C-Linx Configuration Software Version 6.4.4.0
Copyright © 2014 Fike Corporation
Report Printed on 23/12/2014
Project Filename 'C:\Users\cbonilla\Desktop\Programaciones\19-12-14 DC GART -OSINERGMIN.lnx'
Cheetah Xi Panel 001 Configuration
Sales Outlet Information
WESTFIRE SUDAMERICA SRL
Calle Las Palomas 277
Lima, Surquillo Lima 34
Customer Information
Name
AddressCity, State ZIP
Page 1 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
2/12
Cheetah Xi Panel 001
Miscellaneous Settings
AC Trouble Delay 12 hours
Abort Type 5
Panel Walktest Enabled
Fan Restart Automatic Restart
Auxiliary Loop Module No Module
Auxiliary Power Module No Module
Aux Battery Supervision Disabled
Transformer Type 240VAC
Main Battery Supervision Enabled
SLC Wiring Style Style 4 - Class B
Ground Fault Supervision L1 Enb L2 Enb
Unsilence Time 24 hours
Silence Reminder Disabled
Silence Inhibit Disabled
Silence Mode UL Silence Mode
Panel Sync Protocol System Sensor
Panel Switch Operation Drill/Silence/Acknowledge Switches Enabled
Positive Alarm Sequence Disabled
New Device Record Missing Trb Disabled
Auto Message Sent at 12:00AM Disabled
Eclipse Device Error Device Error is Trouble
AHU Fire Dept Key Not Required to restart AHU
Defaults
Panel Line 2 Message WESTFIRE SUDAMERICA
Password 1 1000
Password 2 0000
Password 3 0000
Password 4 0000
Password 5 0000
Password 6 0000
Password 7 0000
Password 8 0000
Default Photo Sensor
Page 2 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
3/12
Common Settings
Custom Message Line 1 '1-001 PHOTO DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Alarm Verification Alarm Verification Disabled
Alarm Sensitivity Settings
Sensor Broadcast State Sensor Broadcasts ALARM
Pre-Alarm 1 Disabled
Pre-Alarm 2 Disabled
Acclimate High 2.0%
Acclimate Low 2.5%
Pre-Discharge Type Type A: Alarm Only
Drift Compensation Warning 80%
Drift Compensation Trouble 100%Walktest Level Walktest using Smoke at Alarm Level
Device Summing Settings
Broadcast Threshold 1 Disabled
Broadcast Threshold 2 Disabled
Broadcast Threshold 3 Disabled
Broadcast Threshold 4 Disabled
Broadcast Threshold 5 Disabled
Broadcast Threshold 6 Disabled
Broadcast Threshold 7 DisabledBroadcast Threshold 8 Disabled
Summing Address 1 No Device
Summing Address 2 No Device
Summing Address 3 No Device
Summing Address 4 No Device
Summing Address 5 No Device
Summing Address 6 No Device
Summing Address 7 No Device
Summing Address 8 No Device
Summing Alarm Level Disabled
Summing Activation State Summing Disabled
Remote Annunciator Settings
Remote Annunciator Type No Annunciator
Remote Annunciator Silence Non-Silenceable
Remote Annunciator PAS Disabled
Page 3 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
4/12
Default Photo/Heat Sensor
Common Settings
Custom Message Line 1 '1-001 PHO/HT DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Alarm Verification Alarm Verification Disabled
Alarm Sensitivity Settings
Sensor Broadcast State Sensor Broadcasts ALARM
Pre-Alarm 1 Disabled
Pre-Alarm 2 Disabled
Acclimate High 2.0%
Acclimate Low 2.5%
Flame Enhancement Enabled
Pre-Discharge Type Type A: Alarm Only
Drift Compensation Warning 80%
Drift Compensation Trouble 100%
Walktest Level Walktest using Smoke at Alarm Level
Device Summing Settings
Broadcast Threshold 1 Disabled
Broadcast Threshold 2 Disabled
Broadcast Threshold 3 Disabled
Broadcast Threshold 4 Disabled
Broadcast Threshold 5 Disabled
Broadcast Threshold 6 Disabled
Broadcast Threshold 7 Disabled
Broadcast Threshold 8 Disabled
Summing Address 1 No Device
Summing Address 2 No Device
Summing Address 3 No Device
Summing Address 4 No Device
Summing Address 5 No Device
Summing Address 6 No DeviceSumming Address 7 No Device
Summing Address 8 No Device
Summing Alarm Level Disabled
Summing Activation State Summing Disabled
Page 4 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
5/12
Remote Annunciator Settings
Remote Annunciator Type No Annunciator
Remote Annunciator Silence Non-Silenceable
Remote Annunciator PAS Disabled
Default Photo/Duct Sensor
Common Settings
Custom Message Line 1 '1-001 DUCT DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Alarm Verification Alarm Verification Disabled
Alarm Sensitivity Settings
Sensor Broadcast State Sensor Broadcasts ALARM
Pre-Alarm 1 Disabled
Pre-Alarm 2 Disabled
Acclimate High 2.0%
Acclimate Low 2.5%
Pre-Discharge Type Type A: Alarm Only
Drift Compensation Warning 80%
Drift Compensation Trouble 100%
Walktest Level Walktest using Smoke at Alarm Level
Page 5 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
6/12
Device Summing Settings
Broadcast Threshold 1 Disabled
Broadcast Threshold 2 Disabled
Broadcast Threshold 3 Disabled
Broadcast Threshold 4 Disabled
Broadcast Threshold 5 Disabled
Broadcast Threshold 6 Disabled
Broadcast Threshold 7 Disabled
Broadcast Threshold 8 Disabled
Summing Address 1 No Device
Summing Address 2 No Device
Summing Address 3 No Device
Summing Address 4 No Device
Summing Address 5 No Device
Summing Address 6 No Device
Summing Address 7 No DeviceSumming Address 8 No Device
Summing Alarm Level Disabled
Summing Activation State Summing Disabled
Remote Annunciator Settings
Remote Annunciator Type No Annunciator
Default Ion Sensor
Common Settings
Custom Message Line 1 '1-001 ION DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Alarm Verification Alarm Verification Disabled
Page 6 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
7/12
Alarm Sensitivity Settings
Sensor Broadcast State Sensor Broadcasts ALARM
Pre-Alarm 1 Disabled
Pre-Alarm 2 Disabled
Acclimate High 065 MIC
Acclimate Low 065 MIC
Pre-Discharge Type Type A: Alarm Only
Drift Compensation Warning 90%
Drift Compensation Trouble 100%
Walktest Level Walktest using Smoke at Alarm Level
Smoldering Enhancement Disabled
Device Summing Settings
Broadcast Threshold 1 Disabled
Broadcast Threshold 2 Disabled
Broadcast Threshold 3 DisabledBroadcast Threshold 4 Disabled
Broadcast Threshold 5 Disabled
Broadcast Threshold 6 Disabled
Broadcast Threshold 7 Disabled
Broadcast Threshold 8 Disabled
Summing Address 1 No Device
Summing Address 2 No Device
Summing Address 3 No Device
Summing Address 4 No Device
Summing Address 5 No DeviceSumming Address 6 No Device
Summing Address 7 No Device
Summing Address 8 No Device
Summing Activation Level Disabled
Summing Activation State Summing Disabled
Remote Annunciator Settings
Remote Annunciator Type No Annunciator
Remote Annunciator Silence Non-Silenceable
Remote Annunciator PAS Disabled
Default Heat Sensor
Page 7 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
8/12
Common Settings
Custom Message Line 1 '1-001 HEAT DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Alarm Verification Alarm Verification Disabled
Alarm Sensitivity Settings
Pre-Alarm 1 Disabled
Pre-Alarm 2 Disabled
Daytime Alarm 135°F
Nighttime Alarm 135°F
Pre-Discharge Type Type A: Alarm Only
Walktest Level Walktest using Heat at 135°F
Fixed Temp or Rate Sensor Implements Fixed Temperature Detection
Remote Annunciator Settings
Remote Annunciator Type No Annunciator
Remote Annunciator Silence Non-Silenceable
Remote Annunciator PAS Disabled
Default Monitor Module
Common Settings
Custom Message Line 1 '1-001 INPUT MANALRM'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Input Function Manual Alarm
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Wiring Style Class B
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Default Mini Monitor Module
Page 8 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
9/12
Common Settings
Custom Message Line 1 '1-001 MINI MANALRM'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Input Function Manual Alarm
Input Latching Type Latching Input
Input Contact Type Normally Open Contact
Input Short Detection Short Detection is Disabled
Zone Assignments 001
Default Pull Station Module
Common Settings
Custom Message Line 1 '1-001 PULL STATION'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Input Function Manual Alarm
Zone Assignments 001
Default Control Module
Common Settings
Custom Message Line 1 '1-001 OUTPUT MODULE'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'Zone Assignments 001
Drill Output Pattern On Continuous
Silence Output is Silenceable
Positive Alarm Sequence PAS is Disabled
Power Supply Monitor Monitor is Enabled
Output Control Settings
Priority State Action Pattern
01 Alarm Zone 001 On Continuous
32 Test Alarm Zone 001 Walktest
Default Relay Module
Page 9 of 12
C-Linx Configuration Software Fike Corporation
-
8/9/2019 Prog. Sala Gart
10/12
Common Settings
Custom Message Line 1 '1-001 RELAY MODULE'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
Drill Operation Drill Operation Disabled
Silence Output is Non Silenceable
Positive Alarm Sequence PAS is Disabled
Relay Monitoring Relay Monitoring is Disabled
Dry Contact Dry Contact Not Used
Output Control Settings
Priority State Action Relay State
01 Alarm Zone 001 On
Default Release Module
Common Settings
Custom Message Line 1 '1-001 RELEASING MOD'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments No Zone Assignments
Output Control Settings
Output Type No Output Device
Output State No Output State
Default FAAST Sensor
Common Settings
Custom Message Line 1 '1-001 FAAST DETECT'
Custom Message Line 2 'LOOP 1'
Custom Message Line 3 'ADDRESS 001'
Zone Assignments 001
FAAST States
Fire 2 Disabled No Alarm Verification
Fire 1 Alarm, Latching No Alarm Verification
Action 2 Disabled, Non-Latching No Alarm Verification
Action 1 Disabled, Non-Latching No Alarm Verification
Alert Disabled, Non-Latching No Alarm Verification
Acclimate Disabled
Page 10 of 12
C-Linx Configuration Software Fike Corporation
-