1
© ABB Group March 31, 2010 | Slide 1
Protection Relay for TransmissionIED 670 Series
王中平王中平王中平王中平,,,, 高雄電機技師公會高雄電機技師公會高雄電機技師公會高雄電機技師公會,,,, 2010/03/31
Image courtesy of the Taiwan Tourism Bureau
© ABB Group March 31, 2010 | Slide 2
The Relion® product familyFrom intercontinental transmission grids to secondary distribution kiosks
� 670 series - optimized for
transmission applications
� 630 series - optimized for
advanced distribution
applications
� 610 series - for dedicated
distribution applications
� 650 series – your best
choice for sub-transmission
applications
� 615 series - standard
configurations for
distribution applications
� 60_ series - for secondary
distribution applications
2
© ABB Group March 31, 2010 | Slide 3
� Same
� mechanical 19” design
� internal CAN bus & I/O cards
� Principle algorithms & logic
� Extended modular hardware
� Max 24 Analogue Inputs
� Max 14 I/O boards (i.e..224BI / Max 4 BOM = 98BO)
� More powerful CPU & memory capacity
� 600 MHz, 256 Mb DRAM + 64 Mb Flash
� Extended functional library (IEC 61850 nodes)
� Disturbance Recorder (100 x 3.4 s; 40 A + 96B)
� Extended communication facilities
� Multiple SA protocols
� Multiple differential communication channels
� Graphical HMI
� Engineering tool; PCM 600
� Signal matrix
� IEC 61850 configuration
IED670 670 vs 500 series; Evolution not Revolution
© ABB Group March 31, 2010 | Slide 4
IED670 Robust design for HMI, communication, AI and I/O
3
© ABB Group March 31, 2010 | Slide 5
IED670 Select your perfect hardware
© ABB Group March 31, 2010 | Slide 6
BIM
(max 11/14st)
16 binary inputs
BOM
(max 4st)
24 binary outputs
IOM
(max 6st)6 Transducer inputs,
setting range + 20 mA
MIM
(max 4st)
12 binary outputs
and 8 binary inputs
� Up to 24 analog inputs per IED permit integration of main and back-up protection in one IED
and/or additional objects
IED670 Available I/O-modules 1/1 19” case
4
© ABB Group March 31, 2010 | Slide 7
� Transformer Input Module TRM 6I + 6U, 9I+3U or 12I
� One or two - TRM1 & TRM2 for 12 or 24 analogue CT or VT inputs
� Analog Digital Conversion module ADM1 and ADM2 for TRM inputs
� Central Processing Unit NUM
� GPS time synchronization module GSM (option)
� Time synchronization via binary signal and communication ports IRIG-B
� Binary Input / Output modules BIM, SOM, BOM, IOM, MIM
� Power supply module PSM
IED670 670 Series Hardware Platform
© ABB Group March 31, 2010 | Slide 8
ABB IED 670
A/D
Module
~~
Analogue
Module
~~
A/D6 I
6 U
3
3
3
3
ConversionInput
Logics
Comm-uni-
cation
Main
ModuleProcessing
GPS
ModuleSynch
Binary
ModuleI/O
I/O
Binary
Module
I/O
CAN1Mbit/s
TRM AD1 NUM GSM BIM
PCU
OEMLDCM
Binary
ModuleI/O
BIM BIM MIM PSM
I/O I/O I/O
BOMBOM
Binary
Module
I/OBinary
Module
I/OPower
Module
SupplymA
Module
Input
mAI/O
IED670 670 Series Hardware Platform
5
© ABB Group March 31, 2010 | Slide 9
Transformer module (TRM 12) 1 A 5A 110/220 V
6I and 6U 6 6
6I and 6U 6 6
9I + 3U 9 3
9I + 3U 9 3
9I + 3U 5 4 3
12I 12
12I 12
6I
5I + 5U
6
5 5
IED670 Standardized Transformer Modules
© ABB Group March 31, 2010 | Slide 10
� GPS time synch module (GSM)
� IRIG-B time synch
� Up to 4 Protection Communication Modules for multi terminal line differential (LDCM)
� Optical Communication modules
� OEM IEC 61850-8-1 Ethernet
� OEM IEC 61850-9-2 Ethernet (restricted)
� SLM LON(1); SPA or IEC103
� RS485 DNP 3.0 module
� Static binary output module (SOM)
1/1 19” rack, 6U high
½ 19” rack, 6U high
IED670 Available I/O-modules 1/1 19” case
6
© ABB Group March 31, 2010 | Slide 11
� IED 670s are designed to communicate with substation automation systems
� IEC 61850-8-1
� verified by independent test institution
� IEC 60870-5-103
� LON
� SPA
� DNP 3.0
� TCP/IP communication to the PCM 600 tool
� IEC 61850-9-2 for process bus
� ANSI C37.94 for teleprotection
PC Ethernet connection
IEC 60870-5-103
or SPA
IEC 61850 8-1
or LON
192 binary
signals remote
communication
4 x 4 analog channels
4 x 8 binary signals
remote communication
IED670 Communication
© ABB Group March 31, 2010 | Slide 12
GOOSE
� Peer to peer communication
� An IED sends information by multicasting
� Only IEDs which are defined to listen (subscribers) receive this message
GOOSE = Generic Object Oriented System-wide Events
Data to be sent to other IEDs are
defined in the engineering tool
ProtectionControlProtectionControl Control &
Protection
IED670 ALL IED670 include GOOSE
7
© ABB Group March 31, 2010 | Slide 13
IED670 Powerful Information Management
� Protection and Control IED Manager for the 600 series
� PCM600
� PCM 600 consists of following tools:
� Application Configuration(CAP531)
� Signal Matrix (SMT)
Configuration of:
I/O cards,
Analog Input Cards
GOOSE
64 kbit communication
� Parameter Setting (PST)
� Disturbance Handling
� Graphic Display Editor (SLD Editor)
� Time scheduler
� Signal Monitoring
� Event Viewer
� User Management
© ABB Group March 31, 2010 | Slide 14
IED670 One Common Tool
8
© ABB Group March 31, 2010 | Slide 15
IED670 PCM600 Parameter Setting
© ABB Group March 31, 2010 | Slide 16
� All parameters set in primary quantities within
the pre-defined setting ranges
� Clear overview of parameter settings
uploaded from an IED and settings entered in
PCM 600
� Versatile filtering functions:
� Basic and advanced parameters
� Visible and hidden parameters
� Changed parameters
� Parameter value in IED differs from
the parameter value in PCM 600 and
invalid parameters
IED670 Full Control Over Parameter Settings
9
© ABB Group March 31, 2010 | Slide 17
� Easy to instantiate the power
system object into the display page
and assign it to its switching
function
� Easy to include on-line
measurement in the IED HMI
� Easy to set node attributes like
name, name position and sort index
� Extensive IEC and ANSI symbol
library
IED670 PCM600 Graphical Configuration of IED HMI
© ABB Group March 31, 2010 | Slide 18
� Signal monitoring for on-line information about the measured quantities and status of binary input and output signals
� All signals can be monitored in a signal list
� A report can be generated, printed and exported to Excel
� Event viewer for viewing process events and internal system events on-line
IED670 Monitoring
10
© ABB Group March 31, 2010 | Slide 19
IED670 Signal Matrix Tool (SMT)
© ABB Group March 31, 2010 | Slide 20
IED670 Signal Matrix Tool (SMT)
11
© ABB Group March 31, 2010 | Slide 21
HARDWARE: Binary Input Card
IED670 SMT: Virtual and Real Binary Inputs
© ABB Group March 31, 2010 | Slide 22
IED670 The role of SMT for Binary Outputs
12
© ABB Group March 31, 2010 | Slide 23
IED670 Analog Input Configuration
© ABB Group March 31, 2010 | Slide 24
� 40 analog channels
� flexible analog configuration
� voltages and/or currents (30 channels via AIM, LDCM or Σ-block)
� derived analog signals (10 channels)
� setting possibilities:
� be recorded or not
� trig disturbance recording
� 96 binary channels
� any internal or external (via BIM) binary signal
� these 96 signals are logged into IED internal Event List
� setting possibilities:
� be recorded or not
� trig disturbance recording and trigger mode
� be included in Indications
� activate local HMI LED
IED670 Disturbance Recorder – Inputs
13
© ABB Group March 31, 2010 | Slide 25
TOTAL RECORDING
Visualisation of the full disturbance: analog and binary signals.
IED670 PCM 600 - Disturbance Report Tool
© ABB Group March 31, 2010 | Slide 26
� The event buffer can store and show on display
up to 1000 events on a FIFO principle
� The events are time tagged with a resolution of
1 ms
� The user can choose in having the last event on
top or the last event on bottom
� Events can be defined as a part of the
Disturbance Report
� Upload event list to PC
� Event list sorting facility
Ev e n
No r t Co n nh e c o n2 0 0 4 - 1 2 1- 7 0 8 : 3 7
t s L i s t
51 2 : 1 7 : 4 . 7 1 151 2 : 1 7 : 4 . 1 1 TR I P - T 1RL
5 3 . 6 1 15 . 1 1 TR I P - T PR I
. 6 1 1. 1 1 ZM3 - STL 1
. 6 1 1. 1 1 CB1 - CLOSE
51 2 : 1 6 : 8 . 7 1 151 2 : 1 : . 1 1 ZCOM- CS
5 7 . 6 1 15 . 1 1 TR I P - T PR I
. 6 1 1. 1 1 TOC1 - T PR I
52 0 0 4 - 1 2 1-
51 2 : 1 7 : 6 . 7 1 151 2 : 1 7 : . 1 1
5 5 . 6 1 15 . 1 1
. 6 1 1. 1 1
. 6 1 1. 1 1
51 2 : 1 6 : 8 . 7 1 151 2 : 1 : . 1 1
5 7 . 6 1 15 . 1 1
. 6 1 1. 1 1
42 0 0 4 - 1 2 1-
51 2 : 1 7 : 6 . 7 1 151 2 : 1 7 : . 1 1
5 5 . 6 1 15 . 1 1
. 6 1 1. 1 1
. 6 1 1. 1 1
51 2 : 1 6 : 8 . 7 1 151 2 : 1 : . 1 1
5 7 . 6 1 15 . 1 1
. 6 1 1. 1 1
32 0 0 4 - 1 2 1-
51 2 : 1 7 : 6 . 7 1 151 2 : 1 7 : . 1 1
5 5 . 6 1 15 . 1 1
. 6 1 1. 1 1
. 6 1 1. 1 1
22 0 0 4 - 1 2 1-
o n
o n
o n
o n
o f f
o n
o n
t i
450
210
660
970
690
210
110
TR I P - T 1RL
TR I P - T PR I
ZM3 - STL 1
CB1 - CLOSE
ZCOM- CS
TR I P - T PR I
TOC1 - T PR I
o n
o n
o n
o n
o f f
o n
o n
450
210
660
970
690
210
110
TR I P - T 1RL
TR I P - T PR I
ZM3 - STL 1
CB1 - CLOSE
ZCOM- CS
TR I P - T PR I
TOC1 - T PR I
o n
o n
o n
o n
o f f
o n
o n
450
210
660
970
690
210
110
TR I P - T 1RL
TR I P - T PR I
ZM3 - STL 1
CB1 - CLOSE
o n
o n
o n
o n
450
210
660
970
\ E v e n t
IED670 Event List Handling
14
© ABB Group March 31, 2010 | Slide 27
IED670 IED670 Operation introduction
© ABB Group March 31, 2010 | Slide 28
Status indication
� GreenSteady: In serviceFlashing: Internal failureDark : No power supply
� Yellow:Steady: Disturbance recorder triggeredFlashing: IED in test mode
� Red:Steady: Trip command issued
Flashing: IED blocked
Measurements
� Single line diagram presents measurements
� Selected measurements
� Selected calculated values
IED670 Fast Access to Information
15
© ABB Group March 31, 2010 | Slide 29
� Service Value Measurement (I, U, P, Q, S, f)
� Configurable logic and event counter
� Signal and Tripping matrix
� Remote communication (requires LDCM)
� Event list (1000 signals)
� Disturbance recorder for 40 analogue & 96 digital channels
� 100 disturbances
� Trip value & internal signals report
� Supervision of I, U and mA inputs
� Real time clock with external synchronization
� 1 ms time tagging resolution
� 6 setting groups
� >< U, I, I1 , I2 , 3I0 , f, Z configurable functions
� Self supervision & diagnostics
IED670 Main Basic Functions in IED 670
© ABB Group March 31, 2010 | Slide 30
� Five Zone full scheme distance protection
� Five terminal line differential protection
� Six input transformer differential protection
� Generator differantial/block differential
� High impedance and restricted EF differential
� Ultra High Speed bus differential protection
� Phase segregated directional comparison
� Adaptive Breaker Failure Protection
� Four step Dir/Undir overcurrent protection
� Four step Dir/Undir earthfault protection
� Over Excitation & Over Load Protection
� Multi purpose protection (E.g. Generators, Mho)
� Multi bay & Multi breaker Control, AR & SC
� Multi input measurement (24 AI)
� High accuracy fault locator
IED670 Main Application Functions in IED670
16
© ABB Group March 31, 2010 | Slide 31
IED670 – Application areas
REC670
REL670
RET670
RED670
� Busbar protection IED for
� Autotransformers
� Shunt Reactors
� Shunt Capacitors
REB670� Generator protection IED for
� small to medium sized generators
REG670
IED670
© ABB Group March 31, 2010 | Slide 32
IED670 ABB Substation Automation Web Site
17