www.belimo.com 1
Turnkey automation station MONICO-..• Forms an efficient fire protection
system together with the motorisation sets BF(G)24MP
• Completely wired controller in matching control cabinet
• For control and monitoring of fire dampers via MP-Bus
• As stand-alone or master/slave configuration
Technical data
Electrical data Power supply voltage AC 230 V ±15%, 50/60 HzInternal supply voltage of controller 24 VACConnection Terminal strips, max. 250 VAC
Cable diameter 0.5…2.5 mm2
Bus connection MP-Bus 2-wire, conductor length up to 800 m @ 0.75 mm2
Connection of up to 8 Top Line fire protection actua-tors
Inputs/outputs Digital inputs Connection of floating contacts from the fire alarm and ventilation system.Supply from controller, 6 mA
Digital outputs 2 relay outputs for fan release and transmission of the fault report.Switching capacity 250 VAC, 2A
Safety Protection class II totally insulatedDegree of protection IP65EMC CE according to 89/336/EECMode of operation Type 1 (acc. to EN 60730-1)Ambient temperature range –10 ... +60°CNon-operating temperature range –20 ... +70°CAmbient humidity range 5 ... 95% RH, non-condensating (EN 60730-1)Maintenance Maintenance-free
Dimensions/weight Dimensions 420 x 314 x 143 mm (H x W x D)Weight approx. 4.8 kg
Safety notes
!
• The MONICO system solution is not allowed to be used outside the specified field of application, especially in aircraft or in any other airborne means of transport.
• Please note: 230 V power supply voltage!• Only components explicitly approved for this purpose by Belimo are allowed to be
used for the MONICO system solution.• The network may only be configured, and the system configuration changed, by suitably
trained and authorised personnel!• Check the relevant standards and national directives prior to planning the system. Consult
a fire protection expert if necessary.
Technical data sheet MONICO-..
Products no longer available
Automation station for fire dampers
2 www.belimo.com
Electrical installation
Master station connection(MONICO-1M)
Slave station connection(MONICO-1S)
System configuration
Controller in MONICO-.. automation station The controller is installed in the automation station and completely wired. After the fire dampers have been connected via the MP-Bus, the digital inputs/outputs and possibly further slave stations have been connected and the supply voltage has been applied, the MONICO-.. fire protection system is ready for parameterisation and commissioning.
Motorisation sets BF(G)24MP The motorisation sets (BF24MP and BFG24MP) consist of a communications-capable fire protection actuator of the Top Line series with an integrated thermoelectrical tripping device and a communication and power supply unit for connection to the MP-Bus® network.These motorisation sets are only provided to fire damper manufacturers!
External operating panel Z-PKT0FSW210 The optionally available operating panel Z-PKT0FSW210 allows the MONICO-.. fire protection system to be decentrally controlled and operated. The operating panel is connected to the pLAN bus of the controller.
MONICO-..
Mechanical installation
Control cabinet installation The control cabinet is fastened directly to the wall with 4 screws (for dimensions / drill hole distances, see page 24).Protective caps must be attached (guarantees protection class II).Observe enclosed installation instructions!
TC1
QF1
XP1
XA
TC1
QF1
XP1
XA
FU3 / 4
TCONN
GND
FU3 / 4
TCONN
GND
Master and slave station designations
TC1 Transformer 230/24 V, 30 VAQF1 Automatic circuit breaker, primaryFU3 / 4 Fuse, secondary
XP1 Terminal strip for mains connection
XA Terminal strip for bus connection and digital inputs/outputs
TCONN pLAN connection stripGND Ground connection rail
Products no longer available
Automation station for fire dampers
www.belimo.com 3
PEXP1 L N
XA MP GND
pLANTCONN MONICO-1S
AC 230 V
PEXP1 L N
C4XA NO4 C5 NO5 IDC1 ID1 IDC1 ID2 MP GND
pLANTCONN MONICO-1M
AC 230 V
Electrical installation (Continued)
Wiring diagramMaster
Wiring diagramSlave
pLAN connection TCONN pLAN connection strip
Slave station connection
Relay outputs
Digital inputs
2-wire MP-Bus® (BF(G)24MP set)
Master station connection
2-wire MP-Bus® (BF(G)24MP set)
MONICO-..
Fan release
Fault
Fire alarm system
Ventilation system
The jumpers J14 and J15 must be attached at position 1 and 2.
6 5 4 3 2 1 0
1 2 3 1 2 3J14 J15
ConnectionsTerminal screw connection Telephone plug pin Function0 – Grounding for shielded cable1 12 2 GND3 3 Rx– / Tx–4 4 Rx+ / Tx+5 5 GND6 –
Products no longer available
Automation station for fire dampersMONICO-..
4 www.belimo.com
1 2 3 4 5 6 7
BKN230-24MP
BF(G)24TL-T-ST
AC 230 V
MP GND
MPGND
PC Tool
LED
M
24 V
24 V Ya
MP BUSTECHNOLOGY BY BELIMO
®
Electrical installation (Continued)
pLAN connection
Connection of fire damperto MP-Bus
User interface
Operation of the system
Master station operating panelThe master station has an operating panel, consisting of an LCD display and a keyboard with 6 keys.
MONICO-.. MONICO-.. MONICO-..
BF(G)24MP set
max. 200 m
2 x 2 wires twisted (0.5 mm2) shielded
Master Slave Slave
Optional smoke detector contact (floating)
Prg
1 2 3 4
5 6 7
Esc
Operating panel on master stationNo. Display / key Function1 LCD Display infos
2 Prg
1 2 3 4
5 6 7
EscDisplay and reset faults
3 Prg Open navigation menus4 Esc To overview / back5
Prg
1 2 3 4
5 6 7
Esc
Scroll down
6
Prg
1 2 3 4
5 6 7
Esc
Scroll up
7
Prg
1 2 3 4
5 6 7
Esc
Confirm entry
Key combinations on master Key combinations for external operating panel
Software information display Prg
1 2 3 4
5 6 7
Esc +
Prg
1 2 3 4
5 6 7
Esc
(> 3 s) Software information display
Prg
1 2 3 4
5 6 7
Esc
/
Prg
1 2 3 4
5 6 7
Esc
(> 10 s)
Call up addressing functions Prg
1 2 3 4
5 6 7
Esc +
Prg
1 2 3 4
5 6 7
Esc
+ Connect supply voltage Set display contrast Prg
1 2 3 4
5 6 7
Esc + Prg +
Prg
1 2 3 4
5 6 7
Esc
/
Prg
1 2 3 4
5 6 7
Esc
Call up addressing functions
Prg
1 2 3 4
5 6 7
Esc
/
Prg
1 2 3 4
5 6 7
Esc
(> 5 s)
Slave addressingPrg
1 2 3 4
5 6 7
Esc +
Prg
1 2 3 4
5 6 7
Esc
+ Connect supply voltage (controller) *
Jump between master / slave Prg + Esc
* Address of the operating panel must be 0!
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 5
Prg
Esc
M01…M07
Menu structure
Keys Menu tree
Main menu
Installation(password)
Maintenance(password)
History Clock Inputs/Outputs
Info Network
Language selection
Networkconfiguration
Fanrelease
Actuator section
Addressing
Scenariomanagement
Configuration offire alarmand ventilation input
Configuration ofreports
pLANmanagement
Reset to basic setting
Manualsystem test
Automatic system test
Test of local actuator
Adaptation
Display switch-off delay
Actuator info
Faults
Manualsystem test
Automaticsystem test
Test of localactuator
Addressing
Adaptation
Display switch-off list
Actuator info
Storedfaults
Test results
Faults of entiresystem
Test results ofentire system
Setdate / time
Setday of the week
Statusdisplay
Reset buffer
System info Actuatorstatus
Lasttest result
pLANstatus
System status
Interface / modem / printer configuration
Text designation for system
Products no longer available
Automation station for fire dampersMONICO-..
6 www.belimo.com
Commissioning
System configurationchecklist
Procedure1) Check electrical connection of system and
switch on entire system2) Select language3) Address stations and external operating
panel (if present), see below4) Reset all stations to basic setting5) Set the number of stations connected to
the network on the master6) Release necessary digital inputs on
the master (for fire alarm system, input of ventilation system)
7) Set time of day
8) If desired, set parameters for automatic system test
9) If GSM modem is present, set SMS configuration
10) Set number of connected actuators at all stations
11) Address digital actuators12) Set desired scenario at each station13) Set groups and system status to “On”14) Trigger system test to test entire system
Systems with slave For systems with slave(s), an external operating panel(Z-PKT0FSW210) is required for commissioning!
Software parameter factory settings See table on page 21
Application software Same software for master and slaveThe stations are supplied with preinstalled application software. The same software is installed in the master and the slave.
Addressing System division and network addressesMaster and slave are addressed from 1 to max. 12 or 32 for one operating panel.
32
Master Slave Slave
MP
BU
ST
EC
HN
OL
OG
Y B
Y B
EL
IMO
®
MP
BU
ST
EC
HN
OL
OG
Y B
Y B
EL
IMO
®
MP
BU
ST
EC
HN
OL
OG
Y B
Y B
EL
IMO
®
230
VAC
230
VAC
230
VAC
BF24MP set orBFG24MP set
BF24MP set orBFG24MP set
BF24MP set orBFG24MP set
MP1
MP2
MP3
to MP8
MP1
MP2
MP3
MP1
MP2
MP3
RS232
Group 1 Group 2 Group 3
to MP8 to MP8
pLAN
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 7
Commissioning (Continued)
Addressing of the controllers Addressing of the master:– Keep “UP” and “ALARM” key pressed– Switch on power supply of the master– The following display will appear after a few seconds:
PLAN ADDRESS: 1
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
The master always has address 1!(This is the factory setting!)
– The desired address can be set with the “UP” and “DOWN” key and saved with the “ENTER” key.
Addressing of external operating panel:Address 32 is already set for the external operating panel upon delivery (default value)!– Keep all 3 “arrow keys” pressed for at least 5 s
Display address
setting………………… :32
I/O Board address:02
Address of the external operating panel
Shows the address of the controller to which the operating panel is connected
P:01 Adr Priv/Shared
Trm1 32 Sh
Trm2 None --
Trm3 None -- Ok?YES
Should always be set to “Sh” (Shared)
Confirm any changes by entering “YES”
See also the separate documentation (data sheet) of the external operating panel.
Addressing of slave (factory setting: address 2):– Connect external operating panel to slave– Keep all 3 “arrow keys” pressed for at least 5 s
Display address
setting………………… : 0
Set address of external operating panel to 0!
The following display appears:
Display ADDRESS
Changed
– Switch off power supply of slave– Keep “UP” and “ALARM” key on the external operating panel pressed– Switch power supply on again– The following display will appear after a few seconds:
PLAN ADDRESS: 2
UP: INCREASE
DOWN: DECREASE
ENTER: SAVE & EXIT
Set address for the slave
– The desired address can be set with the “UP” and “DOWN” key and saved with the “ENTER” key.
Important:After the slaves have been addressed, set the address of the external operating panel back to 32!
Products no longer available
Automation station for fire dampersMONICO-..
8 www.belimo.com
Main menu
Main menuThe main menu is accessed by pressing the “Esc” key several times.
Display
Group: 00/00 M01
Function: SLAVE
Group status : OFF
System status: OFF
Shows in which group you are / how many groups are present in total.
Shows function of the respective station (master / slave).
Switches the individual groups on and off. Factory setting: ON
Switches the overall system on and off. Factory setting: OFF
Display
Group: 00/00 M02
Local configuration
Actuators num.:
Enter number of connected digital and standard actuators.
Enter number of digital actuators (BF-Top). Factory setting: 0
Display
Group: 00/00 M03
Actuators status:
1 2 3 4 5 6 7 8
C C C C C C C C
Display of the actuator positions.
1…8: digital actuators.
C = closed, O = open
Display
Group: 00/00 M04
Safety function act.
1 2 3 4 5 6 7 8
N N N N N N N N
Safety function display(triggered by BAE, smoke detector, excess temperature of actuator).
Has safety function been triggered?
N = no, Y = yes
Display
Group: 00/00 M05
Dig. act. fault:
1 2 3 4 5 6 7 8
N N N N N N N N
Display for fault in actuator.(overload, MP-Bus, etc.)
Is a fault present?
N = no, Y = yes
Display
Group: 00/00 M06
Last test result:
1 2 3 4 5 6 7 8
N N N N N N N N
Display of the last test result. Was a fault determined during the last test run?
N = no, Y = yes
Display
Group: 00/00 M07
Fault reset:
1 2 3 4 5 6 7 8
N N N N N N N N
Allows a pending fault message to be reset. Remark: If the fault is still present, it cannot be reset.
Reset fault?
N = no, Y = yes
Esc
Main menu
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 9
Main menu (Continued)
Display
Group: 00/00 M08
Fan status : OFF
Fault status: OFF
Status display of the digital outputs.
Digital output contact for fan release: Status
Digital output contact for collective fault: Status
Display
Group reset: M09
01:0 02:0 03:0 04:0
05:0 06:0 07:0 08:0
09:0 10:0 11:0 12:0
Status display of the stations connected to the network. Non-connected stations are not displayed.
0 = inactive, not present, 1 = active
Display
Group on/off: M12
01:0 02:0 03:0 04:0
05:0 06:0 07:0 08:0
09:0 10:0 11:0 12:0
Slave on = 1
Slave off = 0
Installation
Password entry
Display
Installation Menu
Password: 0000
The installation menu is protected by a password.
Enter passwords using the scroll keys.
Language selection
Display
Language: C01
DEUTSCH
Select menu language.
Select menu language.
Network configuration
Display
Contr. config. C02
Num. of controllers
(pCOxs) present in
the pLan: 00 Enter number of controllers connected to the network. Factory setting: 00
Fan release
Display
C03
Delay of actions
on startup:
30 s Enter fan startup delay. Factory setting: 30 s
Installation
Languageselection
Networkconfig.
Installation
Fanrelease
Installation
Products no longer available
Automation station for fire dampersMONICO-..
10 www.belimo.com
Installation (Continued)
Actuator selection
Display
MPBUS Act. conf. C04
Actuators num.: 0 Enter number of connected actuators.
AddressingThe actuators can only be addressed if “Group config.” in display C05 is set to “Yes”. After the actuators have been addressed, “Group config.” must be set to “OFF” again!The digital actuators can be addressed in two ways: – manually (MAN, with hand crank)– automatically (AUTO, with serial number of the actuator).
Manual addressing
Display
MPBUS Act. conf. C05
Group config: No
Current act.:
Configuration group: Yes = addressing of the actuators possible, No = standard operation of the system
No / Yes
Actuator that is currently being queried
Display
Actuator 1/ C06
Address. type: MAN
Set address : No
Display of the current actuator (act. 1 = MP1).
Select method: manual (MAN) / automatic (AUTO).
Start manual addressing (select “Yes”) *.
* NoteAfter “Yes” has been selected, the hand crank of the respective actuator must be operated within 5 min-utes. The corresponding actuator then sends its serial number to the controller and is programmed with the corresponding MP address (here MP1). After the addressing has taken place, the display changes from “Yes” to “No”.
Automatic addressing
Display
Actuator 1/ C06
Address. type: AUTO
Set address : No Select automatic addressing.
Display
Actuator 1/ C07
Serial number:
00000-00000-000-000
Set address: No
Assigns the address (in this case MP1) to the actuator.
Enter the serial number of the respective actuator (with scroll and “ENTER” keys).
Yes = Save address in actuator.
Manualaddressing
Installation
Actuatorselection
Installation
Automaticaddressing
Installation
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 11
Installation (Continued)
Scenario management3 predefined scenarios are available: 1) 1:1: Only the fire damper whose sensor (temperature, smoke) is triggered will close. 2) All: As soon as a sensor (temperature or smoke) in the network is triggered, all fire dampers in the entire network will close. 3) 2: Dependence between each two fire dampers (MP1-MP2, MP3-MP4, MP5-MP6, MP7-MP8).
Display
Scenario Manag. C22
Enable scenario ALL
in the pLAN: No Activate scenario “All”? Factory setting: No
Display
Scenario Manag. C23
Enable scenario 2
on the pLAN: No Yes = Scenario 2 is selected for this station.
Display
C24
Configure local or
remote controller?
LOCAL
Selects the controller in which the scenario is to be set.
Local = master, distributed = slaves
Display
C25
Read scenario’s conf
of controller: 02
Read status: STOP
Reads out the scenario settings of the slaves from the master.
Read in a scenario from a slave.
Reading status
Display
Actuator 1 C26
Scenario : CUSTOM
Group dep.: 02
Actuat.dep: 08
The scenario “CUSTOM” is activated for actuator 1.
A customer-specific scenario could be set here.
Actuator 1 is dependent on actuator 8 in group 2.
Display
Save the current C36
scenario configurat.
in the controller:00
Write status: STOP
Saves a set scenario in the corresponding slave.
Enter controller address.
STOP / START
Display
Scenario Manag. C37
All actuators are
configurated with
scenario ALL!
Display indicating that the scenario “ALL” has been activated for all actuators.
Scenario “ALL” is active.
Scenariomanagement
Installation
Products no longer available
Automation station for fire dampersMONICO-..
12 www.belimo.com
Installation (Continued)
Configuration of the inputs of the fire alarm and ventilation system
Display
Master Control. C49
Enable F&S alarm
from D.I.: Yes
Is a fire alarm system connected to the master?
Yes / No. Factory setting: Yes
Display
Master Control. C50
Enable D.I. from
ventilation sys: No
Close fire dampers when the ventilation system is switched off? (Protection of tangible assets when ventilation system is switched off)
No / Yes. Factory setting: No
Configuration of the actuator messages
Display
Actuator 1/ C51
Enable indication of
Safety message : Yes
Gen. fault msg.: Yes
You can define for each actuator whether the respective messages and faults are to be output. These settings may only be changed after consultation with the person responsible for safety!
Transmit safety message? Factory setting: Yes
Transmit fault message? Factory setting: Yes
pLAN management
Display
pLan Management C61
Enable fault detect
offline loc.: Yes
offline pLAN: Yes
The pLAN messages can be switched off if necessary.
Local message display: Yes / No. Factory setting: Yes
pLAN message display: Yes / No. Factory setting: Yes
Config. offire alarm and ventila-tion input
Installation
Messageconfig.
Installation
pLANmanage-ment
Installation
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 13
Installation (Continued)
Display
pLan Management C62
Delay fault detect.
offline loc.: 000s
offline pLAN: 000s
A fault is displayed when the network is interrupted. The delay time “Disconnection until fault display” can be set here.
Local delay time in s. Factory setting: 30 s
pLAN delay time in s. Factory setting: 30 s
Reset to basic setting
Display
C64
Reset values
to default: No
Reset parameters of the respective station to their basic setting?
No / Yes. Factory setting: See Appendix
Manual system test
Display
Manual test C65
Start test: No
A test run of the entire network can be manually triggered here. All actuators move into the safety position (Closed) and then open again.
Trigger test run? No / Yes
Automatic system test
Display
C66
Enable automatic
self-test: No
Interval: EVERY 24h
The system can be set here so that it automatically carries out a periodic self-test of the entire network. The period type and the time can also be set.
Every 24 hours / monthly / weekly / every 48 hours
Display
Self-test config C67
Start on : Monday
Time : 00 : 00
Setting of start day and time.
Enter start day.
Enter time.
Reset to basicsetting
Installation
Manual system test
Installation
Automaticsystem test
Installation
Products no longer available
Automation station for fire dampersMONICO-..
14 www.belimo.com
Installation (Continued)
Display
Delay before C68
save the result of
self-test: 300s
Saves the test result in the history file.
Set delay time in s. Factory setting: 300 s
Test of local actuator
Display
Local act. test: C69
A1:0 A2:0 A3:0 A4:0
A5:0 A6:0 A7:0 A8:0
Possibility of testing a single actuator within the network.
0 = Standard operation1 = Start test run
When the test run has been successfully completed, the display automatically returns to 0.
Adaptation
Display
Adaptation C70
A1:0 A2:0 A3:0 A4:0
A5:0 A6:0 A7:0 A8:0
Adaptation of a new actuator to the fire damper.
0 = Standard operation1 = Start adaptation
When the adaptation has been successfully completed, the display automatically returns to 0.
Display switch-off delay
Display
C71
LCD Backlight-off
delay: 000s
The switch-off delay time of the display background lighting can be set.
Switch-off delay in s. Factory setting: 120 s
Actuator info
Display
Actuator 1/ C72
ver.HW : 00000
ver.BIOS: 0000000000
00000-00000-000-000
Display of hardware / software version.
Display of hardware version.
Display of BIOS and software version.
Display of actuator serial number.
New password
Display
INSTALL. Menu C80
New password: 0000
Set new password using the scroll keys.Confirm with “ENTER” key.
Enter new password.
Automaticsystem test
Installation
Adaptation
Installation
Display switch-offdelay
Installation
Actuator info
Installation
Test of localactuator
Installation
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 15
Maintenance
Password entry
Display
Maintenance Menu
Password: 0000
Enter the password using the scroll keys.Confirm with “ENTER” key.
Enter password.
Manual system test
Display
Manual test A01
Start test: No
A test run of the entire network can be manually triggered here. All actuators move into the safety position (Closed) and then open again.
Trigger test run? No / Yes
Automatic system test
Display
A02
Enable automatic
self-test: No
Interval: EVERY 24h
The system can be set here so that it automatically carries out a periodic self-test of the entire network. The period type and the time can also be set.
Every 24 hours / monthly / weekly / every 48 hours
Display
Self-test config A03
Start on : Monday
Time : 00 : 00
Setting of start day and time.
Enter start day.
Enter time.
Display
Delay before A04
save the result of
self-test: 000s
Saves the test result in the history file.
Set delay time in s. Factory setting: 300 s
Test of local actuator
Display
Local act. test: A05
A1:0 A2:0 A3:0 A4:0
A5:0 A6:0 A7:0 A8:0
Possibility of testing a single actuator within the network.
0 = Standard operation1 = Start test run
When the test run has been successfully completed, the display automatically returns to 0.
Manualsystem test
Maintenance
Automaticsystem test
Maintenance
Test of local actuator
Maintenance
Products no longer available
Automation station for fire dampersMONICO-..
16 www.belimo.com
Maintenance (Continued)
AddressingThe actuators can only be addressed if “Group config.” in display A06 is set to “Yes”. After the actuators have been addressed, “Group config” must be set to “OFF” again!The digital actuators can be addressed in two ways: – manually (MAN, with hand crank)– automatically (AUTO, with serial number of the actuator).
Display
MPBUS Act. conf. A06
Group config: No
Current act.:
Display of the current actuator (Act. 1 = MP1).
Configure group: Yes / No.
Manual addressing
Display
Actuator 1/ A07
Address. type: MAN
Set address : NoSelect method: manual (MAN) / automatic (AUTO).
Start manual addressing (select “Yes”) *.
* NoteAfter “Yes” has been selected, the hand crank of the respective actuator must be operated within 5 min-utes. The corresponding actuator then sends its serial number to the controller and is programmed with the corresponding MP address (here MP1). After the addressing has taken place, the display changes from “Yes” to “No”.
Automatic addressing
Display
Actuator 1/ A07
Address. type: AUTO
Set address : No
Select automatic addressing.
Display
Actuator 1/ A08
Serial number:
00000-00000-000-000
Set address: No
Assigns the address (in this case MP1) to the actuator.
Enter the serial number of the respective actuator (with scroll and “ENTER” keys).
Yes = Save address in actuator.
Adaptation
Display
Adaptation A23
A1:0 A2:0 A3:0 A4:0
A5:0 A6:0 A7:0 A8:0
Adaptation of a new actuator to the fire damper.
0 = Standard operation1 = Start adaptation
When the adaptation has been successfully completed, the display automatically returns to 0.
Display switch-off delay
Display
A24
LCD Backlight-off
delay: 120s
The switch-off delay time of the display background lighting can be set.
Switch-off delay in s. Factory setting: 120 s
Adaptation
Maintenance
Automaticaddressing
Maintenance
Display switch-offdelay
Maintenance
Manualaddressing
Maintenance
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 17
Maintenance (Continued)
Actuator info
Display
Display of software number / serial number of the actuator.
Display of BIOS and software version.
Display of actuator serial number.
New password
Display
MAINTENANCE Menu A33
New password: 0000
Set new password using the scroll keys.Confirm with “ENTER” key.
Enter new password.
Actuatorinfo
Maintenance
History
Viewing local fault history
Display
Fault history: H01
N°00 00:00 00/00/00
NO FAULTS!
Fault number Time / date
Fault in plain text.
Display
H02
Erase local faults
history memory: No
Delete fault history at this station.
Delete? No / Yes.
Viewing local test history
Display
Test history: H03
n°00 00:00 00/00/00
1 2 3 4 5 6 7 8
N N N N N N N N
Fault number Time / date
Fault determined during test run? No / Yes (N / Y).
Display
H04
Erase local test
history memory: No
Delete test history at this station?
No / Yes
Stored faults
History
Testresults
History
Actuator 1/ A25
ver.BIOS: 0000000000
00000-00000-000-000
Products no longer available
Automation station for fire dampersMONICO-..
18 www.belimo.com
History (Continued)
Viewing fault history of entire system
Display
Stored Master H05
Fault history:
Last update
status: wait...
Load histories of slaves into master.
The slaves send their history data to the master.
Display
Mast. al. hist.: H06
Group:00 N°00
00:00 00/00/00
NO FAULTS!
Select group and fault number.
Time / date
Fault in plain text.
Faults of entire system
History
Viewing test history of entire system
Display
Stored Master H07
Test history:
Last update
Status: wait...
Load saved test results of the slaves into the master.
The slaves send their history data to the master.
Display
Mast.test grp:00 H08
00/00/00 00:00
1 2 3 4 5 6 7 8
N N N N N N N N
Select group and fault number.
Date / time
Fault determined during test run? No / Yes (N / Y).
Test results of entire system
History
Clock
Setting date, time and day of week
Display
Today: K01
00:00 00/00/00
Shows set time and date.
Time / date
Display
Change time: K02
00:00 00/00/00
Day of week:
Set time and date.
Set day of week.
Set date, time
Clock
Set day of week
Clock
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 19
Status display
Inputs/outputs
External modem: For installation and parameterisation, see separate modem documentation
Inputs/outputs
Status display
Display
Digital Input I01
1: C 2: C 3: C
4: C 5: C 6: C
Shows the status of the digital inputs of the station.
C = closed, O = open
C = closed, O = open
Display
Digital Output I02
1: O 2: O 3: O
4: O 5: O
Shows the status of the digital outputs of the station.
C = closed, O = open
C = closed, O = open
Display
I03
BMS ID : 000
Speed : 1200 bps
Protocol : Carel
Shows ID number, transmission speed and transmission protocol
ID number of the system
Transmission speed
Transmission protocol
Display
Erase message I04
queue?
No
Shows inquiry to delete the internal buffer of the interface
Delete internal buffer of the interface: No / Yes
Display
Identification I09
Site ID: 01
Name: Building A
Shows text designation for the system
Text designation for system
Display
Groupe 01 I10
Name: Ground Floor
Shows text designation for the group
Text designation for group
Products no longer available
Automation station for fire dampersMONICO-..
20 www.belimo.com
Info
System info
Display
CAREL S.p.A. F01
Brugine (PD) Italia
Cod.: FLBELMFS0A
Ver.: 2.9 04/07/07
Information on the version of the installed application software.
Belimo application code
Version of the application software
Display
System info F02
Card type: pCO1xs
Bios:04.10 20/02/07
Boot:04.03 03/07/06
Display of the BIOS and boot version number.
BIOS version number
Boot version number
System info
Info
Network
Remark: The network menu is only displayed when at least one slave is connected to the master!
Actuator status
Display
Network status N01
Call group: 02
Selection of the group.
Select group number.
Display
Group: 02/04 N02
Actuators status:
1 2 3 4 5 6 7 8
C C C C C C C C
Status display of the actuators (group 02).
O = open / C = closed
Display
Group: 02/04 N03
Safety funct. active
1 2 3 4 5 6 7 8
N N N N N N N N
Status display of the safety function of the actuators.
A = active / N = not active
Last test result
Display
Group: 02/04 N04
Last test result:
1 2 3 4 5 6 7 8
N N N N N N N N
Status display of last test result: A = active / N = not active
Fault with digital actuator MP7, group 02.
Display
Group: 02/04 N05
Actuators fault:
1 2 3 4 5 6 7 8
N N N N N N N N
Fault with digital actuator MP7, group 02.
A = active / N = not active
Last test result
Network
Actuator status
NetworkProducts no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 21
Software parameter factory settings
Parameters Menu page Factory setting (Range)
Group status M01 on
System status M01 off
Number of digital actuators M02 0 (0...8)Number of stations in pLAN C02 0 (1...15)Ventilation delay C03 30 s (0...999 s)Number of standard actuators C04 0 (0...2)Delay of standard actuators during startup C04 80 s (0...99 s)Scenario management C22, C23 no
Input of fire alarm system C49 yes
Input of ventilation system C50 no
Safety-relevant messages of the actuators C51 – C60 yes
Fault messages of the actuators C51 – C60 yes
pLAN management C61 yes
pLAN delay of fault display C62 30 s (0...99 s)Save test results of the automatic test run: Delay C68 300 s (0...999 s)LCD Backlight-off delay C71 120 s (0...999 s)
Status of the digital output contacts
Status of the digital outputs
Condition Selected scenario
“Fan release” Contact Fault Contact
System test (test of all dampers) 1, 2, or all OFF Open OFF OpenTest of an individual damper 1, 2, or all ON Closed OFF OpenpLAN interruption 1, 2, or all ON Closed ON ClosedSensor (channel, excess temperature, smoke detector) triggered 1 OFF Open ON ClosedSensor (channel, excess temperature, smoke detector) triggered 2 ON 1) Closed ON ClosedSensor (channel, excess temperature, smoke detector) triggered all OFF Open ON ClosedVentilation system off (dig. input open) 1, 2, or all ON Closed OFF OpenVentilation system on (dig. input closed) 1, 2, or all OFF 2) Open OFF OpenFire alarm system triggered (dig. input open) 1, 2, or all OFF Open OFF OpenFire alarm system in standard operation (dig. input closed) 1, 2, or all ON Closed OFF Open
1) Changes to OFF as soon as the last damper of the master controller has closed
2) Changes to ON as soon as the first damper of the master controller is open
Products no longer available
Automation station for fire dampersMONICO-..
22 www.belimo.com
Troubleshooting
Checking / maintenance Please consult the following table before calling the responsible maintenance service!
Display Meaning Solution
System ok!
System works perfectly, no further steps necessary.
–
System: Off
Group: Off
The overall system and the current group are switched off.
Select system and group and switch them on.
Fault display Possible cause Solution
System alarms
01: 02:■ 03: 04:
05: 06:
Shows in which group a fault is present (example: group 2).
= No fault■ = Fault
Update the faults stored in the History menu of the master (screen H5). Select group 2 in screen H6 and read out the detailed fault description. Carry out further steps according to the displayed fault.
Fault display Possible cause Solution
AL01
Fire&Smoke alarm
from D.I. (master)
External fire alarm system reports fire alarm and has closed all fire dampers.
Check the status of the fire alarm system.
Fault display Possible cause Solution
AL04
Fault messages
not available
actuator 1
The bus connection or the supply voltage to the corresponding actuator is interrupted.
Check the bus connection and the supply voltage at the actuator.
Products no longer available
Automation station for fire dampers MONICO-..
www.belimo.com 23
Troubleshooting (Continued)
Fault display Possible cause Solution
AL20
Fault: local unit
off-line pLAN
The local controller can no longer communi-cate via the pLAN bus.
Check pLAN bus connection.
Fault display Possible cause Solution
AL21
Fault: Group 02
off-line pLAN
The first slave (group 02) can no longer communicate via pLAN bus.
Check pLAN connection.
Fault display Possible cause Solution
AL52
Warning:
Actuator 1 closed
in dependence
Digital actuator 1 (MP1) has been closed in dependence on an other actuator.
Scroll further using the scroll keys until the responsible fault is displayed, e.g. “Channel temperature > 72°C digital actuator 2”. This means that actuator 1 has been closed in dependence on actuator 2 (scenario 2 is active).
Fault display Possible cause Solution
Group: 00/00 M03
Actuators status:
1 2 3 4 5 6 7 8
O O O O O * O O
Actuator is not correctly addressed. The display “* ” means that digital actuator 6 (MP6) has not been correctly addressed; the MP-Bus line or the power supply to the actuator is interrupted.
1) Check MP-Bus connection2) Check power supply of the actuator3) Address actuator 6 again
Products no longer available
T3-M
ON
ICO
• en
• 09
.200
7 • S
ubje
ct to
cha
nges
Automation station for fire dampersMONICO-..
24 www.belimo.com
Dimensions
Dimensional diagram of MONICO-.. automation station
200
31492
4841
14 75119
330
420
128
143
Accessories
External operating panel Z-PKT0FSW210 See separate documentation.
Telephone cable Z-S90CONN000
Z-PLW0PGSM00 GSM kit
Cable with telephone plugs.
Dual-band modem kit with antenna, connecting cable and power pack (see separate documentation).
Z-PCO100MDM0 RS232 interface card for connecting GSM modem or serial protocol printer.