These instructions must be read fully before commencing installation.
QUIETFLOW SQS Installation & Maintenance
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com2
Installation InstructionsQUIETFLOW SQS
1.0 General1.1 It is important these Installation and Maintenance Instructions are fully adhered to.1.2 Full details of the unit supplied are shown on the product nameplate. If in doubt about any detail contact Elta Fans Ltd or its agents for clarification.1.3 All electrical installation must be carried out by suitably qualified and competent personnel in accordance with all current statutory requirements.1.4 These instructions cover only the Elta Fans Ltd product and do not include the supply or installation of any safety equipment that may be required e.g. adequate guarding or protection from rotating parts and proper electrical isolation.1.5 Any declarations made by Elta Fans Ltd about product installation and safety, are dependant on the fan equipment being used within installations which themselves meet the requirements of the relevant Standards and Directives of your region.1.6 The fan is designed for use in an ambient temperature of -20°C up to a maximum of +60°C and up to 95% relative humidity. The fan is not suitable for corrosive or explosive atmospheres.1.7 The installer should provide easy access to the fan to facilitate future maintenance.1.8 The installer should ensure the fan is adequately supported.1.9 This product is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the product by a person responsible for their safety. Children should be supervised to ensure that they do not play with the product.1.10 At end-of-life, the unit must be disposed of in an environmentally friendly manner by suitably qualified and competent personnel ina ccordance with the requirements of applicable Standards and Directives.
2.0 Installation
WARNING – The fan must be isolated from the power supply during installation and maintenance. The fan must be earthed in accordance with the local regulations.
2.1 Upon receipt, the fan equipment should be visually inspected to check for any damage. Ensure that the impeller is free to rotate.2.2 If there are any queries concerning the fan equipment, Elta Fans Ltd should be contacted prior to the installation.2.3 The fan must be securely mounted in the desired position to suit the application. The fan can be mounted at any angle.2.4 Check the details on the motor rating plate to ensure that the correct power supply (voltage, frequency and phase) is available. An incorrect power supply will lead to permanent damage to the fan motor.2.5 Refer to the appropriate wiring diagram. Ensure that all earth connections are made.2.6 Means for electrical disconnection must be incorporated in the wiring installation in accordance with the relevant wiring and electrical regulations.2.7 Precaution must be taken to locate the exhaust discharge terminal so as to avoid the backflow of gases into the room from the open flue of gas or other fuel burning appliances.
EC
Please note: This is an estimated adjustment guide
149-CD-POT
The 149-CD-POT is a commissiong device designed to be used with our EC range of fans.
This device will be as standard with our box fan range from May 2018.
The device will allow the for the installer to set the maximum operating speed of the fan that it isconnected to.
The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the149-CD-POT board. This potentionmeter can either be used for single speed adjustment or to set amaximum speed for the fan to operate at when an external control source is used.
If external speed control is required, the jumper connection next to the potentionmeter on the boardwould need to be removed, the installer can then connect to ST1 (using the diagram provided).
When an external speed control is �tted, the maximum speed setting available to the external control islimited by the potentiometer setting of the commissioning device.
10/07/2018MK-149-CD-POT Issue: Saved Date:A
Level / Speed OHMS (Ω)
10 10 (Ω)
9 9 (Ω)
8 8 (Ω)
7 7 (Ω)
6 6 (Ω)
5 5 (Ω)
4 4 (Ω)
3 3 (Ω)
2 1.5 (Ω)
1 500 (Ω)
0 1 (Ω)149-CD-POT
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 3
Installation InstructionsQUIETFLOW SQS EC
3.0 Start Up3.1 Before power is supplied to the unit, check that the wiring is correct as per the fan connection diagram.3.2 At initial start-up, check that impeller rotation and airflow direction is correct.3.3 Check that the motor amperage drawn does not exceed the nameplate rating.
4.0 Fan Maintenance4.1 Inspection of the fan at least once every 12 months is recommended to ensure that the motor, fan blades, and supporting guards, are clean. Any build up of dust and deposits on the blades or guards should be removed using a non-abrasive cleaner.4.2 All fastenings should be checked for tightness. In addition, all rotating items should be checked.4.3 Bearings are of the ‘sealed for life’ type and will not need a detailed inspection.
IMPORTANT - The EC fan has internal electronic overload protection and the AC fan is fitted with an auto-reset thermal cut-out which switches the fan off in the event of a fault condition. Once the motor cools down the fan may start unexpectedly. Only a suitably qualified and competent person may carry out maintenance after the electrical supply has been isolated.
GND 10V E1
MIN MAX
E1GND
ST1
ST2
ST2
E110VGND
MAXMIN
ST1
GND E1
THE ABOVE DIAGRAM SHOWS "ST2".
"ST2" CONNECTIONS ARE FACTORY FITTED.
GND = COMMON•10V = 10VDC INPUT•E1 = 0-10VDC OUTPUT•
YOU CAN DETERMINE THE CURRENT VDC OUTPUT BYDISCONNECTING POWER TO THE UNIT, SETTING AMULTIMETER TO OHMS (Ω) AND PLACING THE TEST PROBESBETWEEN GND AND E1
PLEASE USE THE ESTIMATED ADJUSTMENT GUIDE FOR REFERENCE
THIS IS THE INTERNAL POTENTIOMETERTHIS POTENTIOMETER CAN BE ADJUSTED FOR SINGLE SPEED SETTING OR MAX SPEED SELECTION
THIS LINK/JUMPER SHOULD BE REMOVEDWHEN USING AN EXTERNAL POTENTIOMETEROR EXTERNAL CONTROL SIGNAL CONNECTEDTO "ST1"
THE ABOVE DIAGRAM SHOWS "ST1".
"ST1" CONNECTIONS ARE CLASSED AS"CUSTOMER/USER CONNECTIONS".
GND = COMMON•+ = VDC OUTPUT AS SET BY•
INTERNAL POTENTIOMETERE1 = 0-10VDC INPUT•
149-CD-POT
10/07/2018MK-149-CD-POT Issue: Saved Date:A
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. 149-CD-POT Issue A: 10.07.2018Check the individual product accessories table for fan controller compatibility.
Please note: This is an estimated adjustment guide
149-CD-POT The 149-CD-POT is a commissiong device designed to be used with our EC range of fans. This device will be as standard with our box fan range from May 2018. The device will allow the for the installer to set the maximum operating speed of the fan that it is connected to. The installer or commissioning engineer can adjust the fan speed using the potentiometer built onto the 149-CD-POT board. This potentionmeter can either be used for single speed adjustment or to set a maximum speed for the fan to operate at when an external control source is used. If external speed control is required, the jumper connection next to the potentionmeter on the board would need to be removed, the installer can then connect to ST1 (using the diagram provided). When an external speed control is fitted, the maximum speed setting available to the external control is limited by the potentiometer setting of the commissioning device.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com4
Installation InstructionsQUIETFLOW SQS EC
Table 1: Operational Maintenance
Activity Frequency
Inspect AV mounts for Corrosion or “Sag” 6 months
Check earth bonding 6 months
Dampers check rubber stops and grease (lithium based) pivot points, by removing plastic caps Yearly
Check fixings tightness and conditions of brass track and rivets 26,000 hours / 3 years
Inspect and clean impeller 26,000 hours / 3 years
Remove dirt from motor cooling fins 26,000 hours / 3 years
Check operation of anti-condensation heaters 26,000 hours / 3 years
Check for even tip clearance between impeller and casing – For ATEX 10% of motor shaft diameter with 2mm minimum and 13mm maximum. 26,000 hours / 3 years
Check motor Amps 26,000 hours / 3 years
Any corrosion - treat with suitable chemicals 26,000 hours / 3 years
Check casing seals 26,000 hours / 3 years
Table 2: Terminal Box Maintenance
Activity Frequency
Check that lid seal is in place and not damaged Each time the enclosure is opened
Check that lid fixing screws are in place and secured Each time the enclosure is closed
Check that the mounting bolts are tight and free from corrosion Annually
Check security of all cable glands Annually
Check that all screw clamps terminals are secure Annually and each time enclosure is opened
Check enclosure for damage Annually
5.0 Storage5.1 If the fan is not to be used immediately then it should be stored in a clean, dry, vibration free and lockable location.5.2 The impeller must be spun by hand (ensuring that it does not come to rest in the same position) on a monthly basis to prevent hardening of the grease and possible damage to the bearings.5.3 All items to be stored on pallets that afford adequate protection from damage, dust and high humidity.5.4 If storage periods of longer than 1 month are anticipated then Elta (or their Agent) should be contacted prior to storage taking place, to ensure the storage area provisions will not be detrimental to the well being of Elta products.
6.0 Guarantee Elta Fans Ltd will, free of charge, within a period of 1 year from the date of dIspatch from their works, repair or at its option replace any goods which are proved to have defects as a result of defective materials or workmanship. The goods MUST be returned to Elta Fans Ltd carriage paid for examination.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 5
Wiring DiagramsQUIETFLOW SQS
EC
Please use the table(s) below to match up the product code and the wiring diagram number.
Single Phase 200V - 277V / 50Hz or 60Hz
Three Phase 380V - 480V / 50Hz or 60Hz
PageNo.
Product Code
Wiring Diagram No.
8 SQS100-1ECL 152-00036
8 SQS125-1ECL 152-00036
8 SQS150-1ECL 152-00036
9 SQS200-1ECL 152-00036
10 SQS250-1ECL 152-00036
10 SQS315-1ECL 152-00298951
10 SQS400-1ECL 152-MOEA03K1
10 SQS500-1ECL 152-MOEA03K1
PageNo.
Product Code
Wiring Diagram No.
11 SQS500-3ECL 152-MOEA03K3
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com6
Wiring Diagrams152-00044 EC
FAN C/W POTENTIOMETER SPEED CONTROL (149-POT-10)
200-277V 1PH 50/60HzSUPPLY
149-POT-10
57 621
GREE
N/YE
LLOW
BLUE
BROW
N
WHI
TE
WHI
TE
RED
GREE
N
BLUE
GREY
YELL
OW
WHI
TE
TO MOTOR
FAN
NL E1 A1GND10V
L N
11 14 A2D1
GREE
N
RED
WHI
TE
WHI
TE
GREY
BLUE
WHI
TE
YELL
OW
BROW
N
BLUE
GREE
N/YE
LLOWTO MOTOR
200-277V 1PH 50/60HzSUPPLY
FAN ONLY
FAN
D1 A21411
NL
10V GND A1E1L N
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
11/07/2013MK-152-00044 Issue: Saved Date:C
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-00044 Issue C: 11.07.2013Check the individual product accessories table for fan controller compatibility.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 7
Wiring Diagrams152-00036 EC
BLUE
RED
WHI
TE
YELL
OW
BROW
N
BLUE
GREE
N/YE
LLOW
TO MOTOR
200-277V 1PH 50/60HzSUPPLY
FAN ONLY
FAN
NL E1 A1 GND 10V
L N
FAN C/W POTENTIOMETER SPEED CONTROL (149-POT-10)
NL E1 A1 GND 10V
1 2 7 6 5
L N
RED
BLUE
WHI
TE
YELL
OW
BROW
N
BLUE
GREE
N/YE
LLOW
149-POT-10
TO MOTOR
200-277V 1PH 50/60HzSUPPLY
FAN
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
11/07/2013MK-152-00036 Issue: Saved Date:C
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-00036 Issue C: 11.07.2013Check the individual product accessories table for fan controller compatibility.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com8
Wiring Diagrams152-00036-CD EC
20/06/2018MK-152-00036-CD Issue: Saved Date:B
ALL WIRING AND CONTROLS EQUIPMENT MUST COMPLY TO THE
LATEST IET REGULATIONS, IN PARTICULAR PART 552-01-02/03
JUMPERREMOVED*
MAX SPEEDTRIMMER
NOTE:*JUMPER REMOVED WHEN EXTERNALCONTROL SOURCE IS USED.
PENL
POW
ERCO
NTRO
LS
RED
BLUE
WHITE
YELLOW
G/Y
BLUE
BROWN
200 - 277V 1PH 50HzMAINS SUPPLY
SH100-1ECLSH125-1ECLSH150-1ECLSH200-1ECLSH250-1ECLSH315-1ECL
LN
SINGLE FAN
1PH EC SINGLE FAN C/W 149-CD-POT & 149-POT-10
BLUE
BROW
N
GREE
N/YE
LLOW
1
149-POT-10
5672
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
A1GN
D10
VE1
FOR USE WITH:SQS100-1ECLSQS125-1ECLSQS150-1ECLSQS200-1ECLSQS250-1ECL
SSDR200-1ECSSDR250L-1ECSSDR250H-1EC
REMOVE LINK WHEN USINGEXTERNAL POTENTIOMETER OREXTERNAL CONTROL SIGNAL
POTENTIOMETER FOR SINGLESPEED ADJUSTMENT OR MAXSPEED SELECTION
PENL
POW
ERCO
NTRO
LS
RED
BLUE
WHITE
YELLOW
G/Y
BLUE
BROWN
200 - 277V 1PH 50HzMAINS SUPPLY
SH100-1ECLSH125-1ECLSH150-1ECLSH200-1ECLSH250-1ECLSH315-1ECL
LN
SINGLE FAN
1PH EC SINGLE FAN C/W 149-CD-POT
BLUE
BROW
N
GREE
N/YE
LLOW
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
A1GN
D10
VE1
FOR USE WITH:SQS100-1ECLSQS125-1ECLSQS150-1ECLSQS200-1ECLSQS250-1ECL
SSDR200-1ECSSDR250L-1ECSSDR250H-1EC
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-00036-CD Issue B: 20.06.2018Check the individual product accessories table for fan controller compatibility.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 9
Wiring Diagrams152-104A EC
THERMAL CUT-OUTCONNECT TOCONTROL CIRCUIT
L/U1
N/U2Z1Z2TBTB
THERMAL CUT-OUTCONNECT TOCONTROL CIRCUIT
L/U1
N/U2Z1Z2TBTB
CONTROLLER TERMINAL BOX
EL N
NLENL AUX
FAN
L E
230V 1PH 50Hz SUPPLY
N
104A - CLOCKWISE
FAN C/W TRANSFORMER SPEED CONTROL (149-TC1_)
FAN
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
230V 1PH 50Hz SUPPLY
BLAC
K
WHI
TE
ORAN
GE
BROW
N
BLUE
GREE
N/YE
LLOW
WHI
TE
BROW
N
BLUE
C
1
5
6
7
8
9
A3DRAWING No.
SHEET OF ISSUE
DRAWN BY
DATE
SCALE STATUS
APPROVED
CHECKEDELTA FANS LTD,17 BARNES WALLIS ROAD,SEGENSWORTH INDUSTRIAL ESTATE,FAREHAM, HAMPSHIRE. PO15 5ST.Tel. 01489 566500 Fax. 01489 566555
Elta Fans Ltd. own the copyright of this drawing/
in writing from its owners Elta Fans Ltd.and must not be reproduced without permission
con�dence and which must not be used for anyspeci�cation document which is supplied in
C
FINISH
MATERIAL
SPECIFICATION
DIMENSIONS ARE IN mm UNLESS STATED OTHERWISE
THIS IS A C.A.D. PRODUCED DRAWINGAND THEREFORE NO SUBSEQUENTMANUAL MODIFICATIONS WILL BE
ALLOWED.
TITLE
UNLESS OTHERWISE STATED.
BYISS CN.
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
A
1
B C D E
A C D E
1 1 E
18-10-11
DM
-
I
USED ON
OF THESE VIEWS FOR MANUFACTURINGPURPOSES ARE AT SUPPLIERS RISK.
REFERENCE PURPOSES ONLY. USE
ANY DEVELOPMENT VIEWS SHOWN ONTHIS DRAWING ARE SHOWN FOR
ORIENTATION OF FAN MUST BE AS PERDRAWING OR REFER TO ELTA
A3
GENERAL ā 2.0DUCT CASING LENGTH ā 0.5%BELL CASING DIMENSIONS ā 5.0mm
TOLERANCES
152-104Apurpose other than that for which it is supplied
B
NTS
2
3
4
10
9
8
7
6
5
4
3
2
1
10
C
N/A
N/A
N/A
DMO
DM07/06/2012
DMOK0006RENAMED FROM152-104
D
DM02/05/2012
AWMUPDATED TERMINAL PINTO SHOW ACTUALLOCATION
C
21/11/2011
DMOREMOVED 104XBCOUNTER-CLOCKWISEDRAWING
B
PG03/11/17
LINE AND NEUTRAL RE-ORDERED
ELECTRONIC CONTROLREMOVED
PBK0185E
1 PH MOTOR WITH CAPACITORAND VARIOUS CONTROL OPTIONS
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-104A Issue E: 03.11.2017Check the individual product accessories table for fan controller compatibility.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com10
Wiring Diagrams152-108 EC
WHI
TE
WHI
TE
ORAN
GE
BROW
N
RED
BLUE
GREY
BLAC
K
GREE
N/YE
LLOW
BROW
N
BLAC
K
GREY
BROW
N
BLAC
K
GREY
GREY
RED
WHI
TE
WHI
TE
ORAN
GE
BLAC
K
BLUE
BROW
N
GREE
N/YE
LLOW
TO REVERSE ROTATION SWAP ANY TWO INCOMING SUPPLY CABLES
FAN ONLY
LOW SPEED STAR CONNECTION
L3L2
W1V2V1U2TB TB W2 U1
L1 PE
PEL3L2
W1V2V1U2TB TB W2 U1
L1
TO MOTOR
TO MOTOR
HIGH SPEED DELTA CONNECTION
FAN C/W STAR/DELTA SWITCH
U1W2TBTB U2 V1 V2 W1
FAN TERMINAL BOX
STAR/DELTASWITCH
2 3 6 7 8
W1V2W2U2V1U1
L3L2L1
1514129
L2
WV EL1 L2 L3 U
L1 L3 E
380-440V 3PH 50HzSUPPLY
CONTROLLER TERMINAL BOX
FAN C/W TRANSFORMER SPEED CONTROL (149-TC3_)
FAN TERMINAL BOX
GREY
BLAC
K
BROW
N
BROW
N
BLAC
K
GREY
GREE
N/YE
LLOW
W1V2V1U2TB TB W2 U1
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
11/07/2013MK-152-108 Issue: Saved Date:D
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-108 Issue D: 11.07.2013Check the individual product accessories table for fan controller compatibility.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 11
Wiring Diagrams152-177 EC
TO MOTOR
CONTROLLER TERMINAL BOX
220-240V 1PH 50HzSUPPLY
EL N
NLENL AUX
N/U2
L/U1
N/U2
L/U1
FAN ONLY
TO MOTOR
230V 1PH 50Hz SUPPLY
L N PE
FAN C/W TRANSFORMER SPEED CONTROL (149-TC1_)
FAN
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
GREE
N/YE
LLOW
BLUE
OR G
REY
BLAC
K
BROW
N
GREE
N/YE
LLOW
BLUE
OR G
REY
BLAC
K
BROW
N
BROW
N
BLUE
C
MK-152-177 Issue: C Saved Date: 03/11/17
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-177 Issue C: 03.11.2017Check the individual product accessories table for fan controller compatibility.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com12
Wiring Diagrams152-00298951 EC
4321
10V D1E1GND
200-277V 1PH 50/60HzSUPPLY
L N
1411NL1
5
1 2
GREE
N/YE
LLOW
3 4
TO MOTOR
FAN
1 2 67 5
FAN C/W POTENTIOMETER SPEED CONTROL (149-POT-10)
149-POT-10
A1
A1
FAN
FAN ONLY
TO MOTOR43
GREE
N/YE
LLOW
21 54321
L1 N 11 14 D1E1GND10V
NL
200-277V 1PH 50/60HzSUPPLY
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
C
A3DRAWING No.
SHEET OF ISSUE
DRAWN BY
DATE
SCALE STATUS
APPROVED
CHECKEDELTA FANS LTD,17 BARNES WALLIS ROAD,SEGENSWORTH INDUSTRIAL ESTATE,FAREHAM, HAMPSHIRE. PO15 5ST.Tel. 01489 566500 Fax. 01489 566555
Elta Fans Ltd. own the copyright of this drawing/
in writing from its owners Elta Fans Ltd.and must not be reproduced without permission
con�dence and which must not be used for anyspeci�cation document which is supplied in
C
DIMENSIONS ARE IN mm UNLESS STATED OTHERWISE
BYISS CN.
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
ISS CN. BY
DATE CHKD
A C D E
1 1 A
19-12-13
DM
-
I
A3152-00298951
purpose other than that for which it is supplied
B
NTS
10
C
AWM
DMO05-03-14
NEW DRAWING SEECHANGE NOTE FOR DETAILS.
MBK0091A
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-00298951 Issue A: 05.03.2013Check the individual product accessories table for fan controller compatibility.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 13
Wiring Diagrams152-00298951-CD EC
20/06/2018MK-152-00298951-CD Issue: Saved Date:B
ALL WIRING AND CONTROLS EQUIPMENT MUST COMPLY TO THELATEST IET REGULATIONS, IN PARTICULAR PART 552-01-02/03
CONT
ROL
200 - 277V 1PH 50HzMAINS SUPPLY
FOR USE WITH:SQS315-1ECLSSDR315-1EC
JUMPERREMOVED*
MAX SPEEDTRIMMER
E110
VGN
DD1
A1
149-CD-POTST2
ST1
GND E1
MAXMIN
E110VGND
2 7 6 5
149-POT-10
1
GREE
N/YE
LLOW
BROW
N
BLUE
1PH EC SINGLE FAN C/W 149-CD-POT & 149-POT-10
SINGLE FAN
1411
NL
L N PE
1
2
G/Y
4
3
POW
ER
2
1
4
3
5
NOTE:*JUMPER REMOVED WHEN EXTERNALCONTROL SOURCE IS USED.
5
3
4
1
2
POW
ER
3
4
G/Y
2
1
PENL
LN
1114
SINGLE FAN
1PH EC SINGLE FAN C/W 149-CD-POT
BLUE
BROW
N
GREE
N/YE
LLOW
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
A1D1
GND
10V
E1
POTENTIOMETER FOR SINGLESPEED ADJUSTMENT OR MAXSPEED SELECTION
REMOVE LINK WHEN USINGEXTERNAL POTENTIOMETER OREXTERNAL CONTROL SIGNAL
FOR USE WITH:SQS315-1ECLSSDR315-1EC
200 - 277V 1PH 50HzMAINS SUPPLY
CONT
ROL
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-00298951-CD Issue B: 20.06.2018Check the individual product accessories table for fan controller compatibility.
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com14
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-MOEA03K1 Issue D: 18.07.2013Check the individual product accessories table for fan controller compatibility.
Wiring Diagrams152-MOEA03K1 EC
200-277V 1PH 50/60HzSUPPLY
L N
24V 10V GND D1 E1 1411 NL1
1 2 3 4 5
GREE
N/YE
LLOW
1 2
GREE
N/YE
LLOW
3 4
TO MOTOR
FAN ONLY
FAN
L N
149-POT-10
10V GND D1 E124V
200-277V 1PH 50/60HzSUPPLY
1 2 3 4 5
GREE
N/YE
LLOW
1 2
GREE
N/YE
LLOW
3 4TO MOTOR
FAN
FAN C/W POTENTIOMETER SPEED CONTROL (149-POT-10)
57 621
L1 N11 14
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
18/07/2013MK-152-MOEA03K1 Issue: Saved Date:D
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 15
ALL WIRING AND CONTROLS EQUIPMENT MUST COMPLY TO THELATEST IET REGULATIONS, IN PARTICULAR PART 552-01-02/03
CONT
ROL
200 - 277V 1PH 50HzMAINS SUPPLY
FOR USE WITH:SQS400-1ECLSQS500-1ECL
SSDR400-1ECSSDR500-1EC
REMOVE LINK WHEN USINGEXTERNAL POTENTIOMETER OREXTERNAL CONTROL SIGNAL
POTENTIOMETER FOR SINGLESPEED ADJUSTMENT OR MAXSPEED SELECTION
GND
10V
D1E1
149-CD-POTST2
ST1
GND E1
MAXMIN
E110VGND
GREE
N/YE
LLOW
BROW
N
BLUE
1PH EC SINGLE FAN C/W 149-CD-POT
SINGLE FAN
1411
NL
L N PE
1
2
G/Y
4
3
POW
ER
2
1
4
3
5
G/Y
24V
CONT
ROL
200 - 277V 1PH 50HzMAINS SUPPLY
FOR USE WITH:SQS400-1ECLSQS500-1ECL
SSDR400-1ECSSDR500-1EC
JUMPERREMOVED*
MAX SPEEDTRIMMER
GND
24V
10V
D1E1
149-CD-POTST2
ST1
GND E1
MAXMIN
E110VGND
2 7 6 5
149-POT-10
1
GREE
N/YE
LLOW
BROW
N
BLUE
1PH EC SINGLE FAN C/W 149-CD-POT & 149-POT-10
SINGLE FAN
1411
NL
L N PE
1
2
G/Y
4
3
POW
ER
2
1
4
3
5
G/Y
NOTE:*JUMPER REMOVED WHEN EXTERNALCONTROL SOURCE IS USED.
20/06/2018MK-152-MOEA03K1-CD Issue: Saved Date:BAll wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-MOEA03K1-CD Issue B: 20.06.2018Check the individual product accessories table for fan controller compatibility.
Wiring Diagrams152-MOEA03K1-CD EC
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com16
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-MOEA03K3 Issue D: 18.07.2013Check the individual product accessories table for fan controller compatibility.
Wiring Diagrams152-MOEA03K3 EC
L1 L3
149-POT-10
L2
10V GND D1 E124V
380-480V 3PH 50/60HzSUPPLY
1 2 3 4 5
GREE
N/YE
LLOW
1 2
GREE
N/YE
LLOW
3 4 5
TO MOTOR
FAN
FAN C/W POTENTIOMETER SPEED CONTROL (149-POT-10)
57 621
L1 L2 L311 14
380-480V 3PH 50/60HzSUPPLY
L1 L2 L3
24V 10V GND D1 E1 1411 L3L2L1
41 2 3 4 5
GREE
N/YE
LLOW
1 2
GREE
N/YE
LLOW
3 5
TO MOTOR
FAN ONLY
FAN
ALL WIRING AND CONTROL EQUIPMENT MUST COMPLY TO THELATEST IEE REGULATIONS, IN PARTICULAR PART 552-01-02/03
18/07/2013MK-152-MOEA03K3 Issue: Saved Date:D
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 17
All wiring and control equipment must comply to the latest IEE regulations, in particular part 552-01-02/03. MK-152-MOEA03K3-CD Issue B: 20.06.2018Check the individual product accessories table for fan controller compatibility.
Wiring Diagrams152-MOEA03K3-CD EC
ALL WIRING AND CONTROLS EQUIPMENT MUST COMPLY TO THELATEST IET REGULATIONS, IN PARTICULAR PART 552-01-02/03
E1
5
BLAC
K
GREY
L3
L3L2
5
3
4
1
2
POW
ER
3
4
G/Y (X2)
2
1
PEL2L1
L111
14
SINGLE FAN
3PH EC SINGLE FAN C/W 149-CD-POT & 149-POT-10
BROW
N
GREE
N/YE
LLOW
1
149-POT-10
5672
GND 10V E1
MIN MAX
GND
ST1
ST2
149-CD-POT
E1D1
10V
24V
GND
MAX SPEEDTRIMMER
JUMPERREMOVED*
FOR USE WITH:SQS500-3ECL
SSDR500-3EC
380-480V 3PH 50HzMAINS SUPPLY
CONT
ROL
NOTE:*JUMPER REMOVED WHEN EXTERNALCONTROL SOURCE IS USED.
5
BLAC
K
GREY
L3
L3L2
5
3
4
1
2
POW
ER
3
4
G/Y (X2)
2
1
PEL2L1
L111
14
SINGLE FAN
3PH EC SINGLE FAN C/W 149-CD-POT
BROW
N
GREE
N/YE
LLOW
GND 10V E1
MIN MAX
E1GND
ST1
ST2
149-CD-POT
E1D1
10V
24V
GND
POTENTIOMETER FOR SINGLESPEED ADJUSTMENT OR MAXSPEED SELECTION
REMOVE LINK WHEN USINGEXTERNAL POTENTIOMETER OREXTERNAL CONTROL SIGNAL
FOR USE WITH:SQS500-3ECL
SSDR500-3EC380-480V 3PH 50Hz
MAINS SUPPLY
CONT
ROL
20/06/2018MK-152-MOEA03K3-CD Issue: Saved Date:B
Tel 01384 275800 Fax 01384 275810 Email [email protected] Website eltafans.com18
EU Declaration of Conformity Declaration of Incorporation
Description of Equipment:Building Services Ranges - Air movement fan
Equipment model numbers for safe area fans:SCP, SPA, SAX, SCD, SDA, SCC, SLC, SCPP, SPP, SAMF, HIT, SEM, SEL, ISEO IMF, SH, SSD, SQS, SQSDCV, SQU, SMB, STD, SQT, SQTDCV, SCH, SCHT, SSDR, SSDRDCV, STDR, STDRDCV, SB, SQU-HT, SSQU-HT, SDF, ZFHIC, SRC, SRC, CF, TF, SSRL, BLB, BLTF
Relevant / applied directives:Machinery directive 2006/42/EC, Low voltage directive 2014/35/EU
Relevant / applied directives where applicable:Energy related products directive 2009/125/EC (when used in Europe)Electromagnetic compatibility directive 2014/30/EU (where driven via Inverter)RoHS 2011/65/EU and its amendments (including Directive 2015/863/EU)
Relevant / applied directives where applicable:BS EN ISO 12100 : 2010BS EN 14694 : 2003 + A1 : 2011BS EN 308:1997BS EN ISO 5801:2008
In accordance with the Machinery Directive 2006/42/EC;
The design of the partly completed machine, listed above, complies with the Essential Health and Safety Requirements (EHSRs) of ANNEX I, sections 1.1.2, 1.1.5, 1.4.1, 1.5.1 in EC Machinery Directive 2006/42/EC.
Machinery is incomplete and must not be put into service until such time as the machinery which is partly complete, is to be incorporated, and has been assessed and Declared in Conformity with the provisions of any relevant parts of the Machinery Directive.
We undertake to transmit, upon reasoned request by appropriate national authorities, relevant information relating to the partly completed machinery identified above.
Manufacturer:Elta Fans Limited46 Third AvenuePensnett Trading EstateKingswinfordWest MidlandsDY6 7USUnited Kingdom
Date / Signature of Manufacturer: Document last revised: 20th July 2020
Name / Position of Signatory: Mr. Robert Rees Q.A.Manager Elta Fans LtdThis is an electronic document and is valid without a signature or date. ECD F Issue Status D
Herewith we declare that the air movement equipment below, on the basis of its design and construction as partly completed machines brought onto the market complies with relevant health and safety requirements of the EC Directives stated below. In the event that alterations are made to the machinery without prior consent from Elta Fans Ltd, this declaration becomes invalid.
EU Declaration of conformity/incorporation
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication. Confirmation of dimensions and data will be supplied on request. 19
NotesQUIETFLOW SQS
535-IOM0028 Issue C
eltafans.com
Tel +44 (0) 1384 275800Fax +44 (0) 1384 275810Email [email protected]
46 Third Avenue, Pensnett Trading Estate, Kingswinford, West Midlands, DY6 7US United Kingdom
Tel +44 (0) 1489 566500Fax +44 (0) 1489 566555Email [email protected] / [email protected]
17 Barnes Wallis Road, Segensworth East Industrial Estate, Fareham, Hampshire, PO15 5TT United Kingdom
Applied Technology & Building Services Export
Building Services
BS EN ISO 9001:2015 FM 556465
A member ofHEVAC ASSOCIATION