583 Product Data 585 Model Specifications 588 Fastener Selection 593 Construction Details 595 Vertical Joint Options A, B, C, D & E 595 Drip 597 Corner 598 Vertical Joint Layout 599 KS600/900/1000 LS LongSpan Wall System LongSpan Horizontally & Vertically Laid Insulated Wall System For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Transcript of Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet...

Page 1: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

583

Product Data 585

Model Specifications 588

Fastener Selection 593

Construction Details 595

• Vertical Joint OptionsA, B, C, D & E 595

• Drip 597• Corner 598• Vertical Joint Layout 599

KS

60

0/9

00/

100

0 L

S

Long

Spa

n W

all S

yste

m

LongSpanHorizontally & Vertically LaidInsulated Wall System

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 2: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

LongSpan™ is a frame to frame wall system which eliminates side rails

and internal linings

“”

584

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 3: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

585

Profiles AvailableThe external weather sheet is available in four profiles:

• MR (Micro-Rib)• EB (Euro-Box)• MM (Mini-Micro)• WV (Wave)

Available LengthsStandard lengths 1.8 to 8.2 metres 8.2 to 16 metres can besupplied but are subject to a transport surcharge. Panels less than1.8m long can be supplied and are subject to an extra cost.

KS

100

0 L

S

Long

Spa

n P

rodu

ct D

ata

KS600/900/1000 LS - MR/EB/MM/WV Wall SystemLongSpan

Panel length

Application KS600/900/1000 LS LongSpan wall is a frame to frame spanning,secret fixed system which can be laid horizontally. Suitable for allbuilding applications except where there are low temperatureinternal conditions.

These panels cannot be end lapped.

A - Core thickness (mm) 80 100 120 140

Weight (kg/m2) 0.63/0.63 steel 15.4 16.2 17.0 17.8

600/900/1000mm cover widthKS1000 LS

Cor

eth

ickn

ess

Dimensions & Weight

Product Tolerance

Length -5mm +5mm

Width -2mm +2mm

Thickness -2mm +2mm

End Squareness -3mm +3mm

Flatness (per metre) -2mm +2mm

Product Reference Application Description

KS600/9001000 LongSpan wall panel with Loss Prevention LS-LPCB Certification Board (LPCB) approval

for wall applications.

Ref. No. 260/28 to LPS 1181

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 4: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

586

KS600/900/1000 LS - MR/EB/MM/WV Wall SystemLongSpan

Material – SteelSubstrate• ZA255 Galvalloy hot-dip alloy coated steel (95% Zn/5% Al) to

BS EN 10214: 1995, for HPS200 and Celestia.• Galvalloy, hot-dipped zinc coated steel to BS EN 10147: 1992.

Grade Fe E220G with a Z275 zinc coating, for PVDF.• Standard external sheet thickness 0.63mm, standard internal

sheet thickness 0.63mm. Other thicknesses can be supplied tospecial order.

Coatings – External Weather Sheet• HPS200 Plastisol: 200 micron thick high performance coating

applied to the weatherside of the panel. Designed to achieve high levels of durability and colour stability is highly resistant to damage in transit and on-site.

• PVDF: 27 micron thick stove fluorocarbon coating which has excellent colour stability even at temperatures as high as 120ºC.

• Celestia: 120 micron thick Plastisol coating. 16 metallic colours.• Reverse side of sheet coated with grey polyester coating.• The steel is available in either plain or stucco embossed finish.

Coatings-Internal Liner Sheet• Lining Enamel: 15 micron thick coating developed for use for

the internal lining of insulated panels. Standard colour is ‘brightwhite’ with an easy clean surface.

• HPS200 Plastisol: 200 micron thick coating used in areas where there is high internal humidity, or a corrosive environment.

• Stelvetite Foodsafe: This is a 120 micron thick chemically inertpolymer film bonded to steel substrate for cladding of cold stores, food processing buildings and other hygiene applications.

• Reverse side of sheet coated with a light grey polyester coating.• The sheet is available in either plain or stucco embossed finish.

Insulation Core• Polyisocyanurate (PIR): with zero ozone depletion (Zero ODP).

Available in LPCB certified product range, please contactKingspan Technical Design Bureau.

SealsFactory Applied Side Joint SealAll side joints have a factory applied seal fitted into the groove toautomatically seal the joint between panels.

PerformanceThermal Insulation

Panel Thickness (mm) U value W/m2K

80 0.30

100 0.23

120 0.17

140 0.15

U -Thermal transmittance W/m2K

BiologicalKingspan panels are normally immune to attack from mould, fungi,mildew and vermin, no urea formaldehyde is used in theconstruction, and the panels are not considered deleterious.

FireSteel inner and outer facings have a Class 1 surface spread offlame to BS476 Part 7: 1987, and are class O as defined bybuilding regulations.

KS600/900/1000 LS panels are available with LPCB certification,with steel facings.

AcousticsKS1000 LS panels comply with Building Regulations Part E fornon-domestic buildings. For residential, domestic, educationand healthcare building applications, BB93 and HTM 2045solutions, consult Kingspan Technical Design Bureau.

All KS1000 LS panels have a single figure weighted soundreduction Rw = 25dB.

Building Regulations & StandardsKingspan insulated roof and wall systems conform to the followingBuilding Regulations and Standards (Non-domestic buildings):

i) Approved Document A: Structure (England & Wales)

ii) Approved Document B: Fire (England & Wales)

iii) Approved Document E: Resistance to the Passage of Sound (England & Wales)

iv) Approved Document Part L2: Conservation of Fuel & Power (England & Wales)

v) Building Standard Part D: Structural Fire Precautions (Scotland)

vi Building Standard Part H: Resistance to the Transmission of Sound (Scotland)

vii) Building Standard Part J: Conservation of Fuel & Power (Scotland)

viii) Building Standard Part L: Conservation of Fuel & Energy (Ireland)

Quality & DurabilityKingspan Insulated panels are manufactured from the highestquality materials, using state of the art production equipment torigorous quality control standards, complying with ISO 9001: 2000standard, ensuring long term reliability and service life.

Sound Reduction Index (SRI) Tested

Frequency Hz 125 250 500 1k 2k 4k

SRI dB 20.1 21.1 24.6 24.9 29.6 38.0

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 5: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

587

KS

100

0 L

S

Long

Spa

n P

rodu

ct D

ata

KS600/900/1000 LS - MR/EB/MM/WV Wall SystemLongSpan

Guarantees & WarrantiesKingspan will provide external coating and product warranties andguaranties on an individual project basis.

PackingStandard PackingKingspan KS600/900/1000 LS panels are stacked horizontallyalternate face up and require turning over during unpacking /erection.Removable hot melt adhesive is laid between each panel. The topbottom, sides and each end are protected with polystyrene andtimber packing and the entire pack is wrapped in polythene.The number of panels in each pack depends on the panelthickness, as shown in the table. Typical pack height is 1100mm.

Sea FreightFully timber crated packs are available on projects requiringdelivery by sea freight shipping, at additional cost. Alternatively,steel containers can be used. Special loading charges apply.

DeliveryAll deliveries (unless indicated otherwise) are road transport toproject site. Off loading is the responsibility of the client.

Site Installation Procedure We recommend that panels are installed using mechanical liftingmethods. Site assembly instructions are available from theKingspan Technical Design Bureau.

Panel Core Thickness 80 100 120 140

No. panel/pack (max.) 11 10 7 7

Product Reference Typical Single Span

KS1000 LS 80 5.0m

KS1000 LS 100 6.0m

KS1000 LS 120 7.0m

KS1000 LS 140 8.0m

Notes:These typical spans are based on a design wind pressure and suction of0.9kN/m2, for guidance only.

Please check exact design wind loads for building (obtained from the projectengineer) with the load/span table below.

Typical Spans

StructuralUnfactored Load/Span Table (use calculated design windload values unfactored)

5. For Intermediate Values linear interpolation may be used

6. Load Span Tables for panel specifications not shown are available fromthe Kingspan Technical Design Bureau.

7. The allowable steelwork tolerance between bearing planes of adjacentcolumns is L/600 where L is the column spacing.

SPAN Core Load Uniformly Distributed Loads (kN/m2)CONDITION Thickness Type Span L in metres

(mm) 3.0 3.5 4.0 4.5 5.0 5.5 6.0 6.5 7.0 7.5 8.0

SINGLE SPAN 80 Pressure 3.05 2.34 1.82 1.43 1.14 0.91 - - - - -Outer sheet Suction 2.77 2.08 1.58 1.22 0.94 0.74 - - - - -0.63mm steel 100 Pressure 4.00 3.22 2.55 2.04 1.65 1.35 1.11 0.92 - - -Inner sheet Suction 3.83 2.94 2.29 1.80 1.43 1.15 0.93 0.76 - - -0.63mm steel 120 Pressure 3.31 2.69 2.20 1.81 1.51 1.26 1.07 0.90 0.77 - -

L Suction 2.43 1.97 1.60 1.31 1.08 0.90 0.75 0.63 - - -140 Pressure 5.60 4.80 4.10 3.36 2.77 2.31 1.94 1.64 1.39 1.19 1.02

Suction 5.60 4.76 3.81 3.09 2.53 2.08 1.73 1.44 1.21 1.02 0.87

Notes:1. Values have been calculated using the limit state method described in the

European recommendations for the design of sandwich panels.(ECCS document No.115 2001). Taking imposed loads and temperatureinto account.

2. For Each value individual and combined load cases with appropriate loadfactors and temperatures have been considered. These are detailed under“Structural Performance” in the Building Design Section.

3. The table is for dark coloured panels.

4. The following deflection limits have been used:Pressure loading L/100

Suction loading L/100

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 6: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

588

Construction ApplicationStandard Internal and External Environments - LPS 1181 Grade B

KS600/900/1000 LS - LongSpan/Zero ODP/LPCB Wall System Horizontally Laid Ref No: 1/5.77/LPS-B

SealsHorizontal Panel JointsTo be a tongue (male) and groove (female) type of joint with afactory applied weather seal located within the groove (female)section.

JunctionsJunctions between the roof panel system and walls / penetrationsinsulated with mineral fibre insulation.Internal face of panel to be air sealed along the full length by anunbroken 6mm diameter bead of gun grade sealant.

FastenersPrimaryAll primary fasteners must be self tapping, self drilling screws,manufactured from carbon steel, anti corrosion coated, and fittedwith a 16mm diameter bonded stainless washer.All fasteners to be located through the tongue (male) section of thepanel.

To comply with the requirements of BS6399: Part 2: 1997, it maybe necessary to provide additional fixings through the malesection, in areas of high local suction.

Through FixWhere panels have their male sections removed on site, or due toloadings, they must be face fixed with a similar type of fastener.The fasteners must be covered by a flashing to maintain theconcealed fix appearance.

Panel StartAt the drip level a Panel Support, Ref: LS BC 80, 100, 120 or 140runs for the full length of the panel, levelled with packers and isfixed to the floor slab at a maximum of 500mm centres.

SecondaryFlashings to be stitched at 450mm centres (maximum) withcarbon steel stitching screws, complete with 14mm diameterbonded stainless washers and colour matched low profiled heads.

ApplicationThe following specification is for the KS600/900/1000 LS/Zero ODP/LPCB LongSpan Insulated Wall system is laidhorizontally frame to frame on buildings with internal humidity classenvironments 1-4 inclusive.

For internal humidity class environment 5 i.e. swimming poolscontact Kingspan Technical Design Bureau.

KS600/900/1000 LongSpan panels are Loss PreventionCertification Board (LPCB) certified to LPS 1181 Grade B.

Materials & CoatingsExternal Weather SheetSubstrate to be 0.63mm thick Z275 Galvatite hot-dip zinc coatedsteel to BS EN10147: 1992. External coating to be Corus UKLimited Colorcoat PVDF, 27 microns thick. Colour – Standard.

Reverse to have a light grey polyester coating.

Insulation CoreTo consist of 140 thick, closed cell, with zero ozone depletion(Zero ODP) and LPCB certified polyisocyanurate (PIR) insulation.

The auto-adhesive properties of the core bond the external andinternal sheets together, and control the panel thickness achievedduring manufacture.

Internal Liner SheetSubstrate to be 0.63mm thick hot-dip zinc coated Steel toBS EN10147: 1992.

Internal coating to be Lining Enamel, 15 microns thick. Colour - White.

Reverse to have a light grey polyester coating.

PerformanceThermal InsulationThe Panel must have a Thermal transmittance (U value) of 0.15W/m2K, calculated using the method required by the BuildingRegulations Part L2 (England & Wales) and Building StandardsPart J (Scotland).

FireThe external and internal faces of the panel to beClass 0 in accordance with the Building Regulationswhen tested to BS476: Part 6: 1989 andPart 7: 1987.

This product has passed all the requirements of LPS 1181: Issue 3

AirtightnessOverall airtightness for complete envelope less than 10m3/hr/m2

at 50Pa.

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 7: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

589

KS

100

0 L

SLo

ngS

pan

Mod

el S

peci

ficat

ions

Construction ApplicationStandard Internal and External Environments - LPS 1181 Grade B

KS600/900/1000 LS - LongSpan/Zero ODP/LPCB Wall System Horizontally Laid Ref No: 1/5.77/LPS-B

Construction DetailsVertical Panel Joints

Option AVertical panel joint to be an Option A top hat with insert flashing,to the same specification as the external weather sheet, weathersealed along the full length using two runs of Scapa Tapes 4mmdiameter butyl rubber sealant, Ref: 0311.

Top hat flashing to be fixed with stitcher screws to vertical jointcleats, Ref: LS THC A/B.

Vertical joint cleats, Ref: LS THC A/B at 500mm maximumcentres, riveted to outer face of panel with Avex type rivets.

Canister applied insulation to any gaps between board panels.

AWP fillers to be installed and bedded on silicone sealant at thehorizontal joint location with bridging silicone seal applied betweenAWP filler and supporting structure.

Rear of panel to have EPDM 95mm x 10mm self adhesive air sealbubble gasket Ref: VJ2 applied to vertical supporting steelwork.

Flashings All external flashings to be made from 0.63mm thick coated to thesame specification as the outer sheet of the panel. Colour – Standard.

All flashings to be weather sealed at laps and along the full lengthby an unbroken bead of Scapa Tapes 4mm diameter butyl rubbersealant, Ref: 0311.

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 8: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

590

Construction ApplicationStandard Internal and External Environments - LPS 1181 Grade B

KS600/900/1000 LS - LongSpan/Zero ODP/LPCB Wall System Horizontally Laid Ref No: 1/5.77/LPS-B

All flashings to have butt straps and sealed with two unbrokenruns of Scapa Tape 9mm wide x 3mm thick butyl rubber sealanttape, Ref: 0311.

AWP fillers to be installed and bedded on silicone sealant at thehorizontal joint location with bridging silicone seal applied betweenAWP filler and supporting structure.

All internal flashings to be made from 0.4mm thick steel substrate,to the same specification as the inner sheet, Colour - White.

All internal flashings to be air sealed at laps and along the fulllength by an unbroken bead of Scapa Tape 6mm diameter butylrunner sealant tape, Ref: 0311. End laps to be air sealed withVapourflex or gun grade sealant.

Panel LengthsExact lengths to be determined by the cladding contractor fromthe steelwork drawing, but typically using 6000mm lengths.

Construction RequirementsSteelwork Tolerance The steel frame must be made and assembled to an accuracy ofL/600 between fixing planes of adjacent sheeting rails, where L isthe rail spacing and generally to BS5950: Part 2: 1992.

InstallationAll fasteners and seals to be of correct specification and installedas indicated on the project construction drawings.

Site cut panels must provide accurate, true lines with no distortion,panels to be cut with powered reciprocating type saw and allexposed site cut panels to be treated with a suitable edgeprotection lacquer. Cut openings for outlets, vents, flues etc. to bethe minimum size necessary.

Remove all swarf and any foreign matter immediately from theexternal surface of panels.

Panels must be assembled so that joint widths are consistent andparallel.

SafetyThe contractor is to determine and use a safe method of workingthroughout the installation and construction period, whichcomplies with HSE & CDM requirements.

NBS Format SpecificationH43 - Metal Composite Panel

Cladding/CoveringTo be read with Preliminaries/General Conditions.

127A Metal Composite Panel Wall Cladding to Walls

• Drawing reference(s): _________• Supports: Cold rolled rail system

Bearing width: Minimum 50mm• Manufacturer and reference: Kingspan horizontally laid wall

system for standard internal and external environments andLoss Prevention Certification Board certified to LPS 1181Grade B.

• Panels:Profile reference: KS600/900/1000 LS/Zero ODP/LPCB LongSpan InsulatedWall PanelExternal facings:• Material: Galvatite hot-dip zinc coated steel to BS EN

10147, grade Fe E220G with Z275 zinc coating.• Thickness: 0.63mm

• Finish/Colour: Colorcoat PVDF, colour standardInternal facings:• Material: Hot-dip zinc coated steel to BS EN 10147.• Thickness: 0.63mm• Finish/Colour: Lining Enamel, colour White.Core insulation: Zero ODP and LPCB certified.Panel thickness: 140mm

• Male/female panel joint sealant:• Factory applied weather seal set in rebate.• Kingspan AWP filler and Scapa Tapes Ref: 0004 silicone

sealant, site applied at the end of each panel whereflashings pass over the joint.

• Scapa Tapes Ref: 0004 neutral cure silicone seal to male joints.• Fasteners: Fasteners: As determined by clause 220E

Number and location:• For panels: As determined by clause 197A, but with each

panel fixed to each support using not less than twofasteners located through tongue section, as recommendedby cladding manufacturer.

• For flashings/trims at vertical joints: Fix to each support usingone fastener.

NBS

P

L U

SP

LU

S

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 9: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

591

KS

100

0 L

SLo

ngS

pan

Mod

el S

peci

ficat

ions

Construction ApplicationStandard Internal and External Environments - LPS 1181 Grade B

• Vertical joints:Type: Option A with recessed top-hat flashing and insert with4mm diameter Scapa Tapes Ref: 0311 butyl rubber sealant.Top-hat flashing to be fixed with stitcher screws to vertical jointcleats, Ref: LS THC A/B. Vertical joint cleats, Ref: LS THC A/Bat 500mm maximum centres, riveted to outer face of panelwith Avex type rivets.

Finish/colour: Finish as external face of panels.• Canister applied insulation to any gaps between panels.• Vertical panel joint to have VJ2 EPDM 95mm x 10mm self

adhesive air seal bubble gasket applied to verticalsupporting steelwork and lapped over drip flashing

• Accessories:• LongSpan base channel, Ref: LS BC 80,100,120 or 140

running for full length of the panel, levelled with packers andis fixed to the floor slab at a maximum of 500mm centres.

• Thermal Transmittance (U Value) calculated using the methodrequired by the Building Regulations Part L2 (England & Wales)and Building Standards Part J (Scotland): 0.15 W/m2K.

• Air leakage rate of 10m3/hr/m2 at 50 Pa.• Other requirements:

• Internal face of panel to be air sealed along the full lengthby an unbroken 6mm diameter bead of gun grade sealant.

197A - Attachment• Determine the number and location of cladding fasteners

recommended by the cladding manufacturer to resist windloads calculated in accordance with BS 6399:Part 2 StandardMethod and BS 5427:Part 1.

• Calculate wind loads on roof and wall cladding appropriate tolocation, exposure, roof height, building shape and size inaccordance with BS 6399: Part 2 Standard Method andBS 5427: Part 1.

Basic wind speed (Vb): ___ m/sAltitude factor (Sa): ___Direction factor (Sd): ___Seasonal factor (Ss): 1Probability factor (Sp): 1Terrain and building factor (Sb): ___External and internal size effect factors (Ca): 1External pressure coefficients (Cpe): As determined fromBS 6399:Part 2, clauses 2.4 and 2.5.Internal pressure coefficients (Cpi): As determined fromBS 6399:Part 2, clause 2.6.Dominant opening: _________

220E - Fasteners• Manufacturer: One of the following:

SFS Intec Ltd, tel. 0113 208 5500Ejot Ecofast Ltd, tel. 0113 247 0880

• Panel fasteners: Self drilling, self tapping screws with bondedwashers.Type(s), size(s) and drilling capacity: As recommended byfastener manufacturer to suit type and thickness of supports,and thickness of cladding panels.

Screw material: Anti-corrosion coated carbon steel.Washer material: Grade 304 austenitic stainless steel.Washer size: 16mm diameter.Heads: Not coloured.

• Fasteners for vertical joint flashings/trims: As panel fasteners.• Fasteners for panel bearers: As panel fasteners but with

15mm diameter washers.• Flashing fasteners: Stitching screws with bonded washers.

Screw/washer material: As panel fasteners.Washer size: 14mm diameter.Heads: With low profiled heads to match colour of the flashing.

275 - Continuity Thermal Insulation• Junctions between the roof panel system and walls /

penetrations insulated with canister applied insulation.• Placement: Secure and continuous with cladding/ covering

insulation.

310A - Purpose Made Cold Formed Metal Accessories -External

• Drawing reference(s): _________• Material/finish: As external face of cladding.

Thickness: 0.63mmColour: To match external face of cladding.Workmanship as section Z11.

• Fixing: Stitch to external face of panels at 450mm centresusing secondary fasteners as specified for the claddingsystem.

• Sealing: Single line of 4mm diameter Scapa Tapes Ref: 0311,site applied between flashing and panel.

311A - Purpose Made Cold Formed Metal Accessories -Internal

• Drawing reference(s): _________• Material/finish: As internal face of cladding.

Thickness: 0.63mmColour: White.Workmanship as section Z11.

• Fixing: Stitch to internal face of panels at max. 450mm centresusing secondary fasteners as specified for the claddingsystem.

• Sealing: Single line of 6mm diameter Scapa Tapes Ref: 0311,site applied between flashing and panel.

• End laps to be air sealed with Vapourflex or gun grade sealant.

KS600/900/1000 LS - LongSpan/Zero ODP/LPCB Wall System Horizontally Laid Ref No: 1/5.77/LPS-B

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 10: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

592

Construction ApplicationStandard Internal and External Environments - LPS 1181 Grade B

KS600/900/1000 LS - LongSpan/Zero ODP/LPCB Wall System Horizontally Laid Ref No: 1/5.77/LPS-B

Concealed panelfixing

Factory appliedweather seal

Detail 1 - Horizontal Panel Joint Detail 3 - Drip Detail

Note: Number of fasteners depends on the actual design suction loads.

Detail 2 - Fastener Locations

Detail 4 - Vertical Joint Detail

Panel fasteners at joint only. Number dependentupon design wind suction loadings.

Air seal – EPDM bubble gasket 95 x 10mm,Kingspan Ref: VJ2 Supplied in 25m rolls

PIR board insulation with fire rated Alfasbond(FR) canister insulation to fill any gaps if required

to maintain continuity of insulation

Air seal – gun-grade sealant to male joint

KS1000 LS insulated wallpanel horizontally laid

Column face

Air seal – 9mm x 3mmbutyl rubber sealant

Internal closure flashing with100mm sealed laps

Drip flashing

Base channel (Ref: LS BC 140)for full length of panel levelled

with packers and fixed to floorslap at 500mm maximum centres

Air seal – continuous beadof gun-grade sealant

140mm thick panel

Alfasbond (FR) canisterapplied insulation

AWP joint filler and gun-grade sealant

4mm diameter butyl rubber sealant (site applied)

Option A top hat (roll formed) 30mm deepwith 100mm sealed butt straps. Supplied inmax. 6000mm lengths.

KS1000 LS horizontally laid

Snap on cover flashing. Maximum 6000mm lengths

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 11: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

593

SFS Intec Fastener Selector Guide

KS

100

0 L

SLo

ngS

pan

Fast

ener

Sel

ecti

on

Product: Steel - KS600/900/1000 LS Wall System - Concealed Joint Fixed (Thickness -20mm) (16mm diameter sealing washer)

RailType &Thickness

CoreCarbon Steel Fasteners Austenitic Stainless Steel Fasteners

Thickness(Building Classifications - Standard & Temperature Controlled) (Building Classifications - High Humidity, Low Temp, Hygiene)

(mm) Plain 8mm Hex Head Plain Irius Head (uno) Plain 8mm Hex Head

Hot Rolled 80 SDT14-A16-5,5x93 SDT14-L12-A16-5,5x93 SXC14-S16-5,5x955-12mm 100 SDT14-A16-5,5x113 SDT14-L12-A16-5,5x113 SXC14-S16-5,5x114(14)

120 SDT14-A16-5,5x132 SDT14-L12-A16-5,5x132 SXC14-S16-5,5x134

140 SDT14-A16-5,5x160 Irius not available SXC14-S16-5,5x165

Stitching fasteners for general fixing of flashings

Sela Moulded Head Irius Powder Coated Head Sela Moulded Head Irius Powder Coated Head

SLP2-T-A14-4,8x20xcolour SDL3-L12-T15-5,5x25xcolour SLP2-S-A14-4,8x20xcolour SXL2-L12-A14-5,5x22xcolour

Coloured rivet option 1661/0619xcolour

Extruded top hat at vertical joint

Use stitching fasteners as shown for flashings at foot of this table

Concealed through-fix behind flashings

Carbon Steel Stainless Steel

Use the Irius head fastener as listed for the KS1000 RW wall panel Use the hex head as listed for the KS1000 RW wall panel, but omit but omit the washer e.g. Hot rolled SDT14-L12-5,5xlength the S16 washer and use an additional flat countersunk washer

(IRD82x40) through a 30mm diameter hole in the outer skin of panel for for flush finish e.g. SXC14-5,5xlength + IRD82x40

Visible through fix where necessary

Use colour headed fasteners as listed for the KS1000 RW wall panels

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 12: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

594

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 13: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

595

KS

100

0 L

S

Long

Spa

n C

onst

ruct

ion

deta

ils

Vertical Joint Details

Option A Detail

Option B Detail

Panel fasteners at joint only.Number dependent upon designwind suction loadings.

Air seal – EPDM bubble gasket95 x 10mm, Kingspan Ref: VJ2Supplied in 25m rolls

AWP joint filler and gun-grade sealant

4mm diameter butyl rubber sealant (site applied)

Option A top hat (roll formed) 30mmdeep with 100mm sealed butt straps. Supplied in max. 6000mm lengths.For fixing see page 11.

Panel fasteners at joint only.Number dependent upondesign wind suction loadings.

Air seal – EPDM bubble gasket95mm x 10mm, Kingspan Ref: VJ2Supplied in 25m rolls

AWP joint filler andgun-grade sealant

4mm diameter butyl rubbersealant (site applied)

Option B top hat (roll formed) 30mmdeep with 100mm sealed butt straps. Supplied in max. 6000mm lengths.For fixing see page 11.

Min. steel bearingface 75mm

Min. steel bearingface 75mm

40mm

35mm

35mm 30mm 35mm

35mm

Min. steel bearingface 75mm

Min. steel bearingface 75mm

40mm

35mm

35mm 30mm 35mm

35mm

PIR board insulation with fire rated Alfasbond(FR) canister insulation to fill any gaps if required

to maintain continuity of insulation

PIR board insulation with fire rated Alfasbond(FR) canister insulation to fill any gaps if

required to maintain continuity of insulation

Air seal – gun-grade sealant to male joint

Air seal – gun-grade sealant to male joint

KS1000 LS horizontally laid

KS1000 LS horizontally laid

Snap on cover flashing. Maximum 6000mm lengths

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 14: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

596

Vertical Joint Details

Option D Detail

Option C Detail

Min. steel bearingface 75mm

Min. steel bearingface 75mm

10mm

Alfasbond (FR) canister applied insulation

Air seal – gun-grade sealant to male joint

KS1000 LS horizontally laid

Option C ‘Shadow Line’ feature flashing with 100mmsealed butt straps. Supplied in max. 6000mm lengths

Air seal – gun-grade sealant to male joint

KS1000 LS horizontally laid

Kingspan extruded aluminium insert sectionRef: IN11. Supplied in 6000mm lengths.

Air seal – EPDM bubble gasket95mm x 10mm, Kingspan Ref: VJ2Supplied in 25m rolls

Panel fasteners at joint only.Number dependent upon designwind suction loadings.

AWP joint filler andgun-grade sealant

4mm diameter butyl rubbersealant (site applied)

Air seal – EPDM bubblegasket 95 x 10mm, KingspanRef: VJ2 Supplied in 25m rolls

Panel fasteners at joint only.Number dependent upondesign wind suction loadings.

AWP joint filler and gun-grade sealant

EPDM integral fir tree seal. Supplied in 50m rolls.

Option D extruded aluminium tophat section TH30 30mm deep with100mm sealed butt straps.Supplied in 6000mm lengths.For fixing see page 11.

15mm

25mm 25mm

35mm 35mm80mm

Min. steel bearingface 75mm

Min. steel bearingface 75mm

50mm

35mm 35mm

35mm 35mm34mm

PIR board insulation with fire rated Alfasbond(FR) canister insulation to fill any gaps if

required to maintain continuity of insulation

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 15: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

597

KS

100

0 L

S

Long

Spa

n C

onst

ruct

ion

deta

ils

Vertical Joint & Drip Details

Option E Detail

Panel fasteners at joint only.Number dependent upondesign wind suction loadings.

Air seal – EPDM bubble gasket95mm x 10mm, Kingspan Ref: VJ2Supplied in 25m rolls

AWP joint filler and gun-grade sealant

Min. steel bearingface 75mm

Min. steel bearingface 75mm

50mm

35mm

35mm 34mm 35mm

35mm

Air seal – gun-grade sealant to male joint

KS1000 LS horizontally laid

KS1000 LS insulated wall panel horizontally laid

Column face

Air seal – 9mm x 3mm butyl rubber sealant

Internal closure flashing with 100mm sealed laps

Drip flashing

Base channel (Ref: LS BC 140) for full length of panel levelledwith packers and fixed to floor slap at 500mm maximum centres

Air seal – continuous bead of gun-grade sealant

EPDM integral fir tree seal. Supplied in 50m rolls.

Option D extruded aluminium top hat sectionTH30 30mm deep with 100mm sealed buttstraps. Supplied in 6000mm lengths.For fixing see page 11.

Drip Detail140mm thick panel

Note: Kingspan extruded aluminium sections are supplied mill finished asstandard or can be specified polyester powder coated to BS or RAL colours

Kingspan extruded aluminium insert sectionRef: IN23. Supplied in 6000mm lengths.

PIR board insulation with fire rated Alfasbond(FR) canister insulation to fill any gaps if required

to maintain continuity of insulation

Alfasbond (FR) canister applied insulation

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 16: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

598

Drip & Corner Details

Drip Detail

Corner Detail

KS1000 LS insulated wall panel horizontally laid

Column face

Air seal – 9mm x 3mm butyl rubber sealant

Internal closure flashing with 100mm sealed laps

Drip flashing

80mm thick panel

Air seal – continuous bead of gun-grade sealant

Panel fasteners at joint only.Number dependent upon designwind suction loadings

AWP joint filler and gun-grade sealant

4mm diameter butyl rubbersealant (site applied)

Alfasbond (FR) canister applied insulation

Corner flashing with sealed butt straps

AWP joint filler and gun-grade sealant

Panel thickness

Corner column with corner plate by others

Air seal – 95mm x10mm EPDM bubblegasket supplied in 25m rolls (Ref: VJ2)

Air seal – gun-grade sealant to male joint

KS1000 LS horizontally laid

4mm diameter butyl rubber sealant (site applied)

Base channel (Ref: LS BC 80) for full length of panel levelled with packers and fixed to floor slap at 500mm maximum centres

Alfasbond (FR) canister applied insulation

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info

Page 17: Product Data 585 Model Specifications 588 Fastener ...Profiles Available The external weather sheet is available in four profiles: • MR (Micro-Rib) • EB (Euro-Box) • MM (Mini-Micro)

599

KS

100

0 L

S

Long

Spa

n C

onst

ruct

ion

deta

ils

Vertical Joint Layout

Vertical Joint Layout

Enlarged Vertical Joint Detail

KS1000 LS horizontally laid

Drip flashing

Horizontal panel joint

Top hat joint cleats at 500mmmaximum centres using avex rivets(Ref: LS THC A/B or LS THC D/E)

500m

m m

ax50

0mm

max

500m

m m

axTop hat fixed to top

hat support cleats

Snap on cover cap

Top hat support cleats at 500mmmax centres using avex rivets

Avex rivets

4mm diameter butyl rubber seal

Vertical top hat

KS1000 LShorizontally laid

For more information on Kingspan Insulated Panels visit www.barbourproductsearch.info