RACK and RACK-MOUNT OPTIONS CONFIGURATION GUIDE
description
Transcript of RACK and RACK-MOUNT OPTIONS CONFIGURATION GUIDE
RACK and RACK-MOUNT OPTIONSCONFIGURATION GUIDE
Ver 1.6 October 2008NEC Computers
Enterprise Computing B.U.
Rack configuration Guide Rev 1.6 Pag. 3
42U RACK FRAME (FIS and NO FIS) FEATURES
Front View Rear View Top View Packaged
NEC 42U Customer Installable Rack NEC 42U Factory Integrated rack
Part Number NZA-4220-00-00 NZA-4230-00-00
EIA Capacity 42U 42U
External Height (mm) 2013 2013
External Depth (mm) 1050 1050
External Width (mm) 700 700
Inner Frame Width (mm) 450 (19") 450 (19")
Inner Frame Depth (mm) 870 870
Weight (Kg, Empty) 130 140
Maximum Load (Kg) on Casters 840 840
Maximum Load (Kg) on Feet 840 840
Total Weight (Kg) on Feet 970 980
Maximum Load x U (Kg) 20 20
Shippable Loaded No Yes - (980Kg Max total weight)
Stabilizers [AZA-4018-00-00] Optional [AZA-4018-00-00] Optional
Casters Yes - Included Yes - Included
Perforated Front Door Yes - Included Yes - Included
U numbering on four mounting rails Yes - Included Yes - Included
Perforated Rear Door Yes - Included Yes - Included
Accessory [AZA-4017-00-00] (Included) [AZA-4017-00-00] (Included)
Cable guides [AZA-4022-00-00] (Optional) Yes - Included
Side fillers [AZA-4020-00-00] (Optional) Yes - Included
Structure assembly SCREWED SCREWED/WELDED
Rack configuration Guide Rev 1.6 Pag. 4
16U RACK FRAME FEATURES
Front View Rear View Top View Packaged
NEC 16U Rack Frame
Part Number NZA-1600-00-00
EIA Capacity 16U
External Height (mm) 940
External Depth (mm) 1000
External Width (mm) 600
Inner Frame Width (mm) 450 (19")
Inner Frame Depth (mm) 868
Weight (Kg, Empty) 90
Maximum Load (Kg) on Casters 320
Maximum Load (Kg) on Feet 320
Total Weight (Kg) on Feet 410
Maximum Load x U (Kg) 20
Shippable Loaded Yes - Full (410Kg)
Accessory [AZA-4017-00-00] (Included)
U numbering on four mounting rails Yes - Included
Stabilizers Front - Included
Casters Yes - Included
Perforated Front Door Yes - Included
Perforated Rear Door Yes - Included
Rack configuration Guide Rev 1.6 Pag. 5
Front mounting holes (same for the rear side)
To install a NEC Express rack-mount system into a non-NEC rack cabinet, the following requirements must be met. Check the specification of your cabinet or measure your cabinet size before installation.
1. A standard EIA 19-inch rack cabinet
2. Perforations are provided for cooling both on the front and rear doors. (For proper ventilation, NEC Express rack cabinet is provided with perforations of 67% square holes on rear doors and 78% Honeycomb on front door.)
3. Vertical mounting rails are provided both on the front and rear sides of your cabinet to
Secure the system. The rails must have the form and hole sizes required as below. (The rails are often described as “mount angles”.)
Vertical mounting rails to secure the system
Longer than 450mm
NEC Express Rack-Mount System Assembly
Rack configuration Guide Rev 1.6 Pag. 6
Description16U
frame
42U
frameNotes
AFrom the front vertical mounting rail to the inside of the front door
>65mm >65mm
BFrom the front vertical mounting rail to rear mounting rail
710 to 870mm 710 to 870mm
CFrom the rear side of the system to the inside of the rear door
>100mm >100mm
D
Inside width
(not including rail assemblies and objects attached on the surface)
NA >480mmFront side mounting rails for 16U
Rack frame. Include the red colored rail
E
Inside width
(not including rail assemblies and objects attached on the surface)
>508mm NA
Front side mounting rails for 42U
Rack frame. Red colored rails excluded
4. Following inner size specification must be respected
E
Rack configuration Guide Rev 1.6 Pag. 7
Master PDU [ASP-4022-00-00]
#1 inlet IEC320/C19#12 outlet IEC320/C13
Can be installed HorizontallyIn 16U frame
Can be installed Horizontally and/or VerticallyIn 42U and 42UFIS frames
Number of U used
Can be used in 42U Frame
Can be used in 42U FIS Frame
Can be used in 16U Frame
Picture
Comment:
If Warning message read it carefully
Short description
Reference [ASP-4022-00-00] in blue available codes[ASP-4022-00-00] in red EOL codes[XXX-XXXX-XX-XX] Not yet introduced product under evaluation
1 Y Y Y
H H V
How to read the block diagram in this document
Connection line means: it can be connected, used with
the other component
Notes
Rack configuration Guide Rev 1.6 Pag. 8
19-inch Rack 16U and 42U
Frames Options Frames Options
Front side fillers [AZA-4002-00-00] 1U *[AZA-4003-00-00] 2U *[AZA-4004-00-00] 3U *[AZA-4005-00-00] 6U *
To optimize the RACK cooling unused space in front Rack side must be filled with these front side fillers- Each code contains #2 fillers and requested screws/Captive nuts.
Front side stabilizer [AZA-4018-00-00]
Stabilizer is used to make rack frame structure more stable it must be fixed on the front side of rack frame .
lateral front side filler with brush[AZA-4019-00-00]
To optimize rack cooling and to allow front side equipment cabling. AZA-4019-00-00 contains 1 lateral front side filler with brush
Lateral front side filler [AZA-4020-00-00]
To optimize rack cooling lateral rack filler. AZA-4020-00-00 contains 4 rigid lateral front side filler42U FIS delivered with AZA-4020-00-00 installed
Vertical Cable guide [AZA-4022-00-00]
Cable guide vertically installable on the back side of 42U rack frames.AZA-4022-00-00 contains 1 Vertical Cable guide 42U FIS delivered with #2 AZA-4022-00-00 installed
* Y Y Y
H H
- Y Y Y
- N Y Y
- V
- N Y Y
- V
- N Y Y
- V
Rack configuration Guide Rev 1.6 Pag. 9
Frame options installation details and usage
[AZA-4019-00-00]Or
[AZA-4020-00-00]
[AZA-4018-00-00]
[AZA-4022-00-00]
[AZA-4002-00-00] 1U[AZA-4003-00-00] 2U[AZA-4004-00-00] 3U[AZA-4005-00-00] 6U
[AZA-4019-00-00] typical usageLAN switch cables connection Keeping optimum rack cooling
Indication of U numbering Are stick on the four mounting rails
Rack configuration Guide Rev 1.6 Pag. 10
Rack baying kit[AZA-4021-00-00]
42U rack frames baying kit. After removing rack’s lateral side covers, two or more frames can be solidly joined.
1U Universal rail kit[AZA-1100-00-00]
Universal fixing rails kit. It can be used to install equipment that are not specifically provided with rack installation rails. Devices installed on xx must be within these maximum specificationWidth: between 410mm and 450 mmDepth: between 650mm and 900 mmWeight: < 80Kg
M5 Screws, washer s and captive nuts kit [AZA-4017-00-00]
Kit containing Qty 20 of each:M5x16 screws, captive nuts and washer s
- Y Y Y
-
- N Y Y
-
1 Y Y Y
H H
Rack configuration Guide Rev 1.6 Pag. 11
Display/Keyboard/Mouse Container Display/Keyboard/Mouse Container
LCD/Keyboard/Mouse Container [NZA-4060-00-00]
Container to store a LCD/ keyboard/mouse in a rack cabinet.
Integrated LCD/Keyboard/Touch Pad tray[AZA-4050-UU-00] US keyboard[AZA-4050-FF-00] FR keyboard[AZA-4070-02-00] FR keyboard[AZA-4070-23-00] US keyboard
Integrated LCD, keyboard touch pad in a 1U rack cabinet.It can be connected to any of following KVM AEX-0800-00-00 / AEX-1610-00-00 / AEX-1630-00-00 / AEX-1625-00-00
Keyboard/Mouse Container [AZA-4009-00-00]
Container to store keyboard and mouse in a rack cabinet.
Generic Support (2U)[AZA-4024-00-00] Replace [AZA-4006-00-00]It can support any device within these max specifications:Width:<=450mmDepth: <=400mmWeight: <=18Kg
2 Y Y Y
H H
1 Y Y Y
H H
2 Y Y Y
H H
2 Y Y Y
H H
Mini Keyboard + Mouse PS2 MW[AIP-0020-FF-00] French keyboard [AIP-0020-UU-00] US keyboard[AIP-0020-BB-00] British keyboard
Mini keyboard 104 keys + mouse
- Y Y Y
- -
Integrated LCD/Keyboard/Touch Pad + 16 ports KVM tray[CDV-LCDX-02-00] FR keyboard[CDV-LCDX-23-00] US keyboard
Integrated LCD, keyboard touch pad in a 1U rack cabinet.Integrating a KVM 16 ports It can be chained to any of following KVM AEX-0800-00-00 / AEX-1610-00-00 and CDV-KVMX-IP-00 to enable Over IP
1 Y Y Y
H H
16P KVM
Rack configuration Guide Rev 1.6 Pag. 12
KVM (Keyboard Video Mouse) SwitchesKVM (Keyboard Video Mouse) Switches
Server Switch Unit (8 servers/1User) [AEX-0800-00-00]
The Server Switch Unit [AEX-0800-00-00] allows up to 8 servers to be controlled by one set of a display, keyboard and mouse. By connecting 9 Server Switch Units in a tree structure, up to 64 servers can be controlled. It can be cascading with AEX-1610-00-00 and/or AEX-0800-00-00
PS2 type interface to CAT5 adapter[ACN-0810-00-00]VGA and PS2 adapter shipped with 1.5m and 3m CAT5 green cable
Server Switch Unit (16 servers/1User) [AEX-1610-00-00]
The Server Switch Unit [AEX-1610-00-00] allows up to 16 servers to be controlled by one set of a display, keyboard and mouse. By connecting 17 Server Switch Units in a tree structure, up to 256 servers can be controlled. It can be cascading with AEX-1610-00-00 and/or AEX-0800-00-00
USB type interface to CAT5 adapter[ACN-0811-00-00]
VGA and USB adapter shipped with 1.5m and 3m CAT5 green cable
Server Switch Unit Over IP (16 servers/1user local or Connection over IP) [AEX-1630-00-00]
The Server Switch Unit [AEX-1630-00-00] allows up to 16 servers to be controlled by one set of a display, keyboard and mouse. By connecting nine Server Switch Units in a tree structure, up to 256 servers can be controlled. It can be cascading with with AEX-1610-00-00 and/or AEX-0800-00-00
1 Y Y Y
H H V
1 Y Y Y
H H V
1 Y Y Y
H H
- Y Y Y
- - -
- Y Y Y
- - -
KVM over Ip enabler [CDV-KVMX-IP-00]
The Over Ip enabler Unit is chained to the local KVM AEX-1610-00-00 and/or AEX-0800-00-00 in order to add, in addition to a local video/keyboard/mouse, Over IP functionality
1 Y Y Y
H H V
Rack configuration Guide Rev 1.6 Pag. 13
Direct connection 1 to 8 [AEX-0800-00-00] or 16[AEX-1610-00-00] servers
Server Switch Unit Server
Configuration 1
RICCACN-0810-00-00
orACN-0811-00-00
Kvm cat5 green cable 1.5m and 3m cable
AEX-0800-00-00or
AEX-1610-00-00
Over IP connection 1 to 16 servers using AEX-1630-00-00
Server Switch Unit Server
Configuration 2
RICCACN-0810-00-00
orACN-0811-00-00
Kvm cat5 green cable 1.5m and 3m cable
AEX-1630-00-00
LAN
Server Switch Unit Server
Configuration 3
RICCACN-0810-00-00
orACN-0811-00-00
Kvm cat5 green cable 1.5m and 3m cable
AEX-1610-00-00 or AEX-0800-00-00
LAN
Over IP connection extension using xxx-xxxx-xx-xx
CDV-KVMX-IP-00
Rack configuration Guide Rev 1.6 Pag. 14
Connecting 1 to 256 servers locally or remotely managed, cascading server Switch Units
Server Switch Unit (Master) Server Switch Unit
(Slave)
Server
Server
Configuration 4
Up to eightor
sixteen servers
installable
LAN
ACN-0810-00-00or
ACN-0811-00-00
ACN-0810-00-00
Server
Up to eightor
sixteen servers
installable
AEX-0800-00-00or
AEX-1610-00-00Or
AEX-1630-00-00
AEX-0800-00-00or
AEX-1610-00-00
Over Ip connection only if master KVM is AEX-1630-00-00
Rack configuration Guide Rev 1.6 Pag. 15
Connecting up to 256 servers locally or remotely managed, cascading server Switch Units
Server Switch Unit (Master) Server Switch Unit
(Slave)
Server
Server
Configuration 5
Up to eightor
sixteen servers
installable
LAN
ACN-0810-00-00or
ACN-0811-00-00
ACN-0810-00-00
Server
Up to eightor
sixteen servers
installable
AEX-0800-00-00or
AEX-1610-00-00
AEX-0800-00-00or
AEX-1610-00-00
CDV-KVMX-IP-00
Rack configuration Guide Rev 1.6 Pag. 16
PS2 type interface to CAT5 adapter[ACN-0820-00-00]
VGA and PS2 adapter shipped with 3m CAT5 green cable
Server Switch Unit (16 servers/2User) [AEX-1625-00-00]
The Server Switch Unit [AEX-1625-00-00] allows the control of 16 servers with two set of a display, keyboard and mouse. By connecting 17 Server Switch Units in a tree structure, up to 256 servers can be controlled.
USB type interface to CAT5 adapter[ACN-0821-00-00]
VGA and USB adapter shipped with 3m CAT5 green cable
Direct connection 1 to 16 servers up to 2 users
Server Switch Unit
Server
Configuration 1
AVRIQACN-0820-00-00
orACN-0821-00-00
Kvm cat5 green cable 1.5m and 3m cable
AEX-1625-00-00
Up to sixteen servers
installableUser A
User B
1 Y Y Y
H H
- Y Y Y
- - -
- Y Y Y
- - -
Rack configuration Guide Rev 1.6 Pag. 17
Server Switch Unit (Slave)
Server
Server
Configuration 3
Up to sixteen servers
installable
AVRIQACN-0820-00-00
orACN-0821-00-00
Server
Up to sixteen servers
installable
Server Switch Unit (Master)
AEX-1625-00-00User A
User B
1) ACN-0820-00-00 and ACN-0821-00-00 can only be used with AEX-1625-00-00do not use them with ACN-0800-00-00 or ACN-1610-00-00 or ACN-1630-00-00
2) AEX-1625-00-00 can only be chained with same model AEX-1625-00-00. Do not chain it with ACN-0800-00-00 or ACN-1610-00-00 or ACN-1630-00-00
3) Only one level of chaining are supported for all base KVM ACN-0800-00-00 ACN-1610-00-00 ACN-1630-00-00 and AEX-1625-00-00
4) In order to avoid mixing LAN and KVM cables, use specific green cable for KVM connection and grey cables for LAN. Mixing LAN and KVM connection can put out of order your equipment !
Important KVM rules
CableACN-0114-00-00
Connecting 1 to 256 servers locally or remotely managed, cascading server Switch Units
Rack configuration Guide Rev 1.6 Pag. 18
UPS (Uninterruptible Power Supply) UPS (Uninterruptible Power Supply)
APC SUA1500RMI2U [ABA-1520-00-00]
1500 VA / 980 Watts #1 inlet IEC320/C14#4 outlets IEC320/C13#1 Smart SlotSerial/USB Management
APC SUA3000RMI2U[ABA-3020-00-00]
3000 VA / 2700 Watts #1 inlet IEC320/C20 #8 outlets IEC320/C13#1 outlet IEC320/C19#1 Smart SlotSerial/USB Management
APC SURTD5000RMXLI[ABA-5010-00-00]
#1 terminal input block #8 outlets IEC320/C13#2 outlet IEC320/C19#2 Smart SlotSerial Management
UPS Cable latch [ASP-0007-00-00]
#1 inlet IEC60309#1 outlet cable
UPS cable latch[ASP-0005-00-00]
#1 inlet IEC60309#1 outlet cable
[ASP-0006-00-00]
#1 inlet IEC320/C19#1 outlet IEC60309
2 Y Y Y
H H
2 Y Y Y
H H
3 Y Y Y
H H
- Y Y Y
- -
- Y Y Y
- -
- Y Y Y
- -
Rack configuration Guide Rev 1.6 Pag. 19
UPS 8 port expander[AEX-2008-00-00]
8-Port Share-UPS Interface Expander
1 Y Y Y
H H
- Y Y Y
- -
UPS network card[AEX-2031-00-00]
Smart UPS network management card
- Y Y Y
- -
UPS serial card[AEX-2200-00-00]
Smart UPS #2 additional serial ports interface
Epress5800 Server
UPS Configurations 1
UPS
[ABA-1520-00-00][ABA-3020-00-00][ABA-5010-00-00]
Connecting 1 server to UPS with serial connection
Power cable
serial cable
Epress5800 Servers
UPS
[ABA-1520-00-00][ABA-3020-00-00][ABA-5010-00-00]
+[ABA-5010-00-00]
Power cable
serial cableEpress5800 Server
[ACN-2000-00-00]
[ACN-2000-00-00]
Rack configuration Guide Rev 1.6 Pag. 20
ABA-1520-00-00 ABA-3020-00-00 ABA-5010-00-00
Watt VA hours:minuts:sec hours:minuts:sec hours:minuts:sec
50 70 5:21:00 5:00:00 6:56:00100 140 3:05:00 3:06:00 4:35:00200 280 1:31:00 1:46:00 2:40:00300 420 0:55:00 1:10:00 1:51:00400 560 0:37:00 0:52:00 1:23:00500 700 0:26:00 0:40:00 1:06:00600 840 0:19:00 0:33:00 0:55:00700 980 0:14:00 0:27:00 0:47:00800 1120 0:11:00 0:23:00 0:40:00900 1260 0:09:00 0:20:00 0:35:001000 1400 - 0:17:00 0:31:001200 1680 - 0:13:00 0:25:001400 1960 - 0:11:00 0:21:001600 2240 - 0:09:00 0:17:001800 2520 - 0:07:00 0:15:002000 2800 - 0:06:00 0:13:002500 3500 - 0:04:00 0:09:003000 4200 - - 0:07:003400 4760 - - 0:05:00
Estimated autonomie in hours:minutes
UPS Configurations 2
UPS
[ABA-1520-00-00][ABA-3020-00-00][ABA-5010-00-00]
Power cable
serial cable
Server
Up to eightservers
installable
serial cable
AEX-2008-00-00
Following table show the estimated autonomy of devices connected to a UPS.
- Define max load connected to UPS in Watt or VA and find the autonomy in Hours:Minutes
8-Port Share-UPS serial serial Interface Expander
Rack configuration Guide Rev 1.6 Pag. 21
PDU (Power Distribution Units) PDU (Power Distribution Units)
Master PDU [ASP-0020-00-00]
#1 inlet IEC60309 (32A no protection)#8 outlet IEC320/C13(x4 10A circuit breaker)#2 outlet IEC320/C19(x2 16A circuit breaker)
Slave PDU [ASP-0022-00-00]
#1 inlet IEC320/C19 (16A no protection)#12 outlet IEC320/C13(x2 10A circuit breaker)#1outlet IEC320/C20(no protection)
Slave PDU [ASP-0021-00-00]
#1 inlet IEC320/C14 (10A fuse protection)#8 outlet IEC320/C13(no protection)
1 Y Y Y
H H V
1 Y Y Y
H H
1 Y Y Y
H H V
IEC320 Power cord[ACN-2001-00-00]
3 m power cord with one C13 and one C14 plug
1 Y Y Y
H H V
Rack configuration Guide Rev 1.6 Pag. 22
PDU (Power Distribution Units) PDU (Power Distribution Units)
Master PDU [ENS-12C1-32-01]
#1 inlet IEC60309 (32A no protection)#12 outlet IEC320/C13(x4 10A circuit breaker)
- No output cables included !!!
1 Y Y Y
H H V
Master PDU [ENS-2C13-32-01]
#1 inlet IEC60309 (32A no protection)#2 outlet IEC320/C13(x2 10A circuit breaker)#4 outlet IEC320/C19(x4 16A circuit breaker)
- No output cables included !!!
1 Y Y Y
H H V
Master PDU [ENS-8C13-32-01]
#1 inlet IEC60309 (32A no protection)#8 outlet IEC320/C13(x4 10A circuit breaker)#2 outlet IEC320/C19(x2 16A circuit breaker)
- No output cables included !!!
1 Y Y Y
H H V
Master PDU [ENS-6C19-32-01]
#1 inlet IEC60309 (3x32A no protection)#6 outlet IEC320/C19(x6 16A circuit breaker)
- No output cables included !!!
1 Y Y Y
H H V
IEC320 Power cord[ACN-2001-00-00]
3 m power cord with C13/C14 plugs
0 Y Y Y
H H V
IEC320 Power cord[ACN-2002-00-00]
2 m power cord with one C19 and one C20 plug
0 Y Y Y
H H V
3 Phases input needed !
Rack configuration Guide Rev 1.6 Pag. 23
PDU (Power Distribution Units) PDU (Power Distribution Units)
Slave PDU [ENS-12C1-16-01]
#1 inlet IEC320/C19 (16A no protection)#12 outlet IEC320/C13(x4 10A circuit breaker)
- Include one input cable ACN-2002-00-00- No output cables included !!!
Slave PDU [ENS-6C13-16-01]
#1 inlet IEC320/C14 (10A no protection)#4 outlet IEC320/C13(x2 10A circuit breaker)
- Include one input cable ACN-2001-00-00- No output cables included !!!
1 Y Y Y
H H
1 Y Y Y
H H V
IEC320 Power cord[ACN-2001-00-00]
3 m power cord with one C13 and one C14 plug
0 Y Y Y
H H V
Rack configuration Guide Rev 1.6 Pag. 24
PDUs blocks diagram
10A CB
10A CB
EN
S-6C
13-16-01
10A CB
10A CB
10A CB
10A CB
EN
S-12C
1-16-01
10A CB
10A CB
10A CB
10A CB
16A CB16A CB16A CB16A CB
10A CB
10A CB
16A CB16A CB16A CB16A CB16A CB16A CB
10A CB
10A CB
10A CB
10A CB
10A CB
10A CB
10A CB
10A CB
16A CB16A CB
EN
S-12C
1-32-01
EN
S-2C
13-32-01
EN
S-8C
13-32-01
EN
S-6C
19-32-01
Slave PDUs
Master PDUs
Rack configuration Guide Rev 1.6 Pag. 25
INL
ET
TY
PE
PO
WE
R IN
LE
T
SID
E
SERVEUR Max WATT Max Curr. Max BTU NR R IEC L/R W W/O
110Eh 300 1,36 1024 1 C14 R NA 800110Ej 380 1,73 1297 1 C14 R NA110Ek 380 1,73 1297 1 C14110Rf-1 350 1,59 1195 1 C14 R NA120Mf 700 3,18 2389 2 2 C14 R 1350 NA120Rd-1 IDE 350 1,59 1195 1 C14 L 1250 NA120Rd-1 SCSI 350 1,59 1195 1 C14 L 1250 NA120Re-1 120Rf-1 SATA 500 2,27 1707 1 C14 L 1250120Re-1 120Rf-1 SCSI 525 2,39 1792 1 2 C14 L 1250120Rg-1 SATA 650 2,95 2218 1 C14 L120Rg-1 SAS 650 2,95 2218 1 2 C14 L120Rh-1 SAS/SATA Fixed PSU 650 2,95 2218 1 C14 L120Rh-1 SAS/SATA HS PSU 750 3,41 2560 1 2 C14 L120Rf-2 500 2,27 1707 1 2 C14 L 1200120Rg-2 120Rh-2 600 2,73 2048 1 2 C14 L 1200120Ri-2 SAS 750 3,41 2560 1 2 C14 L120Rj-2 SAS/SATA 750 3,41 2560 1 2 C14 L120Ef-Lg Fixed PSU 450 2,05 1536 1 C14 R 1350 NA120Ef-Lg Hot Swap 450 2,05 1536 1 2 C14 R 1350 NA120Eg FIXED PSU 600 2,73 2048 1 C14 R 1350 NA120Eg HS PSU 500 2,27 1707 1 2 C14 R 1350 NA120Eh-2 550 2,50 1877 1 1 C14 R120Eh-2 HS 650 2,95 2218 1 2 C14 R120Lh 500 2,27 1707 1 2 C14 R 1350 NA120Li 700 3,18 2389 1 2 C14 R 1350 NA320Lb-R 1200 5,45 4096 2 C14 L NA320Lc-R 1200 5,45 4096 2 C14 L NA320Fa 1400 6,36 4778 2 C14 R NA320Fb 1400 6,36 4778 2 C14 R NA320Fc 1500 6,82 5120 2 C14 L NA140Hc 1200 5,45 4096 2 3 C14 R/M/L 1400 NA140Hd 1200 5,45 4096 2 3 C14 R/M/L 1400 NA2U MDEU 200 0,91 683 1 C14 R NA
INL
ET
Nb
CA
BL
E-A
RM
CA
BL
E
LE
NG
TH
Devices power specifications 1-3
Max WATT = Maximum power consumption for full configuration in wattMax Curr. = Maximum current required Max BTU = Maximum BTU dissipated by equipment at maximum power consumptionInlet Nb NR = Number of inlet plugs for non redundant configurationInlet Nb R = Number of inlet plugs for non redundant configurationInlet type = inlet plug typePower supply side = Looking from the back of the device where the PSU are placed Right Left CenterCable-Arm / Cable Length = minimum cable length W or W/O cable arm to connect the device
Rack configuration Guide Rev 1.6 Pag. 26
INL
ET
TY
PE
PO
WE
R IN
LE
T
SID
E
SERVEUR Max WATT Max Curr. Max BTU NR R IEC L/R W W/O
2U MDEU HS 330 1,50 1126 0 2 C14 L NAS1300 BAS 480 2,18 1638 0 2 C14 L/M NA 500S1300 DEU 480 2,18 1638 0 2 C14 L/M NA 500S1400 BAS 510 2,32 1741 0 2 C14 L/M NA 500S1400 DEU 480 2,18 1638 0 2 C14 L/M NA 5003U DEU ST1430 450 2,05 1536 1 2 C14 L/M 1350 NAST1430 U320 450 2,05 1536 0 2 C14 L/M 1350 NAST1220 400 1,82 1365 1 2 C14 R/L NADx-10 500 2,27 1707 0 2 C14 R/M NAS1500 BAS 510 2,32 1741 0 2 C14 L/M NA 500S1500 DEU 480 2,18 1638 0 2 C14 L/M NA 500S2300 BAS 260 1,18 887 0 2 C14 L/M NA 500S2300 DEU 480 2,18 1638 0 2 C14 L/M NA 500AIT3 1U 55 0,25 188 1 C14 R NAAIT3 2U 100 0,45 341 1 C14 R NALIBRARY NEC 0,00 0140He 2100 9,55 7167 3 4 C14 R NA140Hf 2100 9,55 7167 3 4 C14 R NA140Rc-4 860 3,91 2935 2 2 C14 R NA140Rd-4 1400 6,36 4778 2 4 C14 R NA140Re-4 1400 6,36 4778 2 4 C14 R NA140Rf-4 1400 6,36 4778 2 C14 R/L NAT220Ra-1 411 1,87 1403 1 RTM600 300 1,36 1024 1 C14 R NA 800TM710 400 1,82 1365 1 C14 R NATM800 400 1,82 1365 1 C14 R NATM1400 450 2,05 1536 1 C14 R NATW100 TS100 400 1,82 1365 1 C14 R NASYNERWAY SD1000 1300 5,91 4437 2 3 C14 R NASYNERWAY SD2000 1300 5,91 4437 0 3 C14 R NAS/WA2500 DPS 600 2,73 2048 1 C14 R NAS/WA2500 FSP 550 2,50 1877 1 C14 R NAS/WA2500 HS 600 2,73 2048 2 3 C14 R NASA2500R-1 500 2,27 1707 1 C14 R NASA2510R-1 450 2,05 1536 1 C14 R NASI1110-R1 350 1,59 1195 1 C14 RSI1120-R1 350 1,59 1195 1 C14 RSI1720 550 2,50 1877 1 1 C14 RSI1720 HS 650 2,95 2218 1 2 C14 R180Rc-4 1050 4,77 3584 2 C14 R NA180Rc-4 LOCKOUT 370 1,68 1263 2 C14 R NA
INL
ET
Nb
CA
BL
E-A
RM
CA
BL
E
LE
NG
TH
Devices power specifications 2-3
Rack configuration Guide Rev 1.6 Pag. 27
INL
ET
TY
PE
PO
WE
R IN
LE
T
SID
E
SERVEUR Max WATT Max Curr. Max BTU NR R IEC L/R W W/O
xI1310 0,00 0WA1310 400 1,82 1365 RWI1510 550 2,50 1877xA2510 670 3,05 2287 C14 RxA2510 HS 0,00 0 C14 R420Ma 1-2 CPU 620 2,82 2116 1 2 C14 R NA420Ma 3-4 CPU 1240 5,64 4232 2 3 C14 R NA420Ma 5-6 CPU 1860 8,45 6348 3 4 C14 R NA420Ma2 1-2 CPU 740 3,36 2526 1 2 C14 R NA420Ma2 3-4 CPU 1480 6,73 5051 2 3 C14 R NA420Ma2 5-6 CPU 2220 10,09 7577 3 4 C14 R NA120Ba-4 1-2 CPU 1028 4,67 3509 1 2 C14 R NA120Ba-4 3-4 CPU 2056 9,35 7017 2 3 C14 R NA120Ba-4 5-6 CPU 3084 14,02 10526 3 4 C14 R NABROCADE 3200 8 ports 75 0,34 256 1 C143Com SWITCH 24 ports 0,00 0UPS 3KVA 2700 12,27 9215 C20UPS 5KVA 3500 15,91 11946 HWLXN2000 LTO3 5U 240 1,09 819KVM SWITCH AV2000 40 0,18 137 1 C14KVM SWITCH AV2015 40 0,18 137 1 C141U LCD TRAY 25 0,11 85 1 C14LCD 17" 38 0,17 130 1 C6KVM SWITCH 8 ports 15 0,07 51 1 C14KVM SWITCH 16 ports 15 0,07 51 1 C14KVM SWITCH 16 ports IP 45 0,20 154 1 C14
INL
ET
Nb
CA
BL
E-A
RM
CA
BL
E
LE
NG
TH
Devices power specifications 3-3
Rack configuration Guide Rev 1.6 Pag. 28
A
A
B
B
C
C
42 U frames
16 U frame
42U 16U1st Install the heaviest devices on rack lower positions A
1U<=A<=20U 1U<=A<=6U
2nd If a LCD/keyboard/mouse tray need to be installed put it positions B
20U<=B<22U 15U<=B<=16U
3rd Install the lightest devices on rack higher positions C
25U<=C<=42U 11U<=C<=14U
4rd Install remaining devices in positions D
23U<=D<=34U 7U<=D<=10U
D
D
RACK installation rules
Use last available release of InRack Wizard software for RACK configuration
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 29
42U RACK installation rules
NEC
Exp5800 server
D >=125cm
D is the minimum rack clearance between two 42U frames to allow easy maintenance
front
front
Minimum clearance around a 42U frames
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 30
16U RACK installation rules
NEC
Exp5800 server
D >=125cm
D is the minimum rack clearance between two 16U frames to allow easy maintenance
front
front
Minimum clearance around a 16U frames
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 31
PDU
PDU
Master
PDU
Power source
Express5800 Server
PSU
Express5800 Server
PSU
Express5800 Server
PSU
Fig. 1
PDU
PDU
Power source
Master
PDU
Express5800 Server
PSU
PSU
Express5800 Server
PSU
PSU
Express5800 Server
PSU
PSU
Fig. 2
Power source
PDU
PDU
UPS
Express5800 Server
PSU
PSU
Express5800 Server
PSU
PSU
Express5800 Server
PSU
PSU
Fig. 3
PDU
PDU
UPS
PDU
PDU
PSU PSU
Epress5800Server
PSU PSU
Epress5800Server
PSU PSU
Epress5800Server
Power source
Fig. 4
PDU
PDU
PDU
PDU
PSU PSU
Epress5800Server
PSU PSU
Epress5800Server
PSU PSU
Epress5800Server
Power source (UPS)Power source (MPDU)
Fig. 5
RACK power redundancy distribution configurations
UPS
or
Master PDU
UPS
or
Master PDU
Power source (UPS)Power source (MPDU)
In following power distribution diagrams, five different ways to configure interconnection of Master PDU, Slave PDU, UPS and servers power redundancy.
In red components that represent a single point of failure (SPOF). Failure on red components will induce a power failure on all components cascaded. Configuration 5 is the one completely redundant, configuration 1 has no redundancy.
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 32
L1 Imax 11A
L6 Imax 15A
L5 Imax 12A
PDU connection rules
C14
C14
C14
C14
C14
C14
C14
C14
C20
C20
60309
C19
C13
C13
C19
ASP-0020-00-00
31A
C13
C13
C13
C13
C13
C19
C19
L2 Imax 6A
L3 Imax 7A
L4 Imax 9A
Do not exceed MAX current allowed for the single defined plug.Imax current for IEC320-C13/C14 is 10AL1 Imax > 10A
Do not exceed maximum current allowed for group of plugs.ASP-0020-00-00 has 4 groups of two C14 plugs protected by a 10A circuit breaker L2 Imax + L3 Imax > 10A
Do not exceed MAX PDU input current.ASP-0020-00-00 has one IEC60309 input plug with maximum current of 32A. Protection by over current must be guarantee by the upfront device where this PDU is connected. L4 Imax + L5 Imax + L6 Imax > 32A
C13
Connector Type
Connector Name Appliance
Inlet
Max Current
IEC320-C13 IEC320-C14 10Amp
IEC320-C19 IEC320-C20 16Amps
IEC60309 IEC60309 32Amps
(single phase)
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 33
PDU selection and sizing rules
Example of interconnection of one Master PDU ASP-0020-00-00 and two slaves ASP-0022-00-00 with different load devices
C14
C14
C14
C14
C14
C14
C14
C14
C20
C20
C14
C14
C14
C14
C14
C14
C14
C14
C19
Imax 4AC13
C13
C13
C13
1st - List all your devices you want to install inside the rack frame- using the “devices power specifications” pag. 16-17 define the maximum current and plug type for each device
2nd - Using PDU specification identify the maximum current per groups of outputs
example: ASP-0022-00-00 has two groups of six C13 plugs. Each group is protected by 10A circuit breakers.
3rd - Adding all PDU output currents you should not exceed max input current allowed by PDU
example: ASP-0020-00-00 has an IEC60309 input plug limited to 32A
4rd - Select your power distribution model between the ones listed on page 21
C14
C14
C14
C14
C20
C19
Imax 1A
Imax 6AC13
C13
C19
C14
C14
C14
C14
C14
C14
C14
C14
C14
C14
C14
C14
C20C19
C13
C13
Imax 2x6AASP-0022-00-00
ASP-0022-00-00
ASP-0020-00-00
d
evic
es I
Max
<=
10
A
Imax 3A
Imax 1AC13
C13C13
C13
C13
C13
d
evic
es I
Max
<=
16
A
d
evic
es I
Max
<=
10
A
d
evic
es I
Max
x
gro
up
<=
10
A
dev
ices
I M
ax
x g
rou
p <
= 1
6A
d
evic
es I
Max
<=
32
A
15A
10A
Imax 4A
C13
C13
31A
d
evic
es I
Max
<=
10
A
dev
ices
I M
ax <
=
10A
d
evic
es I
Max
<=
16
A
60309
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 34
Rack cooling
front
rear
Rack
fram
e
Rack cooling air flow
Air cooling flow is always going from the front to the back of the rack frame
With out the front side panels and laterals Covers exhausted warm
air will be xxx from the front side
Front and lateral cover usage
Example of Rack assemblyUsing front and lateral covers
Pictures showing temperatures inside the rack with and with out the side/front panels
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 35
Rack cooling
Rack organization in a datacenter with raised floor and suspended ceiling with air-conditioner
Air Conditioner
Building floor
Raised floor
Grilles Grilles
Suspended ceiling
GrillesGrilles
Building ceiling
Grilles
Fro
nt
Fro
nt
Fro
nt
Fro
nt
Rear
Rear Rear
Rear
Ra
ck
Ra
ck
Ra
ck
Ra
ck
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 36
Rack cooling
CFMThe abbreviation for cubic feet per minute. CFM is used to measure the flow of air through a delivery system or space.BTUThe abbreviation for British Thermal Unit. A measurement of heat energy commonly used to measure heat loads in data centers and IT rooms in North America. A BTU is defined as the amount of heat energy required to raise the temperature of one pound of water by one degree Fahrenheit in one hour. This unit should be replaced by WattWattA measurement of energy commonly used to measure electrical and heat loads in data centers and IT rooms. The wattage consumed by the IT equipment, lights, etc. is the amount of heat energy to be removed from the room by the air conditioning system. This term is becoming more common when specifying cooling systems.Relative HumidityThe amount of water vapor contained in air relative to the maximum amount the air is capable of holding. Expressed in %.Ton (Cooling)A measurement of heat energy commonly used historically to measure heat loads in data centers and IT rooms in North America. A ton is equal to 12,000 BTUs and is the amount of heat energy required to melt 2000 pounds (907kg) of ice in one day (24 hours). This is an archaic term typically used to specify heat output when expressed in Tons / day, where the use of the more modern term Watts is the simpler and more universal measure that should be used.
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 37
English to Metric Conversion table
Type of Unit From English Units
To Metric Units Multiply By
Cooling Ton (refrigeration) Kilowatts 3.517
BTU/Second Kilowatts 1.054
BTU/Hour Kilowatts 0.000293
Length Foot Meter 0.3048
Room Area Square Foot Square Meter 0.09290
Mass Pound Kilogram 0.4536
Floor Loading Pounds / Square Foot
Kilograms / Square Meter
4.882
Volume Cubic Feet Cubic Meter 0.02832
Gallon Liter 3.785
Pipe Flow Rate Gallons / Minute Liters / Second 0.06364
Air Flow Rate Cubic Feet / Minute Cubic Meters / Second
0.000471
Air Flow Velocity
Feet / Second Meters / Second 0.3048
Temperature Degree Fahrenheit Degree 0.5555x(Fahrenheit-32)
Very useful free ware program to convert any units can be downloaded at this linkhttp://joshmadison.com/article/convert-for-windows/
Some of the most commonly used unit
Tec Notes
Rack configuration Guide Rev 1.6 Pag. 38
Revision Date Comment
Rev 1.1 March 2008 - First document release
Rev 1.2 May 2008 - Document change history added
-Fix pag 10 codes AZA-4070-02-00 and AZA-4070-23-00 comments swapped
-Fix pag 10 code AZA-4060-00-00 to NZA-4060-00-00
Rev 1.3 May 2008 -Fix pag 16 code ABA-5010-00-00 is 3U not 5U
Rev 1.4 June 2008 -Fix pag 2 42U rack frames specifications
-Add pag 10 AZA-4006-00-00 replaced by AZA-4024-00-00
-Fix pag 16 UPS information updated
Rev 1.5 September 2008 - added new PDU, 1U LCD/Keyboard + KVM, over ip
- added more slides on cooling
Rev 1.6 October 2008 -Fixed wrong references on pages 13 and 14
Document change history