Cabling test in PROFINET ■ ■A physical check of each line in the form of a point-to-point connection in PROFINET networks is to be made by a cable tester.
PROlinetestArt. No. 112010010
ETHERtest V4Art. No. 112010003Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 47-62
PROFINET commissioning criteria to ensure a reliable operation
The release of the new PROFINET Commissioning Guideline by the PI (PROFIBUS & PROFINET International) stipulates important commissioning criteria. These ensure that the PROFINET network remains stable from the beginning and are summarized below.
PROFINET commissioning PROFINET Commissioning Guideline
Version 1.36 | Dec. 14
System reserve test of POF cabling ■ Power budget (optical system reserve) = Unit of measure- ment for the light reserve capacity available in the section between transmitter and receiver
■ Influenced by cable length, plug-in connections and the transmitting and receive power of the devices
PROscan® ActiveArt. No. 117000014 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 88/89
■ ■Discarded packets: telegrams rejected by the switch caused by e.g. interference, transmission errors or over-flow in queues in switches
■ CRC error detection (error telegrams)
Discarded packets / Error telegrams
PROscan® ActiveArt. No. 117000014 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 93/94
Based on the design predefinitions there have to be checked:
■ ■Maximum line depth (number of passing devices in one communication line, e.g. switches or IO devices with integrated switches)
■ ■Node information (firmware and hardware versions, device types, names acc. to naming convention)
Topology test
PROscan® ActiveArt. No. 117000014 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 91/92
Indu-Sol GmbH Blumenstrasse 3 04626 Schmoelln
Telephone: +49 (0) 34491 5818-0 Telefax: +49 (0) 34491 5818-99
Email: [email protected] Homepage: www.indu-sol.com
Indu-Sol GmbH – Specialist in Fieldbus Technology
Products ConsultingTrainingMonitoringDiagnosis
Upd
ated
03/
2016
PROFINET commissioning criteria to ensure a reliable operation
■ ■In communication hubs with high data flows → network connection to the controller
■ Measurement required prior to each controller having a multi controller application
Net load
PROFINET-INspektor® NTArt. No. 124030100 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 95-97
Jitter ■ ■an important parameter for long-term trouble-free operation
■ ■Fluctuation in the time intervals of PROFINET packets → long delay, meaning high jitter
■ ■Constantly high jitter is evidence of a changed load ratio, topology changes or device replacement PROFINET-INspektor® NT
Art. No. 124030100 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 102
TEXT
Our products as all-in-one solution
PROFINET Diagnostic set IIIArt. No. 114010020
PROFINET DiagnosticDUOArt. No. 124030020
Both solutions provide for testing all the required commissioning criteria.
incl. wiring test in PROFINET and shield current measurement.
PROFINET communication monitoring (telegram gap) ■ Each controller has an internal error counter that triggers a fieldbus error when threshold values are exceeded.
■ A higher threshold value increases the fault tolerance if an error occurs, but also extends time until faults are detected.
■ Recommendation is to retain the standard setting 3. If the setting is changed, a check is needed to determine, if the time is sufficiently short.
PROFINET-INspektor® NTArt. No. 124030100 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 87
Broadcast and multicast traffic ■ The broadcast and multicast traffic is to be checked.
PROFINET-INspektor® NTArt. No. 124030100 Source: Commissioning Guideline by the PI (V 1.36 / Dec. 14) p. 98-101
PROmanage® NTArt. No. 117000030