Project Information Design Information - HVAC-Talk
Transcript of Project Information Design Information - HVAC-Talk
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Load Short Form
�
3/10/16
�
Date:
�
Entire House
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Information
�
Infiltration
�
Clg
�
Htg
�
Simplified
�
Method
�
99
�
30
�
Outside db (°F)
�
Average
�
Construction quality
�
75
�
70
�
Inside db (°F)
�
0
�
Fireplaces
�
24
�
40
�
Design TD (°F)
�
M
�
-
�
Daily range
�
50
�
50
�
Inside humidity (%)
�
29
�
36
�
Moisture difference (gr/lb)
�
HEATING EQUIPMENT
�
COOLING EQUIPMENT
�
Make
�
n/a
�
Make
�
n/a
�
Trade
�
n/a
�
Trade
�
n/a
�
Model
�
n/a
�
Cond
�
n/a
�
AHRI ref
�
n/a
�
Coil
�
n/a
�
AHRI ref
�
n/a
�
Efficiency
�
n/a
�
Efficiency
�
n/a
�
Heating input
�
Sensible cooling
�
Btuh
�
0
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
0
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
0
�
Actual air flow
�
cfm
�
0
�
Actual air flow
�
cfm
�
0
�
Air flow factor
�
cfm/Btuh
�
0
�
Air flow factor
�
cfm/Btuh
�
0
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
n/a
�
Load sensible heat ratio
�
0
�
ROOM NAME
�
Area
�
Htg load
�
Clg load
�
Htg AVF
�
Clg AVF
�
(ft²)
�
(Btuh)
�
(Btuh)
�
(cfm)
�
(cfm)
�
2ND FLOOR
�
d
�
1328
�
11673
�
7314
�
525
�
525
�
1ST FLOOR
�
d
�
2749
�
42131
�
22412
�
1050
�
1050
�
Entire House
�
d
�
4077
�
53804
�
29719
�
1575
�
1575
�
Other equip loads
�
3864
�
2280
�
Equip. @
�
1.04
�
RSM
�
33151
�
Latent cooling
�
3964
�
TOTALS
�
4077
�
57667
�
37115
�
1575
�
1575
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 2
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Load Short Form
�
3/10/16
�
Date:
�
1ST FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Information
�
Infiltration
�
Clg
�
Htg
�
Simplified
�
Method
�
99
�
30
�
Outside db (°F)
�
Average
�
Construction quality
�
75
�
70
�
Inside db (°F)
�
0
�
Fireplaces
�
24
�
40
�
Design TD (°F)
�
M
�
-
�
Daily range
�
50
�
50
�
Inside humidity (%)
�
29
�
36
�
Moisture difference (gr/lb)
�
HEATING EQUIPMENT
�
COOLING EQUIPMENT
�
Make
�
Make
�
Trane
�
Trade
�
Trade
�
TRANE
�
Model
�
Cond
�
4TTR6036B1
�
AHRI ref
�
Coil
�
4TXFH041CC3+*DH1B065A9H3
�
AHRI ref
�
5867043
�
Efficiency
�
80 AFUE
�
Efficiency
�
12.5 EER, 15.3 SEER
�
Heating input
�
Btuh
�
0
�
Sensible cooling
�
Btuh
�
23940
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
10260
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
34200
�
Actual air flow
�
cfm
�
1050
�
Actual air flow
�
cfm
�
1050
�
Air flow factor
�
cfm/Btuh
�
0.025
�
Air flow factor
�
cfm/Btuh
�
0.047
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
Load sensible heat ratio
�
0.85
�
ROOM NAME
�
Area
�
Htg load
�
Clg load
�
Htg AVF
�
Clg AVF
�
(ft²)
�
(Btuh)
�
(Btuh)
�
(cfm)
�
(cfm)
�
BRKFST WITH WIC
�
105
�
3375
�
2041
�
84
�
96
�
KITCHEN
�
284
�
0
�
1239
�
0
�
58
�
ENTRY
�
315
�
6162
�
3769
�
154
�
177
�
DINING
�
304
�
2014
�
628
�
50
�
29
�
STUDY
�
162
�
5517
�
2408
�
138
�
113
�
UTILTIY
�
101
�
1180
�
1019
�
29
�
48
�
BATH 4
�
52
�
0
�
0
�
0
�
0
�
BED 4
�
208
�
4298
�
1497
�
107
�
70
�
M WIC
�
95
�
0
�
0
�
0
�
0
�
MBATH & SMALL WIC
�
360
�
3292
�
1280
�
82
�
60
�
M BED
�
366
�
7625
�
3584
�
190
�
168
�
GREAT
�
398
�
8667
�
4948
�
216
�
232
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 3
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
1ST FLOOR
�
d
�
2749
�
42131
�
22412
�
1050
�
1050
�
Other equip loads
�
3864
�
2280
�
Equip. @
�
1.04
�
RSM
�
25580
�
Latent cooling
�
4397
�
TOTALS
�
2749
�
45995
�
29977
�
1050
�
1050
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 4
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Load Short Form
�
3/10/16
�
Date:
�
2ND FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Information
�
Infiltration
�
Clg
�
Htg
�
Simplified
�
Method
�
99
�
30
�
Outside db (°F)
�
Average
�
Construction quality
�
75
�
70
�
Inside db (°F)
�
0
�
Fireplaces
�
24
�
40
�
Design TD (°F)
�
M
�
-
�
Daily range
�
50
�
50
�
Inside humidity (%)
�
29
�
36
�
Moisture difference (gr/lb)
�
HEATING EQUIPMENT
�
COOLING EQUIPMENT
�
Make
�
Make
�
Trane
�
Trade
�
Trade
�
XR16
�
Model
�
Cond
�
4TTR6018B1
�
AHRI ref
�
Coil
�
4TXFH033CC3+*DH1B040A9H2
�
AHRI ref
�
5864647
�
Efficiency
�
80 AFUE
�
Efficiency
�
13.0 EER, 15 SEER
�
Heating input
�
Btuh
�
0
�
Sensible cooling
�
Btuh
�
12040
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
5160
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
17200
�
Actual air flow
�
cfm
�
525
�
Actual air flow
�
cfm
�
525
�
Air flow factor
�
cfm/Btuh
�
0.045
�
Air flow factor
�
cfm/Btuh
�
0.072
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
Load sensible heat ratio
�
0.85
�
ROOM NAME
�
Area
�
Htg load
�
Clg load
�
Htg AVF
�
Clg AVF
�
(ft²)
�
(Btuh)
�
(Btuh)
�
(cfm)
�
(cfm)
�
BATH 3
�
94
�
568
�
310
�
26
�
22
�
BED 2
�
295
�
3502
�
2053
�
158
�
147
�
BATH 2
�
87
�
546
�
295
�
25
�
21
�
BED 3
�
221
�
1608
�
1333
�
72
�
96
�
BED 5
�
338
�
3466
�
2154
�
156
�
155
�
GAME
�
293
�
1982
�
1170
�
89
�
84
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 5
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
2ND FLOOR
�
d
�
1328
�
11673
�
7314
�
525
�
525
�
Other equip loads
�
0
�
0
�
Equip. @
�
1.04
�
RSM
�
7578
�
Latent cooling
�
1299
�
TOTALS
�
1328
�
11673
�
8877
�
525
�
525
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Load Multizone Summary Report
�
3/10/16
�
Date:
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Infiltration Summary
�
Heating
�
Cooling
�
ZONE NAME
�
Volume
�
ACH
�
AVF
�
HTM
�
Volume
�
ACH
�
AVF
�
HTM
�
ft³
�
cfm
�
Btuh/ft²
�
ft³
�
cfm
�
Btuh/ft²
�
0.6
�
29
�
0.14
�
12677
�
2.6
�
68
�
0.32
�
12677
�
2ND FLOOR
�
0.6
�
89
�
0.16
�
34092
�
2.6
�
206
�
0.36
�
34092
�
1ST FLOOR
�
Entire House
�
46769
�
0.37
�
274
�
2.7
�
46769
�
0.19
�
118
�
0.8
�
Load and AVF Summary
�
ROOM NAME
�
Area
�
Htg load
�
Clg load
�
Htg AVF
�
Clg AVF
�
ft²
�
Btuh
�
Btuh
�
cfm
�
cfm
�
22
�
26
�
310
�
568
�
94
�
BATH 3
�
147
�
158
�
2053
�
3502
�
295
�
BED 2
�
21
�
25
�
295
�
546
�
87
�
BATH 2
�
96
�
72
�
1333
�
1608
�
221
�
BED 3
�
155
�
156
�
2154
�
3466
�
338
�
BED 5
�
84
�
89
�
1170
�
1982
�
293
�
GAME
�
525
�
525
�
7314
�
11673
�
1328
�
2ND FLOOR
�
96
�
84
�
2041
�
3375
�
105
�
BRKFST WITH WIC
�
58
�
0
�
1239
�
0
�
284
�
KITCHEN
�
177
�
154
�
3769
�
6162
�
315
�
ENTRY
�
29
�
50
�
628
�
2014
�
304
�
DINING
�
113
�
138
�
2408
�
5517
�
162
�
STUDY
�
48
�
29
�
1019
�
1180
�
101
�
UTILTIY
�
0
�
0
�
0
�
0
�
52
�
BATH 4
�
70
�
107
�
1497
�
4298
�
208
�
BED 4
�
0
�
0
�
0
�
0
�
95
�
M WIC
�
60
�
82
�
1280
�
3292
�
360
�
MBATH & SMALL WIC
�
168
�
190
�
3584
�
7625
�
366
�
M BED
�
232
�
216
�
4948
�
8667
�
398
�
GREAT
�
1050
�
1050
�
22412
�
42131
�
2749
�
1ST FLOOR
�
Entire House
�
4077
�
53804
�
29719
�
1575
�
1575
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Loads for Multiple Orientations
�
3/10/16
�
Date:
�
Entire House
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
74
�
-
�
Wet bulb (°F)
�
7.5
�
15.0
�
Wind speed (mph)
�
Front Door
�
North
�
Northeast
�
East
�
Southeast
�
South
�
Southwest
�
West
�
Northwest
�
Sensible Load (Btuh)
�
33151
�
38348
�
40218
�
36927
�
32944
�
36949
�
39090
�
37067
�
Latent Load (Btuh)
�
3964
�
3964
�
3964
�
3964
�
3964
�
3964
�
3964
�
3964
�
Total Load (Btuh)
�
37115
�
42312
�
44182
�
40891
�
36908
�
40912
�
43054
�
41030
�
Heating AVF (cfm)
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
�
Cooling AVF (cfm)
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
�
1575
Building Orientation Cooling Load
Tot
al C
oolin
g Lo
ad (
Btu
h)
Direction Front Door faces
0
10000
20000
30000
40000
50000
N NE E SE S SW W NW
�
Front Door faces North
�
Current Orientation:
�
Front Door faces East
�
Highest Cooling Load:
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 2
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Loads for Multiple Orientations
�
3/10/16
�
Date:
�
2ND FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
74
�
-
�
Wet bulb (°F)
�
7.5
�
15.0
�
Wind speed (mph)
�
Front Door
�
North
�
Northeast
�
East
�
Southeast
�
South
�
Southwest
�
West
�
Northwest
�
Sensible Load (Btuh)
�
7578
�
8621
�
9161
�
8559
�
7578
�
8621
�
9161
�
8559
�
Latent Load (Btuh)
�
1299
�
1299
�
1299
�
1299
�
1299
�
1299
�
1299
�
1299
�
Total Load (Btuh)
�
8877
�
9920
�
10460
�
9858
�
8877
�
9920
�
10460
�
9858
�
Heating AVF (cfm)
�
525
�
525
�
525
�
525
�
525
�
525
�
525
�
525
�
Cooling AVF (cfm)
�
525
�
525
�
525
�
525
�
525
�
525
�
525
�
525
Building Orientation Cooling Load
Tot
al C
oolin
g Lo
ad (
Btu
h)
Direction Front Door faces
0
5000
10000
15000
N NE E SE S SW W NW
�
Front Door faces North
�
Current Orientation:
�
Front Door faces East
�
Highest Cooling Load:
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:34
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 3
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Loads for Multiple Orientations
�
3/10/16
�
Date:
�
1ST FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
74
�
-
�
Wet bulb (°F)
�
7.5
�
15.0
�
Wind speed (mph)
�
Front Door
�
North
�
Northeast
�
East
�
Southeast
�
South
�
Southwest
�
West
�
Northwest
�
Sensible Load (Btuh)
�
25580
�
29733
�
31194
�
28368
�
25374
�
28394
�
29929
�
28507
�
Latent Load (Btuh)
�
4397
�
4397
�
4397
�
4397
�
4397
�
4397
�
4397
�
4397
�
Total Load (Btuh)
�
29977
�
34129
�
35590
�
32764
�
29770
�
32790
�
34326
�
32904
�
Heating AVF (cfm)
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
�
Cooling AVF (cfm)
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
�
1050
Building Orientation Cooling Load
Tot
al C
oolin
g Lo
ad (
Btu
h)
Direction Front Door faces
0
10000
20000
30000
40000
N NE E SE S SW W NW
�
Front Door faces North
�
Current Orientation:
�
Front Door faces East
�
Highest Cooling Load:
�
Bold /italic values have been manually overridden
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Building Analysis
�
3/10/16
�
Date:
�
Entire House
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Heating
Walls
Glazing
Other
CeilingsFloors
Infiltration
Ducts
Ventilation
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
22.0
�
12673
�
3.2
�
Walls
�
14.8
�
8544
�
14.0
�
Glazing
�
1.7
�
983
�
15.6
�
Doors
�
10.8
�
6228
�
2.3
�
Ceilings
�
18.1
�
10461
�
3.8
�
3.8
�
Floors
�
20.4
�
11763
�
2.6
�
Infiltration
�
5.5
�
3153
�
Ducts
�
0
�
0
�
Piping
�
0
�
0
�
Humidification
�
6.7
�
3864
�
Ventilation
�
0
�
Adjustments
�
100.0
�
57667
�
Total
�
Cooling
Walls
Glazing
Doors Ceilings
Other
Infiltration
Ducts
Internal Gains
Ventilation
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
19.2
�
6146
�
1.6
�
Walls
�
26.0
�
8325
�
13.6
�
Glazing
�
2.6
�
848
�
13.5
�
Doors
�
15.7
�
5028
�
1.8
�
Ceilings
�
0.0
�
9
�
0.0
�
Floors
�
9.3
�
2979
�
0.6
�
Infiltration
�
6.4
�
2054
�
Ducts
�
7.1
�
2280
�
Ventilation
�
13.5
�
4330
�
Internal gains
�
0
�
0
�
Blower
�
0
�
Adjustments
�
100.0
�
31999
�
Total
�
Latent Cooling Load = 3964 Btuh
�
Overall U-value = 0.192 Btuh/ft²-°F
�
Data entries checked.
�
Bold /italic values have been manually overridden
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 2
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Building Analysis
�
3/10/16
�
Date:
�
1ST FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Heating
Walls
Glazing
Doors
CeilingsFloors
Infiltration
Ducts
Ventilation
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
20.4
�
9387
�
3.2
�
Walls
�
14.9
�
6864
�
14.0
�
Glazing
�
2.1
�
983
�
15.6
�
Doors
�
7.0
�
3230
�
2.3
�
Ceilings
�
22.7
�
10441
�
3.8
�
3.8
�
Floors
�
19.2
�
8854
�
2.6
�
Infiltration
�
5.2
�
2373
�
Ducts
�
0
�
0
�
Piping
�
0
�
0
�
Humidification
�
8.4
�
3864
�
Ventilation
�
0
�
Adjustments
�
100.0
�
45995
�
Total
�
Cooling
Walls
Glazing
DoorsCeilings
Infiltration
Ducts
Internal Gains
Ventilation
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
18.4
�
4553
�
1.6
�
Walls
�
28.3
�
6979
�
14.2
�
Glazing
�
3.4
�
848
�
13.5
�
Doors
�
10.6
�
2608
�
1.8
�
Ceilings
�
0
�
0
�
0
�
Floors
�
9.1
�
2242
�
0.6
�
Infiltration
�
6.2
�
1542
�
Ducts
�
9.2
�
2280
�
Ventilation
�
14.7
�
3640
�
Internal gains
�
0
�
0
�
Blower
�
0
�
Adjustments
�
100.0
�
24692
�
Total
�
Latent Cooling Load = 4397 Btuh
�
Overall U-value = 0.167 Btuh/ft²-°F
�
Data entries checked.
�
Bold /italic values have been manually overridden
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 3
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Building Analysis
�
3/10/16
�
Date:
�
2ND FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Heating
Walls
Glazing
Ceilings
Other
Infiltration
Ducts
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
28.1
�
3285
�
3.2
�
Walls
�
14.4
�
1680
�
14.0
�
Glazing
�
0
�
0
�
0
�
Doors
�
25.7
�
2998
�
2.3
�
Ceilings
�
0.2
�
20
�
2.0
�
2.0
�
Floors
�
24.9
�
2910
�
2.6
�
Infiltration
�
6.7
�
780
�
Ducts
�
0
�
0
�
Piping
�
0
�
0
�
Humidification
�
0
�
0
�
Ventilation
�
0
�
Adjustments
�
100.0
�
11673
�
Total
�
Cooling
Walls
Glazing
Ceilings
Other
Infiltration
Ducts
Internal Gains
�
% of load
�
Btuh
�
Btuh/ft²
�
Component
�
21.8
�
1593
�
1.6
�
Walls
�
18.5
�
1352
�
11.3
�
Glazing
�
0
�
0
�
0
�
Doors
�
33.1
�
2420
�
1.8
�
Ceilings
�
0.1
�
9
�
0.9
�
Floors
�
10.1
�
737
�
0.6
�
Infiltration
�
7.0
�
512
�
Ducts
�
0
�
0
�
Ventilation
�
9.4
�
690
�
Internal gains
�
0
�
0
�
Blower
�
0
�
Adjustments
�
100.0
�
7314
�
Total
�
Latent Cooling Load = 1299 Btuh
�
Overall U-value = 0.270 Btuh/ft²-°F
�
Data entries checked.
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
Entire House
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
1669
�
1.57
�
3441
�
3.24
�
15.0
�
0.081
�
1062
�
n
�
1531
�
1.57
�
3157
�
3.24
�
15.0
�
0.081
�
974
�
e
�
22
�
1.57
�
46
�
3.24
�
15.0
�
0.081
�
14
�
se
�
1420
�
1.57
�
2928
�
3.24
�
15.0
�
0.081
�
904
�
s
�
23
�
1.57
�
48
�
3.24
�
15.0
�
0.081
�
15
�
sw
�
1481
�
1.57
�
3053
�
3.24
�
15.0
�
0.081
�
942
�
w
�
6146
�
1.57
�
12673
�
3.24
�
15.0
�
0.081
�
3911
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% outdoor insect screen; 6.67 ft head ht
�
139
�
11.6
�
168
�
14.0
�
0
�
0.350
�
12
�
n
�
1841
�
12.8
�
2016
�
14.0
�
0
�
0.350
�
144
�
s
�
1110
�
26.4
�
588
�
14.0
�
0
�
0.350
�
42
�
w
�
3090
�
15.6
�
2772
�
14.0
�
0
�
0.350
�
198
�
all
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
1796
�
10.6
�
2380
�
14.0
�
0
�
0.350
�
170
�
n
�
192
�
24.0
�
112
�
14.0
�
0
�
0.350
�
8
�
e
�
273
�
19.5
�
196
�
14.0
�
0
�
0.350
�
14
�
se
�
2201
�
11.9
�
2597
�
14.0
�
0
�
0.350
�
186
�
s
�
262
�
19.5
�
188
�
14.0
�
0
�
0.350
�
13
�
sw
�
512
�
24.0
�
299
�
14.0
�
0
�
0.350
�
21
�
w
�
5235
�
12.7
�
5772
�
14.0
�
0
�
0.350
�
412
�
all
�
Doors
�
11D0: Door, wd sc type
�
565
�
13.5
�
655
�
15.6
�
0
�
0.390
�
42
�
n
�
283
�
13.5
�
328
�
15.6
�
0
�
0.390
�
21
�
e
�
848
�
13.5
�
983
�
15.6
�
0
�
0.390
�
63
�
all
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
5028
�
1.82
�
6228
�
2.26
�
19.0
�
0.408
�
2759
�
Floors
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 2
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
20P-19c: Flr floor, frm flr, 10" thkns, carpet flr fnsh, r -19 cav ins,
�
amb ovr
�
9
�
0.90
�
20
�
2.00
�
19.0
�
0.050
�
10
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
264
�
0
�
0
�
10441
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 3
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
2ND FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
487
�
1.57
�
1004
�
3.24
�
15.0
�
0.081
�
310
�
n
�
572
�
1.57
�
1179
�
3.24
�
15.0
�
0.081
�
364
�
e
�
513
�
1.57
�
1058
�
3.24
�
15.0
�
0.081
�
327
�
s
�
21
�
1.57
�
44
�
3.24
�
15.0
�
0.081
�
14
�
w
�
1593
�
1.57
�
3285
�
3.24
�
15.0
�
0.081
�
1014
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
634
�
10.6
�
840
�
14.0
�
0
�
0.350
�
60
�
n
�
712
�
11.9
�
840
�
14.0
�
0
�
0.350
�
60
�
s
�
1346
�
11.2
�
1680
�
14.0
�
0
�
0.350
�
120
�
all
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
2420
�
1.82
�
2998
�
2.26
�
19.0
�
0.408
�
1328
�
Floors
�
20P-19c: Flr floor, frm flr, 10" thkns, carpet flr fnsh, r -19 cav ins,
�
amb ovr
�
9
�
0.90
�
20
�
2.00
�
19.0
�
0.050
�
10
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 4
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
1ST FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
1182
�
1.57
�
2436
�
3.24
�
15.0
�
0.081
�
752
�
n
�
959
�
1.57
�
1977
�
3.24
�
15.0
�
0.081
�
610
�
e
�
22
�
1.57
�
46
�
3.24
�
15.0
�
0.081
�
14
�
se
�
907
�
1.57
�
1870
�
3.24
�
15.0
�
0.081
�
577
�
s
�
23
�
1.57
�
48
�
3.24
�
15.0
�
0.081
�
15
�
sw
�
1459
�
1.57
�
3009
�
3.24
�
15.0
�
0.081
�
929
�
w
�
4553
�
1.57
�
9387
�
3.24
�
15.0
�
0.081
�
2897
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% outdoor insect screen; 6.67 ft head ht
�
139
�
11.6
�
168
�
14.0
�
0
�
0.350
�
12
�
n
�
1841
�
12.8
�
2016
�
14.0
�
0
�
0.350
�
144
�
s
�
1110
�
26.4
�
588
�
14.0
�
0
�
0.350
�
42
�
w
�
3090
�
15.6
�
2772
�
14.0
�
0
�
0.350
�
198
�
all
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
1162
�
10.6
�
1540
�
14.0
�
0
�
0.350
�
110
�
n
�
192
�
24.0
�
112
�
14.0
�
0
�
0.350
�
8
�
e
�
273
�
19.5
�
196
�
14.0
�
0
�
0.350
�
14
�
se
�
1489
�
11.9
�
1757
�
14.0
�
0
�
0.350
�
126
�
s
�
262
�
19.5
�
188
�
14.0
�
0
�
0.350
�
13
�
sw
�
512
�
24.0
�
299
�
14.0
�
0
�
0.350
�
21
�
w
�
3890
�
13.3
�
4092
�
14.0
�
0
�
0.350
�
292
�
all
�
Doors
�
11D0: Door, wd sc type
�
565
�
13.5
�
655
�
15.6
�
0
�
0.390
�
42
�
n
�
283
�
13.5
�
328
�
15.6
�
0
�
0.390
�
21
�
e
�
848
�
13.5
�
983
�
15.6
�
0
�
0.390
�
63
�
all
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
2608
�
1.82
�
3230
�
2.26
�
19.0
�
0.408
�
1431
�
Floors
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 5
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
264
�
0
�
0
�
10441
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 6
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
GREAT
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
363
�
1.57
�
748
�
3.24
�
15.0
�
0.081
�
231
�
s
�
589
�
1.57
�
1215
�
3.24
�
15.0
�
0.081
�
375
�
w
�
952
�
1.57
�
1963
�
3.24
�
15.0
�
0.081
�
606
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% outdoor insect screen; 6.67 ft head ht
�
1841
�
12.8
�
2016
�
14.0
�
0
�
0.350
�
144
�
s
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
575
�
1.82
�
712
�
2.26
�
19.0
�
0.408
�
316
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
40
�
0
�
0
�
1563
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 7
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BRKFST WITH WIC
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
22
�
1.57
�
46
�
3.24
�
15.0
�
0.081
�
14
�
se
�
119
�
1.57
�
245
�
3.24
�
15.0
�
0.081
�
76
�
s
�
23
�
1.57
�
48
�
3.24
�
15.0
�
0.081
�
15
�
sw
�
69
�
1.57
�
141
�
3.24
�
15.0
�
0.081
�
44
�
w
�
233
�
1.57
�
481
�
3.24
�
15.0
�
0.081
�
148
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
273
�
19.5
�
196
�
14.0
�
0
�
0.350
�
14
�
se
�
291
�
11.9
�
343
�
14.0
�
0
�
0.350
�
25
�
s
�
262
�
19.5
�
188
�
14.0
�
0
�
0.350
�
13
�
sw
�
512
�
24.0
�
299
�
14.0
�
0
�
0.350
�
21
�
w
�
1337
�
18.3
�
1026
�
14.0
�
0
�
0.350
�
73
�
all
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
191
�
1.82
�
237
�
2.26
�
19.0
�
0.408
�
105
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
22
�
0
�
0
�
874
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 8
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
KITCHEN
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
(none)
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
(none)
�
Ceilings
�
(none)
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 9
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
ENTRY
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
316
�
1.57
�
651
�
3.24
�
15.0
�
0.081
�
201
�
n
�
492
�
1.57
�
1014
�
3.24
�
15.0
�
0.081
�
313
�
w
�
808
�
1.57
�
1665
�
3.24
�
15.0
�
0.081
�
514
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% outdoor insect screen; 6.67 ft head ht
�
1110
�
26.4
�
588
�
14.0
�
0
�
0.350
�
42
�
w
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
85
�
10.6
�
112
�
14.0
�
0
�
0.350
�
8
�
n
�
Doors
�
11D0: Door, wd sc type
�
283
�
13.5
�
328
�
15.6
�
0
�
0.390
�
21
�
n
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
558
�
1.82
�
691
�
2.26
�
19.0
�
0.408
�
306
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
24
�
0
�
0
�
930
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 10
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
DINING
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
190
�
1.57
�
392
�
3.24
�
15.0
�
0.081
�
121
�
n
�
31
�
1.57
�
65
�
3.24
�
15.0
�
0.081
�
20
�
w
�
222
�
1.57
�
457
�
3.24
�
15.0
�
0.081
�
141
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
254
�
10.6
�
336
�
14.0
�
0
�
0.350
�
24
�
n
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
26
�
1.82
�
32
�
2.26
�
19.0
�
0.408
�
14
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
17
�
0
�
0
�
653
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 11
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
STUDY
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
141
�
1.57
�
292
�
3.24
�
15.0
�
0.081
�
90
�
n
�
255
�
1.57
�
525
�
3.24
�
15.0
�
0.081
�
162
�
e
�
255
�
1.57
�
525
�
3.24
�
15.0
�
0.081
�
162
�
w
�
651
�
1.57
�
1341
�
3.24
�
15.0
�
0.081
�
414
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% outdoor insect screen; 6.67 ft head ht
�
139
�
11.6
�
168
�
14.0
�
0
�
0.350
�
12
�
n
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
444
�
10.6
�
588
�
14.0
�
0
�
0.350
�
42
�
n
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
295
�
1.82
�
366
�
2.26
�
19.0
�
0.408
�
162
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
39
�
0
�
0
�
1543
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 12
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
UTILTIY
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
69
�
1.57
�
143
�
3.24
�
15.0
�
0.081
�
44
�
n
�
24
�
1.57
�
49
�
3.24
�
15.0
�
0.081
�
15
�
w
�
93
�
1.57
�
191
�
3.24
�
15.0
�
0.081
�
59
�
all
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
11D0: Door, wd sc type
�
283
�
13.5
�
328
�
15.6
�
0
�
0.390
�
21
�
n
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
59
�
1.82
�
73
�
2.26
�
19.0
�
0.408
�
33
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
8
�
0
�
0
�
316
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 13
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BATH 4
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
(none)
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
(none)
�
Ceilings
�
(none)
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 14
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BED 4
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
234
�
1.57
�
483
�
3.24
�
15.0
�
0.081
�
149
�
n
�
244
�
1.57
�
502
�
3.24
�
15.0
�
0.081
�
155
�
e
�
39
�
1.57
�
81
�
3.24
�
15.0
�
0.081
�
25
�
s
�
517
�
1.57
�
1066
�
3.24
�
15.0
�
0.081
�
329
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
380
�
10.6
�
504
�
14.0
�
0
�
0.350
�
36
�
n
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
85
�
1.82
�
106
�
2.26
�
19.0
�
0.408
�
47
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
37
�
0
�
0
�
1444
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 15
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
M WIC
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
(none)
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
(none)
�
Ceilings
�
(none)
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 16
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
MBATH & SMALL WIC
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
90
�
1.57
�
185
�
3.24
�
15.0
�
0.081
�
57
�
e
�
255
�
1.57
�
525
�
3.24
�
15.0
�
0.081
�
162
�
s
�
344
�
1.57
�
710
�
3.24
�
15.0
�
0.081
�
219
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
192
�
24.0
�
112
�
14.0
�
0
�
0.350
�
8
�
e
�
273
�
11.9
�
322
�
14.0
�
0
�
0.350
�
23
�
s
�
465
�
15.0
�
434
�
14.0
�
0
�
0.350
�
31
�
all
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
268
�
1.82
�
332
�
2.26
�
19.0
�
0.408
�
147
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
25
�
0
�
0
�
989
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 17
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
M BED
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
231
�
1.57
�
476
�
3.24
�
15.0
�
0.081
�
147
�
n
�
371
�
1.57
�
765
�
3.24
�
15.0
�
0.081
�
236
�
e
�
132
�
1.57
�
271
�
3.24
�
15.0
�
0.081
�
84
�
s
�
734
�
1.57
�
1513
�
3.24
�
15.0
�
0.081
�
467
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
925
�
11.9
�
1092
�
14.0
�
0
�
0.350
�
78
�
s
�
Doors
�
11D0: Door, wd sc type
�
283
�
13.5
�
328
�
15.6
�
0
�
0.390
�
21
�
e
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
550
�
1.82
�
681
�
2.26
�
19.0
�
0.408
�
302
�
Floors
�
22A-tpl: Bg floor, light dry soil, on grade depth
�
0.989
�
54
�
0
�
0
�
2130
�
39.6
�
0
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 18
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BED 3
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
137
�
1.57
�
282
�
3.24
�
15.0
�
0.081
�
87
�
s
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
356
�
11.9
�
420
�
14.0
�
0
�
0.350
�
30
�
s
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
403
�
1.82
�
499
�
2.26
�
19.0
�
0.408
�
221
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 19
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BATH 3
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
86
�
1.57
�
178
�
3.24
�
15.0
�
0.081
�
55
�
s
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
170
�
1.82
�
211
�
2.26
�
19.0
�
0.408
�
94
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 20
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BATH 2
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
85
�
1.57
�
175
�
3.24
�
15.0
�
0.081
�
54
�
n
�
Partitions
�
(none)
�
Windows
�
(none)
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
159
�
1.82
�
196
�
2.26
�
19.0
�
0.408
�
87
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 21
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BED 2
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
212
�
1.57
�
437
�
3.24
�
15.0
�
0.081
�
135
�
n
�
226
�
1.57
�
467
�
3.24
�
15.0
�
0.081
�
144
�
e
�
78
�
1.57
�
160
�
3.24
�
15.0
�
0.081
�
50
�
s
�
21
�
1.57
�
44
�
3.24
�
15.0
�
0.081
�
14
�
w
�
537
�
1.57
�
1108
�
3.24
�
15.0
�
0.081
�
342
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
380
�
10.6
�
504
�
14.0
�
0
�
0.350
�
36
�
n
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
538
�
1.82
�
666
�
2.26
�
19.0
�
0.408
�
295
�
Floors
�
20P-19c: Flr floor, frm flr, 10" thkns, carpet flr fnsh, r -19 cav ins,
�
amb ovr
�
9
�
0.90
�
20
�
2.00
�
19.0
�
0.050
�
10
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 22
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
BED 5
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
322
�
1.57
�
664
�
3.24
�
15.0
�
0.081
�
205
�
e
�
212
�
1.57
�
437
�
3.24
�
15.0
�
0.081
�
135
�
s
�
534
�
1.57
�
1102
�
3.24
�
15.0
�
0.081
�
340
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
356
�
11.9
�
420
�
14.0
�
0
�
0.350
�
30
�
s
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
617
�
1.82
�
764
�
2.26
�
19.0
�
0.408
�
338
�
Floors
�
(none)
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 23
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Component Constructions
�
3/10/16
�
Date:
�
GAME
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Design Conditions
�
Location:
�
Cooling
�
Heating
�
Indoor:
�
75
�
70
�
Indoor temperature (°F)
�
San Antonio Kelly Field A, TX, US
�
24
�
40
�
Design TD (°F)
�
ft
�
679
�
Elevation:
�
50
�
50
�
Relative humidity (%)
�
°N
�
29
�
Latitude:
�
Outdoor:
�
29.0
�
36.3
�
Moisture difference (gr/lb)
�
Cooling
�
Heating
�
Infiltration:
�
99
�
30
�
Dry bulb (°F)
�
Simplified
�
Method
�
)
�
M
�
(
�
21
�
-
�
Daily range (°F)
�
Average
�
Construction quality
�
74
�
-
�
Wet bulb (°F)
�
0
�
Fireplaces
�
7.5
�
15.0
�
Wind speed (mph)
�
Construction descriptions
�
Gain
�
Loss
�
Clg HTM
�
Htg HTM
�
Insul R
�
U-value
�
Area
�
Or
�
Btuh
�
Btuh/ft²
�
Btuh
�
Btuh/ft²
�
ft²-°F/Btuh
�
Btuh/ft²-°F
�
ft²
�
Walls
�
12C-2bw : Frm wall, brk 4" ext, r -13 cav ins, 1/2" gypsum board int
�
fnsh, r -2 ext bd ins, 2"x4" wood frm, 16" o.c. stud
�
190
�
1.57
�
392
�
3.24
�
15.0
�
0.081
�
121
�
n
�
24
�
1.57
�
49
�
3.24
�
15.0
�
0.081
�
15
�
e
�
214
�
1.57
�
441
�
3.24
�
15.0
�
0.081
�
136
�
all
�
Partitions
�
(none)
�
Windows
�
2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap, 1/8"
�
thk: 2 glazing, clr low -e outr, air gas, vnl frm mat, clr innr, 1/4" gap,
�
1/8" thk; 50% blinds 45°, medium; 50% outdoor insect screen; 6.67 ft
�
head ht
�
254
�
10.6
�
336
�
14.0
�
0
�
0.350
�
24
�
n
�
Doors
�
(none)
�
Ceilings
�
16X19-0ad: Attic ceiling, asphalt shingles roof mat, r -20 roof ins, 5/8"
�
gypsum board int fnsh
�
534
�
1.82
�
662
�
2.26
�
19.0
�
0.408
�
293
�
Floors
�
(none)
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 1
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Project Summary
�
3/10/16
�
Date:
�
Entire House
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Notes:
�
Design Information
�
San Antonio Kelly Field A, TX, US
�
Weather:
�
Winter Design Conditions
�
Summer Design Conditions
�
Outside db
�
°F
�
30
�
Outside db
�
°F
�
99
�
Inside db
�
°F
�
70
�
Inside db
�
°F
�
75
�
Design TD
�
°F
�
40
�
Design TD
�
°F
�
24
�
Daily range
�
M
�
Relative humidity
�
%
�
50
�
Moisture difference
�
gr/lb
�
29
�
Heating Summary
�
Sensible Cooling Equipment Load Sizing
�
Structure
�
Btuh
�
50651
�
Structure
�
Btuh
�
27665
�
Ducts
�
Btuh
�
3153
�
Ducts
�
Btuh
�
2054
�
Central vent (90 cfm)
�
3864
�
Btuh
�
Central vent (90 cfm)
�
Btuh
�
2280
�
Humidification
�
Btuh
�
0
�
Blower
�
Btuh
�
0
�
Piping
�
Btuh
�
0
�
Equipment load
�
Btuh
�
57667
�
Use manufacturer's data
�
n
�
Rate/swing multiplier
�
1.04
�
Infiltration
�
Equipment sensible load
�
Btuh
�
33151
�
Method
�
Latent Cooling Equipment Load Sizing
�
Simplified
�
Construction quality
�
Average
�
0
�
Fireplaces
�
Structure
�
Btuh
�
3463
�
Ducts
�
Btuh
�
501
�
Cooling
�
Heating
�
Central vent (90 cfm)
�
Btuh
�
1732
�
4077
�
4077
�
Area (ft²)
�
Equipment latent load
�
Btuh
�
3964
�
46769
�
46769
�
Volume (ft³)
�
Air changes/hour
�
0.19
�
0.37
�
Equipment total load
�
Btuh
�
37115
�
Equiv. AVF (cfm)
�
118
�
274
�
Req. total capacity at 0.70 SHR
�
ton
�
3.9
�
Heating Equipment Summary
�
Cooling Equipment Summary
�
Make
�
n/a
�
Make
�
n/a
�
Trade
�
n/a
�
Trade
�
n/a
�
Model
�
n/a
�
Cond
�
n/a
�
AHRI ref
�
n/a
�
Coil
�
n/a
�
AHRI ref
�
n/a
�
Efficiency
�
n/a
�
Efficiency
�
n/a
�
Heating input
�
Sensible cooling
�
Btuh
�
0
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
0
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
0
�
Actual air flow
�
cfm
�
0
�
Actual air flow
�
cfm
�
0
�
Air flow factor
�
cfm/Btuh
�
0
�
Air flow factor
�
cfm/Btuh
�
0
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
n/a
�
Load sensible heat ratio
�
0
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 2
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Project Summary
�
3/10/16
�
Date:
�
1ST FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Notes:
�
Design Information
�
San Antonio Kelly Field A, TX, US
�
Weather:
�
Winter Design Conditions
�
Summer Design Conditions
�
Outside db
�
°F
�
30
�
Outside db
�
°F
�
99
�
Inside db
�
°F
�
70
�
Inside db
�
°F
�
75
�
Design TD
�
°F
�
40
�
Design TD
�
°F
�
24
�
Daily range
�
M
�
Relative humidity
�
%
�
50
�
Moisture difference
�
gr/lb
�
29
�
Heating Summary
�
Sensible Cooling Equipment Load Sizing
�
Structure
�
Btuh
�
39758
�
Structure
�
Btuh
�
20870
�
Ducts
�
Btuh
�
2373
�
Ducts
�
Btuh
�
1542
�
Central vent (90 cfm)
�
3864
�
Btuh
�
Central vent (90 cfm)
�
Btuh
�
2280
�
Humidification
�
Btuh
�
0
�
Blower
�
Btuh
�
0
�
Piping
�
Btuh
�
0
�
Equipment load
�
Btuh
�
45995
�
Use manufacturer's data
�
n
�
Rate/swing multiplier
�
1.04
�
Infiltration
�
Equipment sensible load
�
Btuh
�
25580
�
Method
�
Latent Cooling Equipment Load Sizing
�
Simplified
�
Construction quality
�
Average
�
0
�
Fireplaces
�
Structure
�
Btuh
�
2303
�
Ducts
�
Btuh
�
362
�
Cooling
�
Heating
�
Central vent (90 cfm)
�
Btuh
�
1732
�
2749
�
2749
�
Area (ft²)
�
Equipment latent load
�
Btuh
�
4397
�
34092
�
34092
�
Volume (ft³)
�
Air changes/hour
�
0.16
�
0.36
�
Equipment total load
�
Btuh
�
29977
�
Equiv. AVF (cfm)
�
89
�
206
�
Req. total capacity at 0.70 SHR
�
ton
�
3.0
�
Heating Equipment Summary
�
Cooling Equipment Summary
�
Make
�
Make
�
Trane
�
Trade
�
Trade
�
TRANE
�
Model
�
Cond
�
4TTR6036B1
�
AHRI ref
�
Coil
�
4TXFH041CC3+*DH1B065A9H3
�
AHRI ref
�
5867043
�
Efficiency
�
80 AFUE
�
Efficiency
�
12.5 EER, 15.3 SEER
�
Heating input
�
Btuh
�
0
�
Sensible cooling
�
Btuh
�
23940
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
10260
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
34200
�
Actual air flow
�
cfm
�
1050
�
Actual air flow
�
cfm
�
1050
�
Air flow factor
�
cfm/Btuh
�
0.025
�
Air flow factor
�
cfm/Btuh
�
0.047
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
Load sensible heat ratio
�
0.85
�
Bold /italic values have been manually overridden
�
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
�
2016-Aug-10 12 :35:36
�
Right -Suite ® Universal 2017 17.0.04 RSU 06753
�
Page 3
�
... UGH IN LOADS\ 10122 DESCENT MONTEGO 7053 (N).rup Calc = MJ8 Front Door faces : N
�
10122 DESCENT
�
Job:
�
Project Summary
�
3/10/16
�
Date:
�
2ND FLOOR
�
RKM
�
By:
�
AIRTRON
�
SAN ANTONIO, TX
�
Project Information
�
SITTERLE HOMES
�
For:
�
MONTEGO 7053
�
Notes:
�
Design Information
�
San Antonio Kelly Field A, TX, US
�
Weather:
�
Winter Design Conditions
�
Summer Design Conditions
�
Outside db
�
°F
�
30
�
Outside db
�
°F
�
99
�
Inside db
�
°F
�
70
�
Inside db
�
°F
�
75
�
Design TD
�
°F
�
40
�
Design TD
�
°F
�
24
�
Daily range
�
M
�
Relative humidity
�
%
�
50
�
Moisture difference
�
gr/lb
�
29
�
Heating Summary
�
Sensible Cooling Equipment Load Sizing
�
Structure
�
Btuh
�
10893
�
Structure
�
Btuh
�
6802
�
Ducts
�
Btuh
�
780
�
Ducts
�
Btuh
�
512
�
Central vent (0 cfm)
�
Btuh
�
0
�
Central vent (0 cfm)
�
Btuh
�
0
�
Humidification
�
Btuh
�
0
�
Blower
�
Btuh
�
0
�
Piping
�
Btuh
�
0
�
Equipment load
�
Btuh
�
11673
�
Use manufacturer's data
�
n
�
Rate/swing multiplier
�
1.04
�
Infiltration
�
Equipment sensible load
�
Btuh
�
7578
�
Method
�
Latent Cooling Equipment Load Sizing
�
Simplified
�
Construction quality
�
Average
�
0
�
Fireplaces
�
Structure
�
Btuh
�
1160
�
Ducts
�
Btuh
�
139
�
Cooling
�
Heating
�
Central vent (0 cfm)
�
Btuh
�
0
�
1328
�
1328
�
Area (ft²)
�
Equipment latent load
�
Btuh
�
1299
�
12677
�
12677
�
Volume (ft³)
�
Air changes/hour
�
0.14
�
0.32
�
Equipment total load
�
Btuh
�
8877
�
Equiv. AVF (cfm)
�
29
�
68
�
Req. total capacity at 0.70 SHR
�
ton
�
0.9
�
Heating Equipment Summary
�
Cooling Equipment Summary
�
Make
�
Make
�
Trane
�
Trade
�
Trade
�
XR16
�
Model
�
Cond
�
4TTR6018B1
�
AHRI ref
�
Coil
�
4TXFH033CC3+*DH1B040A9H2
�
AHRI ref
�
5864647
�
Efficiency
�
80 AFUE
�
Efficiency
�
13.0 EER, 15 SEER
�
Heating input
�
Btuh
�
0
�
Sensible cooling
�
Btuh
�
12040
�
Heating output
�
Btuh
�
0
�
Latent cooling
�
Btuh
�
5160
�
Temperature rise
�
°F
�
0
�
Total cooling
�
Btuh
�
17200
�
Actual air flow
�
cfm
�
525
�
Actual air flow
�
cfm
�
525
�
Air flow factor
�
cfm/Btuh
�
0.045
�
Air flow factor
�
cfm/Btuh
�
0.072
�
Static pressure
�
in H2O
�
0
�
Static pressure
�
in H2O
�
0
�
Space thermostat
�
Load sensible heat ratio
�
0.85
�
Job #: 10122 DESCENT
�
Performed by RKM for :
�
SITTERLE HOMES
�
MONTEGO 7053
�
AIRTRON
�
SAN ANTONIO, TX
�
Scale: 1 : 114
�
Page 1
�
Right -Suite ® Universal 2017
�
17.0.04 RSU06753
�
2016 -Aug -10 12:36:43
�
...122 DESCENT MONTEGO 7053 (...
�
N
�
Level 2
BED 3
BATH 3
FOYER BELOW
GAME
BATH 2
BED 2
BED 5
GREAT OPEN TO BELOW
�
Job #: 10122 DESCENT
�
Performed by RKM for :
�
SITTERLE HOMES
�
MONTEGO 7053
�
AIRTRON
�
SAN ANTONIO, TX
�
Scale: 1 : 114
�
Page 2
�
Right -Suite ® Universal 2017
�
17.0.04 RSU06753
�
2016 -Aug -10 12:36:43
�
...122 DESCENT MONTEGO 7053 (...
�
N
�
Level 1
GREAT
BRKFST WITH WIC
KITCHEN
ENTRY
DINING
STUDY
UTILTIY
BATH 4
BED 4
M WIC
MBATH SMALL WIC
M BED