features and damage. Significant

    progress continues to be made in this area,10–12 with increasingly robust detection sensitivity being demonstrated

    even in the presence of environmental variability.

    The second challenge is the more practical problem of data and power connectivity to a distributed sensor

    network in a large aerospace structure. The easiest connectivity solution is to use wires and a number of strategies

    for ultrasonic composite SHM based on wired transducers have been investigated.13,14 The main limitation of a

    wired system is that a large number of conductive routes and transducer control units such as multiplexers need

    to be integrated into the structure as well. For a large structure, the amount of wiring and electronics not only

    increases weight, manufacturing and installation costs,15 but potentially decreases the reliability of the system,

    due to the possibility of failures in the wiring. A widely-researched alternative is to use wireless RF protocols (e.g.

    wifi, ZigBee) for communication,16,17 but the major challenge for wireless systems is power consumption. If the

    power source is a battery or other energy storage device then when the power source is exhausted, replacement

    presents a significant problem if the sensors are embedded or integrated into a structure such as a composite

    aircraft.15 An alternative solution is to use power-harvesting technology such as photovoltaic, thermoelectric,

    piezoelectric devices and rectenna arrays for the wireless unit. However, in order to provide enough power for

  • sensing electronics and data communication, current power-harvesting requires complex, bulky devices.18

    In this paper, a rapid, impact-damage detection solution is proposed that falls between conventional NDT

    and fully-integrated SHM. Rather than attempting to embed sensors, power sources and data communication

    into the structure, only the sensing elements are embedded and measurements are made using an external

    device. The advantage of this approach over a fully-integrated SHM system is that the sensors are inert when

    not in use and no energy storage or long-range data transfer need be considered. The potential advantages over

    conventional NDT (where the sensors as well as instrumentation are separate to the structure) is (a) the ease and

    speed with which measurements can be made and (b) the fact that sensors remain at precisely fixed positions

    in the structure, enabling baseline signal comparison techniques to be employed if required. The concept of the

    proposed system for impact detection in a composite structure is shown in Fig. 1(a). A distributed array of

    inert sensors is permanently embedded in the composite structure and they are probed using an external device

    termed the inspection wand. The inspection wand could be deployed either manually, as shown in the figure, or

    using a platform such as a unmanned aerial vehicle. When the inspection wand is in close physical proximity to

    a sensor, the sensor is activated and a measurement is made. A key attraction of the system is that it enables

    quantitative measurements to be rapidly obtained from sensors at precisely-defined locations using an inspection

    wand that does not have to be precisely positioned or even physically coupled to the structure.

    An inductively-coupled transducer system (ICTS) was initially proposed by Greve et al.,19,20 and inductive

    coupling is employed in the current paper to realize the concept shown in Fig. 1(a). The same technique has

    also been used by Wu et al. for through-thickness inspection with flexible transducers.21,22 The proposed ICTS

    is shown in Fig. 1(b) and consists of three coils. One coil (termed the transducer coil) is physically connected

    to a piezoelectric transducer and forms a sensor unit, which is embedded in the structure. The other two coils

    (termed the transmitting and receiving coils) are in the separate inspection wand, where they are connected

    to the output and input channels of ultrasonic instrumentation. Importantly, a completely-embedded sensor

    benefits from the physical protection provided by the host structure and also, if manufactured correctly, exhibits

    superior ultrasonic coupling to the structure compared to a surface-mounted sensor.

    Previously, a model of an ICTS parameterised by physical constants, such as the number of turns and

    diameter of each coil, was developed and validated.23 In the current paper, this electromagnetic coupling model

    was used to develop the optimised design for guided wave detection of impact damage described in Section 2.2.

    A process to practically embed an optimised sensor into composite is demonstrated in Section 2.3. In order to

    enable single-shot measurements with high signal-to-random-noise ratio and to compensate for the effect of wand

    misalignment, the linear shift between the axes of the coils, several signal processing techniques are described in

  • Compositestructure

    Embeddedsensors

    Embeddedsensor

    Inspectionwand

    InspectionwandTransmitter

    coil

    Receivercoil Piezoelectric

    transducer

    Transducercoil

    (a)Fromsignal

    generator

    Todigital

    oscilloscope

    Inductive

    coupling

    (b)

    Figure 1. (a) Concept of the inductively-coupled transducer system (ICTS) and (b) detail of the inductive coupling

    between inspection wand and embedded sensor.

    Section 2.4. The consistency of embedded sensors, the performance of misalignment compensation methods and

    finally the use of the system to detect impact damage are reported in Section 3.

  • 2. SYSTEM DESIGN

    2.1 Methodology and Objectives

    The inspection target for the system described in the current paper is to detect the damage from a 10 J low-

    velocity impact in a composite panel at distance of up to 1000 mm from a sensor location.1,2 Because the

    intended use of the proposed system is for rapid routine manual inspection, it was decided that the inspection

    target should be achievable in a single-shot measurement with a realistic degree of inspection wand misalignment

    relative to the sensor.

    Guided elastic waves (Lamb waves) have been widely acknowledged as one of the most promising tools for

    long range detection of various types of defect in different materials and structures,24 and deployable guided

    wave systems have been successfully used for industrial NDT inspections of simple structures such as pipes25–27

    and rails.28,29 Because a guided wave sensor can potentially detect damage over a significant surrounding

    area, a permanent sparse array of guided wave sensors in pitch-catch mode is an ideal candidate for large-area

    SHM. In the current paper, a sparse array of guided wave sensors, each operating independently in pulse-echo

    mode, is used as the basis of the composite impact damage detection system. The damage in the structure

    is detected and localised by identifying the appearance of new reflected signals in the pulse-echo mode instead

    of new diffracted signals in pitch-catch mode. The pulse-echo configuration is more practical for use in this

    particular application, requiring only a single inspection wand to be aligned with a single sensor to perform a

    measurement. To achieve a reasonable inspection range and sensitivity to damage, the fundamental extensional

    (S0) mode in the 0.35-0.5 MHz mm frequency-thickness product range is used. The motivation for this is that at

    higher frequency-thickness products, higher-order modes exist making signals harder to interpret, while at lower

    frequency-thickness products, the sensitivity to localised defects is diminished. The attenuation of the S0 mode

    due to material damping is also significantly less than the fundamental flexural (A0) mode30 and the S0 mode

    is also less susceptible to attenuation due to energy leakage if the structure has liquid-loading (as is the case in,

    for example, wet-wing designs). Due to the complexity of aerospace composite structure, it is assumed that the

    system will operate in a baseline subtraction mode to suppress reflections from benign structural features, such

    edges and stiffeners.31,32

    The embedded sensor unit should be of minimal size, especially thickness, to reduce its impact on structural

    integrity. For the reasons outlined above, it is necessary to use the S0 Lamb wave mode, which requires a

    transducer that is sensitive to in-plane motion. As complete structural coverage in terms of defect detection

    is desired, the transducers should have omni-directional sensitivity to this mode. Therefore thin, disk-shaped

    piezoelectric transducers operating primarily in an axi-symmetric radial mode are used (specifically 16 mm

  • diameter, 0.3 mm thick devices manufactured from NCE51 piezoelectric material supplied by Noliac Group,

    Kvistgaard, Denmark).

    It is worth noting that the electromagnetic coupling and ultrasonic measurement are considered as indepen-

    dent challenges in this paper. This allows well-understood electromagnetic modelling33 and ultrasonic guided

    wave SHM experience34 to be adopted separately in the design process.

    2.2 Electromagnetic design

    Fig. 2(a) shows a typical ICTS pulse-echo time-domain response.35 Cross-talk due to direct coupling between

    the transmitting and receiving coils gives rise to a dead-zone in the coverage provided by a sensor unit, as the

    cross-talk obscures signals from nearby reflectors, as indicated in Fig. 2(b). Inductively-coupled systems are

    susceptible to incoherent electromagnetic interference (EMI) from other circuits causing incoherent or random

    noise. The signal prior to the cross-talk in Fig. 2(a) gives an indication of the level of such noise. Obtaining an

    adequate signal-to-random-noise ratio, SR, is an important consideration for the design of the ICTS. However,

    simply designing to maximise the amplitude of the received signal will result in a resonant circuit, which is how

    most inductive power transfer systems are designed.36,37 In fact, signal fidelity is of equal if not greater concern

    in the design of ICTS than SR. Resonance is manifested as long signal ring-down which has several undesirable

    effects, one of which is poor temporal resolution. More importantly, resonance increases the duration of cross-

    talk and consequently the size of the dead-zone around each sensor. To quantify the signal fidelity of an ICTS

    response from a sensor on a particular structure, the signal-to-cross-talk ratio, SX , of a received signal, v(t), is

    defined as:

    SX =|H {v(t)}|t=t1

    ∫ 2δδ|H {v(t)}|dt

    (1)

    where H {.} indicates a Hilbert transform, t1 is the arrival time of a reference reflection signal, and δ is the

    duration of the input signal used to drive the ICTS whose peak is assumed to start at t = 0. The numerator in

    this expression is signal amplitude and the denominator is the mean cross-talk signal amplitude in the period,

    yellow region in Fig. 2, after the input signal has finished. The latter would be theoretically zero if the ICTS

    had no resonance and is consequently a measure of signal fidelity.

    In practice, it has been found that an ICTS designed to maximise SX also achieves an acceptable SR (i.e.

    one that is not a limit on system performance). Therefore, SR is not considered in the electromagnetic design

    process, but will be discussed further in the context of signal processing.

    As noted, the electromagnetic design and ultrasonic measurements are considered as independent challenges

    in this paper. The objective of the electromagnetic design here is therefore to optimise the electromagnetic

  • Figure 2. (a) Typical pulse-echo response from ICTS and (b) inspection coverage of single ICTS sensor. Yellow shading

    is (a) refer to a δ to 2δ region

    coupling aspect of an ICTS for a specified piezoelectric transducer and ultrasonic instrument. In other words,

    the electromagnetic optimisation is performed on the basis that the specified piezoelectric transducer would

    yield a suitable ultrasonic signal if it were physically wired to an appropriate ultrasonic pulser-receiver. Here,

    a combined digital-oscilloscope signal-generator unit (HS3, TiePie Engineering, Sneek, Netherlands) is used as

    the ultrasonic instrumentation. An optimisation procedure is applied to electromagnetic design to maximize

    SX for the ICTS for a specified input signal (a 5 cycle Gaussian windowed toneburst at a centre frequency of

    160 kHz). The predefined constants of the system such as output impedance of signal generator, impedance of

    digital oscilloscope and manufacturing limitations are listed in Table. 1(a) along with system information such

    as thickness of PCB substrate and input signal.

    In order to reduce the physical size of the embedded sensor, the secondary coil in the sensor is a double-sided

    planar coil fabricated on a printed circuit board (PCB) that surrounds the piezoelectric disc. Therefore, the

    inner diameter of this coil is constrained to the diameter of the piezoelectric disc plus 4 mm radial clearance for

    connection soldering, thus giving a minimum inner coil diameter of 24 mm. Also, in order to decrease the size

    of all coils and the number of design parameters, the PCB manufacturing resolution, k, is used to define both

    the PCB track width as well as the distance between the two neighbouring tracks. Because the transmitting and

    receiving coils are built into a opposite side of a single PCB, these coils are single sided.

    The specifications of the optimised three coil design based on the constraints given before are listed in

    Table. 1(b). Fig. 3 shows SR, SX of the optimised system at different reading distances. It can be seen that

    although SX does decrease with reading distance, the decrease is fairly modest comparing to SR. SR drops

    exponentially and approach to zero as reading distance increased. For this optimized system, the maximum

  • Table 1. (a) List of predefined constants for electromagnetic design and (b) specifications of optimized coils after electro-

    magnetic design.

    reading distance is 40 mm, where signal-to-random-noise ratio is equal to 2 (6 dB). It worth noting that the

    experimentally measured noise level was used to calculate SR.

    2.3 Embedded sensor design

    Fig. 4(a) shows the process developed to manufacture an encapsulated sensor unit for embedding in a composite

    structure. First, the piezoelectric disc is placed in a circular cut-out in the centre of a double-sided PCB containing

    the secondary coil with dimensions determined from the optimisation procedure (24 mm inner diameter, 38.4 mm

    outer diameter, double-sided with 19 turns on each side). Then, the assembled unit is cured with 0.075 mm

    thick insulation layers (Pyralux LF, Dupont, Wilmington, USA) on both sides. The insulation layers consist of

    polyimide film coated on both sides with acrylic adhesive. The result is an encapsulated sensor unit in the form

    of a 0.45 mm thick, 55 mm diameter disc, which is ready for embedding into a composite material.

    Sensor units were embedded into a glass fibre composite panel (Hexcel 950, Hexcel, Stamford, CT, USA)

    cured at 125 ◦C and a carbon fibre composite panel (Hexcel M21, Hexcel, Stamford, CT, USA) cured at 180 ◦C

    with 7 bar pressure applied. The glass fibre and carbon fibre composite panel lay-up sequences are shown in

    Figs. 4(b) and (c) respectively and the finished panels are shown in Fig. 5. The glass fibre panel is used for impact

    damage detection tests and the carbon fibre panel for sensor performance studies. The embedded ICTS can be

    visually identified in the glass fibre panel, but their presence in the carbon fibre material is only detectable via

    a slight thickening on the non-tool side. In the carbon fibre plate there are three ICTSs and one wired unit for

    reference. The effect of embedding on the strength of composite structure is open research topics, but has been

  • 0 10 20 30 40 500

    50

    100

    150

    200

    250

    Reading distance (mm)

    SR

    0 10 20 30 40 500

    1

    2

    3

    4

    5

    6

    7

    Reading distance (mm)

    SX

    (b)(a)

    Figure 3. (a) Signal-to-random-noise ratio, SR, and (b) Signal-to-cross-talk ratio, SX , of the optimized system given in

    Table 1(b) as a function of the reading distance in linear scale. Experimentally measured random noise level was used

    to calculated SR. The dashed lines in (a) and (b) refer to optimum reading distance where maximum SX is achieved;

    the dash-dotted lines in (a) and (b) refer to a reading distance where the signal is 2 times (6dB) higher than the random

    noise level.

    studied by Yang et al.38 It has been found that embedding a sensor with polyimide bond ply does not decrease

    the strength of the composite structure.

    2.4 Signal processing

    In this section the signal processing associated with the embedded ICTS is described. The signal processing

    is required for two purposes: to allow single-shot measurements with high signal-to-random-noise ratio and to

    allow successful baseline signal subtraction despite signal variability due to inspection wand misalignment.

    2.4.1 Excitation and pre-processing

    Let u(t) be the desired input signal to the ICTS, where t is time. This is typically a short, limited-bandwidth

    toneburst of duration T . In order to enable single-shot measurements with high signal-to-random-noise ratio,

    the system response, v(t), to u(t) is recovered from the system response, vc(t), to a narrowband chirped input

    signal, uc(t), of duration NcT . In the following, F{.} and F−1{.} are the forward and inverse Fourier transform

    operators and ω is angular frequency. The necessary chirp excitation is given by:

    uc(t) = F−1{U(ω)C(ω)} (2)

  • Figure 4. (a) Manufacture of encapsulated unit for embedding application. (b) The lay-up sequence of Hexcel 950 glass

    fibre and (c) Hexcel M21 carbon fibre composite laminated plate with embedded ICTS.

    Figure 5. (a) Glass fibre composite panel with embedded ICTS, (b) carbon fibre composite panel with three embedded

    ICTSs. The circle and inset picture in (a) show the position where 10 J impact damage was introduced and the delami-

    nation on the reverse side of the panel. In (b), the dotted circles represent the positions of ICTSs, and the stars represent

    laser measurement points on the edge of the panel.

    where U(ω) = F{u(t)} is the frequency spectrum of the desired input signal and C(ω) = F{c(t)} is the

    frequency spectrum of a linear chirp signal, c(t), defined over the interval 0 ≤ t ≤ NcT given by:

    c(t) = sin(ω1t+(ω2 − ω1)t2

    NcT) (3)

    where ω1 and ω2 are the start and end frequencies of the chirp. The bandwidth of c(t) (i.e. from ω1 to ω2)

    must span the bandwidth of u(t). The stretch factor, Nc, specifies the duration of the chirp signal relative to

  • the duration of the desired input signal. The increase in SR associated with a chirp is proportional to√Nc.

    39

    The frequency-domain response of the system, V (ω), to the desired input signal is extracted from the system

    response to the chirp excitation, vc(t), through the following frequency-domain deconvolution augmented with a

    bandpass filter, G(ω), to remove out-of-band noise:

    V (ω) =F{vc(t)}G(ω)

    C(ω). (4)

    Thus the final time-domain response of the system to the desired input signal is:

    v(t) = F−1{V (ω)}. (5)

    2.4.2 Effect of coil misalignment

    In an infinitely-large, featureless structure, impact damage could be directly detected by the appearance of a

    reflection in v(t). However, in a real structure, large signals are present due to reflections from benign structural

    features and these must be suppressed in order to be able to detect much smaller signals due to impact damage.

    The detection of new impact damage therefore requires comparison of the current signal with an earlier baseline

    signal. Here, baseline signal subtraction is employed as this has the advantage of being a linear operation with

    predictable performance.34 It has been found that the amplitude of a received signal from an ICTS varies

    dramatically with changes in the relative position of coils,19,23 which here is due to imprecise positioning of

    the inspection wand between repeated measurements at the same sensor. This presents a major challenge for

    baseline signal subtraction that must be overcome in order to achieve reliable damage detection.

    Fig. 6(a) shows waveforms prior to baseline subtraction from the ICTS embedded in glass fibre plate for

    coil separations of 12 and 17 mm. The coil separation is defined as the distance between the plane of the

    sensor and the plane of inspection wand under the assumption of perfect coaxial and angular alignment. The

    effective input signal was a Gaussian-windowed, 5-cycle (defined by the −40 dB points of the Gaussian window)

    toneburst with centre frequency 160 kHz and the results were obtained using chirp excitation with Nc = 1300.

    The change in amplitude of the first echo signal for a range of coil separations is shown in Fig. 6(b). As the coil

    separation increases, the signal amplitude drops and decreases by about 65% of its original amplitude when the

    coil separation is increased by 8 mm.

    However, amplitude variation is not the only effect resulting from coil misalignment. The corresponding

    spectra for the first echo signals shown in Fig. 6(a) are shown in Fig. 6(c). There is a small change in the

    frequency of the spectral peak for the two coil separations and this is plotted for a range of separation distances

    in Fig. 6(d). Similar results are found for lateral misalignment.

  • 0 100 200 300 400 500−1.5

    −1

    −0.5

    0

    0.5

    1

    1.5

    Distance8away8from8sensor8zmmd

    Arb

    .8uni

    ts

    Dps=12mmDps=17mm

    12 13 14 15 16 17 18 19 200.2

    0.4

    0.6

    0.8

    1

    Dps zmmd

    |Hzv

    ztdd

    | t=t 1

    12 13 14 15 16 17 18 19 201.79

    1.8

    1.81

    1.82

    1.83

    1.84

    1.85 x8105

    Dps zmmd

    f p

    1 1.5 2 2.5x8105

    0

    2000

    4000

    6000

    8000

    10000

    Frequency8zHzd

    Arb

    .8uni

    ts

    Dps=12mmDps=17mm

    zad zbd

    zddzcd

    Figure 6. (a) Time-domain signals obtained from ICTS in glass fibre composite for coil separations of 12 and 17 mm and

    (b) amplitude of first echo as a function of coil separation. (c) Frequency spectra of first echo signals for coil separations

    of 12 and 17 mm and (d) frequency of spectral peak as a function of coil separation.

    2.4.3 Received signal compensation

    Pure amplitude variations can be effectively compensated by normalisation. In this approach to compensation

    prior to baseline subtraction, both the received signal, v(t), and baseline, v0(t), are normalised to the maximum

    amplitude of the envelope of the first echo. Therefore, the residual signal using amplitude normalisation is:

    ∆norm(t) =v(t)

    |H {v(t)}|t=t1− v0(t)|H {v0(t)}|t=t1

    . (6)

    Since spectral shape as well as signal amplitude are changed by the coil misalignment, amplitude normalisation

    is generally inadequate. Here, an inverse filter40 is employed to achieve better compensation for coil misalignment

    effects. This is calculated from the measurement and baseline spectra of the first echo in each signal:

    I(w) =F{v0(t1 − δ ≤ t ≤ t1 + δ)}F{v(t1 − δ ≤ t ≤ t1 + δ)}

    (7)

    Consequently, the residual signal obtained using the inverse filter method is:

    ∆inv(t) = F−1{V (ω)I(ω)− V0(ω)} (8)

    where V (ω) = F{v(t)} and V0(ω) = F{v0(t)}.

  • 2.4.4 Beam spread compensation

    In order to quantify the damage detection capability of the system, it is desirable for the response to a given

    level of damage to be independent of its distance from a sensor. In a complex structure, this would most likely

    require some form of experimental calibration procedure. However, in a simple plate, the reduction in signal

    amplitude with distance is predictable and due to a combination of dissipative and geometric attenuation. As the

    attenuation of the S0 mode in composites, particularly along the fibre direction, is low,30 geometric attenuation

    due to the divergence of both transmitted and scattered waves is the dominant effect. Both result in an amplitude

    reduction proportional to the square root of propagation distance. Hence the amplitude of the response from

    localised damage for a single sensor operating in pulse-echo mode is expected to be proportional to the reciprocal

    of the distance of damage from the sensor. Therefore, it is instructive to scale the amplitude of residual signals

    with distance from sensor, d, and to only consider the envelope of the signal. Consequently, the quantity plotted

    in subsequent residual signal graphs is

    rnorm,inv = d|H {∆inv(2d/vg)}|, (9)

    where vg is the group velocity of the S0 mode at the center frequency of the input signal, 160 kHz.

    3. SYSTEM TESTING

    In this section, the embedded ICTS and signal processing techniques described previously are investigated for

    consistency, performance in the presence of inspection wand misalignment and ultimately for their ability to

    detect impact damage.

    3.1 Sensor consistency

    The performance consistency of ICTS is initially tested through the investigation of the frequency response of the

    devices embedded in carbon fibre plate described in Section 2.3. The three embedded ICTS and a surface-bonded

    ICTS are wirelessly probed using the inspection wand at a coil separation distance of 12 mm. The effective input

    signals are 5-cycle, Gaussian-windowed tonebursts with various centre frequencies. They are applied using chirp

    excitation signals with Nc = 1300 and 24 V peak-peak voltage. Meanwhile, a laser vibrometer (OFV-505,

    Polytec, Harpenden, Hertfordshire, UK) is used to measure the in-plane guided wave displacement generated by

    each ICTS on the edge of the plate nearest to each sensor. In-plane displacement measurements are necessary

    as the S0 mode has very low out-of-plane displacement in this frequency range. The sensor positions and laser

    measuring points are shown in Fig. 5. A typical signal measured by the laser interferometer is shown in Fig. 7(a).

    The set-up for the laser vibrometer is fixed for all the measurements and the edge of the carbon fibre plate is

    polished at the measurement points.

  • −5 0 5 10 15xA10−5

    −0.1

    −0.05

    0

    0.05

    0.1

    0.15

    TimeA(s)

    In−p

    lane

    Adis

    plac

    emen

    tA(ar

    b.Au

    nits

    )

    1 1.5 2 2.5 3xA105

    0

    0.05

    0.1

    0.15

    FrequencyA(Hz)

    Am

    plitu

    deA(a

    rb.u

    nits

    )

    DirectAattachedAICTSEmbeddedAICTSA1EmbeddedAICTSA2EmbeddedAICTSA3

    FirstAarrival

    (a) (b)

    Figure 7. (a) Typical in-plane displacement due to ICTS measured using laser interferometer for an effective input signal

    with centre frequency of 160 kHz. (b) Spectra of first arrival signals for three embedded ICTSs and one surface-bonded

    ICTS.

    Fig. 7(b) shows the frequency response of both embedded and surface-bonded ICTS. It can be seen from this

    figure that consistent performance in terms of both signal amplitude and peak response frequency is obtained with

    the three embedded ICTS. Furthermore, the signal amplitude obtained by embedding the ICTS into composite

    is almost twice that of a surface-bonded ICTS. This is thought to be because a better bond layer between the

    unit and structure is achieved through the curing process and because both sides of sensor are bonded to the

    structure. The frequency shift of the peak response between the embedded ICTS and directly-bonded ICTS is

    due to the fact that the capacitance between the neighbouring tracks in the transducer coil is increased due to

    the increased permittivity contributed by the carbon fibre. It is worth noting that the consistency of embedded

    ICTS in absolute terms is potentially very attractive for an SHM system as it makes system calibration to an

    absolute level of impact damage much more straightforward.

    3.2 Baseline signal subtraction

    Enveloped subtraction results obtained using both simple normalisation, Eq. 6, and the inverse filter technique,

    Eq. 8, are shown in Fig. 8 for various degrees of coil misalignment. These results were obtained from the ICTS in

    the damage-free, glass-fibre composite plate. Again, the input signal was a 5-cycle, Gaussian-windowed toneburst

    with centre frequency 160 kHz and the results were obtained using chirp excitation with Nc = 1300. For the

    baseline signal, the inspection wand was placed 12 mm above the embedded transducer and aligned laterally

  • to maximise the signal amplitude. It worth noting that the residual signals are normalised to the maximum

    amplitude of the impact damage echo for impact damage study in the next section.

    From Fig. 8, it can be seen that the residual signal level achieved by using the inverse filter technique is much

    better than the the results obtained using the amplitude normalisation technique, with more than 3 times (10 dB)

    better suppression of reflections from benign features achieved for all cases. However, the question remains as to

    whether the residual signal is low enough to allow impact damage to be detected. Also, it is possible that the

    inverse filter could suppress the signal introduced by the impact damage. These issues are discussed in the next

    section.

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensorlbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensorlbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensorlbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensorlbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensolrbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    100 200 300 400 500 600 700 800 900 10000

    0.5

    1

    1.5

    Distancelawaylfromlsensorlbmm)

    Nor

    m.lr

    esid

    ualls

    igna

    l

    ResiduallsignallwithlnormalizationResiduallsignallwithlinverselfilter10Jlimpactlthreshold

    ba) bd)

    be)

    bf)bc)

    bb)

    Figure 8. Enveloped residual signals after baseline subtraction with (a) 3 mm, (b) 6 mm, (c) 9 mm coil horizontal

    misalignment, and (e) 3 mm, (f) 6 mm, (g) 9 mm coil vertical separation variation by using normalization (grey line),

    and inverse filter (black line) signal processing techniques. The dashed line represents the 10 J impact damage threshold

    discussed in Section 3.3

    .

    3.3 Impact damage detection

    The glass fibre panel was subjected to a 10 J impact at a distance of 125 mm from the ICTS, resulting in a

    delamination around 20 mm diameter, as shown in the inset in Fig. 5 (a). Fig. 9 shows the residual signals after

    baseline subtraction using the inverse filter method, when the coils are perfectly aligned with 12 mm separation.

    The residual signals are normalised to the maximum amplitude of the impact damage echo.

    From Fig. 9(b), it can be seen that the reflected signal from a 10 J impact can be clearly identified at the

  • 0 100 200 300 400 500 600 700 800 9000

    0.5

    1

    1.5

    Distanceuawayufromusensoru(mm)

    Nor

    mal

    ised

    ures

    idua

    lusig

    nal

    0 100 200 300 400 500 600 700 800 9000

    0.5

    1

    1.5

    Distanceuawayufromusensoru(mm)

    Nor

    mal

    ised

    ures

    idua

    lusig

    nal

    Residualusignal10Juimpactudamageuthreshold

    (b)

    (a)

    Figure 9. Residual signals from (a) damage free structure, and (b)structure with 10 J impact damage. Grey lines in (a)

    and (b) refer to the location of damage.

    expected distance away from the transducer of 125 mm. This qualitatively shows that the embedded ICTS is

    capable of detecting impact damage in a composite plate and that the inverse filter did not suppress the signal.

    Note that the increased residual signals after 125 mm are due to forward scattering from the impact interfering

    with subsequent edge reflections. Although not directly interpretable, the appearance of these signals provides

    another opportunity for detecting damage.41

    Fig. 9(a) shows that the normalised residual signal is still significantly smaller (6 dB) than the 10 J threshold

    (the dashed horizontal lines) even at a distance of 1000 mm away from the sensor. The amplitude of the threshold

    is defined as the maximum value of the 10 J impact damage echo. This suggests that the inspection range of the

    embedded ICTS is around 1000 mm, when the inspection wand is perfectly aligned. The 10 J impact damage

    threshold is also plotted in Fig. 8 (the dashed horizontal lines). From this it can be seen that as the misalignment

    increases, the performance of the inverse filter decreases and the coherent noise level increases due to worsening

    suppression of reflections from structural features. However, when the coil misalignment is smaller than 5 mm

    the residual signal is still about 4.5 dB lower than the threshold at a distance of 1000 mm away from the sensor.

    To maintain a signal-to-coherent-noise ratio of 6 dB for 10 J impact damage at a distance of 1000 mm, more

    detailed experiments reveal that the maximum horizontal and vertical coil misalignments are 10 mm and 4 mm.

  • 4. CONCLUSION

    This paper has demonstrated a structurally-integrated sensing system for large-area impact-damage detection

    in composite panels. The system uses a inert, guided wave sensor embedded in the composite panel, which is

    externally activated from an inductively-coupled inspection wand. The design of the inductive coupling link has

    been optimised for the application using a previously-developed model. To enable highly-consistent, single-shot

    measurements to be made rapidly and without precise alignment of the inspection wand several signal processing

    steps have been employed: chirp excitation, deconvolution and band-pass inverse filtering. The last step of inverse

    filtering enables baseline signal subtraction techniques to be employed to detect the occurrence of relatively weak

    scattered signals from impact damage in the presence of large reflections from benign structural features. The

    system has been experimentally demonstrated on two composite panels and 10 J impact damage successfully

    detected. It is estimated that the system could detect this level of impact damage at a range of up to 1000 mm.

    It is worth noting that, although the inverse filter technique is specifically developed here for compensation

    of ICTS coil misalignment, the principles are general and could be applied to compensation of signal changes

    due to environmental variation, such as temperature. These are major issues when using the baseline signal

    subtraction for general guided wave SHM applications.

    Here, the construction of the inverse filter is based on the assumption that the echo signals used to generate it

    only change due to coil misalignment effects. This raises a potential concern that damage signals may be masked

    if they interact with this echo. This has not caused a problem in the impact detection example presented here

    even though forward scattered signals from the damage must have interacted with the edge echo. Although the

    presence of these forward scattered signals has been suppressed (as evidenced by the low residual signal level at

    the position of the first edge echo in Fig. 9(b) at 225 mm), the presence of the new direct echo from the impact

    at 125 mm is separate and is not suppressed. However, there would be a problem if the direct echo from the

    impact damage itself had overlapped with the first edge echo. In a real system, it would therefore be desirable

    for all points in a structure to be within the inspection range of more than one sensor.

    REFERENCES

    1. K. S. Ahmed, S. Vijayarangan, and A. Kumar, “Low velocity impact damage characterization of woven

    jute-glass fabric reinforced isothalic polyester hybrid composites,” Journal of Reinforced Plastics and Com-

    posites 26, pp. 959–976, 2007.

    2. M. V. Hosur, F. Chowdhury, and S. Jeelani, “Low-velocity impact response and ultrasonic nde of woven

    carbon/epoxy-nanoclay nanocomposites,” Journal of Composite Materials 41, pp. 2195–2212, 2007.

  • 3. N. P. Avdelidis, D. P. Almond, A. Dobbinson, B. C. Hawtin, C. Ibarra-Castanedo, and X. Maldague,

    “Aircraft composites assessment by means of transient thermal ndt,” Progress in Aerospace Scienes 40,

    pp. 143–162, 2004.

    4. D. Zenkert, A. Shipsha, P. H. Bull, and B. Hayman, “Damage tolerance assessment of composite sandwich

    panels with localised damage,” Composites Science and Technology 65, pp. 2597–2611, 2005.

    5. B. Beral and H. Speckmann, “Structural health monitoring (shm) for aircraft structures: A challenge for sys-

    tem developers and aircraft manufacturers,” Proc. 4th Int. Workshop on Structural Health Monitoring 1,2,

    pp. 12–29, 2001.

    6. M. A. Hamstad, “A review - acoustic emission, a tool for composite material studies,” Experimental Me-

    chanics 26, pp. 7–13, 1986.

    7. J. M. Carlyle, H. L. Bodine, S. S. Henley, R. L. Dawes, R. Demeski, and E. V. Hill, “Practical ae methodology

    for use on aircraft,” American Society for Testing and Materials Special Technical Publication 1353, pp. 191–

    205, 1999.

    8. C. R. Farrar and K. Worden, “An introduction to structural health monitoring,” Proceedings of The Royal

    Society of London Series A-Mathematical Physical and Engineering Sciences 365, pp. 303–315, 2007.

    9. C. Boller, “Next generation structural health monitoring and its integration into aircraft design,” Interna-

    tional Journal of Systems Science 31, pp. 1333–1349, 2000.

    10. K. Worden, C. R. Farrar, G. Manson, and G. Park, “The fundamental axioms of structural health mon-

    itoring,” Proceedings of The Royal Society of London Series A-Mathematical Physical and Engineering

    Sciences 463, pp. 1639–1664, 2007.

    11. T. Clarke, F. Simonetti, and P. Cawley, “Guided wave health monitoring of complex structures by sparse

    array systems: Influence of temperature changes on performance,” Journal of Sound and Vibration 329,

    pp. 2306–2322, 2010.

    12. Z. Lu, S. J. Lee, J. E. Michaels, and T. E. Michaels, “On the optimization of temperature compensation for

    guided wave structural health monitioring,” Review of Progress in Quantitative Nondestructive evaluation

    1211, pp. 1860–1867, 2010.

    13. X. L. Qing, A. Kumar, C. Zhang, I. F. Gonzales, G. P. Guo, and F. K. Chang, “A hybrid piezoelectric/fiber

    optic diagnostic system for structural health monitoring,” Smart Material and Structure 14, pp. 98–103,

    2005.

    14. M. Lin, X. Qing, A. Kumar, and S. J. Beard, “Smart layer and smart suitcase for structural health monitoring

    applications,” in SPIE — Smart Structures and Materials, Proc. SPIE 4332, 2001.

  • 15. J. P. Lynch and K. J. Loh, “A summary review of wireless sensors and sensor networks for structure health

    monitoring,” The Shock and Vibration Digest 38(2), pp. 91–128, 2006.

    16. S. Jang, H. Jo, S. Cho, K. Mechitov, J. A. Rice, S. H. Sim, H. J. Jung, C. B. Yun, J. Spencer, F. Billie, and

    G. Agha, “Structural health monitoring of a cable-stayed bridge using smart sensor technology: deployment

    and evaluation,” Smart Structures and Systems 6, pp. 439–459, 2010.

    17. P. P. Liu, S. F. Yuan, and L. Qiu, “Development of a pzt-based wireless digital monitor for composite impact

    monitoring,” Smart Materials and Structures 21, p. 035018.1035018.10, 2012.

    18. X. L. Zhao, T. Qian, G. Mei, C. Kwan, R. Zane, C. Walsh, T. Paing, and Z. Popovic, “Active health moni-

    toring of an aircraft wing with an embedded piezoelectric sensor/actuator network: ii. wireless approaches,”

    Smart Materials and Structures 16, pp. 1218–1225, 2007.

    19. D. W. Greve, H. Sohn, C. P. Yue, and I. J. Oppenheim, “An inductively coupled lamb wave transducer,”

    IEEE Sensors 7(1-2), pp. 295–301, 2007.

    20. P. Zheng, D. Greve, and I. Oppenheim., “Crack detection with wireless inductively-coupled transducers,” in

    SPIE — Sensors and Smart Structures Technologies for Civil Mechanical, and Aerospace Systems, 69321,

    2008.

    21. M. Kobayashi, K. T. Wu, L. Song, C. K. Jen, and N. Mrad, “Structural health monitoring of composites

    using integrated and flexible piezoelectric ultrasonic transducers,” Journal of Intelligent Material Systems

    and Structures 20, pp. 969–977, 2009.

    22. K. Wu, C. Jen, and N. Mrad., “Non-contact local and global damage detection with integrated ultrasonic

    transducers,” in SPIE — Sensors and Smart Structures Technologies for Civil Mechanical, and Aerospace

    Systems, 69321, 2008.

    23. C. H. Zhong, A. J. Croxford, and P. D. Wilcox, “Investigation of inductively coupled ultrasonic transducer

    system for nde,” IEEE Transactions on Ultrasonics Ferroelectrics and Frequency Control 60, pp. 1115–1125,

    2013.

    24. Z. Q. Su, L. Ye, and Y. Lu, “Guided lamb waves for identification of damage in composite structures: A

    review,” Journal of Sound and Vibration 295, pp. 753–780, 2006.

    25. M. J. S. Lowe, D. N. Alleyne, and P. Cawley, “Defect detection in pipes using guided waves,” Ultrosonic 36,

    pp. 147–154, 1998.

    26. D. N. Alleyne, B. Pavlakovic, M. J. S. Lowe, and P. Cawley, “Rapid, long range inspection of chemical

    plant pipework using guided waves,” Review of Progress in Quantitative Nondestructive Evaluation 557,

    pp. 180–187, 2001.

  • 27. R. Long, P. Cawley, and M. J. S. Lowe, “Acoustic wave propagation in buried iron water pipes,” Proceedings

    of The Royal Society of London Series A-Mathematical Physical and Engineering Sciences 459, pp. 2749–

    2770, 2003.

    28. J. L. Rose, M. J. Avilioli, and W. J. Song, “Application and potential of guided wave rail inspection,”

    Insight Non-Destructive Testing and Condition Monitoring 44, pp. 353–358, 2002.

    29. P. D. Wilcox, M. Evans, B. Pavlakovic, D. Alleyne, K. Vine, P. Cawley, and M. J. S. Lowe, “Guided wave

    testing of rail,” Insight–NDT and Condition Monitoring 45, pp. 413–420, 2003.

    30. R. A. Badcock and E. A. Birt, “The use of 0-3 piezocomposite embedded lamb wave sensors for detection

    of damage in advanced fibre composites,” Smart Material and Structures 9, pp. 291–297, 2000.

    31. Y. Kagawa, T. Tsuchiya, B. Fujii, and K. Fujioka, “Discrete huygens’ model approach to sound wave

    propagation,” Journal of Sound and Vibration 218, pp. 419–444, 1998.

    32. Y. H. Lu and J. E. Michaels, “A methodology for structural health monitoring with diffuse ultrasonic waves

    in the presence of temperature variations,” Ultrasonics 43, pp. 717–731, 2005.

    33. Y. Lee, “Rfid coil design,” application note, Microchip Technology Inc., 1998.

    34. A. J. Croxford, P. D. Wilcox, B. W. Drinkwater, and G. Konstantinidis, “Strategies for guided-wave struc-

    tural health monitoring,” Proceedings of The Royal Society of London Series A-Mathematical Physical and

    Engineering Sciences 463, pp. 2961–2981, 2007.

    35. C. Zhong, P. Wilcox, and A. Croxford, “Inductively coupled transducer system for damage detection in

    composites,” in SPIE — Health Monitoring of Structural and Biological Systems, 8348, 2012.

    36. B. Lenaerts and R. Puers, “Inductive powering of a freely moving system,” Sensors and Actuators A:

    Physical 123-24, pp. 522–530, 2005.

    37. B. Lenaerts and R. Puers, “An inductive power link for a wireless endoscope,” Biosensors and Bioelectron-

    ics 22, pp. 1390–1395, 2007.

    38. S. M. Yang, C. C. Hung, and K. H. Chen, “Design and fabrication of a smart layer module in composite

    laminated structures,” Smart Materials and Structures 14, pp. 315–320, 2005.

    39. J. E. Michaels, S. J. Lee, A. J. Croxford, and P. D. Wilcox, “Chirp excitation of ultrasonic guided waves,”

    Ultrasonics 53, pp. 265–270, 2013.

    40. R. C. Gonzales, R. E. Woods, and S. L. Eddins, Digital Image Processing Using Matlab, Prentice Hall, 2003.

    41. E. B. Flynn, M. D. Todd, P. D. Wilcox, B. W. Drinkwater, and A. J. Croxford, “Maximum-likelihood

    estimation of damage location in guided-wave structural health monitoring,” Proceedings of The Royal

    Society of London Series A-Matematical Physical and Engineering Sciences 467, pp. 2575–2596, 2011.