PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

36
GENERAL NOTES LEGEND 1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including proper placement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific service temperatures. For assistance with exterior wall design, consult with a building science professional. 2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations. 3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install components per manufacturer and project specific requirements. *Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products. LIST OF DRAWINGS WINDOW DETAILS AT MASONRY CLADDING BASE OF WALL DETAILS AT MASONRY CLADDING LEDGER DETAILS AT MASONRY CLADDING PARAPET DETAILS AT MASONRY CLADDING EXPANSION AND CONTROL JOINT DETAILS WINDOW DETAILS AT NON-MASONRY CLADDING NON-MASONRY CLADDING DETAILS CURTAINWALL DETAILS AT NON-MASONRY CLADDING PWM-001 WINDOW HEAD DETAIL MASONRY CLADDING PWM-002 WINDOW JAMB DETAIL MASONRY CLADDING PWM-003 WINDOW SILL DETAIL MASONRY CLADDING PWM-003 (3D-1) WINDOW FLASHING SEQUENCE SHEET-APPLIED FLASHING PWM-003 (3D-2) SHEET-APPLIED FLASHING PRESTRIP PWM-004 BASE-OF-WALL DETAIL MASONRY CLADDING PWM-004 (3D-1) BASE-OF-WALL FLASHING SEQ. (OPT. 1) MASONRY CLADDING PWM-004 (3D-2) BASE-OF-WALL FLASHING SEQ. (OPT. 2) MASONRY CLADDING PWM-004 (ALT 1) BASE-OF-WALL DETAIL (ALTERNATE 1) MASONRY CLADDING PWM-004 (ALT 2) BASE-OF-WALL DETAIL (ALTERNATE 2) MASONRY CLADDING PWM-005 FLOOR LINE DETAIL MASONRY CLADDING PWM-005 (3D-1) FLOOR LINE FLASHING SEQ. (OPT. 1) MASONRY CLADDING PWM-005 (3D-2) FLOOR LINE FLASHING SEQ. (OPT. 2) MASONRY CLADDING PWM-006A MASONRY ANCHOR DETAIL CMU SUBSTRATE PWM-006B MASONRY ANCHOR DETAIL FRAMED SUBSTRATE PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-008 EXPANSION JOINT DETAIL PWM-009 CONTROL JOINT DETAIL PWM-010 WINDOW HEAD DETAIL NON-MASONRY CLADDING PWM-011 WINDOW JAMB DETAIL NON-MASONRY CLADDING PWM-012 WINDOW SILL DETAIL NON-MASONRY CLADDING PWM-013 FLOOR LINE DETAIL NON-MASONRY CLADDING PWM-014 CONCRETE STEM WALL DETAIL NON-MASONRY CLADDING PWM-015 BASE-OF-WALL DETAIL AT GRADE NON-MASONRY CLADDING PWM-016 BASE-OF-WALL DETAIL NON-MASONRY CLADDING PWM-017 INSIDE CORNER DETAIL NON-MASONRY CLADDING PWM-017 (ALT) INSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDING PWM-018 OUTSIDE CORNER DETAIL NON-MASONRY CLADDING PWM-018 (ALT) OUTSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDING PWM-019 KNIFEPLATE PENETRATION DETAIL NON-MASONRY CLADDING PWM-020 PENETRATION DETAILS NON-MASONRY CLADDING PWM-021 CURTAINWALL HEAD DETAIL NON-MASONRY CLADDING PWM-022 CURTAINWALL JAMB DETAIL NON-MASONRY CLADDING PWM-023 CURTAINWALL SILL DETAIL NON-MASONRY CLADDING DEFLECTION JOINT PWM-024 DEFLECTION JOINT NON-MASONRY CLADDING 3" = 1' LIST OF DRAWINGS DRAWING: PWM-000 SCALE: EFFECTIVE DATE: 2020.05.21 SUPERCEDES: PERM-A-BARRIER ® WALL MEMBRANE NEW

Transcript of PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

Page 1: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

LIST OF DRAWINGSWINDOW DETAILS AT MASONRY CLADDING

BASE OF WALL DETAILS AT MASONRY CLADDING

LEDGER DETAILS AT MASONRY CLADDING

PARAPET DETAILS AT MASONRY CLADDING

EXPANSION AND CONTROL JOINT DETAILS

WINDOW DETAILS AT NON-MASONRY CLADDING

NON-MASONRY CLADDING DETAILS

CURTAINWALL DETAILS AT NON-MASONRY CLADDING

PWM-001 WINDOW HEAD DETAIL MASONRY CLADDINGPWM-002 WINDOW JAMB DETAIL MASONRY CLADDINGPWM-003 WINDOW SILL DETAIL MASONRY CLADDINGPWM-003 (3D-1) WINDOW FLASHING SEQUENCE SHEET-APPLIED FLASHINGPWM-003 (3D-2) SHEET-APPLIED FLASHING PRESTRIP

PWM-004 BASE-OF-WALL DETAIL MASONRY CLADDINGPWM-004 (3D-1) BASE-OF-WALL FLASHING SEQ. (OPT. 1) MASONRY CLADDINGPWM-004 (3D-2) BASE-OF-WALL FLASHING SEQ. (OPT. 2) MASONRY CLADDINGPWM-004 (ALT 1) BASE-OF-WALL DETAIL (ALTERNATE 1) MASONRY CLADDINGPWM-004 (ALT 2) BASE-OF-WALL DETAIL (ALTERNATE 2) MASONRY CLADDING

PWM-005 FLOOR LINE DETAIL MASONRY CLADDINGPWM-005 (3D-1) FLOOR LINE FLASHING SEQ. (OPT. 1) MASONRY CLADDINGPWM-005 (3D-2) FLOOR LINE FLASHING SEQ. (OPT. 2) MASONRY CLADDINGPWM-006A MASONRY ANCHOR DETAIL CMU SUBSTRATEPWM-006B MASONRY ANCHOR DETAIL FRAMED SUBSTRATE

PWM-007 PARAPET DETAIL MASONRY CLADDING

PWM-008 EXPANSION JOINT DETAIL PWM-009 CONTROL JOINT DETAIL

PWM-010 WINDOW HEAD DETAIL NON-MASONRY CLADDINGPWM-011 WINDOW JAMB DETAIL NON-MASONRY CLADDINGPWM-012 WINDOW SILL DETAIL NON-MASONRY CLADDING

PWM-013 FLOOR LINE DETAIL NON-MASONRY CLADDINGPWM-014 CONCRETE STEM WALL DETAIL NON-MASONRY CLADDINGPWM-015 BASE-OF-WALL DETAIL AT GRADE NON-MASONRY CLADDINGPWM-016 BASE-OF-WALL DETAIL NON-MASONRY CLADDINGPWM-017 INSIDE CORNER DETAIL NON-MASONRY CLADDINGPWM-017 (ALT) INSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDINGPWM-018 OUTSIDE CORNER DETAIL NON-MASONRY CLADDINGPWM-018 (ALT) OUTSIDE CORNER DETAIL (ALTERNATE) NON-MASONRY CLADDINGPWM-019 KNIFEPLATE PENETRATION DETAIL NON-MASONRY CLADDINGPWM-020 PENETRATION DETAILS NON-MASONRY CLADDING

PWM-021 CURTAINWALL HEAD DETAIL NON-MASONRY CLADDINGPWM-022 CURTAINWALL JAMB DETAIL NON-MASONRY CLADDINGPWM-023 CURTAINWALL SILL DETAIL NON-MASONRY CLADDING

DEFLECTION JOINTPWM-024 DEFLECTION JOINT NON-MASONRY CLADDING

3" = 1'

LIST OF DRAWINGS DRAWING: PWM-000

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 2: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

OPTION 1

3" M

IN.

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING(STAR CUT AT BOLT) - PRIMESUBSTRATE WHERE REQUIRED

5. MORTAR COLLECTION MESH6. MASONRY WEEP/VENT7. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE

8. CONTINUOUS SHELF ANGLESUPPORT PER STRUCTURAL

9. SHEET METAL FLASHING PER ARCH10. PERM-A-BARRIER® SELF-ADHERED

FLASHING*

3" M

IN.

OPTION 2

EXTE

RIO

R

INTE

RIO

R

SEE DETAIL OPTIONS(RIGHT)

3" M

IN.

2

5

8

6

1

7

4

7

3

10

91

4

3

3

3" = 1'

WINDOW HEAD DETAIL -MASONRY CLADDING

DRAWING: PWM-001

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 3: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE AROUNDFASTENER IF REQUIRED

4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

5. SHEET METAL FLASHING PER ARCH6. INTERIOR AIR SEALANT OVER

BACKER ROD

6

3" MIN.

3

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

OPTION 1

EXTERIOR

INTERIORSEE DETAIL OPTIONS(RIGHT)

OPTION 2

3" MIN.

25 414 13

3" = 1'

WINDOW JAMB DETAIL -MASONRY CLADDING

DRAWING: PWM-002

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 4: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. NON-FLANGED WINDOW SYSTEM2. INTERIOR AIR SEALANT OVER

BACKER ROD3. SHEET METAL FLASHING

SANDWICHED BETWEENINTERMITTENT SHIMS

4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

5. PERM-A-BARRIER® WALL MEMBRANE6. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE

2

3

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

GENERAL NOTES

OPTION 1

OPTION 2

EXTE

RIO

R

INTE

RIO

R

SEE DETAIL OPTIONS(RIGHT)

3" M

IN.

1

5

44

5

6

3" = 1'

WINDOW SILL DETAIL -MASONRY CLADDING

DRAWING: PWM-003

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 5: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. SHEATHING SUBSTRATE2. PERM-A-BARRIER® DETAIL

MEMBRANE, NPS DETAIL MEMBRANE,ALUMINUM FLASHING, OR WALLFLASHING - PRIME SUBSTRATE WHEREREQUIRED; SEE PWM-003 (3D-2)

3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL MEMBRANE5. WINDOW PER ARCH

LEGENDSTEP 1 STEP 2

STEP 3 STEP 4

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable self-adhered flashing products.

GENERAL NOTES

2

3

1

4

5

4

4

· CONTINUOUS AIR AND WATER SEALAT PERIMETER OF FENESTRATION,FENESTRATION ATTACHMENT, ANDDRAINAGE OF ROUGH OPENING TOBE PER PROJECT SPECIFICREQUIREMENTS

· SEAL ALL NON-WATER SHEDDINGEDGES WITH ACCEPTABLE SEALANT

· OPTIONAL: WINDOW FLASHINGSEQUENCE CAN BE COMPLETEDAFTER FIELD APPLICATION OFPERM-A-BARRIER® WALL MEMBRANE

NOTE

3" = 1'

WINDOW FLASHING SEQUENCE -SHEET APPLIED FLASHING

DRAWING: PWM-003 (3D-1)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 6: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

WINDOW PRESTRIP VARIATIONS

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

3"

3"

DETAIL A

LAP BACK FLAP OFSILL CORNER PIECEO/ END DAM

CUT LINES SHOWNDASHED

FOLD LINES SHOWNSOLID

TYPICAL SILL PRESTRIPCORNER DETAILINGAT SILL BACK DAMANGLE

BACK DAM ANGLEHEIGHT PER ARCH

BACK DAM ANGLEHEIGHT PER ARCH

CORNER PATCHESINSTALLED AT TOPAND BOTTOMCORNERS OF JAMBFLASHING - CENTERPATCH AT CORNER

PRESS INTO CORNERTO CREATE TIGHTSEAL AND PREVENTPATCH FROMBRIDGING AT ALL 90DEGREE SUBSTRATEANGLE CHANGES.

DETAIL B

CORNER PATCH(SEE DETAIL A)

FOLDING TEMPLATE

V.I.F.

· WINDOW PRESTRIP PERM-A-BARRIER®

DETAIL MEMBRANE, NPS DETAILMEMBRANE, ALUMINUM FLASHING,OR WALL FLASHING

· PRIME SUBSTRATE WHERE REQUIRED

B

A

CD

A

B

C D

A. WITHOUT BACK DAM ANGLE B. WITH BACK DAM ANGLE

3"

V.I.F.

3"

3" 3"

3"

3"3"

V.I.F.

1"MIN.

3"

3"

3" 3"

3"

STEP 2

STEP 3

STEP 1

SEE DETAIL B(RIGHT)

SEE DETAIL A(RIGHT)

3"3"

V.I.F.

STEP 2

STEP 3

STEP 1

V.I.F.

3"

1"

6"

3" = 1'

SHEET-APPLIED FLASHING PRESTRIPDRAWING: PWM-003 (3D-2)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 7: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED

5. BELOW GRADE WATERPROOFINGSYSTEM - SEE GCPAT.COM

6. SHEET METAL FLASHING PER ARCH7. GROUT SOLID TO HEIGHT OF CURB -

SLOPE TOP8. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

3" M

IN.

3" M

IN.

S

SLOPE

SEE PWM-004 (3D-1) FOR 3D DETAIL

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

SEE PWM-004 (3D-2) FOR 3D DETAIL

SEE DETAIL OPTION(RIGHT)

EXTE

RIO

R

INTE

RIO

R

OPTION 2

OPTION 1

2

6

7

1

3

4

3

4

5

1

8

4

4

5

8

3" M

IN.

3" M

IN.

3" = 1'

BASE OF WALL DETAIL -MASONRY CLADDING

DRAWING: PWM-004

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 8: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED

5. SHEET METAL FLASHING PER ARCH6. GROUT SOLID TO HEIGHT OF CURB -

SLOPE TOP7. BELOW GRADE WATERPROOFING

SYSTEM - SEE GCPAT.COM8. MASONRY WEEP/VENT

SEE PWM-004 (OPTION 1) FOR 2D DETAIL

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

652 743 418

3" = 1'

BASE OF WALL FLASHING SEQUENCE (OPTION 1) -MASONRY CLADDING

DRAWING: PWM-004 (3D-1)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 9: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING -PRIME SUBSTRATE WHERE REQUIRED

5. SHEET METAL FLASHING PER ARCH6. GROUT SOLID TO HEIGHT OF CURB -

SLOPE TOP7. BELOW GRADE WATERPROOFING

SYSTEM - SEE GCPAT.COM8. MASONRY WEEP/VENT

SEE PWM-004 (OPTION 2) FOR 2D DETAIL

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

65 3 74 43 12 8

3" = 1'

BASE OF WALL FLASHING SEQUENCE (OPTION 2) -MASONRY CLADDING

DRAWING: PWM-004 (3D-2)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 10: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING5. SHEET METAL FLASHING PER ARCH

SLOPE

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R1'

-0"

6"

3"

2

5

1

3

4

3" = 1'

BASE OF WALL DETAIL (ALTERNATE 1) -MASONRY CLADDING

DRAWING: PWM-004 (ALT 1)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 11: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL FLASHING5. SHEET METAL FLASHING PER ARCH

SLOPE

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R1'

-0"

6"

3"

2

5

1

3

4

NOTE· CONSULT GCP FOR BELOW GRADE

WATERPROOFING COMPATIBILITYAND CONNECTION

3" = 1'

BASE OF WALL DETAIL (ALTERNATE 2) -MASONRY CLADDING

DRAWING: PWM-004 (ALT 2)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 12: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE LIQUID

MEMBRANE, OR GCP APPROVEDSEALANT - 1-INCH TROWELED BEAD

4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING

(STAR CUT AT BOLT), PRIME SUBSTRATEWHERE REQUIRED

6. CONTINUOUS SHELF ANGLE SUPPORTPER STRUCTURAL

7. SHEET METAL FLASHING PER ARCH8. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE

3" M

IN.

84" MIN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

3" M

IN.

SEE PWM-005 (3D-1) FOR 3D DETAIL

OPTION 1

SEE PWM-005 (3D-2) FOR 3D DETAIL

OPTION 2

4

2

6

7

5

1

3

1

5

1

8

8

3" = 1'

FLOOR LINE DETAIL -MASONRY CLADDING

DRAWING: PWM-005

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 13: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. BITUTHENE MASTIC, BITUTHENE

LIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING,

PRIME SUBSTRATE WHERE REQUIRED6. CONTINUOUS SHELF ANGLE

SUPPORT PER STRUCTURAL7. SHEET METAL FLASHING PER ARCH8. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

SEE PWM-005 (OPTION 1) FOR 2D DETAIL

7 62 4

81

3 51

3" = 1'

FLOOR LINE FLASHING SEQUENCE (OPT. 1) -MASONRY CLADDING

DRAWING: PWM-005 (3D-1)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 14: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. MASONRY ANCHOR DETAILING (SEE

DRAWING PWM-006)3. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

4. MORTAR COLLECTION MESH5. PERM-A-BARRIER® WALL FLASHING,

PRIME SUBSTRATE WHERE REQUIRED6. CONTINUOUS SHELF ANGLE

SUPPORT PER STRUCTURAL7. SHEET METAL FLASHING PER ARCH

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

SEE PWM-005 (OPTION 2) FOR 2D DETAIL

7 62 4

31

35 1

3" = 1'

FLOOR LINE FLASHING SEQUENCE (OPT. 2) -MASONRY CLADDING

DRAWING: PWM-005 (3D-2)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 15: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

1. PERM-A-BARRIER® WALL MEMBRANE2. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE FILLETSURROUNDING WIRE TIE PENETRATION

2

1

PERSPECTIVE VIEW

SECTION VIEW

NOTE· ALL CMU JOINTS TO BE STRUCK FULL

AND FLUSH

3" = 1'

MASONRY ANCHOR DETAIL -CMU SUBSTRATE

DRAWING: PWM-006A

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 16: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

1. PERM-A-BARRIER® WALL MEMBRANE2. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE AROUNDFASTENER AT FRONT AND BACK FACEOF MASONRY ANCHOR

2

1

PERSPECTIVE VIEW

SECTION VIEW

12

3" = 1'

MASONRY ANCHOR DETAIL -FRAMED SUBSTRATE

DRAWING: PWM-006B

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 17: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. ROOF MEMBRANE AND ROOF

DETAILS3. SEE CONTROL JOINT DETAIL

PWM-0094. MASONRY WEEP/VENT

4" M

IN.

· CONSULT GCP & ROOFINGMANUFACTURER FORCOMPATIBILITY AND CONNECTIONAT ROOF INTERFACE

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

NOTE

2

4

3

1

3" = 1'

PARAPET DETAIL -MASONRY CLADDING

DRAWING: PWM-007

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 18: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

INTERIOR

EXTERIORPLAN VIEW

PERSPECTIVE VIEW

1. COMPRESSIBLE JOINT FILLER -MAXIMUM 4-INCH WIDE JOINTCAPABLE OF A MAXIMUM 50%MOVEMENT IN COMPRESSION ANDELONGATION

2. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® WALL MEMBRANE5. PERM-A-BARRIER® SELF-ADHERED

FLASHING* INVERTED STRIP

NOTE· WIDTH OF THE INVERTED STRIP SHALL

BE TWICE THE WIDTH OF THEEXPANSION JOINT TOACCOMMODATE MOVEMENT - ALLSEAMS, OVERLAPS, JOINTS, ANDEDGES SEALED WITH S100

· MAXIMUM 4 INCH WIDE JOINTCAPABLE OF A MAXIMUM 50%MOVEMENT IN COMPRESSION ANDELONGATION

· CLADDING AND CLOSURE BYOTHERS NOT SHOWN FOR CLARITY

1

1

5

2

3

4

5 42 3

3" = 1'

EXPANSION JOINT DETAIL -MASONRY CLADDING

DRAWING: PWM-008

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 19: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. BACKER ROD AND COMPATIBLESEALANT

2. PERM-A-BARRIER® WALL MEMBRANE

· MAX 1/2-INCH JOINT CAPABLE OFMAXIMUM 10% MOVEMENT INCOMPRESSION AND ELONGATION

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

NOTE

PLAN VIEW

PERSPECTIVE VIEW

1 2

1

2

3" = 1'

CONTROL JOINT DETAIL -MASONRY CLADDING

DRAWING: PWM-009

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 20: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER®

SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER

ARCH6. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

OPTION 1

OPTION 2

EXTE

RIO

R

INTE

RIO

R

SEE DETAIL OPTIONS(RIGHT)

2

1

3

4

5

6

4

5

4

3

3" = 1'

WINDOW HEAD DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-010

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 21: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. PERM-A-BARRIER®

SELF-ADHERED FLASHING*4. SHEET METAL FLASHING PER

ARCH5. INTERIOR AIR SEALANT OVER

BACKER ROD

5

3" MIN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

OPTION 2

SEE DETAIL OPTIONS(RIGHT)

OPTION 1

EXTERIOR

INTERIOR

3" MIN.

24 413 13

3" = 1'

WINDOW JAMB DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-011

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 22: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. NON-FLANGED WINDOWSYSTEM

2. INTERIOR AIR SEALANT OVERBACKER ROD

3. SHEET METAL FLASHINGSANDWICHED BETWEENINTERMITTENT SHIMS

4. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD

5. PERM-A-BARRIER®

SELF-ADHERED FLASHING*6. PERM-A-BARRIER® WALL

MEMBRANE7. CLADDING ATTACHMENT -

CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

2

3

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

OPTION 1

EXTE

RIO

R

INTE

RIO

R

OPTION 2

SEE DETAIL OPTIONS(RIGHT)

3" M

IN.

1

7

5

4

5

6

6

3" = 1'

WINDOW SILL DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-012

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 23: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER®

SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER

ARCH3"

MIN

.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

3" M

IN.

3" M

IN.

2

5

4

1

3

1

DRAWING: PWM-013

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

3" = 1'

FLOOR LINE DETAIL -NON-MASONRY CLADDING

Page 24: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER®

SELF-ADHERED FLASHING*5. TWO-PIECE SHEET METAL

FLASHING PER ARCH3"

MIN

.3"

MIN

.

· CONFIRM MAXIMUM SERVICETEMPERATURE OF PERM-A-BARRIERPRODUCTS DIRECTLY UNDEREXPOSED METAL FLASHING

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

NOTE

EXTE

RIO

R

INTE

RIO

R

2

1

3

4

5

3" = 1'

CONCRETE STEM WALL DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-014

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 25: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER®

SELF-ADHERED FLASHING*5. TWO-PIECE SHEET METAL

FLASHING PER ARCH6. BELOW GRADE

WATERPROOFING SYSTEM - SEEGCPAT.COM3"

MIN

.3"

MIN

.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

2

5

1

3

4

6

3" = 1'

BASE-OF-WALL AT GRADE DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-015

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 26: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THEGCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER®

SELF-ADHERED FLASHING*5. SHEET METAL FLASHING PER

ARCH6. TERMINATION PER HORIZONTAL

WATERPROOFING SYSTEMMANUFACTURER

7. HORIZONTAL WATERPROOFINGSYSTEM - SEE GCPAT.COM

6

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

2

1

3

4

5

7 NOTE· CONSULT GCP FOR HORIZONTAL

WATERPROOFING COMPATIBILITYAND CONNECTION

3" = 1'

BASE-OF-WALL DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-016

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 27: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER®

SELF-ADHERED FLASHING*.PRIME SUBSTRATE WHEREREQUIRED

2. PERM-A-BARRIER® WALLMEMBRANE

3. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS

2" M

IN.

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

31 2

3" = 1'

INSIDE CORNER DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-017

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 28: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS

2" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

21

3" = 1'

INSIDE CORNER DETAIL (ALTERNATE) -NON-MASONRY CLADDING

DRAWING: PWM-017 (ALT)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 29: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® DETAILMEMBRANE, NPS DETAILMEMBRANE, ALUMINUMFLASHING, OR WALL FLASHING.PRIME SUBSTRATE WHEREREQUIRED

2. PERM-A-BARRIER® WALLMEMBRANE

3. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS

3" M

IN.

2" MIN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

32 1

3" = 1'

OUTSIDE CORNER DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-018

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 30: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -DETAIL PER GCPATREQUIREMENTS

2" MIN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

21

3" = 1'

OUTSIDE CORNER DETAIL (ALTERNATE) -NON-MASONRY CLADDING

DRAWING: PWM-018 (ALT)

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 31: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. CLADDING ATTACHMENT -CONFIRM DETAILINGREQUIREMENTS WITH THE GCPATREPRESENTATIVE

3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUID MEMBRANE- FLASHING AND CANT SEAL

4. KNIFE PLATE PENETRATION5. POLYURETHANE SEALANT OR

NON-SHRINK GROUT PERBACKUP WALL TYPE

6. JOINT TREATMENT PER DETAILPWM-009

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

PERSPECTIVE VIEW

2" M

IN.

2" M

IN.

2" MIN.

2"MIN.

2" M

IN.

2"MIN.

5

3

SECTIONVIEW

2

4

2

4

3

6

3

1

1

3" = 1'

KNIFEPLATE PENETRATION DETAIL -NON-MASONRY CLADDING

DRAWING: PWM-019

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 32: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - 1-INCHTROWELED BEAD

3. AIR AND WATER TIGHT BOXAND PENETRATION

4. AIR AND WATER TIGHT PIPE ORDUCT PENETRATION

5. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUIDFLASHING, BITUTHENE MASTIC,OR BITUTHENE LIQUIDMEMBRANE - FLASHING ANDCANT SEAL

2 1/

2" M

IN

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

EXTE

RIO

R

INTE

RIO

R

3

4

5

1

2

1

5

2 1/

2" M

IN

3" = 1'

PENETRATION DETAILS -NON-MASONRY CLADDING

DRAWING: PWM-020

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 33: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. CLADDING ATTACHMENT -

CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE

3. BITUTHENE MASTIC, BITUTHENELIQUID MEMBRANE, OR GCPAPPROVED SEALANT - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

5. SHEET METAL FLASHING PER ARCH6. INTERIOR AIR SEALANT OVER

BACKER ROD7. PERM-A-BARRIER® S100,

PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

R

SEE DETAIL OPTION(RIGHT)

OPTION 1

OPTION 2

3" M

IN.

3" M

IN.

6

3" M

IN.

3" M

IN.

6

5

2

5

3

4

1

7

4

1

3" = 1'

CURTAINWALL HEAD DETAIL DRAWING: PWM-021

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 34: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALL MEMBRANE2. CLADDING ATTACHMENT -

CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE

3. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

4. SHEET METAL FLASHING PER ARCH5. INTERIOR AIR SEALANT OVER

BACKER ROD

3" MIN.

5

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

SEE DETAIL OPTIONS(RIGHT)

OPTION 1

OPTION 2

EXTERIOR

INTERIOR

24 413 3 1

3" MIN.

3" = 1'

CURTAINWALL JAMB DETAIL DRAWING: PWM-022

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 35: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

3" M

IN.

1. CURTAINWALL SILL OVERMANUFACTURER'S STARTER TRACK

2. INTERIOR AIR SEALANT OVERBACKER ROD

3. PERM-A-BARRIER® S100,PERM-A-BARRIER® LIQUID FLASHING,BITUTHENE MASTIC, OR BITUTHENELIQUID MEMBRANE - 1-INCHTROWELED BEAD

4. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

5. PERM-A-BARRIER® WALL MEMBRANE6. CLADDING ATTACHMENT -

CONFIRM DETAILING REQUIREMENTSWITH THE GCPAT REPRESENTATIVE

2

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

EXTE

RIO

R

INTE

RIO

ROPTION 1

OPTION 2

SEE DETAIL OPTIONS(RIGHT)

3" M

IN.

6

1

5

4

3

4

5

3" = 1'

CURTAINWALL SILL DETAIL DRAWING: PWM-023

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW

Page 36: PWM-007 PARAPET DETAIL MASONRY CLADDING PWM-002 …

1. PERM-A-BARRIER® WALLMEMBRANE

2. PERM-A-BARRIER® SELF-ADHEREDFLASHING*

3. MINIMUM 3/4" BACKER ROD4. PERM-A-BARRIER DETAIL

MEMBRANE INVERTED STRIPSUFFICIENT IN SIZE TO COVERBACKER ROD

5. CLADDING ATTACHMENT,CONFIRM DETAILINGREQUIREMENTS WITH THE GCPATREPRESENTATIVE

3" M

IN.

3" M

IN.

GENERAL NOTES

LEGEND

1. Detail not suitable for all climates. Avoiding excessive moisture accumulation in exterior walls is dependent on many factors including properplacement of insulation and water, air, and vapor control layers in the wall. Confirm membranes are suitable for project specific servicetemperatures. For assistance with exterior wall design, consult with a building science professional.

2. Install all GCP products in accordance with GCP Product Data Sheets and GCP recommendations.3. GCP products are indicated in the detail legend in BOLDFACE font. Detail components by others are indicated in GRAY FONT. Install

components per manufacturer and project specific requirements.

*Refer to air barrier system product data sheet for acceptable SELF-ADHERED FLASHING* products.

3

1

2

4

OPTION 2

OPTION 3

1

2

3

4

1

5

2

3

4

5

5

3" = 1'

DEFLECTION JOINT DRAWING: PWM-024

SCALE:

EFFECTIVE DATE: 2020.05.21

SUPERCEDES:

PERM-A-BARRIER® WALLMEMBRANE

NEW