PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369)...

14
PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV Protection of high voltage system assets

Transcript of PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369)...

Page 1: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

— PRODUC T BROCHURE

Type PEXLIM Surge Arresters 72-362 kVProtection of high voltage system assets

Page 2: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

2

—Surge arresters from ABBReliable protection of electrical equipment

ABB is a pioneering technology leader in power grids, electrification products, industrial automation and robotics and motion, serving customers in utilities, industry and transport & infrastructure globally. Continuing a history of innovation spanning more than 130 years, ABB today is writing the future of industrial digitalization with two clear value propositions: bringing electricity from any power plant to any plug and automating industries from natural resources to finished products. As title partner in ABB Formula E, the fully electric international FIA motorsport class, ABB is pushing the boundaries of e-mobility to contribute to a sustainable future. ABB operates in more than 100 countries with about 147,000 employees.

ABB offers a wide range of products from 208 V up to 1200 kV that help enhance the reliability, efficiency and quality of power in transmission and distribution grids, power plants and industries while minimizing environmental impact. The wide product range is complemented by a comprehensive service offering.

ABB surge arresters are the primary

protection against atmospheric and

switching over voltages. ABB offers a

complete range of surge arresters for

high and medium voltage

applications. The range comprises of

AC and DC solutions up to 1,100kV

and arresters for special applications

like railways, DC-voltage limiting

devices and many other purposes.

The designs comply with the IEC

60099-4 and ANSI/IEEEC62.11.

Page 3: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

TYPE PEXLIM SURGE ARRESTERS 72-362KV 3

PEXLIM offers an ideal alternative to traditional porcelain-housed arresters. High mechanical strength in combination with a direct-molded polymeric housing, gives a good combination of performance.

The PEXLIM family of arresters have been optimized to fulfill the market requirements in the voltage segment 72 - 362 kV and can meet requirements of specific applications where high strength, low weight, reduced clearance, and flexible mounting requirements are needed.

—PEXLIM Metal Oxide Surge ArresterABB’s family of HV direct-molded polymer arresters

PEXLIM surge arresters are designed to perform under harsh environmental conditions. They are best suited for applications with high mechanical strength demands, high seismic requirements, or sea salt, soot or acid rain and other such harsh environments. Applications include:

• Protection of substation equipment• Loads requiring high mechanical strength• Seismic areas• Polluted areas• Transformers and reactors• Capacitor banks

—Quick selection guide

System voltage - Nominal Surge Arrester - ANSI/IEEE Ratings

Maximum Three-wire Four-wire Three-wireFour-wire grounded

Four-Wire grounded high impedance

Vm Vn Vn Vr / VMCOV Vr / VMCOV Vr / VMCOV

kVrms kVrms kVrms kVrms kVrms kVrms

2.52 2.4 3 / 2.55

4.37Y / 2.52 4.16Y / 2.40 3 / 2.55 5 / 4.25

4.37 4.16 5 / 4.25

5.04 4.8 6 / 5.10

7.24 6.9 9 / 7.65

8.73Y / 5.04 8.32Y / 4.8 6 / 5.1 12 / 10.2

12.6Y / 7.27 12.0Y / 6.93 9 / 7.65 15 / 12.7

13.09Y / 7.56 12.47Y / 7.2 9 / 7.65 18 / 15.3

13.86Y / 8.0 13.2Y / 7.62 10 / 8.40 18 / 15.3

14.49Y / 8.37 13.8Y / 7.97 10 / 8.40 18 / 15.3

14.49 13.8 18 / 15.3

21.82Y / 12.6 20.78Y / 13.2 15 / 12.7 27 / 22.0

24.0Y / 13.86 22.86Y / 13.2 18 / 15.3 30 / 24.4

24.15 23.0 30 / 24.4

26.19Y / 15.12 24.94Y / 14.4 21 / 17.0 33 / 27.0

36.23Y / 20.92 34.5Y / 19.92 27 / 22.0 45 / 36.5

36.23 34.5 45 / 36.5

48.30 46 48/ 39

72.50 69 72 / 57

123 115 108 / 84

145 138 120 / 98

170 161 144 / 115

245 230 192 / 152

362 345 276 / 220

550 500 420 / 335

800 765 588 / 470

Page 4: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

4

PEXLIM P-Z Available Q4 2018

Classifications

Arrester classificationIEC 60099-4, Ed. 3.0

IEEE Std. C62.11-2012Station; SH

Station

Line discharge class IEC 60099-4, Ed. 2.2 Class 4

Energy class (switching surge energy) IEEE Std. C62.11-2012 G

Performance data

Maximum system voltages (Vm) Vm 72 - 362 kVrms

Duty cycle rated voltages (Vr) Vr 60 - 288 kVrms

Classifying current (IEEE/ANSI)(IEC)

IEEE / ANSIIEC

10 / 15 kApeak

20 kApeak

Discharge current withstand strengthHigh current 4/10 µsLow current 2000 µs

100 kApeak

1,600 Apeak

Switching surge energy rating Wth 13.0 kJ / kVMCOV

Short circuit / pressure relief capability 65 kArms sym

Mechanical strengthSpecified long-term load (SLL)

Specified short-term load (SSL)2,212 ft-lbs / 3.0 kNm4,425 ft-lbs / 6.0 kNm

Service conditions

Ambient temperatureDesign altitude

Frequency

-58 F to +113 F**3,280 ft / 1,000 m

15 - 62 Hz

PEXLIM P-X Obsolete Q4 2018

Classifications

Arrester classificationIEC 60099-4, Ed. 3.0

IEEE Std. C62.11-2012Station; SH

Station

Line discharge class IEC 60099-4, Ed. 2.2 Class 4

Energy class IEEE Std. C62.11-2012 G

Performance data

Maximum system voltages (Vm) Vm 72-362 kVrms

Duty cycle rated voltages (Vr) Vr 60-288 kVrms

Classifying current (IEEE/ANSI)(IEC)

IEEE / ANSIIEC

10 / 15 kApeak

20 kApeak

Discharge current withstand strengthHigh current 4/10 µsLow current 2000 µs

100 kApeak

1,600 Apeak

Switching surge energy rating Wth 13.0 kJ/kVMCOV

Short circuit / pressure relief capability 65 kArms sym

Mechanical strengthSpecified long-term load (SLL)

Specified short-term load (SSL)1,843 f-lbs / 2.5 kNm

2,950 ft-lbs / 4.0 kNm

Service conditions

Ambient temperatureDesign altitude

Frequency

-58 F to +113 F**3,280 ft / 1,000 m

15 - 62 Hz

PEXLIM Q-Y

Classifications

Arrester classificationIEC 60099-4, Ed. 3.0

IEEE Std. C62.11-2012Station; SM

Station

Line discharge class IEC 60099-4, Ed. 2.2 Class 3

Energy class IEEE Std. C62.11-2012 E

Performance data

Maximum system voltages (Vm) Vm 72 - 362 kVrms

Duty cycle rated voltages (Vr) Vr 60 - 288 kVrms

Classifying current (IEEE/ANSI)(IEC)

IEEE / ANSIIEC

10 kApeak

10 kApeak

Discharge current withstand strengthHigh current 4/10 µsLow current 2000 µs

100 kApeak

1000 Apeak

Switching surge energy rating Wth 9.0 kJ / kVMCOV

Short circuit / pressure relief capability 65 kArms sym

Mechanical strengthSpecified long-term load (SLL)

Specified short-term load (SSL)1,843 ft-lbs / 2.5 kNm2,950 ft-lbs / 4.0 kNm

Service conditions

Ambient temperatureDesign altitude

Frequency

-58 F to +113 F**3,280 ft / 1,000 m

15 - 62 Hz

—** Higher altitudes designs available on request

Page 5: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

5

—PEXLIMFigures

—Figure 1

—Figure 2

—Figure 4

—Figure 5

—Figure 3

Page 6: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

6

Ratings(kVrms)

TOV(kVrms) Maximum discharge voltage with different current waveforms

Rated voltage MCOV

With prior duty of 9 kJ/kVMCOV SPL 30/60 us LPL 8/20 us FOW 0.5 us 1

Vr VMCOV 1 sec 10 sec 0.5 kA 1 kA 2 kA 1 kA 3 kA 5 kA 10 kA 15 kA 20 kA 40 kA 10 kA

60 48 66 62 115 118 123 121 129 134 141 149 155 173 152

96 76 106 99 184 190 197 193 207 214 226 238 248 277 244

108 88 119 112 207 213 222 218 233 241 254 268 279 312 274

120 98 133 124 230 237 246 242 259 268 282 298 310 347 305

132 106 146 137 253 261 271 266 285 295 310 327 341 382 335

180 144 199 186 346 355 369 363 388 402 423 446 465 520 457

192 152 212 199 369 379 394 387 414 429 451 476 496 555 487

228 182 252 236 438 450 468 459 492 509 536 565 589 659 579

258 209 285 267 495 509 529 520 557 576 606 640 667 746 655

264 212 292 273 507 521 542 532 570 589 620 655 682 763 670

276 220 305 286 530 545 566 556 595 616 649 684 713 798 700

288 230 318 298 553 569 591 580 621 643 677 714 744 832 731

—PEXLIM Q-YElectrical characteristics

—1 Non-inductive discharge level.

Page 7: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

7

—PEXLIM Q-YVertical mounting styles and technical data

Vm (kV)IEEE Rating

Vr VMCOV Style Number 1

Creepage Distance

inches (mm)

BIL 1.2/50 us dry kVpeak

Weight (mass)

lbs (kg)A

inches (mm)B

inches (mm)C

inches (mm)D

inches (mm) Fig

72 60 48 Q060YV072A 113.7 (2889) 390 62 (28) 29.2 (742) 1

72 60 48 Q060YV072AUHR 113.7 (2889) 390 62 (28) 29.2 (742) 5

145 96 76 Q096YH145A 147.2 (3740) 499 77 (35) 37.6 (955) 1

145 96 76 Q096YH145AUHR 147.2 (3740) 499 77 (35) 37.6 (955) 5

145 108 88 Q108YH145A 147.2 (3740) 499 75 (34) 37.6 (955) 1

145 108 88 Q108YH145AUHR 147.2 (3740) 499 75 (34) 37.6 (955) 5

145 120 98 Q120YH145A 147.2 (3740) 499 75 (34) 37.6 (955) 1

145 120 98 Q120YH145AUHR 147.2 (3740) 499 75 (34) 37.6 (955) 5

170 132 106 Q132YH170A 179.1 (4549) 580 88 (40) 45.1 (1146) 2

170 132 106 Q132YH170AUHR 179.1 (4549) 580 88 (40) 45.1 (1146) 5

245 180 144 Q180YH245A 261.0 (6629) 889 132 (60) 64.0 (1625) 15.7 (400) 6.3 (160) 3

245 180 144 Q180YH245B 294.5 (7480) 998 152 (69) 73.0 (1855) 23.6 (600) 11.8 (300) 3

245 192 152 Q192YH245A 294.5 (7480) 998 150 (68) 72.4 (1838) 15.7 (400) 6.3 (160) 3

245 228 182 Q228YV245A 326.3 (8289) 1079 163 (74) 79.8 (2026) 23.6 (600) 11.8 (300) 3

362 258 209 Q258YH362A 408.2 (10369) 1388 229 (104) 103.5 (2629) 55.1 (1400) 39.4 (1000) 27.6 (700) 4

362 264 212 Q264YH362A 408.2 (10369) 1388 234 (106) 103.5 (2629) 55.1 (1400) 39.4 (1000) 27.6 (700) 4

362 264 212 Q264YH362B 358.2 (9098) 1160 196 (89) 86.5 (2197) 55.1 (1400) 19.7 (500) 3

362 276 220 Q276YH362A 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3

362 288 230 Q288YH362A 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3

—1 Style numbers ending in UHR are capable of underhung mounting. However, mechanical strength SSL and SLL are reduced by 25%.2 Contact factory for seismic applications.

Page 8: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

8

—PEXLIM P-ZElectrical characteristics

Ratings(kVrms)

TOV(kVrms) Maximum discharge voltage with different current waveforms

Rated voltage MCOV

With prior duty of 13 kJ/kVMCOV SPL 30/60 us LPL 8/20 us FOW 0.5 us 1

Vr VMCOV 1 sec 10 sec 0.5 kA 1 kA 2 kA 1 kA 3 kA 5 kA 10 kA 15 kA 20 kA 40 kA 10 kA

60 48 66.0 63.0 114 116 121 118 126 130 137 144 149 164 145

66 54 72.6 69.3 125 128 133 130 138 143 150 158 164 180 160

96 76 106 101 182 186 193 189 201 207 218 230 239 262 233

108 88 119 113 204 210 217 213 226 233 246 259 269 295 262

120 98 132 126 227 233 241 236 251 259 273 288 299 328 291

132 106 145 139 250 256 265 260 276 285 300 317 329 360 320

180 144 198 189 341 349 362 354 377 389 410 432 448 491 436

192 152 211 202 363 373 386 378 402 415 437 461 478 524 465

228 182 251 239 432 442 458 449 477 493 519 547 568 622 552

258 209 284 271 488 501 518 508 540 558 587 619 643 704 625

264 212 290 277 500 512 530 520 553 571 601 634 658 721 640

276 220 304 290 522 536 554 543 578 597 628 662 688 753 669

288 230 317 302 545 559 579 567 603 622 655 691 717 786 698

—1 Non-inductive discharge level.

Page 9: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

9

—PEXLIM P-ZVertical mounting styles with standard and technical data

Vm (kV)IEEE Rating

Vr VMCOV Style Number 1

Creepage Distance

inches (mm)

BIL 1.2/50 us dry kVpeak

Weight (mass)

lbs (kg)A

inches (mm)B

inches (mm)C

inches (mm)D

inches (mm) Fig

72 60 48 P060ZV072A 113.7 (2889) 390 75 (34) 29.2 (741) 1

72 60 48 P060ZV072AUHR 113.7 (2889) 390 75 (34) 29.2 (741) 5

72 66 54 P066ZV072A 113.7 (2889) 390 74 (34) 29.2 (741) 1

72 66 54 P066ZV072AUHR 113.7 (2889) 390 74 (34) 29.2 (741) 5

123/145 96 76 P096ZH145A 147.2 (3740) 499 94 (43) 37.6 (954) 1

123/145 96 76 P096ZH145AUHR 147.2 (3740) 499 94 (43) 37.6 (954) 5

123/145 108 88 P108ZH145A 147.2 (3740) 499 93 (42) 37.6 (954) 1

123/145 108 88 P108ZH145AUHR 147.2 (3740) 499 93 (42) 37.6 (954) 5

123/145 120 98 P120ZH145A 147.2 (3740) 499 91 (42) 37.6 (954) 1

123/145 120 98 P120ZH145AUHR 147.2 (3740) 499 91 (42) 37.6 (954) 5

170 132 106 P132ZH170A 179.1 (4549) 580 111 (51) 45.1 (1145) 2

170 132 106 P132ZH170AUHR 179.1 (4549) 580 111 (51) 45.1 (1145) 5

245 180 144 P180ZH245A 261.0 (6629) 889 159 (72) 64.6 (1641) 23.6 (600) 11.8 (300) 3

245 192 152 P192ZH245A 294.5 (7480) 998 180 (82) 72.3 (1837) 15.7 (400) 6.3 (160) 3

245 228 182 P228ZH245A 294.5 (7480) 998 176 (80) 72.3 (1837) 15.7 (400) 6.3 (160) 3

245 228 182 P228ZV245A 326.3 (8289) 1079 197 (90) 79.7 (2025) 23.6 (600) 11.8 (300) 3

362 258 209 P258ZH362A 406.6 (10327) 1360 270 (123) 101.8 (2586) 55.1 (1400) 39.4 (1000) 27.6 (700) 4

362 264 212 P264ZH362A 406.6 (10327) 1360 269 (122) 101.8 (2586) 55.1 (1400) 39.4 (1000) 27.6 (700) 4

362 276 220 P276ZH362A 408.2 (10369) 1388 272 (123) 103.5 (2628) 55.1 (1400) 39.4 (1000) 23.6 (600) 4

362 288 230 P288ZH362A 408.2 (10369) 1388 270 (123) 103.5 (2628) 55.1 (1400) 39.4 (1000) 23.6 (600) 4

—1 Style numbers ending in UHR are capable of underhung mounting. However, mechanical strength SSL and SLL are reduced by 25%.2 Contact factory for seismic applications.

Page 10: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

10

Ratings(kVrms)

TOV(kVrms) Maximum discharge voltage with different current waveforms

Rated voltage MCOV

With prior duty of 13 kJ/kVMCOV SPL 30/60 us LPL 8/20 us FOW 0.5 us 1

Vr VMCOV 1 sec 10 sec 0.5 kA 1 kA 2 kA 1 kA 3 kA 5 kA 10 kA 15 kA 20 kA 40 kA 10 kA

60 48 66.0 63.0 114 116 121 118 126 130 137 144 149 164 145

66 54 72.6 69.3 125 128 133 130 138 143 150 158 164 180 160

96 76 106 101 182 186 193 189 201 207 218 230 239 262 233

108 88 119 113 204 210 217 213 226 233 246 259 269 295 262

120 98 132 126 227 233 241 236 251 259 273 288 299 328 291

132 106 145 139 250 256 265 260 276 285 300 317 329 360 320

180 144 198 189 341 349 362 354 377 389 410 432 448 491 436

192 152 211 202 363 373 386 378 402 415 437 461 478 524 465

228 182 251 239 432 442 458 449 477 493 519 547 568 622 552

258 209 284 271 488 501 518 508 540 558 587 619 643 704 625

264 212 290 277 500 512 530 520 553 571 601 634 658 721 640

276 220 304 290 522 536 554 543 578 597 628 662 688 753 669

288 230 317 302 545 559 579 567 603 622 655 691 717 786 698

—PEXLIM P-XElectrical characteristics

—1 Non-inductive discharge level.

Page 11: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

11

—PEXLIM P-XVertical mounting styles with standard and technical data

Vm (kV)IEEE Rating

Vr VMCOV Style Number 1

Creepage Distance

inches (mm)

BIL 1.2/50 µs dry

kVpeak

Weight (mass)

lbs (kg)A

inches (mm)B

inches (mm)C

inches (mm)D

inches (mm) Fig

72 60 48 P060XV072A 89.4 (2270) 400 59 (27) 29.0 (737) 1

72 66 54 P066XV072A 89.4 (2270) 400 62 (28) 29.0 (737) 1

123/145 96 76 P096XH145B 142.7 (3625) 578 89 (40) 42.6 (1081) 1

123/145 108 88 P108XH145B 142.7 (3625) 578 87 (40) 42.6 (1081) 1

123/145 120 98 P120XH145A 142.7 (3625) 578 85 (39) 42.6 (1081) 1

170 132 106 P132XH170A 178.7 (4540) 800 119 (54) 55.2 (1401) 15.7 (400) 6.3 (160) 3

245 180 144 P180XM245A 232.1 (5895) 978 140 (64) 68.7 (1744) 15.7 (400) 6.3 (160) 3

245 180 144 P180XH245A 285.4 (7250) 1156 178 (81) 83.0 (2107) 23.6 (600) 11.8 (300) 3

245 192 152 P192XH245B 285.4 (7250) 1156 176 (80) 83.0 (2107) 23.6 (600) 11.8 (300) 3

362 258 209 P258XH362A 374.8 (9520) 1556 253 (115) 113.2 (2876) 47.2 (1200) 39.4 (1000) 23.6 (600) 4

362 264 212 P264XH362A 374.8 (9520) 1556 252 (114) 113.2 (2876) 47.2 (1200) 39.4 (1000) 23.6 (600) 4

362 276 220 P276XH362A 374.8 (9520) 1556 250 (114) 113.2 (2876) 47.2 (1200) 39.4 (1000) 23.6 (600) 4

362 288 230 P288XH362A 374.8 (9520) 1556 239 (109) 113.2 (2876) 35.4 (900) 31.5 (800) 15.7 (400) 4

—1 Style numbers ending in UHR are capable of underhung mounting. However, mechanical strength SSL and SLL are reduced by 25%.2 Contact factory for seismic applications.

Page 12: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

12

—PEXLIMMountings and hardware

—Master Nameplate

—Drilling Plan3-Hole on 8.74" to 10" B.C.4-Hole on 9.45" B.C.

—Line Terminal (aluminum)

—Ground Terminal (galvanized)

—Adapter Plate3-Hole on 10" B.C.4-Hole on 12.53" B.C.6-Hole on 16.5" B.C.

Part No: 4F0107G01

—Insulating Base Kit with Adapter Plate (6-Hole Mount)

Part No: 4F0106G01

Page 13: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

TYPE PEXLIM SURGE ARRESTERS 72-362KV 13

—Insulating Base Kit for PEXLIM Q-Y/P-X/P-Z with 3 InsulatorsPart No: 4F0108G01

—Seismic Insulating Base Kit for PEXLIM Q-Y/P-X/P-Zwith 4 Insulators

Part No for PEXLIM Q-Y/P-X: 4F0109G02Part No for PEXLIM P-Z: 4F0109G03

—Seismic Insulating Base Kit for PEXLIM Q-Y/P-X with 3 InsulatorsPart No: 4F0109G01

Page 14: PRODUCT BROCHURE Type PEXLIM Surge Arresters 72-362 kV ... · 362 288 230 q288yh362a 408.2 (10369) 1388 224 (102) 103.5 (2629) 55.1 (1400) 19.7 (500) 3 1 Style numbers ending in UHR

—ABB Inc. High Voltage Surge Arresters100 Distribution CircleMt. Pleasant, PA, USA 15666Phone: +1 724-696-1500

abb.com/highvoltage

2GN

L010

011

RE

V A

_9.2

018

© Copyright 2018 ABB. All rights reserved. Specifications subject to change without notice.

Additional informationWe reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB.