![Page 1: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/1.jpg)
© 2015 HDR, all rights reserved.
Scott Elling – HDR Inc.
Protecting Feeders With Distributed Resource
![Page 2: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/2.jpg)
Several Hundred Mega Watts of distributed PV
Distribution Grid is no longer radial
Protection Considerations
Background
![Page 3: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/3.jpg)
Quick Review
Protection considerations
Reclosing
Inverters vs Rotating Mass
Challenges
Directionality with PV
Agenda
![Page 4: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/4.jpg)
Complete coverageo Relay Reach
Minimize outages
ProtectionConsiderations
![Page 5: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/5.jpg)
Protective Reach
No Dead Zones
![Page 6: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/6.jpg)
Protective Reach
No Dead Zones
Verify Relay trips for Ph-Ph Fault
![Page 7: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/7.jpg)
Protective Reach
No Dead Zones
Verify Relay trips for Ph-Gr Fault
![Page 8: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/8.jpg)
Protective Reach
Ph-Ph Ph-Gr
*Plotted in CAPE
![Page 9: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/9.jpg)
Selectivity
TOC Coordinationo Upstreamo Downstream
Minimize Outages
![Page 10: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/10.jpg)
Trip feeder before transformer fuse begins to melt
Upstream TOC Coordination
![Page 11: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/11.jpg)
Trip feeder before transformer fuse begins to melt
Verify Ph-Ph Fault
Upstream TOC Coordination
![Page 12: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/12.jpg)
Trip feeder before transformer fuse begins to melt
Verify Ph-Gr Fault
Upstream TOC Coordination
![Page 13: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/13.jpg)
Ph-Ph Ph-Gr
Upstream TOC Coordination
*Plotted in CAPE
![Page 14: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/14.jpg)
Fuse should melt before feeder relay sends trip
Trip Saving Scheme
Downstream TOC Coordination
![Page 15: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/15.jpg)
Fuse should melt before feeder relay sends trip
Trip Saving Scheme
Verify 3-Ph Fault
Downstream TOC Coordination
![Page 16: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/16.jpg)
Fuse should melt before feeder relay sends trip
Trip Saving Scheme
Verify Ph-Gr Fault
Downstream TOC Coordination
![Page 17: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/17.jpg)
3-Ph Ph-Gr
Downstream TOC Coordination
*Plotted in CAPE
![Page 18: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/18.jpg)
How is relay reach affected?
How TOC coordination affected?
What happens when we add PV?
![Page 19: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/19.jpg)
Infeed
o Accounts for a portion of the voltage drop to the fault
o Fault current provided by Substation reduces
Effects on Relay Reach
![Page 20: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/20.jpg)
Infeed
o Accounts for a portion of the voltage drop to the fault
o Fault current provided by Substation reduces
o Recheck Ph-Ph Fault
Effects on Relay Reach
![Page 21: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/21.jpg)
Infeed
o Accounts for a portion of the voltage drop to the fault
o Fault current provided by Substation reduces
o Recheck Ph-Gr Fault
Effects on Relay Reach
![Page 22: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/22.jpg)
Ph-Ph Ph-Gr
Effects on Relay Reach
*Plotted in CAPE
![Page 23: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/23.jpg)
The infeed desensitizes the Substation relay
Fault clearing times could become very high
The relay might not reach the entire zone of protection
Effects on Relay Reach
![Page 24: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/24.jpg)
Source is intermittent
We need to protect for the worst case
PV may only be used against you
Does it adversely affect coordination?
![Page 25: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/25.jpg)
Remove infeed to downstream devices when coordinating with Substation Relay
PV may only be used against you
![Page 26: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/26.jpg)
Remove infeed to downstream devices when coordinating with Substation Relay
PV may only be used against you
![Page 27: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/27.jpg)
Do not remove the PV when coordinating the feeder reclosers with downstream fuses
PV may only be used against you
![Page 28: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/28.jpg)
Coordination and Reach Summary
Time in Cycles Before AfterReach Trip Time Ph-Ph 115 200Reach Trip Time Ph-Gr 345 565Upstream CTI 15 15Downstream CTI 17 17
*CTI: Coordination Time Interval
![Page 29: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/29.jpg)
PV behaves like a current source Inverters have no inertia Zero-sequence and negative-sequence current suppressed Positive-sequence current limited
Inverters vs Rotating Mass
![Page 30: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/30.jpg)
I1,PV limited
I2,PV suppressed
I0,PV exists via Ground Transformer
Sequence Networks
![Page 31: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/31.jpg)
I1,PV limited
I2,PV suppressed
I0,PV exists via Ground Transformer
Ph-Gr Fault
Sequence Networks
![Page 32: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/32.jpg)
I1,PV limited I2,PV suppressed
Sequence Networks
Ph-Ph Fault
![Page 33: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/33.jpg)
IEEE 1547 states DER should shut down in less than two seconds if Utility source is lost
UL 1741 certification
DER Employs Anti-Islanding
![Page 34: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/34.jpg)
Rotating Mass on same distribution grid
Transfer Trip to avoid islanding
Transfer Trip
![Page 35: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/35.jpg)
Distributed resource includes Anti-Islanding Protection Do not reclose before the Anti-Islanding operates Load-to-Generation ratio – Supervision may not be necessary
if the minimum load exceeds the DER by an adequate threshold
Reclosing Considerations
![Page 36: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/36.jpg)
Dead Line Only
Hot Bus – Dead Line
Synchronous Voltage
Potential Required
Be mindful of upstream reclosing
Supervision Options
![Page 37: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/37.jpg)
Use caution with ATO Schemeso Allow Anti-Islanding Protection to operate before throwing over to
Back-up Transformerso Add supervision or a time delay to operation
Ensure voltage regulators support bi-directional flow and set them accordingly
Substation Considerations
![Page 38: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/38.jpg)
Modelling the PV DERo Gathering necessary information in allotted timeo Nonconventional system parameters
Quantity of installations over limited time periodo Hundreds of MW installed in a 2 year span
Challenges Encountered
![Page 39: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/39.jpg)
Smaller fused distribution transformers leave very little or no budget to squeeze consecutive protective zoneso Transformer fuse to Feeder relay to downstream recloser to solar
garden fuse
Some reclosers fit the desired standard installation better than others
Sorting out whether issues were existing or caused by the PV insertion
Challenges Encountered
![Page 40: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/40.jpg)
Reverse looking directional element set more sensitive than non-directional elemento PV will not provide negative sequence current
Reverse looking directional element to supervise recloserso Directionality is inherent simply based on magnitudeo PV supplies 1.1 – 1.3 p.u. current under fault condition
Should directionality be utilized?
![Page 41: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/41.jpg)
Questions?
![Page 42: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/42.jpg)
System Parameters
![Page 43: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/43.jpg)
System ParametersA - SourceVoltage 69 kVMVA 100R1 0.04201 puX1 0.16803 pu (Subtransient)R0 0.03151 pu (Subtransient)X0 0.1890 pu
B - High Side FuseSpeed Class SlowDesignation 100E
C - Distribution Transformer69 kV – 13.8 kVDyg1MVA 8.4/10.5Z1 7%Z0 6%
D - Feeder Relay TOC CurvesPhase Pick-up 672 APhase Time Dial 1.2Phase Curve U.S. InverseGround Pick-up 480 AGround Time Dial 7 Ground Curve U.S. Very Inverse
![Page 44: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/44.jpg)
System ParametersE - Line SegmentR1 0.07194 puX1 0.17223 puR0 0.24890 puX0 0.60360 pu
F - Branch FuseSpeed Class TDesignation 140T
G - Line SegmentR1 0.57551 puX1 1.37786 puR0 1.99118 puX0 4.82882 pu
H - Line SegmentR1 0.03597 puX1 0.08612 puR0 0.12445 puX0 0.30180 pu
I - Recloser TOC CurvesPhase Pick-up 300 APhase Time Dial 2Phase Curve U.S. Very InverseGround Pick-up 150 AGround Time Dial 7Ground Curve U.S. Very Inverse
![Page 45: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/45.jpg)
System ParametersJ - Inverter Step-up FuseSpeed Class TDesignation 40T
K - Ground Transformer* 5 parallel transformersZig-ZagMVA 1Base kV 13.8R0 0.03 puX0 0.6 pu
L - Inverter Step-up (ISU) Transformer* 5 parallel transformers13.8 kV – 480 VYd1MVA 1Z1 6%Z0 6%
M - Lump PV Source and Inverter* 5 parallel sourcesVoltage 480 VMVA 1R1 0.0 puX1 0.217 pu (Subtransient)R2 InfiniteX2 InfiniteR0 InfiniteX0 InfiniteCurrent Limit 1.2 pu
![Page 46: Protecting Feeders With Distributed Resource · Protecting Feeders With Distributed Resource Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection](https://reader030.fdocuments.net/reader030/viewer/2022040601/5e9381633061891d5303464a/html5/thumbnails/46.jpg)