Project Report of Electrical

download Project Report of Electrical

of 49

Transcript of Project Report of Electrical

  • 8/3/2019 Project Report of Electrical

    1/49

    IN ELECTRICAL SYSTEM

    (15 JUNE TO 20 JULY) NUCLEAR POWER CORPORATION

    (A GOVT. OF INDIA ENTERPRISE)

    GUIDED BY: PREPARED BY :Mr. RAMESH CHANDRA REKHA VERMATraning Suptd. B.E IIInd Year (ELECTRICAL)

    A.M.U, ALIGARHMr.S.K.Verma, SO/E

    Traning officer

    1

  • 8/3/2019 Project Report of Electrical

    2/49

    1) I am indebted & thankful to our respectable ShriN.S. RANA, SO/F, Electrical Engineer forextending all his advices, help and guidancehereby making it possible for me to complete

    the project.

    2) I am also thankful to S/Shri H.S.SINGH,AJAYPATHAK,& R.K. SHARMA for his help, supportand cooperation.

    REKHA VERMAB.E. IIIrd YearELECTRICAL

    A.M.U, ALIGARH

    2

  • 8/3/2019 Project Report of Electrical

    3/49

    Energy : The pulse of all life

    And the lord said Let there be light.

    This verse from the holy bible clearly brings out the dependence of the light, but it also

    further our scientific belief that energy is most definitely the key component in the foundationas well as flourishing of all life on this planet. Just the perfect amount of solar energy

    reaching earth has enabled life to evolve here.

    Today the human beings, we find ourselves resting on the pinnacle of progress, but if we trace

    the history of our civilization, we will find that through the ages, we have measured our

    development eventually in terms of how much energy we can produce, consume, convert or

    govern. In his long journey from a measly slave to the master of nature, man has learned to

    harness energy and to use it for his own benefit.

    One careful look around us shall be sufficient to reveal that today, we live our lives in the

    cozy cradle of a world which is moulded to suit best to our requirements by the advancedtechnology of the day; and technology, it just provides us with never and better ways to

    manipulate energy and put it to use. Our lamps convert electrical energy to light to illuminate

    our world, our cars burn petrol to give mechanical energy and enhance our locomotion and

    our air-conditioners working as reverse heat engines, cool our room to suit our need.

    We can very reasonably say that energy in some form or the other, is the pulse of our lives

    today. After all can we imagine our lives without the machines and the gadgets buzzing

    around us but what is worth noting here is that we always need to supply any appliances with

    energy and manipulate it for our benefit. If we want to run our car, we need to supply it with

    the chemical energy in the form of petrol, if we want our fans; we need to supply it with

    electrical energy. One of the fundamental laws of nature is the law of conservation of energy.

    We need to provide energy to our entire energy based appliances before they can be of any

    use

    3

  • 8/3/2019 Project Report of Electrical

    4/49

    INTRODUCTION OF NAPS

    One of the chief aims of the Department Of Atomic Energy is the

    development of Nuclear Energy for economic generation as analternative source of electric power when in due course the conventionalsources will be exhausted in the country.

    Petroleum prices are escalating. The amount of coal required for 400MWe power generations of the order of 5 x 10 6 kgs per day. Whereas anuclear power station of the same capacity need only 200 kg of AtomicFuel per day. Transportation of coal of such magnitude over longdistance is not economical.

    The strategy adopted for Indian Nuclear Power program is that heavywater power reactors using natural uranium would produce power andplutonium in the first stage. The plutonium produced from these reactorswould be used to set high breeding ratio fast reactors to produceadditional power and plutonium in the second stage. In the third stagethorium would be utilized in both the fast and the thermal reactors whichwould give unlimited source of power.

    Consequently it was decided to build twin PHWR (pressurized Heavywater reactor) type of power reactors. The site is selected by a highpowered committee, based on the need of electrical power, the potentialof industrial expansion, availability of large quantities of water and lesspopulation.

    NARORA, a small ancient village, is situated on the bank of holy riverGanga in the district Bulandshahr in Uttar Pradesh. The plant is about 60km from Aligarh which is the nearest population centre.

    With the synchronization of the Narora Atomic Power Station withnorthern grid through five lines of 220KV, it occupied an important placeon the power map of the India. With this, yet another important milestonein the Indian nuclear programme has been achieved as NAPS is an efforttowards standardization of PHWR units and a stepping stone to the500MWe units. A significant and unique feature of this project has beenthe evolution of the design suitable for seismic sites.

    The NAPS is a twin unit module of 220MWe each of pressurized heavy

    water reactors. The reactors use natural uranium available in India asfuel and heavy water produced in the country as moderator and coolant.

    4

  • 8/3/2019 Project Report of Electrical

    5/49

    The execution of this project, including design, engineering erection,commissioning, and operation has been done by the Indian engineersand Scientists. The foreign exchange component is about only 10% of

    the project cost of Rs. 723 crores- mostly for the import of specialmaterials and equipment.

    NAPS is the fourth Nuclear Power Station in the country after Tarapur inMaharasthra, Rawatbhata in Rajasthan & Kalpakkam in TamilNadu.NAPS is the 1st indigenous nuclear power plant of India. The station hastwo pressurized heavy water reactors with an installed capacity of 220Mwe each using natural uranium as fuel.

    The station is connected to high voltage net work through five 220 KVlines, one to Moradabad, one to Harduaganj, one to Simboli, and two tokhurja. It is designed for base load operation as a commercial station.

    5

  • 8/3/2019 Project Report of Electrical

    6/49

    NARORA ATOMIC POWER STATION

    6

  • 8/3/2019 Project Report of Electrical

    7/49

    Reactor building houses the reactor primary heat transport system,moderator system, reactivity system, fuel handling system and some ofthe auxiliaries. The turbo-generator and its associated conventionalequipment, emergency diesel sets, control and power MG sets, stationbatteries, electrical switch gear compressors, chillers and main controlroom are located in turbine building. Both the units share common

    facilities such as service building, spent fuel storage bay and otherauxiliary devices such as heavy water upgrading and wastemanagement facility.

    NAPS has two natural draught cooling and two induced draughtcooling towers.

    NAPS has the following main parts:-

    1. Administration Building.2. Overhead water tank.3. Canteen4. Natural Draught Cooling Towers5. 220KV Switch Yard6. Stack.7. Service Building8. Small LOCA Room.9. Reactor Building.

    10. Purification Building11. Turbine Building12. Pump house

    7

  • 8/3/2019 Project Report of Electrical

    8/49

    8

  • 8/3/2019 Project Report of Electrical

    9/49

    S.NO DATA SPECIFICATION

    1. Transmission Lines Five

    230KV Narora-Moradabad Single Line

    230KV Narora-Harduaganj Single Line

    230KV Narora-Shimboli Single Line

    230KV Narora-Khurja Double Line

    2. Stack Height 142 Meters

    3. NDCT Height 128 Meters

    4. NDCT Top Dia. 107 Meters

    5. NDCT Base Dia. 58 Meters

    6. NDCT Throat Dia. 53 Meters

    7. Steam Flow 1314 Tonnes/hour

    8. PHT Flow 12700 Tonnes/hour

    9. Steam Pressure 48-40 kg/cm2

    10. PHT Pressure 87.0 kg/cm2

    11. CCW Flow 39000 Tonnes/hour

    12. Coolant Tubes 306

    13. No. of Fuel Bundles in one channel 12

    14. Fuel Bundle Weight 15 kgs

    15. Condenser Pressure 680 mm of hg

    16. RB Design Pressure 1.25 kg/cm2

    17. Station Load 18-20 MWe

    18. Generator Power 220 MWe19. Grid Voltage 220 KV

    Foundation Stone 4th

    Jan. 1974 4th

    Jan. 1974Excavation Started 15th Feb. 1976 15th Feb. 1976

    Fuel loading 11th oct. 1988 9th aug. 1991

    Ist criticality 12th march 1989 24th oct. 1991

    Commercialization 29th July 1989 5th Jan. 1992

    9

  • 8/3/2019 Project Report of Electrical

    10/49

    Following are the Indias atomic power stations operating as on today:-

    S.NO. PLACE CAPACITY

    1. TAPS (1 & 2) 2X160MWe

    2. RAPS (1 & 2) 2X220MWe

    3. MAPS ( 1 & 2) 4. NAPS( 1 & 2)

    5. KAKRAPAR ( 1 & 2)

    6. KAIGA ( 1 & 2)

    7. RAPS ( 3 & 4)

    8. TAPS ( 4) 1X540 MWe

    Following are the power stations under construction:-

    S.NO. PLACE CAPACITY

    1. TAPS ( 3 ) 1X540 MWe

    2. RAPS ( 5 & 6 ) 2X220 MWe

    3. KAIGA ( 3 & 4 ) 2X220 MWe

    4. KUNDAKULAM ( 1& 2 ) 2X1000 MWe

    10

  • 8/3/2019 Project Report of Electrical

    11/49

    Nuclear Power Plants generate electricity. A Thermal Power Plant burns

    coal to produce heat. The heat converts water to steam, which in turndrives the turbine and the generator to produce electricity. The maindifference between the Nuclear Power Plant and the Thermal PowerPlant is that Thermal Power Plant gets heat energy by burning coalwhereas the Nuclear Power Plant produces heat by the process calledFission of U-235 Nuclei. The heat produced is used to convert water intosteam. The steam runs the turbine and generator and the electricity isgenerated by the generator.

    The fission energy is transported from the fuel bundle with the help ofhigh-pressure heavy water called Primary Heat Transport (PHT). ThePHT System takes away the heat from the fuel bundles and exchangesthis heat to the Demineralised water (Feed water) into the steamgenerator and the steam at a pressure of 40-48 Kg/cm2 is generated inthe steam generator. This steam is then transported through pipes toturbine hall where the turbine and the generator are installed. This steamis then admitted to the turbine, which runs at a speed of 3000 rpm. Thegenerator also runs at the same speed as both are coupled together with

    the coupling. The generator rotor is excited here with the DC voltage andEMF is produced at the stator of generator at 16.5 KV. This generatedvoltage is then stepped up from 16.5 KV to 230 KV by a three phasetransformer and this stepped up electricity is then sent to the stationswitchyard for the further transmission to the Northern Grid. This steamafter working in the turbine is condensed into a surface type ofcondenser and the condensed steam are again fed back to the steamgenerator through a chain of six reheaters.

    NUCLEAR REACTION

    In a fission reaction, besides the two fission products, a few (in the caseof U-235 2.47 on the average) neutrons are emitted . The principle ofchain reaction is very easy therefore: a U235 nucleus is hit by a neutron,upon which fission occurs at a high probability. The neutrons produced inthis process can cause more fissions, 200 MeV energy is released eachtime. Consequently, the process becomes self-sustaining and noexternal neutron source is needed any longer.

    If the neutrons produced from a fission induce only one new fission(because of escaping from the system or being captured inside) we say

    11

  • 8/3/2019 Project Report of Electrical

    12/49

    that the chain reaction is of constant intensity. If the neutrons generatedfrom a fission reaction induce more than one fission than more and morefission reactions will take place in a unit time and the chain reaction willbe diverging.

    12

  • 8/3/2019 Project Report of Electrical

    13/49

    PROTECTIVE RELAY

    It is a device, which senses the abnormal condition ofelectrical equipment or system and isolation. The faultparty from the system by tripping the appropriate circuitbreakers.

    Some abnormal conditions are: -

    1. Insulation failure.2. Breakage of conductor.3. Localized heating.4. Inadequate Rating.

    EFFECT OF FAULT:

    Damage to equipment due to excessive current.

    Loss of supply to large parts of the system.

    FUNCTIONAL CHARACTERSTICS OF RELAY

    Selectivity

    Protection is arranged in zones, which should cover thepower system completely leaving no part unprotected.

    When a fault occurs the protection is required to selectand trip only ckt breaker.13

  • 8/3/2019 Project Report of Electrical

    14/49

    Sensitivity

    It refers to the smallest value of actuating quantity atwhich protection start operating in relation with theminimum value of fault current in protected zone.

    Stability

    It refers to the ability of the system to remain to all load

    condition and faults external to relevant zone.

    Speed

    The function of automatic protection is to isolate faultfrom the power system in much shorter time to meet thefollowing.

    Reliability

    The protection should not fail to operate in the event offaults in the protected zone.

    TYPES OF RELAY:

    Some important relays are given below: -

    Instantaneous over current Relay:

    It is applied for phase fault protection of Motor feeders,Transformers feeders etc.

    14

  • 8/3/2019 Project Report of Electrical

    15/49

    Earth fault relay type:

    It is basically an over current relay used for earth faultprotection of motor feeders and transformer feeder. Itprovides time delayed over current protection.

    Definite time over current relay:

    The relay is used for time grade over current protectionfor feeders and stalling protection for motors.

    Under voltage relay:

    If under voltage occurs below the set point of relay,itdrops and DC relays picks up to give trip signal forbreaker.

    15

  • 8/3/2019 Project Report of Electrical

    16/49

    Instantaneous differential relay

    It is basically a 3 phase over current relaydesigned for more sensitive application. The waythe relay will be connected in the ckt gives it thename differential. The relay is past action andsensitive. It is used for short ckt protection for bigmotor generators.

    Fuse failure relay

    It is used for detecting the failure or inadvertentremoval of voltage transformer, secondary fusesand prevention of incorrect tripping of ckt breakereg:- failure of pt secondary fuse in distance

    protection can result in tripping of the feeder.

    Directional Inverse time over current relay

    Relays will operate for current flowing in eitherdirection. Directional over current relays operate

    only in one particular direction of power flow asdesired.

    Transformer differential Relay

    It is used in phase to phase fault and ground faultprotection of power T/F.

    16

  • 8/3/2019 Project Report of Electrical

    17/49

    It runs at the speed of 3000 RPM. The generator is also runs at thesame speed as both are coupled together with the coupling. Thegenerator rotor is excited here with DC voltage and EMF is producedat

    Capacity - 260MVA

    Voltage on H.v. - 235Kv

    L.V. - 16.5 Kv

    Vector Group - YD11

    Tap changer - off load.

    Cooling - OFWF% impedance - 14 %

    H.V. Bushing - 245Kv, 800A outdoor oil immersed self contained

    bushings are provided for H.V. side.

    H.V. Neutral Bushing - 1000 A , 36Kv weather proof cover mountedshaded porcelain bushing is provided for H.v. neutral.

    L.V. Bushing - 7500 A, 24 Kv weather proof cover mounted shaded

    porcelain bushing are provided for L.V. bushing.

    The neutral end of H.V. winding is brought out through a 36 Kv porcelainbushing provided with C.T. and solidly earth.

    Two explosion vents are mounted on the T/F tank

    provided with rupture diaphgram. These diaphgram

    rupture and relieve the excess pressure that built up

    17

  • 8/3/2019 Project Report of Electrical

    18/49

    inside transformer during serious internal fault and thus

    protects the transformer tank from deformities.

    The transformer is specified with a voltage rate pf220/6.9 KV. The HV voltage corresponds to the voltageof the HV buses of the main output system. The L.V.voltage of 6.9 KV is the no load voltage of the LV side

    on load the voltage drop in the SUT will reduce theterminal voltage to 6.6 KV with the proper selection oftap.

    The star/star connection for HV/LV winding werechosen in order to obtain proper vector matching of 6.6KV unit and station system. The SUT is also specified

    with a unloaded tertiary. The tertiary has a power ratingof about 1/3 of the main winding. The choice ofpercentage impedance for the transformer depends onthe fault level obtainable on the L.V. side and the voltagedrop under full load conditions and motor startingconditions percentage impedance of 0.9% specifiedlimits. The LV fault level to 500 MVA and the voltage

    drops to permissible level.

    The transformer is specified with an unload tap changer

    to maintain steady voltage at the 6.6 KV bus. The onload tap changer has range of +/- 12% insteps of 1-5%. Here only two nos. SUT available for initial start upto unit and supply power to station auxiliary when unit is

    in shut down. SUT take supply from 220 KV grid & Feed

    18

  • 8/3/2019 Project Report of Electrical

    19/49

    to station auxiliary power rating of SUT specified -22/31.5 MVA.Normal load of SUT specified - 20.8 MVA

    Including D2O upgrading plant of 7 MVA T/FLoad on SUT when unit transfer is not availableincluding D2O upgrading plant load 7 MVA - 34.8 MVAType of transformer - outdoor, 3 phase core typeRated voltage - 220/6.6 KVWinding connection Yd1Y0Frequency - 50 Hz

    Winding impedance % (HV-LV) 9%.Winding temperature rise plot to exceed 50 C over 50C ambient.

    19

  • 8/3/2019 Project Report of Electrical

    20/49

    INTRODUCTION

    The class-I power supply consist of two main buses.BUS-U and BUS-V each is fed from 500 Kw. ACVR isfed from class-III buses BUS-P and BUS-Q respectively.Each bus has a 2200 AH battery bank connected to it.The normal supply is fed from class-III buses fromACVR and battery bank is floating on DC bus. The lossof class-III power supply battery bank is supplied2200AH or two 30 min. with the end of discharge voltage204V.

    PURPOSE OF BATTERIES:

    In NAPS batteries bank play a very important rolebecause these batteries are used at the time when theclass supply system-IV, III and II fails. Due to this,batteries start the important loads of a NAPS.

    20

    ACVR

    BATTERY

    BANK 250 V

    DCMOTOR ACGENERATOR IMPORTANTLOADS

    415 AC

  • 8/3/2019 Project Report of Electrical

    21/49

    NUMBER OF BATTERIES BANK CAPACITY:

    Capacity of BB No. of Bank.

    250 V DC power BB 2200 AH 2 per unit.250 V DC control BB 450 AH 2 per unit.48 V DC control BB 300 AH 3 per unit.

    21

  • 8/3/2019 Project Report of Electrical

    22/49

    SYSTEM DISCRIPTION:

    The D.G. set are capable for the parallel

    operation of the class IV and other D.G. set. Wheneverclass four supplies are lost the D.G. set automaticallystart within 30 sec. the system is grounded through aresistance 0.5 ohm. To limit the ground fault current to480 amp. Or less.

    Rated continuous output - 1450 kwOverload capacity for 8 hrs. - 1650 kwOverload capacity for 2 hrs. - 1750 kw

    22

  • 8/3/2019 Project Report of Electrical

    23/49

    OPERATIONAL REQUIREMENTS& CONSTRUCTIONAL FEATURES

    DIESEL ENGINE

    The diesel engine is started by air motor. We store theair in air receiver by the compressor and this air gives sixstarts to D.G. set. For cooling we use oil and heavywater. The cooling arrangement form closed path andcool by the jacket water. If the engine is not in operation

    we use pre-lubricating oil pump for diesel engine whichcirculate the oil in engine after 30 min. We use boosterto give more fuel to engine to start it. We control thespeed of the governing system.

    TECHNICAL DATA OF DIESEL ENGINE

    1.Rating :2600 BHP2.RPM :1000rpm3.No.of strokes :4 stoke4. power factor :0.8 lag5. Engine cylinder :16 cylinder6. Excitation : static Exitation

    7. Pole : 6 pole8. Excitation voltage : 58.5 V9. Excitation current : 326 A

    10. Connection : star, 3 phase

    In the generator we use lap wound type of statorwinding. We excite the generator by 48 V D.C. voltage

    through the slip ring to the rotor or field winding. And by

    23

  • 8/3/2019 Project Report of Electrical

    24/49

    the rotation of rotor an e.m.f. is produced in the statorwinding. If the generatorgenerates 60% of the voltagethen to excite the field winding we use generated

    voltage.

    POWER MOTOR GENERATOR SET:

    This topic covers the control, protection andannunciation of motor generator set.

    SYSTEM DESCRIPTION:

    The motor generator set described are meant foruninterrupted power supply (415v ,3 phase ,50 Hz ) toimportant auxiliaries. The d.c. motor of this MG set fromclass-1st 250v dc supply and 500kw ACVR from class 3rd

    supply and 2200 AH 250V DC batteries.

    On loss of class 4th supply, the class 3rd system willalso loose supply. DG set start restore class 3rdsupply.During this period the 250V DC batteries will continue tosupply the MG set.

    24

  • 8/3/2019 Project Report of Electrical

    25/49

    STARTING METHOD:

    In view of the large size (290 kW) of the DC motor of the

    MG set starting with pony motor has preferred to resistorcontrolled starting on class 1st bus.

    SYSTEM GROUDING:

    In order to reduce the ground fault in the machine isgrounded through a neutral grounding resistor of 0.4

    ohm. This will restrict ground fault current to 600A orless.

    PARALLEL OPERATION

    The MG set can be parallel to the DG set for the purposeof shut down.

    PROTECTION

    The following protections are provided for theDG motor.

    D.C. MOTOR PROTECTION

    1. Over speed protection2. Over voltage protection3. Under frequency and over frequency protection4. Main field under current protection5. Motor over load protection

    ALTERNATOR PROTECTION:25

  • 8/3/2019 Project Report of Electrical

    26/49

    1. Phase instantaneous over current protection2. Backup phase over current protection

    3. Over current protection4. Earth fault protection

    PONY MOTOR PROTECTION:

    Over load protection

    Thermister sensed excess temp. protection.

    TECHNICAL DATA:

    AC MACHINE

    Rated terminal voltage :425V

    Rated continuous output at 0.8 pf :325KVAOver load rating for 30 min :360KVAInsulation class : FLocked rotor current on the :1250Abase load of 140Kw

    DC MOTOR

    Rated normal terminal voltage :258VMaximum working terminal voltage :300VMinimum working terminal voltage :200V

    Rating :290 KWNo load armature current :60A

    26

  • 8/3/2019 Project Report of Electrical

    27/49

    Full load speed :1000rpmArmature current at rated voltage :1350 AInsulation class :F

    PONY MOTOR

    Rating : 37 Kw , 1000 rpmRated voltage : 415V , 50HzCurrent : 67 V

    TECHO GENRATOR

    Output : 150V at 1000rpm

    27

  • 8/3/2019 Project Report of Electrical

    28/49

    The major parameters of the switchyard are givenbelow :

    1. Type :outdoor2. Nominal Voltage :220KV3. Max. operating voltage :240 KV4. Basic impulse levels:

    (a) For transformer winding : 950 KV(peak)(b) For other equipment : 1050

    5. 3 phase fault level :10000 MVA

    6. Short time current rating : 23.6 KA/secfor all equipment

    7. Minimum creep age distance :5600mm totaland For insulation and bushing 2800mmpollute

    8. Number of strain /Suspension/ 6 nos.

    insulation /string : 254 X 140 fog type9. Specified current rating for -(a) Main bus bar : 2000A(b) Bus coupler bay bus : 2000A(c) Bay bus of other element :750A

    28

  • 8/3/2019 Project Report of Electrical

    29/49

    (1) THE CIRCUIT BREAKER : -

    There are 11 Nos. of C.B used in switchyard.These C.B are air blast type manufactured by M/s

    Hindustan Brown Bravery. Following C.B are usedin switchyard as per follows

    CB No. USEDCB -1 Bus couplerCB -2 Generated transformer - (Unit#1)

    CB -3 Start up transformer - (Unit#1)CB -4 One line MuradabadCB -5 SUT - (Unit#2)CB -6 One line - ShimbholiCB -7 One line - KhurjaCB -8 One line - Khurja

    CB -9 GT - (Unit#2)CB -10 Transfer BusCB -11 One line - Harduaganj

    There is a centralized compressed air systemfor feeding air to the circuit. The compressors arehoused in the compressor room located on theeastern side of the switchyard. The air piping is

    29

  • 8/3/2019 Project Report of Electrical

    30/49

    made of copper tubes and are run inside cabletrenches in the switchyard. A ring main systemwith two feed points and in the piping to facilitates

    isolation of any breaker circuit without disturbingair connection to the other circuits.

    These CB are normally closed at pressureabout 30 kg/cm2.

    (2) ISOLATORS / DISCONNECTING SWITCH:

    There are 44 Isolators used in switchyard. TheIsolators are Pneumatically Operated type and arecapable of remote control from control room.These Isolators are worked only on off timecondition. The Isolators are of M/s TMG make and

    are supplied by M/s Volts. Air supply for pneumaticcontrol of the Isolators is also available from thesame centralized compressor mentioned in ParaC.s.I. through separate reducers to reduces thepressure to the required Operating levels forIsolators.

    Grouping Switch are provided on the lineIsolators. These grounding switches aremechanically interlocked with the main Isolators.

    (3) LIGHTNING ARRESTORS

    30

  • 8/3/2019 Project Report of Electrical

    31/49

    Lighting arrestors are provided on all five lines attheir entry into switchyard and also near the HV

    terminals of the power transformer. The arrestorsare of heavy-duty station type manufactured byM/s WS Insulators. The main parameters of thearrestor are as below-

    Rating - 198 KV

    Discharge current - 10 KAImpulse spark over voltage - 550 KV peakSwitching surge spark over - 420/453 KV Powerfrequency spark over - 1.5 times rated

    VoltageReset Voltage - 205 KV

    VOLTAGE TRANSFORMER

    In line with the UPSEBs Practice of providingCVTs for feeding distance protection of lines,CVTs are provided on all 3Q of the 220 KV lines.These CVTs serve the dual function via. VT for the

    line protection and coupling capacitor for carriercommunication.

    Each main bus bar is provided with one set ofelectromagnetic VT for the purpose of meteringsynchronizing and feeding other protection circuit.One single phase cut is provided for the transferbus for synchronizing purposes.

    31

  • 8/3/2019 Project Report of Electrical

    32/49

    CURRENT TRANSFORMER

    Current transformers are used for measure thelarge current flowing in a power line of an ACsupply. It is connected in series with phase wires.Current transfer is connected in switchyard tomeasure the current. It has very few turns (evenmay be one turn only ) on primary winding and

    large number of turns in the secondary winding. Its permeability, low retentively low power loss.Current transformer is oil immersed or compoundfield. Lastly, we can check the large current flowingin a power line of any AC supply system time totime.

    CARRIER COMMUNICATION

    Carrier communication facilities are provided forcommunication between NAPS control room andGrids substations connected to NAPS. Phasecoupling has been envisaged for single circuit lines

    and inter circuit has been envisaged for doublecircuit line to Khurja wave traps are provided onphases associated with the communication.

    The carrier Communication Channel is alsoused for transmitting signals for line protection.

    SYNCHRONIZING ARRANGEMENT ANDREMOTE CONTROL

    32

  • 8/3/2019 Project Report of Electrical

    33/49

    The remote controls for the switchyard circuit areprovided on the control room of NAPS.

    Synchronizing facilities are available forsynchronizing any element to the line bus bars.Emergency and synchronizing control from controlroom.

    All isolators can also be controlled remotely

    from the central control room. However thegrounding switches have to be operated manuallyat the switchyard.

    In NAPS turbo generator is cylindrical poletype, which is directly couple to the turbine andmounted on the same, TG SHORT The turbogenerator has an output rating on 264MVA

    33

  • 8/3/2019 Project Report of Electrical

    34/49

    (237.5MW) at 0.9PF , 16.5KV, 3000 rpm with stemcondition of 39.71Kg/cm2 (9) pressure and 0.26%wet and 250.3C at inlet to stop valve. After

    expansion in a single flow high-pressure turbinemoisture is extracted. In Separator -cum-reheatedwhere steam is reheated to 233 C before it entersthe double flow low-pressure turbine. Stem isextracted from suitable stage of the turbine toprovide for six stages representative feed

    heating ,with a final feed water, temperature of169.05 C. The local quantity of stem flow to theturbine is around 1333.58 tones/hour and designrate of heat turbo generator is 2758 K cal/kWh.

    Stator, conductor is water-cooled. Thestarter bore and Rotor are cooled by Hydrogen,

    since excitation current requirement is large with amaximum of 5000 rpm. Inductor type highfrequency exciter is chosen to avoid commutationproblem, which are experienced in DC exciter.

    PRINCIPLE:The electric generator is based on the principal offaraday laws of electromagnetic Inductiondiscovered by Michael Faraday in 1831.

    E= -NdQ/dt

    34

  • 8/3/2019 Project Report of Electrical

    35/49

    N = No. of turns

    DQ/dt = Rate of change of flux

    E = Induced EMF

    ESSENTIAL REQUIREMENT FOR ONDUCED INA GENERATOR : -

    1. A conductor, where the voltage is induced.

    2. Magnetic field.3. Relative motion between conductor andmagnetic field.

    FOR EXICTATION OF GENERATOR:

    we use static excitation for 235mw, because of

    following reason : - Fast response time.

    High reliability.

    Interchangeability of part during operation.

    Very low maintenance.

    Less space requirement.

    THE STATIC EXICTATION SYSTEM CONSISTOF THE FOLLING :

    1. Excitation transformer.2. Controlled Rectifier Bridge.3. Automatic Voltage regulator.

    4. Field breaker.5. Field flashing circuit.

    35

  • 8/3/2019 Project Report of Electrical

    36/49

    1.Excitation transformer :

    Three single phase dry type transformer rated for833 kv, 16.5kv/332 voltage are connect in delta tothe 16.5 kv system though tap of bus duct from themain generator bus duct. The Lv side of thetransformer are connected in the star and feed therectifiers the DC output of which is fed to the field

    winding of the generator.

    2.Controlled rectifier bridge :

    There are in all four controlled, three-phasethyristar rectifier bridges feeding the field. Thebridges are fed from the excitation transformer and

    are parallel on the output side. Three bridge areadequate the requirement of the excitation andfourth bridge is stand-by to take care of theeventually of one bridge failure. The control signalfor the thyristar are received the regulator cubicles(AVR).

    3.Automatic voltage regulator :Control signals are generated here for rectifier.The AVR derives its input form the PT and CT ofthe generator and controls the excitation forvarying the machine terminal voltage and reactiveoverflow in addition to this basic function of AVR in

    36

  • 8/3/2019 Project Report of Electrical

    37/49

    voltage regulator. The AVR incorporates thefollowing addition feature.

    (a) Rotor current limit :

    AVR protect rotor from overloading and theexcitation system from suffering voltage in excessof the ceiling voltage, the transformer theyre bytime delay features.

    (b) Under excitation limit :A load angle limits in the scheme limits the

    minimum excitation to a valve to which the AVRcan run down and prevents the machine formfailing out of step due to under excitation.

    (c) Slip stabilization :

    This is provided to monitor rotor oscillation andaddition single drive from these oscillation areapplies to the AVR to prevent the machine formfailing out of step.

    (d) Stator current limiter :-

    This limiter monitors the stator current limits theexcitation in case there is stator over load.

    37

  • 8/3/2019 Project Report of Electrical

    38/49

    4. Field breaker :

    The field breaker is of air breast type. In this

    breaker provision is provided to discharge theenergy stored in the field though a non-linearresistance whenever the breaker is open themeans of a special contact of the breaker whenclasses before the field breaker opens.

    5. Field flushing circuit :

    While starting the machine it will be necessary toprovide supply to the field from an external source(415v) three phase transformer rectifier which havefield discharge resistor and over voltage-protection, rotor earth fault relay because the

    terminal connected transformer will not haveadequate voltage to supply the field. The flushingcircuits built the generator voltage to above 70 %of the rated voltage where in the AVR takes overthe built and maintains the voltage at the set valve.

    38

  • 8/3/2019 Project Report of Electrical

    39/49

    MAIN PART OF THE GENERATOR:STATOR :

    Stator care is made of segment varnish insulatedof cold rolled grain oriented silicon steel assemblewith care bars for cooling of care by hydrogen (3.5kg/cm2) steel spacer are provided.

    Stator binding is a 3 phase double layer shortcarded bar type binding having two parallel paths.Fiber wages are provided to hold up coil. Slatesare semi closed.

    ROTAR:

    Rooter is of cylindrical pole type the shaft and bodybeing forced from one piece of an alloy ofchromium, nickel, molybdenum and vanadiumsteel the rotor binding is held in position againstcentrifugal forces by Duralumin wages in the stateportion and by non magnetic steel retaining rings.

    Damper binding is provided in the rotor toprevent over heating of retaining rings during nonsynchronous operation. This damper binding alsoavoid hunting due to unbalanced loading and faultcondition.

    39

  • 8/3/2019 Project Report of Electrical

    40/49

    SLIP RINGS :-

    Slips rings made of steel, along with brush gear is

    provided in the TG shaft to eject excitation currentfrom the static rectifier unit to the rotating mainfield. The slip rings consists of halically group ofimproving brush performance on the rotor shaftand insulated form it the slip rings are providedwith inclined holes for self ventilation.

    COOLING OF GENERATOR :

    Stator cooling :

    Generator stator binding are cooled by DM waterpassing through the hollow conductor. The ring

    type water made of copper are provided separatelyfor DM water inlet and outlet in the stator on theturbine ends.

    DM water is used for stator binding coolingpurpose because of it have : -

    Low viscosity No fire hazards

    Better heat removal capacity

    Low conductivity

    40

  • 8/3/2019 Project Report of Electrical

    41/49

    Rotor cooling :

    Stator and rotor is cooled by hydrogen in the statorand rotor air gap. To axial shaft fans mounted onboth end of rotor body to circulated hydrogen gasin to independent and semitrically closed circuit.

    The direct cooling of rotor binding is done by

    the gap pick up method. Multi-jet flow of hydrogenexposes large amount of rotor binding copper tothe cooling medium thus creating very effectivecooling.

    For indigenously gas cooler are mounted in thestator body for hydrogen cooling. Hydrogen gas is

    used for generator because of it have.

    Heat conductivity is high

    Density is very less

    Heat removed capacity is high

    As to have low voltage losses.

    41

  • 8/3/2019 Project Report of Electrical

    42/49

    TECHNICAL DATA OF TURBO GENERATOR

    1. Power - 237700 KW2. Power factor - 0.903. Rating - 264000 KVA4. Stator - 16500 V ,9240 A5. Rotor - 326 , 27556. RPM - 3000 RPM

    7. Frequency - 50 Hz8. Connection - 3 phase9. Coolant - DM water & Hydrogen10. Insulation - b-type11. Production - 1991-9212. Made by - Haridwar

    42

  • 8/3/2019 Project Report of Electrical

    43/49

    CLASSIFICATION OF SUPPLY SYSTEM INNAPS

    CLASSES OF POWER SUPPLY:

    Each load within the station has been classifiedaccording to degree of reliability required for itssupply.There are four classes of power supply at NAPS.

    Class ofPower Voltage Nature Source

    Class-I 250 VDC Uninterrupted Batterybank

    Class-II 415 AC Uninterrupted Power MGset

    Class-III 415 AC interruptible

    two minutes

    Diesel

    generatoronly for oneor rotor.

    Class-IV 415 AC &6.6 KV

    interruptibleupto 30minutes

    Grid supply& TG Set

    Control

    powersupplyCl-I

    250 VDC uninterrupted Batteries.

    ControlpowersupplyCl-II

    415 VAC240 VAC48 VDC28 VDC

    Uninterruptedsets.

    Control MGsets

    43

  • 8/3/2019 Project Report of Electrical

    44/49

    Class-IV POWER SUPPLY:

    The system has in CWPH. BU-J acts as transfer bus.

    Each bus is charged through an 6.6 KV/415V auxiliarytransfer from 6.6 KV buses. BU-J is kept charged buthas no load and acts as S/by Bus for BU-K, BU-M ofclass-IV in case of unavailability of any auxiliary X-mer.

    BU-J also acts as standby Bus for BU-P & BU-Q of

    class-III system .

    RWPH, NAPP Township, upgrading plant and someMCC's are fed from Class IV in addition to 415 V loadson Class IV. When the grid fails & our plant trips, then6.6 KV and 415 V class IV both systems are dead.Loads on these buses interrupt and do not cause

    any adverse effect on Reactor auxiliaries.

    CLASS-III POWER SUPPLY :

    System feeds to those loads which can beinterrupted shortly. These loads are required to run

    even when Reactor is shut down .

    System is normally charged from 6.6 KV system andwhen the 6.6 KV supply fails DGs automatically startand recharge the system.

    415 V class III has two main buses BU-P and BU-Q.Both are fed by 6.6 KV system through x-mers. Two44

  • 8/3/2019 Project Report of Electrical

    45/49

    auxithe source of supply is from class-III through

    transformer and rectifier. Class-III inturn is fedfrom grid. Class III resumes after 1-2 min.after class IV failure.

    But when class III does not resume the source of poweris from 250 V DC storage batteries and the supplyremains uninterrupted. Batteries have capacity tosupply upto 25 min. when class III is not available.

    CLASS-II POWER SUPPLY :

    Class-II BU-S & BU-T are kept constantly charged bytwo power generator sets to convert 250 V DC to 415V AC. As the motor of MG set is driven by 250 VDCfrom class-I power batteries, the class-II is also

    uninterrupted power supply.

    Class-II may also be tied to class-III if any MG setbecomes unavailable. This condition calls continuousDG set running.

    Potential loss on any cl-III or any cl-II buses initiateemergency transfer i.e. all DG's start to charge anydead bus.

    45

  • 8/3/2019 Project Report of Electrical

    46/49

    CLASS-I POWER SUPPLY :

    250 VDC control power supply sources are two 250VDC battery banks. Each bank supplies to one bus.Normally the buses are kept charged from class-IIIpower through automatic constt. voltage rectifiers(ACVR). On class-III failure batteries supply therequired power. Batteries are recharged on class-IIIresumption.

    Control power supply is used for auto trippingckt., auto closing ckt. & test ckt. for breakers remotely(CR) and locally testing. This has been separated fromclass-I power supply system keeping in view all time,availability and reliability

    46

  • 8/3/2019 Project Report of Electrical

    47/49

    PLANT LAYOUT

    Reactor building houses the reactor primary heat

    transport system, moderator system, reactivitymechanism, fuel handling system and some of theauxiliaries. The turbo-generator and its associatedconventional equipment, emergency diesel sets, controland power MG sets, station batteries, electrical switchgear compressor, chillers and main control room arelocated in turbine building. Both the units share common

    facilities such as service building, spent fuel storage bayand other auxiliary services such as heavy waterupgrading and waste management facility.

    NAPP has two natural draught cooling and two induceddraught cooling towers.

    Legend

    1. Administration Building.2. Overhead Water Tank.3. Canteen4. Natural Draught Cooling Towers5. 220 KV Switch Yard.6. Stack

    7. Service Building8. Small LOCA Room9. Reactor Building10. Purification Building11. Turbine Building.12. Pump House13. Induced Draught Cooling Towers.

    47

  • 8/3/2019 Project Report of Electrical

    48/49

    .

    S.NO. CONTENTS

    1. INTRODUCTION.

    2. RELAY TESTING LAB.3. GENERATOR TRANSFORMER.4. STARTUP TRANSFORMER.5. STATION BATTERIES.6. DIESEL GENERATOR SET.7. SWITCH YARD.8. TURBO GENERATOR.

    9. CLASSIFICATION OF SUPPLY INNAPS.

    48

  • 8/3/2019 Project Report of Electrical

    49/49