Presentation PST_en, Bucharest

download Presentation PST_en, Bucharest

of 49

Transcript of Presentation PST_en, Bucharest

  • 8/2/2019 Presentation PST_en, Bucharest

    1/49

    Siemens Workshop

    Power Transmission and Distribution

    Bucharest, March 2012

    Bucharest, March 2012

  • 8/2/2019 Presentation PST_en, Bucharest

    2/49

    Page 2 Power Transmission and DistributionBucharest 2012

    SIEMENS Transformers Austria, Weiz

    Phase Shifting Transformers Basics and Application

    Phase Shifting Transformers

  • 8/2/2019 Presentation PST_en, Bucharest

    3/49

    Page 3 Power Transmission and DistributionBucharest 2012

    Contents

    Purpose und function of PSTs

    Categories and types

    Operational considerations

    Tap changer application

    Testing

    Recent PST units

    Conclusion

  • 8/2/2019 Presentation PST_en, Bucharest

    4/49

    Page 4 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    Basic funct ion o f a PST

    In principle, a phase shifting transformer creates a phaseshift between the primary (source) and the secondary

    (load) side

    Usually, this phase shift can be varied under load

    Sometimes, it can be made advance or retard

    What is c a l led a Phase Shi f t er?

    A phase shifting transformer is a tool to control the powerflow through specific lines in a complex power transmissionnetwork

  • 8/2/2019 Presentation PST_en, Bucharest

    5/49

    Page 5 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    Pow er f low in pow er sys tem s needs t o becon t ro l led , due to

    technical reasons (e.g. line overloading)

    economical reasons (e.g. committed powertransfer at network node)

    The need is increasing because of liberalization effects

    Th is can be ach ieved w i th a

    Phase Shi f t ing Transf orm er (PST)

  • 8/2/2019 Presentation PST_en, Bucharest

    6/49

    Page 6 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    What does a Phase Shi f t er do?

    It changes the effective phase displacement between the input

    voltage and the output voltage of a transmission line, thuscontrolling the amount of real power that can flow in the line.

    Because of the mainly inductive line impedance, inserting a voltagein phase or opposite to line voltage (changing magnitude of thevoltage) will have an impact on the reactive power flow only, whilea boost voltage with a phase angle perpendicular to the line voltage(creating a phase shift) actually influences the real power flow.

  • 8/2/2019 Presentation PST_en, Bucharest

    7/49

    Page 7 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    How does th is phase sh i ft in f luence t he pow erf l o w ?

    The natural current distribution is dependent on theimpedance of the lines

    i1

    i2

    X1

    X2

    i total

    VS VL

    V

  • 8/2/2019 Presentation PST_en, Bucharest

    8/49

    Page 8 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    i1

    i2VS VL

    V

    V

    The natural distribution may be rather inefficient, if X1 andX2 are extremely different.For example if X1 = 2*X2:

  • 8/2/2019 Presentation PST_en, Bucharest

    9/49

    Page 9 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    Equal iza t ion o f cur rent s :

    An additional voltage source must be introduced

    i1 +

    i

    i2- iX1

    X2

    i total

    VS VL

    ~

    VS

    VPST V1

    V2

  • 8/2/2019 Presentation PST_en, Bucharest

    10/49

    Page 10 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    This additional voltage source, perpendicular to the phasevoltage, generates a circulating current, increasing i1 anddecreasing i2: V1

    i1+ i i2- iVPST

    V2

    V2

    V1

    VLVS VS

    VPST

  • 8/2/2019 Presentation PST_en, Bucharest

    11/49

    Page 11 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    P P QV

    XN

    0 0

    2

    cos sin sin

    Pow er Transfer t hrough Phase Shi f t ing TransformerPrecondition: The voltage at two system nodes which are connected by a line with the

    PST in series is assumed to be independent from the PST phase angle

    VN Nominal system voltage, phase - phaseX Impedance of PST + line (X = XPST + Xline)

    no load phase angle of the PST

    P0 active power flow through PST at phase angle = 0Q0 reactive power flow through PST at phase angle = 0

    P active power flow through PST at no load phase angle Q reactive power flow through PST at no load phase angle

    Q P QV

    XN

    0 0

    2

    1sin cos cos

  • 8/2/2019 Presentation PST_en, Bucharest

    12/49

    Page 12 Power Transmission and DistributionBucharest 2012

    Purpose und function of PSTs

    -0,75

    -0,5

    -0,25

    0

    0,25

    0,5

    0,75

    1

    -0,50 -0,25 0,00 0,25 0,50 0,75 1,00 1,25 1,50

    P(p.u.)

    Q(

    p.u.

    )

    PST pow er f low range as funct ion o ft hroughput load a t zero degree phase sh i f t

  • 8/2/2019 Presentation PST_en, Bucharest

    13/49

    Page 13 Power Transmission and DistributionBucharest 2012

    Categories and types

    Phase shi f t ing t ransform ers can be c lass i f iedfo r d i f fe ren t paramet ers : symmetrical non symmetrical quadrature - non quadrature

    single core - two core

    single tank - two tank

  • 8/2/2019 Presentation PST_en, Bucharest

    14/49

    Page 14 Power Transmission and DistributionBucharest 2012

    Categories and types

    Non-sym m etr ic a l sing le

    core so lu t ion :

    Advantageous for small phase angle,

    Voltage and rating (appr. 15 -20)

    Reversing switch operation is critical

    Delta-connected exciting

    winding, One tap winding One LTC One reversing change-over

    switch

    Phasor Diagram:

    L1 S1

    L2

    S3

    S2

    L3

    Winding Connection with Reversing Switch:

    S3 L2 S1 L3 S2L1

  • 8/2/2019 Presentation PST_en, Bucharest

    15/49

    Page 15 Power Transmission and DistributionBucharest 2012

    Categories and types

    Symm etr ic a l sing le c ore

    so lu t ion :

    Load tap changers exposed to system

    disturbances

    Rating strongly limited by LTC

    Delta-connected

    exciting winding Two tap windings Two tap changers Two advance retard

    switches

    L1 S1

    L2S3

    S2L3

    Phasor Diagram:

    L1 S1 L2 S2 L3 S3Winding Connection with two ARS Switches:

  • 8/2/2019 Presentation PST_en, Bucharest

    16/49

    Page 16 Power Transmission and DistributionBucharest 2012

    Categories and types

    Zig-zag st y le so lut ion

    Common application in Central Europe

    Voltage regulation with phase shifting

    Double wound substation

    transformer Tap changer with phaseshifting option

    Phasor diagrammax. +

    advance

    zero

    H3

    max. -

    H2

    H1

    retard

    H2H2

    H3H3

    H1H1

    Winding arrangement and connections:

    reversingswitch

    Phase shift

    selectorswitch

    H1 H2H3X1 X2 X3

  • 8/2/2019 Presentation PST_en, Bucharest

    17/49

    Page 17 Power Transmission and DistributionBucharest 2012

    Categories and types

    Class ic so lu t ion :

    Widely used for high voltages and ratings

    Phase Shifting Transformer

    Winding Arrangement and Connections:

    S1 L1 S2 L2 S3 L3

    a b c

    Phasor Diagram:

    a

    bc

    Secondary (regulating) circuit

    S1

    L2S3

    S2L3

    L1

    Primary circuit

    Symmetrical two core

    design Series unit and excitingunit

    One LTC

  • 8/2/2019 Presentation PST_en, Bucharest

    18/49

    Page 18 Power Transmission and DistributionBucharest 2012

    Categories and types

    Non-symm etr ic a l op t ion :

    Solution for small phase angles

    Standard UK solution

    Quadrature Booster

    Phasor Diagram:

    a

    bc

    Secondary (regulating) circuit

    S1

    L2

    S3 S2L3

    L1

    Primary circuit

    Winding Arrangement and Connections:

    S1 L1 S2 L2 S3 L3

    a b c Dual core design

    Series unit andexciting unit One LTC simple HV

    connection

  • 8/2/2019 Presentation PST_en, Bucharest

    19/49

    Page 19 Power Transmission and DistributionBucharest 2012

    Categories and types

    Non-symm etr ic a l op t ion :

    Mainly used in Europe

    Combination of autotransformer with PST

    Dual core design

    Autotransformer and

    single core phase shiftingunit Phase angle regulation

    and in phase voltageregulation

    1U

    3 V 3 W

    2 U 1 V 2V 1W 2 W

    3U

    1U

    2U

    1U

    1V

    2V

    1W

    2W

    3U

    3V

    3W

    1U

    3 V 3 W

    2 U 1 V 2V 1W 2 W

    3U

    1U

    3 V 3 W

    2 U 1 V 2V 1W 2 W

    3U

    1U

    2U

    1U

    1V

    2V

    1W

    2W

    3U

    3V

    3W

    1U

    2U

    1U

    1V

    2V

    1W

    2W

    3U

    3V

    3W

  • 8/2/2019 Presentation PST_en, Bucharest

    20/49

    Page 20 Power Transmission and DistributionBucharest 2012

    Operational considerations

    Phase sh i f t i ng t ransform ers in Operat ion :Variation of load voltage due to load current,ohmic components neglected

    iLXPST

    VS VL

    ~

    VPST

    VL0

    j XPST* iL

    iL

    VL VSVL0

    j XPST* iL VPST

  • 8/2/2019 Presentation PST_en, Bucharest

    21/49

    Page 21 Power Transmission and DistributionBucharest 2012

    Operational considerations

    V ol t age a c ro ss PST

  • 8/2/2019 Presentation PST_en, Bucharest

    22/49

    Page 22 Power Transmission and DistributionBucharest 2012

    Operational considerations

  • 8/2/2019 Presentation PST_en, Bucharest

    23/49

    Page 23 Power Transmission and DistributionBucharest 2012

    Operational considerations

  • 8/2/2019 Presentation PST_en, Bucharest

    24/49

    Page 24 Power Transmission and DistributionBucharest 2012

    Operational considerations

  • 8/2/2019 Presentation PST_en, Bucharest

    25/49

    Page 25 Power Transmission and DistributionBucharest 2012

    Operational considerations

  • 8/2/2019 Presentation PST_en, Bucharest

    26/49

    Page 26 Power Transmission and DistributionBucharest 2012

    Operational considerations

    arctan

    cos

    sin

    I

    Ix

    II

    x

    N

    PST

    N

    PST

    1

    Var ia t ion of phase shi f t due to t he load cur ren t

    variation of phase angle due to load current

    I current through PST

    IN nominal PST current

    xPST impedance of PST (pu)

    angle between load voltage and load current(cos = power factor of load)

  • 8/2/2019 Presentation PST_en, Bucharest

    27/49

    Page 27 Power Transmission and DistributionBucharest 2012

    Operational considerations

    d e l t a a l p h a

    a l p h a ( l o a d ) = a l p h a ( n o - l o a d ) + / - d e l t a a l p h a

    0 ,00

    1 , 00

    2 , 00

    3 , 00

    4 , 00

    5 , 00

    6 , 00

    7 , 00

    8 , 00

    9 , 00

    10 , 00

    11 , 00

    12 , 00

    0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

    i m p e d a n c e ( % )

    Rei he1 Re i he2

    Reihe 1=p.f. 0.9, Reihe 2=p.f. 1.0

  • 8/2/2019 Presentation PST_en, Bucharest

    28/49

    Page 28 Power Transmission and DistributionBucharest 2012

    Operational considerations

    Effec t of load on effe ctive phase a ngle

    -6 0

    -4 5

    -3 0

    -1 5

    0

    15

    30

    45

    -16 -12 -8 -4 0 4 8 12 16

    tap pos ition

    p

    h

    ase

    an

    g

    le

    (d

    eg

    re

    e)

    pf 0 .8 , 100% In p f 1.0, 100% In pf -0 .8 , 100% In no - load

  • 8/2/2019 Presentation PST_en, Bucharest

    29/49

    Page 29 Power Transmission and DistributionBucharest 2012

    Operational considerations

    Impedance as low as possible, minimum valuedetermined by short circuit requirements

    With lower impedance, the no load phase angle can bereduced

    Lower no load phase angle means lower design rating,lower weight, lower cost.

    For a g iven phase shi f t under load, designopt i m izat ion is poss ib le :

  • 8/2/2019 Presentation PST_en, Bucharest

    30/49

    Page 30 Power Transmission and DistributionBucharest 2012

    Operational considerations

    Bypass breaker cons idera t ions

    Due to the PSTs impedance, inserting the PST withphase angle zero normally reduces the load flow

    A minimum advance phase angle is necessary to restore

    the original load flow condition

    Therefore, by-passing the PST might be advantageous incertain conditions

    On the other hand, lightning strikes can also appear with

    the PST by-passed Internal stresses have to be investigated carefully for this

    condition

  • 8/2/2019 Presentation PST_en, Bucharest

    31/49

    Page 31 Power Transmission and DistributionBucharest 2012

    Tap changer application

    PSTs can be designed with fixed or variable phase angle.

    For a variable phase angle design, a load tap changer(LTC) and a regulating winding is required.

    In general, the regulating winding and therefore the LTCmust be designed for the maximum design rating of thePST.

    The maximum regulating capacity (switching capacity perstep times the number of steps) is limited by the capacity

    of available tap changers.

    Tap changer app l ica t ion

  • 8/2/2019 Presentation PST_en, Bucharest

    32/49

    Page 32 Power Transmission and DistributionBucharest 2012

    Tap Changer Application

    Power needed to reach a certain displacement in phase angle

    Palpha = 2 x Pthr x sin alpha/2

    Is proportional to the throughputpower and almost proportional to thephase angle

    Palpha rating of the series winding resp. phase shift ing power (MVA)Pthr throughput power (MVA)alpha no-load phase angle (degree)

  • 8/2/2019 Presentation PST_en, Bucharest

    33/49

    Page 33 Power Transmission and DistributionBucharest 2012

    Tap changer application

    Calculation of the max. possible throughput power at a given phase

    angle

    Assumption:

    Approx. 5500kVA step capacity of the LTC (includes retard operation only advanced 6000kVA possible)

    Palpha = 5.5 x k x 3 (phases) x 32 (steps) x / sin alpha/2

    k.correction factor (function of max. phase angle)

    Example: 48 degrees

    Palpha = 5.5 x 0.914 x 3 x 32 x x sin 48/2 = 593 MVA

    Difference to a transformer:For a troughput rating of 600MVA and a in-phase voltage regulation of +/-15% only 0.15 x 600 = 90 MVA

    have to be switched by the on-load tap changer.

  • 8/2/2019 Presentation PST_en, Bucharest

    34/49

    Page 34 Power Transmission and DistributionBucharest 2012

    Tap changer application

    Throughput power versus no-load phase angle

    step capacity 5000 - 6000 kVA, +/32 steps

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    200 400 600 800 1000 1200 1400 1600 1800

    throughput power (MVA)

    no-loadp

    hase

    angle

    (de

    gree)

    5500kVA

    5000kVA

    6000kVA

  • 8/2/2019 Presentation PST_en, Bucharest

    35/49

    Page 35 Power Transmission and DistributionBucharest 2012

    Testing

    Test ing phase shi f t i ng t ransform ers :

    Heat run

    PST fully assembled minimized deviation of loss distribution during short circuit condition access to all windings for resistance measurement

    Specific requirements:

    Dielectric tests

    PST fully assembled and connected necessary to get conditions

    like in service

    Induced voltage test

    tests at zero and maximum phase shift

  • 8/2/2019 Presentation PST_en, Bucharest

    36/49

    Page 36 Power Transmission and DistributionBucharest 2012

    Testing

    Heat run t es t :

    For resistance measurement, all these connections can be opened

    Temporary bushings inserted at all connections between series and exciting unit

    ~

    Series Transformer

    Exciting Transformer

    Auxiliary

    Bushings

    Short circuit connection

  • 8/2/2019 Presentation PST_en, Bucharest

    37/49

    Page 37 Power Transmission and DistributionBucharest 2012

    Testing

    Induc ed vol tage t es t :

    Application of an additional step-up transformer is avoided by proper tap selection

    Temporary bushings are connected to the regulating winding

    S2 L2 S3 L3S1 L1

    Series Transformer

    Exciting Transformer

    ~ Auxiliary bushings

  • 8/2/2019 Presentation PST_en, Bucharest

    38/49

    Page 38 Power Transmission and DistributionBucharest 2012

    Testing

    L ight n ing impu lse tes t :

    Recommended test if by-pass breaker is provided - at least for tap position zero (0)

    Only the primary windings of one phase are shown

    L2S2 S2 L2

    Standard LI test:

    Source- andload- terminalconnected

    Special LI test:

  • 8/2/2019 Presentation PST_en, Bucharest

    39/49

    Page 39 Power Transmission and DistributionBucharest 2012

    Testing

    -50

    0

    50

    100

    150

    0 40 80 120T(s)

    V(%)

    Applied voltage and typical wave shape of voltage at crossover during lightningimpulse test with source and load side terminals connected

    L ight n ing impu lse s t resses in t he ser ies w ind ing

  • 8/2/2019 Presentation PST_en, Bucharest

    40/49

    Page 40 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Two-tank designTwo-core design

    Classical design PST

    700MVA, 230kV, 60Hz

    32no load ( 24Taps); 22.2..-41.8load

    uk: 11.1% Tap 0; 17.4% Tap 24

    Noise Level < 74 dB(A) with fans

  • 8/2/2019 Presentation PST_en, Bucharest

    41/49

    Page 41 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Classical design PST

    Two-tank designTwo-core design

    700MVA, 230kV, 60Hz

    32no load (24 taps);

    22.2at rated load - extreme advance

    -6.3at rated load - mid tap (0)

    -41.8at rated load - extreme retard

    uk: 11.1% Tap 0; 17.4% Tap 24

  • 8/2/2019 Presentation PST_en, Bucharest

    42/49

    Page 42 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Two-tank designTwo-core design

    Classical design PST

    800MVA, 230kV, 60Hz

    35no load ( 32Taps); load 25.3..-44.9

    uk: 11.4% Tap 0 ; 17.6% Tap 32

    Noise Level < 77dB(A)

  • 8/2/2019 Presentation PST_en, Bucharest

    43/49

    Page 43 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Classical design PST

    300 MVA, 138 kV, 60 Hz

    25.0at no load ( 16 taps);

    14.4at rated load - extreme advance

    -5.4at rated load - mid tap -35.6at rated load - extreme retard

    uk: 9.5% Tap 0; 18.6% Tap 16

    Noise level < 70 dB(A)

    Single-tank designTwo-core design

  • 8/2/2019 Presentation PST_en, Bucharest

    44/49

    Page 44 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Classical design PST

    Two-tank designTwo-core design

    575 MVA, 345 kV, 60 Hz

    37,8no load (16 taps);

    27.6at rated load - extreme advance

    -4.9at rated load - mid tap -48.0at rated load - extreme retard

    uk: 8.5% Tap 0 (NR); 17.94% Tap 32 (16R)

    Noise level < 68 dB(A) @ 345 kV

  • 8/2/2019 Presentation PST_en, Bucharest

    45/49

    Page 45 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Classical design PST

    234 MVA, 138 kV, 60 Hz

    25no load ( 16 taps)

    14.4at rated load - extreme advance

    -5.4at rated load - mid tap (0)

    -35.6at rated load - extreme retard uk: 7.62% Tap 0; 18.25% Tap 16

    Noise limit - Octave Band

    Limits M1-R New York

    125 250 500 1000 2000 [Hz]

  • 8/2/2019 Presentation PST_en, Bucharest

    46/49

    Page 46 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Single-tank designSingle-core design

    Delta hexagonal PST

    150MVA, 138kV, 60Hz

    32.9no load ( 16 taps)

    30.1at rated load tap 1

    0.0at rated load tap 17

    uk: 5% tap 1; 0% tap 17

  • 8/2/2019 Presentation PST_en, Bucharest

    47/49

    Page 47 Power Transmission and DistributionBucharest 2012

    Recent PST units

    Phase Sh i f t ing Transformer

    Classical design PST

    Two-tank designTwo-core design

    1200MVA, 400kV, 50Hz

    24no load (32 taps);

    16.6at rated load - extreme advance

    -5.3at rated load - mid tap (0)

    -31.4at rated load - extreme retard

    uk: 9.25% Tap 0; 13.0% Tap 32

    Noise power level < 80 dB(A) - sound house

  • 8/2/2019 Presentation PST_en, Bucharest

    48/49

    Page 52 Power Transmission and DistributionBucharest 2012

    Conclusion

    Phase shifting transformers look similar to normalpower transformers, and they are manufacturedusing the same technology.However, there are some aspects in design andtesting, which only appear in PSTs and therefore

    require special consideration.

    The classical two-tank two-core solution offers thegreatest security in operation at higher voltagelevels as the LTC is not directly exposed to systemdisturbances.

    The single-core solution offers economicadvantages at lower system voltage levels.

  • 8/2/2019 Presentation PST_en, Bucharest

    49/49

    Page 53 Power Transmission and DistributionBucharest 2012

    Thank you foryour attention !