Reliable switching:Installation - Doepke · Lamp type Power rating Current Capacitor max. number of...

6
» Low-noise switching » High grade contact material » High thermal loading capacity of poles » Energy-saving Doepke The experts in residual current protection technology Doepke Reliable switching: Installation contactors HS

Transcript of Reliable switching:Installation - Doepke · Lamp type Power rating Current Capacitor max. number of...

» Low-noise switching

» High grade contact material

» High thermal loading capacity of poles

» Energy-saving

DoepkeThe experts in residual current protection technology

Doepke

Reliable switching:

Installation contactors HS

At-a-glance benefits

Quiet, economical, functional

» Space saving with high lamp loads per pin » Low power consumption » Large clamp cross-sections with generous terminal compartment » Low level of heat build-up » High thermal loading capacity of poles » Low-noise switching

Shocks directly onto the housing:

Housing is not decoupled

Shocks not directly onto the housing:

Housing is decoupled

4

1,2

5

2,4

5

2,6

5

2,6

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

wat

t

HS 20 HS 25 HS 40 HS 63

W - competitors W - Doepke

Specific energy efficiencyCompare to other products

Input power of the Doepke-contactors coil: only 1.2 W – 2.6 W

4

1,2

5

2,4

5

2,6

5

2,6

0

0,5

1

1,5

2

2,5

3

3,5

4

4,5

5

wat

t

HS 20 HS 25 HS 40 HS 63

W - competitors W - Doepke

Specific energy efficiencyCompare to other products

Input power of the Doepke-contactors coil: only 1.2 W – 2.6 W10

mm

2

10 m

m2

25 m

m2

25 m

m2

0

5

10

15

20

25

mm

2

HS 20 HS 25 HS 40 HS 63

mm2 - competitors mm2 - Doepke

User-friendly terminalsCompare to other products

Cable clamping cross section

Principle of low-noise switching

Installation contactors 230 V~

Contact type Rated current Wattage Coil Modules packing unit Article No. Ith (A) AC1/AC3 (kW)HS 20-10 1 NO 20 4,6/- 230 V / 50 Hz 1 1/12 09 980 442HS 20-20 2 NO 20 4.6/- 230 V / 50 Hz 1 1/12 09 980 402 HS 20-11 1 NO, 1 NC 20 4.6/- 230 V / 50 Hz 1 1/12 09 980 404HS 20-02 2 NC 20 4.6/- 230 V / 50 Hz 1 1/12 09 980 406

HS 20-13 1 NO, 3 NC 24 14/3 230 V / 50 Hz 2 1/6 09 980 426HS 20-31 3 NO, 1 NC 24 14/3 230 V / 50 Hz 2 1/6 09 980 424HS 20-40 4 NO 24 14/3 230 V / 50 Hz 2 1/6 09 980 422

HS 25-13 1 NO, 3 NC 25 17/4 230 V / 50 Hz 2 1/6 09 980 412HS 25-30 3 NO 25 17/4 230 V / 50 Hz 2 1/6 09 980 443HS 25-31 3 NO, 1 NC 25 17/4 230 V / 50 Hz 2 1/6 09 980 410HS 25-40 4 NO 25 17/4 230 V / 50 Hz 2 1/6 09 980 408HS 25-04 4 NC 25 17/4 230 V / 50 Hz 2 1/6 09 980 427HS 25-22 2 NO, 2 NC 25 17/4 230 V / 50 Hz 2 1/6 09 980 431

HS 40-40 4 NO 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 414HS 40-30 3 NO 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 440HS 40-31 3 NO, 1 NC 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 416HS 40-20 2 NO 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 439HS 40-22 2 NO, 2 NC 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 429HS 40-02 2 NC 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 437HS 40-04 4 NC 40 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 435

HS 63-40 4 NO 63 43/12.5 230 V / 50 Hz 3 1/4 09 980 418HS 63-30 3 NO 63 43/12.5 230 V / 50 Hz 3 1/4 09 980 438HS 63-31 3 NO, 1 NC 63 43/12.5 230 V / 50 Hz 3 1/4 09 980 420HS 63-22 2 NO, 2 NC 63 27.5/12.5 230 V / 50 Hz 3 1/4 09 980 430

Installation contactors 24 V~

Contact type Rated current Wattage Coil Modules packing unit Article No. Ith (A) AC1/AC3 (kW)HS 20-20 2 NO 20 4.6/- 24 V / 50 Hz 1 1/12 09 980 401HS 20-11 1 NO, 1 NC 20 4.6/- 24 V / 50 Hz 1 1/12 09 980 403HS 20-02 2 NC 20 4.6/- 24 V / 50 Hz 1 1/12 09 980 405

HS 20-13 1 NO, 3 NC 24 14/3 24 V / 50 Hz 2 1/6 09 980 425HS 20-31 3 NO, 1 NC 24 14/3 24 V / 50 Hz 2 1/6 09 980 423HS 20-40 4 NO 24 14/3 24 V / 50 Hz 2 1/6 09 980 421

HS 25-13 1 NO, 3 NC 25 17/4 24 V / 50 Hz 2 1/6 09 980 411HS 25-22 2 NO, 2 NC 25 17/4 24 V / 50 Hz 2 1/6 09 980 432HS 25-31 3 NO, 1 NC 25 17/4 24 V / 50 Hz 2 1/6 09 980 409HS 25-40 4 NO 25 17/4 24 V / 50 Hz 2 1/6 09 980 407HS 25-04 4 NC 25 17/4 24 V / 50 Hz 2 1/6 09 980 428

HS 40-40 4 NO 40 27.5/12.5 24 V / 50 Hz 3 1/4 09 980 413HS 40-31 3 NO, 1 NC 40 27.5/12.5 24 V / 50 Hz 3 1/4 09 980 415HS 40-22 2 NO, 2 NC 40 27.5/12.5 24 V / 50 Hz 3 1/4 09 980 433HS 40-04 4 NC 40 27.5/12.5 24 V / 50 Hz 3 1/4 09 980 436

HS 63-40 4 NO 63 43/12.5 24 V / 50 Hz 3 1/4 09 980 417HS 63-31 3 NO, 1 NC 63 43/12.5 24 V / 50 Hz 3 1/4 09 980 419HS 63-22 2 NO, 2 NC 63 27.5/12.5 24 V / 50 Hz 3 1/4 09 980 434

Accessories HSH 11 1 NO, 1 NC, (AC1/AC15 - 10/3 A), 0.5 module widths 1/10 09 980 497Auxiliary switch for HS 20 (4-pin) / HS 25 / HS 40 / HS 63

HSP 1 25 1/10 09 980 498Lead seal cap for HS 20 (4-pin) / HS 25

SP 40/63 1/10 09 980 499 Lead seal cap for HS 40 / HS 63

Product overview

Artic

le No

. 590

0169

| Date

: 03/2

013 |

© D

oepk

e Sch

altge

räte

GmbH

| Sub

ject to

tech

nical

modifi

catio

ns

DoepkeSchaltgeräte GmbHStellmacherstraße 11 26506 Norden, GermanyPhone +49 4931 1806-0 Fax +49 4931 1806-101Email: [email protected] www.doepke.de

FunctionInstallation contactors are switches activated electromagnetically. If a control current flows through the magnetic coil, the primary circuit closes. It remains in the on-position as long as the control current is flowing.

PropertiesInstallation contactors are particularly well suited to high frequencies of operation for switching high currents. Contactors are only intended up to a point for isolation operations. They must be protected against overloading and short-circuits by upstream protective devices. The HS model satisfies the requirements of utilisation categories AC 1 and AC 3, and to a certain extent AC 7b. The utilisation category denotes the characteristics of the load and the maximum operational current and voltage that the contactor can switch in normal operation. The magnetic coil of the HS model has an extremely low hum level and is suitable for continuous operation (duty ratio 100 %).

ApplicationsInstallation contactors are suitable for versatile deployment in residential and special-purpose buildings, as well as in industrial installations. They are used in switching

» Light bulbs » Fluorescent lamps » Transformers for low voltage halogen lamps » High pressure mercury vapour lamps (HQL, HPL) » Metal halide lamps (HQI, HPI) » Low and high pressure sodium vapour lamps » Thermal storage heating stoves » Drives (motors)

Instal lat ion contactors HS

Doepke

Contact ratings

Lamp typePower rating

Current Capacitor max. number of lamps per pole at 230V / 50 Hz and max. 60°C

W A μF HS20 HS25 HS40 HS63

Light bulbs

60 0.27 - 22 50 92 129

100 0.45 - 13 30 55 77

200 0.91 - 7 15 27 38

300 1.36 - 4 10 19 26

500 2.27 - 3 6 11 16

1000 4.5 - 1 3 6 8

Fluorescent lamps uncompensated

or series compensated

11 0.16 1.3 60 75 210 310

18 0.37 2.7 25 30 90 140

24 0.35 2.5 25 30 90 140

36 0.43 3.4 20 25 70 140

58 0.67 5.3 14 17 45 70

65 0.67 5.3 13 16 40 65

85 0.8 5.3 11 14 35 60

Fluorescent lampsDuo-switch

11 0.07 - 2 x 100 2 x 110 2 x 220 2 x 250

18 0.11 - 2 x 50 2 x 55 2 x 130 2 x 200

24 0.14 - 2 x 40 2 x 44 2 x 110 2 x 160

36 0.22 - 2 x 30 2 x 33 2 x 70 2 x 100

58 0.35 - 2 x 20 2 x 22 2 x 45 2 x 70

65 0.35 - 2 x 15 2 x 16 2 x 40 2 x 60

85 0.47 - 2 x 10 2 x 11 2 x 30 2 x 40

Fluorescent lamps parallel compensated

11 0.09 2.0 30 43 67 107

18 0.13 2.0 20 32 50 80

24 0.16 3.0 15 32 50 80

36 0.27 4.0 10 32 50 80

58 0.45 7.0 6 18 36 46

65 0.5 7.0 5 18 36 46

85 0.6 8.0 4 16 33 44

Fluorescent lamps with electronic

ballast

18 0.09 - 40 40 100 150

36 0.16 - 20 20 52 75

58 0.25 - 15 15 30 55

2 x 18 0.17 - 2 x 20 2 x 20 2 x 50 2 x 60

2 x 36 0.32 - 2 x 10 2 x 10 2 x 25 2 x 30

2 x 58 0.49 - 2 x 7 2 x 7 2 x 15 2 x 20

Transformers for low voltage halogen lamps

20 0.09 - 40 52 110 174

50 0.22 - 20 24 50 80

75 0.33 - 13 16 35 54

100 0.43 - 10 12 27 43

150 0.65 - 7 9 19 29

200 0.87 - 5 5 14 23

300 1.3 - 3 4 9 14

High pressure mercury vapour lamps uncompensated, e. g.: HQL, HPL

50 0.61 - 16 21 38 55

80 0.8 - 12 16 29 40

125 1.15 - 8 11 20 28

250 2.15 - 4 6 11 15

400 3.25 - 3 4 7 10

700 5.4 - 1 2 4 6

1000 7.5 - 1 1 3 4

Lamp typePower rating

Current Capacitor max. number of lamps per pole at 230V / 50 Hz and max. 60°C

W A μF HS20 HS25 HS40 HS63

High pressure mercury vapour lamps

compensated, e. g.: HQL, HPL

50 0.28 7 7 18 36 50

80 0.41 8 5 16 31 44

125 0.65 10 3 13 25 35

250 1.22 18 2 7 14 19

400 1.95 25 1 5 10 14

700 3.45 45 1 3 6 8

1000 4.8 60 - 2 4 6

Metal halide lamps uncompensated

e. g.: HQI, HPI, CDM

35 0.53 - 22 24 57 65

70 1 - 12 14 30 35

150 1.8 - 6 8 17 18

250 3 - 4 5 10 12

400 3.5 - 3 4 8 10

1000 9.5 - 1 1 3 4

2000 16.5 - - - 2 2

400 V per pole2000 10.5 - - - 2 2

3500 18 - - - 1 1

Metal halide lamps compensated

35 0.25 6 8 21 42 58

70 0.45 12 4 11 21 29

150 0.75 20 2 7 13 18

250 1.5 33 1 4 9 11

400 2.1 35 1 4 9 10

1000 5.8 95 - 1 3 4

2000 11.5 148 - - 2 2

400 V per pole2000 6.6 58 - - 3 4

3500 11.6 100 - - 2 3

Metal halide lamps with electronic

ballast (e. g.: PCI) 50-125 x Inlamp for 0.6 ms

20 0.1 integrated 9 9 18 20

35 0.2 integrated 6 6 11 13

70 0.36 integrated 5 5 10 12

150 0.7 integrated 4 4 8 10

Low pressure sodium vapour lamps uncompensated

35 1.5 - 7 9 22 30

55 1.5 - 7 9 22 30

90 2.4 - 4 6 13 19

135 3.3 - 3 4 10 14

150 3.3 - 3 4 10 14

180 3.3 - 3 4 10 14

200 3.3 - 3 4 10 14

Low pressure sodium vapour lamps compensated

35 0.31 20 3 6 15 18

55 0.42 20 2 6 15 18

90 0.63 30 1 4 10 12

135 0.94 45 1 3 7 8

150 1 40 1 3 8 9

180 1.16 40 1 3 8 9

200 1.32 25 - - 10 12

High pressure sodium vapour lamps

uncompensated

150 1.8 - 5 8 17 22

250 3 - 4 5 10 13

330 3.7 - 3 4 8 10

400 4.7 - 2 3 6 8

1000 10.3 - 1 1 3 4

High pressure sodium vapour lamps

compensated

150 0.83 20 2 7 20 25

250 1.5 33 1 4 12 15

330 2 40 1 3 10 13

400 2.4 48 1 2 8 12

1000 6.3 106 - 1 4 6

High pressure sodium vapour lamps with electronic

ballast (e. g.: PCI) 50-125 x Inlamp for 0.6 ms

20 0.1 integrated 9 9 18 20

35 0.2 integrated 6 6 11 13

70 0.36 integrated 5 5 10 12

150 0.7 integrated 4 4 8 10