Refrigeration Piping

download Refrigeration Piping

of 43

Transcript of Refrigeration Piping

  • 8/8/2019 Refrigeration Piping

    1/43

    Refr ig er a t ion Pip in g & Charging

    Res ide nt ia l Ai rCondi t ion i ng R-22

    Rog er D. Hol de r, CM, MSME

    Ref r ige ra t i on i s t he p roc es s o f m oving heat f rom

    o n e l oc a t i o n t o a n o t h e r b y t h e u s e o f r e f r i ge r a n tin a c lo sed c yc l e . The p ip ing and t ub ing sys t emm us t be des igned , i n s t a l l ed and ma in t a ined top rovide p rope r f l ow o f r e f r i ge ran t i n bo th l i qu id

    and gaseous s t a t e s .

  • 8/8/2019 Refrigeration Piping

    2/43

    2

    2

  • 8/8/2019 Refrigeration Piping

    3/43

    3

    3

    Piping & Tubing

    Refrigeration Piping

    Refrigeration is the process of moving heat from one location to another by the use of

    refrigerant in a closed cycle. The piping and tubing system must be designed, installed and

    maintained to provide proper flow of refrigerant in both liquid and gaseous states. A

    successful refrigeration system depends on a good piping design and an understanding of the

    required accessories. The first skill that any refrigeration apprentice mechanic learns is to

    make a soldered joint. Running pipe is so common a task that its critical importance in system

    performance is often overlooked.

    Tubing Inspection & Leak Check

    The object of a good visual inspection of system tubing design is to note obvious oil traps.

    Also look for long vertical suction lengths without p traps and inadequate OD tubing size If the

    system is known to be leaking or if oil is present around mechanical fittings, solder joints,

    gaskets or seals, recover the refrigerant and repair the leaks. Pressurize the system with aresidual amount of refrigerant and dry nitrogen using the recommended test pressure on data

    plate. Maximum test pressures should be approximately 150 psi for high-pressure AC/R

    systems. In chiller applications, controlled hot water or heater blankets will raise pressure

    adequately for a leak check, which should never exceed 10 psi for low pressure chillers. After

    a thorough inspection with a good leak detector, apply a deep vacuum to 500 microns. A good

    triple evacuation, with dry nitrogen and then deep vacuum is the preferred method.

    Piping Basic Principles

    Refrigeration piping involves extremely complex relationships in the flow of refrigerant and oil.

    Fluid flow is the study of the flow of a gas or a liquid, and the inter-relationship of velocity,

    pressure, friction, density and the work required to cause the flow. The design of a

    refrigeration piping system is a continuous series of compromises. It is desirable to have

  • 8/8/2019 Refrigeration Piping

    4/43

    4

    4

    maximum capacity at minimum cost, as well as proper oil return. Since oil must pass through

    the compressor cylinders to provide lubrication, a small amount of oil is always circulating

    with the refrigerant. Oil and refrigerant vapor, however, do not mix readily, and the oil can be

    properly circulated through the system only if the mass velocity of the refrigerant vapor is

    great enough to sweep the oil along. To ensure oil circulation adequate velocities of

    refrigerant must be maintained in the suction and discharge lines, and in the evaporator.

    The design of refrigerant piping systems should:

    Ensure proper refrigerant feed to evaporators.

    Provide practical refrigerant line sizes without excessive pressure drop.

    Prevent excessive amounts of lubricating oil from being trapped in any part of the system.

    Protect the compressor at all times from loss of lubricating oil.

    Prevent liquid refrigerant or oil slugs from entering the compressor during operating and

    idle time. Maintaining a clean and dry system.

    Refrigerant Line Velocities Economics, pressure drop, noise, and oil entrapment require establishing feasible design

    velocities in refrigerant lines.

    Suction line 700 to 4000 fpm

    Discharge line 500 to 3500 fpm Condenser drain line 100 fpm or less

    Liquid line 125 to 450 fpm

    Higher gas velocities are sometimes found in relatively short suction lines, on comfort air

    conditioning or other applications where the operating time is only 2000 to 4000 hours per

    year and where low initial cost of the system may be more significant than low operating cost.

    In the Industrial refrigeration applications where equipment runs continuously, should bedesigned with low refrigerant velocities for most efficient compressor performance and low

    equipment operating cost. Care must be taken that the velocities is not to low that oil is taped

    in the refrigeration lines.

    Liquid line from condenser to receivers should be sized for 100 fpm or less to ensure positive

  • 8/8/2019 Refrigeration Piping

    5/43

    5

    5

    gravity flow without incurring backup of liquid flow. Liquid lines from receivers to evaporator

    should be sized to maintain velocities below 300 fpm, thus minimizing or preventing liquid

    hammer when solenoids or other electrically operated valves are used.

    Refrigerant Line Sizing

    In sizing refrigerant lines, cost considerations favor keeping line size as small as possible.

    However, suction and discharge line pressure drops cause loss of compressor capacity and

    increased power use. Excessive liquid line pressure drops can cause the liquid refrigerant to

    flash, resulting in faulty expansion valve operation. Refrigeration systems are designed so that

    friction pressure losses do not exceed a pressure differential equivalent to a corresponding

    change in the saturation boiling temperature. The primary measure for determining pressure

    drop is a change in saturation temperature. Pressure drop in refrigerant lines causes a

    reduction in system efficiency. Correct sizing must be based on minimizing cost andmaximizing efficiency. Pressure drop calculations are determined as normal pressure loss

    associated with a change in saturation temperature of the refrigerant. Typically, the

    refrigeration system will be sized for pressure losses of 2F or less for each segment of the

    discharge, suction, and liquid lines. An HFC refrigerant liquid line is sized for pressure losses

    of 1F or less.

    Discharge lines should be designed to:

    Avoid trapping oil at part-load operation. Prevent condensed refrigerant and oil from draining back to the head of the compressor.

    Have carefully selected connections from a common line to multiple compressors.

    Avoid developing excessive noise or vibration from hot-gas pulsation, compressor

    vibration, or both.

    When sizing discharge lines, considerations similar to those applied to the suction line are

    observed. Pressure loss in discharge lines increases the required compressor power per unit

    of refrigeration and decreases the compressor capacity by increasing the compression ratio.While the discharge line pressure drop is not as critical as that of the suction line, the

    accepted maximum values are 4 psi for R-12 and 6 psi for R-22. The same minimum gas

    velocities of 500 feet per minute in horizontal runs and 1000 feet per minute in vertical runs

    with upward gas flow are observed. The maximum acceptable gas velocity, based on noise

    considerations, is 4000 feet per minute.

  • 8/8/2019 Refrigeration Piping

    6/43

    6

    6

    Condenser Drain Line

    The line between a condenser (not providing liquid subcooling) and a liquid receiver, when

    such an arrangement is used, must be carefully sized. While it is almost impossible to oversize

    such a line, under sizing is to be avoided. An undersized line can restrict the flow of refrigerant

    to the extent that some of it is held in the condenser. If some of the condenser surface is

    flooded, the capacity is reduced. These causes the head pressure to rise and decrease the

    overall system capacity. At the same time, the power to drive the compressor rises.

    There are a few points that the piping designer should keep in mind.

    Condenser drain line velocity should be 100 fpm or less.

    The distance from the condenser to receiver should be as short as possible.

    The condenser must be located above the receiver.

    If the system is equipped with an air-cooled condenser and a liquid receiver, it is good

    practice to locate the receiver within the building. Some means should be provided to isolate

    the receiver from the condenser during cold weather shutdown, such as a combination check

    and relief valve.

    Receiver

    Refrigerant receivers are vessels used to store excess refrigerant while still allowing

    circulation throughout the system. Receivers perform the following functions:

    Provide pumpdown storage capacity when another part of the system must be serviced or

    the system must be shut down for an extended time. In some water-cooled condenser

    systems, the condenser also serves as a receiver if the total refrigerant charge does not

    exceed its storage capacity.

    Handle the excess refrigerant charge that occurs with air-cooled condensers using the

    flooding type condensing pressure control.

    Accommodate a fluctuating charge in the low side. Drain the condenser of liquid.

    Maintain an adequate affective condensing surface on system where the operating charge in

    the evaporator and or condenser varies for different loading conditions. When an evaporator is

    fed with a thermal expansion valve, hand expansion valve, or low-pressure float, the operating

    charge in the evaporator varies considerably depending on the loading. During low load, the

    evaporator requires a larger charge since the boiling is not as intense. When the load

  • 8/8/2019 Refrigeration Piping

    7/43

    7

    7

    increases, the operating charge in the evaporator decreases, and the receiver must store

    excess refrigerant. Hold the full charge of the idle circuit on systems with multicircuit evaporators that shut off

    the liquid supply to one or more circuits during reduced load.

    Receiver Design Considerations

    Receiver should be close to the condenser.

    If there is any doubt about the line size, use the larger of the sizes.

    Always adhere to the minimum vertical dimension required to overcome friction.

    Install a pressure relief device on top of each receiver and on condenser.

    The surge receiver pressure relief device is piped together with condensers.

    Size the receiver to hold 40 to 125% of refrigerant charge depending on system load

    variance.

    When a through type receiver is used, the liquid must always flow from the condenser to the

    receiver. The piping must provide free flow of liquid from the condenser to the receiver by

    equalizing the pressure between the two. If a vent is not used, the piping between condenser

    and receiver is sized so that liquid flows in one direction and gas flows in the opposite

    direction. Sizing the condensate drain line for 100 fpm liquid velocity is usually adequate to

    attain this flow. Piping should slop at least 0.25 in/ft and eliminate any natural liquid traps. The

    condensate drain line should be sized so that the velocity does not exceed 100 fpm.

    Please consult the manufacturers literature for making receiver capacity comparisons when

    changing refrigerants.

    Liquid Lines

    Pressure drop should not be so large as to cause gas formation in the liquid line or insufficient

    liquid pressure at the liquid feed device. Systems are normally designed so that the pressure

    drop in the liquid line, due to friction, is not greater than that corresponding to about a 1 to

    2F change in saturation temperature.

    Pressure drop (in psig) for a change of 1F saturation at 100F condensing

    pressure: (R-508B is at 10F):

  • 8/8/2019 Refrigeration Piping

    8/43

    8

    8

    Liquid subcooling is the only method of overcoming the liquid line pressure losses in

    order to guarantee liquid at the expansion device in the evaporator. If the subcooling is

    insufficient, flashing will occur within the liquid line and degrade the efficiency of the

    system. Friction pressure drops in the liquid line are caused by accessories such as

    solenoid valves, filter driers, and hand valves, as well as by the piping and fittings

    between the receiver outlet and the refrigerant feed device at the evaporator. Liquid

    line risers are also a source of pressure loss. The loss due to a riser is approximately0.556 psi per foot of liquid lift. The total loss is the sum of all friction losses plus the

    pressure loss from liquid risers. Refrigeration systems that have no liquid risers and

    have the evaporator below the condenser and/or receiver benefit from a gain in

    pressure due to liquid weight. They can thus tolerate larger friction losses without

    flashing. When flashing occurs, the overall efficiency is reduced and the system may

    malfunction. The only way to reduce the effect of pressure loses and friction is by

    subcooling the refrigerant.

    Suction Lines

    Suction lines are more critical than liquid and discharge line from a design and

    construction standpoint. They should be designed to: Provide a minimum pressure drop at full load.

    Return oil from the evaporator to the compressor under minimum load conditions.

    Prevent oil from draining from an active evaporator into an idle one.

    A pressure drop in the suction line reduces a systems capacity by forcing the

    compressor to operate at a lower suction pressure, in order to maintain a desired

    evaporating temperature in the coil. As the suction pressure is decreased, each pound

    of refrigerant returning to the compressor occupies a greater volume, and the weight

    of the refrigerant pumped by the compressor decreases. For example, a typical low

  • 8/8/2019 Refrigeration Piping

    9/43

    9

    9

    temperature R-502 compressor at -40F evaporating temperature will lose almost 6% of

    its rated capacity for each 1 psi suction line pressure drop. Normally accepted design

    practice is to use a suction line pressure drop equivalent to a 2F change in saturation

    temperature.

    Of equal importance in sizing the suction line is the necessity of maintaining adequate

    velocities to properly return oil to the compressor. Studies have shown that oil is most

    viscous in a system after the suction vapor has warmed up a few degrees from the

    evaporating temperature, so that the oil is no longer saturated with the refrigerant.

    This condition occurs in the suction line after the refrigerant vapor has left the

  • 8/8/2019 Refrigeration Piping

    10/43

    10

    10

    evaporator.

    Movement of the oil through suction lines is dependent on both the mass and velocity

    of the suction vapor. As the mass or density decreases, higher velocities are required

    to force the oil along.

    Nominal minimum velocities of 700 fpm in horizontal suction lines and 1500 fpm invertical suction lines have been recommended and used successfully for many years

    as suction line sizing design standards. Use of the one nominal velocity provided a

    simple and convenient means of checking velocities. However, tests have shown that

    in vertical risers the oil tends to crawl up the inner surface of the tubing, and the larger

    the tubing, the greater velocity required in the center of the tubing to maintain tube

    surface velocities that will carry the oil. The exact velocity required in the vertical line

    is dependent on both the evaporating temperature and the line size, and under varying

    conditions, the specific velocity required might be either greater or less than 1500 fpm.

    An HFC refrigerant, however, is designed for 1500 fpm or greater.

    Always pitch vapor lines in the direction of flow, 1/2 inch per ten-foot of suction line.

    P traps for uphill oil return should be used after the first 6- foot and every 12-foot

    thereafter. It is good practice to use an inverted trap just before entering the

    compressor.

    Double Risers

    On systems equipped with capacity control compressors, or where tandem or multiple

    compressors are used with one or more compressor cycled off for capacity control, a

    single suction line riser may result in either unacceptably high or low gas velocities. A

    line properly sized for light load conditions may have too high a pressure drop atmaximum load, and if the line is sized based on full load condition, then velocities may

    not be adequate conditions to move oil through the tubing at light load. On air

    conditioning applications where somewhat higher pressure drops at maximum load

    conditions can be tolerated without any major penalty in overall system performance,

    it is usually preferable to accept the additional pressure drop imposed by a single

    vertical riser. However, on medium or low temperature applications where pressure

  • 8/8/2019 Refrigeration Piping

    11/43

    11

    11

    drop is more critical and where separate risers from individual evaporators are not

    possible, a double riser may be necessary to avoid an excessive loss of capacity.

    A typical double riser has a small and large riser. The two should be sized so that the

    total cross-sectional area is equivalent to the cross-section area of a single riser that

    would have both satisfactory gas velocity and acceptable pressure drop at maximumload conditions. The larger is trapped and the smaller line must be sized to provide

    adequate velocities and acceptable pressure drop when the entire minimum load is

    carried in the smaller riser.

    Another method of suction oil return is the use of a double riser, as shownin Figure 1. Oil return is accomplished with this method at minimum loads. In addition,

    excessive pressure drop at full load is avoided. The small riser A is sized to return

    oil under minimum capacity conditions. Riser B which, may be larger, is sized so

    pressure drop through both risers during full load conditions is adequate. Traps with

    minimum oil holding capacity are recommended.

  • 8/8/2019 Refrigeration Piping

    12/43

    12

    12

    Suction Line Double Risers Sizing

    Single Riser Size Double Riser Sizes 2/3, 1/3

    1 1/8 = .83 7/8 and 3/4 = .83

    1 3/8 = 1.26 1 1/8 and 7/8 = 1.311 5/8 = 1.78 1 3/8 and 7/8 = 1.74

    2 1/8 = 3.10 1 5/8 and 1 3/8 = 3.04

    2 5/8 = 4.77 2 1/8 and 1 5/8 = 4.88

    3 1/8 = 6.81 2 5/8 and 1 5/8 = 6.55

    Defrost Gas Supply Lines

    Sizing refrigeration lines to supply defrost gas to one or more evaporator is an

    estimate at best. The parameters associated with sizing the defrost gas lines are

    related to allowable pressure drop and refrigerant flow rate during defrost. Design

    professionals typically use approximately two times the evaporator load for effective

    refrigerant flow rate to determine line-sizing requirements. The pressure drop is not as

    critical during the defrost cycle, and many engineers have used velocity as criterion

    for determining line size. The effective condensing temperature and average

    temperature of the gas must be determined. The velocity determined at saturated

    conditions will give a conservative line size. It is recommended that initial sizing be

    based on twice the evaporator flow rate and that velocities from 1000 to 2000 fpm be

    used for determining the defrost gas supply line size.

    Refrigerant Line Capacity Tables & Equivalent Lengths Of Valves & Fittings

    Refrigerant line capacity tables are based on unit pressure drop per 100 ft length ofstraight pipe or per combination of straight pipe, fitting, and valves with friction drop

    equivalent to a 100 ft length of straight pipe. Generally, pressure drop through valves

    and fittings is determined by establishing the equivalent straight length of pipe of the

    same size with the same friction drop. Alternately, one rule of thumb is to add 50% to

    the calculated pipe length to account for pressure drops from fittings and valves.

  • 8/8/2019 Refrigeration Piping

    13/43

    13

    13

    Expansion & Contraction

    Temperature change will expand and contract all refrigeration piping material.Techniques must allow for expansion and contraction changes to prevent stresses

    that may buckle, bend or rupture the refrigerant piping. he two common methods of

    taking care of expansion and contraction in copper piping are the expansion loops

    or pipe offsets. During the installation of the line, care must be taken that the line

    maintains a perfect alignment.

    On average, coppers coefficient of expansion is 0.0000104 inch per inch per degreeFahrenheit. Thus, expansion of copper is 1.25 inch per 100 feet per 100F change. For

    example, a copper compressor discharge line of 75 feet long at 225F could have a

    temperature change of 150F in a 70F room. Therefore, 1.25 X 1.55 (temperature

    change per 100F) X .75 (length per 100 feet) will equal 1.453 inches of expansion. The

    75 foot long line would now be approximately 75 feet, 1-1/2 inches long.

    Location & Arrangement of Piping

    Refrigerant lines should be as short and direct as possible to minimize tubing and

    refrigerant requirements and pressure drops. Plan piping for a minimum number of

    joints, using as few elbows and other fitting as possible, but provide sufficient

    flexibility to absorb compressor vibration and stresses due to thermal expansion and

    contraction.

  • 8/8/2019 Refrigeration Piping

    14/43

    14

    14

    Arrange refrigerant piping so that normal inspection and servicing of the compressor

    and other equipment is not hindered. Do not obstruct the view of the oil level sight

    glass, or run piping so that it interferes with the removal of compressor cylinder head,

    end bells, access plates, or any internal parts. Suction line piping to the compressor

    should be arranged so that it will not interfere with removal of the compressor for

    servicing.

    You must provide adequate clearance for insulation installation between the piping,

    wall, and hangers. Use sleeves that are sized to permit installation of both pipe and

    insulation through floor, walls, or ceilings. Set the sleeves prior to pouring of concrete

    or erection of brickwork. Piping must not interfere with passages or obstruct

    headroom, windows, or doors. Refer to ASHRAE Standard 15, Safety Code for

    Mechanical Refrigeration, and other governing local codes for restrictions that may

    apply.

    Protection Against Damage To Piping

    Protection against damage is necessary, particularly for small lines, which have a false

    appearance of strength. Where traffic is heavy, provide protection against impact from

    pedestrian and motorized traffic.

    Piping InsulationAll piping joints and fittings should be thoroughly leak tested before insulation is

    sealed. Suction lines should be insulated to prevent sweating and heat gain. Insulation

    covering lines on which moisture can condense or lines subjected to outside

    conditions must be vapor sealed to prevent any moisture travel through the insulation,

    or condensation in the insulation. Although the liquid line ordinarily does not require

    insulation, the suction and liquid lines can be insulated together. The liquid line should

    be insulated to minimize heat gain if it passes through an area of higher temperature.Hot gas discharge lines usually are not insulated, however, they should be insulated if

    the heat dissipated is objectionable or if necessary to prevent injury from high

    temperature surfaces.

  • 8/8/2019 Refrigeration Piping

    15/43

    15

    15

    Vibration & Noise in Piping

    Two undesirable effects of vibration of refrigerant piping are: 1) physical damage to

    the piping, which may result in the breaking of brazed joints and consequent loss of

    charge; and 2) transmission of noise through the piping itself and through building

    construction with which the piping may come into direct physical contact. Both can beeliminated or minimized by proper piping design and installation.

    Using Manufacturers Pressure Drop & Velocity Charts

    Always size for pressure drop first, then velocity. On the top right of the pressure drop

    chart in Figure 8-3, you will find tons of refrigeration or cooling capacity calibrated in

    Btu per hour up to 1 ton, and in tons of cooling from 1 ton to 100 tons. You start thesizing procedure by drawing a straight line from your systems designated capacity

    through the diagonal lines on the right side of the chart.

    The diagonal lines represent: The evaporator temperature, used to size the suction line.

    The discharge line temperature, used to size the hot gas discharge.

    The liquid lines diagonal line, used to size the liquid line.

  • 8/8/2019 Refrigeration Piping

    16/43

    16

    16

    The diagonal lines on the left of the chart represent the actual tubing sizes that will be

    derived by your calculation. Starting at the bottom line, representing 3/8" OD Type Lcopper tubing and increasing in size up through 6-1/8. Draw a horizontal line from each

    intersection of tonnage and each of the three diagonal lines, horizontally across

    through the tubing sizes.

    On the bottom left of the chart you will find the pressure drop graph. The three

    horizontal lines represent condenser coil temperature applications. The curved

    diagonal lines are pressure drop in psi per 100 ft. When you have determined

    necessary condenser coil temperature follow the horizontal line to the required

    pressure drop. Draw a line straight up until it intersects with the horizontal line used to

    determine tubing size. If it falls in between two sizes then your size is the tubing size

    up and to the left. For example, lets size for a 6-ton R-134a medium temperature walk-

    in refrigerator using the chart in your book:

  • 8/8/2019 Refrigeration Piping

    17/43

    17

    17

    First, find 6 tons on the top right of your chart and draw a vertical line straight down

    through all of the diagonal lines.

    Medium temperature requires a 20F evaporator so draw a line from the diagonal line

    designated 20F horizontally all the way across the chart.

    Do the same from the diagonal line labeled Discharge Line.

    And again from the diagonal line labeled Liquid Line.

    The suction line pressure drop maximum for medium temperature is 1-1/2 psi so the

    suction line size will be 1-5/8". We require a 3psi pressure drop for our liquid line so

    the line size is 5/8". The hot gas discharge line is a bit more forgiving, 10 psi or less,

    so 1-1/8" will work adequately. The velocity chart is very similar to the pressure drop

    chart and is used in the same way. The idea is to confirm the sizes you found on the

    pressure chart by cross checking with the applicable velocities on the velocity chart. If

    you plot the same temperature variables on the velocity chart, youll find the sizes

    chosen will fall between minimum and maximum velocities recommended for each

    refrigeration line. There are exceptions and sometimes economical compromises on

    many close-coupled and field fabricated systems. It is these exceptions that may need

    careful consideration before retrofit.

  • 8/8/2019 Refrigeration Piping

    18/43

    18

    18

  • 8/8/2019 Refrigeration Piping

    19/43

    19

    19

  • 8/8/2019 Refrigeration Piping

    20/43

    20

    20

  • 8/8/2019 Refrigeration Piping

    21/43

    21

    21

  • 8/8/2019 Refrigeration Piping

    22/43

    22

    22

  • 8/8/2019 Refrigeration Piping

    23/43

    23

    23

  • 8/8/2019 Refrigeration Piping

    24/43

    24

    24

  • 8/8/2019 Refrigeration Piping

    25/43

    25

    25

  • 8/8/2019 Refrigeration Piping

    26/43

    26

    26

    404A

  • 8/8/2019 Refrigeration Piping

    27/43

    27

    27

  • 8/8/2019 Refrigeration Piping

    28/43

    28

    28

    402A

  • 8/8/2019 Refrigeration Piping

    29/43

    29

    29

  • 8/8/2019 Refrigeration Piping

    30/43

    30

    30

  • 8/8/2019 Refrigeration Piping

    31/43

    31

    31

  • 8/8/2019 Refrigeration Piping

    32/43

    32

    32

  • 8/8/2019 Refrigeration Piping

    33/43

    33

    33

    Charging Residential Air Conditioning R-22

    Different types of metering devices have different ways of charging. A Thermostatic

    Expansion Valve (TXV) is charged to the subcooling of the liquid line leaving thecondenser. A fixed orifice is charged to the superheat of the suction line leaving the

    evaporator. To under stand why this is, it requires an understanding of the physical

    properties of the refrigeration cycle. The four main components of the refrigeration

    cycle include: Compressor

    Condenser

    Metering Devices

    Evaporator

    These four components are divided into sections and explained in depth as follows.

    Compressor

    The Compressor compresses a low-pressure superheated gas into a high-pressuresuperheated gas. If the suction gas is not superheated, the compressor can be

    damaged. The compressor pulls the refrigerant out of the evaporator and pushes it

    though a condenser. The act of compression is performed by any one of the following

    six types of compressors: a reciprocating piston, rotary, scroll, screw, centrifugal, and

    sonic compressors. Of the six, the reciprocating and scroll compressors are the two

    most frequently found in a residential air conditioning system.

    The mass flow rate produced by a compressor is equal to the mass of the suction gas

    pulled in by the compressor. The compressors out put is equally only to its intake

    because the mass flow must be equal. The process of compression, through mass

    flow, raises the temperature and pressure of the refrigerant. The result of the

    temperature increase is superheat. Pressure and temperature of the refrigerant must

    be higher than the condensing temperature. The refrigerant temperature must be

  • 8/8/2019 Refrigeration Piping

    34/43

    34

    34

    higher so heat can flow into the condensing medium. This process explains the

    necessary relationship between the increased pressure and the rise in temperature. If

    the pressure and temperature is not increased through compression, there is no heat

    transferred from the refrigerant to the condensing medium. The compressor has a

    maximum inlet temperature of about 70 degrees and outlet of about 225 degrees.

    Inlet refrigerant gas cools the compressor motor.

    Desuperheating (heat leaving the refrigerant gas) of refrigerant begins as it is

    discharged. From a compressor and pushed into a condenser.

    Condenser

    The condenser removes heat and changes a high-pressure vapor into a high-pressureliquid. As the superheated (high-pressure) gas is pushed into the condenser, it is

    desuperheated, that is the temperature is reduced to saturated pressure-temperature.

    The refrigerant does not start to change state until the temperature reaches saturated

    pressure-temperature. The only variable that can change the temperature is a

    pressure change. (See table 1) At saturation pressure-temperature point, the change

    of state becomes latent heat (invisible or hidden heat). Latent heat is a lack of rise orfall of temperature during a change of state (saturation). When the temperature does

    not rise or fall it is at saturation and the change of state process begins. Refrigerant

    continues to change state at one pressure-temperature. The only variable that can

    change a temperature is a pressure change. If a temperature change occurs a

    pressure change occurs. If a pressure change occurs a temperature change occurs.

    At the change of state the refrigerant liquid and vapor are at the same temperature.

    This is defined as equilibrium contact. The temperatures of the liquid and vapors will

    stay the same until the temperature of the refrigerant starts to drop. Temperature of

    the refrigerant start to drop once 98% to 99% of the refrigerant becomes a liquid. This

    is called subcooling. Subcooling is a temperature below saturated pressure-

    temperature. (See table 1) Subcooling is a measurement of how much liquid is in the

    condenser. In air conditioning, it is important to measure subcooling because the

    longer the liquid stays in the condenser, the greater the sensible (visible) heat loss.

  • 8/8/2019 Refrigeration Piping

    35/43

    35

    35

    Low subcooling means that a condenser is empty. High subcooling means that a

    condenser is full. Over filling a system increases, pressure due to the liquid filling of a

    condenser that shows up as high subcooling. To move the refrigerant from

    condenser to the liquid line, it must be pushed down the liquid line to a metering

    device. If a pressure drop occurs in the liquid line and the refrigerant has no

    subcooling, the refrigerant will start to re-vaporize (change state from a liquid to avapor) before reaching the metering devise.

    Refrigerant 22

    Liquid line

    Saturated temperate - Temperature = subcooling

    200 psig = 101 degrees - 96 degrees = 5 degrees

    210 psig = 105 degrees - 90 degrees = 15 degrees

    240 psig = 114 degrees - 98 degrees = 16 degrees

    (Table 1)

    Metering Devices

    A metering device is a pressure drop point, which has two jobs:

    1. Holds refrigerant back in a condense; and

    2. Feeds refrigerant into the evaporator.

    When high-pressure liquid enters a metering device, pressure starts to drop, as the

    temperature remains the same until it reaches saturation pressure-temperature. At

    this time both the pressure and temperature continues to drop to evaporator pressure-

    temperature. (See table 2) Low-pressure liquid that is leaving the metering device is

    boiling at saturated pressure-temperature. The process of a refrigerant changing its

    state (from a liquid to a vapor) in the metering device is called flash gas. Flash gas is

    what cools the refrigerant liquid in the metering device. A system with no subcooling

  • 8/8/2019 Refrigeration Piping

    36/43

    36

    36

    has more gas that is flashed and less capacity.

    Evaporators The refrigerant enters the evaporator as a boiling low-pressure liquid at saturated

    pressure-temperature. It continues to boil at one temperature as long as the pressure

    remains the same. If there is not a pressure change in the evaporator, there will not be

    a temperature change in the refrigerant changing state. At saturation, refrigerant

    absorbs latent heat, which is a change of state heat. The refrigerant changes state at

    one temperature (for any one pressure) from the beginning of the evaporator until the

    entire liquid refrigerant has become a vapor. The only variable that can change a

    temperature is a pressure change. If a temperature change occurs a pressure change

    occurs. In latent heat, the liquid and vapor are at the same temperature due toequilibrium contact. When heat is added to the gas, past saturation pressure-

    temperature, it is called superheat. (See Table 2) Superheat is an indication of how full

    the evaporator is of liquid refrigerant. High superheat means the evaporator is empty.

    Low superheat means the evaporator is full. There have been reports that liquid

    refrigerant can still be boiling with 2 degrees of superheat. Superheat should never

    be observed below 4 degrees or a compressor failure may occur. The superheat gas

    is pulled into the compressor were it starts the cycle again.

    Refrigerant 22

    suction line

    Saturated temperate - Temperature = superheat

    58 psig = 32 degrees - 44 degrees = 12 degrees

    64 psig = 37 degrees - 47 degrees = 10 degrees

    70 psig = 41 degrees - 50 degrees = 9 degrees

    (Table 2)

  • 8/8/2019 Refrigeration Piping

    37/43

    37

    37

    Charging MethodsBefore charging of a residential air conditioning system, two temperatures must be

    recorded:

    1. Condensing air inlet dry bulb temperature.

    2. Evaporator air inlet wet bulb temperature. Wet bulb temperature is a measurement

    of the heat contained within air. Air may have many different wet bulb temperaturesfor one dry bulb temperature, depending on relative humidity of the air.

    Different types of metering devices have different ways of charging.

    Thermostatic Expansion Valve R-22A/C with a Thermostatic Expansion Valve (TXV) is charged to the subcooling of the

    liquid line leaving the condenser because the superheat is fixed. The superheat is

    fixed at 8 to 12 degrees in most residential air conditioning systems. Subcooling is the

    amount of liquid held back in the condenser. This allows the liquid to give up more

    heat, below saturated pressure- temperature. For every one degree of subcooling at

    the same condensing pressure, capacity will increase .5 percent. Increasing

    subcooling with an increase of discharge pressure and compression ratio, decrease

    capacity. Add 5 degrees of subcooling for every 30 feet of liquid line lift.

    To measure subcooling:

    1. Obtain refrigerant saturation pressure-temperature. Take a pressure reading of the

    liquid line leaving the condenser. Refrigerant saturation temperature is the pressure-

    temperature when the refrigerant is turning from a high-pressure vapor into a high-

    pressure liquid (giving up heat). At saturation pressure-temperature, both liquid and

    vapor are at the same temperature.

    2. Convert pressure to temperature with a pressure temperature chart.3. Take a temperature reading at the leaving liquid line of the condenser.

    4. Compare both, the saturated temperature and leaving liquid line temperature.

    Subtracting one from the other, the difference is the amount the refrigerant has cooled

    past saturated temperature. This is subcooling. (See table 1)

    This four-step procedure is known as subcooling. Manufacturers should be able to

  • 8/8/2019 Refrigeration Piping

    38/43

    38

    38

    identify the amounts of subcooling they have designed into a system. A low charge

    will give a low subcooling. An overcharge will give a high subcooling along with a

    high compression ratio. Do not worry about a few bubbles in the sight glass. Sight

    glasses will not always be clear with a full charge. The zeotropes refrigerant group is

    known for their fractionation. It is possible to never have a clear sight glass. To

    determine what the subcooling should be in a system (see table 3).

    Subcooling for A/C with TXV R-22

    Evaporator Inlet Air Temperature Fahrenheit Wet Bulb57 59 61 63 65 67 69 71 73

    Outside AirTemperature DB75 25 24 23 22 21 20 19 18 1780 24 23 22 21 20 19 18 17 1585 23 22 21 20 19 18 17 16 1490 22 21 20 19 18 16 15 14 1295 21 20 19 18 17 15 13 12 10100 20 19 18 17 15 13 12 10 8105 19 18 17 16 14 12 10 8 6110 17 16 15 13 12 10 8 6 4115 15 14 13 12 10 8 6 4 2

    (Table 3) + --2 degrees

    Fixed Orifice R-22A/C with a fixed orifice is charged to the superheat of the suction line leaving the

    evaporator. Superheat is the gas temperature above the saturated temperature.

    Superheat can be split into two types of heat:

    1. Superheat of the evaporators; and

    2. Total superheat entering the compressor.

    The evaporators superheat must be figured at the evaporator outlet not at the

    compressor inlet. Total superheat is figured at the compressor inlet.

    To measure evaporator superheat:

    1. Take a pressure reading of the suction line-leaving evaporator to get refrigerant

    saturation pressure-temperature. Refrigerant saturation temperature is the pressure-

  • 8/8/2019 Refrigeration Piping

    39/43

    39

    39

    temperature when the refrigerant is turning from a low-pressure liquid to a low-

    pressure vapor (absorbing heat). At saturation pressure-temperature, both liquid and

    vapor are at the same temperature.

    2. Convert pressure to temperature with a pressure temperature chart. If reading is

    obtained at the compressor, not at the evaporator leaving line, you may have to add a

    few pounds of pressure due to pressure drop in the suction line.3. Take a temperature reading at the leaving suction line of the evaporator.

    4. Compare both, the saturated temperature and the leaving suction line temperature.

    Subtracting one from the other, the difference is the amount the refrigerant gas has

    heated past saturated temperature. This is superheat. (See table 2)

    This four-step procedure is known as superheat. Manufacturers should be able to

    identify the amounts of superheat they have designed into a system. A low charge will

    give a high superheat. An overcharge will give a low superheat along with a higher

    compression ratio. To determine what superheat in a system should be, see (table 4).

    Superheat for A/C with fixed Orifice R-22

    Evaporator Inlet Air Temperature Fahrenheit Wet Bulb

    54 56 58 60 62 64 66 68 70 72 74Outside AirTemperature DB60 13 17 18 20 24 26 28 30 33 36 3965 11 13 15 17 18 22 25 28 30 33 3670 8 11 12 14 16 18 22 25 28 30 3375 5 7 10 12 14 16 18 23 26 28 3080 4 6 8 12 14 16 18 23 27 2885 4 6 8 12 14 17 20 25 2790 4 6 9 12 15 18 22 25

    95 4 7 11 13 16 20 23100 5 8 11 14 18 20105 4 6 8 12 15 19110 5 7 11 14 18115 5 8 13 16

    (Table 4) +-- 2 degrees

  • 8/8/2019 Refrigeration Piping

    40/43

    40

    40

    Total Superheat Method

    Some residential air-conditioning system with fixed orifice may be charged by the total

    superheat method. Various equipment manufacturers furnish charts with their units

    that explain the proper procedures to the installing or servicing technician.

    This method, similar to evaporator superheat method, is effective only when the indoor

    conditions are within 2F of desired indoor comfort conditions and the suctionpressure and temperature is stabilized.

    To measure total superheat:

    1. Read and record the outdoor ambient air-dry bulb temperature entering the

    condenser.

    2. Read and record suction line pressure and temperature at the suction service valve

    or service port at compressor.

    3. From Table 5, the reading at the intersection of vapor pressure and outdoor ambient

    temperature should coincide with the actual vapor line temperature.

    4. If the vapor line temperature is not the same, adjust the refrigerant charge. Adding

    R-22 will raise suction pressure and lower suction line temperature. Removing R-22

    will lower suction pressure and raise suction line temperature.

    Caution: If adding R-22 increases both suction pressure and temperature, the unit is

    overcharged.

    This method is very useful when performing preventive maintenance or corrective

  • 8/8/2019 Refrigeration Piping

    41/43

    41

    41

    service on residential air conditioning. Remember to always refer to the

    manufacturers recommendations whenever possible.

    Vapor pressure at service valve

    52 54 56 58 60 62 64 66 68 70 72 74 76 78 80 82 84

    Outdoor T Vapor line T at compressor F

    100+ 43 45 46 47 49 50 51 53 54 55

    100 44 45 47 48 49 51 52 53 55 56 57

    95 45 47 48 50 51 52 54 55 56 58 59 60

    90 49 51 52 54 55 56 58 59 60 62

    85 52 53 55 56 58 59 61 62 63

    80 53 55 56 58 59 61 62 63 65

    75 55 56 58 59 61 62 64 65 66

    70 55 57 58 60 61 63 64 66 67

    65 57 58 60 61 63 64 66 67 69

    RefrigerationThe use of sight glass for charging is common in refrigeration. It is better to charge a

    system first by measuring the operating condition (discharge and suction pressures,

    suction line temperature, compressor amps, super heat, subcooling and coils

    temperature deferential) before using the liquid line sight glass. If the sight glass is

    close to the exit of the condenser or if there is very little subcooling at the sight glass,

    bubbles may be present even when the system is properly charged. If a system is

    charged to full sight glass, overcharging may be the result, decreasing efficiency.

    Note: Follow the manufacturer recommendation for superheat and subcooling.

  • 8/8/2019 Refrigeration Piping

    42/43

    42

    42

    A Thermostatic Expansion Valve (TXV) is designed to maintain a constant superheat.

    Over charging a TXV will rise subcooling, increases system pressures, and decreases

    system efficiency. Under charging a TXV will decrease subcooling, increases

    superheat, decrease system capacity, and lower refrigerant velocity leaving oil in the

    evaporator. An Automatic Expansion Valve (AXV) is a constant evaporator pressurevalve and not normally used in A/C. A fixed orifices is the simplest metering devise

    made and the most critical to charge. Over charging fixed orifices will lower

    superheat, increases pressures, decrease efficiency, and flood the compressor with

    liquid refrigerant. Under charge, the fixed orifices will raise superheat, lower pressure,

    lower capacity, and lower refrigerant velocity leaving oil in the evaporator. Always

    refer to the manufacturer recommendations on charging fixed orifices.

    The process of charging to superheat and subcooling improves an air conditioning

    systems efficiency, capacity and lessens equipment failures. Always let system

    stabilize (10 to 20 minutes) after adjusting the charge, this takes time but improves

    efficiency and capacity.

    Remember when changing refrigerants all superheat and subcooling adjustments have

    to be checked and recorded. The procedure of recording adjustments is called

    Baselining. This procedure not only saves time, money, and aggravation but it is asign of a professional.

    Roger D. Holder, CM, BSME, Is the owner of R D Holder Eng in Bakersfield CA, 661-

    665-8893, He also is a Refrigeration and Air Conditioning specialist at National

    Technical Transfer Inc., P. O. Box 4558 Englewood, CO 80155 (800) 922-2820

  • 8/8/2019 Refrigeration Piping

    43/43

    43