Pres11 - Selective Coordination 2-02

60
© 2001 Cooper Bussmann, Inc. Suggestion on How to Use Industry Trainers are encouraged to use this material in their sessions Download both the PowerPoint file (.ppt) and script file (.pdf) Print the script file (.pdf) and read the script as you view the PowerPoint presentation in the “Slide Show” view. In this way you see the slides in large format and have animation (if there is any) Must have PowerPoint and Adobe Reader application software on your system.

description

ljk

Transcript of Pres11 - Selective Coordination 2-02

Page 1: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Suggestion on How to Use

• Industry Trainers are encouraged to use this material in their sessions

• Download both the PowerPoint file (.ppt) and script file (.pdf)

• Print the script file (.pdf) and read the script as you view the PowerPoint presentation in the “Slide Show” view. In this way you see the slides in large format and have animation (if there is any)

• Must have PowerPoint and Adobe Reader application software on your system.

Page 2: Pres11 - Selective Coordination 2-02

Selective Coordination

Page 3: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

• For 600 Volts & less

• Easy concept to understand

• Hard to verify, if you do not know what to look for

• Misinterpretations or lack of understanding is very prevalent

• People review curves (hand drawn or computer generated) and they do not know how to interpret

Page 4: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

Definition:

The act of isolating a faulted circuit from the remainder of the electrical system, thereby eliminating unnecessary power outages. The faulted circuit is isolated by the selective operation of only the overcurrent protective device closest to the overcurrent condition.

Page 5: Pres11 - Selective Coordination 2-02

Without Selective Coordination With Selective Coordination

Selective Coordination: Avoids BlackoutsSelective Coordination: Avoids Blackouts

OPENS

NOT AFFECTED

UNNECESSARYPOWER LOSS

OPENS

NOT AFFECTEDFault Faul

t

Page 6: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination: NEC®

240.2 Definitions

Coordination.

The proper localization of a fault condition to restrict outages to the equipment affected, accomplished by the choice of selective fault-protective devices.

Page 7: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination: NEC®

240.12 Electrical System Coordination where orderly shutdown required to minimize hazards

620.62 Selective Coordination required where more than one elevator is supplied by single feeder.

517.17 Selective coordination between main and feeder required for health care facilities where main has GFP (feeder also required to have GFP).

Page 8: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

Chapter 2 Video

Selective Coordination

Page 9: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

Coordination

Circuit Breakers

Page 10: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Bimetal

Magnetic Element

Line

Load

Trip BarCircuit Breaker

Operation

Page 11: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Bimetal

Line

Load

Trip Bar Thermal Overload Operation

Normal State

Page 12: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Line

Load

Trip Bar

Bimetal

Thermal Overload Operation

Unlatch & Open

Page 13: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Magnetic Element

Line

Load

Trip Bar Short Circuit Operation

Normal State

Page 14: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsUnlatch

Magnetic Element

Line

Load

Trip Bar Short Circuit Operation

Unlatching

Page 15: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Magnetic Element

Line

Load

Trip Bar Short Circuit Operation

Opening

Page 16: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Spring Loaded ContactsLatch

Magnetic Element

Line

Load

Trip Bar Short Circuit Operation

Cleared

Page 17: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Coordination - Thermal-Mag Circuit BreakersCoordination - Thermal-Mag Circuit Breakers

Thermal Magnetic Molded Case Circuit Breaker Time-Current Curve Overload Region

Instantaneous RegionInterrupting TimeUnlatching Time

Interrupting RatingInterrupting Rating

Page 18: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Coordination - Thermal-Mag Circuit Breakers (See SPD)Coordination - Thermal-Mag Circuit Breakers (See SPD)

Page 19: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

Current

Tim

e

A

B

C

D

4000A Fault

Page 20: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

OPENS

NOT AFFECTED

UNNECESSARYPOWER LOSS Fault

Lacking Coordination

Page 21: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination - Insulated Case Circuit Breakers (See SPD)

Selective Coordination - Insulated Case Circuit Breakers (See SPD)

2000A Insulated Case Circuit Breaker STD Is an Option - Allows breaker to delay opening Instantaneous Override built-in: may be as low as 12X the breaker rating Will often result in lack of coordination

Page 22: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination - Insulated Case Circuit Breakers (See SPD)

Selective Coordination - Insulated Case Circuit Breakers (See SPD)

2000A Insulated Case with STD and Instantaneous Override and 100A Molded Case Thermal Magnetic Circuit breaker - NO Coordination in Short-Circuit Region (above 21,000A)

Page 23: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination - LV Air Power Circuit Breakers (See SPD)Selective Coordination - LV Air Power Circuit Breakers (See SPD)

Short Time Delay - Allows the fault current to flow for up to 30 cycles.

Used to coordinate with downstream

Subjects equipment to high mechanical and thermal stresses, often violating 110.10

Arc Flash/ Blast Risks Much Higher

High Cost, Larger Equipment

Page 24: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination: Fuses

Page 25: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Page 26: Pres11 - Selective Coordination 2-02
Page 27: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Time Current Curves

Selective Coordination:Fuses (See SPD)

Page 28: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selectivity Ratio

Guide Based on

Thermal Principle

Based on I2t Clear Clear

Not MeltNot Melt

I2t melting > I2t Clearing 1200 A 600 A

Selective Coordination:Fuses (See SPD)

Page 29: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination (See SPD )

Selectivity Ratio Table Assures Coordination!No Plotting required!

LOW-PEAK® : LOW-PEAK®

2:1 Line:Load Ratio

Lin

e S

ide

Fu

se

Load Side Fuse

Page 30: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Example:

Main: KRP-C 1200 SP

Feeder: LPS-RK 200 SP

Branch: LPS-RK-30 SP

MSB

1200 A

200 A

30 A

480V, 3 phase

MCC

GFP

Selective Coordination - Fuses

Page 31: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination - Fuses

Use Selectivity Table

Main KRP-C 1200 SP

Feeder LPS-RK 200 SP

Branch LPS-RK 30 SP

What happens: Branch Circuit Isca = 5000 A or 50,000A or 300,000A ?

Page 32: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Lineside KRP-C 1200SP to Loadside LPS-RK 200SP

1200/200 = 6:1 Table only need 2:1 Selective Coordination

Lineside LPS-RK 200SP to Loadside LPS-RK 30SP

200/30= 6.67:1 Table only need 2:1

Selective Coordination

Selective Coordination- Fuses

Page 33: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Fault

NOT AFFECTED

OPENS

Selective Coordination

Page 34: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

Simple Rules for Checking

• Circuit Breakers (instantaneous trip)

• Fuses

Page 35: Pres11 - Selective Coordination 2-02

Can you look at this Can you look at this and assess whether and assess whether coordinated?coordinated?

You do not even You do not even need to draw curve!need to draw curve!

Page 36: Pres11 - Selective Coordination 2-02

Simple Rule:Simple Rule:(Amp rating) x (I.T. setting) =(Amp rating) x (I.T. setting) = Isca @ which CB will unlatch:Isca @ which CB will unlatch:

CB IT ITCB IT IT Amp Amp Set Set Amp PickupAmp Pickup 100 5X100 5X 500 500 200 5X200 5X 1,000 1,000 400 10X 4,000400 10X 4,0001600 12X1600 12X 19,00019,000

See SPD See SPD

100 A100 A200 A200 A

400 A400 A

1600 A1600 A

Page 37: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

• You already know the simple rule for fuses.

• Simply use amp rating ratios

• Typically 2:1 for

Low Peak Fuses to Low Peak Fuses

Page 38: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Selective Coordination

• Do coordination exercise using simple rules– Fusible system

– Circuit breaker system

• It’s simple!

Page 39: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Fault 10000 Amps

Low PeakKRP-C 1000 SP

Low PeakLPJ 200 SP

Low PeakLPJ 20 SP

Are These Selectively Coordinated?

Page 40: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Fault 10000 Amps

Low PeakKRP-C 1000 SP

Low PeakLPJ 200 SP

Low PeakLPJ 20 SP

Are These Selectively Coordinated?

OPENS

NOT AFFECTED

Fault 10000 Amps

Low PeakKRP-C 1000 SP

Low PeakLPJ 200 SP

Low PeakLPJ 20 SP

Selectively Coordinated

Page 41: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Are These Selectively Coordinated?

Fault 10000 Amps

1000 A. CBIT @ 10 X

200 A. CBIT @ 10 X

20 A. CBIT @ 10X

Page 42: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Are These Selectively Coordinated?

Fault 10000 Amps

1000 A. CBIT @ 10 X

200 A. CBIT @ 10 X

20 A. CBIT @ 10X

Not Coordinated

OPENS

NOT AFFECTED

Fault 10000 Amps

1000 A. CBIT @ 10 X

200 A. CBIT @ 10 X

20 A. CBIT @ 10X

Page 43: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

UnnecessaryBlackout

The Issue:Lack of coordinationtakes out other loads

OPENSFault 10000 Amps

1000 A. CBIT @ 10 X

200 A. CBIT @ 10 X

20 A. CBIT @ 10X

Page 44: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Ground Fault Protection 230-95

Page 45: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

See SPDSee SPD

Page 46: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

GFP Health Care 517-17

Where one level of GFP is provided per 230.95 or 215.10 an additional step of GFP on feeders required.

The Ground Fault Protection for service and feeder shall be fully Selectively Coordinated

What does this mean ?

Page 47: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

517-17 Health Care GFP

Main 1200 A CB

Feeder 200 A CB

GFP on Main & Feeder

Does this meet 517-17?

Page 48: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

517-17 Health Care GFP

Main 1200 A Fuse

Feeder 200 A Fuse

GFP on Main & Feeder

Does this meet 517-17?

Page 49: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

Following Excerpts from IEEE Standards

Page 50: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 242-1986 “BUFF BOOK”Protection and Coordination of Industrial and Commercial Power Systems

Page 263 6.4.1 Protection (Series Connection). It should be noted that selectivity will not be provided at any current level where the breaker trip characteristic curves overlap when this protection scheme is used, that is, both circuit breakers will trip.

Page 51: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 242-1986 “BUFF BOOK”Protection and Coordination of Industrial and Commercial Power Systems

Page 528 Coordination 14.2.2

Coordination can easily be achieved with low voltage current-limiting fuses that have fast response times. Manufacturer’s time current curves and selectivity ratio guides are used for both overload and short-circuit conditions, precluding the need for calculating time intervals.

Page 52: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 141-1993 “RED BOOK” Electrical Power Distribution for Industrial Plants

Page 256 5.7.2.3 Low-voltage circuit breakers. To achieve this level of selectivity, power circuit breakers utilize short-time delay trips. The equipment protected by this breaker must be designed to handle the available short-circuit current for the duration of the short-time delay.

Page 53: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 242-1986 “BUFF BOOK”Protection and Coordination of Industrial and Commercial Power Systems

Page 528 Coordination 14.1 A coordination study should be made when the available short-circuit current of the source to the plant is increased.

Page 54: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 242-1986 “BUFF BOOK”Protection and Coordination of Industrial and Commercial Power Systems

Page 528 Coordination 14.1 A coordination study or revision of a previous study may be needed for an existing plant when new loads are added to the system or when existing equipment is replaced with higher rated equipment.

Page 55: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 602-1996 “WHITE BOOK”Electrical Systems in Health Care Facilities

Page 57/58 3.7.1.1 Protection requirements. As total selectivity and maximum safety to personnel are critical, a total short-circuit coordination, and component protection study shall be performed.

Page 56: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 141-1993 “RED BOOK” Electrical Power Distribution for Industrial Plants

Page 256 5.7.2.3 Low-voltage circuit breakers. It should be recognized that providing selectivity to the load-side devices may result in equipment bus structures being underprotected. The Standards for such equipment, ANSI/UL 891-1984 [B21] for switchboards, ANSI/UL 845-1987 [B20] for motor control centers,

Page 57: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems

Page 135 5.5.4 Short-time delay

All MCCBs and most ICCBs with a short time delay have an instantaneous override. If selective coordination is required for fault currents above the instantaneous override level, a power circuit breaker defined as an LVPCB with a short-time delay option, as shown in Figure 5-16, should be considered.

Page 58: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 242-1986 “BUFF BOOK”Protection and Coordination of Industrial and Commercial Power Systems

Page 252 6.3 Trip Unit The resulting combination of long-time delay and short-time delay characteristics provides delayed tripping for all levels of overcurrent below the instantaneous response. This provides time for downstream circuit breakers to operate and clear the fault. The withstand of other electrical components in the current path should be checked to be certain they can handle the additional stress associated with the longer clearing time.

Page 59: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems

Page 62 3.38 Series-connected rating. Sometimes it is erroneously thought that series combinations are at a disadvantage with regard to coordination as compared to fully rated systems. The fact is that even fully rated circuit breakers with instantaneous trips will not “coordinate” once the fault level exceeds both circuit breakers’ instantaneous trip levels.

Page 60: Pres11 - Selective Coordination 2-02

© 2001 Cooper Bussmann, Inc.

IEEE 1015-1997 “BLUE BOOK” Applying Low-Voltage Circuit Breakers Used in Industrial and Commercial Power Systems

Page 134 5.5.3 Series MCCBs

Selective coordination is limited to currents below the instantaneous pickup of the line-side circuit breaker. For any fault downstream of the load-side MCCB having a current greater than the instantaneous pickup of the line-side MCCB, both circuit breakers trip, and power is interrupted to unfaulted circuits fed by the line-side circuit breaker.