![Page 1: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/1.jpg)
Copyright © SEL 2017
Protection Challenges for North America’s First Combined Cable / Overhead
Double-Circuit 500 kV Transmission Line With Mutual Coupling
Denis Bucco, Curtis Sanden, Arturo Torres, and Edward Wong Southern California Edison
Jordan Bell, Normann Fischer, and John ThompsonSchweitzer Engineering Laboratories, Inc.
Copyright © SCE and SEL 2017
![Page 2: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/2.jpg)
Project Background
• New 75-mile 500 kV transmission line• Single-circuit and double-circuit construction• Protection package System A – Line current differential
System B – Directional comparison blocking
System C – Permissive overreaching transfer trip
![Page 3: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/3.jpg)
Decreasing Land Availability…
CSUSB WRI ©
© 2016 Google
![Page 4: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/4.jpg)
From Overhead…
To Underground
![Page 5: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/5.jpg)
TransitionTowers
East
West
![Page 6: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/6.jpg)
Cable Layout
![Page 7: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/7.jpg)
Vaults and Terminations
![Page 8: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/8.jpg)
Overall Line Composition
![Page 9: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/9.jpg)
Line Section 1: 33 Miles
• Two conductors per phase• Segmented ground wires
![Page 10: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/10.jpg)
Line Section 2: 28 Miles
• Two conductors per phase• Segmented ground wires
![Page 11: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/11.jpg)
Line Section 3: 4 Miles
• Underground• Two cables per phase
![Page 12: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/12.jpg)
Line Section 4: 8 Miles
• Line 1: 500 kV line• Line 2: Future 500 kV line
![Page 13: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/13.jpg)
Impedance Comparison
UndergroundZ1 = 0.02 + j0.31 = 0.31 ∠86° ohms / mile
Z0 = 0.20 + j0.13 = 0.24 ∠33° ohms / mile
OverheadZ1 = 0.05 + j0.58 = 0.58 ∠85° ohms / mile
Z0 = 0.44 + j2.13 = 2.17 ∠78° ohms / mile
![Page 14: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/14.jpg)
IG ~ 0
Ground Wire Segmentation
• Phase conductors induce voltage in ground wire• Induced voltage leads to circulating current and losses
• Segmenting ground wires prevents circulating current
IG ≠ 0
![Page 15: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/15.jpg)
Line Impedance Calculation
Where:
ZAA = Self impedance
ZAB and ZBC = Mutual impedance between phases
ZAA′, ZAB′, and ZAC′ = Mutual impedance between the A-phase conductor Line 1 and φ-phase conductor Line 2
VADROP = ZAA • IA + ZAB • IB + ZAC • IC + …ZAA′ • IA′ + ZAB′ • IB′ + ZAC′ • IC′
![Page 16: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/16.jpg)
Put in Matrix Form…
VADROP
VBDROP
VCDROP
VAʹDROP
VBʹDROP
VCʹDROP
ZAA ZAB ZAC ZAAʹ ZABʹ ZACʹ
ZBA ZBB ZBC ZBAʹ ZBBʹ ZBCʹ
ZCA ZCB ZCC ZCAʹ ZCBʹ ZCCʹ
ZAʹA ZAʹB ZAʹC ZAʹAʹ ZAʹBʹ ZAʹCʹ
ZBʹA ZBʹB ZBʹC ZBʹAʹ ZBʹBʹ ZBʹCʹ
ZCʹA ZCʹB ZCʹC ZCʹAʹ ZCʹBʹ ZCʹC
IA
IB
IC
IAʹ
IBʹ
ICʹ
•=
![Page 17: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/17.jpg)
…Then Sequence Domain
Z0 w x Z0M wm xm
w Z1 y wm z1m ym
x y Z2 xm ym z2m
Z0M wm xm Z0ʹ xʹ yʹ
wm z1m ym xʹ Z1ʹ zʹ
xm ym z2m yʹ zʹ Z2ʹ
=(Z012)
Line 1 Mutual
Mutual Line 2
![Page 18: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/18.jpg)
Parallel Line Apparent Impedance
ZS_TERM = m • ZL1 (1 – ½ m)
ZT_TERM = ½ • ZL1 • (1 – m2)
![Page 19: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/19.jpg)
Double-Circuit Apparent Impedance
0
2
4
6
8
10
0% 20% 40% 60% 80% 100%
Ohm
s Se
cond
ary
TheoreticalApparent
![Page 20: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/20.jpg)
Sequence Impedance Through Energization
Positive-sequence Zero-sequence
![Page 21: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/21.jpg)
Impedance Calculation
Matrix calculationZ1 = 3.26 + j33.32 Ω
Z0 = 24.73 + j142.65 Ω
EnergizationZ1 = 3.56 + j33.92 Ω
Z0 = 25.30 + j144.80 Ω
![Page 22: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/22.jpg)
Charging Current Leads to High Voltage
Distributed capacitance charging current
Total charging current
Voltage rise
![Page 23: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/23.jpg)
Charging Current Leads to High Voltage
≈ 2 amperes per mile overhead≈ 40 amperes per mile underground
Ph Ph1_CHRG 1
VI j C3−= ω
550
560
570
580
590
0 10 20 30 40 50 60 70
Volta
ge (k
V)
Line Distance (Miles)
Vincent
![Page 24: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/24.jpg)
Protection System Validation
• Reduce short-circuit model to area of interest• Maintain 500 kV system with boundary equivalents• Build model in real-time digital simulator • Choose realistic operating conditions• Integrate physical relays with simulation
![Page 25: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/25.jpg)
Protection System ValidationTest Plan
• Basic internal and external faults• Line energization and load pickup• Zone 1 margin• High-impedance faults• Batch tests
![Page 26: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/26.jpg)
Batch Tests
• All internal and external fault locations (21 internal and 10 external)
• Ten fault types (AG, BG, CG, ABG, BCG, CAG, AB, BC, CA, and ABCG)
• Four fault inception angles (0, 30, 60, and 90 degrees)• All load flow cases
![Page 27: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/27.jpg)
Distance Element Performance
0.0
2.0
4.0
6.0
4.5 3.3 2.2 1.1 0.0Mea
sure
d Im
peda
nce
(Ohm
s)
Theoretical Impedance (Ohms)
Mira Loma
0.0
2.0
4.0
6.0
0.0 1.5 3.0 4.5 6.0
Mea
sure
d Im
peda
nce
(Ohm
s)
Theoretical Impedance (Ohms)
Vincent
![Page 28: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/28.jpg)
Zone 1 PerformanceManufacturer A
0%
20%
40%
60%
80%
100%
0% 20% 40% 60% 80% 100%
Ope
ratio
ns
Fault Location
![Page 29: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/29.jpg)
Zone 1 PerformanceManufacturer A
Zone 1 PerformanceManufacturer A
3
3.5
4
4.5
5
5.5
6
6.13 6.50 6.88 7.25 7.63 8.00 8.38
Impe
danc
e (O
hms)
Time (Cycles)
![Page 30: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/30.jpg)
Modify Settings and RepeatManufacturer A
0%
20%
40%
60%
80%
100%
0% 20% 40% 60% 80% 100%
Ope
ratio
ns
Fault Location
![Page 31: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/31.jpg)
How Did the Other Relay Do?Manufacturer B
0%
20%
40%
60%
80%
100%
0% 20% 40% 60% 80% 100%
Ope
ratio
ns
Fault Location
![Page 32: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/32.jpg)
Manufacturer A Distance Performance
0.0
0.8
1.5
2.3
3.0
0% 20% 40% 60% 80% 100%
Ope
ratin
g Ti
me
(Cyc
les)
Fault Location
![Page 33: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/33.jpg)
Manufacturer B Distance Performance
0.0
0.8
1.5
2.3
3.0
0% 20% 40% 60% 80% 100%
Ope
ratin
g Ti
me
(Cyc
les)
Fault Location
![Page 34: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/34.jpg)
Manufacturer B Differential Performance
0.0
0.8
1.5
2.3
3.0
0% 20% 40% 60% 80% 100%
Ope
ratin
g Ti
me
(Cyc
les)
Fault Location
![Page 35: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/35.jpg)
Impedance-BasedFault LocatorManufacturer A
0.0
5.0
10.0
15.0
20.0
0.0 11.2 22.4 33.6 44.8 56.0 67.2Faul
t Loc
atio
n E
rror
(Mile
s)
Fault Location (Miles)
0.0
5.0
10.0
15.0
20.0
0.0 11.2 22.4 33.6 44.8 56.0 67.2Faul
t Loc
atio
n E
rror
(Mile
s)
Fault Location (Miles)
![Page 36: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/36.jpg)
Traveling-Wave Fault Locator
• Explored to evaluate functionality on this composite line• Simulated in non-real time• Saved waveforms and replayed into the relays• Evaluated the relay response
![Page 37: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/37.jpg)
Traveling-Wave Reflections
LL1, V1 LL2, V2 LL3, V3 LL4, V4
t0
t1
t2
t3t4
OpenClosed
IncidentReflectedJunction
![Page 38: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/38.jpg)
Traveling-Wave Waveform
-5.0
-3.0
-1.0
1.0
3.0
5.0
Cur
rent
Mag
nitu
de(A
mpe
res
Seco
ndar
y)
Time (Cycles)
![Page 39: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/39.jpg)
Traveling-Wave Measurements
-100
-60
-20
20
60
0 160 320 480 640 800 960 1,120
Trav
elin
g-W
ave
Mag
nitu
de
(Am
pere
s)
Time (Microseconds)
t0
t1
t2
t3 t4
![Page 40: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/40.jpg)
Traveling-Wave Fault Locator Accuracy
-0.40
-0.20
0.00
0.20
0.40
0.60
0.00 18.67 37.34 56.01 74.68
Faul
t Loc
ator
Err
or
(Mile
s)
Line Length (Miles)
![Page 41: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/41.jpg)
Summary
• Transmission line incorporated underground cables• Protection scheme needed reevaluation to include
multiple line current differential relays• Real-time digital simulation validated relay performance
![Page 42: Protection Challenges for North America’s First Combined ...prorelay.tamu.edu/wp-content/uploads/sites/3/2017/04/1-Protection... · Positive-sequence. Zero-sequence. Impedance Calculation](https://reader034.fdocuments.net/reader034/viewer/2022052609/5b15de877f8b9ae4038bed70/html5/thumbnails/42.jpg)
Questions?