    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    The Pennsylvania State University

    Energized Electrical Safety ProgramIntroduction:

    Electricity is a serious workplace hazard, capable of causing both employee injury

    and property damage. It is the policy of the Pennsylvania State University (PSU) toprotect all employees, students, and other personnel from potential electrical hazards.

    This will be accomplished through compliance with the work practices described

    herein along with effective application of engineering controls, administrative

    controls, and the use of personal protective equipment.

    The PSU electrical safety program is founded on the principle of avoiding energized

    work unless it is absolutely necessary. Live parts will be deenergized before anemployee works on or near them unless one of the following conditions applies:

    Deenergizing introduces additional or increased hazards. Examples ofadditional or increased hazards would include interruption of life support

    equipment, deactivation of emergency alarm systems, or shutdown of hazardouslocation ventilation systems.

    Deenergizing is not possible due to equipment design or operationallimitations. Examples of this situation would include testing of electrical circuits

    that can only be performed with the circuit energized and work on circuits thatform an integral part of a continuous process that would otherwise need to be

    completely shut down in order to permit work on one circuit or piece of

    equipment.

    Live parts are operating at less than 50 volts to ground and there is noincreased exposure to electrical burns or to explosion due to electrical arcs.

    Live parts are to be deenergized in accordance with the PSU Lockout/TagoutProgram. If live parts are not placed in an electrically safe condition, the work

    practices described in this document must be used to protect employees.

    Purpose:

    This program has been established in order to:

    Ensure the safety of employees who may work on or near electrical systems. Ensure that work units understand and comply with safety standards related to

    electrical work.

    Ensure that work units follow uniform practices during the completion ofelectrical work.

    Scope & Applicability:

    This program applies to all Penn State properties and work performed by Penn State

    employees regardless of job site location. The Hershey Medical Center and the

    College of Medicine are exempt from this program.

    Page 1 of 1

  • 8/2/2019 PSU Energized Electrical Safety Program

    2/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Table of Contents

    1.0 References2.0 Responsibilities3.0 Definitions4.0 Training5.0 Working On or Near Live Parts

    5.1 Energized electrical work permit5.2 Testing, troubleshooting and voltage measuring5.3 Approach boundaries to live parts5.4 Other precautions for personnel activities

    6.0 Personal Protective Equipment6.1 General requirements6.2 Flash protection boundary6.3 Flame-resistant apparel & underlayers6.4 Rubber insulating equipment

    7.0 Insulated Tools & Equipment8.0 Labeling9.0 Alerting Techniques10.0 Contract EmployeesAppendix A: Energized Electrical Work Permit

    Appendix B: Approach Boundaries to Live Parts for Shock Protection

    Appendix C: Hazard/Risk Category Classifications

    Appendix D: Protective Clothing and Personal Protective Equipment Matrix

    Appendix E: PPE for Common Electrical Work Tasks at PSU

    Appendix F: Work Unit PPE Requirements for Energized Tasks

    Appendix G: Inspection Schedule for Rubber Insulating Equipment

    Appendix H: Arc Flash Warning Label (Example)

    Page 2 of 2

  • 8/2/2019 PSU Energized Electrical Safety Program

    3/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    1.0 References:

    The following documents were used as references when developing this program:

    NFPA 70E, Standard for Electrical Safety in the Workplace, 2009 edition OSHA 29 CFR 1910.331 through 1910.335, Electrical Safety-Related Work

    Practices Pennsylvania State University Lockout/Tagout Program- SY35

    2.0 Responsibilities:2.1 Budget Executives and Budget Administrators

    Ensure that responsibilities assigned within this program are carried outwithin their administrative work unit.

    Designate individuals responsible for the implementation of the electricalsafety program within their work unit.

    Actively support this program as part of the work units overall safetyeffort.

    2.2 Environmental Health and Safety Department Assist work units in implementing the provisions of this program. Periodically review and update this written program. Provide or coordinate general training for work units on the content of this

    program.

    Evaluate the overall effectiveness of the electrical safety program on aperiodic basis.

    Serve as chair of PSU Electrical Safety Committee.2.3 Safety Officers

    Determine the applicability of the electrical safety program to activitiesconducted within their work unit.

    Coordinate implementation of the electrical safety program within thework unit.

    Assist in the investigation of all injuries and incident involving electricalwork.

    Ensure that the records outlined in section 4.0 of this program aremaintained for their work unit.

    2.4 Supervisors Ensure employees comply with all provisions of the electrical safety

    program.

    Ensure that electrical equipment is labeled with appropriate arc flashwarning labels.

    Ensure employees receive training appropriate to their assigned electricaltasks and maintain documentation of such training.

    Page 3 of 3

  • 8/2/2019 PSU Energized Electrical Safety Program

    4/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Develop and maintain a listing of all qualified employees under theirsupervision.

    Ensure employees are provided with and use appropriate protectiveequipment.

    2.5 Employees Follow the work practices described in this document, including the use of

    appropriate protective equipment and completion of pre-use inspections.

    Attend all training required relative to this program. Immediately report any concerns related to electrical safety to supervision.

    2.6 OPP Electrical Engineering

    Complete calculations required by this program when needed. Place an emphasis on controlling electrical hazards through the application

    of engineering and design controls.

    2.7 PSU Electrical Safety Committee

    Meet on a periodic basis to review electrical safety issues at PSU. Review all energized electrical work permits submitted for approval. Promote consistency in how electrical tasks are completed within the

    various work units of PSU.

    3.0 Definitions:The following terms are defined in order to allow a better understanding of this

    program:

    Arc rating: The maximum incident energy resistance demonstrated by a material(or a layered system of materials) prior to breaking open or at the onset of asecond-degree skin burn. This rating is assigned to electrical protective clothing

    and is normally expressed in calories per square centimeter (cal/cm2).

    Electrically safe work condition: A state in which the conductor or circuit partto be worked on or near has been disconnected from energized parts,

    locked/tagged in accordance with PSU policy, tested to ensure the absence ofvoltage, and grounded if determined necessary.

    Energized: Electrically connected to or having a source of voltage. Exposed (as applied to live parts): Capable of being inadvertently touched or

    approached from closer than a safe distance by a person. It is applied to parts thatare not suitably guarded, isolated, or insulated.

    Flash hazard analysis: A study investigating a workers potential exposure toarc-flash energy, conducted for the purpose of injury prevention and the

    determination of safe work practices along with appropriate levels of PPE.

    Flash protection boundary: An approach limit at a distance from exposed liveparts within which a person could receive a second degree burn if an electrical arc

    flash were to occur.

    Page 4 of 4

  • 8/2/2019 PSU Energized Electrical Safety Program

    5/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Flash suit: A complete FR clothing and equipment system that covers the entirebody, except for the hands and feet. (Such a suit typically includes pants, jacket,and a bee-keeper style hood fitted with a face shield).

    FR apparel: Flame-resistant apparel; describes a broad category of clothingdesigned to protect employees from electrical arc events during completion of

    energized tasks. Incident energy: The amount of energy impressed on a surface, a certain distance

    from the source, generated during an electrical arc event. One of the units used tomeasure incident energy is calories per square centimeter (cal/cm

    2).

    Limited approach boundary: An approach limit at a distance from an exposedlive part within which a shock hazard exists.

    Live parts: Energized conductive components. Prohibited approach boundary: An approach limit at a distance from an

    exposed live part within which work is considered the same as making contactwith the live part.

    PPE: An acronym for Personal Protective Equipment. Qualified person: One who has skills and knowledge related to the construction

    and operation of the electrical equipment and installation and has received

    training on the hazards involved.

    Restricted approach boundary: An approach limit at a distance from anexposed live part within which there is an increased risk of shock (due toelectrical arc-over combined with inadvertent movement) for personnel working

    in close proximity to the live part.

    Testing and Troubleshooting: Process of analyzing the operation of a faultypiece of electrical equipment/circuit in order to determine why it is notfunctioning normally. The multimeter is a commonly used piece of testing

    equipment used to measure voltage and resistance. As soon as tools such as a

    screwdriver, wrench, pliers, etc are used on or near a live circuit, the task is nolonger considered testing and troubleshooting.

    Unqualified person: Any person who does not meet the definition of a qualifiedperson.

    Working near (live parts): Any activity within a Limited Approach Boundary. Working on (live parts): Coming in contact with live parts via tools, probes, test

    equipment, hands, feet, or other body parts regardless of the level of PPE worn.

    There are two categories of working on:Diagnostic (testing) is taking readingsor measurements of electrical equipment with approved test equipment that does

    not require making any physical change to the equipment; repairis any physical

    alteration of electrical equipment (such as making or tightening connections,removing or replacing components, etc.)

    4.0 Training:4.1Employees who are exposed to an electrical hazard that is not reduced to a safe

    level by the installation (panel cover, outlet cover, etc) must be trained.

    Page 5 of 5

  • 8/2/2019 PSU Energized Electrical Safety Program

    6/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    4.2Training must be provided before the employee is assigned duties that involvework near or on electrical systems.

    4.3The level of electrical safety training provided is dependent on whether theemployee is classified as a qualified person or unqualified person.

    4.4A qualified person shall be trained and knowledgeable in all of the followingtopics:

    1.) Construction and operation of equipment on which work is assigned.

    2.) Skills and techniques necessary to distinguish exposed energized parts fromother parts of electrical equipment.

    3.) Skills and techniques necessary to determine the nominal voltage of exposed

    live parts.

    An individual can obtain knowledge in the three topics listed abovethrough a combination of methods including the individuals education,

    electric license, past work experience, and on-the-job training.4.) The approach distances specified in this document and the corresponding

    voltages to which the qualified employee will be exposed.5.) The process necessary to determine the degree and extent of electrical hazards

    along with the PPE and job planning necessary to perform the task safely.

    An individual must attend an NFPA 70E training session approved byEHS to obtain the required knowledge of the two topics listed above.

    4.5A person can be considered qualified with respect to certain equipment andmethods but unqualified for others.

    4.6An unqualified person shall be trained in the inherent hazards of electricity andany related work practices that are necessary for their safety.

    4.7Each work unit shall maintain a record of all electrical training provided to theiremployees along with a listing of all employees classified as qualified persons.

    5.0 Working On or Near Live Parts:5.1Energized Electrical Work Permit:

    5.1.1 If live parts are not placed in an electrically safe condition, work to be

    performed shall be considered energized electrical work and will beperformed by written permit only.

    5.1.2 A copy of the PSU Energized Electrical Work Permit can be foundin Appendix A of this document. The intent of this permit is to ensure

    that all appropriate safety precautions are taken prior to starting

    energized electrical work.

    Page 6 of 6

  • 8/2/2019 PSU Energized Electrical Safety Program

    7/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    5.1.3 The permit is to be originated by the individual requesting that theenergized work be completed. The requestor is responsible for

    completing Section I of the permit.

    o The requestor will normally be the supervisor of the employeeswho will be completing the work.

    o The requestor may also be an individual from a work unit wherethe work is to be completed. If this is the case, Section I of thepermit must be completed by a unit administrator.

    5.1.4 The qualified persons completing the task are responsible forcompleting Section II of the permit.

    5.1.5 Members of the PSU Electrical Safety Committee must approve thepermit prior to commencing work. An approval signature must be

    obtained from one committee member within each of the following

    three groups:

    OPP Electrical Engineer Member of EHS Safety Officer of Work Unit (if at University Park) or

    Commonwealth Services Representative (if at a campus

    location).

    5.1.6 A job briefing is required before the start of each job involving

    energized electrical work. Each qualified person shall be briefed on

    the job. At a minimum the briefing must include the following:

    associated electrical hazards, work procedures, special precautions,isolation points and procedures, emergency response, PPErequirements, and other work in the immediate area.

    5.1.7 The permit must be posted in the area where the energized work is

    taking place for the duration of the task.

    5.1.8 At least two qualified employees must be present for all energized

    work requiring a permit.

    5.1.9 If both qualified employees are working on the circuit, an attendant is

    required to control any unqualified person from entering the limitedapproach boundary. The attendant can be an unqualified person as

    long as he or she remains outside the limited approach boundary.

    5.1.10 Copies of all energized electrical work permits must be provided to

    both the work unit Safety Officer and the EHS Department upon

    completion of the task.

    Page 7 of 7

  • 8/2/2019 PSU Energized Electrical Safety Program

    8/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    5.2 Testing, Troubleshooting, and Voltage Measuring

    5.2.1 Work related to testing, troubleshooting, and voltage measuring may

    be completed without an energized electrical permit providedappropriate safe work practices and PPE are used.

    5.3 Approach Boundaries to Live Parts:

    5.3.1 Observing a safe approach distance from exposed energized parts is an

    effective means of maintaining electrical safety. As the distance

    between an individual and live parts increases, the potential for anelectrical injury decreases.

    5.3.2 Safe approach distances will be determined for all tasks in whichapproaching personnel are exposed to live parts.

    5.3.3 Safe approach distances to fixed live parts can be determined byreferring to Appendix B, Approach Boundaries to Live Parts for

    Shock Protection. This appendix can be used to identify the Limited,

    Restricted, and Prohibited Approach Boundaries associated with

    various system voltages.

    5.3.4 Unqualified persons may only cross the Limited Approach Boundarywhen they are under the direct supervision of a qualified person.

    5.3.5 Qualified persons may not cross or take any conductive object closerthan the Restricted Approach Boundary unless one of the following

    conditions applies:

    The qualified person is insulated or guarded from the live parts andno uninsulated part of the qualified persons body crosses theProhibited Approach Boundary.

    The live parts are insulated from the qualified person and from anyother conductive object at a different potential.

    5.3.6 Crossing the Prohibited Approach Boundary is considered the same as

    making contact with energized parts. Qualified persons may only

    cross this boundary when all of the following precautions have been

    taken:

    The qualified person has specific training to work on energizedparts.

    The qualified person has obtained an approved EnergizedElectrical Work Permit.

    Page 8 of 8

  • 8/2/2019 PSU Energized Electrical Safety Program

    9/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    The qualified person uses PPE appropriate for working onenergized parts which is rated for the voltage and energy levelinvolved.

    5.4 Other Precautions for Personnel Activities:

    5.4.1 Employees shall not reach blindly into areas that might contain

    exposed live parts.

    5.4.2 Employees shall not enter spaces containing live parts unless

    illumination is provided that allows the work to be performed safely.

    5.4.3 Conductive articles of jewelry and clothing (such as watchbands,

    bracelets, rings, key chains, necklaces, metalized aprons, cloth with

    conductive thread, metal headgear, or metal frame glasses) shall not beworn where they present an electrical contact hazard with exposed live

    parts.

    5.4.4 Conductive materials, tools, and equipment that are in contact with any

    part of an employees body shall be handled in a manner that prevents

    accidental contact with live parts. Such materials and equipmentinclude, but are not limited to, long conductive objects such as ducts,

    pipes, tubes, conductive hose and rope, metal-lined rules and scales,

    steel tapes, pulling lines, metal scaffold parts, structural members, and

    chains.

    5.4.5 When an employee works in a confined space or enclosed space (such

    as a manhole or vault) that contains exposed live parts, the employeeshall use protective shields, barriers, or insulating materials as

    necessary to avoid contact with these parts. Doors, hinged panels, and

    the like shall be secured to prevent them from swinging intoemployees.

    6.0 Personal Protective Equipment:6.1General Requirements

    6.1.1 Employees working in areas where electrical hazards are present shall

    be provided with, and shall use, protective equipment that is designedand constructed for the specific body part to be protected and for the

    work to be performed.

    6.1.2 Work units will provide electrical protective equipment required bythis program at no cost to employees, such as FR apparel, eye

    protection, head protection, hand protection, insulated footwear, and

    Page 9 of 9

  • 8/2/2019 PSU Energized Electrical Safety Program

    10/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    face shields. Work units are not responsible for providing non-FRunderlayers to employees.

    6.1.3 All protective equipment shall be maintained in a safe, reliablecondition by the employee to whom it is issued.

    6.1.4 Employees shall wear nonconductive head protection whenever there

    is a danger of head injury from electric shock or burns due to contactwith live parts or from flying objects resulting from an electrical

    explosion.

    6.1.5 Employees shall wear nonconductive protection for the face, neck, and

    chin whenever there is danger of injury from exposure to electric arcs

    or flashes or from flying objects resulting from an electrical explosion.

    6.1.6 Employees shall wear protective equipment for the eyes whenever

    there is a danger of injury from electric arcs, flashes, or from flyingobjects resulting from an electrical explosion.

    6.1.7 Employees shall wear rubber insulating gloves where there is danger

    of hand and arm injury due to contact with live parts or possibleexposure to arc flash burn. The following ratings can be found on

    voltage rated gloves:

    Class 00 = Protect against voltage up to 500 volts Class 0 = Protect against voltage up to 100 volts Class 1 = Protect against voltage up to 7500 volts Class 2 = Protect against voltage up to 17,000 volts Class 3 = Protect against voltage up to 26,500 volts Class 4 = Protect against voltage up to 36,000 volts

    6.1.8 Where insulated footwear is used as protection against step and touch

    potential, dielectric overshoes shall be required. Insulated footwearshall not be used as the primary protection. The integrity of the

    insulating quality of such footwear cannot be established easily after

    the worker has been wearing them in the working environment.

    6.1.9 Face shields without an arc rating will not be used for electrical work.Safety glasses or goggles must always be worn underneath faceshields.

    6.1.10 Additional illumination may be needed when using tinted face shieldsas protection during electrical work.

    6.1.11 Employees shall wear hearing protection whenever there is a danger ofnoise overexposure resulting from an electrical explosion.

    Page 10 of 10

  • 8/2/2019 PSU Energized Electrical Safety Program

    11/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    6.2Flash Protection Boundary6.2.1 Personal protective equipment shall be provided to and used by all

    employees working within the Flash Protection Boundary.

    6.2.2 For systems that are 600 volts or less, the Flash Protection Boundaryshall be a minimum of four feet, based on the product of clearing time

    of 2 cycles (0.033 sec) and the available bolted fault current of 50 KAor any combination not exceeding 100 kA cycles (1667 ampere

    seconds). The Flash Protection Boundary for systems under 600

    volts may also be calculated through engineering analysis usingAnnex D of NFPA 70E (2009 edition).

    6.2.3 For systems that are above 600 volts, the Flash Protection Boundaryshall be determined through engineering analysis.

    6.2.4 The specific protective equipment to be worn within the FlashProtection Boundary can be determined by one of the following three

    methods:

    (1)Complete a detailed flash hazard analysis under engineeringsupervision that determines the incident exposure energy of each

    employee. Appropriate protective clothing can then be selectedbased on the calculated exposure level. Criteria for completing

    such an analysis can be obtained from the EHS Department.

    (2)Determine the hazard level of the task by referring to NFPA 70ETable 130.7 (C) (9), Hazard/Risk Category Classifications(Appendix C of this document). This table also indicates whethervoltage-rated gloves and/or voltage-rated tools need to be used.

    Once the hazard level of the task has been determined, the required

    PPE can then be ascertained from NFPA 70E Table 130.7 (C) (10),Protective Clothing and PPE Matrix. (Appendix D of this

    document).

    (3)Refer to Appendix E of this document to determine the necessaryPPE for a given task. This appendix defines the PPE requirements

    for common electrical tasks based on the information contained in

    Appendices C and D.

    6.2.5 Each work unit shall develop and maintain a listing of the specific PPE

    requirements for each energized electrical task conducted by theiremployees using the form found in Appendix F of this document.

    Page 11 of 11

  • 8/2/2019 PSU Energized Electrical Safety Program

    12/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    6.3Flame-Resistant Apparel & Underlayers6.3.1 FR apparel shall be visually inspected before each use. FR apparel

    that is contaminated or damaged shall not be used. Protective itemsthat become contaminated with grease, oil, flammable liquids, or

    combustible liquids shall not be used.

    6.3.2 The garment manufacturers instructions for care and maintenance ofFR apparel shall be followed.

    6.3.3 When FR apparel is worn to protect an employee, it shall cover allignitable clothing and allow for movement and visibility.

    6.3.4 FR apparel must cover potentially exposed areas as completely aspossible. FR shirt sleeves must be fastened and FR shirts/jackets must

    be closed at the neck.

    6.3.5 Non-melting, flammable garments (i.e. cotton, wool, rayon, silk, or

    blends of these materials) may be used as underlayers beneath FR

    apparel.

    6.3.6 Meltable fibers such as acetate, nylon, polyester, polypropylene, and

    spandex shall not be permitted in fabric underlayers next to the skin.(An incidental amount of elastic used on non-melting fabric underwear

    or socks shall be permitted).

    6.3.7 When FR apparel is required, garments worn as outer layers over FR

    apparel (i.e. jackets or rainwear) must also be made from FR material.

    6.3.8 Flash suits must permit easy and rapid removal by the user.

    6.4Rubber Insulating Equipment6.4.1 Rubber insulating equipment includes protective devices such as

    gloves, sleeves, blankets, and matting.

    6.4.2 Insulating equipment must be inspected for damage before each days

    use and immediately following any incident that could have caused

    damage.

    6.4.3 An air test must be performed on rubber insulating gloves before each

    use. To complete an air test, manually fill the glove with air. Foldover the cuff to seal the air inside the glove. Detect any leaking air by

    either listening for escaping air or feeling the escaping air by holding

    the glove near the face.

    Page 12 of 12

  • 8/2/2019 PSU Energized Electrical Safety Program

    13/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    6.4.4 Insulating equipment found to have defects that might affect itsinsulating properties must be removed from service until testing

    indicates that it is acceptable for continued use.

    6.4.5 Where the insulating capability of protective equipment is subject to

    damage during use, the insulating material shall be protected by anouter covering of leather or other appropriate material.

    6.4.6 Rubber insulating equipment must be tested according to the schedule

    in Appendix G.

    6.4.7 Rubber insulating equipment must be stored in an area protected from

    light, temperature extremes, excessive humidity, ozone, and other

    substances and conditions that may cause damage.

    6.4.8 No repairs to rubber insulating equipment shall be attempted without

    the approval of the EHS Department.

    7.0Insulated Tools & Equipment:7.1 Only insulated tools and equipment shall be used within the Limited

    Approach Boundary of exposed energized parts.

    7.2 Insulated tools shall be rated for the voltages on which they are used. 7.3 Insulated tools shall be designed and constructed for the environment to which

    they are exposed and the manner in which they are used.

    7.4 Fuse or fuse holder handling equipment, insulated for the circuit voltage, shallbe used to remove or install a fuse if the fuse terminals are energized.

    7.5 Ropes and handlines used near exposed energized parts shall benonconductive.

    7.6 Portable ladders used for electrical work shall have nonconductive side rails.

    8.0Labeling:8.1 All switchboards, panel boards, industrial panels, motor control centers, and

    meter socket enclosures shall be labeled using a label similar to the one foundin Appendix H.

    Page 13 of 13

  • 8/2/2019 PSU Energized Electrical Safety Program

    14/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    9.0Alerting Techniques:9.1 Barricades shall be used in conjunction with safety signs to prevent or limit

    access to work areas containing live parts. Conductive barricades shall not beused where they might cause an electrical hazard. Barricades shall be placed

    no closer than the Limited Approach Boundary.

    9.2 If signs and barricades do not provide sufficient protection, an attendant willbe assigned to warn and protect pedestrians. The primary duty of the

    attendant shall be to keep unqualified persons out of the work area where an

    electrical hazard exists. The attendant shall remain in the area as long as thereis a potential exposure to electrical hazards.

    10.0 Contract Employees:10.1 PSU shall inform contractors engaged in electrical work of any known

    hazards applicable to the work being performed. Contractors are required tofollow all applicable OSHA regulations and NFPA 70E standards.

    Page 14 of 14

  • 8/2/2019 PSU Energized Electrical Safety Program

    15/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix A: Energized Electrical Work Permit

    Part I: To be completed by the requester or supervisor of the job(1) Identify requester: Name:__________________________ Work Unit:__________________________

    (2) Job location:

    (3) Description of work to be done:

    (4) Explain why the circuit cannot be deenergized or the work delayed until the next scheduled outage:

    (5) Signature of requester:___________________________Title:__________________________________

    Part II: To be completed by the qualified person(s) completing the work(6) Description of circuit and equipment:

    (7) Detailed description of procedure to be used in performing the above work:

    (8) Safe work practices to be used: (Check all that apply)

    Barriers/Boundaries Non-conductive covers/blanketsVoltage rated tools Attendant

    PPE OTHER (Describe)

    LOTO other circuits/tools

    (9) Maximum Voltage that will be exposed:

    (10) What rating is the upstream protective device? (Amperage):

    (11) Limited, Restricted and Prohibited Boundaries for shock hazard: Refer to the arc flash label (if present), if not

    see Appendix B of this program or Table 130.2(c) in the NFPA 70E 2009 standard)

    Limited boundary =_________________________ Restricted boundary = _______________________ Prohibited boundary =_______________________

    (12) Determination of flash protection boundaries:

    4 Feet for 600 Volts or less, based on the product of clearing time of 2 cycles (0.033 sec) and the available

    bolted fault current of 50 KA or any combination not exceeding 100 kA cycles (1667 ampere seconds). Higher Voltages must be calculated by Electrical Engineer. Calculation Results: _____Ft ______inches

    (13) Hazard/Risk Category (See Appendix D of this program):

    Page 15 of 15

  • 8/2/2019 PSU Energized Electrical Safety Program

    16/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    (14) PPE required to safely perform the task: (Either see Appendix C and D of this program, Tables 130.7(c)(9) and

    130.7(c)(10) in the NFPA 70E 2009 standard, or Appendix E)

    - Check all that apply.

    - Circle class of PPE and minimum calorie rating where applicable.

    Voltage rated gloves class 00, 0, 1, 2, 3, 4

    Long sleeve shirt (non-melting)

    Voltage rated tools Long pants (non-melting)

    Safety glasses or goggles Long sleeve FR shirt - Calorie rating 4, 8, 25, 40

    Hearing protection Long FR pants - Calorie rating 4, 8, 25, 40

    Hardhat - (Class C up to 2,200 Volts / Class G up to

    20,000 Volts) FR coveralls- Calorie rating 4, 8, 25, 40

    Hardhat with flame retardant liner - (Class C up to

    2,200 Volts / Class G up to 20,000 Volts)

    FR jacket or rainwear- Calorie rating 4, 8, 25, 40

    Leather boots/shoes Flash suit- Calorie rating 4, 8, 25, 40

    Leather gloves Flash hood - Calorie rating 4, 8, 25, 40

    Dielectric over-boots/shoes Balaclava (sock hood) Hazard/Risk Category 2*only

    Arc rated face-shield - Calorie rating 4, 8, 25, 40 OTHER:

    (15) Method used to restrict access to the work area:

    Safety Signs and Tags (tape, physical barrier)

    Attendant

    (16) Will a job briefing be completed that covers all of the following items? Yes

    Hazards associated with the job Energy source controls

    Work procedures involved PPE

    Special precautions Other

    Do you agree the above work can be done safely? Yes (Forward to EHS) No (Return to requester) Note that

    additional information may be requested by the PSU Electrical Safety Committee.

    Qualified Person performing work: ____________________________________ Date: ______________Qualified Person performing work: ____________________________________ Date: ______________

    Attendant:_________________________________________________________ Date: ______________

    Qualified Persons Supervisor: _______________________________________ Date: _______________

    Part III: To be completed by members of PSU Electrical Safety Committee

    Approvals:

    Safety Officer (UP): Signature__________________________Job Title__________________Date______________

    Commonwealth Services Representative (Campus): Signature__________________Job Title___________Date_____

    Electrical Engineer (OPP): Signature__________________Job Title____________________________Date________

    EHS: Signature______________________Job Title______________________________Date___________________

    Permit Expiration Date:

    Approved NOT Approved

    Page 16 of 16

  • 8/2/2019 PSU Energized Electrical Safety Program

    17/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix B: Approach Boundaries to Live Parts for Shock Protection

    (All dimensions are distance from live part to employee)

    Nominal System

    Voltage(phase to phase)

    Limited Approach

    Boundary(fixed circuit parts

    only)

    Restricted

    ApproachBoundary

    (includes

    inadvertent

    movement adder)

    Prohibited

    ApproachBoundary

    Less than 50 V Not Specified Not Specified Not Specified

    50 V to 300 V 3 feet, 6 inches Avoid Contact Avoid Contact

    301 V to 750 V 3 feet, 6 inches 1 foot 1 inch

    751 V to 15 kV 5 feet 2 feet, 2 inches 7 inches

    Over 15 kV ormovable conductor

    See NFPA 70 E Table 130.2 (C)

    Limited Approach Boundary: Distance from an exposed live part within which a shockhazard exists. An unqualified person may not cross this boundary unless they are

    continuously escorted by a qualified person.

    Restricted Approach Boundary: Distance from an exposed live part within which thereis an increased risk of shock (due to electrical arc-over combined with inadvertent

    movement) for personnel working in close proximity to the live part. This boundary mayonly be crossed by a qualified person who is safely insulated or guarded from the live

    parts.

    Prohibited Approach Boundary: Distance from an exposed live part within which workis considered the same as making contact with the live part. This boundary may only be

    crossed by a qualified person who has specific training to work on energized parts; hasobtained an approved Energized Electrical Work Permit; and uses PPE appropriate for

    working on energized parts which are rated for the voltage and energy level involved.

    (Note: A permit is not required for work related to testing, troubleshooting, and voltagemeasuring).

    Flash Protection Boundary (not listed in table): Distance from exposed live partswithin which a person could receive a second degree burn if an electrical arc flash were

    to occur. This boundary may only be crossed by a qualified person wearing theappropriate PPE. For systems that are 600 volts or less, the Flash Protection Boundary

    shall be a minimum of four feet, based on the product of clearing time of 2 cycles (0.033

    sec) and the available bolted fault current of 50 KA or any combination not exceeding100 kA cycles (1667 ampere seconds). (The Flash Protection Boundary for systems

    under 600 volts that do not meet the above criteria or are above 600 Volts will be

    determined by an Electrical Engineer). An engineering analysis must be performed todetermine the Flash Protection Boundary for systems that are above 600 volts.

    Page 17 of 17

  • 8/2/2019 PSU Energized Electrical Safety Program

    18/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix C: Hazard/Risk Category Classifications

    Tasks Performed on Energized Equipment

    Hazard/Risk

    Category

    Rubber

    Insulating

    Gloves

    Insulated

    and

    Insulating

    Hand ToolsPanelboards Rated 240 V and Below (See Note 1)Perform infrared thermography and other non-contact

    inspections outside the restricted approach boundary

    0 N N

    Circuit breaker (CB) or fused switch operation with

    covers on

    0 N N

    CB or fused switch operation with covers off 0 N N

    Work on energized parts, including voltage testing 1 Y Y

    Remove/install CBs or fused switches 1 Y Y

    Removal of bolted covers (to expose bare, energizedelectrical conductors and circuit parts) 1 N N

    Opening hinged covers (to expose bare, energizedelectrical conductors and circuit parts) 0 N N

    Work on energized electrical conductors and circuit

    parts fed directly by a branch circuit of the panelboard

    1 Y Y

    Panelboards or Switchboards Rated > 240 V and up to 600 V (with molded case or

    insulated case circuit breakers) (See Note 1)Perform infrared thermography and other non-contact

    inspections outside the restricted approach boundary

    1 N N

    CB or fused switch operation with covers on 0 N N

    CB or fused switch operation with covers off 1 Y N

    Work on energized electrical conductors and circuit

    parts, including voltage testing 2 * Y Y

    Work on energized electrical conductors and circuit

    parts of utilization equipment fed directly by a branch

    circuit of the panelboard or switchboard

    2* Y Y

    Other 600 V Class (277 V through 600 V, nominal) Equipment - Note 2 (except as

    indicated)Removal of bolted covers (to expose bare, energized

    electrical conductors and circuit parts)

    2* N N

    Opening hinged covers (to expose bare, energizedelectrical conductors and circuit parts)

    1 N N

    Work on energized electrical conductors and circuit

    parts, including voltage testing.

    2* Y Y

    Application of safety grounds, after voltage testing 2* Y N

    Additional Information: See NFPA 70E Table 130.7(C)(9) for more tasks and voltages

    Rubber insulating gloves are gloves rated for the maximum line-to-line voltage upon which work will bedone.

    Insulated and insulating hand tools are tools rated and tested for the maximum line-to-line voltage uponwhich work will be done, and are manufactured and tested in accordance with ASTM F 1505, Standard

    Specification for Insulated and Insulating Hand Tools.

    Y = Yes (required) N = No (not required)Notes:(1) Maximum of 25 kA short circuit current available; maximum of 0.03 second (2 cycle) fault clearing time.(2) Maximum of 65 kA short circuit current available; maximum of 0.03 second (2 cycle) fault clearing time.

    Page 18 of 18

  • 8/2/2019 PSU Energized Electrical Safety Program

    19/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix D: Protective Clothing and Personal Protective Equipment (PPE) Matrix

    Hazard/Risk Category Protective Clothing and PPE

    Hazard/Risk Category 0

    Protective Clothing, Nonmelting (according to ASTMF 1506-00) or Untreated Natural Fiber (i.e., untreated

    cotton, wool, rayon, or silk, or blends of these

    materials with a fabric weight of at least 4.5 oz/yd2)

    FR Protective Equipment

    Shirt (long sleeve) and Pants (long)

    Safety glasses or safety goggles

    Hearing protection (ear canal inserts)

    Leather gloves (As needed) (Note 2)

    Hazard/Risk Category 1

    FR Clothing, Minimum Arc Rating of 4 cal/cm2 (Note1)

    FR Protective Equipment

    Arc-rated long-sleeve shirt and pants (Note 3)or Arc- rated coveralls (Note 4)

    Arc-rated face shield or arc flash suit hood (Note 7)Arc-rated jacket, parka, or rainwear (As needed)

    Hard hat

    Safety glasses or safety gogglesHearing protection (ear canal inserts)

    Leather gloves (Note 2)

    Leather work shoes (As needed)

    Hazard/Risk Category 2

    FR Clothing, Minimum Arc Rating of 8 cal/cm2 (Note

    1)

    FR Protective Equipment

    Arc-rated long-sleeve shirt and pants (Note 5)

    or Arc-rated coveralls (Note 6)

    Arc-rated face shield or arc flash suit hood (Note 7)

    Arc-rated jacket, parka, or rainwear (As needed)

    Hard hat

    Safety glasses or safety gogglesHearing protection (ear canal inserts)

    Leather gloves (Note 2)

    Leather work shoes

    Hazard/Risk Category 2*

    FR Clothing, Minimum Arc Rating of 8 cal/cm2 (Note

    1)

    FR Protective Equipment

    Arc-rated long-sleeve shirt and pants (Note 5)

    or Arc-rated coverall (Note 6)Arc-rated arc flash suit hood (Note 10)

    Arc-rated jacket, parka, or rainwear (As needed)

    Hard hat

    Safety glasses or safety gogglesHearing protection (ear canal inserts)

    Leather gloves (Note 2)

    Leather work shoes

    Page 19 of 19

  • 8/2/2019 PSU Energized Electrical Safety Program

    20/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Hazard/Risk Category 3

    FR Clothing, Minimum Arc Rating of 25 cal/cm2

    (Note 1)

    FR Protective Equipment

    Arc-rated long-sleeve shirt and pants (Note 8)

    or Arc-rated coverall (Note 8)

    Arc-rated flash suit jacket (Note 8)

    Arc-rated flash suit pants (Note 8)Arc-rated flash suit hood (Note 8)

    Arc-rated jacket, parka, or rainwear (As needed)

    Hard hat with FR hard hat linerSafety glasses or safety goggles

    Hearing protection (ear canal inserts)

    Arc-rated gloves (Note 2)Leather work shoes

    Hazard/Risk Category 4

    FR Clothing, Minimum Arc Rating of 40 cal/cm2

    (Note 1)

    FR Protective Equipment

    Arc-rated long-sleeve shirt and pants (Note 9)

    or Arc-rated coverall (Note 9)

    Arc-rated flash suit jacket (Note 9)Arc-rated flash suit pants (Note 9)Arc-rated flash suit hood (Note 9)

    Arc-rated jacket, parka, or rainwear (As needed)

    Hard hat with FR hard hat liner

    Safety glasses or safety goggles

    Hearing protection (ear canal inserts)

    Leather gloves (Note 2)

    Leather work shoes

    Notes:

    1. See Table 130.7 (C) (11). Arc rating for a garment or system of garments is expressed in cal/cm2.2. If rubber insulating gloves with leather protectors are required, additional leather or arc-rated gloves

    are not required. The combination of rubber insulating gloves with leather protectors satisfies the arc

    flash protection requirement.3. The FR shirt and pants used for Hazard/Risk Category 1 shall have a minimum arc rating of 4 cal/cm24. Alternate is to use FR coveralls (minimum arc rating of 4 cal/cm2) instead of FR shirt and FR pants5. FR shirt and FR pants used for Hazard/Risk Category 2 shall have a minimum arc rating of 8 cal/cm26. Alternate is to use FR coveralls (minimum arc rating of 8 cal/cm2) instead of FR shirt and FR pants.7. A face shield with a minimum arc rating of 4 cal/cm2 for Hazard Risk Category 1 or a minimum arc

    rating of 8 cal/cm2 for Hazard/Risk Category 2, with wrap-around guarding to protect not only theface, but also the forehead, ears, and neck (or alternatively, a flash suit hood), is required.

    8. An alternate is to use a total FR clothing system and hood, which shall have a minimum arc rating of25 cal/cm2 for Hazard/Risk Category 3.

    9. The total clothing system consisting of FR shirt and pants and/or FR coveralls and/or arc flash coat andpants and hood shall have a minimum arc rating of 40 for Hazard/Risk Category 4.

    10. Alternate is to use face shield with a minimum arc rating of 8 cal/cm2 and a balaclava (sock hood) witha minimum arc rating of 8 cal/cm2 and which covers the face, head and neck except for the eye andnose areas.

    Page 20 of 20

  • 8/2/2019 PSU Energized Electrical Safety Program

    21/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix E

    PPE for Common Electrical Work Tasks at PSU

    (Not an all inclusive listing of work tasks)

    (PPE contingent on criteria found in the Notes section of Appendix C)

    Panelboards or other equipment rated 240 V and below

    Job Tasks performed on energized

    equipment

    Protective Requirements

    Perform infrared thermography and other non-

    contact inspections outside the restricted approach

    boundary. (hazard/risk category 0)

    Non-melting or untreated natural fiber:

    Long sleeve shirt Long pants

    PPE: Safety glasses or safety goggles Hearing protection Leather gloves (as needed)

    Circuit breaker or fused switch operation with

    covers on. (hazard/risk category 0)Non-melting or untreated natural fiber:

    Long sleeve shirt Long pants

    PPE:

    Safety glasses or safety goggles Hearing protection Leather gloves (as needed)

    Circuit breaker or fused switch operation with

    covers off. (hazard/risk category 0)Non-melting or untreated natural fiber:

    Long sleeve shirt Long pants

    PPE:

    Safety glasses or safety goggles Hearing protection Leather gloves (as needed)

    Page 21 of 21

  • 8/2/2019 PSU Energized Electrical Safety Program

    22/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Panelboards or other equipment rated 240 V and below

    Job Tasks performed on energizedequipment

    Protective Requirements

    Work on energized electrical conductors and circuit

    parts, including voltage testing and troubleshooting.

    (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE: Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes (as needed)

    Remove or install circuit breakers or fusedswitches. (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4)

    Face-shield or flash suit hood (Calrating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes (as needed)

    Page 22 of 22

  • 8/2/2019 PSU Energized Electrical Safety Program

    23/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Panelboards or other equipment rated 240 V and below

    Job Tasks performed on energizedequipment

    Protective Requirements

    Removal of bolted covers (to expose bare,

    energized electrical conductors and circuit parts).

    (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE: Hardhat Safety glasses or goggles Hearing protection Leather gloves Leather work shoes (as needed)

    Opening hinged covers (to expose bare, energized

    electrical conductors and circuit parts). (hazard/riskcategory 0)

    Non-melting or untreated natural fiber:

    Shirt (long sleeve) Pants (long)

    PPE: Safety glasses or safety goggles Hearing protection Leather gloves (as needed)

    Work on energized electrical conductors and circuitparts of utilization equipment fed directly by branch

    circuit of the panelboard. (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes (as needed)

    Page 23 of 23

  • 8/2/2019 PSU Energized Electrical Safety Program

    24/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Panelboards or Switchboards Rated greater than 240 V and up to

    600 Volts (with molded case or insulated case circuit breakers)

    Job Tasks performed on energized

    equipment

    Protective Requirements

    Perform infrared thermography and other non-

    contact inspections outside the restricted approachboundary. (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Leather gloves Leather work shoes (as needed)

    Circuit or fused switch operation with covers on.

    (hazard/risk category 0)

    Non-melting or untreated natural fiber:

    Shirt (long sleeve) Pants (long)

    PPE:

    Safety glasses or safety goggles Hearing protection Leather gloves (as needed)

    Circuit breaker or fused switch operation with

    covers off. (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes (as needed)

    Page 24 of 24

  • 8/2/2019 PSU Energized Electrical Safety Program

    25/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Panelboards or Switchboards Rated greater than 240 V and up to

    600 Volts (with molded case or insulated case circuit breakers)

    Job Tasks performed on energizedequipment

    Protective Requirements

    Work on energized electrical conductors and circuitparts, including voltage testing and troubleshooting.

    (hazard/risk category 2*)

    FR Clothing, minimum arc rating of 8:

    Long sleeve shirt AND long pants(Cal rating of 8) ORCoveralls

    (Cal rating of 8)

    Arc flash suit hood ORFace shield (Cal rating of 8)

    AND Balaclava (Cal rating of 8)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes

    Work on energized electrical conductors and circuitparts of utilization equipment fed directly by a

    branch circuit of the panelboard or switch.

    (hazard/risk category 2*)

    FR Clothing, minimum arc rating of 8: Long sleeve shirt AND long pants

    (Cal rating of 8) ORCoveralls(Cal rating of 8)

    Arc flash suit hood ORFace shield (Cal rating of 8)

    AND Balaclava (Cal rating of 8)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber insulating gloves Leather gloves Leather work shoes

    Page 25 of 25

  • 8/2/2019 PSU Energized Electrical Safety Program

    26/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Other 600 V Class (277 V through 600 V, nominal) Equipment

    Job Tasks performed on energized

    equipment

    Protective Requirements

    Lighting or small power transformers (600 V, maximum)

    Removal of bolted covers (to expose bare,energized electrical conductors and circuit parts)

    (hazard/risk category 2*)

    FR Clothing, minimum arc rating of 8:

    Long sleeve shirt AND long pants(Cal rating of 8) ORCoveralls

    (Cal rating of 8)

    Arc flash suit hood ORFace shield (Cal rating of 8)

    AND Balaclava (Cal rating of 8)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Leather gloves

    Leather work shoesOpening hinged covers (to expose bare, energizedelectrical conductors and circuit parts)

    (hazard/risk category 1)

    FR Clothing, minimum arc rating of 4:

    Long sleeve shirt and long pants(Cal rating of 4)

    ORCoveralls (Cal rating of 4) Face-shield or flash suit hood (Cal

    rating of 4)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Leather gloves Leather work shoes (as needed)

    Page 26 of 26

  • 8/2/2019 PSU Energized Electrical Safety Program

    27/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Other 600 V Class (277 V through 600 V, nominal) Equipment

    Job Tasks performed on energized

    equipment

    Protective Requirements

    Work on energized electrical conductors and circuit

    parts, including voltage testing.(hazard/risk category 2*)

    FR Clothing, minimum arc rating of 8:

    Long sleeve shirt AND long pants(Cal rating of 8) ORCoveralls (Cal

    rating of 8)

    Arc flash suit hood ORFace shield (Cal rating of 8)

    AND Balaclava (Cal rating of 8)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE:

    Hardhat Safety glasses or goggles Hearing protection Rubber Insulating gloves Leather gloves Leather work shoes

    Application of safety grounds, after voltage testing

    (hazard/risk category 2*)

    FR Clothing, minimum arc rating of 8:

    Long sleeve shirt AND long pants(Cal rating of 8) ORCoveralls (Calrating of 8)

    Arc flash suit hood ORFace shield (Cal rating of 8)

    AND Balaclava (Cal rating of 8)

    Jacket, parka, or rainwear (asneeded based on conditions)

    PPE: Hardhat Safety glasses or goggles Hearing protection Rubber Insulating gloves Leather gloves Leather work shoes

    Page 27 of 27

  • 8/2/2019 PSU Energized Electrical Safety Program

    28/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix F: Work Unit PPE Requirements for Energized Tasks

    Description of Task Equipment Voltage Hazard/Risk

    Category

    Specific PPE To Be

    Worn

    Page 28 of 28

  • 8/2/2019 PSU Energized Electrical Safety Program

    29/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix G: Inspection Schedule for Rubber Insulating Equipment

    Type of Equipment When to TestRubber insulating line hose Upon indication that insulating value is

    suspect

    Rubber insulating covers Upon indication that insulating value is

    suspect

    Rubber insulating blankets Before first issue and every 12 months

    thereafter (*)

    Rubber insulating gloves Before first issue and every 6 months

    thereafter (*)

    Rubber insulating sleeves Before first issue and every 12 monthsthereafter (*)

    (*) If the insulating equipment has been electrically tested but not issued for service, it may

    not be placed into service unless is has been electrically tested within the previous 12months.

    Page 29 of 29

  • 8/2/2019 PSU Energized Electrical Safety Program

    30/30

    PSU Energized Electrical Safety ProgramIssue Date: March 10, 2010

    Appendix H: Arc Flash Warning Label (Example)