EXISTING INTAKE LOUVER AND DAMPER
TO BE RELOCATED AS SHOWN.
EX. 48"x80" INTAKE HOOD.
REFER TO EXHAUST HOOD
DETAIL 1 THIS SHEET.
EX. 72"x40" OUTLET
SLEEVE TO REMAIN
EXISTING MECHANICAL
DETAIL THIS SHEET
UP
ELEC PANELS
NORTH
ADDITION
E
5a
F
Ex
1 2 3
654
4b4a
B
97b
6a
C1
8
C3
8x
Dy
7a 7bb
6
Ey
E
D
C
B
ELEC PANELS
EXISTING 2"
WATER SERVICE
EXISTING 4"∅SANITARY
G G G G
M
EX. 1" GAS SERVICE
EX. COGEN UNIT
M
EX. DCW UP
G
EX. 1" GAS TO CO.1
EX. 3/4" GAS TO F.1 & HWH.1
G G
CO.1
Dy
ROTATE EX. HOOD 180° TO ACCOMMODATE NEW GOOSENECK.
REFER TO EXHAUST HOOD DETAIL 2 SHEET M1.
98 8x
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
EXISTING/DEMOMECHANICAL LAYOUT
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
MD1
N
EXISTING/DEMO MECHANICAL LAYOUT
SCALE:
1
16
"=1'-0"
EXISTING/DEMO MECHANICAL DETAIL
SCALE:
1
4
"=1'-0"
EXHAUST HOOD DETAIL 1
SCALE:
1
8
"=1'-0"
UP
SOUTH ADDITION
MAINTENANCE SHOP
NORTH
ADDITION
DN
DN
FS
CTRL
NO2
CO
NO2
CO
NO2
CO
EF-1
EF-2
LV-1 @ HEIGHT TO MATCH EXISTING
42x34 EXHAUST DUCT UP TO MATCH EXISTING.
OPEN ENDED WITH BIRDSCREEN.
DRILL DRAIN HOLES TO MATCH EXISTING.
TYP. 2
RELOCATED INTAKE LOUVER
HEIGHT TO MATCH EXISTING
MECHANICAL DETAILS
THIS SHEET
M
MD-1
M
MD-2
M
MD-3
NEW SUMP PIT WITH
SP-1 BELOW
NEW TRENCH DRAIN TD-1
SEE ARCHITECTURAL
DRAWINGS
CO
CO
CO
E
5a
D3
-3 -2-4
C0
C4
A
F
Ex
1
-5
G
2 3
1B
65
D1
A1
10
4
-5
1a-2-3-4
G
F
Ex
D2
C2
A1
4b4a
B
E
97b
6a
1a
C1
8
C3
8x
Dy
7a 7bb
6
Ey
E
D
C
B
A
98
7654321
NEW TRENCH DRAIN TD-1
SEE ARCHITECTURAL
DRAWINGS
4" @ 1%
4" @ 1%
1
1
1
RETURN DUCT ELBOW
BELOW ROOF
F-1 w/ CC.1
SUSPENDED
FROM CEILING
NEW 2" SAN FROM S.1
GGGGGGG
SP-2
AC-1 WALL MOUNTED AT HIGH
LEVEL. CONTRACTOR TO PROVIDE
MOUNTING AS REQUIRED.
FD.1
S.1
1-1/2" SUMP DISCHARGE @1%
TO TRENCH @ 6' A.F.F.
ROUTE PIPE BETWEEN BUILDING
COLUMNS AND EXTERIOR WALL.
HWT.1
NEW 3/4" DCW. INSULATE & HEAT TRACE LINE
FROM MAINTENANCE ROOM PENETRATION
BACK TO MECHANICAL ROOM CONNECTION.
A
400
TYP. 3
T
SUPPLY AND RETURN DUCT SIZES
TO MATCH FURNACE OPENINGS.
c/w ACOUSTIC INSULATION.
F.1
HRV.1
HRV.1 SUSPENDED
FROM CEILING
FRESH AIR INTAKE
LOUVER LV.2
EF.3
EF.2 ON ROOF ABOVE WELD
TABLE. DUCT OPEN ENDED
BELOW ROOF. REFER TO
ARCH. DRAWINGS.
FRESH AIR INTAKE
LOUVER LV.3
EF.4
EF.3 ON ROOF. 10"x10" DUCT
DOWN THRU ROOF.
REFER TO ARCH. DRAWINGS.
M
MD-4
T
REVERSE ACTING
THERMOSTAT
FS
CONNECT FAN
STARTER TO EF-3
CONNECT FAN
STARTER TO
EF-2/MD-3
1" DRAIN LINE INTO F.F.D. AT
TOP OF WALL. ROUTE DOWN
OUTSIDE OF WALL TO SAN BELOW
3" VENT THRU ROOF
6"∅ DUCT TYP.
HWT-1 ABOVE
HRV INTAKE
BELOW OPEN
TO SPACE
10"x10"
10"x10" DOWN THROUGH ELECTRICAL
ROOM CEILING TO EXHAUST GRILLE
AT CEILING HEIGHT.
B
300
EQUIPMENT
CONDENSATE
HWT-1 DRAIN LINE
ROUTE SUMP DISCHARGE DOWN
WALL AND INTO TRENCH
UP THRU ROOF
NEW 1/2" DCW &
DHW DN TO S.1.
RA
HEAT TRACE TO BE CHROMALOX SRF 5-2C
CABLE, WITH UBC INTEGRATED POWER AND
THERMOSTAT CONTROL, OR EQUIVALENT.
FFD
TRAP SEAL PRIMER
UNDER SINK
FS
EXISTING 2"
WATER SERVICE
EXISTING 4"∅SANITARY
G
M
EX. 1" GAS SERVICE. UPGRADE EX.
GAS MATER TO MEET NEW DEMAND.
COORDINATE WITH UNION GAS.
EX. COGEN UNIT
M
EX. DCW UP TO
MECHANICAL ROOM
EX. 1" GAS TO EX. COGEN UNIT
EX. 3/4" GAS TO EX. EQUIP
GGGG
NEW 3/4" GAS LINE TO NEW
F.1 ALONG EXTERIOR WALL
ABOVE PUMP ROOM ROOF.
CO.1
NEW 3/4" WATER LINE SERVING MAINTENANCE SHOP.
CONTRACTOR TO DETERMINE MOUNTING HEIGHT ON SITE.
CONNECT TO EXISTING WATER LINE IN MECHANICAL ROOM.
EX. WATER METER
BELOW
1'-0"
2'-0"
4'-0"
1
6
0
°
METAL BIRD SCREEN MOUNTED
WITH ANGLE IRON FRAME.
SEE DETAIL 3 THIS SHEET.
4
'
-
0
"
PROVIDE DUCT SUPPORT.
SEE STRUCTURAL DRAWING S2.1
DUCT SUPPORT, SEE
STRUCTURAL DRAWING S2.1
FIELD MEASURE EXISTING HOOD AND MATCH
GOOSENECK CROSS SECTION AREA TO HOOD.
FABRICATE GOOSENECK TO CURRENT SMACNA
STANDARDS. CONTRACTOR TO PROVIDE SHOP
DRAWINGS PRIOR TO FABRICATION.
4a4a 4b4b 5a5a 6a6a 66 8 8x 9
METAL SCREEN FRAME
BOLTS
SCREEN
ANGLE IRON REINFORCING
6'-6
3
4"
11'-1
5
8"±
NEW AIR INTAKE
GOOSENECK
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
PLANT/MAINTENANCEROOM MECHANICAL
LAYOUT
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
M1
N
MECHANICAL LAYOUT
SCALE:
1
16
"=1'-0"
MAINTENANCE SHOP MECHANICAL LAYOUT
SCALE:
1
16
"=1'-0"
OFFICE MECHANICAL LAYOUT
SCALE:
1
16
"=1'-0"
EXHAUST HOOD DETAIL 2
SCALE:
1
8
"=1'-0"
DETAIL 3
SCALE:6"=1'-0"
EXHAUST HOOD ELEVATION
SCALE:
1
16
"=1'-0"
SOUTH ADDITION
DN
DN
30m x 38mm∅ FIRE HOSE
(98.4' x 1.5")
30m x 38mm∅ FIRE HOSE
(98.4' x 1.5")
FDC
VALVE
ROOM
EBB.1
D3
-3 -2-4
F
Ex
1
-5
G
2 3
1B
-5
1a-2-3-4
G
F
Ex
D2
C2
A1
E
D
C
B
A
6"∅ FIRE SERVICE. COMPLETE WITH DOUBLE
CHECK VALVE BACK FLOW PREVENTER.
CONNECT TO SITE SERVICES 5' FROM BUILDING.
DESIGN NOTES
1. STANDPIPE SYSTEM TO BE INSTALLED AS PER N.F.P.A. STANDARD #14 AND
ONTARIO BUILDING CODE (OBC) WHEREVER APPLICABLE.
2. PLANT AREA WHERE STANDPIPE SYSTEM IS TO BE INSTALLED IS AN UNHEATED
BUILDING. A DRY SYSTEM IS REQUIRED. ALL CONTROL VALVES, PUMPS, AND AIR
COMPRESSOR TO BE INSTALLED IN HEATED VALVE ROOM.
3. STATIC PRESSURE AT WATER MAIN WAS MEASURED AT 53 PSI. CONTRACTOR TO
DETERMINE PUMP REQUIREMENTS TO MEET MINIMUM HOSE STATION FLOW AND
PRESSURE REQUIREMENTS AS PER OBC 3.2.9.
4. FIRE PROTECTION CONTRACTOR TO DETERMINE COMPRESSED AIR
REQUIREMENTS. A STAND ALONE COMPRESSOR IS TO BE SUPPLIED IN THE VALVE
ROOM.
5. ALL MATERIALS TO BE U.L.C. LISTED AND APPROVED BY ALL LOCAL AUTHORITIES.
6. ALL SUPERVISED VALVES, FLOW SWITCHES AND LOW PRESSURE MONITORING
SWITCHES TO BE CONNECTED TO EXISTING FIRE ALARM SYSTEM (IF APPLICABLE)
OR NEW FIRE ALARM OR NEW FIRE ALARM SYSTEM (IF APPLICABLE) BY
ELECTRICAL CONTRACTOR.
7. POWER SUPPLY TO STANDPIPE SYSTEM COMPONENTS, SUCH AS SUPERVISED
VALVES AND AIR COMPRESSORS, TO BE PROVIDED BY ELECTRICAL CONTRACTOR
AS REQUIRED.
8. PROVIDE FIRE ALARM VERIFICATION BEFORE COMPLETION OF PROJECT IN
ACCORDANCE WITH O.B.C. 3.2.4.5. SUBMIT COPY OF TECHNICIANS REPORT AND
CERTIFICATE.
DESIGN CRITERIA
1. STANDPIPE SYSTEM TO BE HYDRAULICALLY DESIGNED IN ACCORDANCE WITH
N.F.P.A. 14 "INSTALLATION OF STANDPIPE AND HOSE SYSTEMS" FOR A DRY SYSTEM.
STANDPIPE GENERAL NOTES:
1. FIRE PROTECTION CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR HYDRAULIC
CALCULATIONS AND PIPING SIZE FOR OWNERS INSURANCE COMPANY APPROVAL.
2. DRAWINGS AND CALCULATIONS ARE TO BE SEALED BY A PROFESSIONAL
ENGINEER REGISTERED IN ONTARIO AND COMPETENT FOR WORK DESIGNED.
3. PROVIDE CUTTING AND PATCHING FOR WORK AND ARRANGE TO MAKE GOOD ALL
FINISHES.
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
FIRE PROTECTIONAND VALVE ROOM
LAYOUTS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
M2
N
FIRE PROTECTION LAYOUT
SCALE:
1
16
"=1'-0"
HVAC EQUIPMENT SCHEDULE
TAG ID DESCRIPTION MAKE MODEL
AIR FLOW
(CFM)
HEATING
INPUT
COOLING
CAPACITY
VOLTAGE
UNIT WEIGHT
kg (lbs)
REMARKS
F.1 NEW FURNACE GOODMAN GMS800603AN 1200 60 MBH
115/1/60
HEATING
OUTPUT
-48 MBH
40 (88)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.
MCA (AMPS) MOCP (AMPS)
154.8
HRV.1 HEAT RECOVERY VENTILATOR LIFEBREATH 195 DCS 216 -
120/1/60
--
40 (88)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.151.5
AC.1 AIR CONDITIONER GOODMAN GSX130301 - -
208/1/60
27 MBH-
52.3 (115)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.2516.7
CC.1 COOLING COIL GOODMAN CHPF2430B6 - - -27 MBH-
25 (55)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.--
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
EBB.1 ELECTRIC BASEBOARD HEATER OUELLET OPR1002 - -
120/1/60
-1000 W
11.8 (26)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.15-
ASHRAE 62.1 VENTILATION SUMMARY
SPACE IDENTIFICATION
FAB SHOP
SPACE TYPE
GENERAL MANUFACTURING
SPACE AREA
(SQ. FEET)
800
NUMBER OF
OCCUPANTS
3
AREA OUTDOOR
AIR RATE
(CFM/SQFT)
0.18
PEOPLE OUTDOOR
AIR RATE
(CFM/PERSON)
10
DISTRIBUTION
EFFECTIVENESS
(Ez)
1.0
SYSTEM EFFICIENCY
(Ev)
0.9
DIVERSITY
1.0
REQUIRED OUTDOOR
AIR RATE
(CFM)
220
LOUVERS & DAMPERS SCHEDULE
MOTORIZED DAMPER
TAG ID DESCRIPTION SIZE MAKE REMARKS
TAMCO
MODEL
SERIES 1000
BELIMO DAMPER MOTOR & ALL CONTROLS
MOTOR ELECTRICAL: 120/1/60, END SWITCHES
STATIONARY DRAINABLE LOUVER E.H. PRICE DE439
W/ FORMED METAL SILL & BIRD SCREEN
TO SUIT LOUVER
& EXHAUST FAN
108x84
MD-1, 2,
3, 4
LV-1
STATIONARY DRAINABLE LOUVER E.H. PRICE DE439
W/ FORMED METAL SILL & BIRD SCREEN
26x24LV-2
STATIONARY DRAINABLE LOUVER E.H. PRICE DE439
W/ FORMED METAL SILL & BIRD SCREEN
14x12LV-3
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
HEIGHTUNIT#
HWT.1
CAPACITY
WATER HEATER SCHEDULE
INPUT (kW)
MAKE MODEL # DIAMETER SHIPPING WEIGHTTYPE
A.O.SMITH EJC-6 6 USG ELECTRIC 1650 15.25" 14.25" 35 lbs
WEIGHT W/ WATER
~85 lbs
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
UNIT # DESCRIPTION
HWH.1
EX. HOT WATER HEATER
INPUT CAPACITY (MBH)
(WHEN COGEN UNIT IS RUNNING)
-
GAS DEMAND SCHEDULE
TOTAL GAS DEMAND 411 MBH
F.1 -
CO.1 351
AC.1 60
EX. COGEN UNIT
NEW FURNACE
EX. FURNACE
INPUT CAPACITY (MBH)
(WHEN COGEN UNIT IS NOT RUNNING)
76
224 MBH
88
-
60
MECHANICAL LEGEND
SYMBOL DESCRIPTION
BURIED SANITARY PIPE
DOMESTIC COLD WATER SUPPLY
3" FLOOR DRAIN
FD.1
PIPE DOWN
PIPE UP
DOMESTIC HOT WATER SUPPLY
SYMBOL DESCRIPTION
HOSE BIB COMPLETE WITH VACUUM BREAKER
TSP
TRAP SEAL PRIMING UNIT
G G
NEW GAS
G G
GAS VALVE
PRESSURE REDUCING VALVE
SUPPLY, RETURN, TRANSFER, EXHAUST,
AIR GRILLE/REGISTER TAGD
250
CFM
TYPE
T
CONTROL THERMOSTAT
CARBON MONOXIDE MONITOR
MMOTORIZED AIR DAMPER
CONTROL WIRING
NITROGEN DIOXIDE MONITOR
CO
NO2
FS
CTRL
FAN STARTER
HAZARDOUS GAS CONTROL PANEL
ROOFTOP EXHAUST FAN
ISOLATION VALVE
BV
BALANCING VALVE
BURIED SANITARY PIPE
EXISTING PIPE
SIDEWALL EXHAUST FAN
CO
SANITARY CLEAN OUT
T
REVERSE ACTING THERMOSTATSIAMESE FIRE DEPARTMENT CONNECTION
RA
3" FUNNEL FLOOR DRAIN
FFD.1
EXHAUST FAN SCHEDULE
EF-1,2
WALL MOUNTED EXHAUST FAN
FAN # DESCRIPTION MAKE MODEL
AIR FLOW
(CFM)
STATIC
PRESSURE
FAN MOTOR
kW (HP)
VOLTAGE
UNIT WEIGHT
kg (lbs)
GREENHECK AER-E36C-310-A 18000
2.87 (3.85)
0.4 in wc
208/60/3 72.7 (160)
FLA
16.7
EF-3 ROOF MOUNTED EXHAUST FAN GREENHECK GB-161 1800
0.142 (0.19)
0.2 in wc
120/1/6028.6 (63)
5.8
EF-4 ROOF MOUNTED EXHAUST FAN GREENHECK G-090-E 300
0.015 (0.02)
0.2 in wc
120/1/60 11.8 (26)
-
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
SEQUENCE OF OPERATIONS - GAS DETECTIONS SYSTEMS
1. LOW LEVEL ALARM NITROGEN DIOXIDE (NO2)
IF ANY NITROGEN DIOXIDE (NO2) SENSOR POINT DETECTS 0.72PPM GAS OR MORE, DAMPERS MD-1 &
MD-2's SHALL OPEN & WHEN FULLY OPENED AS SENSED BY THEIR END SWITCHES EF-1's SHALL BE
ENERGIZED. LOW ALARM LED LIGHTS FOR POINT IN ALARM.
2. HIGH LEVEL ALARM NITROGEN DIOXIDE (NO2)
IF NITROGEN DIOXIDE (NO2) GAS CONCENTRATION LEVELS CONTINUE TO RISE & ANY SENSOR
DETECTS 2.0PPM GAS, W/ VENTILATION CONTACTS CONTINUING TO OPERATE, THE UNIT AUDIBLE
ALARM SOUNDS & HIGH ALARM INDICATOR LIGHTS ON THE CENTRAL CONTROLLER DISPLAY.
3. LOW LEVEL ALARM CARBON MONOXIDE (CO)
IF ANY CARBON MONOXIDE (CO) SENSOR POINT DETECTS 25PPM GAS OR MORE, DAMPERS MD-1 &
MD-2's SHALL OPEN & WHEN FULLY OPENED AS SENSED BY THEIR END SWITCHES EF-1's SHALL BE
ENERGIZED. LOW ALARM LED LIGHTS FOR POINT IN ALARM.
4. HIGH LEVEL ALARM CARBON MONOXIDE (CO)
IF CARBON MONOXIDE (CO) GAS CONCENTRATION LEVELS CONTINUE TO RISE & ANY SENSOR
DETECTS 100PPM GAS, W/ VENTILATION CONTACTS CONTINUING TO OPERATE, THE UNIT AUDIBLE
ALARM SOUNDS & HIGH ALARM INDICATOR LIGHTS ON THE CENTRAL CONTROLLER DISPLAY.
SEQUENCE OF OPERATIONS - WAREHOUSE
1. EXHAUST FAN EF-1's SHALL BE INTERLOCKED W/ FRESH AIR & EXHAUST AIR DAMPERS MD-1 & MD-2 AS
WELL AS THE GAS DETECTION SYSTEM (SEE "SEQUENCE OF OPERATIONS - GAS DETECTION SYSTEMS")
2. EF-1 SHALL BE CONTROLLED BY AN "HOA" SWITCH. EF-1 SHALL BE ENERGIZED WHEN MD-1 & MD-2
ARE COMPLETELY OPENED AS SENSED BY THEIR END SWITCHES.
SEQUENCE OF OPERATIONS - FABRICATION SHOP
1. EXHAUST FAN EF-2 SHALL BE CONTROLLED BY A SINGLE THROW SWITCH AND SHALL BE INTERLOCKED
W/ FRESH AIR DAMPER MD-3.
SEQUENCE OF OPERATIONS - ELECTRICAL ROOM
1. EF-3 SHALL BE CONTROLLED BY A REVERSE ACTING THERMOSTAT. EF-3 SHALL BE ENERGIZED WHEN
THE THERMOSTAT READS 35°C.
PUMP SCHEDULE - ELECTRICAL
TAG # DESCRIPTION MAKE MODEL # MOTOR
SUBMERSIBLE WASTE
WATER SUMP PUMP
SP-1
HEAD
Meters (Feet)
FLOW
L/s (gpm)
ZOELLER 49
1/4hp (0.19 kW) 3 (10) 1.6 (25)
MCA (AMPS) MOCP (AMPS)VOLTAGE
120/1/60
4.0 15
REMARKS
INSTALL PER MANUFACTURERS INSTALLATION
INSTRUCTIONS
PREASSEMBLED WASTE
WATER SUMP PUMP SYSTEM
SP-2 ZOELLER 900-0002
3/10hp (0.22 kW) 3 (10) 2.2 (35)120/1/60
9.7 15
INSTALL PER MANUFACTURERS INSTALLATION
INSTRUCTIONS
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
DIFFUSER, REGISTER & GRILLE SCHEDULE
TAG DESCRIPTION
SUPPLY AIR GRILLEA
CFM
400
MAKE
PRICE
MODELSIZE
16" x 6" 510
EXHAUST AIR GRILLEB
300 PRICE10" x 10" 530
NOTE: WHEN COGEN UNIT IS RUNNING
HWH.1 AND F.1 DO NOT DEMAND GAS.
PLUMBING EQUIPMENT SCHEDULE
TAG ID DESCRIPTION
MANUFACTURER /
MODEL
S.1
STAINLESS STEEL SERVICE SINK - S.S. TUBULAR LEGS W/ ADJUSTABLE
FEET, 2 HOLES 8" ON CENTRE, BACKSPLASH MOUNTED TWO HANDLE
MANUAL FAUCET W/ SPRAY HOSE, VACUUM BREAKER, BUCKET HOOK AND
PROJECTION SPOUT W/
3
4
" HOSE ADAPTER (MF'R: CHICAGO FAUCETS,
MODEL 509-GCLAB-ES) AND ALL INSTALLATION/MOUNTING HARDWARE
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
FRANKE
SSL2418-1/2
1
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
MECHANICAL LEGENDSAND SCHEDULES
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
M3
N
GENERAL SPECIFICATIONS
THE SCOPE OF WORK SHALL INCLUDE ALL LABOUR, MATERIALS, EQUIPMENT, AND TOOLS
REQUIRED FOR A COMPLETE AND WORKING INSTALLATION AS DETAILED WITHIN THESE
DRAWINGS AND SPECIFICATIONS TO THE SATISFACTION OF THE ENGINEER.
SECTIONS OF THESE SPECIFICATIONS ARE NOT INTENDED TO DELEGATE FUNCTIONS OR TO
DELEGATE WORK AND SUPPLY TO ANY SPECIFIC TRADE.
THE DRAWINGS AND SPECIFICATIONS SHALL BE READ IN CONJUNCTION WITH BASE
BUILDING DRAWINGS AND SPECIFICATIONS. THE BASE BUILDING STANDARDS SHALL FORM
THE BASIS FOR THIS CONSTRUCTION.
PROVIDE ALL WORK IN ACCORDANCE WITH THE REQUIREMENTS OF ALL GOVERNING
AUTHORITIES, AND LOCAL BY-LAWS.
CONFORM TO THE BEST MODERN PRACTICES OF WORKMANSHIP AND INSTALLATION
METHODS AND EMPLOY ONLY SKILLED TRADESPEOPLE WORKING UNDER THE DIRECTION OF
FULLY QUALIFIED PERSONNEL.
APPLY FOR, OBTAIN, AND PAY FOR ALL PERMITS, LICENCES, INSPECTIONS, EXAMINATIONS
AND FEES REQUIRED PRIOR TO COMMENCEMENT OF CONSTRUCTION.
VISIT AND INSPECT THE SITE OF THE WORK TO VERIFY LOCATION AND ELEVATION OF
EXISTING SERVICES, INCLUDING LOCATIONS OF EXISTING CAPPED SERVICES, WHICH MAY
AFFECT THE TENDER AND WORK OF THIS DIVISION (ELECTRICAL, WATER, SANITARY,
DUCTWORK ETC.) BEFORE SUBMISSION OF TENDER AND PROCEEDING WITH WORK. ALLOW
FOR ANY RE-ROUTING OF EXISTING AND/OR NEW SERVICES AND EQUIPMENT AS REQUIRED
TO AVOID INTERFERENCES IN TENDER PRICE.
SHOULD ANY DISCREPANCY APPEAR BETWEEN THE DRAWINGS AND SPECIFICATIONS, WHICH
LEAVE THE CONTRACTOR IN DOUBT AS TO THE TRUE INTENT AND MEANING OF THE PLANS,
AND SPECIFICATIONS, THE CONTRACTOR SHALL OBTAIN A RULING FROM THE ENGINEER IN
WRITING BEFORE SUBMITTING A TENDER. REPORT TO THE ENGINEER ALL AMBIGUITIES,
DISCREPANCIES, OMISSIONS, ERRORS, DEPARTURES FROM BUILDING BYLAWS AND/OR
FROM GOOD PRACTICE. IF THIS IS NOT DONE IT WILL BE ASSUMED THAT THE MOST
EXPENSIVE ALTERNATIVE HAS BEEN INCLUDED IN THE TENDER PRICE. FOR ANY RULING TO
BECOME BINDING, THE ENGINEER MUST ISSUE THE NEW DIRECTION IN A PUBLISHED FORM.
ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE APPROVED SCHEDULE TO MEET THE
PROJECT COMPLETION DATE AND ALL SPECIFIED INTERIM SCHEDULES.
ALL SHUTDOWNS OF ANY PORTION OF THE EXISTING BASE BUILDING SYSTEMS SHALL BE
PERFORMED BY THE OWNER'S BUILDINGS OPERATIONS STAFF AND/OR COORDINATED WITH
THE OWNER FOR THE TIME AND DURATION OF INTERRUPTIONS AND ADHERE TO THE
LANDLORD'S INSTRUCTIONS IN THIS REGARD. CAREFULLY SCHEDULE DISRUPTIONS TO
KEEP "DOWN TIME" TO A MINIMUM. COST FOR SHUTDOWNS, DRAINING AND REFILLING OF
BASE BUILDING SYSTEMS SHALL BE INCLUDED IN THE TENDER PRICE.
IN ALL AREAS REQUIRING CORE DRILLING THROUGH EXISTING FLOOR SLAB FOR
MECHANICAL SERVICES, ETC. ALLOW FOR ALL NECESSARY RADIOGRAPHY TO LOCATE
HIDDEN ELECTRICAL SERVICES, STRUCTURAL REINFORCING, ETC., AND INCLUDE ALL COSTS
IN TENDER PRICE. COORDINATE THIS WORK WITH LANDLORD AND/OR TENANT
COORDINATOR FOR TIME, DURATION AND LOCATIONS REQUIRED, AND ADHERE TO THE
LANDLORD'S REQUIREMENTS. SUBMIT CORE DRILLING PLAN TO BASE BUILDING
STRUCTURAL ENGINEER FOR APPROVAL PRIOR TO COMMENCEMENT OF WORK.
CHECK AND VERIFY LOCATION OF EXISTING MECHANICAL AND ELECTRICAL INTERFERENCES
IN CEILING SPACE OF FLOOR BELOW AND/OR BELOW FLOOR SLAB IN ALL AREAS REQUIRING
CORE DRILLING AND/OR CUTTING OF FLOOR SLAB ON GRADE AND ENSURE COMPATIBILITY
OF AREA BELOW TO THE SATISFACTION OF THE LANDLORD.
INCLUDE COST OF PREMIUM TIME IN TENDER PRICE FOR WORK DURING NIGHTS,
WEEKENDS, OR OTHER TIME OUTSIDE NORMAL WORKING HOURS NECESSARY TO MAINTAIN
ALL MECHANICAL SERVICES IN OPERATION, AND TO COMPLETE THE WORK.
CUTTING, CORING, DRILLING, PATCHING, FLASHING, REPAIRS AND CLEAN-UP OF EXISTING
SURFACES REQUIRED AS A RESULT OF THE REMOVAL AND/OR RELOCATION OF EXISTING
EQUIPMENT AND PIPING, AND/OR INSTALLATION OF NEW EQUIPMENT AND PIPING TO BE
INCLUDED IN TENDER PRICE. EMPLOY AND PAY APPROPRIATE SUB-TRADE WHOSE WORK IS
INVOLVED, FOR CARRYING OUT WORK DESCRIBED ABOVE.
SUBMIT SHOP DRAWINGS FOR ALL ITEMS SPECIFIED. FOR EQUIPMENT, PROVIDE
PERFORMANCE, PHYSICAL AND OPERATING DATA AS DESCRIBED IN THE SPECIFICATIONS
AND LISTED IN EQUIPMENT SCHEDULES. PROVIDE PERFORMANCE CURVES FOR ALL PUMPS
AND FANS. INCLUDE SOUND AND VIBRATION DATA FOR ALL EQUIPMENT SUCH AS FANS,
VAV TERMINALS AND CHILLERS.
DURING PROGRESS OF WORK, SUBSTITUTE PRODUCTS WILL ONLY BE CONSIDERED WHEN
TENDERED PRODUCTS BECOME UNOBTAINABLE AND WRITTEN PROOF IS SUBMITTED. ALL
ALTERNATE ITEMS SUBMITTED FOR CONSIDERATION MUST NOT EXCEED AVAILABLE SPACE
LIMITATIONS.
EQUIPMENT LISTED AS “EQUAL” IN SPECIFICATIONS OR SUBMITTED AS EQUAL BY THE
CONTRACTOR MUST MEET ALL SPACE REQUIREMENTS, SPECIFIED CAPACITIES AND MUST
HAVE EQUIPMENT CHARACTERISTICS OF SPECIFIED EQUIPMENT AS INTERPRETED BY
ENGINEER. INSTALL EQUIPMENT IN STRICT ACCORDANCE WITH MANUFACTURER'S
PUBLISHED RECOMMENDATIONS.
THE ARCHITECT/INTERIOR DESIGNER AND ENGINEER MUST PROVIDE ACCEPTANCE OF ANY
PRODUCT AS EQUAL BEFORE IT IS ALLOWED TO BE USED ON THIS PROJECT.
ALL ADDITIONAL COSTS FOR MECHANICAL, ELECTRICAL, STRUCTURAL AND ARCHITECTURAL
REVISIONS REQUIRED TO INCORPORATE MATERIALS SUBSTITUTED BY CONTRACTOR SHALL
BE RESPONSIBILITY OF THIS CONTRACTOR. MAKE REVISIONS TO RECORD DRAWINGS
INCORPORATING ALL ALTERNATES AND/OR SUBSTITUTIONS AND ALL RELATED CHANGES.
INSTALL ALL CONCEALED MECHANICAL EQUIPMENT REQUIRING ADJUSTMENT OR
MAINTENANCE IN LOCATIONS EASILY ACCESSIBLE THROUGH ACCESS PANELS AND DOORS.
INSTALL SYSTEMS AND COMPONENTS TO RESULT IN A MINIMUM NUMBER OF ACCESS
PANELS.
PROVIDE ALL ACCESS DOORS IN CEILINGS OR WALLS WHERE SHOWN AND/OR REQUIRED
FOR PROPER SERVICING OF EQUIPMENT. SIZE, FINISH, TYPE, AND FINAL LOCATION TO
COMPLY WITH ARCHITECT/INTERIOR DESIGNER'S APPROVAL. ACCESS DOORS IN RATED
CEILINGS OR WALLS SHALL BE ULC APPROVED FOR THE APPLICATION.
PROVIDE THE OWNER WITH A WRITTEN WARRANTY, FOR ALL LABOUR, MATERIALS, AND
EQUIPMENT IN THIS CONTRACT, FOR A PERIOD OF ONE YEAR COMMENCING AT SUCH TIME
AS THE OWNER, OR THEIR REPRESENTATIVE, DEEMS THE WORK ACCEPTABLE.
TESTING AND COMPLETION OF CONTRACT
THE CONTRACTOR SHALL BE RESPONSIBLE TO TEST AND RUN AND COMMISSION ALL
EQUIPMENT. HIRE AND PAY FOR THE EQUIPMENT MANUFACTURER'S REPRESENTATIVE
TO START-UP ALL EQUIPMENT AND CHECK OUT ALL ASSOCIATED CONTROLS AND SAFETY
CUTOUTS, THIS INCLUDES, THERMOSTATS, OUTDOOR AIR DAMPERS, FIRE STATS,
EXHAUST FAN INTERLOCKS, ETC. THIS WORK SHALL BE COMPLETE AND ANY
DEFICIENCIES RECTIFIED PRIOR TO NOTIFYING THE BALANCING COMPANY THAT THE
SYSTEMS ARE READY TO BE BALANCED.
ALL SYSTEMS SHALL BE COMPLETE, TESTED AND READY FOR USE, WITH ALL EQUIPMENT
AND CONTROLS FUNCTIONING CORRECTLY.
SUBMIT ALL CERTIFICATES OF INSPECTION AND TEST RESULTS TO THE OWNER FOR
REVIEW.
A CLEAN, UNDAMAGED SET OF CONTRACT DRAWINGS INCLUDING COORDINATION
DRAWINGS AND SHOP DRAWINGS SHALL BE KEPT AT THE JOB SITE AS AS-BUILT RECORD
DOCUMENTS. MARK RECORD SETS IN A CLEAR, LEGIBLE MANNER, USING RED INK (NO
PENCILS); TO SHOW THE ACTUAL INSTALLATION, WHERE THE INSTALLATION VARIES
FROM THE WORK AS ORIGINALLY SHOWN. MARK ALL DRAWINGS NECESSARY TO SHOW
CONDITIONS FULLY AND ACCURATELY. GIVE PARTICULAR ATTENTION TO CONCEALED
ELEMENTS THAT WOULD BE DIFFICULT TO MEASURE AND RECORD AT A LATER DATE.
ASSEMBLE TWO (2) MANUALS, EACH CONTAINING DATA SHEETS, BROCHURES,
OPERATING, MAINTENANCE, RECOMMENDED SPARE PARTS, LUBRICATING
INSTRUCTIONS, WRITTEN WARRANTY, REVIEWED AIR AND WATER BALANCING REPORTS,
AND A COMPLETE SET OF REVIEWED SHOP DRAWINGS AND BIND IN HARD
COVER. IDENTIFY COVER “OPERATION AND MAINTENANCE MANUAL”. MANUALS SHALL
BE SEPARATED WITH DIVIDERS IN LOGICAL SECTIONS AND VOLUMES.
PROVIDE A COMPLETE COST BREAKDOWN OF ALL MATERIALS, EQUIPMENT AND LABOUR
COSTS ASSOCIATED WITH EACH SUBMISSION FOR EXTRA OR DELETED WORK.
IDENTIFY EACH PIPED AND DUCTED SERVICE SHOWING NAME AND SERVICE, INCLUDING
TEMPERATURE AND PRESSURE WHERE RELEVANT, AND WITH DIRECTIONAL ARROWS TO
INDICATE FLOW. LOCATE IDENTIFICATION AND FLOW ARROWS NOT MORE THAN 3M (10
FEET) AND AT EACH CHANGE IN THE DIRECTION OF THE PIPE AND AT TAKE-OFFS. USE
WORDING INDICATED ON THE MECHANICAL LEGEND. USE 50MM (2”) HIGH STENCIL
LETTERS.
REUSE EXISTING MATERIALS AND EQUIPMENT WHEREVER POSSIBLE AND PROVIDE NEW
ONLY WHERE REQUIRED AND AS SPECIFIED TO ENSURE A COMPLETE INSTALLATION.
ALL EQUIPMENT, MATERIALS AND ASSOCIATED CONTROLS NOT USED IN THIS CONTRACT
SHALL BE RETURNED TO THE LANDLORD/OWNER.
HVAC DUCTWORK AND FITTINGS
ALL DUCTWORK AND HANGERS SHALL BE FABRICATED IN ACCORDANCE WITH THE
LATEST ASHRAE AND SMACNA RECOMMENDATIONS.
NOTE THAT DIMENSIONS ON DRAWINGS ARE CLEAR INSIDE DIMENSIONS. WHERE
ACOUSTIC INSULATION IS INSTALLED, INCREASE DIMENSIONS ACCORDINGLY.
PROVIDE FLEXIBLE CONNECTORS BETWEEN ALL AIR HANDLING EQUIPMENT AND
ADJACENT DUCTWORK. FLEXIBLE CONNECTIONS SHALL CONSIST OF A
PRE-ASSEMBLED UNIT COMPLETE WITH 75MM (3”) LONG GALVANIZED DUCT
CONNECTOR AND 150MM (6”) WIDE NEOPRENE FLEXIBLE CONNECTOR EQUAL TO
DURO DYNE NEOPRENE.
FLEXIBLE DUCTS SHALL BE FLEXMASTER TRIPLE LOCK MODEL #T/L OR APPROVED
EQUAL, SPIRAL WOUND ALUMINUM STRIP WITH AIR TIGHT AND LEAK-PROOF
TRIPLE LOCK SEAM. DUCTING SHALL CONFORM TO NFPA 90A AND UL-181.
FLEXIBLE DUCTS SHALL BE OF SIZE EQUAL TO DIFFUSER NECK SIZE. DO NOT
RESTRICT DUCT FREE AREA. USE GEAR CLAMPS FOR SECURING FLEXIBLE DUCTS
TO RIGID DUCT CONNECTIONS SUCH AS SPIN-IN FITTINGS, ETC. AND NECKS OF
DIFFUSERS AND SEAL AIR TIGHT WITH DURO-DYNE DUCT SEALER. ROUND
FLEXIBLE DUCTS SHALL BE INSTALLED AS ONE CONTINUOUS PIECE, MAXIMUM
1.5M (5') LONG. REMAINDER SHALL BE ROUND RIGID DUCT. JOINING OF
FLEXIBLE DUCTS IS NOT PERMITTED.
SEAL ALL JOINTS IN SUPPLY, RETURN AND EXHAUST DUCTWORK WITH
DURO-DYNE WATER-BASED HIGH VELOCITY DUCT SEALER OR EQUIVALENT
MEETING REQUIREMENTS OF AUTHORITIES HAVING JURISDICTION AND SMACNA
SEAL CLASS A.
FINAL LOCATION OF NEW SUPPLY AIR DIFFUSERS, BOOTS, LIGHT TROFFERS,
REGISTERS, RETURN AND EXHAUST AIR GRILLES SHALL BE COORDINATED WITH
THE LATEST ARCHITECTURAL AND ELECTRICAL REFLECTED CEILING PLANS.
PROVIDE FIRE DAMPERS WHERE SHOWN ON DRAWING AND/OR WHERE REQUIRED
BY LOCAL AUTHORITIES AND/OR APPLICABLE CODES IN DUCT SECTIONS
COMPLETE WITH APPROVED ACCESS DOORS.
WHERE TRANSFER AND/OR RETURN AIR OPENINGS ARE NOTED ON THE
DRAWINGS (WITHOUT DUCTWORK/DIFFUSERS), THE MECHANICAL CONTRACTOR
IS RESPONSIBLE TO PROVIDE THE LAYOUT TO THE GENERAL TRADES. THIS
CONTRACTOR SHALL CO-ORDINATE AND VERIFY THAT THE REQUIRED NUMBER
AND SIZE OF OPENINGS HAVE BEEN PROVIDED.
PROVIDE NEW BALANCING DAMPERS FOR ALL DUCT BRANCHES, AND IN ALL
LOCATIONS NECESSARY FOR BALANCING THE AIR SYSTEMS, WITH SUITABLE
MEANS OF CEILING ACCESS. PROVIDE VOLUME DAMPERS FOR ALL NEW SUPPLY
AIR DIFFUSERS AND REGISTERS.
TEST, BALANCE AND ADJUST ALL AIR TO OBTAIN THE DESIGN AIR QUANTITIES
AND TEMPERATURE RISES/DROPS ACROSS TERMINAL HEATING/COOLING
ELEMENTS. MARK THE FINAL BALANCE POSITION ON ALL BALANCING DAMPERS
AND ADJUSTABLE AIR TURNING DEVICES AND BALANCE FITTINGS. SUBMIT AIR
SYSTEM TEST AND BALANCE REPORT IN TRIPLICATE TO THE ENGINEER AND
LANDLORD. INDICATE ALL TEST RESULTS INCLUDING COIL ENTERING AND
LEAVING AIR TEMPERATURES, CLOSEST AND FURTHEST OUTLET SUPPLY AIR
TEMPERATURES AND AVERAGE ROOM TEMPERATURES FOR ALL AIR SYSTEMS.
THIS WORK SHALL BE PERFORMED BY A TESTING AND BALANCING CONTRACTOR
WHO IS A MEMBER OF AABC OR NEBB AND APPROVED BY THE LANDLORD, OR
WHEN REQUIRED, BY THE LANDLORD'S TESTING AND BALANCING CONTRACTOR.
IN AREAS WITH DRYWALL CEILINGS, THIS WORK SHALL BE DONE PRIOR TO
ENCLOSING OF CEILING SPACE.
INCLUDE EXTENDED SERVICE OF 90 DAYS, AFTER COMPLETION OF TEST AND
BALANCE WORK, DURING WHICH TIME THE ENGINEER, AT HIS DISCRETION, MAY
REQUEST RE-CHECKING OR RE-SETTING OF ANY SYSTEMS AND/OR EQUIPMENT IN
THE TEST REPORT FOR A MAXIMUM PERIOD OF EIGHT (8) HOURS OF SITE TIME.
ADJUST AND/OR REPLACE EXISTING AIR HANDLING UNIT FAN BELTS, AND
SHEAVES AS REQUIRED TO OBTAIN THE REQUIRED DESIGN SUPPLY AIR
QUANTITIES INDICATED ON PLANS.
MODIFY HVAC DUCTWORK TO SUIT SITE CONDITIONS. MAINTAIN EQUAL CROSS
SECTIONAL AREA AT ALL SECTIONS TO ENSURE DESIRED AIR FLOWS.
HVAC CONTROLS
ALL CONTROLS SHALL BE SUPPLIED AND INSTALLED BY THE MECHANICAL
CONTRACTOR AND APPROVED BY OWNER.
PROVIDE AND INSTALL CONDUIT, WIRE, ELECTRIC RELAYS, CONNECTIONS AND
OTHER DEVICES REQUIRED FOR CONTROL CIRCUIT WIRING, WHETHER LINE
OR LOW VOLTAGE, FOR A COMPLETE AND OPERATING CONTROL SYSTEM. THE
CONTROLS CONTRACTORS SHALL EITHER USE THEIR OWN ELECTRICIANS, OR
USE AN ELECTRICAL SUB-TRADE ACCEPTABLE TO ENGINEER TO SUPPLY AND
INSTALL ALL CONDUIT AND WIRING FOR SYSTEMS AS SPECIFIED.
LOCATIONS OF TEMPERATURE SENSORS ARE INDICATED ON THE DRAWINGS.
MOUNTING HEIGHT OF OCCUPANT ADJUSTABLE THERMOSTATS SHALL BE
1400mm TO 1500mm FROM FINISHED FLOOR. MOUNTING HEIGHT OF
NON-ADJUSTABLE THERMOSTATS SHALL BE 1500 MM [5 FT. 0 IN.] FROM
FINISHED FLOOR. CONFIRM FINAL LOCATIONS WITH THE
ARCHITECT/INTERIOR DESIGNER BEFORE INSTALLATION. AVOID DRAFTS,
STAGNANT AIR, EFFECTS OF OTHER SYSTEMS, OBSTRUCTED LOCATION, AND
LOCATION EXPOSED TO DAMAGE.
SHOP DRAWINGS SHALL INCLUDE A CONTROL DIAGRAM INDICATING HOW
CONTROLS ARE ELECTRICALLY CONNECTED FOR EACH SYSTEM, AND
EQUIPMENT LIST AND MANUFACTURERS DATA SHEETS AND A DESCRIPTION OF
THE CONTROL SEQUENCE FOR EACH SYSTEM.
THE OPERATING AND MAINTENANCE MANUAL SHALL CONTAIN AS BUILT SHOP
DRAWINGS AND OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONTROL
EQUIPMENT.
PLUMBING
INSTALL ALL PIPING IN THE BEST WORKMANLIKE MANNER AND IN ACCORDANCE
WITH THE BEST PRACTICES OF THE TRADE.
PROVIDE ALL BRONZE BALL TYPE ISOLATING VALVES ON MAIN AND/OR BRANCH
LINES AND FOR EACH INDIVIDUAL PIECE OF EQUIPMENT SERVED WITH HOT AND
COLD WATER LINES. ALL VALVES SHALL BE SUITABLE FOR THE OPERATING
PRESSURE OF THE SYSTEM IN WHICH THEY ARE INSTALLED.
PROVIDE DI-ELECTRIC COUPLINGS/UNIONS WHERE COPPER PIPING CONNECTS TO
FERROUS METAL EQUIPMENT SUCH AS STEEL STORAGE TANKS, PRV'S, ETC. AND
STEEL, BLACK IRON, CAST IRON OR GALVANIZED IRON PIPING.
FINAL LOCATION OF ALL NEW PLUMBING FIXTURES SHALL BE COORDINATED ON
SITE WITH ALL TRADES. REFER TO ARCHITECTURAL/INTERIOR DESIGNER
DRAWINGS AND DETAILS FOR EXACT LOCATION OF PLUMBING FIXTURES.
PROVIDE NEW PLUMBING FIXTURES WHERE INDICATED ON PLAN. ALL FIXTURES
SHALL BE OF FIRST QUALITY, BEST GRADE OBTAINABLE, CLEANED AND IN
PERFECT CONDITION FOR THE OWNER TAKEOVER. FIXTURES SHALL BE PIPED
COMPLETE IN A FIRST CLASS MANNER WITH ALL NECESSARY APPURTENANCES
FOR A COMPLETE FIXTURE IN EVERY RESPECT. INSTALL ALL COMPONENTS IN
STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
PROVIDE A TRAP SEAL PRIMER ON ALL NEW FLOOR DRAINS, FUNNEL FLOOR
DRAINS AND HUB DRAINS. FOR INDIVIDUAL OR REMOTE DRAINS, PROVIDE
PRECISION PLUMBING PRODUCTS INC. MODEL PO-500 AUTOMATIC TRAP SEAL
PRIMER VALVE, WITH 12MM (½") NPT (M TO F) CONNECTIONS WITH STRAINER
AND INTEGRAL BACK FLOW PREVENTER AND VACUUM BREAKER. COMPLETE WITH
YS-8 SUPPLY TUBE. FOR INSTALLATIONS WITH LARGE NUMBERS OF TRAPS IN
CLOSE PROXIMITY, PROVIDE ELECTRONIC TRAP PRIMING SYSTEMS EQUIVALENT
TO P.P.P. INC. PRIME-TIME™ ELECTRONIC TRAP PRIMER.
DISCONNECT AND CAP ALL EXISTING DRAIN, VENT, HOT AND COLD WATER PIPES
NOT USED IN THIS CONTRACT AT FLOOR, WALL OR CEILING. PROVIDE NEW
PIPING ONLY WHERE NECESSARY AND REUSE EXISTING WHEREVER POSSIBLE AND
WHERE CONDITIONS PERMIT.
INSULATION - PLUMBING SERVICES
PROVIDE INSULATION MATERIALS WITH A MAXIMUM THERMAL CONDUCTIVITY OF
{0.036 W/M.ºC} [0.25 BTU.IN/(HR.FT2ºF] AT {38ºC} [100ºF] MEAN TEMPERATURE.
COVER ALL DOMESTIC HOT AND COLD WATER, CONDENSATE AND STORM DRAIN
PIPING WITH PRE-MOLDED LOW PRESSURE GLASS FIBER INSULATION. FOR
DOMESTIC COLD WATER, CONDENSATE, AND STORM DRAIN PIPING USE FACTORY
APPLIED PAPER FREE ASJ VAPOUR BARRIER JACKET.
ACCEPTABLE MANUFACTURERS: OWENS CORNING PIPE INSULATION, JOHNS
MANVILLE FIBERGLAS PIPE INSULATION, MANSON FIBERGLAS PIPE INSULATION
OR KNAUF PIPE INSULATION.
INSULATION THICKNESS SHALL BE AS FOLLOWS;
DOMESTIC COLD WATER:ALL PIPE SIZES - 25MM (1”) INSULATION
DOMESTIC HOT WATER: UP TO 1” - 25MM (1”) INSULATION
1” AND LARGER - 40MM (1-1/2”) INSULATION
COVER ALL FITTINGS, VALVES, WATER METERS AND APPURTENANCES CONNECTED
TO HOT AND COLD WATER PIPING AND CONDENSATE DRAIN PIPING WITH
FABRICATED MITERED OR PREFORMED SECTIONS OF SPECIFIED INSULATION OR
ARMAFLEX WITH THICKNESS SHOWN ABOVE. SEAL INSULATION FOR COLD
WATER FITTINGS WITH A VAPOUR BARRIER ADHESIVE AND REINFORCE WITH
GLASS OPEN WEAVE FIBER TAPE AND FINISH SMOOTH WITH A COAT OF MASTIC.
WHERE INSULATED PIPING IS EXPOSED (AREAS WITHOUT CEILINGS,
MECHANICAL/COMPUTER ROOMS, ETC.) PROVIDE PVC JACKET AND FITTING
COVERS INSTALLED AS PER MANUFACTURER'S INSTRUCTIONS, AND CONFORMING
TO THE SPECIFIED FLAME SPREAD/SMOKE DEVELOPED RATING.
WASTE AND VENT PIPING SYSTEMS
CAST IRON SOIL PIPE COMPONENTS:
PIPE: CAST IRON SOIL PIPE TO CAN/CSA-B70.
MECHANICAL JOINT COMPONENTS: HUBLESS FITTINGS, ELASTOMERIC
GASKETS AND STAINLESS STEEL MECHANICAL JOINT COUPLINGS TO
CAN/CSA-B70.
COPPER TUBE COMPONENTS.
PIPE: DWV COPPER TUBE: TO ASTM B306.
JOINT AND FITTING COMPONENTS.
.1 WROUGHT COPPER FITTINGS: TO ANSI B16.29.
.2 CAST COPPER, BRASS AND BRONZE FITTINGS: TO ANSI B16.23.
.3 SOLDER JOINTS: TO ASTM B32.
.4 BRAZED JOINTS: TO ASTM B664.
ABS PIPE COMPONENTS.
PIPE: ABS PLASTIC PIPE: TO CAN/CSA-B181.1.
JOINT AND FITTING COMPONENTS:
.1 FITTINGS: ABS FITTINGS TO CAN/CSA-B181.1.
.2 ABS SOLVENT CEMENT: TO ASTM D2235.
.3 ABS - PVC SOLVENT CEMENT: TO ASTM D3138.
PVC PIPE COMPONENTS:
PIPE: PVC PLASTIC PIPE TO CAN/CSA-B181.2.
.JOINT AND FITTING COMPONENTS:
.1 FITTINGS: PVC FITTINGS TO CAN/CSA-B181.2.
.2 PVC SOLVENT CEMENT: TO ASTM D2564.
.3 ABS-PVC SOLVENT CEMENT: TO ASTM D3138.
ALL DOMESTIC WATER PIPE, JOINTS, AND FITTINGS
.1 ALL PIPES PENETRATING FIRE RATED WALL ASSEMBLIES TO BE
MINIMUM REGULAR COPPER PIPE OR TYPE L COPPER TUBING.
.2 COPPER PIPE: ASTM B42 WITH ASME B16.22 WROUGHT COPPER OR
ASME B16.18 CAST COPPER, BRASS AND BRONZE FITTINGS, ASTM
B32 SOLDER.
.3 COPPER TUBE: ASTM B88 WITH ASME B16.22 WROUGHT COPPER
OR ASME B16.18 CAST COPPER, BRASS AND BRONZE FITTINGS,
ASTM B32 SOLDER.
.4 CPVC SCHEDULE 40 PIPE: ASTM F441/F441M WITH ASTM F438
SOCKET, ASTM F439 SOCKET, OR ASTM F437 THREADED
TYPE FITTINGS.
.5 CPVC SYSTEM: ASTM D2846/D2846M, SDR 11, PIPE OR TUBE AND
SOCKET FITTINGS.
.6 PEX DISTRIBUTION SYSTEM: ASTM F877, SDR 9 TUBING ASTM
F1807, METAL-INSERT TYPE WITH COPPER CRIMP RINGS AND
MATCHING PEX TUBE DIMENSIONS.
.7 PROVIDE AND INSTALL PEX TUBING EQUIVALENT TO 'Wirsbo hePEX'
TUBING COMPLETE WITH OXYGEN DIFFUSION BARRIER AND
INSTALLED AS PER CAN/CSA-137.5 STANDARD.
.8 ACR COPPER: ASTM B280.
.9 DWV COPPER: ASTM B306.
JOINTS AND FITTINGS:
.1 WROUGHT COPPER FITTINGS: ASME B16.22.
.2 CAST COPPER, BRASS AND BRONZE FITTINGS: ASME B16.18.
.3 SOLDER JOINTS: ASTM B32.
INSTALL ALL GAS APPLIANCES AND PIPING IN ACCORDANCE WITH
CSAB149.1 NATRUAL GAS AND PROPANE INSTALLATION CODE.
INSTALL ALL GAS APPLIANCES IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS
GAS APPLIANCES/PIPING
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
MECHANICALSPECIFICATIONS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
M4
N
UP
EXISTING LIGHT TO BE
REMOVED
EXISTING LIGHT TO BE
REMOVED
EXISTING LIGHT TO BE
REMOVED
EXISTING LIGHT TO BE
REMOVED
EXISTING SECURITY CAMERA.
RELOCATE TO CLEAR HEIGHT OF
NEW MAINTENANCE SHOP.
EXISTING SECURITY CAMERA TO BE
RELOCATED
SERVICE SWITCH TO BE REMOVED
METERING CABINET TO BE REMOVED
X
X X
E
5a
-3 -2
C0
C4
A
F
Ex
1 2 3
65
D1
A1
10
4
4b4a
B
E
97b
6a
1a
C1
8
C3
8x
Dy
7a 7bb
6
Ey
E
D
C
B
A
98
7654321
MM
RELOCATE POWER SUPPLY
FOR MOTORIZED DAMPER
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
EXISTING/DEMOELECTRICAL LAYOUT
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
ED1
N
EXISTING/DEMO ELECTRICAL LAYOUT
SCALE:
3
32
"=1'-0"
UP
SOUTH ADDITION
MAINTENANCE SHOP
NORTH
ADDITION
DN
DN
22 2
222
22 2
22
2 2
2 2
2 2 2
2
2
8
8
8
8
X
X X
X
4 4 44
4
444
SUB2-6
SUB2-6
SUB2-6
SUB2-6
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-7,9
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB1-11,13
SUB2-4
SUB2-4
SUB2-4
PP2-10 PP2-10
PP1-8,10PP1-8,10PP1-8,10
PP1-8,10 PP1-8,10 PP1-8,10PP1-8,10
PP1-8,10
MAINTENANCE SPOT LIGHTS. COORDINATE
EXACT LOCATIONS WITH GMI.
A7
A7
A13
A13
NOTE: EXTEND EXISTING LIGHTING
CIRCUITS TO NORTH ADDITION
5 5
5
7
A-14
6
1
7
A-12
7
A-12
7
A-12
6
7
A-14
1
7
A-14
1
1
6
E
5a
D3
-3 -2-4
C0
C4
A
F
Ex
1
-5
G
2 3
1B
65
D1
A1
10
4
-5
1a-2-3-4
G
F
Ex
D2
C2
A1
4b4a
B
E
97b
6a
1a
C1
8
C3
8x
Dy
7a 7bb
6
Ey
E
D
C
B
A
98
7654321
7
7
A-12
A-12
3
SUB2-11,13
SUB1-11,13
X
SUB2-6
1
1 2 3 4
A
B
3 3 3 3 3
3 3 3 3 3
3 3 3 3 3
3 3 3 3 3
6
6
TP1-8
TP1-8
7
TP1-1,3
7
TP1-1,3
7
TP1-1,3
7
TP1-1,3
TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6
TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6
TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6
TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6 TP1-4,6
NOTE: BUILDING EXTERIOR LIGHTING TO
BE POWERED FROM EXISTING PANEL A
CIRCUITS AS IDENTIFIED ON DRAWING.
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
NEW LIGHTINGLAYOUT
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E1
N
MAIN BUILDING LIGHTING LAYOUT
SCALE:
1
16
"=1'-0"
DRIVE THROUGH SHELTER LIGHTING LAYOUT
SCALE:
1
16
"=1'-0"
UP
SOUTH ADDITION
MAINTENANCE SHOP
NORTH
ADDITION
DN
DN
20A MAINTENANCE
RECEPTACLE.
TYPICAL.
NOTES:
1. RECEPTACLES IN NORTH AND SOUTH ADDITIONS ARE
TO BE MOUNTED 3' A.F.F. UNLESS NOTED OTHERWISE.
2. LIGHTING CONTROLS, FAN CONTROLS, AND GAS
DETECTION CONTROLLER TO BE LOCATED NEXT TO SUB
PANELS.
120V SUBPANEL-SUB 2
600V SUBPANEL-SUB 1
BALER CONTROL PANEL
RUN CONDUIT
THROUGH WALL
RUN CONDUIT
THROUGH WALL
RUN CONDUIT UP WALL AND
ABOVE DOOR OPERATORS
DOOR OPENER
SUB2-8,10,12
DOOR OPENER
DOOR
OPENER
SUB2-8
SUB2-2,4,6
SUB2-1
SUB2-1
SUB2-1
SUB2-1
SUB1-1,3,5
SUB2-1
SUB2-2
SP-1
SUB2-1
SUB2-3
CONTRACTOR TO CONNECT TO
NEAREST RECEPTACLE CIRCUIT
M
MM
SUB2-5,7,9
EF-1
SUB2-5,7,9
EF-1
SUB2-8
SUB2-8
E
5a
D3
-3 -2-4
C0
C4
A
F
Ex
1
-5
G
2 3
1B
65
D1
A1
10
4
-5
1a-2-3-4
G
F
Ex
D2
C2
A1
4b4a
B
E
97b
6a
1a
C1
8
C3
8x
Dy
7a 7bb
6
Ey
E
D
C
B
A
98
7654321
SUB2-12
EBB.1
SUB2-10
RUN CONDUIT AND CONNECT
TO EXISTING SERVICE
GAS DETECTION PANEL
SUB2-14,16,18
WELD RECP.
CONNECT NEW SERVICE TO
EXISTING SPLITTER
1
NOTES:
1. RECEPTACLES IN NORTH AND SOUTH ADDITIONS ARE
TO BE MOUNTED 3' A.F.F. UNLESS NOTED OTHERWISE.
2. LIGHTING CONTROLS, FAN CONTROLS, AND GAS
DETECTION CONTROLLER TO BE LOCATED NEXT TO SUB
PANELS.
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
MAIN BUILDING POWER LAYOUT
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E2
N
MAIN BUILDING POWER LAYOUT
SCALE:
1
16
"=1'-0"
PP2
120/208V
PANEL
PP1
347/600V
PANEL
45KVA
TRANSFORMER
600A SPLITTER
100A
DISCONNECT
300A
DISCONNECT
NEW 400A DISCONNECT
IN EXISTING BUILDING
TO BALER
TO EXISTING SPLITTER
IN EXISTING BUILDING
METER
CABINET
MAIN 600A
SERVICE ENTRANCE
SWITCH
TO 120V
SUB PANEL
TO 600V
SUB PANEL
60A
DISCONNECT
1
SEE NEW ELECTRICAL
ROOM LAYOUT DETAILS
MAINTENANCE SHOP
208V AIR
COMPRESSOR
BAND SAWTABLE SAWDRILL PRESS
20A FUTURE TOOLS
WELD REC.
MOUNTED @ WORK
BENCH HEIGHT
MOUNTED @ WORK
BENCH HEIGHT
EF-2
AC.1
F.1
PP2-7 PP2-8 PP2-5 PP2-3 PP2-1
PP2-9,11,13
PP2-6 PP2-6 PP2-6 PP2-6 PP2-6
PP2-6
EF-3
PP2-25
PP2-26
HWT-1 ABOVE
PP2-16
M
PP2-14
PP2-12
PP2-2,4
HRV.1
PP2-24
SP-2
PP2-22
PP2-21,23
PP1-2,4,6
HT.1
1
EyEy
4a4a
4b4b
66a6a 6
1 2 3 4
A
B
TP1
120/208V PANEL
TP1-2 TP1-2
TP1-2 TP1-2
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
TRAILER/MAINTENANCE AREA
POWER LAYOUTS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E3
N
NEW ELECTRICAL LAYOUT
SCALE: N.T.S.
MAINTENANCE SHOP POWER LAYOUT
SCALE:
1
4
"=1'-0"
DRIVE THROUGH SHELTER POWER LAYOUT
SCALE:
1
16
"=1'-0"
SAND
GRADE LEVEL
75m
m75m
m
900m
m
190mm
WARNING TAPE
450m
m
190mm 190mm 190mm 190mm
A BC C
B A N
190mm
N
190mm
1
SAND
CABLE
FINISHED FLOOR
75m
m75m
m
900m
m
300m
m
CONDUIT WITH
BELL END
TP1
120/208 PANEL
PROPOSED
ADDITION
F.F.E. = 299.25
PROPOSED
ADDITION
F.F.E. = 299.25
EXISTING GMI BUILDING
F.F.E. = 299.25
EXISTING GMI OFFICE
PROPOSED
ADDITION
F.F.E. = 299.25
(MATCH EXISTING)
PROPOSED
DRIVE THROUGH
SHELTER
LOADING
DOCK
TRENCH TO SHELTER
SEE NOTE 6
SEE NOTE 5
ENTRANCE SWITCH
TRENCH TO NEW ELECTRICAL ROOM.
SEE DETAIL 1.
NEW 750 KVA TRANSFORMER
EXISTING SERVICE TO OFFICE BUILDING.
DISCONNECT FROM EXISTING TRANSFORMER
AND CONNECT TO NEW TRANSFORMER.
PANEL C
LAMP POST
CARD READER
RELOCATE EXISTING
LIGHT AND CARD READER
NOTES:
1. UNLESS OTHERWISE NOTED, DIRECTLY BURIED CABLES SHALL BE INSTALLED TO MEET MINIMUM
COVER REQUIREMENTS OF 900mm FROM THE TOP OF THE CABLE TO THE FINISHED GRADE.
2. BACKFILL CONTAINING LARGE ROCK, PAVING MATERIAL, CINDERS, LARGE OR SHARPLY ANGULAR
SUBSTANCES, OR CORROSIVE MATERIAL SHALL NOT BE USED IN THE CABLE TRENCH.
3. SUITABLE MARKING TAPE SHALL BE BURIED DIRECTLY ABOVE THE CABLE(S) AND AT AN
APPROXIMATE DEPTH HALFWAY BETWEEN THE SABLE(S) AND THE FINISHED GRADE.
4. CABLES ENTERING THROUGH THE FINISHED FLOOR REQUIRE A BELL END CONDUIT TERMINATING
300mm ABOVE THE TRENCH FLOOR. SEE DETAIL 2.
5. RUN CABLE FROM PANEL TO ROOF. CONTRACTOR IS TO DETERMINE BEST ROUTING FOR CABLE
ALONG THE ROOF TO THE CORNER OF THE ADDITION AND BACK DOWN TO TRENCH.
6. DIRECT BURY CABLE IN TRENCH AS PER DETAIL 3.
NOTES:
1. RELOCATE LAMP POST AND CARD READER TO LOCATION SHOWN.
2. EXTEND TRENCH AND WIRING TO NEW LOCATIONS.
3. SEE DRAWING P5 FOR CONCRETE WORK.
SAND
GRADE LEVEL
900m
m
WARNING TAPE
450m
m
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
SITE LAYOUT ANDTRENCHING DETAILS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E4
N
DETAIL 1 (2 WIRES PER PHASE)
DETAIL 2 (CABLE ENTERING THROUGH FINISHED FLOOR)
SITE ELECTRICAL PLAN
SCALE: N.T.S.
DETAIL 3
ELECTRICAL LIGHTING SCHEDULE
INDEX MANUFACTURER
LUMINAIRE
TYPE
ITEM NUMBER
STELLA UNIBODY RUNNING
MAN COMBO EXIT AND
SAFETY LIGHT
BEGHELLI CANADA
SLU-RM-6-80-L-1-
OLR-C-BTMR2-5W
-
LUMINOUS
FLUX
120V
VOLTAGE
5
QUANTITY
1
CONNECTED
LOAD
2 W
FBX HIGHBAY 8-2LINEP
2.62L5 4000K BOARDS
4-95W DRIVERS 5.1K
RESISTORS NO OPTICS OPEN
PHILIPS FBX36LL40-347 37102 lm 347V 202 255.5 W
INSTALLATION
WALL MOUNT
ABOVE DOOR
SUSPENDED
39' AFF
PHILIPS 4' VAPORLUME
2-LP3.2.1 4000K BOARDS
95W DRIVER 1.37K
RESISTOR
PHILIPS
DWAE51LH840-4-
UNV
5186 lm 208V 213 47.4 W
SHELTER TENT -
SURFACE MOUNT
ON PURLINS
VALVE ROOM -
SURFACE MOUNT
4' LBX 2-2LP 1.0 4000K
BOARDS 75W DRIVER 9.1K
RESISTOR
PHILIPS LBX70L840-347 7904 lm 347V 84 53.4 W
SUSPENDED
12' AFF
GARDCO FLOODLIGHT
PHILIPS
FX2-128-G2-T-A-
RM-N-A-3-N-N
16204 lm 120V 3
5
139 W
WALL MOUNT
12' AFF
ECCO LUNA LED EMERGENCY
LIGHT
BEGHELLI CANADA
CO1A-10W-205L-
EO-120/277/347
- 120V 6
6
-
WALL MOUNT
12' AFF
FLOOD LIGHT WITH PHOTO
CELL
ECO POWER
FLF-G2-80W-CW-
V4-B002
8590 lm 208V 12
7
78.9 W
SURFACE MOUNT
22' AFF
FBX HIGHBAY 8-2LINEP
2.62L5 4000K BOARDS
4-95W DRIVERS 5.1K
RESISTORS NO OPTICS OPEN
PHILIPS FBX36LL40-347 37102 lm 347V 48 255.5 W
SUSPENDED
45' AFF
1
ELECTRICAL LEGEND
120V RECEPTACLE
COMBINATION EXIT SIGN/EMERGENCY LIGHTING UNIT
EXTERIOR LIGHT FIXTURE
ELECTRIC MOTORS OR MOTORIZED EQUIPMENT
2' x 4' CEILING LIGHT FIXTURE
X
6" x 4' CEILING LIGHT FIXTURE
WELD OUTLET
ELECTRIC DISCONNECT
EMERGENCY LIGHTING UNIT
PANEL - CIRCUIT NUMBERPC-#
MOTORIZED DAMPERMD
750KVA
PAD-MOUNTED TRANSFORMER
ISC = 15.5 KA
600A, 600V
SERVICE ENTERING SWITCH
NEW METERING CABINET AS PER
HYDRO ONE SPECIFICATIONS
100A, 600V
DISCONNECT
300A, 600V
DISCONNECT
SCRAP BALER
347/600V PANEL
3PH 4 WIRE
100A MAIN DISCONNECT
45KVA
347/600V PRIMARY
120/208 SECONDARY
3 PHASE 4 WIRE
SUB 2
120/208V
3 PHASE 4 WIRE PANEL
100A MAIN DISCONNECT
A
B
E
E
C
D
D
F
G
B
A) 2x PARALLEL RUNS OF 600 MCM AI RWU90 (SEE DETAIL 1 PAGE E4)
B) 2x PARALLEL RUNS OF 400 MCM CU R90 78mm CONDUIT
C) 2x PARALLEL RUNS OF 4/0 AWG CU 63mm CONDUIT
D) 2 AWG CU R90 41mm CONDUIT
E) 400 MCM CU R90 78mm CONDUIT
F) 8 AWG CU R90 27mm CONDUIT
G) 1 AWG CU R90 41mm CONDUIT
600A 347/600V SPLITTER
400A, 600V
DISCONNECT
C
TO EXISTING SPLITTER
IN EXISTING BUILDING
60A, 600V
DISCONNECT
SUB 1
347-600V
3 PHASE 4 WIRE
100A MAIN DISCONNECT
GROUND INCOMING SERVICE AS
PER OESC 10-204.
PROVIDE GROUND ELECTRODES
AS PER OESC 10-700 AND #3/0
CU GROUND CONDUCTORS TO
GROUND INCOMING SERVICE.
DO NOT RELY ON THE WATER
MAIN FOR A GROUND.
1
1
2
4
1
3
PANEL SCHEDULE
EXTERIOR LIGHTS
15 A
PANEL NAME: TP1
VOLTAGE: 120/208V
MAINS AMP: 100 A
A B C
RECEPTACLES
15 A
65
8
10
7
9
1211
14
16
13
15
1817
NOTES:
1. PANEL REQUIRES INGRESS
PROTECTION IP44.
2. CONTRACTOR TO FEED PANEL TP1
FOR AVAILABLE CIRCUIT IN PANEL C.
15 A
15 A
EMERGENCY LIGHTS
BAY LIGHTS
2
4
1
3
PANEL SCHEDULE
BAND SAW
20 A
PANEL NAME: PP2
VOLTAGE: 120/208V
MAINS AMP: 125 A
A B C
HVAC
25 A
20 A
BENCH RECEPTACLES
15 A
65
20 A
8
10
7
9
1211
14
16
13
15
1817
20
22
19
21
2423
26
28
25
27
3029
32
34
31
33
3635
38
40
37
39
4241
TABLE SAW
DRILL PRESS
FUTURE TOOL
20 A
20 A
WELD RECP.
50 A
SUB PANEL
FUTURE TOOL
20 A
EMERGENCY LIGHTS
15 A
FURNACE
15 A
INTAKE LOUVER
15 A
WATER HEATER
20 A
EXTERIOR LIGHTS
15 A
20 A
HEAT TRACE
SUMP PUMP
15 A
HEAT RECOVERY UNIT
15 A
EXHAUST FAN 3
15 A
EXHAUST FAN 4
15 A
2
4
1
3
PANEL SCHEDULE
50 A
PANEL NAME: PP1
VOLTAGE: 347/600V
MAINS AMP: 100 A
A B C
30 A
AIR COMPRESSOR
65
8
10
7
9
1211
14
16
13
15
1817
SUB PANEL
15 A
LIGHTS
1
2
4
1
3
PANEL SCHEDULE
PANEL NAME: SUB 1
VOLTAGE: 347/600V
MAINS AMP: 100 A
A B C
DOOR OPERATOR
65
8
10
7
9
1211
14
16
13
15
1817
20
22
19
21
2423
DOOR OPERATOR
LIGHT BANK 1
LIGHT BANK 2 DOOR OPERATOR
15 A
15 A
2
4
1
3
PANEL SCHEDULE
RECEPTACLES
15 A
PANEL NAME: SUB 2
VOLTAGE: 120/208V
MAINS AMP: 100 A
A B C
SUMP PUMP
15 A
20 A
MAINTENANCE FLOODS
15 A
65
8
10
7
9
1211
14
16
13
15
1817
20
22
19
21
2423
MAINTENANCE RECP.
EXIT AND EMERG. LIGHTS
15 A20 A
EXHAUST FANS DAMPER MOTORS
15 A
BASE BOARD HEATER
15 A
GAS DETECTORS
15 A15 A
VALVE ROOM LIGHT
20 A
WELD RECP.
EXISTING PANEL C
30A BREAKER
CONTRACTOR TO DETERMINE
AVAILABLE CIRCUIT
PANEL TP1
10 AWG CU 21mm
CONDUIT UNTIL TRENCH
THEN DIRECT BURY
X MD
MOTORIZED
DAMPER
X
EF
EF
EF1
EF2
CONTACTOR
120V, 15A
CONTACTOR
208V, 20A
CONTROL
PANEL
GAS MONITORING
SYSTEM
NOTES:
1. A CONTROL PANEL IS TO BE SUPPLIED. THIS PANEL SHALL ALLOW
FOR MANUAL OPERATION OF EF-1 AND EF-2 INDEPENDENTLY.
2. ACTUATION OF ANY OR ALL OF THE EXHAUST FANS SHALL OPEN
THE INTAKE LOUVERS.
3. OPERATING LIGHTS SHALL INDICATE IF FANS ARE OPERATIONAL.
4. ALARM FROM GAS MONITORING SYSTEM SHALL OVERRIDE ANY
MANUAL SETTINGS AND ACTUATE BOTH FANS.
120V
C
N
BANK 1 BANK 2 N
2 POLE LIGHTING CONTACTOR IN
GENERAL PURPOSE ENCLOSURE
30A, 347V c/w 120V COIL.
ALLEN BRADLEY OR EQUIVALENT.
TAG
HT.1
MODEL
ELECTRICAL EQUIPMENT SCHEDULE
MOCP (AMPS)
DESCRIPTION MAKE VOLTAGE
POWER AND THERMOSTAT CONTROLLER CHROMALOX UBC
208/1/60
20
NOTE: HT.1 WILL POWER CHROMOLOX SRF 5-2C CABLE. TO BE INSTALLED AS PER MANUFACTURERS INSTRUCTIONS.
1
HVAC EQUIPMENT SCHEDULE
TAG ID DESCRIPTION MAKE MODEL
AIR FLOW
(CFM)
HEATING
INPUT
COOLING
CAPACITY
VOLTAGE
UNIT WEIGHT
kg (lbs)
REMARKS
F.1 NEW FURNACE GOODMAN GMS800603AN 1200 60 MBH
115/1/60
HEATING
OUTPUT
-48 MBH
40 (88)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.
MCA (AMPS) MOCP (AMPS)
154.8
HRV.1 HEAT RECOVERY VENTILATOR LIFEBREATH 195 DCS 216 -
120/1/60
--
40 (88)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.151.5
AC.1 AIR CONDITIONER GOODMAN GSX130301 - -
208/1/60
27 MBH-
52.3 (115)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.2516.7
CC.1 COOLING COIL GOODMAN CHPF2430B6 - - -27 MBH-
25 (55)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.--
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
EBB.1 ELECTRIC BASEBOARD HEATER OUELLET OPR1002 - -
120/1/60
-1000 W
11.8 (26)
INSTALL AS PER MANUFACTURER'S INSTRUCTIONS.15-
HEIGHTUNIT#
HWT.1
CAPACITY
WATER HEATER SCHEDULE
INPUT (kW)
MAKE MODEL # DIAMETER SHIPPING WEIGHTTYPE
A.O.SMITH EJC-6 6 USG ELECTRIC 1650 15.25" 14.25" 35 lbs
WEIGHT W/ WATER
~85 lbs
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
EXHAUST FAN SCHEDULE
EF-1,2
WALL MOUNTED EXHAUST FAN
FAN # DESCRIPTION MAKE MODEL
AIR FLOW
(CFM)
STATIC
PRESSURE
FAN MOTOR
kW (HP)
VOLTAGE
UNIT WEIGHT
kg (lbs)
GREENHECK AER-E36C-310-A 18000
2.87 (3.85)
0.4 in wc
208/60/3 72.7 (160)
FLA
16.7
EF-3 ROOF MOUNTED EXHAUST FAN GREENHECK GB-161 1800
0.142 (0.19)
0.2 in wc
120/1/6028.6 (63)
5.8
EF-4 ROOF MOUNTED EXHAUST FAN GREENHECK G-090-E 300
0.015 (0.02)
0.2 in wc
120/1/60 11.8 (26)
-
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
PUMP SCHEDULE - ELECTRICAL
TAG # DESCRIPTION MAKE MODEL # MOTOR
SUBMERSIBLE WASTE
WATER SUMP PUMP
SP-1
HEAD
Meters (Feet)
FLOW
L/s (gpm)
ZOELLER 49
1/4hp (0.19 kW) 3 (10) 1.6 (25)
MCA (AMPS) MOCP (AMPS)VOLTAGE
120/1/60
4.0 15
REMARKS
INSTALL PER MANUFACTURERS INSTALLATION
INSTRUCTIONS
PREASSEMBLED WASTE
WATER SUMP PUMP SYSTEM
SP-2 ZOELLER 900-0002
3/10hp (0.22 kW) 3 (10) 2.2 (35)120/1/60
9.7 15
INSTALL PER MANUFACTURERS INSTALLATION
INSTRUCTIONS
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
LOUVERS & DAMPERS SCHEDULE
MOTORIZED DAMPER
TAG ID DESCRIPTION SIZE MAKE REMARKS
TAMCO
MODEL
SERIES 1000
BELIMO DAMPER MOTOR & ALL CONTROLS
MOTOR ELECTRICAL: 120/1/60, END SWITCHES
TO SUIT LOUVER
& EXHAUST FAN
MD-1, 2, 3
NOTE: EQUIPMENT OF EQUAL PERFORMANCE IS ACCEPTABLE
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
ELECTRICAL LEGENDS,SCHEDULES AND
DETAILS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E5
N
ELECTRICAL POWER LAYOUT AND WIRE DETAILS
DRIVE THROUGH SHELTER
SINGLE LINE DIAGRAM
VENTILATION CONTROLS
INTERIOR LIGHTING CONTROL DIAGRAM
PART 1 : GENERAL REQUIREMENTS
1. REQUIREMENTS INCLUDED
1. THE GENERAL REQUIREMENTS, DIVISION 01 AND ANY SUPPLEMENTARY GENERAL CONDITIONS
OF THE CONTRACT SHALL FORM A PART OF THIS SPECIFIFICATION. THE REQUIREMENTS OF
THIS SECTION APPLY TO ALL SECTIONS OF THIS SPECIFICATION.
2. THE DRAWINGS AND SPECIFICATIONS COMPLIMENT EACH OTHER AND TOGETHER STIPULATE
THE CONTRACT REQUIREMENTS. THE MORE RESTRICTIVE CONDITIONS APPLY WHEN
INTERPRETING DISCREPANCIES BETWEEN THE DRAWINGS AND SPECIFICATIONS.
3. FULLY UNDERSTAND THE INTENT AND FUNCTION OF THE SYSTEMS DESCRIBED IN THIS
SPECIFICATION. ALL ELECTRICAL SYSTEMS COVERED UNDER DIVISION 16 SHALL BE FULLY
COMPLETE, TESTED, OPERABLE AND READY FOR OWNER'S USE. USE THE INFORMATION
CONTAINED IN THE RELEVANT DRAWINGS AND/OR SPECIFICATION SECTIONS SUPPLEMENTED
WITH DATE CONTAINED WITHIN OTHER SPECIFICATION SECTIONS OR PROVIDED BY
EQUIPMENT SUPPLIERS OR OTHER SUB-CONTRACTORS. NO EXTRA WILL BE ALLOWED IN ORDER
TO COMPLETE SYSTEMS INADEQUATELY INSTALLED OR NOT FULLY OPERATIONAL.
2. WORK INCLUDED1. PROVIDE ALL LABOUR, MATERIAL, EQUIPMENT, TOOLS AND TRANSPORTATION FOR THE SUPPLY
AND INSTALLATION OF COMPLETE ELECTRICAL SYSTEMS AS SHOWN ON THE DRAWINGS,
SPECIFIED HEREIN OR AS REASONABLY INFERABLE FROM EITHER.
3.REFERENCES1. PROVIDE MATERIAL CONFORMING TO THE MOST UP-TO-DATE CSA AND/OR ULC REQUIREMENTS.
2. REGULATORY AGENCIES:
1. ELECTRICAL SAFETY AUTHORITY
4. WORKMANSHIP1. ONLY FIRST-CLASS WORKMANSHIP PERFORMED BY QUALIFIED TRADE-PERSONS WILL BE
ACCEPTED. NOT ONLY WITH REGARDS TO SAFETY AND DURABILITY BUT ALSO IN TERMS OF
ACCESSIBILITY AND NEATNESS OF DETAIL. UNSATISFACTORY WORKMANSHIP SHALL BE
CORRECTED AT THE CONTRACTOR'S EXPENSE.
2. EMPLOY SPECIALIZED LABOUR AS REQUIRED FOR THE INSTALLATION, TESTING AND/OR
COMMISSIONING OF SPECIFIC SYSTEMS TO ENSURE PROPER OPERATION.
3. THE CONTRACTOR IS RESPONSIBLE FOR ALL DAMAGES RESULTING FROM THE EXECUTION OF
THIS WORK.
5.DRAWINGS1. THE DRAWINGS ARE INTENDED TO BE DIAGRAMMATIC AND INDICATE THE GENERAL
ARRANGEMENT OF EQUIPMENT ONLY. NOT ALL BUILDING ELEMENTS ARE SHOWN. DO NOT
SCALE THE DRAWINGS OR USE FOR FABRICATION PURPOSES.
2. MAKE USE OF ALL AVAILABLE DOCUMENTATION, PRIOR TO TENDER, IN ORDER TO DETERMINE
THE SCOPE OF WORK. NO CONCESSION SHALL BE MADE FOR FAILURE TO MAKE USE OF THE
COMPLETE PACKAGE OF DRAWINGS AND SPECIFICATIONS MADE AVAILABLE DURING THE
TENDER PERIOD.
3. MAKE ALLOWANCES FOR SITE CONDITIONS AND CO-ORDINATION WITH OTHER TRADES.
6.RECORD DRAWINGS1. ONE SET OF PRINTS SHALL BE MAINTAINED IN GOOD CONDITION ON THE JOB-SITE AND BE
MARKED WITH RED INK TO INDICATE DEVIATIONS MADE FROM THE ORIGINAL, TENDERED
DRAWINGS. THESE DRAWINGS SHALL BE LABELLED “AS BUILT” AND SUBMITTED TO THE
ENGINEER PRIOR TO FINAL INSPECTION.
7. SHOP DRAWINGS1. SUBMIT SHOP DRAWINGS FOR EQUIPMENT AS INDICATED IN THE INDIVIDUAL SPECIFICATION
SECTIONS. DO NOT ORDER EQUIPMENT PRIOR TO RECEIPT OF APPROVED SHOP DRAWINGS.
2. SHOP DRAWINGS SHALL CONTAIN THE FOLLOWING INFORMATION:
1. EQUIPMENT DESIGNATION FROM DRAWINGS (E.G. POWER PANEL 'A', LIGHT FIXTURE 'BB').
2. GENERAL CONTRACTOR AND ELECTRICAL SUBCONTRACTOR'S REVIEW STAMP.
3. MANUFACTURER AND CATALOGUE OR MODEL NUMBER.
4. EQUIPMENT RATINGS, DIMENSIONS AND WEIGHT.
5. THE ENGINEER'S REVIEW OF SHOP DRAWINGS IS TO ENSURE GENERAL CONFORMITY WITH THE
INTERNET OF THE DESIGN. THE ELECTRICAL SUB-CONTRACTOR BEARS FULL RESPONSIBILITY
FOR ACTUAL EQUIPMENT DESIGN, QUALITY, FUNCTION, CODE COMPLIANCE AND INSTALLATION.
8.PERMITS AND FEES1. OBTAIN AND PAY FOR ALL PERMITS REQUIRED FOR THE EXECUTION OF THE WORK GOVERNED
BY THIS SPECIFICATION.
2. CHARGES OR FEES TO LOCAL UTILITIES IN CONJUNCTION WITH THEIR WORK ASSOCIATED
WITH THE PROJECT WILL BE PAID DIRECTLY BY THE OWNER. PROVIDE TO THE UTILITIES ANY
INFORMATION THEY REQUIRE IN ORDER TO DETERMINE THEIR SCOPE OF WORK.
3. UPON COMPLETION OF THE WORK PROVIDE AN UNCONDITIONAL CERTIFICATE OF ACCEPTANCE
FROM ONTARIO ELECTRICAL SAFETY AUTHORITY.
9.RULES AND REGULATIONS1. ENSURE THAT THE INSTALLATION CONFORMS TO ALL REQUIREMENTS OF THE MOST CURRENT
ONTARIO ELECTRICAL SAFETY CODE AND BULLETINS, ONTARIO BUILDING CODE, CSA
STANDARDS, ONTARIO FIRE CODE AND/OR ANY OTHER APPLICABLE MUNICIPAL OR PROVINCIAL
REGULATION.
2. THE DRAWINGS SHOW THE MINIMUM STANDARD ACCEPTABLE REGARDLESS OF ANY LESSER
STANDARD SET BY APPLICABLE CODE OR REGULATION.
10. INSPECTION1. THE WORK SHALL BE AVAILABLE FOR INSPECTION BY THE ENGINEER AT ANY TIME.
2. IF WORK IS DETERMINED TO BE UNACCEPTABLE IN TERMS OF THESE SPECIFICATIONS, THE
CONTRACTOR SHALL TAKE IMMEDIATE MEASURES TO CORRECT THE DEFICIENCY.
3. INFORM THE ENGINEER WHEN THE WORK IS READY FOR FINAL INSPECTION. DEFECTS SHALL BE
MADE GOOD BEFORE FINAL PAYMENT IS AUTHORIZED.
11. ABBREVIATIONS AND DEFINITIONS1. WHEREVER WORDS SUCH
AS “APPROVED”, “SATISFACTORY”, “DIRECTED”, “PERMITTED”, “REQUIRED” OR SIMILAR
PHRASES ARE USED IN THIS SPECIFICATION IT SHALL BE IMPLIED THAT THE
WORDS “BY (TO) THE ENGINEER” FOLLOWS.
2. WHEREVER THE WORD “PROVIDE” IS USED IT SHALL BE UNDERSTOOD THAT IT IS EQUIVALENT
TO “FURNISH AND INSTALL”, COMPLETE AND IN PLACE, INCLUDING
ACCESSORIES, FINISHES, TESTS AND SERVICES TO RENDER ITEM SO SPECIFIED COMPLETE
READY FOR USE.
3. WHEREVER THE WORD “FURNISH” IS USED IT MEANS PROCUREMENT OF FABRICATION OF
MATERIALS, EQUIPMENT, OR COMPONENTS, OR PERFORMANCE OF SERVICES TO EXTENT
SPECIFIED AND SHOWN. WHERE USED WITH RESPECT TO MATERIALS, EQUIPMENT, OR
COMPONENTS, THE TERM INCLUDES CRATING AND DELIVERY TO PROJECT SITE BUT IS NOT
INTENDED TO INCLUDE INSTALLATION OF ITEM, EITHER TEMPORARY OR FINAL.
4. WHEREVER THE WORD “INSTALL” IS USED IT MEANS PLACEMENT OF MATERIALS, OR
COMPONENTS, INCLUDING RECEIVING, UNLOADING, TRANSPORTING, STORAGE, UNCRATING
AND INSTALLING AND PERFORMANCE OF SUCH TESTING AND FINISH WORK AS IS COMPATIBLE
WITH THE DEGREE OF INSTALLATION SPECIFIED.
1. ABBREVIATIONS COMMONLY USED ON THE DRAWINGS ARE LISTED BELOW:
1/2/3P SINGLE, DOUBLE OR THREE POLE
A AMPS/AMPERAGE
B/F BARRIER FREE
C CONDUIT
CSA CANADIAN STANDARDS ASSOCIATION
DP DISTRIBUTION PANEL
ESA ELECTRICAL SAFETY AUTHORITY
FHP FRACTIONAL HOSE POWER
MH MOUNTING HEIGHT
NBC NATIONAL BUILDING CODE
OBC ONTARIO BUILDING CODE
OESC ONTARIO ELECTRICAL SAFETY CODE
SN SOLID NEUTRAL
SWBRD SWITCHBOARD
ULC UNDERWRITER'S LABORITORIES OF CANADA
W WATTS/WATTAGE
WP WEATHERPROOF
WM WALL MOUNTED
V VOLTS/VOLTAGE
XFRMR TRANSFORMER
PART 2: PRODUCTS1. MATERIALS AND EQUIPMENT1. MATERIALS TO BE NEW AND CSA/ULC APPROVED.
2. MATERIALS AND EQUIPMENT SPECIFIED BY TECHNICAL DESCRIPTION ONLY SHALL BE
OF THE BEST QUALITY ATTAINABLE FOR APPLICATION.
3. USE THE SAME MANUFACTURER, TYPE AND STYLE OF EQUIPMENT FOR PARTICULAR
GROUPINGS, CLASS OR TYPE OF EQUIPMENT USED ON THE PROJECT.
4. REQUESTS FOR CHANGES TO THE PROJECT SCHEDULE, EQUIPMENT OR CONTRACT
VALUE DUE TO LATE ORDERING OF EQUIPMENT WILL NOT BE CONSIDERED.
2. SUBSTITUTIONS1. REQUESTS FOR APPROVAL OF ALTERNATIVE EQUIPMENT SHALL BE SUBMITTED
COMPLETE WITH ALL PHYSICAL AND PERFORMANCE SPECIFICATIONS AND SHALL NOT
DELAY THE PROJECT SCHEDULE. ALTERNATE EQUIPMENT INSTALLED WITHOUT
WRITTEN APPROVAL MAY BE REPLACED, AT NO COST TO THE OWNER, WITH THE
SPECIFIED EQUIPMENT.
2. MAKE ALLOWANCE FOR THE WORK OF THE GENERAL CONTRACTOR OTHER
SUB-CONTRACTORS AFFECTED BY THE USE OF THE ALTERNATE EQUIPMENT.
QUOTATIONS SUBMITTED WITH RESPECT TO THE USE OF THE SUBSTITUTE SHALL
INCLUDE THE COSTS INCURRED BY ANY OTHER TRADES AFFECTED BY THE USE OF THE
PROPOSED EQUIPMENT.
3. CONDUCTORS1. MINIMUM GAUGE FOR CONDUCTORS USED FOR POWER CIRCUITS IS #12 AWG COPPER.
THE SIZE TO BE ADJUSTED FOR DE-RATING DUE TO CONDUIT FILL, AMBIENT
TEMPERATURE AND TO LIMIT VOLTAGE DROP TO NO MORE THAN 2% ON ANY FEEDER
OR BRANCH CIRCUIT.
2. INSULATION TO BE RATED AT 600 VOLT EQUAL TO CSA RATED T90 (NYLON) OR
R/RW/RWU90 (CROSS-LINKED POLYETHYLENE) AND WHERE A SPECIFIC TYPE OF
INSULATION IS SHOWN THAT TYPE SHALL BE USED.
3. ALL CONDUCTORS SHALL BE COLOUR CODED AT TERMINATIONS TO PANEL(S) AND
EQUIPMENT. FOR CONDUCTORS #10 AWG AND SMALLER THE COLOUR SHALL BE THE
INSULATION OF THE CONDUCTOR. LARGER CONDUCTORS MAY BE PROVIDED WITH
A 2” (50MM) BAND OF APPROPRIATELY COLOURED TAPE ADJACENT TO THE
TERMINATION.
4. INSULATION COLOUR CODING TO BE AS FOLLOWS:
PHASE “A” RED
PHASE “B” BLACK
PHASE “C” BLUE
NEUTRAL WHITE
GROUND GREEN
4. RACEWAYS1. PROVIDE RACEWAYS AS INDICATED ON THE DRAWINGS. WHERE SIZE IS NOT SPECIFIED
PROVIDE IN ACCORDANCE WITH THE REQUIREMENTS ON THE OESC.
2. THE FOLLOWING CONDUIT TYPES ARE APPROVED FOR USE ON THIS PROJECT:
1. ELECTRICAL METALLIC TUBING (EMT) FOR GENERAL USE.
2. RIGID ALUMINUM CONDUIT (RAC) WHERE SUSCEPTIBLE TO MECHANICAL DAMAGE.
3. RIGID POLYVINYL CHLORIDE (PVC) CONDUIT BELOW GRADE OR IN POURED CONCRETE
STRUCTURES.
4. LIQUID TIGHT FLEXIBLE METALLIC CONDUIT FOR FINAL CONNECTIONS TO EQUIPMENT.
5. UTILIZE STEEL, SETCREW CONNECTIONS AND COUPLINGS FOR EMT CONDUIT. DIE-CAST
OR PRESSURE-CAST CONNECTORS AND COUPLINGS ARE NOT ACCEPTABLE. LIQUID
TIGHT FITTINGS ARE TO BE USED OUTDOORS OR WHERE CONDUIT IS DIRECTLY
EXPOSED TO MOISTURE.
5. ARMORED CABLES1. WHERE PERMITTED, MULTIPLE CONDUCTOR, ARMORED CABLES MAY BE AC-90,
ACWU-90 OR TECK-90 WITH COPPER CONDUCTORS.
2. WHERE PERMITTED, SINGLE CONDUCTOR, ARMORED CABLES MAY BE ACWU-90 OR
RA-90 WITH COPPER CONDUCTORS.
6. STANDARD OUTLET BOXES1. SIZE AND SELECT INDIVIDUAL BOXES IN ACCORDANCE WITH THE OESC BASED ON THE
INSTALLED DEVICE(S) AND THE NUMBER AND GAUGE OF CONDUCTORS CONTAINED
WITHIN AND FOR THE INSTALLED LOCATION.
2. WHEREVER MULTIPLE DEVICES ARE SHOWN IN A GROUP PROVIDE GANGED BOXES
COMPLETE WITH A SUITABLE PLASTER-RING AND INTERNAL BARRIERS WHERE OUTLETS
FOR MORE THAN ONE SYSTEM ARE GROUPED.
3. CAST ALUMINUM BOXES SHALL BE USED IN SURFACE MOUNT OUTDOOR APPLICATIONS.
4. PVC BOXES SHALL BE USED IN CONCRETE STRUCTURES.
5. OUTLET BOXES FOR COMMUNICATION AND DATA SYSTEMS ARE TO
BE 4” (100MM) SQUARE COMPLETE WITH A SUITABLE PLASTER-RING.
7. ACCESS PANELS AND DOORS1. ACCESS PANELS AND DOORS TO HAVE A FIRE RATING SUITABLE FOR THE INSTALLED
LOCATION.
2. ACCESS PANELS AND DOORS TO BE PRIMED AND PAINTED, MINIMUM 12 GAUGE, FLUSH
MOUNTED WITH CONCEALED HINGES, ANCHOR STRAP, LOCK AND TRIM TO SUIT THE
MATERIAL OF THE SURROUNDING SURFACE.
3. MINIMUM SIZE TO BE 6” x 6” (150MM x 150MM) FOR HAND ACCESS
AND 24” x 18” (600MM x 450MM) FOR PERSON ACCESS.
8. SPLITTERS
1. WELDED SHEET METAL ENCLOSURE MADE FROM CODE GAUGE STEEL, PRIMED,
COMPLETE WITH SCREW-ON OR HINGED COVER FOR SURFACE MOUNTING.
2. ENCLOSURE TO BE EEMAC RATED FOR INSTALLED LOCATION.
3. INTERNAL WIRE LUGS TO MATCH SIZE REQUIREMENTS OF FEEDER AND CIRCUIT
WIRING.
4. PROVIDE A MINIMUM OF THREE (3) SPARE CIRCUIT WIRE POSITIONS ON EACH SET OF
LUGS FOR SPLITTERS RATED 600 AMP OR LESS.
5. LENGTH OF SPLITTER TO BE 12” (300MM) LONGER THAN MINIMUM NECESSARY TO
MOUNT EQUIPMENT REQUIRED FOR THE PROJECT UNLESS NOTED OTHERWISE.
10. JUNCTION AND PULL BOXES
1. SIZE AND SELECT BOXES IN ACCORDANCE WITH THE OESC FOR THE NUMBER AND
GAUGE OF CONDUCTORS CONTAINED WITHIN AND FOR THE INSTALLED LOCATION.
2. WELDED SHEET METAL ENCLOSURE MADE FROM CODE GAUGE STEEL, PRIMED AND
PAINTED AND RATED FOR THE INSTALLED LOCATION COMPLETE WITH SCREW-ON OR
HINGED COVER FOR SURFACE MOUNTING. MINIMUM SIZE TO BE 6” x 6” (150MM
x 150MM).
3. ENCLOSURE TO BE EEMAC RATED FOR INSTALLED LOCATION.
4. FLUSH MOUNTED BOXES TO BE SIMILAR TO ABOVE AND TO BE COMPLETE WITH
A 1” (25MM) TRIM TO CONCEAL WALL OR CEILING OPENING.
5. PVC BOXES TO BE USED IN CONCRETE STRUCTURES.
11. CABINETS
1. SIZE AND SELECT CABINETS IN ACCORDANCE WITH THE OESC FOR THE ENCLOSED
EQUIPMENT.
2. CABINETS AND EQUIPMENT ENCLOSURES ARE TO BE MANUFACTURED FROM CODE
GAUGE STEEL, PRIMED AND PAINTED COMPLETE WITH LOCKING DOOR, CONCEALED
HINGES AND A REMOVABLE EQUIPMENT-MOUNTING PANEL.
3. ENCLOSURE TO BE EEMAC RATED FOR INSTALLED LOCATION.
4. FLUSH MOUNTED CABINETS TO BE PROVIDED WITH APPROPRIATE TRIM AND
HARDWARE.
12. SWITCHES
1. SWITCHES SHALL BE TOGGLE STYLE, SPECIFICATION GRADE, SILENT OPERATION,
SLOW-MAKE, SLOW BREAK RATED FOR THE AMPACITY AND VOLTAGE OF THE
CONNECTED CIRCUIT.
2. SINGLE POLE UNLESS SHOWN AS KEY-OPERATED, 3-WAY OR 4-WAY ON THE DRAWINGS.
13. LED LIGHTING
1. AS SPECIFIED IN LIGHTING SCHEDULE
14. RECEPTACLES
1. GENERAL PURPOSE RECEPTACLES:
1. DUPLEX RECEPTACLES TO BE 15 AMP, 125 VOLT, U-GROUND, CSA #5-15R
CONFIGURATION. UNLESS SPECIFIED OTHERWISE ON DRAWINGS.
2. GROUND FAULT RECEPTACLES
1. DUPLEX, GROUND FAULT RECEPTACLES TO BE 15 AMP, 125 VOLT, U-GROUND, CSA
#5-15R CONFIGURATION, CLASS A, TRIP LEVEL OF 4-6MA WITH TEST AND RESET
PUSHBUTTONS.
3. EQUIPMENT RECEPTACLES:
1. EQUIPMENT RECEPTACLES TO BE RATED AS SHOWN ON THE DRAWINGS COMPLETE
WITH OUTLET BOX, MOUNTING/COVERPLATE AND ALL REQUIRED INSTALLATION
ACCESSORIES.
15. COVER PLATES
1. COVER PLATES SHALL BE PROVIDED FOR ALL OUTLET BOXES AS FOLLOWS:
1. GENERAL AREAS - SMOOTH STAINLESS STEEL
2. SERVICE AREAS - GALVANIZED STEEL
3. WET LOCATIONS - HINGED, GASKETED, GRAY LEXAN
16. DISTRIBUTION PANELS
1. LOCATION AND RATINGS AN INDICATED ON DRAWINGS.
2. THE PANEL ENCLOSURE SHALL BE CODE GAUGE STEEL, BAKED GRAY ASA61 ENAMEL
FINISH WITH A REMOVABLE FRONT COVER AND BE EEMAC RATED FOR THE INSTALLED
LOCATION. THE BUILDING IS SPRINKLERED.
3. MAIN BUS MAY BE ALUMINUM OR COPPER FOR BOLT-ON CIRCUIT BREAKERS.
4. DIRECTORY CARD IN METAL FRAME WITH PLASTIC COVER.
5. THE SHORT CIRCUIT RATING OF THE PANEL SHALL FULLY MATCH THE LOWEST RATED
BRANCH OR MAIN CIRCUIT BREAKER.
17. PANEL BOARDS
1. LOCATION AND RATINGS AS INDICATED ON DRAWINGS.
2. ENCLOSURE TO BE CODE GAUGE STEEL, BAKED GRAY ASA61 ENAMEL FINISH,
REMOVABLE FRONT COVER, LOCKING DOOR COMPLETE WITH FLUSH MOUNTED LOCK,
TWO KEYS AND TRIM FOR SURFACE OR RECESSED MOUNTING AND TO BE EEMAC RATED
FOR THE INSTALLED LOCATION.
3. MAIN BUS MAY BE ALUMINUM OR COPPER FOR BOLT-ON CIRCUIT BREAKERS.
4. DIRECTORY CARD IN METAL FRAME WITH PLASTIC COVER.
5. COMBINATION PANELS TO HAVE FACTORY INSTALLED MAIN BREAKER IN SEPARATE
COMPARTMENT AND BE RATED FOR SERVICE ENTRANCE DUTY.
6. THE SHORT CIRCUIT RATING OF THE PANEL SHALL FULLY MATCH THE LOWEST RATED
BRANCH OR MAIN CIRCUIT BREAKER.
18. DISCONNECT SWITCHES - GENERAL
1. ALL EQUIPMENT OF SIMILAR TYPE SHALL BE BY ONE MANUFACTURER.
2. ENCLOSURE TO BE EEMAC RATED FOR INSTALLED LOCATION.
3. RATINGS TO BE MINIMUM REQUIRED MATCHING THE CONNECTED EQUIPMENT LOAD
UNLESS SPECIFIED OTHERWISE ON THE DRAWINGS.
19. MOTOR DISCONNECT SWITCHES
1. FOR MOTORS RATED UP TO 1/6HP AND 120V USE SPECIFICATION GRADE 1P SWITCHES.
2. FOR MOTORS RATED UP TO 1/4HP TO 1HP AND 250V USE HOSE-POWER
RATED, SIGNLE-THROW, QUICK-MAKE/QUICK-BREAK TOGGLE SWITCHES IN FACTORY
ENCLOSURES WITH PROVISIONS TO BE LOCKED IN THE “OFF” POSITION.
3. FOR MOTORS RATED GREATER THAN 1HP AND/OR 250V USE MANUFACTURED,
HORSEPOWER RATED SAFETY SWITCHES COMPLETE WITH LOCKABLE, INTEGRAL
OPERATING HANDLE AND QUICK-MAKE/QUICK BREAK, SILVER PLATED CONTACTS.
COVER TO BE MECHANICALLY INTER-LOCKED WITH HANDLE TO PREVENT OPENING
WHEN IN THE “ON” POSITION”.
4. WHERE DISCONNECTS ARE REQUIRED TO BE FUSIBLE PROVIDE FUSE HOLDERS
SUITABLE FOR THE TYPE AND VOLTAGE OF THE FUSE INSTALLED WITH SPRING
REINFORCED FUSE CLIPS AS NECESSARY.
20. CIRCUIT DISCONNECT SWITCHES
1. FUSIBLE SWITCHES TO HAVE FUSE HOLDERS SUITABLE FOR THE TYPE AND VOLTAGE OF
THE FUSE INSTALLED WITH SPRING REINFORCED FUSE CLIPS AS NECESSARY.
21. CONTROLS - GENERAL
1. ALL EQUIPMENT OF SIMILAR TYPE SHALL BE BY ONE MANUFACTURER.
2. EQUIPMENT TO BE EEMAC RATED FOR INSTALLED LOCATION.
22. CIRCUIT BREAKERS - GENERAL
1. ALL CIRCUIT BREAKERS FOR THIS PROJECT SHALL BE BY ONE MAUFACTURER.
2. QUICK-MAKE, QUICK-BREAK WITH ARC-QUENCHING DEVICE, TRIP-FREE HANDLE,
THERMAL OVERLOAD AND INSTANTANEOUS MAGNETIC TRIP, AMBIENT TEMPERATURE
COMPENSATING TYPE.
3. MINIMUM INTERRUPTING CAPACITIES AS FOLLOWS:
1. DISTRIBUTION PANELS - 22,000 AMPERES ASYMMETRICAL
2. PANEL BOARDS (240V) - 10,000 AMPERES ASYMMETRICAL
3. PANEL BOARDS (600V) - 14,000 AMPERES ASYMMETRICAL
4. BREAKERS SHALL BE MOUNTED TO THE BUS AS FOLLOWS:
1. DISTRIBUTION PANELS - BOLT-ON DESIGN
2. PANEL BOARDS - BOLT-ON DESIGN
MULTI-POLE BREAKERS TO HAVE A COMMON/TRIP HANDLE.
20. FUSES
1. FUSES SHALL BE BY ONE MANUFACTURER THROUGHOUT THE PROJECT.
2. FEEDER FUSES UP TO 600V AND OVER 600A SHALL BE CSA CLASS HRC-L.
3. FEEDER FUSES UP TO 600V AND 600 A SHALL BE CSA CLASS HRC-J.
4. GENERAL PURPOSE CIRCUIT PROTECTION FUSES SHALL BE CSA CLASS H.
5. MOTOR AND TRANSFORMER CIRCUITS SHALL BE DUAL-ELEMENT, TIME DELAY, CSA
CLASS HRC-D.
6. FUSES 30A OR LESS MAY BE PLUG STYLE.
24. LIGHT FIXTURES
1. LIGHTING FIXTURES ARE TO BE COMPLETE WITH LAMPS, BALLASTS AND ALL MOUNTING
OR INSTALLATION ACCESSORIES FOR THE LUMINARIES INDICATED IN THE LIGHTING
FIXTURE SCHEDULE AND/OR ON THE DRAWINGS.
2. REFER TO THE ARCHITECTURAL DRAWINGS FOR DETAILS RELATING TO CEILING
AND/OR WALL ORIENTATION AND CONSTRUCTION IN ORDER TO ESTABLISH THE
PROPER REQUIREMENTS FOR HANGERS, BRACKETS, PENDANTS, BALL-JOINT SWIVEL
BASES, THREADED RODS AND OTHER SIMILAR INSTALLATION ACCESSORIES.
25. LAMPS
1. FURNISH LAMPS AS REQUIRED BY THE LIGHTING FIXTURE SCHEDULE AND THE FIXTURE
SPECIFICATION.
26. BALLASTS
1. PROVIDE BALLASTS AS REQUIRED BY THE FIXTURE SPECIFICATION AND THE LAMP
OPERATING PARAMETERS INCLUDING SPECIALIZED BALLAST AS REQUIRED FOR
DESIGNATED APPLICATIONS.
2. ALL BALLASTS ARE TO BE COMPLETELY COMPATABLE WITH THE FIXTURE/LAMP
COMBINATION SPECIFIED IN THE LIGHTING FIXTURE SCHEDULE AND LIGHTING
MANUFACTURER'S RECOMMENDATIONS.
27. EMERGENCY LIGHTING- GENERAL
1. PROVIDE EMERGENCY BATTERY UNITS AS INDICATED ON THE DRAWINGS.
2. PROVIDE LIGHTING FIXTURES WHERE INDICATED ON THE DRAWINGS.
16. EMERGENCY BATTERY UNIT
1. UNIT TO HAVE LONG LIFE (10 YEAR LIFE EXPECTANCE), SEALED LEAD/ACID, LOW
MAINTENANCE BATTERIES CAPABLE OF MAINTAINING THE CONNECTED LOAD PLUS 25%
RESERVE CAPACITY FOR A MINIMUM DURATION OF 30 MINUTES AND BE PROVIDED
WITH THE FOLLOWING FEATURES:
2. CHARGER: 100% SOLID STATE, TEMPERATURE COMPENSATING, REVERSE POLARITY
PROTECTED, AUTO-EQUALIZER CAPABLE OF RE-CHARCHING BATTERIES TO FULL
CAPACITY WITHIN 12 HOURS ABD 2 FUSED OUTPUTS.
3. TRANSFER UNIT: 100% SOLID STATE, CAPABLE OF INSTANTANEOUS TRANSFER OF
ENTIRE CONNECTED LOAD ON NORMAL POWER FAILURE OR CONNECTIONS.
4. CABINET: MINIMUM 18 GAUGE ENAMEL PAINTED STEEL ENCLOSURE WITH 1 METER
POWER CODE AND MOUNTING SHELF AS REQUIRED.
5. FEATURES: “PUSH-TO-TEST” BUTTON, AC POWER “ON” LAMP, HIGH CHARGE INDICATOR
AND BATTERY CONDITION INDICATOR.
29. EXIT LIGHT
1. ALL EQUIPMENT SHALL BE BY ONE MANUFACTURER THROUGHOUT THE PROJECT.
2. EXIT LIGHTING FIXTURE TO BE EXTRUDED ALUMINUM CONSTRUCTION, UNIVERSAL
MOUNTING, SINGLE OR DOUBLE FACE AS REQUIRED, PICTOGRAM FILMS WITH
DIRECTION INDICATION AS REQUIRED AND THE FOLLOWING FEATURES:
1. INDIRECT LED ILLUMINATION OF FACEPLATE.
2. SELF-CONTAINED ELECTRONIC COMPONENTS TO DIRECTLY ACCEPT AC AND DC POWER
INPUTS.
3. POWER CONSUMPTION SHALL BE 5W OR LESS.
31. COMMUNICATIONS- GENERAL
1. PROVIDE ALL RACEWAYS, WIRING, EQUIPMENT AND ACCESSORIES RELATING TO THE
POWER SUPPLY WIRING AS GOVERNED BY OTHER SECTIONS OF THE SPECIFICATION.
ALL ELECTRICAL MATERIAL TO BE AS RECOMMENDED BY THE EQUIPMENT/SYSTEM
SUPPLIER UNLESS SPECIFIED OTHERWISE ON THE DRAWINGS.
32. RACEWAYS THERMOSTATS
1. CONDUITS TO THERMOSTATS OUTLET BOXES INSTALLED IN WALLS TO BE
½” (12mm) UNLESS SPECIFICALLY NOTED OTHERWISE.
2. BOXES SHALL BE 2”x4” (50mm x 100mm) MOUNTED HORIZONTALLY AS REQUIRED TO
SUIT THERMOSTAT OR SENSOR UNLESS SPECIFICALLY NOTED OTHERWISE.
3. CONFIRM ALL REQUIREMENTS WITH CONTROLS CONTRACTOR PRIOR TO ROUGH-IN.
PART 3: EXECUTION
1. GENERAL REQUIREMENTS
1. ALLOW FOR THE TRANSPORTATION OF EQUIPMENT THROUGH THE CONSTRUCTION
SITE AND BUILDING. REPAIR ALL SURFACES AFFECTED BY THE MOVEMENT OF
MATERIAL.
2. CLEAN ALL EQUIPMENT IMMEDIATELY PRIOR TO FINAL INSPECTION.
2. STORAGE OF MATERIALS
1. PROVIDE A SUITABLE, ON-SITE OFFICE SPACE AND A DRY, PROTECTED STORAGE AREA
FOR MATERIAL AND EQUIPMENT TO MAINTAIN FACTORY FINISH.
2. KEEP THE SITE FREE OF DEBRIS AND SURPLUS MATERIAL.
3. UPON COMPLETION OF WORK REMOVE ALL TOOLS AND SURPLUS MATERIAL FROM SITE.
3. SLEEVING, CUTTING AND PATCHING
1. ALLOW FOR ALL SLEEVING, CUTTING, PATCHING AND PAINTING REQUIRED FOR THIS
WORK. USE ONLY SKILLED CRAFTSMAN FOR EACH TYPE OF WORK.
2. ALL HOLES THROUGH THE EXTERIOR MEMBRANE OF THE BUILDING ARE TO BE MADE
WATERPROOF. UTILIZE ACCEPTABLE METHODS OF FLASHING, CAULKING, ETC.
3. ALL HOLES IN CONCRETE AND OTHER STRUCTURAL MEMBERS ARE TO BE APPROVED BY
THE STRUCTURAL ENGINEER PRIOR TO CUTTING. THE WORK IS TO BE CARRIED OUT
UNDER THE SUPERVISION OF THE GENERAL CONTRACTOR.
4. GROUNDING AND TESTING
1. PROVIDE A COMPLETE GROUNDING SYSTEM; THERE IS NO ATTEMPT TO INDICATE ALL
OF THE GROUNDING REQUIREMENTS ON THE DRAWINGS.
2. BALANCE PHASE CURRENT SO THAT THE CURRENT ON ANY PHASE IS WITHIN 10% OF
THE MEAN VALUE.
3. TEST BONDING CONTINUITY OF METALLIC RACEWAYS.
4. TEST THE INSULATION GROUND FAULT RESISTANCE AND MERGER FEEDERS PRIOR TO
ENERGIZING.
5. TEST FOR PROPER EQUIPMENT OPERATION.
6. PROVIDE THE FOLLOWING TEST AND INCLUDE DATA IN OPERATING AND MAGNA
MANUAL
7. VOLTAGE READING AT THE FOLLOWING LOCATIONS:
1. DISTRIBUTION PANEL MAINS.
2. POWER AND/OR LIGHTING PANEL MAINS.
3. EQUIPMENT CONNECTIONS.
4. THE RECEPTACLE FURTHEST FROM THE MAIN ELECTRICAL SERVICE EQUIPMENT.
2. AMPERAGE READING AT THE FOLLOWING LOCATIONS:
1. DISTRIBUTION PANEL FEEDERS.
2. POWER AND/OR LIGHTING PANEL FEEDERS.
3. EQUIPMENT FEEDERS.
5. CORROSION, PROTECTION AND TOUCH-UP
1. PRIME AND PAINT ALL FERROUS METAL SUPPORTS, BRACKETS, ETC.
2. PROTECT ALL MATERIAL AND EQUIPMENT FROM ABUSE AND DAMAGE. REPAIR ANY
DAMAGED SURFACE TO MATCH FACTORY FINISH.
6. EQUIPMENT IDENTIFICATION
1. PROVIDE LAMACOID LABELS ON ALL DISTRIBUTION AND CONTROL EQUIPMENTS
DETAILED BELOW:
1. LABELS TO BE 1/8” (3mm) THICK WHITE BACKGROUND WITH 1/4" (6mm) BLACK
LETTERING.
2. LABELS TO CONFIRM TO WORDING SPECIFIED IN INDIVIDUAL SPECIFICATION
SECTIONS.
2. MECHANICALLY FASTEN LAMACOID LABELS TO THE EQUIPMENT WITH SELF TAPING
SCREWS IN PRE-DRILLED HOLES.
3. TEMPORARY EQUIPMENT MARKINGS SHALL BE MADE IN INCONSPICUOUS LOCATIONS
PREFERABLY ON THE INSIDE OF THE PANEL OR ENCLOSURE. ALL TEMPORARY
MARKINGS SHALL BE REMOVED PRIOR TO FINAL INSPECTION.
4. JUNCTION BOXES TO BE EXTERNALLY LABELED WITH INDELIBLE MARKER INDICATING
CIRCUITS CONTAINED INSIDE.
7. ELECTRICAL/MECHANICAL INTERFACE
1. ALL LINE VOLTAGE POWER SUPPLIES INCLUDING OVER-CURRENT PROTECTION,
OVER-LOAD PROTECTION, MOTOR STARTERS AND CONTROLLERS, LINE VOLTAGE
WIRING AND DISCONNECT MEANS SHALL BE PROVIDED UNDER THIS SECTION, EXCEPT
IN THE CASE OF UNITIZED EQUIPMENT WHERE THE MOTOR STARTERS/CONTROLLERS
FORM PART OF AN ITEM OF PACKED EQUIPMENT.
2. ALL PRESSURE SWITCHES, THERMOSTATS, SOLENOID VALVES, DAMPER MOTORS AND
SIMILAR EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY MECHANICAL
SUN-CONTRACTOR FOR WIRING BY DIVISION 16.
3. OBTAIN THE ELECTRICAL RATINGS AND DATA FOR MECHANICAL EQUIPMENT, FROM THE
MECHANICAL SUB-CONTRACTOR, PRIOR TO ROUGH-IN WIRING AND CONNECTION OF
THE EQUIPMENT. REPORT ANY DISCREPANCIES BETWEEN THE SUPPLIED EQUIPMENT
AND THE RATINGS SHOWN ON THE ELECTRICAL DRAWINGS TO THE ENGINEER
WITHOUT DELAY.
4. THE MECHANICAL AND ELECTRICAL CONTRACTORS SHALL BIND THEMSELVES TO THE
ACCURACY AND COMPLETENESS OF THIS WORK, AND MUTUALLY WARRANT THE WORK
INTERFACED UNDER THESE REQUIREMENTS.
8. MOUNTING
1. PROVIDE ALL SUPPORTS REQUIRED FOR THIS WORK. EVERY CONDUIT TO HAVE AT
LEAST ONE SUPPORT AND ALL BOXES, FIXTURES, PANELS AND EQUIPMENT ARE TO BE
SUPPORTED INDEPENDENTLY OF CONNECTING CONDUITS.
2. INSTALL SWITCHES, RECEPTACLES AND OTHER OUTLETS ON A COMMON CENTRELINE
WHEN SHOWN TOGETHER.
3. MOUNTING HEIGHTS AS INDICATED ON DRAWINGS AND EQUIPMENT SCHEDULES.
4. REFER TO THE ARCHITECTURAL DRAWINGS FOR AREAS OF THE BUILDING DESIGNATED
AS BARRIER-FREE.
9. CONDUCTORS
1. INSTALL CONDUCTORS IN RACEWAYS AND TERMINATE AT EQUIPMENT OR SPLICES TO
OTHER WIRING.
2. CONDUCTORS FOR FEEDERS TO BE IDENTICAL IN TERMS OF CHARACTERISTICS AND
LENGTH AND FREE OF SPLICES.
3. USE ONLY SOLDER LESS CONDUCTORS IN APPROVED BOXES FOR SPLICES/JOINTS IN
BRANCH CIRCUIT WIRING.
10. RACEWAYS
1. INSTALL CONDUITS COMPLETE WITH ALL CONNECTORS, COUPLING, STRAPS, PULL AND
JUNCTION BOXES TO FORM A CONTINUOUS RACEWAY FOR THE INSTALLATION OF
CONDUCTORS AT A LATER TIME.
2. RACEWAYS ARE TO BE CONCEALED IN ALL FINISHED AREAS. IN SERVICE AND UTILITY
AREAS CONDUITS MAY BE EXPOSED AND SHALL BE GROUPED AND INSTALLED PARALLEL
TO BUILDING LINES. WHERE THE CONDUITS CANNOT BE INSTALLED ON BUILDING
SURFACES PROVIDE CHANNELS SURFACE MOUNTED OR SUSPENDED FROM STRUCTURAL
COMPONENTS OF THE BUILDING WITH THREADED RODS.
3. MAINTAIN REQUIRED CLEARANCES FROM STEAM OR HOT WATER LINES AND HEATING
OR OTHER SIMILAR EQUIPMENT.
4. OPENINGS FOR RACEWAYS PASSING THROUGH STRUCTURAL MEMBERS OR LARGER
THAN 1 1/4" (32mm) IN CONCRETE SLAB MUST BE REVIEWED AND APPROVED BY THE
STRUCTURAL ENGINEER PRIOR TO INSTALLATION.
5. EMPTY CONDUITS AND RACEWAY SYSTEM CONDUITS SHALL BE PROVIDED COMPLETE
WITH BOXES, COVER PLATES, BUSHINGS, CAPS AND PULL-CORDS.
6. PROVIDE FULL BOXES IN COMMUNICATIONS CONDUIT SYSTEMS AS DIRECTED BY THE
COMMUNICATIONS CABLE INSTALLER.
7. PROVIDE CONDUIT SEALS WHERE REQUIRED BY THE OESC.
11. CABLES
1. CABLES ARE TO BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS TO
ACHIEVE DESIRED AMPERE RATING OF THE CONDUCTORS.
2. FEEDER CABLES ARE TO BE FREE OF SPLICES.
3. SINGLE CONDUCTOR CABLES ARE TO BE SECURED WITH NON-FERROUS STRAPS OR
CLIPS AT INTERVALS REQUIRED BY THE OESC TO A FLAT BUILDING SURFACE OR
FABRICATED SUPPORT ASSEMBLY.
4. SECURE MULTIPLE CONDUCTOR CABLES TO STRUCTURAL COMPONENTS OF THE
BUILDING USING APPROVED METHODS. TIE-WIRE NOT ACCEPTABLE.
5. MULTIPLE CONDUCTOR, ARMORED CABLES MAY BE USED FOR FINAL CONNECTIONS TO
LIGHTING FIXTURES OR EQUIPMENT AND FOR BRANCH CIRCUIT WIRING CONCEALED
MAXIMUM EXPOSED LENGTH SHALL BE 10'-0” (3000mm).
6. STANDARD OUTLET BOXES
1. ALL BOXES ARE TO BE FLUSH MOUNTED EXCEPT IN SERVICE AND UTILITY AREAS.
2. GANG BOXES WHEREVER DEVICES ARE SHOWN TOGETHER. WHEN ADJACENT BOXES
CANNOT BE GANGED INSTALL ON COMMON CENTERLINE IN EITHER A HORIZONTAL OF
VERTICAL ORIENTATION.
3. SECURE OUTLET BOXES INDEPENDENTLY FROM CONNECTING CONDUITS.
4. CONFIRM MILLWORK, FURNITURE AND DOOR SWINGS FROM ARCHITECTURAL
DRAWINGS PRIOR TO ROUGH-IN.
5. FILL UN-USED KNOCKOUT OPENINGS WITH PURPOSE-MADE FILLERS.
INSTALL BLANK COVER PLATES ON ALL UNUSED OUTLET BOXES.
11. BACKBOARDS
1. PROVIDE BACKBOARDS FOR THE MOUNTING OF MAIN ELECTRICAL SERVICE EQUIPMENT,
WHERE SHOWN ELSEWHERE ON THE DRAWINGS.
2. PROVIDE SELF SUPPORTING FRAMEWORK WHERE THERE IS INSUFFICIENT WALL SPACE
TO MOUNT THE EQUIPMENT OR THE ADJACENT STRUCTURE IS NOT CAPABLE OF
SUPPORTING THE WEIGHT OF THE EQUIPMENT.
14. ACCESS PANELS AND DOORS
1. PROVIDE ACCESS PANELS OR DOORS WHERE REQUIRED FOR ACCESS TO ELECTRICAL
EQUIPMENT INSTALLED AS PART OF THIS WORK OR FOR EXISTING EQUIPMENT
CONCEALED AS PART OF THE WORK OF OTHER TRADES.
2. PROVIDE ALL PANELS, DOORS AND FRAMES TO THE APPROPRIATE DIVISION FOR THE
INSTALLATION AT THE COST IF THIS DIVISION.
3. PAINTING OF THE DOORS SHALL BE BY OTHERS.
16. SPLITTERS
1. FURNISH AND INSTALL SPLITTERS IN A NEAT, LOGICAL ARRANGEMENT SQUARE TO
BUILDING LINES ON BACKBOARDS OR METALLIC STRUCT/CHANNELS.
2. CONNECT TO POWER SUPPLY FEEDER. THE FEEDER WIRING IS TO BE IDENTIFIED (BY
PHASE) AND TERMINATED AT THE LUGS WITH NO EXCESS LENGTH.
3. PREPARE THE SPLITTER FOR THE INSTALLATION OF CIRCUIT DISCONNECT SWITCHES,
COMBINATION STARTERS, ETC.
17. JUNCTION AND PULL BOXES
1. SUPPLY AND INSTALL PULL AND JUNCTION BOXES IN RACEWAY SYSTEMS AS REQUIRED
TO INSTALL THE CONDUCTORS.
2. INSTALL BOXES IN INCONSPICUOUS BUT ACCESSIBLE LOCATIONS, USUALLY IN
ACCESSIBLE CEILING SPACES OR IN SERVICE AND UTILITY AREAS. PROVIDE DRYWALL
ACCESS PANELS AS REQUIRED.
3. SECURE BOXES INDEPENDENT OF CONNECTING CONDUITS.
4. JUNCTION BOXES TO BE LABELED WITH PERMANENT MARKER INDICATING CIRCUITS
CONTAINED INSIDE.
18. CABINETS
1. FURNISH AND INSTALL CABINETS FOR THE INSTALLATION OF ELECTRICAL
COMPONENTS INCLUDED IN THIS WORK OR COVERED BY A DIFFERENT SPECIFICATION
OR FOR THE FUTURE INSTALLATION OF EQUIPMENT BY OTHERS.
2. MOUNT BACKBOARDS OR METALLIC STRUCT/CHANNELS.
3. PRIME FLUSH MOUNTED CABINETS IN FINISHED AREAS FOR FINISHED PAINTING BY
OTHERS.
4. BOXES TO BE LABELED WITH DATA INDICATING EQUIPMENT CONTAINED INSIDE.
19. DEVICES
1. INSTALL ELECTRICAL DEVICES IN OUTLET BOXES CONNECT TO POWER SUPPLY AND/OR
CONTROL WIRING AND AFFIX COVER PLATE OVER DEVICE AND OUTLET BOX.
2. REFER TO THE ARCHITECTURAL DRAWINGS TO DETERMINE THE BARRIER-FREE AREAS
OF THE BUILDING AND POSITION THE DEVICES AT THE MOUNTING HEIGHT THAT IS
APPROPRIATE FOR THE DESIGNATION OF THE INSTALLED LOCATION.
3. REFER TO ARCHITECTURAL MILLWORK DRAWINGS TO DETERMINE THE EXACT
CONSTRUCTION DETAILS OF THE MILLWORK PRIOR TO ROUGH-IN. POSITION THE
DEVICES IN SUCH A MANNER SO THAT THEY ARE NOT BLOCKED BEHIND THE UNITS OR
REQUIRE THE COVER PLATES TO BE FIELD MODIFIED TO ALLOW THEM TO BE
INSTALLED.
4. INSTALL SWITCHES AND RECEPTACLES OR OTHER OUTLETS WITH DIFFERENT
MOUNTING HEIGHTS ON AN COMMON CENTERLINE WHEN SHOWN TOGETHER.
5. DO NOT MOUNT DEVICES BACK TO BACK.
6. REPLACE ANY DEVICES OR COVER PLATES THAT HAVE BEEN DAMAGED OR MARKED BY
PAINT CONSTRUCTION.
20. SWITCHES
1. INSTALL SINGLE POLE SWITCHES SO THAT SWITCH IS CLOSED WITH THE TOGGLE IN
THE UP POSITION.
2. GROUP SWITCHES TOGETHER IN A COMMON OUTLET BOX WITH A MATCHING MULTIPLE
GANG COVER PLATE WHERE TWO OR MORE ARE SHOWN IN ONE LOCATION.
21. RECEPTACLES
1. IN GENERAL, RECEPTACLES SHALL BE INSTALLED VERTICALLY SO THAT LINE AND
NEUTRAL OPENINGS ARE ABOVE GROUND PRONG.
2. GANG RECEPTACLES TOGETHER IN COMMON OUTLET BOX WHERE TWO OR MORE ARE
SHOWN IN ONE LOCATION.
3. INSTALL RECEPTACLES HORIZONTALLY WHERE REQUIRED TO CLEAR MILLWORK OR
FURNITURE.
4. INSTALL OUTDOOR, WEATHERPROOF RECEPTACLES HORIZONTALLY.
22. COVER PLATES
1. MOUNT COVER PLATES FLUSH TO WALL FOR RECESSED DEVICES.
2. PROVIDE BLANK COVER PLATES ON ALL UNUSED DEVICE OUTLET BOXES.
3. INSTALL COVER PLATES AFTER PAINTING IS COMPLETED, WHERE IT IS TO BE
INSTALLED ON A PAINTED SURFACE.
23. DISTRIBUTION PANELS
1. INSTALL PANEL ON A FIRE-RATED BACKBOARD AND/OR A SELF-SUPPORTING
FRAMEWORK WHERE THERE IS INSUFFICIENT WALL SPACE TO MOUNT THE PANEL OR
THE STRUCTURE IS NOT CAPABLE OF SUPPORTING THE WEIGHT OF THE PANEL(S).
2. CONNECT TO POWER SUPPLY FEEDER. THE FEEDER WIRING IS TO BE IDENTIFIED (BY
PHASE) AND TERMINATED AT THE LUGS WITH NO EXCESS LENGTH.
3. COMPLETE A TYPE WRITTEN PANEL DIRECTORY AND INSTALL IN FRAME.
4. PROVIDE LABEL ON THE PANEL COVER INDICATING PANEL NAME ON ONE LINE WITH
FEEDER AMPERES, VOLTAGE, PHASE AND WIRES ON A LINE
BELOW (E.G. “DP-1, 400A, 347/600V, 3PH, 4W”). REFER TO DRAWINGS FOR PANEL
IDENTIFICATION.
24. DISCONNECT SWITCHES
1. FURNISH AND INSTALL DISCONNECT SWITCHES COMPLETE WITH FUSES AND CONNECT
TO POWER SUPPLY WIRING TO THE CONNECTED LOAD.
2. MOUNT ALL EQUIPMENT IN NEAT, LOGICAL ARRANGEMENT. WIRING TO BE LABELED
AND TERMINATED AT RIGHT ANGLES TO THE DEVICE OR EQUIPMENT WITH NO EXCESS
LENGTH.
3. PROVIDE A SELF-SUPPORTING FRAMEWORK WHERE THERE IS INSUFFICIENT WALL
SPACE TO MOUNT THE EQUIPMENT OR ADJACENT STRUCTURE IS NOT CAPABLE OF
SUPPORTING THE WEIGHT OF THE DISCONNECT(S).
4. PROVIDE LAMACOID LABELS ON CIRCUIT DISCONNECTS INDICATING CONNECTED
LOADS, VOLTAGE RATING AND MAXIMUM FUSE SIZE ON THREE (3) SEPARATE
LINES (E.G. “HVAC-1, *208/3*, MAX FUSE 20A).
25. CONTROLS
1. FURNISH AND INSTALL CONTROL ACCESSORIES AS INDICATED ON THE DRAWINGS AND
REQUIRED BY THIS SPECIFICATION. CONNECT TO POWER SUPPLY AND CIRCUIT WIRING
TO ACHIEVE THE CONTROL DESIRED.
2. MOUNT ALL EQUIPMENT IN A NEAT, LOGICAL ARRANGEMENT. WIRING TO BE LABELED
AND TERMINATED AT RIGHT ANGLES TO THE DEVICE OR EQUIPMENT WITH NO EXCESS
LENGTH.
3. PROVIDE WIRING DIAGRAMS FOR CONTROL CIRCUITS AND MOUNT INSIDE COVER OF
EQUIPMENT ENCLOSURE.
4. TEST ALL CONTROL SEQUENCES AND CONFIRM PROPER OPERATION PRIOR TO FINAL
INSPECTION.
26. CIRCUIT BREAKERS
1. PROVIDE CIRCUIT BREAKERS AS INDICATED ON THE PANEL SCHEDULES AND/OR SINGLE
LINE DIAGRAMS.
2. ENSURE THAT ALL BREAKERS HAVE AN INTERRUPTING CAPACITY SUITABLE FOR THE
APPLICATION.
3. TERMINATE BRANCH CIRCUIT WIRING IN THE BREAKER LUG. WIRING TO BE LABELED
AT RIGHT ANGLES TO THE CIRCUIT BREAKER WITH NO EXCESS LENGTH.
27. FUSES
1. FUSES FOR FEEDERS TO BE AS INDICATED ON THE DRAWINGS.
2. FUSES FOR MOTOR AND TRANSFORMER CIRCUITS TO BE BASED ON THE NAMEPLATE
RATING OF THE EQUIPMENT.
3. ENSURE THAT ALL FUSES ARE CORRECTLY RATED FOR THE APPLICATION.
4. SHIP FUSES IN THEIR ORIGINAL CONTAINERS AND INSTALL IN DISCONNECT SWITCHES
AND/OR SWITCHBOARDS IMMEDIATELY PRIOR TO ENERGIZING CIRCUIT.
5. PROVIDE THREE (3) SPARE FUSES OF EACH SIZE AND TYPE RATED 200A OR GREATER.
6. PROVIDE SIX (6) SPARE FUSES OF EACH SIZE AND TYPE RATED LESS THAN 200A.
7. HAND OVER SPARE FUSES (IN ORIGINAL CONTAINERS) TO THE OWNER UPON
COMPLETION OF THE PROJECT.
28. LIGHTING
1. REVIEW ALL AVAILABLE DRAWINGS AND EXISTING SITE CONDITIONS (AS APPLICABLE)
TO ENSURE THAT THE FIXTURE IS COMPLETE WITH ALL OF THE REQUIRED MOUNTING
HARDWARE AND ACCESSORIES.
2. INSTALL LIGHTING FIXTURES COMPLETE WITH ALL LAMPS, TRIM AND MOUNTING
HARDWARE AND CONNECT TO POWER SUPPLY AND CONTROL WIRING AS INDICATED
ON THE DRAWINGS FOR A COMPLETE AND FINISHED UNIT(S).
3. INSTALL LIGHTING FIXTURES IN MECHANICAL AND OTHER SERVICE ROOMS AFTER THE
MECHANICAL AND ELECTRICAL EQUIPMENT IS IN PLACE. LOCATE LUMINARIES TO CLEAR
ALL OBSTRUCTIONS. PROVIDE ADDITIONAL SUPPORT TO HANG FIXTURES BELOW
DUCTS AND EQUIPMENT.
4. ENSURE FIXTURES ARE INSTALLED IN SUCH A MANNER AS TO FACILITATE THE
REPLACEMENT OF LAMPS.
5. PROVIDE ALL SUPPORT BLOCKING AS NECESSARY FOR THE INSTALLATION OF LIGHTING
FIXTURES. SUPPORTS SHALL BE CONCEALED BEHIND WALLS OR ABOVE CEILINGS.
6. LIGHTING FIXTURES INSTALLED IN ACOUSTIC TILE CEILINGS ARE TO BE SUPPORTED
INDEPENDENTLY FROM THE CEILING GRID IN A MINIMUM OF TWO LOCATIONS BY
CHAIN CONNECTED TO THE BUILDING STRUCTURE.
29. EMERGENCY LIGHTING
1. FURNISH AND INSTALL BATTERY LIGHTING UNITS AND REMOTE FIXTURES COMPLETE
WITH ALL REQUIRED ACCESSORIES AND MOUNTING HARDWARE FOR A COMPLETE AND
FUNCTIONAL INSTALLATION.
2. CONNECT TO LINE AND/OR LOW VOLTAGE POWER SUPPLIES. UTILIZE WIRING
METHODS AND SIZE CONDUCTORS FOR VOLTAGE DROP AS ALLOWED BY THE OESC.
3. ENSURE FIXTURES ARE INSTALLED IN SUCH A MANNER AS TO FACILITATE
REPLACEMENT OF LAMPS. AIM FIXTURES TO PROVIDE OPTIMUM COVERAGE OF FLOOR
AREAS.
4. UTILIZE WIRING METHODS AND SIZE CONDUCTORS FOR VOLTAGE DROP AS ALLOWED
BY OESC.
5. TEST OPERATION OF ALL EQUIPMENT PRIOR TO FINAL INSPECTION.
6. PROVIDE DUPLEX RECEPTACLES ON LOCAL LIGHTING CIRCUIT ADJACENT TO BATTERY
UNIT UNLESS DETAILED OTHERWISE ON THE DRAWINGS.
30. EXIT LIGHTING
1. PROVIDE FIXTURES WHERE INDICATED ON THE DRAWINGS.
2. FURNISH AND INSTALL ALL FIXTURES COMPLETE WITH ALL LAMPS, TRIM AND
MOUNTING HARDWARE FOR A COMPLETE AND FINISHED APPEARANCE.
3. PROVIDE ALL SUPPORT BLOCKING AS NECESSARY FOR THE INSTALLATION OF LIGHTING
AND BATTERY UNITS.
4. CONNECT LINE AND LOW VOLTAGE POWER SUPPLIES. UTILIZE WIRING METHODS AND
SIZE CONDUCTORS FOR VOLTAGE DROP AS ALLOWED BY OESC.
5. TEST OPERATION OF ALL EQUIPMENT PRIOR TO FINAL INSPECTION.
6. WHERE AN EXIT LIGHT FIXTURE IS SHOWN AT A DOOR ON THE DRAWINGS MOUNT
FIXTURE ON WALL 6” (150mm) ABOVE THE DOOR AND ON THE CENTERLINE OF THE
DOOR.
31. MECHANICAL EQUIPMENT
1. INSTALL POWER SUPPLY WIRING AND CONNECT TO MECHANICAL EQUIPMENT.
2. ALL LINE VOLTAGE POWER SUPPLIES INCLUDING OVER-CURRENT PROTECTION,
OVER-LOAD PROTECTION, MOTOR STARTERS/CONTROLLERS, LINE VOLTAGE WIRING
AND LOCAL DISCONNECTING MEANS SHALL BE PROVIDED UNDER THIS SECTION,
EXCEPT IN THE CASE OF UNITIZED EQUIPMENT WHERE THE MOTOR
STARTERS/CONTROLLERS FORM PART OF THE PACKED EQUIPMENT.
3. OBTAIN THE ELECTRICAL RATINGS AND DATA FOR MECHANICAL EQUIPMENT, FROM THE
MECHANICAL CONTRACTOR, PRIOR TO ROUGH-IN AND CONNECTION OF THE
EQUIPMENT. REPORT ANY DISCREPANCIES BETWEEN THE SUPPLIED EQUIPMENT AND
THE RATINGS SHOWN ON THE ELECTRICAL DRAWINGS TO THE ENGINEER WITHOUT
DELAY.
4. THE MECHANICAL AND ELECTRICAL CONTRACTORS SHALL BIND THEMSELVES TO THE
ACCURACY AND COMPLETENESS OF THIS WORK, AND MUTUALLY WARRANT THE WORK
INTERFACED UNDER THESE REQUIREMENTS.
32. MOTORIZED OVERHEAD DOORS
1. INSTALL POWER SUPPLY WIRING AND CONNECT TO MOTORIZED DOOR OPERATOR.
2.
PROJECT NUMBER
DRAWN CHECKED
SCALEDATE
FILE NAME
DRAWING
DATEDESCRIPTIONREV.
This drawing is the property ofSPH Engineering Inc. and is not tobe copied or distributed for anyreason or by any means withoutthe permission of the owner.
DRAWING
PROJECT
CLIENT
FAX: 519-539-5775TEL: 519-539-5700
SPH ENGINEERING INC.REAL WORLD ENGINEERING SOLUTIONS
N4S 8V8WOODSTOCK, ONTARIO
UNIT #165 SPRINGBANK AVE. N.
18134GMImainM4
STAMP NORTH ARROW
DATE
ISSUED FORPRELIMINARYCLIENT REVIEWSITE PLAN APPROVAL
BUILDING PERMITTENDERCONSTRUCTION
2018-10-01
.
Toll Free: 1-877-392-9766
Tel: (519) 842-4392
49 North Street East , Tillsonburg , ON N4G 1B4
email:[email protected]
Fax: (519) 688-2470
CONSTRUCTION LTD.
Grassmere
ww
w.g
rass
me
re.c
om
design-build construction services
R. W. SPENCER
RE
G
IS
T
E
R
E
D
P
R
O
F
ESS
IO
N
A
L
E
N
G
IN
EE
R
P
R
O
V
I
N
C
E
OF
O
N
T
A
R
I
O
100191633
2018-10-01
2018-04-12
GG RS
AS NOTED
18134
ELECTRICALSPECIFICATIONS
PROPOSED ADDITIONSGMI BUILDING
BEARDS LANE, WOODSTOCK, ON
E6
N