PSV Calculation.ppt

79
OIL & GAS WorleyParsons OIL&GAS PSV Sizing Calculation PSV Sizing Calculation 23-June-05 23-June-05

description

PSV Calculation

Transcript of PSV Calculation.ppt

Page 1: PSV Calculation.ppt

OIL & GAS

WorleyParsons

OIL&GAS

PSV Sizing CalculationPSV Sizing Calculation

23-June-0523-June-05

Page 2: PSV Calculation.ppt

OIL & GAS

CONTENTCONTENT

• INTRODUCTION

• PSV TYPES

• CHATTERING PROBLEM

• SIZING CALCULATION

• EXAMPLE

Page 3: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

• Relief systems are provided on a platform in order to ensure the safe operation of the facilities.

• In accordance with API RP 14C, all hydrocarbons handling equipment and pressure vessels will be provided with two levels of over protection, high pressure trip (PSHH) with shutdown action, and protection by mechanical devices, Pressure Safety Valve (PSV) or Rupture Disc.

• PSVs are installed at every point identified as potentially hazardous, that is, at points where upset conditions create pressure which may exceed the maximum allowable working pressure.

Page 4: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

How High Pressure Develop

• Over heating • High head ( from pumping or compression) • Over Filling • Failure of Regulator / Control valve. • External Fire • Runaway Reaction • Combustion of gas/dust • Freezing • Thermal Expansion• Loss of Mixing • Others

Page 5: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

Definitions

• Operating pressureOperating pressure : The gauge pressure during normal service.

• Set PressureSet Pressure : The pressure at which the relief device begins to activate or open.

• Maximum Allowable Working Pressure (MAWP)Maximum Allowable Working Pressure (MAWP) : The maximum guage pressure permissible at the top of a vessel for a designated temperature.Vessel fails at 4 to 5 times of MAWP!!!! . But only hydrostatically tested to 1.5 times.

• AccumulationAccumulation : The pressure increase over the maximum allowable working pressure of a vessel during the relief process. Expressed as % of MAWP.

Page 6: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

Set Pressure

Relief begin to open

Accumulation

Pressure

Time

Page 7: PSV Calculation.ppt

OIL & GAS

Definitions

• Over PressureOver Pressure : The pressure increase in vessel over the set pressure during the relieving process. Overpressure is equivalent to the accumulation when the set pressure is at the MAWP. Expressed as % of set pressure. Must be specified prior relief design. Typically 10 % ( or for fire 21%) will be used.

Pressure

Time

Relief begin to open

Set Pressure

Over Pressure

INTRODUCTIONINTRODUCTION

Page 8: PSV Calculation.ppt

OIL & GAS

Definitions

• Blow-downBlow-down : The pressure difference between the relief set pressure and the relief reseating pressure.

• Maximum Allowable Accumulated PressureMaximum Allowable Accumulated Pressure : The sum of the maximum allowable working pressure plus the allowable accumulation.

INTRODUCTIONINTRODUCTION

Page 9: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

Guideline for relief pressures (Adapted from API RP 520 : “ Sizing, Selection, and Installation of Pressure-Relieving Devices in “ Sizing, Selection, and Installation of Pressure-Relieving Devices in Refineries.”Refineries.” , page 3)

Page 10: PSV Calculation.ppt

OIL & GAS

Definitions

• Back PressureBack Pressure : The pressure at the outlet of the relief device during the relief process due to pressure in the discharge system.

1. Superimposed Back Pressure. 2. Built-up Back Pressure.

Total Back Pressure = Superimposed Back Pressure + Built-up Back Pressure

INTRODUCTIONINTRODUCTION

Page 11: PSV Calculation.ppt

OIL & GAS

INTRODUCTIONINTRODUCTION

Definitions

1. Superimposed Back Pressure is the back pressure which may exist at the outlet of a particular relief valve when connectedto a closed system. The pressure can be constant or variable. The Superimposed back pressure always exists even when the reliefvalve is closed.

2. Built-up Back Pressure is the pressure at the discharge of a relief device which develops due to the relief flow through the device when the relief valve opens. The built-up back pressuredepends on the valve itself but also on the design of the relief piping. It can reach excessive values in the case of vary high set pressures and/or poorly designed piping with too much pressureLoss. The built-up back pressure is variable.

Page 12: PSV Calculation.ppt

OIL & GAS

PSV TYPESPSV TYPES

General Design of PSV

1. Direct acting type

• Oldest and most common.• Kept closed by a spring or weight to oppose lifting force of process pressure.

2. Balanced Bellows.

3. Pilot operated type

• Kept closed by process pressure

4. Modulating Pilot.

Page 13: PSV Calculation.ppt

OIL & GAS

PSV TYPESPSV TYPES

The following types of PSV are generally used.

1. Conventional PSV2. Balanced Type PSV (Balanced Bellow)3. Pilot Operated PSV4. Modulating Pilot Operated PSV5. Thermal PSV

Page 14: PSV Calculation.ppt

OIL & GAS

PSV TYPESPSV TYPES

Conventional PSV Advantages• Most reliable type if properly sized and operated• Versatile -- can be used in many services• Compatible with fouling or dirty service.

Disadvantages• Relieving pressure affected by back pressure• Susceptible to chatter if built-up back pressure is too high

Page 15: PSV Calculation.ppt

OIL & GAS

Balanced Bellow PSV

PSV TYPESPSV TYPES

Advantages• Relieving pressure not affected by back pressure.• Can handle higher built-up back pressure.• Protects spring from corrosion.• Wide range of materials available & chemical compatibility.

Disadvantages• Bellows susceptible to fatigue/rupture.• May release flammables/toxics to atmosphere.• High maintenance costs.

Page 16: PSV Calculation.ppt

OIL & GAS

Pilot Operated PSV Advantages• Relieving pressure not affected by backpressure• Can operate at up to 98% of set pressure• Less susceptible to chatter (some models)

Disadvantages• Pilot is susceptible to plugging (therefore not recommended for fouling service, eg. Wax).• Limited chemical and high temperature use by “O-ring” seals• Vapor condensation and liquid accumulation above the piston may cause problems• Potential for back flow

PSV TYPESPSV TYPES

Page 17: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Modulating Pilot Operated

There are two main types of pilot control operation

• Pop action : Main valve fully open at set pressure

• Modulating : Main valve opens according to relief demand.

Modulating pilots have additional advantages:

• They only open the main valve enough to keep the system at set pressure which leads to less wasted product being relieved

through the valve.

• Less noise generated by the valve when it is required to relieve.

• Recommended for Wellhead platform PSV.

Page 18: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Main valvepiston lift

Pressure

Opening

Closing

100 % Lift POP Action

Page 19: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Main valvepiston lift

Pressure

OpeningClosing

100 % LiftModulating

Page 20: PSV Calculation.ppt

OIL & GAS

Chattering Problem

• Chattering is the rapid, alternating opening and closing of a PSV.

• Resulting vibration may cause misalignment, valve seat damage and, if prolonged, can cause mechanical failure of valve internals and associated piping.

• Chatter may occur in either liquid or vapor services

CHATTERING PROBLEMCHATTERING PROBLEM

Page 21: PSV Calculation.ppt

OIL & GAS

Cause of Chattering

• Excessive inlet pressure drop

• Excessive built-up back pressure

• Oversized valve

• Valve handling widely differing rates

CHATTERING PROBLEMCHATTERING PROBLEM

Page 22: PSV Calculation.ppt

OIL & GAS

Excessive inlet pressure drop

• Normal PSV has definite pop and reseat pressures.

CHATTERING PROBLEMCHATTERING PROBLEM

Reseat or close pressure Pop or opening pressure

Blow-down = Different between pop and reseat pressure

Page 23: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Excessive inlet pressure drop : Solution

If you can’t change the piping

• Install smaller PSV

• Install different type of PSV

Page 24: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Excessive Built-up Back Pressure

Excessive outlet pressure will also cause chatter.

Avoid• Long outlet piping runs.• Elbows and turns.• Sharp edge reductions.

But if you must• Make outlet piping large!

Page 25: PSV Calculation.ppt

OIL & GAS

CHATTERING PROBLEMCHATTERING PROBLEM

Improper Valve Size

Oversized valve• Must flow at least 25% of capacity to keep valve open.• Especially bad in larger sizes.

Valve handling widely differing rates

• Leads to oversized valve case.

Page 26: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Step Of Sizing CalculationDevelop Process Safety Diagram (PSD)

Develop relief scenarios by using general possible cause and PSD

Determine required relief area for each cases (Gas, Liquid, 2-Phases)

Choose the worst case scenario to be a governing case

Select proper orifice and valve body size based on STD

Calculate inlet line size (Line ∆P < 3%of RP)

Perform preliminary estimate of tail pipe

Perform Flare system modeling to indicate total back pressure and most suitable tail pipe size.

Select PSV type (Conventional, Balanced Bellow, Pilot Operated

Page 27: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Develop Process Safety Diagram (PSD)

Process safety diagram is the diagram which showall installation of all process safety equipments (PSHH,TSHH, PSV, BDV, Rupture disc, etc.) intend to be used inevaluation of all possible relieving scenarios in processfacilities. Process safety diagram must be developed beforeperforming any PSV calculation.

Page 28: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Develop Process Safety Diagram (PSD)

Page 29: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Develop relief scenarios by using general possible cause and PSD

EquipmentPossible Scenarios

PumpHEX LineVessel / Column

Compressor

Blocked Outlet

Thermal Expansion

Tube Rupture

Gas Blow-by

Inlet Control Valve Failure

Exterior Fire

Note : Exterior Fire is not applicable for PHEX!!

Page 30: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Blocked Outlet/ Blocked Discharge

CLOSED

CLOSED

CLOSED

CLOSED

CLOSED

Process Vessel

Compressor Pump

This situation arises from the inadvertent closure of a block valve or failure of a control valve in the closed position on an outlet line. Typical overpressure application where this form of protection is required includes production separators, compressor discharge piping or pump discharge piping. The safety relief valves are sized to handle 100% of the anticipated upstream flow. If the feed stream(s) is multi-phase, the relief rate is the total inlet flow (gas plus liquids).

Page 31: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Thermal Expansion/ Thermal Relief

Heat Exchanger

Line

Hot Side

Cold Side

CLOSED CLOSED CLOSED

Thermal expansion relief valves (TERV’s) are required in liquid-full systems if the system can be blocked in and/or subjected to heat input from the atmosphere or process that results in overpressure.

Page 32: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Tube Rupture

Heat Exchanger

Hot Side

Cold Side OR

Heat Exchanger

Hot Side

Cold Side

Tube rupture causing vapour to enter either the tubeside or shellside of a heat exchanger will cause a pressure spike to travel through the fluid at sonic velocity. Generally, a PSV will not lift fast enough to protect the system. Protection against tube rupture is typically by the use of bursting discs.

Page 33: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Suddenly OpeningPressure at PSHHLiquid at LSLL

Gas blow-by occurs when liquid level in a partially filled vessel drops so low that gas exits via the liquid outlet nozzle due to level control failure. Loss of liquid level will result in gas from the high pressure vessel passing into the low pressure system downstream of the liquid level control valve.

Gas Blow-by

Page 34: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Fail to openPressure at normalLiquid at normal

Inlet Control Valve Failure

The relief rate is equal to the difference between the maximum inlet flow and the flow, at relief conditions, from the outlet valves that remain open. No credit for outlet valves response will be taken i.e. they will be assumed to remain at their normal operating point

(% open).

Page 35: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Exterior Fire

Generally, the production & processing facilities will be segregated into fire areas, by means of plated decks, fire walls, or edge of the platform. During a fire in one of the fire areas, all equipment within that area is assumed to be fully exposed to the fire.

It is assumed that during a fire there is no feed to or product from an affected system, and all normal heat inputs have ceased.

• No credit will be taken for the presence of any water spray systems. • No credit will be taken for thermal insulation on vessels.

Page 36: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Pool Fire Jet Fire

Fire Type

Systems with significant liquidhydrocarbon inventory will be considered for pool fire case. Heat flux will be calculated as per API RP521. Credit for a 40% reduction in heat flux may be taken for good drainage and the presence of prompt fire fighting efforts as specified in API RP 521.

Where potential for jet fire exists, relief load will be calculated for higher heat flux from heat fire. The heat flux generated by jet fire ranges from 50 kW/m2 to 300 kW /m2. However, the net heat flux into the fluid will depend on many factors such as fuel type, vessel temperature, the surface emissivity, the fire environment, the radiative and convective components of the fire.

Page 37: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Vessel Type & Fluid relief type

Vessel type could be :

• Dry or empty vessel• Vessels containing liquid -> Need to consider effect of wetted area of vessel

Fluid relief type could be :

• Fluid is sub-critical: P<0.9*Pc• Fluid is near its critical pressure: 0.9Pc < P < 1.1*Pc• Fluid is super critical (dense phase): P > 1.1*Pc

Pc = Critical PressureP = Relieving Pressure

Page 38: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Fire case

Jet Fire

Dry Vessel Wetted vessel

Sub Critical FlowNear Critical FlowSuper Critical Flow

Pool Fire2 CASES

2 CASES

3 CASES

Totally = 2x2x3 = 12 cases possibleHence 12 methods of calculation for Fire case

Page 39: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Determine required relief area for each case (Gas, Liquid, 2-Phases)

Target of sizing relief valve

1. Determine the relief rate.2. Determine the required relief area.3. Select the standard relief area.

Code and standard required

API RP 520 : “ Sizing, Selection, and Installation of Pressure-Relieving “ Sizing, Selection, and Installation of Pressure-Relieving Devices in Refineries.”Devices in Refineries.”

API RP 521 : “ Guide for Pressure Relieving and Depressuring Systems.”“ Guide for Pressure Relieving and Depressuring Systems.”

Page 40: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Relief Phase

Single Phase Relief

Two Phase Relief

Vapor Phase Relief

Liquid Phase Relief

Relief Type

Continuous Relief

Transient Relief Thermal Relief

Generally

Gas/Vapor

Steam

Relief fluid category

Determine required relief area for each case (Gas, Liquid, 2-Phases)

Page 41: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

• Determine relief rate, some cases (eg. Gas blow-by, tube rupture, fire case etc.) are very complicated and contain many steps of calculation especially fire case.

• API RP520/ 521 shows the simple method of calculation in order to determine the relief rate. This does not govern all relief scenarios. Hence some companies have developed their own procedure to determine the relief rate.

Determine required relief area for each case (Gas, Liquid, 2-Phases)

Page 42: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Vapor Phase Relief

• Relief valves for single phase vapour flow will be sized according to the methodology presented in API RP 520, Section 3 (reference 4).

• The sizing equations fall into 2 categories, depending on whether flow is critical or subcritical.

• The critical pressure must be checked using the equation below:

)1(

1 1

2.

kk

cf kPP

where Pcf = critical flow throat pressure (psia)P1 = upstream relieving pressure (psia)k = ratio of specific heats

Ref. API 520 section 3.6.1.4

Page 43: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Vapor Phase Relief

• If flow is critical (Pcf > downstream pressure P2), the critical sizing equation is used:

AW

CK PK

TZ

Md b

1

Ref. API 520 section 3.6.2.1

WhereA = required effective discharge area of the valve ( in2).W = required flow through the valve (lb/hr).C = coefficient determined from an expression of the ratio of the specific heats of the gas

or vapour at standard conditions. This can be obtained from Figure 26 or Table 9 in API 520.Kd = effective coefficient of discharge = 0.975 P1 = upstream relieving pressure, in psia.Kb = capacity correction factor due to back-pressure. This can be obtained from the manufacturer’s literature or estimated from Figure 27 in API 520. The back-pressure correction factor applies to balanced-bellows valves only.T = relieving temperature of the inlet gas or vapour, in R.Z = compressibility factor for the deviation of the actual gas from a perfect gas, a ratio evaluated at inlet conditions.M = molecular weight of the gas or vapour.

Page 44: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Vapor Phase Relief

• If flow is subcritical, the following equation will be used:

)(..735 2112 PPPM

ZT

KF

WA

d Ref. API 520 section 4.3.3.1

Where A = required effective discharge area of the valve, in square inches.W = required flow through the valve, in pounds per hour.F2 = coefficient of subcritical flow

=

r

rr

k

k kk

k

1

1)(

)1(

12

Ref. API 520 section 4.3.3.1

Page 45: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

k = ratio of the specific heats.r = ratio of back pressure to upstream relieving pressure, P2 /P1.Kd = effective coefficient of discharge = 0.975Z = compressibility at relieving inlet conditions.T = relieving temperature of the inlet gas or vapour (R) M = molecular weight of the gas or vapour.P1 & P2 = upstream relieving pressure and back-pressure pressure respectively (psia)

Vapor Phase Relief

Page 46: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Vapor Phase Relief

• Relief valves in steam service will be sized as follows:

AW

PK K Kd N SH

515 1.

Ref API 520 Section 3.7.1

WhereA = required effective discharge area of the valve ( in2).W = required flow through the valve (lb/hr).P1 = upstream relieving pressure (psia)Kd = effective coefficient of discharge = 0.975KN = correction factor for Napier equation.

= 1 where P1 1515 psia.= (0.1906P1 – 1000)/(0.2292P1 – 1061) where P1 1515 psia and 3215 psia

KSH = superheat steam correction factor. This can be obtained from Table 9 in API RP520. For saturated steam at any pressure, KSH- = 1.0.

Page 47: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Liquid Phase Relief

• For single phase liquid flow, the sizing method specified for certified relief valves will be used.

• The following equation only applies to non-flashing liquids.

AQ

K K K

G

P Pd w v

38 1 2

Ref. API 520 section 4.5.1

Where A = required effective discharge area of the valve ( in2).Q = flow rate, in U.S. gallons per minute.Kd = effective coefficient of discharge that should be obtained from the valve manufacturer. For a preliminary sizing estimation, a discharge coefficient of 0.65 can be used.Kw = correction factor due to back-pressure. If the back-pressure is atmospheric, KW = 1. Balanced-bellows valves in back-pressure service will require the correction factor determined in Figure 31 in API RP520. Conventional valves require no special correction.K-V = correction factor due to viscosity as determined from Figure 32 in API RP520.G = specific gravity of the liquid at the flowing temperature referred to water = 1.0 at 70°F.P1 = upstream relieving pressure, set pressure plus allowable overpressure (psia).P2 = back-pressure (psia).

Page 48: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Two Phase Relief

• For 2-phase relief, the methodology in the newly released API 520 Part 1 Appendix D “Sizing for Two-Phase Liquid/Vapour Relief ” shall be used (see Appendix 1).

• This method has superseded the previous API methods because, in certain circumstances, it has been found that the previous API methods for 2-phase flow can undersize PSVs significantly.

• This sizing method is based on the Leung Omega method, which assumes thermal and mechanical equilibrium; these assumptions correspond to the Homogeneous Equilibrium Model (HEM).

Page 49: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

• Required relief area is calculated from relief rate. Hence relief rate calculation is very important step

• The case which giving the maximum relief area will be a governing case.

Choose the worst case scenario to be a governing case

Determine required relief area for each case (Gas, Liquid, 2-Phases)

Page 50: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

• Selected standard relief area follows API RP526 or GPSA chapter 5 Figure 5-7

• Valve body size ( Inlet diameter x Outlet diameter) follows API STD 526 “Flanged Steel Pressure Relief Valve 4th Ed June 1995”

• Rated flow = (STD relief area) x Relief rate (Required relief area)

Select proper orifice and valve body size based on STD

Page 51: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Calculate inlet line size (Line ∆P < 3%of RP)

• Inlet line sizing is based on pressure drop less than 3 % of relieving pressure

Inlet Line design Consideration

• Inlet line size must be at least equal to PSV inlet flange size.

• Inlet piping should slope continuously upward from vessel to avoid traps.

• Inlet piping should be heat traced if freezing or congealing of viscous liquids could occur.

Page 52: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Inlet Line design Consideration

• A continual clean purge should be provided if coke/polymer formation or solids deposition could occur

• CSO valves should have the stem horizontal or vertically downward

Page 53: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Perform preliminary estimate of tail pipe

• Discharge line sizing is based on Mach No. less than 0.75

Tail Pipe Design Consideration

• Discharge line diameter must be at least equal to PSV outlet flange size.

• Atmospheric risers should discharge at least 10 ft above platforms within 50 ft horizontally

• Radiant heat due to ignition of release should be considered.

Page 54: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Tail Pipe Design Consideration • No check valves, orifice plates or other restrictions permitted.

• Atmospheric discharge risers should have drain hole.

• CSO valves should have the stem oriented horizontally or vertically. • Piping design must consider thermal expansion due to hot/cold release.

• Autorefrigeration and need for brittle fracture resistant materials.

Page 55: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Tail Pipe Design Consideration

• Closed discharge piping should slope continuously downward to header to avoid liquid traps

Page 56: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Page 57: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Perform Flare system modeling to indicate total back pressure and most suitable tail pipe size.

Page 58: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Select PSV type (Conventional, Balanced Bellow, Pilot Operated

TypeValue

(% if set) Conventional Balanced Bellow Pilot Operated

Effects on Valves : Gas applicationsBack Pressure

Constant

VariableSuperimposed

VariableBuilt-up

< 30%

30-50%

>50%

No effect

Lift/Capacity reduced No effectSet point increased

by back pressure

Set point increased by back pressure Flow become sonic

Generally unstable Do not use

Flow become subsonic

Set point varieswith back pressure

10-30%

< 10% No effect

> 50%

30-50%Unstable

Do not use Lift/Capacity reduced

Generally unstable Do not use

No effect

Flow become subsonic

< 10%

Unstable Do not use

Lift/Capacity reduced

No effect No effectNo effect

Generally unstable Do not use

10-30%

> 50%Flow become

subsonic

Page 59: PSV Calculation.ppt

OIL & GAS

SIZING CALCULATIONSIZING CALCULATION

Select PSV type (Conventional, Balanced Bellow, Pilot Operated

TypeValue

(% if set) Conventional Balanced Bellow Pilot Operated

Effects on Valves : Liquid applicationsBack Pressure

Constant

VariableSuperimposed

VariableBuilt-up

< 20%

20-50%

>50%

No effect

Lift/Capacity reduced No effect

Set point increased by back pressure

Set point increased by back pressure Flow become sonic

Generally unstable Do not use

Set point varieswith back pressure

10-20%

< 10% No effect

> 50%

20-50%Unstable

Do not use Lift/Capacity reduced

Generally unstable Do not use

No effect

< 10%

Unstable Do not use

Lift/Capacity reduced

No effect No effect

No effect

Generally unstable Do not use

10-20%

> 50%

Page 60: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

DP = 400 psigPAH = 350 psigOP = 275 psigOT = 80 oF

DP = 250 psigOT = 130 oF

CV = 433

SP = 250 psig

SP = 400 psig

CV = 433FC

FC

V-1

V-2

F-1

F-2

Process Schematic

PSV-1

PSV-2

Page 61: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Assess Relief Scenarios

Scenario Source of Overpressure

JudementScenario to be

considered separately

1 Fire Case An external fire could cause the pressurein V-6010 to rise to the relief valve setting through vaporization of liquids. Equipment layout shown no potential that “jet fire” will happen on located area thus “pool fire” will be determined as a basis for calculation.

Yes

2 Tube Rupture This case is not applicable. No

3 Inlet control valve failure

CVs are fail to close type therefore this caseis not applicable for sizing PSV.

No

Page 62: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Scenario Source of Overpressure

JudementScenario to be

considered separately

4 Gas Blow-by Gas blow-by can occur by • Liquid in a V-1 drop so low that gas exits via the liquid outlet nozzle due to level control failure. Loss of liquid level will result in gas from V-1 passing into V-2 via F-1 and/or F-2.

Gas blow-by is based on follow assumption

• Control valve upstream fails 100 % open• The upstream pressure is at the high pressure alarm.• The downstream pressure is 110 % of the set point of the relief valve on the downstream vessel.• No possibility that the bypass valve around the control valve is opened.

Yes

Assess Relief Scenarios

Page 63: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Scenario Source of Overpressure

JudementScenario to be

considered separately

5 Blocked Outlet1. Water Blocked Discharge. This scenario will relates to two trips; first LIAHH and secondly LAHH. Credit can be taken that either of these two will actuate. It is unreasonable to assume both will fail to response. Hence, this scenario cuts off the feed to vessel and no relief is needed.2. Oil Blocked Discharge. This scenario relates to only oil trip, whileinterface level is already healthy. No credit can be taken that this trip will work. Hence PSV needs oil relief.

Yes

Assess Relief Scenarios

6 Thermal Relief This case is not applicable. No

Page 64: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Possible Relief Scenarios

There are three different possible relief scenarios :• Fire Case.• Gas Blow-by Case. • Blocked Outlet Case.

Page 65: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Fire Case

ScenarioAn external fire could cause the pressure in V-2 to rise to the relief valve setting through vaporization of liquids. Equipment layout shown no potential that “jet fire” will happen on located area thus “pool fire” will be determined as a basis for calculation.

Relief Condition

PSV-2 set pressure = 250 psigAllowable Accumulation = 21%Maximum allowable accumulated pressure = 250x1.21 = 302.5 psig.Relieving temperature = ????

Page 66: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Fire Case

250 psig@61 min , relief temperature = 191.5 oF

Since relief can be initiated after 61 min fired but API RP 520 allow 15 min to handle fire hence “this case will rarely happen in real operation.”

Page 67: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Fire Case

By input all required parameters (eg. Vessel dimensions, fluid relieving properties), in to calculation sheet (WS-CA-PR-025, Rev 0)

Required relief area = 0.183 in2

Relief Load = 4,066 lb/hr

Therefore

Select 1xEx2 orifice with discharge area of 0.196 in2

Page 68: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Gas Blow-by

Scenario Liquid in a V-1 drop so low that gas exits via the liquid outlet nozzle due to level control failure. Loss of liquid level will result in gas from V-1 passing into V-2 via F-1 and/or F-2.

Gas blow-by is based on follow assumption

• Control valve upstream fails 100 % open.• The upstream pressure is at the high pressure alarm.• The downstream pressure is 110 % of the set point of the relief valve on the downstream vessel.• No possibility that the bypass valve around the control valve is opened as locked close. (Note : This may need to be considered in some cases).Relief ConditionPSV-2 set pressure = 250 psigAllowable Accumulation = 10%Maximum allowable accumulated pressure = 250x1.1 = 275 psig.

Page 69: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Gas Blow-by

Assume F-1 and F-2 are same maximum Cv of 433.C1 assumed 26.5 (C1 is normally obtained from valve vendor) Assume only one control valve is fail.

Therefore Cg = C1 x Cv = 433 x 26.5 = 11,474.5V-1 hold pressure at PAH = 350 psig V-2 operating pressure = 275 psig ( 250 psig x 1.1 = 275 psig)Differential pressure = 350-275 = 75 psiReliving temperature = 80 deg F

How to find the maximum relief rate via F-1 and/or F-2 ?????

Page 70: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Gas Blow-by

Maximum relief rate = 245,703.5 lb/hr

Maximum relief ratecan be evaluated from control valve sizing Programs (eg. Fisher,Masoneilan etc.) or sizing equations eg.in GPSA.

Page 71: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Gas Blow-by

By input all required parameters (eg. fluid relieving properties), in to calculation sheet (WS-CA-PR-025, Rev 0) for generally vapor relief.

Required relief area = 11.57 in2

Relief Load = 245,703.5 lb/hr

Therefore

Select 6xRx8 orifice with discharge area of 16 in2

Page 72: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Blocked Outlet

1. Water Blocked Discharge. This scenario will relates to two trips; first LIAHH and secondly LAHH. Credit can be taken that either of these two will actuate. It is unreasonable to assume both will fail to response. Hence, this scenario cuts off the feed to vessel and no relief is needed.

2. Oil Blocked Discharge. This scenario relates to only oil trip, while interface level is already healthy. No credit can be taken that this trip will work. Hence PSV needs oil relief.

Relief conditionPSV-2 set pressure = 250 psigAllowable Accumulation = 10%Maximum allowable accumulated pressure = 250x1.1 = 275 psig.Relieving temperature = 130 oF

Page 73: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Blocked Outlet

From simulation Oil flow rate = 508,100 lb/hr (25,000 bpd) Oil density = 55.21 lb/ft3

By input all required parameters (eg. fluid relieving properties), in to calculation sheet (WS-CA-PR-025, Rev 0) for generally liquid relief.

Required relief area = 2.76 in2

Therefore select a 3xLx4 orifice with discharge area of 2.853 in2

Page 74: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Relief Case Design Orifice Size Relief Phase

Fire Case 1xEx2 Vapor

Gas Blow-by 6xRx8 Vapor

Blocked Outlet 3xLx4 Liquid

Selection of Governing Relief Scenarios

Page 75: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Therefore the governing case is Gas Blow-by case

Required relief rate = 287,530 lb/hrRequired relief area = 11.57 in2

Selected relief area = 16 in2

Rated flow = 16 x 287,530 lb/hr = 397,621 lb/hr 11.57

Selection of Governing Relief Scenarios

Page 76: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Inlet line sizing calculation

Inlet line sizing calculation is based on pressure drop less than 3 % of set pressure

PSV set pressure = 250 psigAllowable pressure drop = 0.03x250 = 7.5 psiMass rated flow = 397,621 lb/hr

Based on maximum rated flow and its relief properties For 8” inlet line, single phase pressure drop is 5.3 psi therefore suitable for inlet line sizing criteria.

Page 77: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Outlet line sizing calculation

Outlet line sizing calculation is based on the maximum Mach No. of 0.75

From preliminary estimation 12” line give Mach No. of 0.71 hence suitable for outlet line sizing criteria.

Result from FlareNet modeling show 10” give Mach No. of 0.45 ?????

Page 78: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Selection of Relief Valve Type

Result from FlareNet simulation give total back pressure of 70 psig

PSV set pressure = 250 psig

PSV type

Conventional

Balanced Bellow

Pilot Operated

% of Maximum Back Pressure Allowable

10% of SP

30% of SP

N/A

Maximum Back Pressure Allowable

(psig)

25 psig

75 psig

N/A

Page 79: PSV Calculation.ppt

OIL & GAS

EXAMPLEEXAMPLE

Summary

6xRx8 Balanced Bellow PSVInlet line size is 8” Outlet line size is 10”

10”8”x10”

8”x6”

8”

Gas Blow-bySet@250 psigBalanced Bellow