Presentation Slides -- Power and Lighting
Transcript of Presentation Slides -- Power and Lighting
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
1
BUILDING ENERGY CODES UNIVERSITY
BUILDING TECHNOLOGIES PROGRAMANSI/ASHRAE/IES Standard 90.1-2010 Power and Lighting
April 2011 – PNNL-SA-79907
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
2
CompliancePower
Mandatory Mandatory ProvisionsProvisions
(required for most compliance
options)
Building SystemBuilding System Compliance OptionsCompliance Options
Energy Code Energy Code ComplianceCompliance
Prescriptive Prescriptive OptionOption
Energy Cost Energy Cost BudgetBudget
Trade Off OptionTrade Off Option
SimplifiedSimplified
Envelope
HVAC
Lighting
SWH
Power
Other
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
3
Low-Voltage Dry Type Distribution Transformers New Buildings Additions Alterations Mandatory Provisions
Voltage drop Automatic receptacle control
Submittals
Section 8Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
4
Comply with the Energy Policy Act of 2005 If not included in scope of EPAct 2005, then no requirements
Exceptions If meet EPAct 2005 exclusions based on NEPA TP-1:
Special purpose applications Not likely in general purpose applications Have multiple voltage taps where highest tap is ≥ 20% more than
lowest tap Some specific products are listed
Section 8 – 8.1.2Low Voltage Dry-Type Distribution Transformers
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
5
Equipment installed in new buildings or additions to existing buildings must comply
Section 8 – 8.1.3 – 8.1.4New Buildings and Additions to Existing Buildings
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
6
Alterations to equipment or systems must comply with requirements applicable to those specific portions of the building and systems being altered
New equipment installed as a direct replacement of existing equipment must comply with requirements for that equipment
Exception Not required for relocation or reuse of existing
equipment at the same site
Section 8 – 8.1.5Alterations to Existing Buildings
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
7
Two types of conductors Feeder conductors
– Connect service equipment to the branch circuit breaker panels– 2% maximum voltage drop allowed at design load
Branch circuit conductors– Run from the final circuit breaker to the outlet or load– 3% maximum voltage drop allowed at design load
These are more stringent than non-enforceable requirements in the National Electric Code (NEC)
ExceptionFeeder conductors and branch circuits dedicated to emergency services
Section 8 – 8.4.1Voltage Drop
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
8
≥ 50% of all 125 volt 15- and 20-amp receptacles (including those in modular partitions) must be controlled by an automatic control device in these space typesPrivate officesOpen officesComputer classroomsExceptionsReceptacles designated for equipment requiring 24 hr operationSpaces with security or safety concerns
Section 8 – 8.4.2Automatic Receptacle Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
9
Automatic control devices must function on:
Time-of-day controller provided to control ≤ 25,000 ft2 and not more than one floor
Occupant sensor to turn off receptacles within 30 minutes of occupant leaving the space
Signal from another control or alarm that indicates the area is unoccupied
Section 8 – 8.4.2Automatic Receptacle Control, con’t
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
10
Owner gets information about the building’s electrical system
Record drawings of actual installation within 30 days
– Single-line diagram of electrical distribution system
– Floor plans showing location and areas served for all distribution
Manuals– Submittal data stating equipment
rating– O&M manuals for equipment– Qualified service agency– Complete narrative of system as it’s
normally intended to operate
Section 8 – 8.7Power Submittals
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
11
ComplianceLighting
Mandatory Mandatory ProvisionsProvisions
(required for most compliance
options)
Building SystemBuilding System Compliance OptionsCompliance Options
Energy Code Energy Code ComplianceCompliance
Prescriptive Prescriptive OptionOption
Energy Cost Energy Cost BudgetBudget
Trade Off OptionTrade Off Option
SimplifiedSimplified
Envelope
HVAC
Lighting
SWH
Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
12
Basic Lighting Requirements
Exemptions
Mandatory Requirements (Interior and
Exterior)
Controls
Switching
Interior Lighting Power
Limits
Building Area
Additional Allowances
+
Efficiency
Space-by-Space
Exemptions
Exterior Lighting Power
Limits+
Total Connected
Power
Interior Lighting Power
Allowance<
OR
Tradable
Non-Tradable
Total Connected
Power
Exterior Lighting Power
Allowance<
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
13
Section 9 Lighting
General Application (Section 9.1)• Scope • Lighting Alterations• Installed Interior Lighting Power• Luminaire Wattage
Compliance Path(s) (Section 9.2)
Mandatory Provisions (Section 9.4)• Lighting control• Exit signs• Exterior building lighting power• Functional testing
Building Area Method Compliance Path (Section 9.5)
Alternative Compliance Path: Space-by-Space Method (Section 9.6)
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
14
Interior spaces of buildings Exterior building features Exterior grounds lighting powered
through buildingExceptions
– Emergency lighting– Lighting required by life safety statute– Lighting within dwelling units of
buildings– Decorative gas lighting
Section 9 Lighting General Scope
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
15
Applies to these retrofits: where luminaires are added, replaced, or removed lamp plus ballast
Requires BOTH interior and exterior alterations to comply with LPD and basic after hours automatic shutoff requirements
Exception:Spaces where alterations involve < 10% of connected lighting load
Section 9 Lighting General Scope - Alterations
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
16
Lots of exemptions (next page)
Calculation methods Building area Space-by-space
Trade-offs of interior lighting power allowance aren’t allowed when both allowed methods are used in different portions of the building
Section 9 Interior Lighting Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
17
Theatrical, stage, film, and video production
Medical and dental procedures Exhibit displays for museums,
monuments, and galleries Plant growth or maintenance Integral to equipment or
instrumentation installed by manufacturer
Integral to both open and glass-enclosed refrigerator and freezer cases
Retail display windows, provided the display is enclosed by ceiling-height partitions
Food warming and food preparation equipment
Interior spaces specifically designated as registered interior historic landmarks
Integral part of advertising or directional signage
Section 9Lighting Power Allowance Exemptions
Exit signs Sale or lighting educational
demonstration systems Lighting for television broadcasting in
sporting activity areas Casino gaming areas Furniture-mounted supplemental task
lighting controlled by automatic shutoff and complying with 9.4.1.4(d)
For use in areas specifically designed for occupants with special needs including visual impairment and other medical and age-related issues
Mirror lighting in dressing rooms and accent lighting in religious pulpit and choir areas
Parking garage transition lighting
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
18
Used for projects involving An entire building A single, independent, and separate occupancy in a multi-
occupancy building
Gross lighted area is multiplied by allowance from Table 9.5.1
Limitations Insensitive to specific space functions and room configurations Generally is more restrictive When a specific building type isn’t listed, “selection of a reasonably
equivalent type” is permitted
Section 9 Building Area Method of CalculatingInterior Lighting Power Allowance
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
19
Part of Table 9.5.1
0.88Exercise Center
0.61Dormitory
0.89Dining: Family
0.90Dining: Cafeteria/Fast Food
0.99Dining: Bar Lounge/Leisure
1.05Court House
1.08Convention Center
0.82Automotive Facility
Lighting Power Density (W/ft2)Building Type
Section 9 - Table 9.5.1Building Types
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
20
Sum of total lighted area of a building
Measured from the exterior faces of the exterior walls or from the centerline of walls separating buildings, but excluding a long list of uses. (See Standard).
Used in the building area method of determining interior lighting power allowance
Section 9Gross Lighted Area
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
21
Divide gross lighted area of the building into each of the space types
Calculate lighting power allowance by multiplying area of space type by lighting power density for that specific space type
Sum all the allowances Advantages
– More flexible– Applicable to all building types– Accounts for actual room areas (e.g., lighting needs of
enclosed office vs. open office)
Section 9 – 9.6.1Space-by-Space Method of Calculating Interior Lighting Power Allowance
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
22
If a space has multiple functions and more than one space type applies Break space into smaller subspaces, using space types from Table 9.6.1
Exceptions If any subspace is < 20% of original space and < 1000 ft2,
don’t need to break it out separately Include area of balconies and other projections when calculating
When calculating spaces and subspaces, limits of the area defined by centerline of interior walls dividing line between subspaces outside surface of exterior walls
Section 9 – 9.6.1Space-by-Space Method of Calculating Subspaces
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
23
Section 9 – 9.6.1Space-by-Space Method of CalculatingInterior Lighting Power Allowance
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
24
Added LPD Adjustment – 9.6.3
• Use only when applying the space by space method• Calculate the Room Cavity Ratio (RCR) for the empty room:
RCR = 2.5 x Room Cavity Height x room perimeter length room area
(Room Cavity Height = Luminaire mounting height – Workplane)
• If RCR is greater than the RCR threshold for that space type, a 20% increase is allowed
• For corridor/transition spaces, this adjustment is allowed when less than 8 feet wide, regardless of the RCR
Room Cavity Ratio Adjustment for relief in unusual spaces
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
25
Added LPD Adjustment
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
26
Added LPD Adjustment
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
27
An increase in the lighting power allowance is allowed for specific space functions when using the space-by-space method. Applications must be automatically controlled, separately from the general lighting, to be turned off during non-business hours
Decorative luminaires in addition to the general lighting at 1.0 W/ft2
Retail display lighting Advanced controls
Section 9 – 9.6.2 Prescriptive Additional Interior Lighting Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
28
Additional Interior Lighting Power Allowance = 1000 watts + (Retail Area 1 x 0.6 W/ft2) + (Retail Area 2 x 0.6 W/ft2) + (Retail Area 3 x 1.4 W/ft2) + (Retail Area 4 x 2.5 W/ft2),
Where: Retail Area 1 = the floor area for all products not listed in Retail Area 2, 3 or 4. Retail Area 2 = the floor area used for the sale of vehicles, sporting goods and
small electronics. Retail Area 3 = the floor area used for the sale of furniture, clothing, cosmetics
and artwork. Retail Area 4 = the floor area used for the sale of jewelry, crystal, and china.
Exception Other merchandise categories may be included in Retail Areas 2 through 4 above,
provided that justification documenting the need for additional lighting power based on visual inspection, contrast, or other critical display is approved by the authority having jurisdiction.
Section 9 – 9.6.2 Retail Display Lighting
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
29
If all mandatory control requirements are met for a space AND advanced controls are installed in that space, THEN additional limited lighting power is allowed:Additional power can be used anywhere in the buildingAdditional Interior Lighting Power Allowance is calculated as
Lighting Power Under Control x Control Factor
Section 9 – 9.6.2 Advanced Controls Incentive
Partial Table 9.6.2 Control Factors Used in Calculating Additional Interior Lighting Power Allowance
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
30
Installed Interior Lighting Power shall include all power used by the luminaires, including lamps, ballasts, transformers, and controls
Exception: in the case where there are two independently operated lighting systems that are controlled to prevent simultaneous operation
– Include only the higher wattage system
Luminaire Wattage for various systems shall be determined in accordance with details in Section 9.1.4
Section 9 – 9.1.3Lighting General
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
31
Line voltage luminaires without ballasts or transformers = max. labeled wattage of the luminaire
Luminaires with ballasts or transformers = wattage of the maximum lamp/auxiliary combination OR max. labeled wattage of the luminaire Except when adjustable ballast factors (base on ballast factor to be
used in the space provided ballast factor isn’t user changeable) Line voltage track = actual wattage with a min. 30 W per foot
OR wattage limit of system’s circuit breaker OR wattage limit of other permanent-current-limiting device(s) on the system
Low voltage track = transformer wattage All others as specified on equipment
Section 9 – 9.1.4Luminaire Wattage
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
32
Automatic lighting shutoff control device required
EXCEPT: Lighting for 24-hour operation Patient care spaces Areas with safety or security concerns
Compliance options:
Control lights on a scheduled basis (automatic time switch) Time-of-day controller Controls ≤ 25,000 ft2 and not more than one floor
Occupant sensor Turn lights off within 30 minutes of occupant leaving the space
Signal from another control or alarm that indicates the area is unoccupied
Section 9 - 9.4.1Mandatory Automatic Shutoff
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
33
Intent is to apply to business entities or structures where whole building control is practical
Example application: Strip mall – individual business unit
Section 9.4.1.1 Application of Automatic Shutoff
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
34
At least one for each room or space enclosed by ceiling-height partitions– To have at least one control step between 30% and 70% (inclusive)
of full lighting power in addition to all off• Exceptions:
– Lighting in corridors, electrical/mechanical rooms, public lobbies, restrooms, stairways, and storage rooms
– Spaces with only 1 luminaire with rated input power < 100W– Space types with lighting power allowance of < 0.6 W/ft2
– in spaces ≤ 10,000 ft2, each control serves 2,500 ft2 maximum and in spaces > 10,000 ft2, serves 10,000 ft2 maximum
Readily accessible to occupants Override of any time-of-day control for
no more than 2 hours Remote location is allowed to
accommodate areas where safety or security is a concern
Section 9 – 9.4.1.2Mandatory: Individual Space Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
35
Additional control required for Display/accent lighting Case lighting Task lighting Nonvisual lighting Demonstration lighting Stairwell lighting
Section 9 – 9.4.1.2 Mandatory Individual Space Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
36
Occupancy sensors are required in: Classrooms and lecture halls Conference, meeting, and training rooms Employee lunch/break rooms Storage and supply rooms between 50 ft2
and 1000 ft2
Rooms used for document copying and printing
Office spaces < 250 ft2
Restrooms Dressing, locker, and fitting rooms
Exceptions:– Spaces with multi-scene control systems– Shop and lab classrooms– Areas with safety or security concern– Lighting required for 24 hour operation
Section 9 – 9.4.1.2 Mandatory Individual Space Controls
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
37
Guestroom lighting must be controlled at room entry•Suites must be controlled at entry to each room or primary entry•Bathrooms controlled to automatically turn off lighting within 60 minutes of occupant leaving space
– Exception: night lighting not > 5W
Section 9 – 9.4.1.2 Mandatory Additional Space Controls
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
38
Stairwells• Automatic reduction control for lighting in enclosed
stairwells to– Automatically reduce lighting power in any control zone by at
least 50% within 30 minutes of all occupants leaving the zone
Section 9 – 9.4.1.2 Mandatory Additional Space Controls
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
39
Parking garage lighting to be automatically controlled, including daylighting•Must reduce lighting power by minimum of 30% when no activity detected for no more than 30 minutes within a lighting zone ≤ 3,600 ft2
•Daylight transition zone lighting– Controlled separately to automatically turn on lighting during
daylight hours and off at sunset•Automatically reduce power in response to daylight for luminaires within 20 ft of any perimeter wall that has
– a net opening to wall ratio of ≥ 40% and– no exterior obstructions within 20 ft
Exceptions•Daylight transition zones and ramps without parking are exempt from 30% reduction and daylight control•Applications using HID of 150W or less or induction lamps are exempt from 30% reduction
Section 9 – 9.4.1.3 Parking Garage Lighting Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
40
Section 9 – 9.4.1.3 Parking Garage Lighting Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
41
Section 9 – 9.4.1.3 Parking Garage Lighting Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
42
Section 9 – 9.4.1.4 Daylight Zone Definition – Under Skylights
© 2010, ASHRAE, ANSI/ASHRAE/IES Standard 90.1-2010, Figure 3.1
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
43
Section 9 – 9.4.1.4 Daylight Zone Definition – Under Rooftop Monitors
© 2010, ASHRAE, ANSI/ASHRAE/IES Standard 90.1-2010, Figure 3.2
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
44
Section 9 – 9.4.1.4 Automatic Daylighting Controls for Primary Sidelighted Area
© 2010, ASHRAE, ANSI/ASHRAE/IES Standard 90.1-2010, Figure 3.3
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
45
Section 9 – 9.4.2Mandatory Exit Signs
Limited to 5 watts per face
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
46
Exterior Building Lighting Power must meet prescribed wattage limits. Exterior applications divided into 2 categories:
• Tradable: allowed wattage may be traded among these applications
• Non-Tradable: allowed wattage cannot be traded between surfaces or with other exterior lighting
Section 9.4.5 Exterior Lighting Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
47
Section 9.4.5 Exterior Lighting Power Zones
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
48
Section 9 Tradable Exterior LPDs
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
49
The total exterior lighting power allowance is the sum of the base site allowance plus individual lighting power densities [LPD]….
Trade-offs are allowed only among “Tradable Surfaces” applications
Some exemptions apply
Section 9 – 9.4.3Exterior Building Lighting Power
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
50
The following are exempt when equipped with separate controls : specialized signal, directional, and marker lighting associated with
transportation; lighting that is integral to advertising signage or directional signage; lighting that is integral to equipment or instrumentation and is installed
by its manufacturer; lighting for theatrical purposes, including performance, stage, film, and
video production; lighting for athletic playing areas; temporary lighting; lighting for industrial production, material handling, transportation sites,
and associated storage areas; theme elements in theme/amusement parks; lighting used to highlight features of public monuments and registered
historic landmark structures or buildings; lighting for hazardous locations; lighting for swimming pools and water features; searchlights.
Section 9 – 9.4.3Exterior Lighting Power Exemptions
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
51
• Lighting must turn off when there is sufficient daylight• Building façade and landscape lighting must be shut
off between– midnight or business closing (whichever is later) and– 6am or business opening (whichever comes first) OR– times established by AHJ
• Power for other lighting (incl. advertising signage) to be automatically reduced by at least 30%
– From midnight or within 1 hour of end of business operations (whichever is later)
– Until 6am or business opening (which is earlier) OR– During any period when no activity has been detected for a
time no longer than 15 minutes
Exceptions Covered vehicle entrances Exits from buildings or parking structures
(where required for safety, security, or eye adaptation)
Section 9 – 9.4.1.7Mandatory Exterior Lighting Control
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
52
• Functional testing (calibrated/adjusted/programmed) of lighting control devices and systems required within 90 days of occupancy– Must be performed by individuals NOT involved in design,
manufacture, or installation– For occupant sensors, time switches, programmable controls, or
photosensors:• Verify all performance criteria is met• Confirm occupant sensor time-out and sensitivity settings• Confirm timers and programs set to turn lights off• Confirm photosensor controls effectively control electric lighting in
response to daylight
Section 9 – 9.4.4Functional Testing
BUILDING ENERGY CODES UNIVERSITY www.energycodes.gov/BECU
53
Section 9 – 9.7 Submittals
Record drawings, to include for each piece of lighting equipment: Location Luminaire identifier Control Circuiting
Operation and maintenance manuals