Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ] · Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]...

129
Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ] National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 1 of 129 11/3/2016 12:03 PM

Transcript of Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ] · Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]...

Public Input No. 1-NFPA 13D-2015 [ Chapter 2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

1 of 129 11/3/2016 12:03 PM

American Society of Mechanical Engineers

Chapter 2 Referenced Publications

2.1 General.

The documents or portions thereof listed in this chapter are referenced within this standard and shall beconsidered part of the requirements of this document.

2.2 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 72 ® , National Fire Alarm and Signaling Code, 2016 edition.

NFPA 220, Standard on Types of Building Construction, 2015 edition.

NFPA 750, Standard on Water Mist Fire Protection Systems, 2014 edition.

2.3 Other Publications.

2.3.1

ANSI

ASME Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI B36.10M, Welded and Seamless Wrought Steel Pipe , 2004.

2.3.2 ASME Publications.

ASME International , Two Park Avenue, New York, NY 10016-5990.

ASME B16.1, Gray Iron Pipe Flanges and Flanged Fittings, Classes 25, 125, and 250 ,

2010

2015 .

ASME B16.3, Malleable Iron Threaded Fittings, Classes 150 and 300 ,

2006

2011 .

ASME B16.4, Gray Iron Threaded Fittings , Classes 125 and 250,

2006

2011 .

ASME B16.5, Pipe Flanges and Flanged Fittings, NPS 1/2 through NPS 24 Metric/Inch Standard ,

2009

2013 .

ASME B16.9, Factory-Made Wrought Buttwelding Fittings ,

2007

2013 .

ASME B16.11, Forged Fittings, Socket-Welding and Threaded ,

2009

2011 .

ANSI/

ASME B16.15,

Cast Bronze Threaded Fittings , 2006

Cast Copper Alloy Threaded Fittings Classes 125 and 250 , 2013 .

ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings ,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

2 of 129 11/3/2016 12:03 PM

2001

2012 .

ASME B16.22, Wrought Copper and Copper Alloy Solder - Joint Pressure Fittings ,

2001

2013 .

ASME B16.25, Buttwelding Ends ,

2007

2012 .

ASME B36.10M, Welded and Seamless Wrought Steel Pipe , 2015 .

2.3.

3

2 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A53/A53M, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Weldedand Seamless , 2012.

ASTM A135/A135M, Standard Specification for Electric-Resistance-Welded Steel Pipe , 2009

(2004)

, reapproved 2014 .

ASTM A234/A234M, Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steelfor Moderate and High Temperature Service ,

2013 e1

2015 .

ASTM A795/A795M, Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Weldedand Seamless Steel Pipe for Fire Protection Use , 2013.

ASTM B32, Standard Specification for Solder Metal , 2008 , reapproved 2014 .

ASTM B43, Standard Specification for Seamless Red Brass Pipe ,

2009

Standard Sizes , 2015 .

ASTM B75/B75M, Standard Specification for Seamless Copper Tube , 2011.

ASTM B88, Standard Specification for Seamless Copper Water Tube ,

2009

2014 .

ASTM B251, Standard Specification for General Requirements for Wrought Seamless Copper andCopper-Alloy Tube , 2010.

ASTM B813, Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copperand Copper-Alloy Tube ,

2010 (2010)

2016 .

ASTM B828, Standard Practice for Making Capillary Joints by Soldering of Copper and Copper AlloyTube and Fittings , 2002 , reapproved 2010 .

ASTM F437, Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80 ,

2009

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

3 of 129 11/3/2016 12:03 PM

2015 .

ASTM F438, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 40 ,

2009

2015 .

ASTM F439, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 80 , 2013.

ASTM F442/F442M, Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe(SDR-PR) , 2013 e1.

ASTM F876, Standard Specification for Crosslinked Polyethylene (PEX) Tubing ,

2013 e1

2015a .

2.3.

4

3 AWS Publications.

American Welding Society,

550 NW LeJeune Road,

8869 NW 36 Street, #130 , Miami, FL

33126

33166-6672 .

AWS A5.8 /A5.8M , Specification for Filler Metals for Brazing and Braze Welding ,

2004

2011, Amendment 1, 2012 .

2.3.

5

4 Other Publications.

Merriam-Webster’s Collegiate Dictionary , 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

2.4 References for Extracts in Mandatory Sections.

NFPA 5000 ® , Building Construction and Safety Code ® , 2015 edition.

Statement of Problem and Substantiation for Public Input

Referenced current SDO names, addresses, standard names, numbers and editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 2-NFPA 13D-2015 [Chapter B]

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

4 of 129 11/3/2016 12:03 PM

Zip:

Submittal Date: Sun Dec 20 00:27:48 EST 2015

Committee Statement

Resolution: FR-1-NFPA 13D-2016

Statement: Latest editions need to be referenced in Chapter 2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

5 of 129 11/3/2016 12:03 PM

Public Input No. 88-NFPA 13D-2016 [ Section No. 2.3.2 ]

2.3.2 ASME Publications.

American Society of Mechanical Engineers, Two Park Avenue, New York, NY 10016-5990.

ASME B16.1, Gray Iron Pipe Flanges and Flanged Fittings, Classes 25, 125, and 250, 2010.

ASME B16.3, Malleable Iron Threaded Fittings, Classes 150 and 300, 2006.

ASME B16.4, Gray Iron Threaded Fittings, Classes 125 and 250, 2006.

ASME B16.5, Pipe Flanges and Flanged Fittings, NPS 1/2 through NPS 24 Metric/Inch Standard, 2009.

ASME B16.9, Factory-Made Wrought Buttwelding Fittings, 2007.

ASME B16.11, Forged Fittings, Socket-Welding and Threaded, 2009.

ANSI/ASME B16.15, Cast Bronze Threaded Fittings, 2006.

ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings, 2001.

ASME B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings, 2001.

ASME B16.25, Buttwelding Ends, 2007.

ASME B16.51, Copper and Copper Alloy Press-Connect Pressure Fittings

Statement of Problem and Substantiation for Public Input

Currently NFPA 13D does not currently reference ASME B16.51 This Standard establishes requirements for cast copper alloy, wrought copper, and wrought copper alloy, press-connect pressure fittings for use with hard drawn seamless copper water tube conforming to ASTM B88 for piping systems conveying water. The press-connect system (tube, fitting, and joint) conforming to this Standard is for use at a maximum pressure of 1 380 kPa (200 psi) over the temperature range from 0°C to 93°C (32°F to 200°F). This Standard provides requirements for fittings suitable for press-connect joining and covers the following:(a) size designations(b) pressure–temperature ratings(c) terminology(d) dimensions and tolerances(e) materials(f) design qualification(g) required installation instructions(h) markings By adding this standard, this will direct users to the correct design and material dimensions for copper press-connect fittings.

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:54:22 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

6 of 129 11/3/2016 12:03 PM

Resolution: FR-1-NFPA 13D-2016

Statement: Latest editions need to be referenced in Chapter 2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

7 of 129 11/3/2016 12:03 PM

Public Input No. 6-NFPA 13D-2016 [ Section No. 2.3.3 ]

2.3.3 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A53/A53M, Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded andSeamless, 2012.

ASTM A135/A135M, Standard Specification for Electric-Resistance-Welded Steel Pipe, 2009 (2004 2014 ).

ASTM A234/A234M, Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel forModerate and High Temperature Service, 2013 e1.

ASTM A795/A795M, Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Weldedand Seamless Steel Pipe for Fire Protection Use, 2013.

ASTM B32, Standard Specification for Solder Metal, 2008.

ASTM B43, Standard Specification for Seamless Red Brass Pipe, 2009.

ASTM B75/B75M, Standard Specification for Seamless Copper Tube, 2011.

ASTM B88, Standard Specification for Seamless Copper Water Tube, 2009.

ASTM B251, Standard Specification for General Requirements for Wrought Seamless Copper andCopper-Alloy Tube, 2010.

ASTM B813, Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copper andCopper-Alloy Tube, 2010 (2010).

ASTM B828, Standard Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tubeand Fittings, 2002.

ASTM F437, Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 2009 2015 .

ASTM F438, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 40, 2009 2015 .

ASTM F439, Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic PipeFittings, Schedule 80, 2013.

ASTM F442/F442M, Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe(SDR-PR), 2013 e1.

ASTM F876, Standard Specification for Crosslinked Polyethylene (PEX) Tubing, 2013 e1 2015a .

Statement of Problem and Substantiation for Public Input

updates

Submitter Information Verification

Submitter Full Name: Marcelo Hirschler

Organization: GBH International

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 17:46:22 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

8 of 129 11/3/2016 12:03 PM

Committee Statement

Resolution: FR-1-NFPA 13D-2016

Statement: Latest editions need to be referenced in Chapter 2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

9 of 129 11/3/2016 12:03 PM

Public Input No. 28-NFPA 13D-2016 [ New Section after 2.4 ]

TITLE OF NEW CONTENT

Underwriters Laboratories Publications

ANSI/UL 213 Standard for Rubber Gasketed Fittings, 2004.

ANSI/UL 852 Standard for Metallic Sprinkler Pipe for Fire Protection Service, 2008.

ANSI/UL 1821 Standard for Thermoplastic Sprinkler Pipe and Fittings For Fire Protection Service,2015.

Statement of Problem and Substantiation for Public Input

Currently the UL 213, UL 852 and UL 1821 Standards are not referenced by NFPA 13D but are widely used standards for Rubber Gasketed Fittings for Fire Protection Service, Metallic Sprinkler Pipe for Fire Protection Service and Thermoplastic sprinkler pipe and fittings for Fire protection service. The addition of the publications coincides with the related public input submittals and will help to more clearly identify accepted reference standards for fire protection pipe and fittings.The addition of these publications coincides with the related public input submittals. There is no fiscal impact associated with this proposal.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 22-NFPA 13D-2016 [Section No. 5.2.5 [Excluding anySub-Sections]]

Standard Referenced inTable

Public Input No. 29-NFPA 13D-2016 [Section No. 5.2.3.2]

Public Input No. 34-NFPA 13D-2016 [Section No. 5.2.2 [Excluding anySub-Sections]]

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 10:24:35 EDT 2016

Committee Statement

Resolution: FR-1-NFPA 13D-2016

Statement: Latest editions need to be referenced in Chapter 2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

10 of 129 11/3/2016 12:03 PM

Public Input No. 41-NFPA 13D-2016 [ New Section after 3.3.1 ]

3.3.1 Bathroom

Within a dwelling unit, any room or compartment containing a lavatory dedicated to personal hygiene, or awater closet, or bathing capability such as a shower or tub, or any combination of facilities thereof.

Statement of Problem and Substantiation for Public Input

Even though the definition can be found in 13R, at times there have been conflicting opinions about what constitutes a bathroom, especially when the bathroom is divided up into two separate rooms and the combined total size exceeds 55 square feet but the individual room size is less than 55 square feet.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 42-NFPA 13D-2016 [New Section after A.3.2.4]

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 21 17:18:52 EDT 2016

Committee Statement

Resolution: FR-19-NFPA 13D-2016

Statement: Even though the definition can be found in 13R, at times there have been conflicting opinions aboutwhat constitutes a bathroom, especially when the bathroom is divided up into two separate roomsand the combined total size exceeds 55 square feet but the individual room size is less than 55square feet.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

11 of 129 11/3/2016 12:03 PM

Public Input No. 32-NFPA 13D-2016 [ New Section after 3.3.6 ]

TITLE OF NEW CONTENT

Press-Connect Fitting-

A permanent mechanical connection for joining copper tubing, steel and stainless steel pipe utilizingelastomeric seal or an elastomeric seal and corrosion-resistant grip ring or rings. Fitting connections aremade with a pressing tool and jaws or rings approved by the fitting manufacturer for use in accordance withthe product listing.

Statement of Problem and Substantiation for Public Input

Currently there is no definition for Press-Connect fittings in NFPA 13D. The term Press-Connect Fitting is used in both the IAPMO and ICC codes. The wide use of Mechanical type fittings has created the need to identify fittings such as Press-Connect and provide definitions to prevent confusion between mechanical fitting types and to help identify the correct standards these fittings are required to be listed to. This definition is proposed to prevent confusion within the industry and aligns definitions for these type fittings. This definition will also help to prevent incorrect terminology in the industry such as referring to Press-Connect fittings as Propress which we have all commonly seen. As the Manufacturer of Propress we do like that our brand name is the name used by those in the industry when referring to Press-Connect fittings, but we do want the industry to have the correct terminology of the fittings to avoid any confusion between manufactured products.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 25-NFPA 13D-2016 [Section No. 5.2.6] Reference to Press-Connect within the code.

Public Input No. 23-NFPA 13D-2016 [Section No. 5.2.7] Refernce to Press-Connect within the code.

Public Input No. 33-NFPA 13D-2016 [Section No. 5.2.4]

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 11:57:06 EDT 2016

Committee Statement

Resolution: Connection methods are either included in tables listing pipe and fittings that do not require specificlistings, or are covered by a manufacturers specific listings. No other connection methods are definedin the standard and the task group doesn’t believe there is a need to add this definition either.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

12 of 129 11/3/2016 12:03 PM

Public Input No. 45-NFPA 13D-2016 [ New Section after 4.1.2 ]

4.1.3

Sprinklers having a temperature rating of 250°F to 300°F (121°C to 149°C) shall be classified as hightemperature-rated sprinklers.

Statement of Problem and Substantiation for Public Input

High temperature-rated sprinklers are called out in 7.5.6.3(4) and as such should be defined in the same manner as ordinary and intermediate temperature-rated sprinklers are.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 09:20:50 EDT 2016

Committee Statement

Resolution: FR-3-NFPA 13D-2016 Agree with submitter. First draft revision created.

Statement: High temperature-rated sprinklers are called out in 7.5.6.3(4) and as such should be defined in thesame manner as ordinary and intermediate temperature-rated sprinklers are.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

13 of 129 11/3/2016 12:03 PM

Public Input No. 77-NFPA 13D-2016 [ Section No. 4.4 ]

4.4 Smoke Alarms.

Smoke When provided, smoke alarms shall be provided installed in accordance with NFPA 72.

Statement of Problem and Substantiation for Public Input

13D does not govern the requirements for the installation of smoke alarms. A local alarm is a foundational and critical element to the 13D standard, and this provision is retained adequately in section 7.6, which requires a waterflow alarm in systems installed in homes without smoke alarms installed in accordance with NFPA 72.

Submitter Information Verification

Submitter Full Name: Chase Browning

Organization: Medford Fire Rescue, Medford Oregon

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 23:41:44 EDT 2016

Committee Statement

Resolution: It was decided to delete this requirement in it's entirety.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

14 of 129 11/3/2016 12:03 PM

Public Input No. 56-NFPA 13D-2016 [ Section No. 5.1.2.1 ]

5.1.2.1

Tanks, expansion tanks, gauges, pumps, hangers, waterflow detection devices, and valves shall not berequired to be listed.

Statement of Problem and Substantiation for Public Input

Based on independent testing, some unlisted hangers used on NFPA 13D sprinkler systems have caused the sprinkler system to catastrophically fail during a fire scenario. A specific example of an unlisted hanger that has been witnessed to fail is the talon clamp with nail. This hanger clamp has a lower melting point than the required sprinkler head activation temperature and actually caused an entire section of the system piping to collapse, rendering the sprinkler system ineffective. If listed hangers are required, this potential hazard can be avoided with little impact to the overall system cost, in keeping with the intent of the standard to provide affordable protection from fire for residents of one- and two-family dwellings.

Submitter Information Verification

Submitter Full Name: Tony Fleming

Organization: Metropolitan Fire Protection

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 27 20:57:35 EDT 2016

Committee Statement

Resolution: FR-47-NFPA 13D-2016 Two new components were added to this section, and the multiple items putinto list form, starting with the water source. The water supply pipe and fittings only need to meet thestandards of the local plumbing code in accordance with 5.3. Connections between a tank and pumpare typically a non-listed hose or flexible connection. The 5' limitation was included to prevent havinga long distance between the tank and pump.

Statement: Based on independent testing, some unlisted hangers used on NFPA 13D sprinkler systems havecaused the sprinkler system to catastrophically fail during a fire scenario. A specific example of anunlisted hanger that has been witnessed to fail is the talon clamp with nail. This hanger clamp has alower melting point than the required sprinkler head activation temperature and actually caused anentire section of the system piping to collapse, rendering the sprinkler system ineffective. If listedhangers are required, this potential hazard can be avoided with little impact to the overall systemcost, in keeping with the intent of the standard to provide affordable protection from fire for residentsof one- and two-family dwellings.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

15 of 129 11/3/2016 12:03 PM

Public Input No. 63-NFPA 13D-2016 [ Section No. 5.1.2.1 ]

5.1.2.1

Tanks, expansion tanks, gauges, pumps, underground pipe and fittings, hangers, waterflow detectiondevices, and valves shall not be required to be listed.

Statement of Problem and Substantiation for Public Input

In the scenario where the water supply source and riser assembly is not in the dwelling unit, underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMA uses this arrangement when providing sprinkler systems for many of their manufactured housing units. This arrangement could also be used when retrofitting an existing dwelling or home. The added text makes it clear that underground pipe and fittings do not have to be listed. However, in accordance with section 5.3 the underground pipe and fittings must comply with the applicable plumbing code for the dwelling or home.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 64-NFPA 13D-2016 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 13:34:46 EDT 2016

Committee Statement

Resolution: FR-46-NFPA 13D-2016

Statement: In the scenario where the water supply source and the riser assembly is not in the dwelling unit,underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMAuses this arrangement when providing sprinkler systems for many of their manufactured housingunits. This arrangement could also be used when retrofitting an existing dwelling or home. The addedtext makes it clear that underground pipe and fittings do not have to be listed. However, inaccordance with section 5.3 the underground pipe and fittings must comply with the applicableplumbing code for the dwelling or home.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

16 of 129 11/3/2016 12:03 PM

Public Input No. 34-NFPA 13D-2016 [ Section No. 5.2.2 [Excluding any Sub-Sections] ]

Pipe or tube used in sprinkler systems shall be of the materials specified in Table 5.2.2 or shall be inaccordance with 5.2.3.

Table 5.2.2 Pipe or Tube Materials and Dimensions

Materials and Dimensions Standard

Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded andSeamless Steel Pipe for Fire Protection Use

ASTM A795

Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded andSeamless

ASTM A53

Welded and Seamless Wrought Steel PipeANSIB36.10M

Standard Specification for Electric-Resistance-Welded Steel Pipe ASTM A135

Standard Specification for Seamless Copper Tube [Copper Tube (Drawn, Seamless)] ASTM B75

Standard Specification for Seamless Copper Water Tube ASTM B88

Standard Specification for General Requirements for Wrought Seamless Copper andCopper-Alloy Tube

ASTM B251

Standard Specification for Liquid and Paste Fluxes for Soldering Applications of Copper andCopper-Alloy Tube

ASTM B813

Specification for Filler Metals for Brazing and Braze Welding (BCuP, copper-phosphorus, orcopper-phosphorus-silver brazing filler metal)

AWS A5.8

Standard Specification for Solder Metal [alloy grades containing less than 0.2 percent lead asidentified in ASTM B32, Table 5, Section 1, and having a solidus temperature that exceeds400°F (204°C)]

ASTM B32

Standard Specification for Seamless Red Brass Pipe

Standard for Metallic Sprinkler Pipe for Fire Protection Service

ASTM B43

UL 852

Statement of Problem and Substantiation for Public Input

Currently this UL standard is not included in NFPA 13D. This standard is widely used by designers, installers and manufacturers and referencing in this table will properly guide the industry to this important and widely used standard. There is no cost associated with this addition to the table.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 28-NFPA 13D-2016 [New Section after 2.4] Referenced Publications

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 09 16:56:54 EDT 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

17 of 129 11/3/2016 12:03 PM

Committee Statement

Resolution: It isn’t appropriate to add a performance standard into Table 5.2.2 Pipe or Tube Materials andDimensions. This table is the list of pipe or tube materials that are not required to be specifically listedfor fire protection service. Other pipe or tube not covered by the standards in the table are allowed tobe used when they meet Section 5.2.3, in essence, when they are listed for sprinkler system use.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

18 of 129 11/3/2016 12:03 PM

Public Input No. 29-NFPA 13D-2016 [ Section No. 5.2.3.2 ]

5.2.3.2 *

Chlorinated polyvinyl chloride (CPVC) pipe and crosslinked polyethylene (PEX) pipe shall comply with theportions of the American Society for Testing and Materials (ASTM) and UL standards specified in Table5.2.3.2 that apply to fire protection service.

Table 5.2.3.2 Specifically Listed Pipe or Tube Materials and Dimensions

Materials and Dimensions Standard

Nonmetallic Piping:

Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Pipe ASTM F442

Standard Specification for Crosslinked Polyethylene (PEX) Tubing

Standard for Thermoplastic Pipe and Fittings for Fire Protection Service

ASTM F876

UL 1821

Statement of Problem and Substantiation for Public Input

This standard was written for CPVC pipe and fittings for Fire Protection Systems and should be included in NFPA 13D to direct manufacturer's, designers and installers to the appropriate standards for Thermoplastic fittings. The addition of the standard will be consistent with referenced standards in the ICC Fire Code TABLE AG101.1 and Section AG102 and will help to prevent confusion within the industry. There is no cost associated with the inclusion of this standard as manufacturers of these products currently list to this standard. UL 1821 has additional performance requirements above and beyond ASTM f442 and ASTM F 876 and should be referenced in this table.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 28-NFPA 13D-2016 [New Section after 2.4] Referenced Publications

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 11:01:54 EDT 2016

Committee Statement

Resolution: It isn’t appropriate to add a performance standard into Table 5.2.3.2 Specifically Listed Pipe or TubeMaterials and Dimensions. This table is the list of pipe or tube materials that are commonly used butstill are required to be specifically listed for fire protection service. Other pipe or tube not covered bythe standards in the table are allowed to be used when they meet Section 5.2.3, in essence, whenthey are listed for sprinkler system use. Finally, there should not be only one performance standardreferenced.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

19 of 129 11/3/2016 12:03 PM

Public Input No. 33-NFPA 13D-2016 [ Section No. 5.2.4 ]

5.2.4

Schedule 10 steel pipe shall be permitted to be joined with press-connect fittings or mechanical groovecouplings approved for service.

5.2.4.1

Where mechanical groove couplings are used to join pipe, grooves shall be rolled on the pipe by anapproved groove-rolling machine.

Statement of Problem and Substantiation for Public Input

Current language does not allow for press connect technology to be used on Schedule 10 piping. Addition of Press-Connect fittings in this section will prevent confusion within the industry on allowable methods for joining schedule 10 pipe. Press-Connect fittings are listed for use with Schedules 40 and 10 pipes as they do not reduce wall thickness of the pipe by threading.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 32-NFPA 13D-2016 [New Section after 3.3.6] Definition of Press-Connect Fitting

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 12:07:50 EDT 2016

Committee Statement

Resolution: The substantiation for PI #33 states that Section 5.2.4 does not allow for press-connect fittings onSchedule 10 piping. The actual language in this section states that mechanical groove couplingsapproved for service are permitted to be used. Press fittings (and any other type offittings/connections) that are listed for use with Schedule 10 piping are allowed to be used inaccordance with those listings per section 5.2.3 and 5.2 9.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

20 of 129 11/3/2016 12:03 PM

Public Input No. 22-NFPA 13D-2016 [ Section No. 5.2.5 [Excluding any Sub-Sections] ]

Fittings used in sprinkler systems shall be of the materials listed in Table 5.2.5 or shall be in accordancewith 5.2.9.

Table 5.2.5 Fitting Materials and Dimensions

Materials and Dimensions Standard

Cast Iron:

Gray Iron Threaded Fittings ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings ASME B16.1

Malleable Iron:

Malleable Iron Threaded Fittings ASME B16.3

Steel:

Factory-Made Wrought Buttwelding Fittings ASME B16.9

Buttwelding Ends ASME B16.25

Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel forModerate and High Temperature Service

ASTM A234

Pipe Flanges and Flanged Fittings ASME B16.5

Forged Fittings, Socket-Welding and Threaded

Rubber Gasketed Fittings for Fire Protection Service

ASME B16.11

UL 213

Copper:

Wrought Copper and Copper Alloy Solder Joint Pressure Fittings

Rubber Gasketed Fittings for Fire Protection Service

ASME B16.22

UL 213

Cast Copper Alloy Solder Joint Pressure Fittings ASME B16.18

Cast Bronze Threaded FittingsANSI/ASMEB16.15

Statement of Problem and Substantiation for Public Input

UL 213 is currently not referenced by NFPA 13D-2016. UL 213 is a widely used standard for Rubber Gasketed Fittings for Fire Protection Service for copper, steel, and stainless steel and should be referenced.Adding this standard reference will harmonize the standards used for Rubber Gasketed Sprinkler pipe fittings.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 23-NFPA 13D-2016 [Section No. 5.2.7]

Public Input No. 25-NFPA 13D-2016 [Section No. 5.2.6]

Public Input No. 28-NFPA 13D-2016 [New Section after 2.4]

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

21 of 129 11/3/2016 12:03 PM

State:

Zip:

Submittal Date: Thu Jun 02 08:40:29 EDT 2016

Committee Statement

Resolution: Adding the standard for rubber gasketed fittings to this table would create confusion on whether thefittings are required to be listed or not. Table 5.2.5 is the list of fittings that do not require specificlistings to be used for fire sprinkler service. Although UL 213 indicates the fittings are intended for fireprotection service, it is a performance standard and therefore it isn’t appropriate to include it in theMaterials and Dimensions table for products that aren’t required to be listed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

22 of 129 11/3/2016 12:03 PM

Public Input No. 89-NFPA 13D-2016 [ Section No. 5.2.5 [Excluding any Sub-Sections] ]

Fittings used in sprinkler systems shall be of the materials listed in Table 5.2.5 or shall be in accordancewith 5.2.9.

Table 5.2.5 Fitting Materials and Dimensions

Materials and Dimensions Standard

Cast Iron:

Gray Iron Threaded Fittings ASME B16.4

Gray Iron Pipe Flanges and Flanged Fittings ASME B16.1

Malleable Iron:

Malleable Iron Threaded Fittings ASME B16.3

Steel:

Factory-Made Wrought Buttwelding Fittings ASME B16.9

Buttwelding Ends ASME B16.25

Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel forModerate and High Temperature Service

ASTM A234

Pipe Flanges and Flanged Fittings ASME B16.5

Forged Fittings, Socket-Welding and Threaded ASME B16.11

Copper:

Wrought Copper and Copper Alloy Solder Joint Pressure Fittings ASME B16.22

Cast Copper Alloy Solder Joint Pressure Fittings ASME B16.18

Cast Bronze Threaded FittingsANSI/ASMEB16.15

Copper and Copper Alloy Press-Connect Pressure Fittings ASME B16.51

Statement of Problem and Substantiation for Public Input

Currently NFPA 13D does not currently reference ASME B16.51 This Standard establishes requirements for cast copper alloy, wrought copper, and wrought copper alloy, press-connect pressure fittings for use with hard drawn seamless copper water tube conforming to ASTM B88 for piping systems conveying water. The press-connect system (tube, fitting, and joint) conforming to this Standard is for use at a maximum pressure of 1 380 kPa (200 psi) over the temperature range from 0°C to 93°C (32°F to 200°F). This Standard provides requirements for fittings suitable for press-connect joining and covers the following:(a) size designations(b) pressure–temperature ratings(c) terminology(d) dimensions and tolerances(e) materials(f) design qualification(g) required installation instructions(h) markings By adding this standard, this will direct users to the correct design and material dimensions for copper press-connect fittings.

Submitter Information Verification

Submitter Full Name: Mark Fasel

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

23 of 129 11/3/2016 12:03 PM

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:56:04 EDT 2016

Committee Statement

Resolution: Adding this ASME standard to this table would create confusion on whether the fittings are required tobe listed or not.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

24 of 129 11/3/2016 12:03 PM

Public Input No. 25-NFPA 13D-2016 [ Section No. 5.2.6 ]

5.2.6

Joints for the connection of copper tube shall be brazed press-connect or brazed on dry pipe andpreaction systems.

Statement of Problem and Substantiation for Public Input

The current language implies that only brazed fittings are to be used in dry pipe and pre-action systems. Copper Press Connect fittings listed to UL 213 Rubber Gasketed Fittings for Fire Protection Service are listed for use in dry and pre-action systems. This modification to the section will remove confusion in this section that only brazed fittings are suitable for these applications.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 22-NFPA 13D-2016 [Section No. 5.2.5 [Excluding anySub-Sections]]

StandardReference

Public Input No. 32-NFPA 13D-2016 [New Section after 3.3.6]

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 09:56:51 EDT 2016

Committee Statement

Resolution: The substantiation for PI #25 states that Section 5.2.6 implies that only brazed fittings are to be usedon copper tube in dry and preaction systems. When making connections to copper tube in thesetypes of systems using fittings that are not specifically listed they must be brazed. Section 5.2.9allows the use of specifically listed products so Copper Press Connect fittings (and any other type offittings/connections) are permitted to be used as long as they are specifically listed for that use.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

25 of 129 11/3/2016 12:03 PM

Public Input No. 23-NFPA 13D-2016 [ Section No. 5.2.7 ]

5.2.7

Joints for the connection of copper tube for wet pipe systems and antifreeze systems shall be solder joints,press-connect or be brazed.

Statement of Problem and Substantiation for Public Input

Currently only soldered or brazed joints are allowed for joining copper per this section

The addition of press-connect will eliminate the confusion for allowable copper pipe joining as press-connect fittings are the most widely used joints outside of brazed or soldered joints. Section 5.2.9 allows other types of fittings to be used where listed for sprinkler systems but there is a need to identify press-connect fittings within the body of the code as their use is now very familiar with building officials, designers and installers and it will help to clarify terminology when referring to these fittings as Press-Connect and not Propress or Sharkbite names which are commonly used to describe Press-Connect and Push Fit style fittings. By adding this terminology it will eliminate confusion of the name of the fitting type.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 22-NFPA 13D-2016 [Section No.5.2.5 [Excluding any Sub-Sections]]

Proposed addition of UL 213 for Rubber GasketedFittings for Fire Protection Service

Public Input No. 32-NFPA 13D-2016 [New Sectionafter 3.3.6]

Submitter Information Verification

Submitter Full Name: Mark Fasel

Organization: Viega Llc

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 02 09:34:44 EDT 2016

Committee Statement

Resolution: Similar to the statement for PI #25, the substantiation for PI #23 states that Section 5.2.7 implies thatonly brazed or solder joints are to be used on wet pipe or antifreeze systems. When makingconnections to copper tube in these types of systems using fittings that are not specifically listed theyare allowed to be brazed or soldered. Section 5.2.9 allows the use of specifically listed products soCopper Press Connect fittings (and any other type of fittings/connections) are permitted to be used aslong as they are specifically listed for that use.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

26 of 129 11/3/2016 12:03 PM

Public Input No. 64-NFPA 13D-2016 [ Section No. 5.3 ]

5.3* Underground Pipe and Fittings .

Any type of pipe or tube acceptable under the applicable plumbing code for underground supply pipe shallbe acceptable as an underground supply for these portions of a fire sprinkler system when .

(1) When installed between the point of connection and the water supply source.

(2)* When installed between a remote system riser and the dwelling or home .

Statement of Problem and Substantiation for Public Input

In the scenario where the water supply source and the riser assembly is not in the dwelling unit, underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMA uses this arrangement when providing sprinkler systems for many of their manufactured housing units. This arrangement could also be used when retrofitting an existing dwelling or home. The added text makes it clear that underground pipe and fittings do not have to be listed. However, in accordance with section 5.3 the underground pipe and fittings must comply with the applicable plumbing code for the dwelling or home.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 63-NFPA 13D-2016 [Section No. 5.1.2.1]

Public Input No. 65-NFPA 13D-2016 [New Section after A.5.3]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 13:37:51 EDT 2016

Committee Statement

Resolution: FR-46-NFPA 13D-2016

Statement: In the scenario where the water supply source and the riser assembly is not in the dwelling unit,underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMAuses this arrangement when providing sprinkler systems for many of their manufactured housingunits. This arrangement could also be used when retrofitting an existing dwelling or home. The addedtext makes it clear that underground pipe and fittings do not have to be listed. However, inaccordance with section 5.3 the underground pipe and fittings must comply with the applicableplumbing code for the dwelling or home.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

27 of 129 11/3/2016 12:03 PM

Public Input No. 35-NFPA 13D-2016 [ Section No. 6.1.1 ]

6.1.1

Every automatic sprinkler system shall have at least one automatic water supply in accordance with 6 .2.

Statement of Problem and Substantiation for Public Input

The term “automatic water supply” is not defined. This revision points the reader in the direction of what the provision is intending.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 16 17:23:53 EDT 2016

Committee Statement

Resolution: The committee does not want to limit the types of automatic water supplies as referenced in 6.2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

28 of 129 11/3/2016 12:03 PM

Public Input No. 18-NFPA 13D-2016 [ Section No. 6.1.3 ]

6.1.3

Where stored water is used as the sole source of supply, the minimum quantity shall be permitted to equalthe two sprinkler highest calculated water demand rate times 7 minutes where dwelling units meet thefollowing criteria:

(1) One story in height

(2) Less than 2000 ft2 (186 m2) in area

Statement of Problem and Substantiation for Public Input

It is not uncommon for designers to design single-sprinkler compartments to a much higher spacing than open areas requiring multiple sprinklers. By doing this, bedrooms and other similar sized rooms can be protected with a single sprinkler. It is not uncommon for the single sprinkler compartments to be designed at 20'x20' spacing, with a 20 gpm flow, and the multiple sprinkler compartments to be designed to 12'x12' spacing with a 16 gpm flow for a two-sprinkler calculation. In such a scenario, the two sprinkler water demand rate is not the highest volume, and therefore, not the highest water supply demand.

Submitter Information Verification

Submitter Full Name: Ivan Humberson

Organization: City Of Gaithersburg, Md.

Street Address:

City:

State:

Zip:

Submittal Date: Thu Apr 28 16:07:45 EDT 2016

Committee Statement

Resolution: FR-11-NFPA 13D-2016 Agree with submitter. First draft revision created.

Statement: It is not uncommon for designers to design single-sprinkler compartments to a much higher spacingthan open areas requiring multiple sprinklers. By doing this, bedrooms and other similar sized roomscan be protected with a single sprinkler. It is not uncommon for the single sprinkler compartments tobe designed at 20'x20' spacing, with a 20 gpm flow, and the multiple sprinkler compartments to bedesigned to 12'x12' spacing with a 16 gpm flow for a two-sprinkler calculation. In such a scenario, thetwo sprinkler water demand rate is not the highest volume, and therefore, not the highest watersupply demand.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

29 of 129 11/3/2016 12:03 PM

Public Input No. 40-NFPA 13D-2016 [ New Section after 6.1.4 ]

6.1.5

The stored water supply requirement of 6.1.2 or 6.1.3 shall be permitted to be a combination of the water inthe storage tank and the refill rate when the refilling method is automatic.

Statement of Problem and Substantiation for Public Input

Currently 6.1.4 specifically indicates water from a well. If using a storage tank with automatic refill, then the refill rate should be allowed to be calculated when determining the size of the holding tank.

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 21 16:18:00 EDT 2016

Committee Statement

Resolution: FR-6-NFPA 13D-2016

Statement: Currently 6.1.4 specifically indicates water from a well. If using a storage tank with automatic refill,then the refill rate should be allowed to be calculated when determining the size of the holding tank.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

30 of 129 11/3/2016 12:03 PM

Public Input No. 54-NFPA 13D-2016 [ Section No. 6.2 [Excluding any Sub-Sections] ]

The following water supply sources shall be considered to be acceptable by this standard:

(1) A connection to a reliable waterworks system with or without an automatically operated pump

(2) An elevated tank

(3) A pressure tank designed to American Society of Mechanical Engineers (ASME) standards for apressure vessel with a reliable pressure source

(4) A stored water source with an automatically operated pump

(5) A well with a pump of sufficient capacity and pressure to meet the sprinkler system demand

(6) A swimming Pool with a pump dedicated to the sprinkler system

Statement of Problem and Substantiation for Public Input

Essentially this is a stored water source that is capable of supplying the sprinkler system demand for the 10 minute duration

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Fri Jun 24 08:04:24 EDT 2016

Committee Statement

Resolution: A swimming pool is a stored water source already allowed by 6.2 (4) so it isn't necessary to add thatspecific option to this list. However the committee did add annex text to offer this option with anexplanation of some concerns.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

31 of 129 11/3/2016 12:03 PM

Public Input No. 66-NFPA 13D-2016 [ New Section after 6.2.3.2 ]

TITLE OF NEW CONTENT

6.2.3* Where a well pump is the source of supply for both the fire sprinkler system and the domesticwater system sections 6.1.4 and 6.5 shall apply.

Statement of Problem and Substantiation for Public Input

While well pumps are an economical solution for a water supply in rural areas, many home builders aren’t aware of this option. The additional annex text should help bring this option to the forefront, provide additional guidance for volume calulations, and decrease the cost of the residential sprinkler system.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 67-NFPA 13D-2016 [New Section after A.6.2]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 13:45:45 EDT 2016

Committee Statement

Resolution: FR-12-NFPA 13D-2016 An asterisk was added to (4) to include annex text that states that aswimming pool is a stored water source as described in 6.2 (4) as long as there is sufficient water inthe pool to meet the requirements of 6.1.2 or 6.1.3.

Statement: While well pumps are an economical solution for a water supply in rural areas, many home buildersaren’t aware of this option. The additional annex text should help bring this option to the forefront,provide additional guidance for volume calulations, and decrease the cost of the residential sprinklersystem.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

32 of 129 11/3/2016 12:03 PM

Public Input No. 43-NFPA 13D-2016 [ Section No. 6.3.1 ]

6.3.1

A multipurpose piping system shall be installed in accordance with 6.3.2 through 6.5. 3. 4 .

Statement of Problem and Substantiation for Public Input

Section 6.4 and 6.5 are not specific to multipurpose piping systems. This may have been a typo in the 2016 edition.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 21 17:28:44 EDT 2016

Committee Statement

Resolution: FR-13-NFPA 13D-2016 Agree with submitter, FD created.

Statement: Section 6.4 and 6.5 are not specific to multipurpose piping systems. This may have been a typo in the2016 edition.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

33 of 129 11/3/2016 12:03 PM

Public Input No. 61-NFPA 13D-2016 [ Section No. 7.2.6 ]

7.2.6 *

Where a pressure-reducing or pressure-regulating valve is installed on a stand alone system, a pressuregauge and a a test connection with a K-factor at least as large as the smallest sprinkler K-factor on thesystem shall be installed downstream of the device.

Statement of Problem and Substantiation for Public Input

Relocate the gauge requirement to section 7.3

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 11:40:51 EDT 2016

Committee Statement

Resolution: FR-14-NFPA 13D-2016 Agree with submitter

Statement: Relocate the gauge requirement to section 7.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

34 of 129 11/3/2016 12:03 PM

Public Input No. 90-NFPA 13D-2016 [ New Section after 7.5.6.3 ]

TITLE OF NEW CONTENT

Type your content here ...

(5) Sprinklers in closets containing ventless clothes dryers shall be of the intermediate-temperatureclassification or higher.

Statement of Problem and Substantiation for Public Input

Ventless clothes dryers placed within closets have the potential to raise ceiling temperatures above 100 F (38 C) for sustained periods of time, potentially weakening the operating mechanisms of ordinary temperature rated fire sprinklers over months or years of use, leading to inadvertent operations. While ventless clothes dryers have been used in Europe for many years, they are fairly new to the North American market, where vented clothes dryers have been the norm. More expensive than vented dryers, they generally incorporate condensers in a “two-loop” system to first heat some incoming air, allowing it to absorb moisture from the damp clothes, then continually condense the heated moist air to release the water before recirculating the resulting dry air within the clothes dryer. Unlike vented dryers, where moist heated air is exhausted to the building exterior, these devices capture the water to a drain or pan, while the heat from the condensing cycle is exhausted into the immediate area.

The condensers in combination machines that both wash and dry the clothes are generally water-cooled, such that quantities of cold water are used to condense the moisture evaporated from the clothes during the drying cycle, and pumped away through the drain line. But the standalone dryer units are air-cooled, using the ambient air as a heat sink. While this heat can be dissipated in a large laundry room, it can be expected to raise the temperatures within a laundry closet to levels unacceptable for ordinary temperature rated sprinklers. All standalone ventless dryers in the market are reportedly of this type.

Submitter Information Verification

Submitter Full Name: Russell Fleming

Organization: International Fire Sprinkler Assn. / NFSA

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 15:56:42 EDT 2016

Committee Statement

Resolution: Made change in FR 17.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

35 of 129 11/3/2016 12:03 PM

Public Input No. 79-NFPA 13D-2016 [ Section No. 7.5.6.3 ]

7.5.6.3*

The following practices shall be observed when installing residential sprinklers unless higher expectedambient temperatures require a higher temperature rating:

(1) Sprinklers under glass or plastic skylights exposed to direct rays of the sun shall be of intermediatetemperature classification.

(2) Sprinklers in an unventilated concealed space under an uninsulated roof or in an unventilated atticshall be of intermediate temperature classification.

(3) Sprinklers installed near specific heat sources that are identified in Table 7.5.6.3 shall be of thetemperature rating indicated in Table 7.5.6.3 unless sprinklers are listed for positioning closer to theheat source.

(4) Sprinklers installed in saunas and steam rooms where the maximum ambient ceiling temperatures arebetween 151°F and 225°F (66°C to 107°C) shall be high temperature–rated spray sprinklers.

Table 7.5.6.3 Minimum Distances for Ordinary and Intermediate Temperature Residential Sprinklers *

From Edge

of Source to Ordinary

Temperature Sprinkler

From Edge

of Source to Intermediate

Temperature Sprinkler

Heat Source in. mm in. mm

Side of open or recessed fireplace 36 900 12 300

Front of recessed fireplace 60 1500 36 900

Coal- or wood-burning stove 42 1050 12 300

Kitchen range 18 450 9 229

Wall oven 18 450 9 229

Hot air flues 18 450 9 229

Uninsulated heat ducts 18 450 9 229

Uninsulated hot water pipes 12 300 6 150

Side of ceiling- or wall-mounted hot air diffusers 24 600 12 300

Front of wall-mounted hot air diffusers 36 900 18 450

Hot water heater or furnace 6 150 3 76

Light fixture

 0 W–250 W 6 150 3 76

 250 W–499 W 12 300 6 150

Additional Proposed Changes

File Name Description Approved

Fireplace2.pdf Guidance for spacing around fireplaces

Statement of Problem and Substantiation for Public Input

The language provided in the table provides ambiguous information about spacing sprinklers with regard to fireplaces. These diagrams provide additional clarification. Alternatively, the Annex comment could be attached to 7.5.6.3(3).

Related Public Inputs for This Document

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

36 of 129 11/3/2016 12:03 PM

Related Input Relationship

Public Input No. 80-NFPA 13D-2016 [New Section after A.7.5.6.3]

Submitter Information Verification

Submitter Full Name: Robert Upson

Organization: National Fire Sprinkler Association

Affilliation: NFSA Engineering and Standards Committee

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 10:40:24 EDT 2016

Committee Statement

Resolution: FR-17-NFPA 13D-2016 Agree with submitter.

Statement: The language provided in the table provides ambiguous information about spacing sprinklers withregard to fireplaces. These diagrams provide additional clarification. Alternatively, the Annexcomment could be attached to 7.5.6.3(3).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

37 of 129 11/3/2016 12:03 PM

Public Input No. 21-NFPA 13D-2016 [ New Section after 8.1.1.2 ]

8.1.1.3 Where a physical barrier exists between the sprinklers that prevents each sprinkler fromdirectly spraying on the other, there shall be no minimum distance between sprinklers.

Statement of Problem and Substantiation for Public Input

Similar to the baffle rules in NFPA 13, this eliminates the need to worry about a minimum distance if there is some physical barrier between the sprinklers. This might be helpful in some room configurations where sprinklers need to be installed within 8 ft of each other.

Submitter Information Verification

Submitter Full Name: Kenneth Isman

Organization: University of Maryland

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 26 12:59:07 EDT 2016

Committee Statement

Resolution: FR-21-NFPA 13D-2016

Statement: Similar to the baffle rules in NFPA 13, this eliminates the need to worry about a minimum distance ifthere is some physical barrier between the sprinklers. This might be helpful in some roomconfigurations where sprinklers need to be installed within 8 ft of each other.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

38 of 129 11/3/2016 12:03 PM

Public Input No. 84-NFPA 13D-2016 [ Section No. 8.1.3.1.2 ]

8.1.3.1.2*

Where construction features or other special conditions exist that are outside the scope of sprinkler listings,listed sprinklers shall be permitted to be installed beyond their listing limitations, provided technicaldocumentation has been provided demonstrating equivalency as approved by the authority havingjurisdiction .

Statement of Problem and Substantiation for Public Input

The purpose of this PI is to require that an approved report be provided prior to installing fire sprinklers outside of their listing. The base code allows for the installation of fire sprinklers outside of their listing, but does not provide guidance on the limitations of this provision. Requiring the report will provide guidance on acceptable methods of installation, even if outside of the listing of the fire sprinkler.

Submitter Information Verification

Submitter Full Name: Lynn Nielson

Organization: City Of Henderson

Affilliation: Self

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:02:03 EDT 2016

Committee Statement

Resolution: Sufficient guidance is already provided in the Annex

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

39 of 129 11/3/2016 12:03 PM

Public Input No. 51-NFPA 13D-2016 [ New Section after 8.2.1.1 ]

TITLE OF NEW CONTENT

Type your content here ...

8.2.1.1.1 The requirements of 8.2.1.1 shall not apply for residential occupancies with ceilings ofnoncombustible or limited-combustible construction where either X.X.X.X (A) or X.X.X.X (B) applies.

(A) Where a vertical change in ceiling elevation within the area of coverage of the sprinkler creates adistance of more than 12 in. (300 mm) between the upper ceiling and the sprinkler deflector, a vertical planeextending down from the ceiling at the change in elevation shall be considered a wall for the purpose ofsprinkler spacing as shown in Figure X.X.X.X (A).

(B) Where the distance between the upper ceiling and the sprinkler deflector is less than or equal to 12 in.(300 mm), the sprinklers shall be permitted to be spaced as though the ceiling was flat, provided theobstruction rules are observed as shown in Figure X.X.X.X (B).

Additional Proposed Changes

File Name Description Approved

vertical_change.jpg

Statement of Problem and Substantiation for Public Input

The proposed chance provides guidance on how to position residential pendent sprinklers under ceilings with varying ceiling planes.

Submitter Information Verification

Submitter Full Name: Mark Fessenden

Organization: Tyco Fire Protection Products

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 16:07:46 EDT 2016

Committee Statement

Resolution: TG finds this is not addressed in other 13 standards, the problem is addressed by current obstructionrules. More demonstration of need should be shown.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

40 of 129 11/3/2016 12:03 PM

Public Input No. 52-NFPA 13D-2016 [ New Section after 8.2.1.1 ]

TITLE OF NEW CONTENT

Type your content here ...

The requirements of 8.2.1.1 shall not apply for residential pendent sprinklers installed as show in FigureX.X.X.X (A) or Figure X.X.X.X (B).

Additional Proposed Changes

File Name Description Approved

Beam_Figures.jpg

Statement of Problem and Substantiation for Public Input

10.2.1(2) or 10.2.1(4) describes how to calculate sprinklers under a beamed ceiling, but no similar criteria exists telling how to install those sprinklers. The proposed chance provides guidance on how to position residential pendent sprinklers under beamed ceilings.

Submitter Information Verification

Submitter Full Name: Mark Fessenden

Organization: Tyco Fire Protection Products

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 16:41:14 EDT 2016

Committee Statement

Resolution: See FR to 8.2.1.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

41 of 129 11/3/2016 12:03 PM

Public Input No. 60-NFPA 13D-2016 [ New Section after 8.2.1.1 ]

8.2.1.2

Pendent and upright sprinklers installed in accordance with 10.2.1 shall be permitted to be installed within 3inches below a beam having a depth no greater than 14 in.

Statement of Problem and Substantiation for Public Input

Both NFPA 13D and NFPA 13R allow for installation of sprinklers below beamed ceilings in the discharge criteria, however, as the listing for installation below beams up to 14 inches has been removed from their certification for this application in response to the FPRF research on this topic in 2011, the proper installation of the sprinklers below the beamed ceilings needs to be addressed in the installation chapter of NFPA 13R and 13D. These proposals address the deflector distance below the beams.

Submitter Information Verification

Submitter Full Name: Louis Guerrazzi

Organization: National Fire Sprinkler Association

Affilliation: UL/FM/NFSA Standards Review Committee

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 11:01:52 EDT 2016

Committee Statement

Resolution: See FR to 8.2.1.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

42 of 129 11/3/2016 12:03 PM

Public Input No. 70-NFPA 13D-2016 [ New Section after 8.2.1.2 ]

Add new section in NFPA 13 D, to allow the positioning of sprinklers within a compartment whichis described by section 10.2 in the Number of Design Sprinklers section.

8.2.1.3 Residential Pendent sprinklers shall be permitted to be installed under or adjacent to beams inaccordance with one of the following installation criteria:

a.) Pendent, recesses pendent and concealed sprinklers shall be permitted to be installeddirectly under a beam with a maximum depth of 14” without regard to the ceiling to deflectordistance.

b.) Pendent sprinklers, including flush type pendent sprinklers, shall be permitted to beinstalled adjacent to beams when the vertical centerline of the sprinkler is no greater than2-inches from the edge of the beam and the deflector or heat collector distance below the beamis installed in accordance with the manufacturer’s published documentation.

Statement of Problem and Substantiation for Public Input

The recent elimination of the specific UL test protocol and criteria for sloped ceiling configurations has caused confusion as to the type and position of sprinklers allowed certain configurations described in the Number of Design Sprinklers section. Current guidelines, which are limited in detail and are open to interpretation, clarification on the positioning of sprinklers to take advantage of section 10.2 is required as the standard currently leaves much open to interpretation.

Submitter Information Verification

Submitter Full Name: John Desrosier

Organization: Tyco Fire Pro

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 16:08:47 EDT 2016

Committee Statement

Resolution: See FR to 8.2.1.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

43 of 129 11/3/2016 12:03 PM

Public Input No. 69-NFPA 13D-2016 [ Section No. 8.2.2.2 ]

8.2.2.2

Sidewall sprinklers that have been listed with specific positioning criteria deflector to ceiling distances shallbe installed in accordance with their listing.

Also Add Section

8.2.2.4 Residential sidewall shall be permitted to be installed at the peak of the ceiling spraying down theslope, or along the wall spraying across the slope as long as the spacing is in accordance with themanufacturer’s design guidelines.

Statement of Problem and Substantiation for Public Input

Clarify the intent of section 8.2.2.2 and add new section in NFPA 13 D, to allow the positioning of sprinklers within a compartment which is described by section 10.2 in the Number of Design Sprinklers section.The recent elimination of the specific UL test protocol and criteria for sloped ceiling configurations has caused confusion as to the type and position of sprinklers allowed certain configurations described in the Number of Design Sprinklers section. Current guidelines, which are limited in detail and are open to interpretation, clarification on the positioning of sprinklers to take advantage of section 10.2 is required as the standard currently leaves much open to interpretation.

Submitter Information Verification

Submitter Full Name: John Desrosier

Organization: Tyco Fire Pro

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 16:04:13 EDT 2016

Committee Statement

Resolution: Note that the research only evaluated at the peak and not along the slope. May have to increaseflows or require two sprinklers to operate.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

44 of 129 11/3/2016 12:03 PM

Public Input No. 72-NFPA 13D-2016 [ Section No. 8.2.5.3.3 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

45 of 129 11/3/2016 12:03 PM

8.2.5.3.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

46 of 129 11/3/2016 12:03 PM

Sprinklers shall be positioned with respect to an obstruction against a wall in accordance with Figure8.2.5.3.3(a) or Figure 8.2.5.3.3(b) .

Figure 8.2.5.3.3(a) Positioning of Sprinkler to Avoid Obstruction Against Walls (Residential Uprightand Pendent Spray Sprinklers).

Figure 8.2.5.3.3(b) Positioning of Sprinkler to Avoid Obstruction Against Walls (ResidentialUpright and Pendent Spray Sprinklers).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

47 of 129 11/3/2016 12:03 PM

Additional Proposed Changes

File Name Description Approved

Revise_Figure_8.2.5.3.3_b_.jpg New Method of Measuring for figure 2

Revise_Figure_8.2.5.3.3_b_.pdf Description of revision

Statement of Problem and Substantiation for Public Input

Revise Figure 8.2.5.3.3 (b) (FIGURE 1) so that the ‘B” dimension is measured from the outmost corner of an obstruction to a point perpendicular on the ceiling. (FIGURE 2)Reasoning:The point of the allowance is to find a distance far enough away from an obstruction to clear the bottom of the obstruction and provide fire protection below it. On flat ceilings the ‘B’ distance is static. In sloped applications the ‘B’ distance changes each time you arrive at a new ‘A’ distance.The equation does not work unless you already have the sprinkler in position. In Figure 2, the B distance is static and the designer or installer can arrive at a distance without first needing to know where the sprinkler is.

Submitter Information Verification

Submitter Full Name: Dan Hubbard

Organization: Uponor Inc

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 17:01:53 EDT 2016

Committee Statement

Resolution: Needs data to substantiate and indicate this does not create more obstruction issues. This will allow

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

48 of 129 11/3/2016 12:03 PM

sprinkler to be closer to obstructions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

49 of 129 11/3/2016 12:03 PM

Public Input No. 12-NFPA 13D-2016 [ Section No. 8.2.5.4.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

50 of 129 11/3/2016 12:03 PM

8.2.5.4.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

51 of 129 11/3/2016 12:03 PM

Sprinklers shall be positioned with respect to continuous obstructions in accordance with Table8.2.5.4.2(a), Figure 8.2.5.4.2(a), Table 8.2.5.4.2(b), Figure 8.2.5.4.2(b, and Figure 8.2.5.4.2(b c )) .

Table 8.2.5.4.2(a) Positioning of Sprinklers to Avoid Obstructions (Residential Sidewall Sprinklers)

Distance from Sidewall

Sprinkler to Side of

Obstruction ( A )

Maximum Allowable Distance of Deflector Above Bottom ofObstruction (in.) ( B )

Less than 8 ft (2400 mm) Not allowed

8 ft (2400 mm) to less than 10 ft(3000 mm)

1 (25 mm)

10 ft (3000 mm) to less than 11 ft(3300 mm)

2 (50 mm)

11 ft (3300 mm) to less than 12 ft(3600 mm)

3 (75 mm)

12 ft (3600 mm) to less than 13 ft(3900 mm)

4 (100 mm)

13 ft (3900 mm) to less than 14 ft(4200 mm)

6 (150 mm)

14 ft (4200 mm) to less than 15 ft(4500 mm)

7 (175 mm)

15 ft (4500 mm) to less than 16 ft(4800 mm)

9 (225 mm)

16 ft (4800 mm) to less than 17 ft(5100 mm)

11 (275 mm)

17 ft (5100 mm) or greater 14 (350 mm)

Note: For A and B, refer to Figure 8.2.5.4.2(a).

Table 8.2.5.4.2(b) Positioning of Sprinklers to Avoid Obstructions Along Wall (Residential SidewallSprinklers)

Distance from Sidewall Sprinkler to Side of

Obstruction ( A )

Maximum Allowable Distance of Deflector

Above Bottom of

Obstruction (in.) ( B )

Less than 1 ft 6 in. (450 mm) 0

1 ft 6 in. (450 mm) to less than 3 ft (900 mm) 1 (25 mm)

3 ft (900 mm) to less than 4 ft (1200 mm) 3 (75 mm)

4 ft (1200 mm) to less than 4 ft 6 in. (1350 mm) 5 (125 mm)

4 ft 6 in. (1350 mm) to less than 6 ft (1850 mm) 7 (175 mm)

6 ft (1850 mm) to less than 6 ft 6 in. (1950 mm) 9 (225 mm)

6 ft 6 in. (1950 mm) to less than 7 ft (2100 mm) 11 (275 mm)

7 ft to (2100 mm) less than 7 ft 6 in. (2250 mm) 14 (350 mm)

Note: For A and B, refer to Figure 8.2.5.4.2(b).

Figure 8.2.5.4.2(a) Positioning of Sprinkler to Avoid Obstruction (Residential Sidewall Sprinklers).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

52 of 129 11/3/2016 12:03 PM

Figure 8.2.5.4.2(b) Positioning of Sprinkler to Avoid Obstruction Along Wall (Residential SidewallSprinklers).

Additional Proposed Changes

File Name Description Approved

NFPA_13D_Fig._8.2.5.4.2_c_.pdf 8.2.5.4.2(c)

Statement of Problem and Substantiation for Public Input

It appears the committee forgot to add this detail to NFPA 13D. It is found in NFPA 13R.

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 23 13:43:42 EST 2016

Committee Statement

Resolution: FR-50-NFPA 13D-2016

Statement: It appears the committee forgot to add this detail to NFPA 13D. It is found in NFPA 13R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

53 of 129 11/3/2016 12:03 PM

Public Input No. 50-NFPA 13D-2016 [ New Section after 8.2.5.6 ]

TITLE OF NEW CONTENT

Type your content here ...   Shadow areas in corridors up to 2   (0.61 m) in depth and up to 9   (2.7 m) in length

behind sidewall sprinklers shall be permi ed as shown in Figure   XXXX (Current 13R: Figure 6.4.6.3.3.2)

Statement of Problem and Substantiation for Public Input

This change aligns the two related sections from 13D & 13R.

Submitter Information Verification

Submitter Full Name: Mark Fessenden

Organization: Tyco Fire Protection Products

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 15:18:42 EDT 2016

Committee Statement

Resolution: FR-33-NFPA 13D-2016

Statement: This change aligns the two related sections from 13D & 13R.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

54 of 129 11/3/2016 12:03 PM

Public Input No. 87-NFPA 13D-2016 [ Section No. 8.2.5.6 ]

8.2.5.6* Shadow Areas.

Shadow areas shall be permitted in the protection area of a an individual sprinkler as long as the

cumulative dry areas do not exceed 15 ft2 (1.4 m2) per sprinkler.

Statement of Problem and Substantiation for Public Input

Shadow area as defined in Section 3.3.9 and use here is intended to apply to the spray pattern of the individual sprinkler.

Submitter Information Verification

Submitter Full Name: Lynn Nielson

Organization: City Of Henderson

Affilliation: Self

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:27:31 EDT 2016

Committee Statement

Resolution: Editorial – doesn’t help

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

55 of 129 11/3/2016 12:03 PM

Public Input No. 20-NFPA 13D-2016 [ New Section after 8.2.7 ]

8.2.7.1

In all compartments that are not larger than 400 ft 3 (11.33 m 3 ), pendent, upright and sidewall residentialsprinklers shall be permitted to be installed at the highest ceiling level without regard to obstructions.

Statement of Problem and Substantiation for Public Input

In the 2016 edition, this section was modified. The allowance to have a sprinkler 18" down was added. However there was a requirement added that it had to be enclosed by walls and a door. There are many small hallways that are technically compartments with openings with adequate lintels that usually have a light in the center and this would allow the light to not be an obstruction. This is not new language as this is how it read in the 2013 edition and prior.

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 26 09:49:52 EDT 2016

Committee Statement

Resolution: See FR 23

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

56 of 129 11/3/2016 12:03 PM

Public Input No. 19-NFPA 13D-2016 [ Section No. 8.2.7 ]

8.2.7 Closets and Small Compartments .

In all closets and compartments that are enclosed by walls and a door and that are smaller than 400 ft3

(11.3 m3), including those housing mechanical equipment, pendent, upright, and sidewall residentialsprinklers shall be permitted to be installed in either of the following situations:

(1) Within 18 in. (460 mm) of the ceiling to avoid obstructions near the ceiling

(2) At the highest ceiling level without regard to obstructions or minimum distances to wall

Statement of Problem and Substantiation for Public Input

This applies to small compartments as well

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Thu May 26 09:49:00 EDT 2016

Committee Statement

Resolution: See FR 23

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

57 of 129 11/3/2016 12:03 PM

Public Input No. 53-NFPA 13D-2016 [ New Section after 8.3.4 ]

8.3.5

Sprinklers shall not be required in an enclosed swimming pool room when provided with a minimum of oneexit door exiting directly to the exterior.

Statement of Problem and Substantiation for Public Input

Enclosed swimming pools generally have a low or no fuel content much less than garages, porches and similar structures including other rooms within the dwelling that are exempt. The majority of the room is water. Limited access to ceiling sprinklers for the purpose of installation and maintenance is difficult. Unique ceiling skylights and or soffiting makes listing requirements difficult to achieve.

Submitter Information Verification

Submitter Full Name: Maurice Pilette

Organization: Mechanical Designs Ltd.

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 20:33:50 EDT 2016

Committee Statement

Resolution: Considered past discussion that these rooms can be converted or pools drained for other use. Ingeneral spaces omitted are not used for living space. This does not meet that. Pools rooms also havefurniture, and storage that maintain the risk and should be protected with sprinklers.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

58 of 129 11/3/2016 12:03 PM

Public Input No. 85-NFPA 13D-2016 [ New Section after 8.3.4 ]

8.3.4.1 Attached garages with any habitable rooms above shall be required to be protected with firesprinklers.

Statement of Problem and Substantiation for Public Input

A fire in a garage without fire sprinklers with habitable rooms above it can undermine the structural integrity of the habitable rooms above and increase the risk of occupants within those rooms not being able to exit the structure safely.

Submitter Information Verification

Submitter Full Name: Lynn Nielson

Organization: City Of Henderson

Affilliation: Self

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:08:18 EDT 2016

Committee Statement

Resolution: Building code requires separation. The passive protection (1 Hour) provides more time than the 10minute limit of the FSS.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

59 of 129 11/3/2016 12:03 PM

Public Input No. 57-NFPA 13D-2016 [ Section No. 8.3.5.1.2 ]

8.3.5.1.2 *

Where fuel-fired equipment is below or on the same level as occupied areas of the dwelling unit, at leastone quick-response intermediate temperature sprinkler shall be installed above the equipment or at the wallseparating the space with the fuel-fired equipment from the occupied space.

Add annex section:

A.8.3.5.1.2. Where a chimney or flue from a fuel-fired equipment passes through a concealed space, it isnot required to locate a sprinkler in this concealed space.

Statement of Problem and Substantiation for Public Input

Some AHJ’s are using this section to require sprinklers in attic adjacent to the chimney for the fuel fired equipment below. This section is intended to apply to the actual fuel-fired equipment and not to the chimney where it passes through the attic. This Annex section will clarify.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 76-NFPA 13D-2016 [New Section after A.8.3.4]

Submitter Information Verification

Submitter Full Name: Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 27 23:13:57 EDT 2016

Committee Statement

Resolution: FR-34-NFPA 13D-2016 This provides good guidance.

Statement: Some AHJ’s are using this section to require sprinklers in attic adjacent to the chimney for the fuelfired equipment below. This section is intended to apply to the actual fuel-fired equipment and not tothe chimney where it passes through the attic. This Annex section will clarify.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

60 of 129 11/3/2016 12:03 PM

Public Input No. 44-NFPA 13D-2016 [ Section No. 8.3.6 ]

8.3.6

Sprinklers shall not be required in covered, unheated projections of the building at entrances/exits as longas the dwelling unit has another means of egress exit .

Statement of Problem and Substantiation for Public Input

The term “egress” can result in the additional cost and complexity of a dry sprinkler being required even though additional exits are available, but may not meet the strict definition of “egress” as defined in the International Residential Code.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 09:19:23 EDT 2016

Committee Statement

Resolution: FR-35-NFPA 13D-2016

Statement: The term “egress” can result in the additional cost and complexity of a dry sprinkler being requiredeven though additional exits are available, but may not meet the strict definition of “egress” as definedin the International Residential Code.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

61 of 129 11/3/2016 12:03 PM

Public Input No. 13-NFPA 13D-2016 [ Section No. 8.3.7 ]

8.3.7

Sprinklers shall not be required for unprotected ceiling pockets that meet the following conditions:

(1) The total volume of all unprotected ceiling pockets in a compartment does not exceed 100 ft3

(2.8 m3).

(2) The entire floor under the unprotected ceiling pocket is protected by the sprinklers at the lower ceilingelevation.

(3)

(4) Skylights not exceeding 32 ft2 (3 m2) shall be permitted to have a plastic cover.

Statement of Problem and Substantiation for Public Input

The charging statement should include the term "unprotected ceiling pocket" as the criteria in 1-3 refer to unprotected ceiling pocket(s).

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 23 13:56:13 EST 2016

Committee Statement

Resolution: Adding the term “unprotected” is redundant and not necessary. The fact that the sprinkler is beingomitted is what makes the pocket unprotected, so saying “unprotected” in the section that states thatthe pocket can be unsprinklered is redundant.

* The interior finish of the unprotected ceiling pocket excluding decorative treatments isnoncombustible or limited-combustible material.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

62 of 129 11/3/2016 12:03 PM

Public Input No. 46-NFPA 13D-2016 [ Section No. 9.2.2.1 [Excluding any Sub-Sections] ]

Except as permitted in 9.2.2.3 2 , antifreeze solutions shall be listed for use in new sprinkler systems.

Statement of Problem and Substantiation for Public Input

It would appear that stating “Except as permitted in 9.2.2.3…” might have been in error as it only refers to the concentration of the antifreeze solutions being limited to the minimum necessary. Instead 9.2.2.2 is referring to limited applications where antifreeze may be considered and only by the permission of the AHJ.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 09:24:46 EDT 2016

Committee Statement

Resolution: FR-36-NFPA 13D-2016

Statement: It would appear that stating “Except as permitted in 9.2.2.3…” might have been in error as it onlyrefers to the concentration of the antifreeze solutions being limited to the minimum necessary. Instead9.2.2.2 is referring to limited applications where antifreeze may be considered and only by thepermission of the AHJ.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

63 of 129 11/3/2016 12:03 PM

Public Input No. 62-NFPA 13D-2016 [ Section No. 9.2.2.3 ]

9.2.2. 3 2.2

The concentration of antifreeze solutions shall be limited to the minimum necessary for the anticipatedminimum temperature.

Statement of Problem and Substantiation for Public Input

Renumber this section and change pointer for using non listed antifreeze

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 11:47:20 EDT 2016

Committee Statement

Resolution: Section has been deleted by FR.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

64 of 129 11/3/2016 12:03 PM

Public Input No. 36-NFPA 13D-2016 [ Section No. 9.3.4 ]

9.3.4 Location and Protection of Dry Pipe and Preaction Valves.

The dry pipe valve, preaction valve, and supply pipe shall be protected against freezing and mechanicalinjury physical damage .

Statement of Problem and Substantiation for Public Input

Sprinkler system components do not get injured; they get damaged. This clarifies the provision.

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPAs Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 16 17:27:51 EDT 2016

Committee Statement

Resolution: FR-26-NFPA 13D-2016

Statement: Sprinkler system components do not get injured; they get damaged. This clarifies the provision.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

65 of 129 11/3/2016 12:03 PM

Public Input No. 11-NFPA 13D-2016 [ New Section after 10.1.1 ]

10.1.2

Sprinkler criteria outside of dwelling unit. Where sprinklers are required outside of the dwelling unit theyshall be designed to provide a minimum discharge density of 0.05 gpm/ft² (2.04 mm/min).

Statement of Problem and Substantiation for Public Input

Section 8.3 indicates the locations that sprinklers can be omitted. Some AHJ's require sprinkler protection be provided in garages and on porches and similar areas outside of dwelling units. Sometimes the use of other than a residential sprinkler is mandated. This will only require that a .05 Gpm/ft² be provided. This is similar to the provision found in NFPA 13R section 7.3.3.1 (3).

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 23 12:48:48 EST 2016

Committee Statement

Resolution: See FR on Section a.8.3.4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

66 of 129 11/3/2016 12:03 PM

Public Input No. 38-NFPA 13D-2016 [ Section No. 10.2.3 ]

10.2.3

For situations not meeting any one of the conditions in 10.2.1, residential sprinklers listed for use inspecific ceiling configurations shall be permitted to be used in accordance with their listing.

Statement of Problem and Substantiation for Public Input

This provides clarification.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 37-NFPA 13D-2016 [Section No. 10.2.4]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 16 17:32:20 EDT 2016

Committee Statement

Resolution: The term “any one” does not have a different meaning than “one”.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

67 of 129 11/3/2016 12:03 PM

Public Input No. 37-NFPA 13D-2016 [ Section No. 10.2.4 ]

10.2.4*

For situations not meeting one of the conditions in 10.2.1 and or 10.2.3, the number of sprinklers in thedesign area shall be determined in consultation with the authority having jurisdiction as appropriate for theconditions.

Statement of Problem and Substantiation for Public Input

It is believed that one of the conditions in either 10.2.1 or 10.2.3 should be the trigger, rather than one of the conditions in both 10.2.1 and 10.2.3.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 38-NFPA 13D-2016 [Section No. 10.2.3]

Submitter Information Verification

Submitter Full Name: Jim Muir

Organization: Building Safety Division, Clark County, Washington

Affilliation: NFPA's Building Code Development Committee (BCDC)

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 16 17:30:12 EDT 2016

Committee Statement

Resolution: The word “and” is appropriate. The only time the AHJ makes up the criteria is when none of theconditions can be met. If you switch to the word “or” as suggested, the AHJ could make up criteriaeven when there are criteria in the standard or a product has a specific listing.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

68 of 129 11/3/2016 12:03 PM

Public Input No. 49-NFPA 13D-2016 [ Section No. 10.4.4 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

69 of 129 11/3/2016 12:03 PM

10.4.4 * General Pipe Sizing Method.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

70 of 129 11/3/2016 12:03 PM

The following is the general pipe sizing method for straight-run systems connected to a city water main of atleast 4 in. (100 mm) in diameter in accordance with 10.4.3(1):

(1) The system flow rate shall be established in accordance with Sections 10.1 and 10.2, and it shall bedetermined that the flow allowed by the water meter meets or exceeds the system demand and thatthe total demand flow does not exceed the maximum flow allowed by the piping system components.

(2) The water pressure in the street shall be determined.

(3) Pipe sizes shall be selected.

(4)

(5)

(6)

(7)

(8) Pressure loss for elevation shall be deducted as follows:

(9) Building height above street (ft) × 0.433 = pressure loss (psi)

(10) Building height above street (m) × 0.098 = pressure loss (bar)

(11)

(12) Pressure loss for piping within the building shall be deducted by multiplying the pressure lossassociated with the pipe material by the total length(s) of pipe in feet (meters).

(13) Pressure loss for valves and fittings shall be deducted as follows:

(14) The valves and fittings from the control valve to the farthest sprinkler shall be counted.

(15) The equivalent length for each valve and fitting as shown in Table 10.4.4(b) , Table 10.4.4(c) ,Table 10.4.4(d),

or

(a) Table 10.4.4(e) or   or as specified by the manufacturer   shall be determined and the valuesadded to obtain the total equivalent length for each pipe size. The friction loss for a flow straightthrough tee or cross shall only be included in calculations performed in accordance with 10.4.9.

(b) The equivalent length for each size shall be multiplied by the pressure loss associated with thepipe material and the values totaled.

(16) In multilevel buildings, the steps in 10.4.4(1) through 10.4.4(8) shall be repeated to size piping foreach floor.

(17) If the remaining pressure is less than the operating pressure established by the testing laboratory forthe sprinkler being used, the sprinkler system shall be redesigned.

(18) If the remaining pressure is higher than required, smaller piping shall be permitted to be used wherejustified by calculations.

(19) The remaining piping shall be sized the same as the piping up to and including the farthest sprinklerunless smaller pipe sizes are justified by calculations.

Table 10.4.4(a) Pressure Losses in psi in Water Meters

Meter Size

(in.)

Flow (gpm) (L/min)

18 or less (68) 23 (87) 26 (98) 31 (117) 39 (148) 52 (197)

5 ⁄ 8 (15 mm) 9 (0.67 bar) 14 (0.97 bar) 18 (1.2 bar) 26 (1.8 bar) 38 (2.6 bar) *

* Pressure loss for a water meter, if any, shall be determined and deducted using one of the following:

Table 10.4.4(a) shall be permitted to be used, even where the sprinkler demand flow exceedsthe meter's rated continuous flow.

Higher pressure losses specified by the manufacturer shall be used in place of those specifiedin Table 10.4.4(a) .

Lower pressure losses shall be permitted to be used where supporting data are provided by themeter manufacturer.

* Pressure losses from the city main to the inside control valve shall be deducted by multiplying thepressure loss associated with the pipe material by the total length(s) of pipe in feet (meters).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

71 of 129 11/3/2016 12:03 PM

Meter Size

(in.)

Flow (gpm) (L/min)

18 or less (68) 23 (87) 26 (98) 31 (117) 39 (148) 52 (197)

3 ⁄ 4 (20 mm) 7 (0.48 bar) 11 (0.76 bar) 14 (1.5 bar) 22 (1.5 bar) 35 (2.4 bar) *

1 (25 mm) 2 (0.14 bar) 3 (0.21 bar) 3 (0.21 bar) 4 (0.28 bar) 6 (0.41 bar) 10 (0.69 bar)

1 1 ⁄ 2 (40 mm) 1 (0.07 bar) 1 (0.07 bar) 2 (0.14 bar) 2 (0.14 bar) 4 (0.28 bar) 7 (0.48 bar)

2 (50 mm) 1 (0.07 bar) 1 (0.07 bar) 1 (0.07 bar) 1 (0.07 bar) 2 (0.14 bar) 3 (0.21 bar)

For SI units, 1 gpm = 3.785 L/min; 1 in. = 25 mm; 1 psi = 0.07 bar.

*Above maximum rated flow of commonly available meters.

Table 10.4.4(b) Equivalent Length in Feet of Fittings and Valves for Schedule 40 Steel Pipe

Diameter

(in.)

45

DegreeElbow

90

DegreeElbow

Long-RadiusElbow

Tee orCross(flow

turned90

degrees)

Tee orCross(flow

straightthrough)

GateValve

AngleValve

GlobeValve

Globe“Y”

PatternValve

CockValve

CheckValve

1 (25mm)

1 (0.3m)

2 (0.6m)

2 (0.6m)

5 (1.5 m) 2 (0.6 m) 012

(3.7m)

28(8.5m)

15 (4.6m)

4 (1.2m)

5 (1.5m)

1 1 ⁄ 4(32 mm)

1 (0.3m)

3 (0.9m)

2 (0.6m)

6 (1.8 m) 2 (0.6 m) 015

(4.6m)

35(10.7m)

18 (5.5m)

5 (1.5m)

7 (2.1m)

1 1 ⁄ 2(40 mm

2 (0.6m)

4 (1.2m)

2 (0.6m)

8 (2.4 m) 3 (0.9 m) 018

(5.5m)

43(13.1m)

22 (6.7m)

6 (1.8m)

9 (2.7m)

2 (50mm)

2 (0.6m)

5 (1.5m)

3 (0.9m)

10 (3 m) 3 (0.9 m)1 (0.3

m)

24(7.3m)

57(17.4m)

28 (8.5m)

7 (2.1m)

11 (3.3m)

For SI units, 1 in. = 25 mm; 1 ft = 0.3 m.

Table 10.4.4(c) Equivalent Length in Feet of Fittings and Valves for Type K Copper Tube

Diameter(in.)

45DegreeElbow

90DegreeElbow

Long-

RadiusElbow

Tee orCross(flow

turned90

degrees)

Tee orCross(flow

straightthrough)

GateValve

AngleValve

GlobeValve

Globe“Y”

PatternValve

CockValve

CheckValve

3 ⁄ 4(20 mm)

01 (0.3

m)0 3 (0.9 m) 1 (0.3 m) 0

7 (2.1m)

14(4.3m)

7 (2.1m)

2 (0.6m)

0

1 (25mm)

1 (0.3m)

2 (0.6m)

2 (0.6m)

6 (1.8 m) 2 (0.6 m) 014

(4.3m)

33 (10m)

18 (5.5m)

5 (1.5m)

6 (1.8m)

1 1 ⁄ 4(32 mm)

1 (0.3m)

3 (0.9m)

2 (0.6m)

5 (1.5 m) 2 (0.6 m) 014

(4.3m)

32(9.8m)

16 (4.9m)

5 (1.5m)

6 (1.8m)

1 1 ⁄ 2(40 mm)

2 (0.6m)

4 (1.2m)

2 (0.6m)

8 (2.4 m) 3 (0.9 m) 018

(5.5m)

43(13.1m)

22 (6.7m)

6 (1.8m)

9 (2.7m)

2 (50mm)

2 (0.6m)

6 (1.8m)

3 (0.9m)

12 (3.7 m) 4 (1.2 m)1 (0.3

m)

28(8.5m)

66(20.1m)

33 (10m)

8 (2.4m)

13 (4m)

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

72 of 129 11/3/2016 12:03 PM

For SI units, 1 in. = 25 mm; 1 ft = 0.3 m.

Table 10.4.4(d) Equivalent Length in Feet of Fittings and Valves for Type L Copper Tube

Diameter(in.)

45DegreeElbow

90DegreeElbow

Long-RadiusElbow

Tee orCross(flow

turned90

degrees)

Tee orCross(flow

straightthrough)

GateValve

AngleValve

GlobeValve

Globe“Y”

PatternValve

CockValve

CheckValve

3 ⁄ 4(20 mm)

02 (0.6

m)0 4 (1.2 m) 1 (0.3 m) 0

8 (2.4m)

18(5.5m)

10 (3m)

3 (0.9m)

0

1 (25mm)

1 (0.3m)

3 (0.9m)

3 (0.9m)

7 (2.1 m) 2 (0.6 m) 016

(4.9m)

38(11.6m)

20 (6.1m)

5 (2.1m)

7 (2.1m)

1 1 ⁄ 4(32 mm)

1 (0.3m)

3 (0.9m)

2 (0.6m)

6 (1.8 m) 2 (0.6 m) 015

(4.6m)

35(10.7m)

18 (5.5m)

5 (1.5m)

7 (2.1m)

1 1 ⁄ 2(40 mm)

2 (0.6m)

4 (1.2m)

2 (0.6m)

9 (2.7 m) 3 (0.9 m) 020

(6.1m)

47(14.3m)

24 (7.3m)

7 (2.1m)

10 (3m)

2 (50mm)

2 (0.6m)

6 (1.8m)

4 (1.2m)

12 (3.7 m) 4 (1.2 m)1 (0.3

m)

30(9.1m)

71(21.6m)

35(10.7m)

9 (2.7m)

14 (4.3m)

For SI units, 1 in. = 25 mm; 1 ft = 0.3 m.

Table 10.4.4(e) Equivalent Length in Feet of Fittings and Valves for Type M Copper Tube

Diameter(in.)

45DegreeElbow

90DegreeElbow

Long-RadiusElbow

Tee orCross(flow

turned90

degrees)

Tee orCross(flow

straightthrough)

GateValve

AngleValve

GlobeValve

Globe“Y”

PatternValve

CockValve

CheckValve

3 ⁄ 4(20 mm)

02 (0.6

m)0 4 (1.2 m) 1 (0.3 m 0

10 (3m)

21(6.4m)

11 (3.3m)

3 (0.9m)

0

1 (25mm)

2 (0.6m)

3 (0.9m)

3 (0.9m)

8 (2.4 m) 3 (0.9 m) 019

(5.8m)

43(13.1m)

23 (7m)

6 (1.8m)

8 (2.1m)

1 1 ⁄ 4(32 mm)

1 (0.3m)

3 (0.9m)

2 (0.6m)

7 (2.1 m) 2 (0.6 m) 016

(4.9m)

38(11.5m)

20 (6.1m)

5 (1.5m)

8 (2.4m)

1 1 ⁄ 2(40 mm)

2 (0.6m)

5 (1.5m)

2 (0.6m)

9 (2.7 m) 3 (0.9 m) 021

(6.4m)

50(15.2m)

26 (7.9m)

7 (2.1m)

11 (3.3m)

2 (50mm)

3 (0.9m)

7 (2.1m)

4 (1.2m)

13 (4 m) 5 (1.5 m)1 (0.3

m)

32(9.8m)

75(22.9m)

37 (11.3m)

9 (2.7m)

14 (4.3m)

For SI units, 1 in. = 25 mm; 1 ft = 0.3048 m.

Statement of Problem and Substantiation for Public Input

Revision clarifies that the friction loss for a flow straight through tee or cross is only required when performing calculations using the Prescriptive Pipe Sizing Method and is not required when hydraulic calculations are performed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

73 of 129 11/3/2016 12:03 PM

Submitter Information Verification

Submitter Full Name: Mark Fessenden

Organization: Tyco Fire Protection Products

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 14:57:57 EDT 2016

Committee Statement

Resolution: FR-38-NFPA 13D-2016 We don’t have technical information that flow through T’s and cross shouldnot be included. Calculating the friction loss through a tee or cross is applicable to sections 10.4.4 aswell as 10.4.9 unless otherwise specifically listed.

Statement: Revision clarifies that the friction loss for a flow straight through tee or cross is only required whenperforming calculations using the Prescriptive Pipe Sizing Method and is not required when hydrauliccalculations are performed.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

74 of 129 11/3/2016 12:03 PM

Public Input No. 15-NFPA 13D-2016 [ New Section after 10.4.6 ]

10.4.6.1

Where the water supply is a public or private water main 4 in (100 mm) nominal in size or larger, only thestatic pressure measured at the main shall be required for performing hydraulic calculations.

Statement of Problem and Substantiation for Public Input

For a 2 sprinkler design, the demand point on the water supply curve with a 4" or larger main will generally be very close to the static. Using the static pressure only for grid calculations should be allowed.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 16-NFPA 13D-2016 [New Section after 10.4.7]

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Wed Mar 23 15:56:10 EDT 2016

Committee Statement

Resolution: FR-28-NFPA 13D-2016

Statement: For a 2 sprinkler design, the demand point on the water supply curve with a 4" or larger main willgenerally be very close to the static. Using the static pressure only for grid calculations should beallowed.

For a two sprinkler design, the demand point on the water supply curve with a 4" or larger main willhave such a low flow relative to the flow available from the main that the available residual pressurewill be so close to the static pressure that it will be indistinguishable. Using just the static pressure forthese calculations is consistent with the other hydraulic calculation procedures permitted by NFPA13D and should be allowed when performing calculations using the other procedures from NFPA 13.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

75 of 129 11/3/2016 12:03 PM

Public Input No. 16-NFPA 13D-2016 [ New Section after 10.4.7 ]

10.4.7.1

Where the water supply is a public or private water main 4 in (100 mm) nominal in size or larger, only thestatic pressure measured at the main shall be required for performing hydraulic calculations.

Statement of Problem and Substantiation for Public Input

For a 2 sprinkler design, the demand point on the water supply curve with a 4" or larger main will generally be very close to the static. Using the static pressure only for loop calculations should be allowed.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 15-NFPA 13D-2016 [New Section after 10.4.6]

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Wed Mar 23 16:06:44 EDT 2016

Committee Statement

Resolution: FR-29-NFPA 13D-2016

Statement: For a two sprinkler design, the demand point on the water supply curve with a 4" or larger main willhave such a low flow relative to the flow available from the main that the available residual pressurewill be so close to the static pressure that it will be indistinguishable. Using just the static pressure forthese calculations is consistent with the other hydraulic calculation procedures permitted by NFPA13D and should be allowed when performing calculations using the other procedures from NFPA 13.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

76 of 129 11/3/2016 12:03 PM

Public Input No. 47-NFPA 13D-2016 [ Section No. 10.4.9.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

77 of 129 11/3/2016 12:03 PM

10.4.9.2 Calculation Procedure.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

78 of 129 11/3/2016 12:03 PM

Determination of the required size for water distribution piping shall be in accordance with the followingprocedure:

(1) Step 1 — Determine Psup . Obtain the static supply pressure that will be available from the water

main from the water purveyor or from a private source, such as a tank system, a private well system, ora combination of these. For a private source, the available water supply pressure shall be based on theminimum pressure control setting for the pump.

(2) Step 2 — Determine PLsvc . Use Table 10.4.9.2(a) to determine the pressure loss in the water service

pipe based on the selected size of the water service.

(3) Step 3 — Determine PLm . Use Table 10.4.4(a) to determine the pressure loss from the water meter

based on the selected water meter size. Where the actual water meter pressure loss is known, PLmshall be the actual loss.

(4) Step 4 — Determine PLd . Determine the pressure loss from devices, other than the water meter,

installed in the piping system supplying sprinklers, such as pressure-reducing valves, backflowpreventers, water softeners, or water filters, taking into account the following:

(5) Device pressure losses shall be based on the device manufacturer's specifications.

(6) The flow rate used to determine pressure loss shall be the rate from Section 10.1 , except that5 gpm (20 L/min) shall be added where the device is installed in a water service pipe that suppliesmore than one dwelling.

(7) As an alternative to deducting pressure loss for a device, an automatic bypass valve shall beinstalled to divert flow around the device when a sprinkler activates.

(8) Step 5 — Determine PLe . Use Table 10.4.9.2(b) to determine the pressure loss associated with

changes in elevation. The elevation used in applying the table shall be the difference between theelevation where the water source pressure was measured and the elevation of the highest sprinkler.

(9) Step 6 — Determine PLsp . Determine the maximum pressure required by any individual sprinkler

based on the following:

(10) The area of coverage

(11) The ceiling configuration

(12) The temperature rating

(13) Any additional conditions specified by the sprinkler manufacturer

(14) Step 7 — Calculate PLt . Using the equation in 10.4.9.1, calculate the pressure available to offset

friction loss in water distribution piping between the service valve and the sprinklers.

(15) Step 8 — Determine the maximum allowable pipe length. Use Table 10.4.9.2(c) through Table10.4.9.2(h) to select a material and size for water distribution piping. The piping material and size shallbe acceptable if the developed length of pipe between the service valve and the most remote sprinklerdoes not exceed the maximum allowable length specified by the applicable table. Interpolation of Ptbetween the tabular values shall be permitted.

Table 10.4.9.2(a) Water Service Pressure Loss (PLsvc)

FlowRate*(gpm)

3⁄4 in. Water ServicePressure Loss (psi)

1 in. Water Service PressureLoss

(psi)

1 1⁄4 in. Water ServicePressure Loss (psi)

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

8 5.1 8.7 11.8 17.4 1.5 2.5 3.4 5.1 0.6 1.0 1.3 1.9

10 7.7 13.1 17.8 26.3 2.3 3.8 5.2 7.7 0.8 1.4 2.0 2.9

12 10.8 18.4 24.9 NP 3.2 5.4 7.3 10.7 1.2 2.0 2.7 4.0

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

79 of 129 11/3/2016 12:03 PM

FlowRate*(gpm)

3⁄4 in. Water ServicePressure Loss (psi)

1 in. Water Service PressureLoss

(psi)

1 1⁄4 in. Water ServicePressure Loss (psi)

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

40 ftor

less

41 ftto 75

ft

76 ftto 100

ft

101 ftto 150

ft

14 14.4 24.5 NP NP 4.2 7.1 9.6 14.3 1.6 2.7 3.6 5.4

16 18.4 NP NP NP 5.4 9.1 12.4 18.3 2.0 3.4 4.7 6.9

18 22.9 NP NP NP 6.7 11.4 15.4 22.7 2.5 4.3 5.8 8.6

20 27.8 NP NP NP 8.1 13.8 18.7 27.6 3.1 5.2 7.0 10.4

22 NP NP NP NP 9.7 16.5 22.3 NP 3.7 6.2 8.4 12.4

24 NP NP NP NP 11.4 19.3 26.2 NP 4.3 7.3 9.9 14.6

26 NP NP NP NP 13.2 22.4 NP NP 5.0 8.5 11.4 16.9

28 NP NP NP NP 15.1 25.7 NP NP 5.7 9.7 13.1 19.4

30 NP NP NP NP 17.2 NP NP NP 6.5 11.0 14.9 22.0

32 NP NP NP NP 19.4 NP NP NP 7.3 12.4 16.8 24.8

34 NP NP NP NP 21.7 NP NP NP 8.2 13.9 18.8 NP

36 NP NP NP NP 24.1 NP NP NP 9.1 15.4 20.9 NP

NP: Not permitted. Pressure loss exceeds reasonable limits.

Notes:

(1) Values are applicable for underground piping materials permitted by the local plumbing code and arebased on an SDR of 11 and a Hazen-Williams C factor of 150.

(2) Values include the following length allowances for fittings: 25 percent length increase for actual lengthsup to 100 ft (30.5 m) and 15 percent length increase for actual lengths over 100 ft (30.5 m).

*Flow rate from Sections 10.1 and 10.2. Add 5 gpm (18.9 lpm) to the flow rate required by 10.4.9.2, Step 4,where the water service pipe supplies more than one dwelling.

Table 10.4.9.2(b) Elevation Loss (PLe)

Elevation (ft)(m) Pressure Loss (psi)(bar)

5 (1.5) 2.2 (0.15)

10 (3) 4.4 (0.30)

15 (4.6) 6.5(0.45)

20 (6.1) 8.7 (0.6)

25 (7.6) 10.9 (0.75)

30 (9.1) 13.0 (0.89)

35 (10.7) 15.2 (1.0)

40 (12.2) 17.4 (1.2)

Table 10.4.9.2(c) Allowable Pipe Length for ¾ in. Type M Copper Water Tubing

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 3⁄4 217 289 361 434 506 578 650 723 795 867

9 3⁄4 174 232 291 349 407 465 523 581 639 697

10 3⁄4 143 191 239 287 335 383 430 478 526 574

11 3⁄4 120 160 200 241 281 321 361 401 441 481

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

80 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

12 3⁄4 102 137 171 205 239 273 307 341 375 410

13 3⁄4 88 118 147 177 206 235 265 294 324 353

14 3⁄4 77 103 128 154 180 205 231 257 282 308

15 3⁄4 68 90 113 136 158 181 203 226 248 271

16 3⁄4 60 80 100 120 140 160 180 200 220 241

17 3⁄4 54 72 90 108 125 143 161 179 197 215

18 3⁄4 48 64 81 97 113 129 145 161 177 193

19 3⁄4 44 58 73 88 102 117 131 146 160 175

20 3⁄4 40 53 66 80 93 106 119 133 146 159

21 3⁄4 36 48 61 73 85 97 109 121 133 145

22 3⁄4 33 44 56 67 78 89 100 111 122 133

23 3⁄4 31 41 51 61 72 82 92 102 113 123

24 3⁄4 28 38 47 57 66 76 85 95 104 114

25 3⁄4 26 35 44 53 61 70 79 88 97 105

26 3⁄4 24 33 41 49 57 65 73 82 90 98

27 3⁄4 23 30 38 46 53 61 69 76 84 91

28 3⁄4 21 28 36 43 50 57 64 71 78 85

29 3⁄4 20 27 33 40 47 53 60 67 73 80

30 3⁄4 19 25 31 38 44 50 56 63 69 75

31 3⁄4 18 24 29 35 41 47 53 59 65 71

32 3⁄4 17 22 28 33 39 44 50 56 61 67

33 3⁄4 16 21 26 32 37 42 47 53 58 63

34 3⁄4 NP 20 25 30 35 40 45 50 55 60

35 3⁄4 NP 19 24 28 33 38 42 47 52 57

36 3⁄4 NP 18 22 27 31 36 40 45 49 54

37 3⁄4 NP 17 21 26 30 34 38 43 47 51

38 3⁄4 NP 16 20 24 28 32 36 40 45 49

39 3⁄4 NP 15 19 23 27 31 35 39 42 46

40 3⁄4 NP NP 18 22 26 29 33 37 40 44

NP: Not permitted.

*Flow rate from Sections 10.1 and 10.2.

Table 10.4.9.2(d) Allowable Pipe Length for 1 in. Type M Copper Water Tubing

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 1 806 1075 1343 1612 1881 2149 2418 2687 2955 3224

9 1 648 864 1080 1296 1512 1728 1945 2161 2377 2593

10 1 533 711 889 1067 1245 1422 1600 1778 1956 2134

11 1 447 596 745 894 1043 1192 1341 1491 1640 1789

12 1 381 508 634 761 888 1015 1142 1269 1396 1523

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

81 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

13 1 328 438 547 657 766 875 985 1094 1204 1313

14 1 286 382 477 572 668 763 859 954 1049 1145

15 1 252 336 420 504 588 672 756 840 924 1008

16 1 224 298 373 447 522 596 671 745 820 894

17 1 200 266 333 400 466 533 600 666 733 799

18 1 180 240 300 360 420 479 539 599 659 719

19 1 163 217 271 325 380 434 488 542 597 651

20 1 148 197 247 296 345 395 444 493 543 592

21 1 135 180 225 270 315 360 406 451 496 541

22 1 124 165 207 248 289 331 372 413 455 496

23 1 114 152 190 228 267 305 343 381 419 457

24 1 106 141 176 211 246 282 317 352 387 422

25 1 98 131 163 196 228 261 294 326 359 392

26 1 91 121 152 182 212 243 273 304 334 364

27 1 85 113 142 170 198 226 255 283 311 340

28 1 79 106 132 159 185 212 238 265 291 318

29 1 74 99 124 149 174 198 223 248 273 298

30 1 70 93 116 140 163 186 210 233 256 280

31 1 66 88 110 132 153 175 197 219 241 263

32 1 62 83 103 124 145 165 186 207 227 248

33 1 59 78 98 117 137 156 176 195 215 234

34 1 55 74 92 111 129 148 166 185 203 222

35 1 53 70 88 105 123 140 158 175 193 210

36 1 50 66 83 100 116 133 150 166 183 199

37 1 47 63 79 95 111 126 142 158 174 190

38 1 45 60 75 90 105 120 135 150 165 181

39 1 43 57 72 86 100 115 129 143 158 172

40 1 41 55 68 82 96 109 123 137 150 164

*Flow rate from Sections 10.1 and 10.2.

Table 10.4.9.2(e) Allowable Pipe Length for ¾ in. CPVC (IPS) Pipe

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 3⁄4 348 465 581 697 813 929 1045 1161 1278 1394

9 3⁄4 280 374 467 560 654 747 841 934 1027 1121

10 3⁄4 231 307 384 461 538 615 692 769 845 922

11 3⁄4 193 258 322 387 451 515 580 644 709 773

12 3⁄4 165 219 274 329 384 439 494 549 603 658

13 3⁄4 142 189 237 284 331 378 426 473 520 568

14 3⁄4 124 165 206 247 289 330 371 412 454 495

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

82 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

15 3⁄4 109 145 182 218 254 290 327 363 399 436

16 3⁄4 97 129 161 193 226 258 290 322 354 387

17 3⁄4 86 115 144 173 202 230 259 288 317 346

18 3⁄4 78 104 130 155 181 207 233 259 285 311

19 3⁄4 70 94 117 141 164 188 211 234 258 281

20 3⁄4 64 85 107 128 149 171 192 213 235 256

21 3⁄4 58 78 97 117 136 156 175 195 214 234

22 3⁄4 54 71 89 107 125 143 161 179 197 214

23 3⁄4 49 66 82 99 115 132 148 165 181 198

24 3⁄4 46 61 76 91 107 122 137 152 167 183

25 3⁄4 42 56 71 85 99 113 127 141 155 169

26 3⁄4 39 52 66 79 92 105 118 131 144 157

27 3⁄4 37 49 61 73 86 98 110 122 135 147

28 3⁄4 34 46 57 69 80 92 103 114 126 137

29 3⁄4 32 43 54 64 75 86 96 107 118 129

30 3⁄4 30 40 50 60 70 81 91 101 111 121

31 3⁄4 28 38 47 57 66 76 85 95 104 114

32 3⁄4 27 36 45 54 63 71 80 89 98 107

33 3⁄4 25 34 42 51 59 68 76 84 93 101

34 3⁄4 24 32 40 48 56 64 72 80 88 96

35 3⁄4 23 30 38 45 53 61 68 76 83 91

36 3⁄4 22 29 36 43 50 57 65 72 79 86

37 3⁄4 20 27 34 41 48 55 61 68 75 82

38 3⁄4 20 26 33 39 46 52 59 65 72 78

39 3⁄4 19 25 31 37 43 50 56 62 68 74

40 3⁄4 18 24 30 35 41 47 53 59 65 71

*Flow rate from Sections 10.1 and 10.2.

Table 10.4.9.2(f) Allowable Pipe Length for 1 in. CPVC (IPS) Pipe

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 1 1049 1398 1748 2098 2447 2797 3146 3496 3845 4195

9 1 843 1125 1406 1687 1968 2249 2530 2811 3093 3374

10 1 694 925 1157 1388 1619 1851 2082 2314 2545 2776

11 1 582 776 970 1164 1358 1552 1746 1940 2133 2327

12 1 495 660 826 991 1156 1321 1486 1651 1816 1981

13 1 427 570 712 854 997 1139 1281 1424 1566 1709

14 1 372 497 621 745 869 993 1117 1241 1366 1490

15 1 328 437 546 656 765 874 983 1093 1202 1311

16 1 291 388 485 582 679 776 873 970 1067 1164

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

83 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

17 1 260 347 433 520 607 693 780 867 954 1040

18 1 234 312 390 468 546 624 702 780 858 936

19 1 212 282 353 423 494 565 635 706 776 847

20 1 193 257 321 385 449 513 578 642 706 770

21 1 176 235 293 352 410 469 528 586 645 704

22 1 161 215 269 323 377 430 484 538 592 646

23 1 149 198 248 297 347 396 446 496 545 595

24 1 137 183 229 275 321 366 412 458 504 550

25 1 127 170 212 255 297 340 382 425 467 510

26 1 118 158 197 237 276 316 355 395 434 474

27 1 111 147 184 221 258 295 332 368 405 442

28 1 103 138 172 207 241 275 310 344 379 413

29 1 97 129 161 194 226 258 290 323 355 387

30 1 91 121 152 182 212 242 273 303 333 364

31 1 86 114 143 171 200 228 257 285 314 342

32 1 81 108 134 161 188 215 242 269 296 323

33 1 76 102 127 152 178 203 229 254 280 305

34 1 72 96 120 144 168 192 216 240 265 289

35 1 68 91 114 137 160 182 205 228 251 273

36 1 65 87 108 130 151 173 195 216 238 260

37 1 62 82 103 123 144 165 185 206 226 247

38 1 59 78 98 117 137 157 176 196 215 235

39 1 56 75 93 112 131 149 168 187 205 224

40 1 53 71 89 107 125 142 160 178 196 214

*Flow rate from Sections 10.1 and 10.2.

Table 10.4.9.2(g) Allowable Pipe Length for ¾ in. PEX Tubing

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 3⁄4 93 123 154 185 216 247 278 309 339 370

9 3⁄4 74 99 124 149 174 199 223 248 273 298

10 3⁄4 61 82 102 123 143 163 184 204 225 245

11 3⁄4 51 68 86 103 120 137 154 171 188 205

12 3⁄4 44 58 73 87 102 117 131 146 160 175

13 3⁄4 38 50 63 75 88 101 113 126 138 151

14 3⁄4 33 44 55 66 77 88 99 110 121 132

15 3⁄4 29 39 48 58 68 77 87 96 106 116

16 3⁄4 26 34 43 51 60 68 77 86 94 103

17 3⁄4 23 31 38 46 54 61 69 77 84 92

18 3⁄4 21 28 34 41 48 55 62 69 76 83

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

84 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

19 3⁄4 19 25 31 37 44 50 56 62 69 75

20 3⁄4 17 23 28 34 40 45 51 57 62 68

21 3⁄4 16 21 26 31 36 41 47 52 57 62

22 3⁄4 NP 19 24 28 33 38 43 47 52 57

23 3⁄4 NP 17 22 26 31 35 39 44 48 52

24 3⁄4 NP 16 20 24 28 32 36 40 44 49

25 3⁄4 NP NP 19 22 26 30 34 37 41 45

26 3⁄4 NP NP 17 21 24 28 31 35 38 42

27 3⁄4 NP NP 16 20 23 26 29 33 36 39

28 3⁄4 NP NP 15 18 21 24 27 30 33 36

29 3⁄4 NP NP NP 17 20 23 26 28 31 34

30 3⁄4 NP NP NP 16 19 21 24 27 29 32

31 3⁄4 NP NP NP 15 18 20 23 25 28 30

32 3⁄4 NP NP NP NP 17 19 21 24 26 28

33 3⁄4 NP NP NP NP 16 18 20 22 25 27

34 3⁄4 NP NP NP NP NP 17 19 21 23 25

35 3⁄4 NP NP NP NP NP 16 18 20 22 24

36 3⁄4 NP NP NP NP NP 15 17 19 21 23

37 3⁄4 NP NP NP NP NP NP 16 18 20 22

38 3⁄4 NP NP NP NP NP NP 16 17 19 21

39 3⁄4 NP NP NP NP NP NP NP 16 18 20

40 3⁄4 NP NP NP NP NP NP NP 16 17 19

NP: Not permitted.

*Flow rate from Sections 10.1 and 10.2.

Table 10.4.9.2(h) Allowable Pipe Length for 1 in. PEX Tubing

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

8 1 314 418 523 628 732 837 941 1046 1151 1255

9 1 252 336 421 505 589 673 757 841 925 1009

10 1 208 277 346 415 485 554 623 692 761 831

11 1 174 232 290 348 406 464 522 580 638 696

12 1 148 198 247 296 346 395 445 494 543 593

13 1 128 170 213 256 298 341 383 426 469 511

14 1 111 149 186 223 260 297 334 371 409 446

15 1 98 131 163 196 229 262 294 327 360 392

16 1 87 116 145 174 203 232 261 290 319 348

17 1 78 104 130 156 182 208 233 259 285 311

18 1 70 93 117 140 163 187 210 233 257 280

19 1 63 84 106 127 148 169 190 211 232 253

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

85 of 129 11/3/2016 12:03 PM

Sprinkler FlowRate*

(gpm)

Water DistributionSize

(in.)

Available Pressure, P t (psi)

15 20 25 30 35 40 45 50 55 60

Allowable Length of Pipe from Service Valve to FarthestSprinkler (ft)

20 1 58 77 96 115 134 154 173 192 211 230

21 1 53 70 88 105 123 140 158 175 193 211

22 1 48 64 80 97 113 129 145 161 177 193

23 1 44 59 74 89 104 119 133 148 163 178

24 1 41 55 69 82 96 110 123 137 151 164

25 1 38 51 64 76 89 102 114 127 140 152

26 1 35 47 59 71 83 95 106 118 130 142

27 1 33 44 55 66 77 88 99 110 121 132

28 1 31 41 52 62 72 82 93 103 113 124

29 1 29 39 48 58 68 77 87 97 106 116

30 1 27 36 45 54 63 73 82 91 100 109

31 1 26 34 43 51 60 68 77 85 94 102

32 1 24 32 40 48 56 64 72 80 89 97

33 1 23 30 38 46 53 61 68 76 84 91

34 1 22 29 36 43 50 58 65 72 79 86

35 1 20 27 34 41 48 55 61 68 75 82

36 1 19 26 32 39 45 52 58 65 71 78

37 1 18 25 31 37 43 49 55 62 68 74

38 1 18 23 29 35 41 47 53 59 64 70

39 1 17 22 28 33 39 45 50 56 61 67

40 1 16 21 27 32 37 43 48 53 59 64

*Flow rate from Sections 10.1 and 10.2.

Statement of Problem and Substantiation for Public Input

The three sets of tables for ¾" pipe are all missing the "¾" in the table heading.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 09:31:30 EDT 2016

Committee Statement

Resolution: FR-42-NFPA 13D-2016

Statement: The three sets of tables for ¾" pipe are all missing the "¾" in the table heading.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

86 of 129 11/3/2016 12:03 PM

Public Input No. 81-NFPA 13D-2016 [ New Section after 12.3.5.1.4.2 ]

12.3.6 Inactive Systems

12.3.6.1* In a detached dwelling or a manufactured home the sprinkler system shall be permitted to be putin an inactive state for any of the following reasons:

(1) After a manufactured home has been installed and testing in the factory and is beingprepared for shipment.

(2) When a manufactured home is being stored for future occupancy.

(3) When the detached dwelling is unoccupied during renovation work, with notification andapproval of the AHJ.

(4) When the detached dwelling is unoccupied for an extended period of time, withnotification and approval of the AHJ.

12.3.6.2 Where a wet pipe system is installed and the piping will be subject to temperatures below 40° F(4°C) the piping and the stored water supply shall be drained.

12.3.6.2.1 * Residential pendent and sidewall sprinklers installed on drops, where the drops are 4” or lessin length, the drops shall not be required to be drained.

12.3.6.3 Prior to the system being restored to service, the system shall be filled with water, pressurized tonormal system pressure, and visually inspected for leaks.

12.3.6.4 Once the system has been restored to service, it shall be inspected and tested in accordance withsection 12.2 of this standard.

Statement of Problem and Substantiation for Public Input

There needs to be guidance for taking a system out of service. There are many instances when an installed system needs to be taken out of service such as for shipping or storage of a manufactured home, or when extensive renovation or remodeling work is going on in the home, or when the home will be unoccupied for an extended period of time. NFPA 13D sprinkler systems are life safety systems and do not need to remain active when the home is being shipped, stored or is unoccupied. This guidance is especially needed when the detached dwelling or manufactured home is subject to freezing temperatures. Once the home is to be occupied again, the system must be tested for leaks and the system and components inspected and testing before restored to service.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 82-NFPA 13D-2016 [New Section after A.12.3.5.1.3]

Public Input No. 83-NFPA 13D-2016 [New Section after A.12.3.5.1.3]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 11:31:54 EDT 2016

Committee Statement

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

87 of 129 11/3/2016 12:03 PM

Resolution: FR-40-NFPA 13D-2016 TG supports based on substantiation. The temperature threshold is to beconsistent with other PI’s that reference freezing. When a single family dwelling is issued a CO theAHJ does not have a mechanism to monitor the condition of the dwelling or its systems.

Statement: There needs to be guidance for taking a system out of service. There are many instances when aninstalled system needs to be taken out of service such as for shipping or storage of a manufacturedhome, or when extensive renovation or remodeling work is going on in the home, or when the homewill be unoccupied for an extended period of time. NFPA 13D sprinkler systems are life safetysystems and do not need to remain active when the home is being shipped, stored or is unoccupied.This guidance is especially needed when the detached dwelling or manufactured home is subject tofreezing temperatures. Once the home is to be occupied again, the system must be tested for leaksand the system and components inspected and testing before restored to service.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

88 of 129 11/3/2016 12:03 PM

Public Input No. 7-NFPA 13D-2016 [ Section No. A.1.1 ]

A.1.1

NFPA 13D is appropriate for protection against fire hazards only in one- and two-family dwellings andmanufactured homes. Residential portions of any other type of building or occupancy should be protectedwith residential sprinklers in accordance with NFPA 13 or in accordance with NFPA 13R. Other portions ofsuch buildings should be protected in accordance with NFPA 13 or NFPA 13R as appropriate for areasoutside the dwelling unit.

The criteria in this standard are based on full-scale fire tests of rooms containing typical furnishings found inresidential living rooms, kitchens, and bedrooms. The furnishings were arranged as typically found indwelling units in a manner similar to that shown in Figure A.1.1(a) , Figure A.1.1(b) , and Figure A.1.1(c).Sixty full-scale fire tests were conducted in a two-story dwelling in Los Angeles, California, and 16 testswere conducted in a 14 ft (4.2 m) wide mobile home in Charlotte, North Carolina.

Sprinkler systems designed and installed according to this standard are expected to prevent flashoverwithin the compartment of origin where sprinklers are installed in the compartment. A sprinkler systemdesigned and installed according to this standard cannot, however, be expected to completely control a fire

involving fuel loads that are significantly higher than average for dwelling units [10 lb/ft2 (49 kg/m2)] andwhere the interior finish has an unusually exhibits either a high flame spread index (greater than 225 200,corresponding to a Class C ) when tested in accordance with ASTM E84, Standard Test Method for SurfaceBurning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface BurningCharacteristics of Building Materials or a high heat release (such as a heat release rate exceeding 800 kW)when tested in accordance with NFPA 286 .

(For protection of multifamily dwellings, see NFPA 13 or NFPA 13R.)

Figure A.1.1(a) Bedroom.

Figure A.1.1(b) Manufactured Home Bedroom.

Figure A.1.1(c) Living Room.

Statement of Problem and Substantiation for Public Input

Any material with a flame spread index above 200 (for a Class C) in accordance with ASTM E84 is basically considered unclassified. In more modern terms the key concern is heat release and the best test for that for interior finish is NFPA 286. An interior finish material must exhibit a peak heat release rate not exceeding 800 kW and not reach flashover in the tests to be considered acceptable.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 8-NFPA 13D-2016 [Section No. B.1.1]

Submitter Information Verification

Submitter Full Name: Marcelo Hirschler

Organization: GBH International

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 17:52:28 EST 2016

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

89 of 129 11/3/2016 12:03 PM

Committee Statement

Resolution: FR-8-NFPA 13D-2016

Statement: Any material with a flame spread index above 200 (for a Class C) in accordance with ASTM E84 isbasically considered unclassified. In more modern terms the key concern is heat release and the besttest for that for interior finish is NFPA 286. An interior finish material must exhibit a peak heat releaserate not exceeding 800 kW and not reach flashover in the tests to be considered acceptable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

90 of 129 11/3/2016 12:03 PM

Public Input No. 3-NFPA 13D-2015 [ New Section after A.1.2 ]

A.1.4

It is the intent of the committee to recognize that future editions of this standard are a further refinement ofthis edition and earlier editions. The changes in future editions will reflect the continuing input of the fireprotection community in its attempt to meet the purpose stated in this standard. Compliance with allrequirements of a future edition could be considered as providing an equivalent level of system integrity andperformance of the system.

Statement of Problem and Substantiation for Public Input

Many AHJ's will not recognize future editions. This annex note is intended to give guidance that use of an entire future edition of the standard could be considered an equivalency as allowed in 1.4. This language will be proposed to other sprinkler standards and has been accepted by NFPA 14 & NFPA 25.

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Dec 22 10:27:44 EST 2015

Committee Statement

Resolution: Added to section 1.4 in main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

91 of 129 11/3/2016 12:03 PM

Public Input No. 42-NFPA 13D-2016 [ New Section after A.3.2.4 ]

A.3.3.1 Bathroom

A room is still considered a bathroom if it contains just a toilet, Additionally, two bathrooms can be adjacentto each other and are considered separate rooms, provided they are enclosed with the required level ofconstruction.

Statement of Problem and Substantiation for Public Input

Even though it can be found in 13R, at times there have been conflicting opinions about what constitutes a bathroom, especially when the bathroom is divided up into two separate rooms and the combined total size exceeds 55 square feet but the individual room size is less than 55 square feet. This language is extracted from the equivalent sections of NFPA 13R.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 41-NFPA 13D-2016 [New Section after 3.3.1] Annex material

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 21 17:24:51 EDT 2016

Committee Statement

Resolution: Added to section 3.3.1 in main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

92 of 129 11/3/2016 12:03 PM

Public Input No. 86-NFPA 13D-2016 [ Section No. A.4.5 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

93 of 129 11/3/2016 12:03 PM

A.4.5

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

94 of 129 11/3/2016 12:03 PM

A scaled drawing where required should show the following:

(1) Address Point of compass

(2) Name of owner (if known)

Size and

(3) Location, including street address

(4) Site plan / vicinity map

(5) For systems supplied by city mains, location and size of city main in street, and location, size, andtype of domestic line, including length to city connection, and water meter location and size. Staticand residual hydrants that were used in flow tests shall be shown. The location of the 5 gpm domesticdemand shall be indicated

(6) Water meter size and utility plans and/or plumbing plans necessary to show connection from watersupply to fire sprinkler system

(7) Current static water pressure or static water pressure provided by the utility

(8) Interior walls

(9) Full height cross section

(10) Ceiling/roof heights and slopes not shown in the full height cross section

(11) Location of partitions, lintels, and doorways. Lintel openings require a cross section view to indicatethe area of the opening

(12) Name and label for each area or room

(13) Indicate by note the minimum rate of water application per sprinkler head, the maximum spacing foreach head, and the domestic demand

(14) Model, manufacturer, temperature, orifice size, and spacing requirements of sprinklers

(15) Make, type, model, temperature rating, nominal K-factor, and number of each type of sprinkler,including sprinkler identification number

(16) Pipe type and schedule of wall thickness

(17) Nominal pipe size and cutting lengths of pipe (or center-to-center dimensions). Where typical branchlines prevail, it shall be necessary to size only one typical line

(18) Location and size of riser nipples and drops

(19) Type of fittings and joints

(20) Type and locations of hangers, and methods of securing sprinklers when applicable

(21) Location and size of all valves and drain pipes

(22) Location and size of water gauges

(23) Type of pipe

(24) Hanger spacing requirement per the pipe manufacturer

(25) Riser detail

(26) Information about antifreeze solution used. Indicate the type of antifreeze used, the amount ofantifreeze in the system, and information about antifreeze compatibility with the pipe.

(27) Installing contractor information

(28) Preliminary hydraulic calculations

(29) (name, address, phone number, email address)

(30) A summary of the hydraulics, including the static pressure, residual pressure, and flow of the watersupply, the pressure and flow demands at the point of connection to the water supply, and thepressure and flow demands at the bottom of the system riser.

(31) Hydraulic reference points shown on the plan that correspond with comparable reference points onthe hydraulic calculation sheets.

(32) Relative elevations of sprinklers, junction points, and supply or reference points.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

95 of 129 11/3/2016 12:03 PM

(33) A graphic representation of the scale used on all plans

Statement of Problem and Substantiation for Public Input

These items will aid plan review and inspections.

Submitter Information Verification

Submitter Full Name: Lynn Nielson

Organization: City Of Henderson

Affilliation: Self

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 14:10:25 EDT 2016

Committee Statement

Resolution: All of the information in the submitter's list isn't necessary for an installation in accordance with thisstandard. The current list of information provided is the minimum for a 13D system. Although notrecommended by this standard, the AHJ can require more information.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

96 of 129 11/3/2016 12:03 PM

Public Input No. 65-NFPA 13D-2016 [ New Section after A.5.3 ]

TITLE OF NEW CONTENT

A. 5.3 (2) There may be instances when the system riser is located at the water supply source orsome other location outside of the dwelling or home. Underground pipe and fittings or tubeacceptable under the applicable plumbing code is adequate to run from the remote system riser tothe dwelling or home.

Statement of Problem and Substantiation for Public Input

In the scenario where the water supply source and the riser assembly is not in the dwelling unit, underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMA uses this arrangement when providing sprinkler systems for many of their manufactured housing units. This arrangement could also be used when retrofitting an existing dwelling or home. The added text makes it clear that underground pipe and fittings do not have to be listed. However, in accordance with section 5.3 the underground pipe and fittings must comply with the applicable plumbing code for the dwelling or home.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 64-NFPA 13D-2016 [Section No. 5.3]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 13:44:13 EDT 2016

Committee Statement

Resolution: FR-46-NFPA 13D-2016

Statement: In the scenario where the water supply source and the riser assembly is not in the dwelling unit,underground pipe and fittings may be needed to run from the riser assembly to the dwelling. FEMAuses this arrangement when providing sprinkler systems for many of their manufactured housingunits. This arrangement could also be used when retrofitting an existing dwelling or home. The addedtext makes it clear that underground pipe and fittings do not have to be listed. However, inaccordance with section 5.3 the underground pipe and fittings must comply with the applicableplumbing code for the dwelling or home.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

97 of 129 11/3/2016 12:03 PM

Public Input No. 67-NFPA 13D-2016 [ New Section after A.6.2 ]

TITLE OF NEW CONTENT

A. 6.2.3 Well pumps are an economical way to provide a water supply source in rural areas withouta municipal water supply. Rather than having a pump and tank assembly as described in sections6.2.1 and 6.2.2 which typically takes up floor space in the dwelling or home and requires a separateac power source among other things, the well pump can be up-sized to accommodate the sprinklerdemand at considerably less cost.

Statement of Problem and Substantiation for Public Input

While well pumps are an economical solution for a water supply in rural areas, many home builders aren’t aware of this option. The additional annex text should help bring this option to the forefront and decrease the cost of the residential sprinkler system.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 66-NFPA 13D-2016 [New Section after 6.2.3.2]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 13:49:47 EDT 2016

Committee Statement

Resolution: FR-12-NFPA 13D-2016 An asterisk was added to (4) to include annex text that states that aswimming pool is a stored water source as described in 6.2 (4) as long as there is sufficient water inthe pool to meet the requirements of 6.1.2 or 6.1.3.

Statement: While well pumps are an economical solution for a water supply in rural areas, many home buildersaren’t aware of this option. The additional annex text should help bring this option to the forefront,provide additional guidance for volume calulations, and decrease the cost of the residential sprinklersystem.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

98 of 129 11/3/2016 12:03 PM

Public Input No. 10-NFPA 13D-2016 [ Section No. A.6.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

99 of 129 11/3/2016 12:03 PM

A.6.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

100 of 129 11/3/2016 12:03 PM

The connection to city mains for fire protection is often subject to local regulation of metering and backflowprevention requirements. Preferred and acceptable water supply arrangements are shown in FigureA.6.2(a)through Figure A.6.2(d) . Where it is necessary to use a meter between the city water main andthe sprinkler system supply, an acceptable arrangement as shown in Figure A.6.2(c)and FigureA.6.2(d)can be used. Under these circumstances, the flow characteristics of the meter are to be includedin the hydraulic calculation of the system [see Table 10.4.4(a)]. Where a tank is used for both domesticand fire protection purposes, a low water alarm that actuates when the water level falls below 110 percentof the minimum quantity specified in 6.1.2 should be provided.

The effect of pressure-reducing valves on the system should be considered in the hydraulic calculationprocedures.

Figure A.6.2(a) , Figure A.6.2(c), or Figure A.6.2(d)are acceptable methods for getting the water supplyinto the unit for a stand-alone sprinkler system (one that does not also provide direct connections to thecold water fixtures) because the common supply pipe for the domestic system and the sprinkler systembetween the water supply and the dwelling unit has a single control valve that shuts the sprinkler system,which helps to ensure that people who have running water to their domestic fixtures also have fireprotection. This serves as a form of supervision for the control valve and can be used to make sure thatthe valve stays open in place of other, more expensive options such as tamper switches with a monitoringservice.

Some water utilities insist on separate taps and supply pipes from the water supply to the dwelling unit forfire sprinkler systems as shown in Figure A.6.2(d) , due to concerns about shutting off the water supply fornonpayment of bills and the desire not to shut off fire protection if this ever occurs. While these types ofarrangements are acceptable, they might not be cost efficient and should be discouraged due to the extracost burden this places on the building owner. The concern over shutting off the water for nonpayment ofbills is a nonissue for a number of reasons. First, the water utilities rarely actually shut off water fornonpayment. Second, if they do shut off water for nonpayment, they are creating violations of all sorts ofhealth and safety codes, allowing people to live in a home without running water. Concern over the fireprotection for those individuals when they are violating all kinds of other health codes is disingenuous.More likely, the water utility will not shut off the water and will follow other legal avenues to collect onunpaid bills, such as liens on property. Millions of people should not have to pay hundreds of millions ofdollars to install separate water taps and lines for the few services that might get shut off.

Figure A.6.2(a) Minimum Requirements for a Stand-Alone System.

Figure A.6.2(b) Acceptable Arrangement for Stand-Alone Piping Systems — Option 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

101 of 129 11/3/2016 12:03 PM

Figure A.6.2(c) Acceptable Arrangement for Stand-Alone Piping System — Option 2.

Figure A.6.2(d) Acceptable Arrangement for Stand-alone Piping Systems — Option 3.

Additional Proposed Changes

File Name Description Approved

NFPA_13D_Fig_A.6.2_e_-Model.pdf NFPA 13D Fig A.6.2(e)

Statement of Problem and Substantiation for Public Input

Add figure E for townhouses. This is a common scenario for supplying standalone NFPA 13D systems. Many

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

102 of 129 11/3/2016 12:03 PM

water purveyors will not allow combined feeds into the dwelling unit. In fact many water purveyors mandate a 2" minimum connection for a sprinkler system. This scenario incorporates a single backflow preventer and uses underground to feed each dwelling unit.

Submitter Information Verification

Submitter Full Name: Peter Schwab

Organization: Wayne Automatic Fire Sprinkler

Street Address:

City:

State:

Zip:

Submittal Date: Tue Feb 23 11:17:19 EST 2016

Committee Statement

Resolution: FR-18-NFPA 13D-2016 Annex text was edited for length and content, some of the language used isinformal and doesn’t necessarily result in broader acceptance of residential fire sprinkler systems.Agree with the submitter and a new drawing was added.

Statement: Add figure E for townhouses. This is a common scenario for supplying standalone NFPA 13Dsystems. Many water purveyors will not allow combined feeds into the dwelling unit. In fact manywater purveyors mandate a 2" minimum connection for a sprinkler system. This scenario incorporatesa single backflow preventer and uses underground to feed each dwelling unit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

103 of 129 11/3/2016 12:03 PM

Public Input No. 73-NFPA 13D-2016 [ Section No. A.6.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

104 of 129 11/3/2016 12:03 PM

A.6.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

105 of 129 11/3/2016 12:03 PM

The connection to city mains for fire protection is often subject to local regulation of metering and backflowprevention requirements. Preferred and acceptable water supply arrangements are shown in FigureA.6.2(a)through Figure A.6.2(d) . Where it is necessary to use a meter between the city water main and thesprinkler system supply, an acceptable arrangement as shown in Figure A.6.2(c)and Figure A.6.2(d)can beused. Under these circumstances, the flow characteristics of the meter are to be included in the hydrauliccalculation of the system [see Table 10.4.4(a) ]. Where a tank is used for both domestic and fire protectionpurposes, a low water alarm that actuates when the water level falls below 110 percent of the minimumquantity specified in 6.1.2 should be provided.

The effect of pressure-reducing valves on the system should be considered in the hydraulic calculationprocedures.

Figure A.6.2(a), Figure A.6.2(c), or Figure A.6.2(d)are acceptable methods for getting the water supplyinto the unit for a stand-alone sprinkler system (one that does not also provide direct connections to thecold water fixtures) because the common supply pipe for the domestic system and the sprinkler systembetween the water supply and the dwelling unit has a single control valve that shuts the sprinkler system,which helps to ensure that people who have running water to their domestic fixtures also have fireprotection. This serves as a form of supervision for the control valve and can be used to make sure that thevalve stays open in place of other, more expensive options such as tamper switches with a monitoringservice.

Some water utilities insist on separate taps and supply pipes from the water supply to the dwelling unit forfire sprinkler systems as shown in Figure A.6.2(d), due to concerns about shutting off the water supply fornonpayment of bills and the desire not to shut off fire protection if this ever occurs. While these types ofarrangements are acceptable, they might not be cost efficient and should be discouraged due to the extracost burden this places on the building owner. The concern over shutting off the water for nonpayment ofbills is a nonissue for a number of reasons. First, It is extremely rare that the water utilities rarely wouldactually shut off water for nonpayment. Second , and even if they do shut off water for nonpayment, theyare creating violations of all sorts of health and safety codes, allowing people to live in a home withoutrunning water. Concern over the fire protection for those individuals when they are violating all kinds ofother health codes is disingenuous. More likely, the water utility will not shut off the water and will followother legal avenues to collect on unpaid bills, such as liens on property. Millions of people should not haveto pay hundreds of millions of dollars to install separate water taps and lines for the few services that mightget shut off. a situation in which the dwelling would be unfit for occupation. As the purpose of an NFPA13D system is life safety, an unoccupied dwelling would not require an active sprinkler system.

Figure A.6.2(a) Minimum Requirements for a Stand-Alone System.

Figure A.6.2(b) Acceptable Arrangement for Stand-Alone Piping Systems — Option 1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

106 of 129 11/3/2016 12:03 PM

Figure A.6.2(c) Acceptable Arrangement for Stand-Alone Piping System — Option 2.

Figure A.6.2(d) Acceptable Arrangement for Stand-alone Piping Systems — Option 3.

Statement of Problem and Substantiation for Public Input

Edit for length and content, some of the language used is informal and doesn’t necessarily result in broader acceptance of residential fire sprinkler systems.

Submitter Information Verification

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

107 of 129 11/3/2016 12:03 PM

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 17:07:47 EDT 2016

Committee Statement

Resolution: While the committee agrees with most of the changes proposed, the last sentence of the submittersnew text was problematic.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

108 of 129 11/3/2016 12:03 PM

Public Input No. 74-NFPA 13D-2016 [ Section No. A.6.2.3 ]

A.6.2.3

The best method for getting the water supply into the unit for a stand-alone sprinkler system (one that doesnot also provide direct connections to the cold water fixtures) is to have a common pipe for the domesticsystem and the sprinkler system between the water supply and the dwelling unit. Once inside the dwellingunit, the pipes can be split to provide the individual domestic and sprinkler systems. In this arrangement, asingle control valve on the combined pipe (prior to the split) as shown in Figure A.6.2(a) being the onlycontrol valve that shuts the sprinkler system is preferred because it ensures that people who have runningwater to their domestic fixtures also have fire protection. This serves as a form of supervision for thecontrol valve and can be used to make sure that the valve stays open in place of other, more expensiveoptions such as tamper switches with monitoring service. Some water utilities insist on separate taps andsupply pipes from the water supply to the dwelling unit for fire sprinkler systems due to concerns aboutshutting off the water supply for nonpayment of bills and the desire not to shut off fire protection if this everoccurs. While this type of arrangement is acceptable [see Figure A.6.2(b) ] , it is not cost efficient andshould be discouraged due to the extra burden this places on the building owner. The concern overshutting off the water for nonpayment of bills is a nonissue for a number of reasons. First, the water utilitiesrarely actually shut off water for nonpayment. Second, if they do shut off water for nonpayment, they arecreating violations of all sorts of health and safety codes, allowing people to live in a home without runningwater. Concern over the fire protection for those individuals when they are violating all kinds of other healthcodes is disingenuous. More likely, the water utility will not shut off the water and will follow other legalavenues to collect on unpaid bills such as liens on property. Millions of people should not have to payhundreds of millions of dollars to install separate water taps and lines for the few services that might getshut off. In a situation where a two-family dwelling or townhouse has a common water supply, there mustbe a way to isolate the sprinkler system in one unit without having to enter another unit. When each unithas its own, accessible shutoff valve and one unit suffers a fire event and cannot be occupied, thedamaged unit can be isolated and other units can remain occupied because they have functioning sprinklersystems.

Statement of Problem and Substantiation for Public Input

Currently this section is an almost word-for word copy of the previous section. It doesn’t seem as though the language needs to be repeated. The language on page 64 of the 13D/13R handbook in the handbook (Ask the AHJ) would be more appropriate to clarify this section.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 17:11:07 EDT 2016

Committee Statement

Resolution: FR-18-NFPA 13D-2016 Annex text was edited for length and content, some of the language used isinformal and doesn’t necessarily result in broader acceptance of residential fire sprinkler systems.Agree with the submitter and a new drawing was added.

Statement: Add figure E for townhouses. This is a common scenario for supplying standalone NFPA 13Dsystems. Many water purveyors will not allow combined feeds into the dwelling unit. In fact many

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

109 of 129 11/3/2016 12:03 PM

water purveyors mandate a 2" minimum connection for a sprinkler system. This scenario incorporatesa single backflow preventer and uses underground to feed each dwelling unit.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

110 of 129 11/3/2016 12:03 PM

Public Input No. 75-NFPA 13D-2016 [ Section No. A.6.3 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

111 of 129 11/3/2016 12:03 PM

A.6.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

112 of 129 11/3/2016 12:03 PM

Multipurpose piping systems consist of a single piping system within a residential occupancy that isintended to serve both domestic and fire protection needs. Basic forms of this system are shown in FigureA.6.3(a), Figure A.6.3(b), Figure A.6.3(c), and Figure A.6.3(d). A network system, as defined in 3.3.11.4,is a type of multipurpose system that utilizes a common piping system supplying domestic fixtures and firesprinklers where each sprinkler is supplied by a minimum of three separate paths. In dwellings wherelong-term use of lawn sprinklers is common, provision should be made for such usage. The supply for thelawn sprinkler system should originate at the main system riser instead of being supplied from thecombined fire sprinkler/domestic water pipe throughout the home.

Figure A.6.3(a) Multipurpose Piping System (Tree System) — Example 1.

Figure A.6.3(b) Multipurpose Piping System (Looped System) — Example 2.

Figure A.6.3(c) Multipurpose Piping System — Example 3 (Network System).

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

113 of 129 11/3/2016 12:03 PM

Figure A.6.3(d) Common Water Supply Connection Serving More Than One Dwelling Unit.

Statement of Problem and Substantiation for Public Input

It doesn’t currently give any suggestions for what the “provision” should be when long term use of lawn sprinklers will be common. An additional flow added to the hydraulic calculations would not be a practical solution as it will not often be apparent what the potential future level of usage will be.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 17:23:44 EDT 2016

Committee Statement

Resolution: The committee doesn't agree that where a lawn sprinkler system is connected will have a detrimentalaffect on the fire sprinkler system as long as provisions are made to account for the location of theconnection.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

114 of 129 11/3/2016 12:03 PM

Public Input No. 48-NFPA 13D-2016 [ New Section after A.7.2.4 ]

A.7.2.1

In the case of a passive-purge or multipurpose system, a plumbing fixture on the system side of the maincontrol valve will meet the requirement for a drain.

Statement of Problem and Substantiation for Public Input

Some may read this to mean that a drain valve at the system riser is required when a plumbing fixture meets the drain requirements called for in this section. The sprinkler system can be adequately drained from a plumbing fixture that is fed from the sprinkler system piping.

Submitter Information Verification

Submitter Full Name: Melisa Rodriguez

Organization: Uponor

Street Address:

City:

State:

Zip:

Submittal Date: Thu Jun 23 09:33:50 EDT 2016

Committee Statement

Resolution: Added to main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

115 of 129 11/3/2016 12:03 PM

Public Input No. 80-NFPA 13D-2016 [ New Section after A.7.5.6.3 ]

A.Table 7.5.6.3

Guidance for spacing around fireplaces

Additional Proposed Changes

File Name Description Approved

Fireplace2.pdf Guidance for spacing around fireplaces

Statement of Problem and Substantiation for Public Input

The language provided in the table provides ambiguous information about spacing sprinklers with regard to fireplaces. These diagrams provide additional clarification. Alternatively, the Annex comment could be attached to 7.5.6.3(3).

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 79-NFPA 13D-2016 [Section No. 7.5.6.3]

Submitter Information Verification

Submitter Full Name: Robert Upson

Organization: National Fire Sprinkler Association

Affilliation: NFSA Engineering and Standards Committee

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 10:41:53 EDT 2016

Committee Statement

Resolution: Added to main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

116 of 129 11/3/2016 12:03 PM

Public Input No. 76-NFPA 13D-2016 [ New Section after A.8.3.4 ]

New Annex Section

A.8.3.5.1.2. Where a chimney or flue from a fuel-fired equipment passes through a concealed space, it isnot required to locate a sprinkler in this concealed space.

Statement of Problem and Substantiation for Public Input

Some AHJ’s are using this section to require sprinklers in attic adjacent to the chimney for the fuel fired equipment below. This section is intended to apply to the actual fuel-fired equipment and not to the chimney where it passes through the attic. This Annex section will clarify.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 57-NFPA 13D-2016 [Section No. 8.3.5.1.2]

Submitter Information Verification

Submitter Full Name: Roland Asp

Organization: National Fire Sprinkler Association

Affilliation: NFSA E&S Committee

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 21:23:48 EDT 2016

Committee Statement

Resolution: N|Based on action in FR A.8.3.4

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

117 of 129 11/3/2016 12:03 PM

Public Input No. 59-NFPA 13D-2016 [ Section No. A.10.2 ]

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

118 of 129 11/3/2016 12:03 PM

A.10.2

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

119 of 129 11/3/2016 12:03 PM

All residential sprinklers have been investigated under a flat, smooth, 8 ft (2.4 m) high horizontal ceiling.Some residential sprinklers have been investigated and listed for use under specific ceiling configurationssuch as a horizontal beamed ceiling. The performance of residential sprinklers under flat, smooth,horizontal ceilings has been well documented throughout the life of NFPA 13D. Prior to 2010, severalmanufacturers of residential sprinklers had performed testing and received listings for residential sprinklersunder certain slopes and in certain beam conditions. In 2010, the Fire Protection Research Foundation(FPRF) conducted a research project consisting of 76 FDS simulations and 12 full-scale fire tests. Theresults have been used to develop system design criteria in a generic manner to simplify the use ofresidential sprinklers. Some residential sprinkler listings still exist for situations beyond the scope of thegeneric design. See the FPRF report, “Analysis of the Performance of Residential Sprinkler Systems withSloped or Sloped and Beamed Ceilings” dated July 2010 for more information.

Questions are frequently asked regarding the minimum two sprinkler design when certain sprinklerperformance statistics have indicated that in a majority of the cases (with residential sprinklers) the fire iscontrolled or suppressed with a single sprinkler. While these statistics might or might not be accurate, thewater supplies for the fire sprinkler systems under which these statistics were generated were designed fortwo or more sprinklers in the first place. When the fires occurred, the first sprinkler operated in excess of itsindividual design flow and pressure because the sprinkler system’s water supply was strong enough tohandle multiple sprinklers and only a single sprinkler opened. At these higher flows and pressures, thedischarge from a single sprinkler was sufficient to limit or suppress the heat generated from the fire. Thisconcept is called “hydraulic increase.” Hydraulic increase can also occur when a water supply’s capabilitiesduring the fire event exceeded that required by the minimum design requirements of the standard. Sincenone of the data used to generate the previously mentioned statistics captured the capabilities of the watersupply in relation to the design requirements, the impact of the hydraulic increase on the number of singlesprinkler activations cannot be determined.

But if the minimum water supply requirement of the standard is reduced to only be capable of handling asingle sprinkler, then there could be no hydraulic increase safety factor. When the first sprinkler opens, itwill only get the flow and pressure that were originally designed for it, and the potential is significant for thatto be insufficient to control the fire, given any obstructions and the layout of the space where the fire starts.

The National Institute for Standards and Technology (NIST), under a grant from the United States FireAdministration, studied this concept several years ago in the hopes of being able to propose a single-sprinkler flow for the 2007 edition of NFPA 13D (see NIST Report NIST GCR 05-875 prepared byUnderwriters Laboratories with a publication date of February 2004). Unfortunately, the research did notsupport the design of a sprinkler system with only the flow for a single sprinkler, even under conditions ofsmall rooms with flat, smooth ceilings. Without the hydraulic increase associated with the two-sprinklerdesign, the fire scenarios were too many where the first sprinkler to open would have insufficient flow tocontrol the fire and then multiple sprinklers would open, causing the room to reach untenable conditionsand the water supply to be overrun. These same fire scenarios were easily controlled by a sprinkler systemdesigned for a two-sprinkler water supply from the start.

In addition to the NIST tests, the National Fire Sprinkler Association conducted a series of full-scale firetests in simulated bedrooms that were 14 ft × 14 ft (4.2 m × 4.2 m) with an adjoining hallway, each with flat,smooth, 8 ft (2.4 m) high ceilings. The tests were performed to determine better rules for keeping sprinklersclear of obstructions like ceiling fans, but baseline tests were also performed without any obstructions at theceiling. In nine out of the twelve tests, including the two baseline tests without obstructions at the ceiling, asprinkler in the hall outside the room of fire origin opened first, followed by the sprinkler in the room oforigin. Even though the room of origin met all of the rules of NFPA 13D as a compartment, a sprinkleroutside of this room was opening first. All of these fires were controlled by the sprinklers, but if the watersupply had only been sufficient for a single sprinkler, the sprinklers might not have been able to provide firecontrol.

For examples of selecting a compartment for consideration, see Figure A.10.2(a) and Figure A.10.2(b),which show examples of design configurations for compartments based on the presence of lintels to stopthe flow of heat.

Figure A.10.2(a) Sprinkler Design Areas for Typical Residential Occupancy — Without Lintel.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

120 of 129 11/3/2016 12:03 PM

Figure A.10.2(b) Sprinkler Design Areas for Typical Residential Occupancy — With Lintel.

d

Additional Proposed Changes

File Name Description Approved

scan0855.pdf Figure A.10.2(b) with suggested correction

Statement of Problem and Substantiation for Public Input

NFPA 13D, 2016 Figure A.10.2(b) currently depicts only an 8" lintel between the Dining and Living Room which meets the compartment definition in the 2007 NFPA 13D standard. Beginning in 2010 NFPA 13D standard, a compartment is limited to 8' wide openings per wall. See NFPA 13D section 3.3.1 for the definition of a compartment. The figure needs to be changed as suggested to depict the maximum permitted 8' wide opening.

Submitter Information Verification

Submitter Full Name: Daniel Mathias

Organization: Absolute Fire Protection, Inc

Affilliation: AFSA

Street Address:

City:

State:

Zip:

Submittal Date: Tue Jun 28 09:39:04 EDT 2016

Committee Statement

Resolution: FR-31-NFPA 13D-2016

Statement: NFPA 13D, 2016 Figure A.10.2(b) currently depicts only an 8" lintel between the Dining and LivingRoom which meets the compartment definition in the 2007 NFPA 13D standard. Beginning in 2010NFPA 13D standard, a compartment is limited to 8' wide openings per wall. See NFPA 13D section3.3.1 for the definition of a compartment. The figure needs to be changed as suggested to depict themaximum permitted 8' wide opening.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

121 of 129 11/3/2016 12:03 PM

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

122 of 129 11/3/2016 12:03 PM

Public Input No. 82-NFPA 13D-2016 [ New Section after A.12.3.5.1.3 ]

TITLE OF NEW CONTENT

A.12.3.6.1 This section only addresses sprinkler systems in detached dwellings or manufactured homesbecause there are no other occupants in adjacent dwelling units affected by the inactive system.

Statement of Problem and Substantiation for Public Input

There needs to be guidance for taking a system out of service. There are many instances when an installed system needs to be taken out of service such as for shipping or storage of a manufactured home, or when extensive renovation or remodeling work is going on in the home, or when the home will be unoccupied for an extended period of time. NFPA 13D sprinkler systems are life safety systems and do not need to remain active when the home is being shipped, stored or is unoccupied. This guidance is especially needed when the detached dwelling or manufactured home is subject to freezing temperatures. Once the home is to be occupied again, the system must be tested for leaks and the system and components inspected and testing before restored to service.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 81-NFPA 13D-2016 [New Section after 12.3.5.1.4.2]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 11:36:31 EDT 2016

Committee Statement

Resolution: Added to main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

123 of 129 11/3/2016 12:03 PM

Public Input No. 83-NFPA 13D-2016 [ New Section after A.12.3.5.1.3 ]

TITLE OF NEW CONTENT

A. 12.3.6.2.1 For drops less than 4” long, the branch line piping and the drops can both be installed in areasbelow 40°F (4°C). Tests have been conducted that prove that as long as the branch line is empty of waterand water is in a drop, when ice forms it will expand into the branch piping without harming the sprinkler orthe system piping.

Statement of Problem and Substantiation for Public Input

There needs to be guidance for taking a system out of service. There are many instances when an installed system needs to be taken out of service such as for shipping or storage of a manufactured home, or when extensive renovation or remodeling work is going on in the home, or when the home will be unoccupied for an extended period of time. NFPA 13D sprinkler systems are life safety systems and do not need to remain active when the home is being shipped, stored or is unoccupied. This guidance is especially needed when the detached dwelling or manufactured home is subject to freezing temperatures. Once the home is to be occupied again, the system must be tested for leaks and the system and components inspected and testing before restored to service.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 81-NFPA 13D-2016 [New Section after 12.3.5.1.4.2]

Submitter Information Verification

Submitter Full Name: Terry Victor

Organization: Tyco Simplex Grinnell

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jun 29 11:39:38 EDT 2016

Committee Statement

Resolution: Added to main body of document.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

124 of 129 11/3/2016 12:03 PM

Public Input No. 2-NFPA 13D-2015 [ Chapter B ]

Annex B Informational References

B.1 Referenced Publications.

The documents or portions thereof listed in this annex are referenced within the informational sections ofthis standard and are not part of the requirements of this document unless also listed in Chapter 2 for otherreasons.

B.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 13R, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies, 2016edition.

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016edition.

NFPA 72 ®, National Fire Alarm and Signaling Code, 2016 edition.

B.1.2 Other Publications.

B.1.2.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A 135 A135 /A135M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 20062009, reapproved 2014 .

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of Building Materials, 20092015b .

ASTM F 437 F437 , Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 80, 1996 2015 .

ASTM F 438 F438 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe Fittings, Schedule 40, 1997 2015 .

ASTM F 439 F439 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe Fittings, Schedule 80, 1997 2013 .

ASTM F 442 F442 /F442M , Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe (SDR-PR), 1997 2015a .

ASTM F 876 F876 , Standard Specification for Crosslinked Polyethylene (PEX) Tubing, 2008 2015a .

IEEE/ ASTM SI 10, Standard for Use of the International System of Units (SI): The Modern Metric System,1997 2010 .

B.1.2.2 FPRF Publications.

Fire Protection Research Foundation, 1 Batterymarch Park, Quincy, MA 02169.

“Analysis of the Performance of Residential Sprinkler Systems with Sloped or Sloped and BeamedCeilings,” July 2010.

Antifreeze Solutions Supplied through Spray Sprinklers – Interim Report, February, 2012.

Antifreeze Systems in Home Fire Sprinkler Systems — Literature Review and Research Plan, June 2010.

Antifreeze Systems in Home Fire Sprinkler Systems — Phase II Final Report, December 2010.

“Sprinkler Insulation: A Literature Review,” July 2011.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

125 of 129 11/3/2016 12:03 PM

B.1.2.3 NFIRS Publications.

National Fire Incident Reporting System, U.S. Fire Administration, 16825 S. Seton Avenue, Emmitsburg,MD 21727.

NFIRS 5.0, Program Manager Toolkit (CD-ROM).

B.1.2.4 NFSA Publications.

National Fire Sprinkler Association, P.O. Box 1000 40 Jon Barrett Road , Patterson, NY 12563.

Valentine and Isman, Kitchen Cabinets and Residential Sprinklers, November 2005.

Valentine and Isman, Interaction of Residential Sprinklers, Ceiling Fans and Similar Obstructions,November 2005.

B.1.2.5 NIST Publications.

National Institute of Standards and Technology, 100 Bureau Drive, Gaithersburg, MD 20899-1070.

NIST GCR 05-875, Research Investigation for Determination of Residential Sprinkler Performance,February 2004.

B.1.2.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/ UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2010 2013 .

ANSI/ UL 1626, Residential Sprinklers for Fire-Protection Service, 2008, revised 2012 .

B.2 Informational References. (Reserved)

B.3 References for Extracts in Informational Sections.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016edition.

Statement of Problem and Substantiation for Public Input

Referenced current SDO names, addresses, standard names, numbers, and editions.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 1-NFPA 13D-2015[Chapter 2]

Referenced current SDO names, addresses, standard names,numbers, and editions.

Submitter Information Verification

Submitter Full Name: Aaron Adamczyk

Organization: [ Not Specified ]

Street Address:

City:

State:

Zip:

Submittal Date: Sun Dec 20 17:35:55 EST 2015

Committee Statement

Resolution: Agree with submitter. First draft revision created.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

126 of 129 11/3/2016 12:03 PM

Public Input No. 8-NFPA 13D-2016 [ Section No. B.1.1 ]

B.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2016 edition.

NFPA 13R, Standard for the Installation of Sprinkler Systems in Low-Rise Residential Occupancies, 2016edition.

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2016edition.

NFPA 72 ®, National Fire Alarm and Signaling Code, 2016 edition.

NFPA 286, 2015 edition.

Statement of Problem and Substantiation for Public Input

needed for correlation with input on annex section.

Related Public Inputs for This Document

Related Input Relationship

Public Input No. 7-NFPA 13D-2016 [Section No. A.1.1]

Submitter Information Verification

Submitter Full Name: Marcelo Hirschler

Organization: GBH International

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 17:57:02 EST 2016

Committee Statement

Resolution: FR-43-NFPA 13D-2016 Agree with submitter. First draft revision created. Staff to update allreferenced publications.

Statement: needed for correlation with input on annex section.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

127 of 129 11/3/2016 12:03 PM

Public Input No. 5-NFPA 13D-2016 [ Section No. B.1.2.1 ]

B.1.2.1 ASTM Publications.

ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959.

ASTM A 135 A135/A135M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 2006 2009(2014) .

ASTM E 84 E84 , Standard Test Method for Surface Burning Characteristics of Building Materials,2009 2015b .

ASTM F 437 F437 , Standard Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe Fittings, Schedule 80, 1996 2015 .

ASTM F 438 F438 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe Fittings, Schedule 40, 1997 2015 .

ASTM F 439 F439 , Standard Specification for Socket-Type Chlorinated Poly (Vinyl Chloride) (CPVC)Plastic Pipe Fittings, Schedule 80, 1997 2013 .

ASTM F 442 F442/F442M , Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) PlasticPipe (SDR-PR), 1997 2013 e1 .

ASTM F 876 F876 , Standard Specification for Crosslinked Polyethylene (PEX) Tubing, 2008 2015a .

IEEE/ASTM SI 10, Standard for Use of the International System of Units (SI): The Modern Metric System,1997.

Statement of Problem and Substantiation for Public Input

date updates

Submitter Information Verification

Submitter Full Name: Marcelo Hirschler

Organization: GBH International

Street Address:

City:

State:

Zip:

Submittal Date: Wed Jan 06 17:41:24 EST 2016

Committee Statement

Resolution: Agree with submitter. First draft revision created.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

128 of 129 11/3/2016 12:03 PM

Public Input No. 55-NFPA 13D-2016 [ Section No. B.1.2.6 ]

B.1.2.6 UL Publications.

Underwriters Laboratories Inc., 333 Pfingsten Road, Northbrook, IL 60062-2096.

ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, 2008, Revised2010 2013 .

ANSI/UL 1626, Residential Sprinklers for Fire-Protection Service, 2008, Revised 2012 .

Statement of Problem and Substantiation for Public Input

This proposed change reflects updates to referenced UL Standards that are referenced.

Submitter Information Verification

Submitter Full Name: Ronald Farr

Organization: UL LLC

Street Address:

City:

State:

Zip:

Submittal Date: Mon Jun 27 15:30:36 EDT 2016

Committee Statement

Resolution: Agree with submitter. First draft revision created.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...

129 of 129 11/3/2016 12:03 PM