1 Rectifiers adjustable to rated voltage
2 1U=44.45mm
3 1TE=5.08mm
4 3 different versions for each nominal voltage
Right to make technical changes reserved
Rectifiers
Device Designation FP1 700 HR 1300 HR 1400 FP1 1800Type Flatpack 700 E48/25 WBrug-1GRM01 E60/21 WBrug-1GRM01 Flatpack 1800Rated output power 700 W 1300 W 1400 W 1800 WInput single-phase single-phase single-phase single-phase
Voltage 85–310 V 90–265 V 90–265 V 85–150 V / 185–275 V
Max. current per phase 7,5 A, sinusoidal 8 A, sinusoidal 8 A, sinusoidal 11 A, sinusoidalFrequency 45–65Hz 45–65Hz 45–65Hz 45–65 HzPower factor λ ≈ 1, EN 61000-3-2 λ ≈ 1, EN 61000-3-2 λ ≈ 1, EN 61000-3-2 λ ≈ 1, EN 61000-3-2
Output IU-characteristic, DIN 41773 IU-characteristic, DIN 41773 IU-characteristic, DIN 41773 IU-characteristic, DIN 41773
Rated voltages 48 V 24 V, 48 V 1 48 V, 60 V 1 24 V, 48 V, 60 V 4
Characteristics
Direct feeding – 2,06 V / cell 2,06 V / cell –Float charging 2,23 V / cell 2,23 V / cell 2,23 V / cell 2,23 V / cellBoost charging 2,33 V / cell 2,33 V / cell 2,33 V / cell 2,33 V / cell
Special charging – – – –Voltage, static regulation ±0,5% ±1 % ±1 % ±0,5 %Rated current 15 A at 48 V 25 A at 24 V, 48 V 24 A at 48 V, 21 A at 60 V 50 A at 27 V, 31 A at 48 V,
25 A at 60 VCurrent limitation at I rated, short-circuit-proof at I rated, short-circuit-proof at I rated, short-circuit-proof at I rated, short-circuit-proofPsophometric noise < 2 mV,
ETS 300 132-2/ITU-T< 2 mV, ETS 300 132-2/ITU-T
< 2 mV, ETS 300 132-2/ITU-T
< 0,96 mV, ETS 300 132-2/ITU-T
Efficiency 0,90 0,89 / 0,91 0,91 / 0,92 0,89 / 0,90 / 0,91Supervision
Output voltage yes yes yes yesHigh temperature yes yes yes yes
LED indicators/Display • LED for operation• LED for fault• LED bar graph for power
• LED for operation• LED for fault• 5 LED for I out
• LED for operation• LED for fault• 5 LED for I out
• LED for operation• LED for fault• LED bar graph for power
Signalling • via monitoring unit • RS 485-Interface• via monitoring unit
• RS 485-Interface• via monitoring unit
• via monitoring unit
Measuring sockets for current and voltage measurement
no yes yes no
General data
EMC (emission) EN 55022/class B EN 55022/class B EN 55022/class B EN 55022/class BIsolation voltages • prim. -> PE 1500 VAC
• prim. -> sec. 3000 VAC• sec. -> PE 1000 VDC
• prim. -> PE 2000 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
• prim. -> PE 2000 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
• prim. -> PE 2000 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
Protection class IP20, EN 60529 IP20, EN 60529 IP20, EN 60529 IP20, EN 60529Safety UL 60950-1/EN 60950-1 CSA 60950-1/UL 60950-1/
EN 60950-1CSA 60950-1/UL 60950-1/ EN 60950-1
UL 60950-1/EN 60950-1
Safety class 1, EN 60950-1 1, EN 60950-1 1, EN 60950-1 1, EN 60950-1Cooling Forced cooling (internal fans,
temperature controlled)Forced cooling (internal fan, temperature controlled)
Forced cooling (internal fan, temperature controlled)
Forced cooling (internal fans, temperature controlled)
Ambient temperature –40 °C to +70 °C –33 °C to +60 °C –33 °C to +60 °C –40 °C to +70 °CHumidity max. 95 % without
condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
Altitude up to 2000 m above sea level up to 2000 m above sea level up to 2000 m above sea level up to 2000 m above sea levelConnections HOT PLUG-IN HOT PLUG-IN HOT PLUG-IN HOT PLUG-IN
Mains DIN 46228/1...4 Power Module according to DIN EN 61076-4-101
Power Module according to DIN EN 61076-4-101
DIN 46228/1…4
Output copper socket female connector 2 mm HM type M with high current contacts according to DIN EN 61076-4-101
female connector 2 mm HM type M with high current contacts according to DIN EN 61076-4-101
copper socketSignals plug according
DIN EN 61076-4-101plug according DIN EN 61076-4-101
Control plug according DIN EN 61076-4-101
plug according DIN EN 61076-4-101
Design type 1 U 2, 42 TE 3 3 U 2, 19 TE 3 3 U 2, 19 TE 3 1 U 2, 42 TE 3
Dimensions (H x W x D) 41,5 x 214 x 243 mm 132 x 96 x 280 mm 132 x 96 x 280 mm 41,5 x 214 x 243 mmWeight 2,8 kg 2,6 kg 2,6 kg 2 ,8 kg
Rectifiers
Device Designation RM 1800 FP2 2000 FP1 2500 RM 11500 RM 18000Type E60 / 25 WBrug-
2GRM01Flatpack2 2000 Flatpack 2500 D60/160 WBrug-
1GRM01D60/250 WBrug-1GRM01
Rated output power 1800 W 2000 W 2500 W 11500 W 18000WInput single-phase single-phase single-phase three-phase three-phase
Voltage 184–265 V 85–150 V / 185–275 V 85–150 V / 174–275 V 230 / 400 V –15 % /+10 %
230 / 400 V –15 % /+10 %
Max. current per phase 11 A, sinusoidal 12,5 A, sinusoidal 16 A, sinusoidal 22,5 A 36 AFrequency 45–65 Hz 45–65 Hz 45–65 Hz 45–65 Hz 45–65 Hz
Power factor λ ≈ 1, EN 61000-3-2 λ ≈ 1, EN 61000-3-2 λ ≈ 1, EN 61000-3-2 λ ≈ 0,95 λ ≈ 0,95Output IU-characteristic, DIN
41773IU-characteristic, DIN 41773
IU-characteristic, DIN 41773
IU-characteristic, DIN 41773
IU-characteristic, DIN 41773
Rated voltages 24 V, 48 V, 60 V 1 48 V 48 V 24 V, 48 V, 60 V 1 24 V, 48 V, 60 V 1
CharacteristicsDirect feeding 2,06 V / cell – – 2,06 V / cell 2,06 V / cellFloat charging 2,23 V / cell 2,23 V / cell 2,23 V / cell 2,23 V / cell 2,23 V / cellBoost charging 2,33 V / cell 2,33 V / cell 2,33 V / cell 2,33 V / cell 2,33 V / cell
Special charging – – – 2,80 V / cell (24 / 48 V operation)
2,80 V / cell (24 / 48 V operation)
Voltage, static regulation ±1 % ± 0,5 % ±0,5 % ± 1 % ±1 %Rated current 30 A at 24 V, 48 V
25 A at 60 V41,7 A at 48 V 52 A at 48 V 160 A at 24 V, 48 V, 60 V 250 A at 24 V, 48 V, 60 V
Current limitation at I rated, short-circuit-proof
at I rated, short-circuit-proof
at I rated, short-circuit-proof
at I rated, short-circuit-proof
at I rated, short-circuit-proof
Psophometric noise < 2 mV, ETS 300 132-2/ITU-T
< 0,96 mV, ETS 300 132-2/ITU-T
< 0,96 mV, ETS 300 132-2/ITU-T
< 2 mV, ETS 300 132-2/ITU-T
< 2 mV, ETS 300 132-2/ITU-T
Efficiency 0,86 / 0,90 / 0,91 0,92 0,91 0,88 / 0,93 / 0,94 0,88 / 0,92 / 0,93Supervision
Output voltage yes yes yes yes yesHigh temperature yes yes yes yes yes
LED indicators/Display • LED for operation• LED for fault
• LED for operation• LED for fault• LED for warning
• LED for operation• LED for fault• LED bar graph
for power
• LCD for display• LED for operation• LED for fault
• LCD for display• LED for operation• LED for fault
Signalling • Signal relay for equipment fault (SV1)
• Signal relay for mains failure (SV2), (Signal-ling contacts 80 VDC, 1 A)
• via monitoring unit
• via monitoring unit • via monitoring unit • RS232-Interface• RS485-Interface• Signal relay for
equipment fault (SV1)• Signal relay for
mains failure (SV2)• via monitoring unit
• RS232-Interface• RS485-Interface• Signal relay for
equipment fault (SV1)• Signal relay for
mains failure (SV2)• via monitoring unit
Measuring sockets for current and voltage measurement
yes no no yes yes
General data
EMC (emission) EN 55022/class B EN 55022/class B EN 55022/class B EN 55022/class B EN 55022/class BIsolation voltages • prim. -> PE 2000 VAC
• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
• prim. -> PE 1500 VAC• prim. -> sec. 3000 VAC• sec. -> PE 750 VDC
• prim. -> PE 1500 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VDC
• prim. -> PE 2000 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
• prim. -> PE 2000 VAC• prim. -> sec. 3000 VAC• sec. -> PE 1000 VAC
Protection class IP20, EN 60529 IP20, EN 60529 IP20, EN 60529 IP20, EN 60529 IP20, EN 60529Safety EN 60950-1 UL 60950-1/EN 60950-1 EN 60950-1 EN 60950-1 EN 60950-1Safety class 1, EN 60950-1 1, EN 60950-1 1, EN 60950-1 1, EN 60950-1 1, EN 60950-1Cooling Forced cooling (inter-
nal fan, temperature controlled)
Forced cooling (inter-nal fans, temperature controlled)
Forced cooling (inter-nal fans, temperature controlled)
Forced cooling (inter-nal fans, temperature controlled)
Forced cooling (inter-nal fans, temperature controlled)
Ambient temperature –10 °C to +45 °C –40°C to + 75 °C –25 °C to +70 °C –10 °C to +50°C –10 °C to +50 °CHumidity max. 95 % without
condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
max. 95 % without condensationETS 300 019/class 3.2
Altitude up to 2000 m above sea level
up to 2000 m above sea level
up to 2000 m above sea level
up to 2000 m above sea level
up to 2000 m above sea level
Connections Front Access HOT PLUG-IN HOT PLUG-IN Front Access Front AccessMains Inlet connector PLUG-IN connector
for mains, output and control
DIN 46228/1...4 Terminals 6 mm²PE with M8 bolt
Terminals 6 mm²PE with M8 bolt
Output Terminals 6 mm² copper socket bolt M8 bolt M8Signals D-Sub 15 Pole plug according
DIN EN 61076-4-101D-Sub 25-Pole D-Sub 25-Pole
Control D-Sub 15 Pole plug according DIN EN 61076-4-101
D-Sub 25-Pole (Signals)RS485 D-Sub 15-PoleRS232 D-Sub 9-Pole
D-Sub 25-Pole (Signals)RS485 D-Sub 15-PoleRS232 D-Sub 9-Pole
Design type 6 U 2, 21 TE 3 1 U 2, 21 TE 3 1 U 2, 42 TE 3 6 U 2, 19“ 6 U 2, 19“Dimensions (H x W x D) 262 x 106 x 360 mm 41,5 x 109 x 327 mm 41,5 x 214 x 343 mm 266 x 448 x 441 mm 266 x 448 x 441 mmWeight 5,8 kg 1,8 kg 3,82 kg 43,5 kg 43,5 kg
1 Rectifiers adjustable to rated voltage
2 1U=44.45mm
3 1TE=5.08mm
4 3 different versions for each nominal voltage
Right to make technical changes reserved
ELTEK VALERE DEuTschLAnD Gmbh
Ferdinand-Porsche-Straße 4560386 Frankfurt am MainGermany
P.O. Box 61 06 5160348 Frankfurt am MainGermany
Phone: +49 (69) 420 02 0Telefax: +49 (69) 420 02 389
www.eltekvalere.deemail: [email protected]