  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 1

    Ultra Fast Earthing SwitchType UFES

    ABB AG, PPMV, V11.05.27

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 2

    Ultra Fast Earthing Switch type UFES The new active internal arc protection

    The new Ultra Fast Earthing Switch type UFES

    Active internal arc protection in addition to available passive protection applicable for nearly all short-circuit proof, air-insulated switchgear

    Highest possible protection for switchgear in regard to the hazardous impacts caused by an internal arc

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 3

    Ultra Fast Earthing Switch type UFES S Speed, Safety, Savings

    Speed A question of (Operation-) time Nearly immediate extinction of an internal arc by fastest intervention of the Ultra Fast Earthing Switch.

    Safety Greatly enhanced protection for personnel, switchgear and the environmentA drastically reduced internal arc duration ensures minimized pressure and temperature rise. This leads, as a consequence, to minimal impacts at the fault location.

    Savings The insurance for your switchgearGreatly increased system and process availability in combination with drastically reduced repair costs.

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 4

    Internal arc faultsReasons of formation

    1. Human errors

    2. Pollution

    3. Animals

    4. Overvoltage

    5. Bad connections

    6. Mechanical faults

    7. Defective devices(e.g. voltage transformer)

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 5

    Internal arc faultsEffects

    Rapid pressure rise

    Heavy injuries of the personnel possible

    for switchgear systems without internal arc classification

    Heavy damages possibleinside of the switchgear, for the integrated devices

    and for the building

    Burning and vaporizationof metal and insulation

    material

    Release of material fragments and hot

    gases

    Rapid temperature rise(up to 20.000C)

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 6

    Internal arc faultsImpacts

    Circuit breaker compartment after internal arc impact

    Cable connection compartment after internal arc impact

    Contact terminal after internal arc impact

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 7

    Active internal arc protection by ABBThe basis for effective protection

    Electronic detection and tripping unit type QRU1

    Continuously monitoring of a defined protection area

    Fast and reliable detection of an internal arc fault by light and fault current parameter

    3 Primary switching elements type U1

    Ultra-fast initiation of a 3-phase short-circuit earthing after detection of a fault by the electronic

    Elimination of the arc by resulting breakdown of the internal arc voltage

    Ultra Fast Earthing Switch type UFES

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 8

    Ultra Fast Earthing Switch type UFESSequence of tripping operation

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 9

    Active internal arc protection by ABB Ultra-fast reaction time

    Effective limitation of damage requires fastest intervention

    Extinction time of the Ultra Fast Earthing Switch:< 4 ms after fault detection

    Short-circuit current IkDC component

    Arcing time with UFES

    Final clearing by upstream circuit-breaker 80 ms + time x

    Reaching time for tripping criteria

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 10

    Ultra Fast Earthing Switch type UFES Electronic

    Electronic detection and tripping unit typeQRU1

    Completely in fast analogue technology

    9 optical inputs for light detection by means of single lens sensors

    3 current inputs for monitoring of the instantaneous current value

    Up to 5 x 30 additional optical inputs with ABB arc guard type TVOC-2

    Exact identification of the fault location

    Continuous self monitoring

    Testing mode

    Simple configurationLens sensor for optical detection

    Electronic detection and tripping unit type QRU 1

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 11

    1

    2

    3

    4

    5

    6

    7

    8

    9

    Ultra Fast Earthing Switch type UFES Primary switching element

    Primary switching element type U1

    Vacuum interrupter and operating system integrated in one compact unit

    Fast and reliable micro gas generator operating mechanism

    Fast switching time of ~ 1.5 ms

    Easy handling

    Low-maintenance

    Flexible installation

    6. Piston7. Cylinder8. Moving contact system9. Micro gas generator

    1. Epoxy insulator2. Fixed contact3. Ceramic insulator4. Moving contact pin5. Rupture joint

    Primary switching element section view

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 12

    Ultra Fast Earthing Switch type UFES Switching principle

    Position after trippingService position

    Drive

    Vacuum-interrupter

    Current flowafter tripping

    Movingdirection

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 13

    Ultra Fast Earthing Switch type UFES Speed Differentiation

    Conventional protection device

    Fault detection by standard relay

    Clearing of the arc fault current by the upstream circuit-breakerFast-acting protection relay with supplementary equipment Fast fault detection by special protection relay Clearing of the arc fault current by the upstream circuit-breaker

    Ultra Fast Earthing Switch type UFES

    Ultra-fast fault detection by UFES electronic type QRU1

    Ultra-fast extinction of an internal arc by switching of the UFES primary switching element type U1

    Final clearing of the fault current by the upstream circuit-breaker

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 14

    Ultra Fast Earthing Switch type UFES Speed Differentiation

    Warc [kVAs]*

    * Constant arc voltage & fault current for the complete fault time Uarc Ik t = Warc (linear function)

    Time in ms

    Fast protection relay

    Limited consequences for equipment and personnel (depending on switchgear design)

    Conventional protection device

    Dramatic consequences possible

    Fire/Explosion hazard, heavy injuries of personnel (depending on switchgear design)

    Ultra Fast Earthing Switch type UFES

    Arc extinction < 4 ms after detection

    Drastic reduction of thermal damages

    Drastically reduced pressure rise

    No consequences to be expected !

    Steel fire

    Copper fire

    Cable fire

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 15

    Ultra Fast Earthing Switch type UFES Speed & Safety Pressure curves

    Exemplary pressure curve, with and without UFES, in a compartment of an air insulated medium voltage switchgear, for an internal arc fault current of 130 kA (peak) / 50 kA (rms)

    Overpressurein bar

    Pressure risewithout UFES

    Pressure risewith UFES

    Reaching time fortripping criteria

    tTC

    Time in mstTC + 4 ms

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 16

    Ultra Fast Earthing Switch type UFES Safety & Savings The internal arc test with UFES

    Busbar compartment afterinternal arc impact with activeUFES protection

    Point of fault initiation in the busbar compartment

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 17

    Ultra Fast Earthing Switch type UFES S - Comparison

    Busbar compartment afterinternal arc impact with activeUFES protection

    Busbar compartment afterinternal arc impact withoutactive UFES protection(50 kA / 100 ms)

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 18

    Ultra Fast Earthing Switch type UFES The formula for effective internal arc protection

    Speedy arc suppression

    Safety for investment and personnel

    Savings in regard of repair and downtime costs

    UFES = S

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 19

    Ultra Fast Earthing Switch type UFES Applicable for highest requirements

    Maximum rated voltage:

    Ur = 40.5 kV Ik = 40 kA (3s)

    Maximum rated short-time withstandcurrent for medium voltage:

    Ik = 50 kA (3s), 63 kA (1s) Ur = 17.5 kV

    Maximum rated short-time withstandcurrent for low voltage :

    Ik = 100 kA (0.5s) Ur = 1.4 kV

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 20

    Ultra Fast Earthing Switch type UFES Available as loose components

    Electronic detection and tripping unit typeQRU1

    3 Primary switchingelements (PSE) type U1

    1 set (3 off) Trippingcables (10 m) withspecial plug for PSE and electronic

    UFES-kit as OEM product, consisting of:

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 21

    Ultra Fast Earthing Switch type UFES Available as ABB Service retrofit solution

    Service-Box

    Service-Box(Illustration: Side-mounted)

    Draw-out technology

    Draw-out unit

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 22

    Ultra Fast Earthing Switch type UFES Available for ABB switchgear (AIS)

    UFES in UniGear Top-Box installation

    UFES in UniGear -Installation in

    cable compartment

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 23

    Ultra Fast Earthing Switch type UFES S - Unbeatable advantages

    Indirect benefit

    Greatly increased system and process availability byavoidance of heavy damages inside the switchgear, of theequipment and the direct environment

    Drastic reduction of downtimes and repair costs

    Example for a production site(e.g. chemical-, paper- or oil industry)

    Risks: Exchange of damaged switchgear panel(s) orequipment necessary

    Consequence: Loss of production for possibly some daysor weeks

    Costs: Up to multiple 100.000 EUR / day possible

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 24

    Ultra Fast Earthing Switch type UFES S - Unbeatable advantages

    Direct benefit

    Greatly increased operator safety for switchgears

    Minimization of pressure rise and gases in the faultycompartment and surrounding switchgear building

  • ABB04.07.2011 UFES Ultraschneller Erdungsschalter | 25

    Ultra Fast Earthing Switch type UFES UFES = S

    Are you attracted by theUFES?

    Please contact

    [email protected]