Practical Remediation Guidance

16
September 2015 PRACTICAL REMEDIATION GUIDANCE for RMG Factories, Signatory Companies and Trade Unions

Transcript of Practical Remediation Guidance

Page 1: Practical Remediation Guidance

ManualFIRE SAFETYfor existing RMG buildings

September 2015

PRACTICAL REMEDIATION GUIDANCEfor RMG Factories, Signatory Companies and Trade Unions

Page 2: Practical Remediation Guidance

2|16

INDEX

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

Appendix A: List of Suppliers and Vendors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

Appendix B: Fire Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Appendix C: FAQs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

Page 3: Practical Remediation Guidance

3|16

INTRODUCTION

This Practical Remediation Guidance provides factory owners, managers, signatory companies and trade unions with answers to common remediation queries that the Accord is receiving regarding: • List of equipment suppliers and vendors, • Fire Alarm and Fire Protection system designs• Locking features, collapsible gates/sliding doors/rolling shutters• Firedoorcertification• Detailedengineeringassessmentsandstructuralretrofittingworks

1. LIST OF SUPPLIERS:

Thelistofsupplierswehavecompiledtohelpfactoriestosourcefireequipmentisbasedonthe information provided by the suppliers. We do not make any quality check during the process of enlistment. The list is not an endorsement or approval by the Accord. There is no approved supplier list by the Accord. Please refer to Appendix A for an updated list of suppliers.

2. FIRE ALARM AND FIRE PROTECTION SYSTEM DESIGNS:

Allfirealarmdesigns,sprinklersystemdesignsandstandpipe(hydrant)designsshallbesubmitted to the Accord for review prior to installation. If the installation work is done without reviewed designs, the system might not be recognized by the Accord. Please refer to Appendix B for drawing submission criteria.

3. LOCKING FEATURES, COLLAPSIBLE GATES/SLIDING DOORS/ROLLING SHUTTERS:

Under the national building code and the Accord, Alliance, and BUET standards, collapsible doorsorgates(horizontal,vertical,roll-uporaccordionstyle)areprohibitedinRMGfactoryegress routes.

• All collapsible gates must be permanently removed from the doorways and stairways which lead to an exit of the building.

• There are no exceptions to this requirement. All lockable, collapsible gates must be removedfromallexitsfromtheRMGfactorybuildings.

• Fire doors can be equipped with security hardware and locks which permit locking from theoutsidewherethedoorcanstillbeopenedfromtheinside(evenwhenthedoorislockedfromtheoutside).

• Fire doors with permitted locking systems as described above provide the same level of security as collapsible gates.

• The time lines in the inspection report are to be followed strictly.

4. FIRE DOOR CERTIFICATION:

• Thefiredoorsmustbecertifiedandmanufacturedbyanauthorizedfiredoormanufacturing facility.

• ThereiscurrentlynoauthorizedmanufacturerofcertifiedfiredoorsinBangladesh.• ThereiscurrentlynoauthorizedBangladeshbasedcertifieroffiredoorsorfiredoor

manufacturing facilities.• Pleaseexercisecarenottopurchasedoorswhicharenotcertified: the

inspectionsinitiativesarereceivinginformationthatfiredoorsarebeingmarketedwhichhaveinauthenticsealsorlabelswhicharenotreallycertifieddoors.Thesedonotmeetthe Accord, Alliance, or national standards. If installed, they would have to be replaced byactualcertifiedfiredoors.

• Toverifythedooryouarepurchasingiscertified:Ask the supplier for the 3rd partycertification(i.e.UL,FM,Intertek,Warrington).Factoryownercanthenchecktheonlinedirectorytoverifytheauthenticityofthe3rdpartycertificationusingthemanufacturer’straceableidentificationnumberwhichisonthedoorratinglabel.

• Firedoorsshallbeequippedwithpanichardwareandaself-closingdevice.Thedoormust close and latch after each use, or be equipped with a magnetic hold open device

Page 4: Practical Remediation Guidance

4|16

designedtoreleaseonfirealarm.• Exitdoorsmustalwaysbeofthe“swing”type.Allfiredoorsmustswingout,inthe

direction of exit travel.• Allfiredoorhardwaresuchashinges,panicbar,selfcloser,visionpanelandlocksmust

alsobecertified.ThereiscurrentlynocertifiedhardwareproducedinBangladesh.ThereiscurrentlynoauthorizedBangladeshbasedcertifieroffiredoorhardwaremanufacturing facilities.

• Acceptablecertificationandauthorizationsforfiredoorsinclude:UL,FM,INTERTEK,Warrington etc.

IfanAccordfactorywishestoconfirmtheacceptabilityofafiredoorpriortopurchasing,theycansendallofthemanufacturer’sliteratureincludingtestingcertificationtotheAccordand we will determine acceptability. Please refer to Appendix Cforfiredoorrequirements.

5. DETAILED ENGINEERING ASSESSMENTS:

Please note the following considerations regarding DEAs:• WedonothaveanyshortlistofconsultingfirmstoconductDEAatthistime• The factory should get approval from the ACCORD before entering into a contract with

anyfirmtoconductaDEA.• OurrequirementsoftheconsultingfirmforconductingDEAsare: 5+yearsofexperienceoftheconsultingfirminrelevantfield 10+yearsofexperienceoftheconcernedengineerinrelevantfield• ThefinalDEAreportmustbeapprovedbytheACCORD.• NoretrofittingworkshallcommencewithoutapprovalfromtheACCORD.• For more details please contact the ACCORD Structural Team.NoadditionstobuildingsareallowedwithoutpriorapprovalfromtheAccord.

The Accord engineering team is available to advise on the above matters where necessary.Please contact them with any further queries:

MohammadShafiqUddin,[email protected]

Md.KamrujjamanGeneralManager–[email protected]

Shahin AzadAccord Lead Electrical [email protected]

Brad LoewenChief Safety [email protected]

Page 5: Practical Remediation Guidance

5|16

APPENDIX A

List of suppliers and vendors:

N.B.:Itissimplyalistofsuppliersthatweareawareof;itisnotanendorsementorapprovalby the Accord.

This is not an Approved list by the ACCORD.

SI Vendor Main Business area/s

Contact Person

Cell Number Email address

1. TRI-ZONE Fire Suppression System;HydraulicCalculation;FireAlarmSystem;FireDoors.

Mr.ZiaulIslamCEO

+8801670024098+8801977124627

[email protected]

2 Guraba Telecom Bangladesh Ltd.

Fire Suppression System;FireAlarmSystem;FireDoors

Mr.K.MShamsulHuq-CEO

+8801730704118 [email protected]

3 HARBINGERTRADING

Fire Suppression System;FireAlarmSystem;FireDoors.

Mr.MamunChowdhury-CEO

+8801711543485+8801938854767

[email protected]

4 MicroElectricalMechanicalSolutionLtd.

Fire Suppression System;FireAlarmSystem;

Md.ZafarHossainExecutive Director

+8801712834949+8801967700352

[email protected]

5 TheToolMaster&Eng. Co.

Fire Suppression System;FireAlarmSystem;FireDoors

AlMamun(Bulbul) +8801674634723 [email protected];[email protected]

6 MultisystemEng.Co.Ltd.

Fire Suppression System;FireAlarmSystem;

Mr.Nafis +8801720056249+8801755507628

[email protected];[email protected]

7 Symantec Technologies Ltd.

Fire Suppression System;FireAlarmSystem;FireDoors.

Mr.RashadulIslamAsst.Manager

+8801614047449+8801614047444

[email protected];[email protected]

8 Bengal International Agencies

Fire Suppression System;FireAlarmSystem;

Mr.ShahjahanSajuManagingDirector

+8801819405398+8801979405398

[email protected];[email protected]

9 Genesis Technologies Ltd.

Fire Suppression System;FireAlarmSystem;

Mr.OmarFarukDirector

+8801914067101 [email protected];[email protected]

10 ICEL Private Ltd. Fire Suppression System;FireAlarmSystem;FireDoors.

Mr.JavedMahmoodManagingDirector

+8801819777779+8801199856500

[email protected]

11 MultiProductEngineering Limited.

Fire Suppression System;FireAlarmSystem;FireDoors.

Mr.ProbodhKumarSahaGeneralManager

+8801713030108 [email protected]

12 ZMInternational Fire Suppression System;FireAlarmSystem;

Mr.ZakirUddinAhmed CEO

+8801920098535 [email protected]

13 Bangladesh Techno rise Limited

Fire Suppression System;FireAlarmSystem;

Mr.KausarulHakimManagingDirector

+8801711548167 [email protected]

14 Aim Tech Ltd Fire Suppression System;FireAlarmSystem;FireDoors.

Engr.AtaulKabirDirector

+8801755504218 [email protected]

Page 6: Practical Remediation Guidance

6|16

15 GRASSHOPER Fire Suppression System;FireAlarmSystem;FireDoors;PPE;

Md.MahmudurRashid-ManagingDirector;

+8801917960900+8801787671919

[email protected];[email protected]

16 NAVANAINTERLINKSLIMITED

Fire Suppression System;FireAlarmSystem;FireDoors.

PrashantaKumarSaha

01713426904;01939911899

[email protected]

17 MorgenInternational Fire Suppression System;FireAlarmSystem;FireDoors.

Md.NiazAliChisty-CEO

+8801711531486 [email protected]

18 PacificEngineersInternational

Fire Suppression System;FireAlarmSystem;FireDoors.

Md.ShahnewajRashedi

+8801913511447 [email protected]

19 TECH.MEEngineeringPVTLtd.

Fire Suppression System;FireAlarmSystem;FireDoors

SujitKumarDey +8801713002402 [email protected]

20 Emkay Enterprises Ltd.

Fire Suppression System;FireAlarmSystem;FireDoors

SAMToufiqulAlam +8801766666910 [email protected]

21 ZedTechnology FireHydrantandFire Alarm System

AnwarHossain +8801790111188, +8801977411188

[email protected];[email protected];web:www.zedtechbd.com

22 OLYMPIAFIREPROTECTION

Fire Suppression System;FireAlarmSystem;FireDoors

MD.WAHIDUDDIN(DIRECTOR)

+8801711546983 [email protected];www.ofpbd.net

23 ATSGROUP(Al-AminTradeSyndcate)

Fire Suppression System;FireAlarmSystem;FireDoors

M.A.KHANJEWELL

+8801911339990 [email protected]

24 ABG Engineering Services Ltd.

Fire Suppression System;FireAlarmSystem;

Mr.FerdousAlamManagingDirector

+8801713065871+8801973992702

[email protected];[email protected]

25 Faa Associates Ltd. Fire Doors Iqbal forkan +8801822220090 [email protected]

26 Sygra International Inc.

Fire Suppression System;FireAlarmSystem;FireDoors

MahbubChoudhury

+8801715505555 [email protected];www.sygraint.com

27 ProjectPlannerAndConsultant

Fire Suppression System;FireAlarmSystem;FireDoors

Md.NuruddinSohel;Chief Operating Officer

+8801913027001, +8801713044656

[email protected];www.projectplannerandconsultant.com

28 Auspicious Bangladesh

Fire Suppression System

Syed Golam Rabby +8801678005689 [email protected]

29 KSInternational Fire Suppression System;FireAlarmSystem;FireDoors

Md.WahedunabiMondal

+8801780222211 [email protected]

30 BENGALTECHNOLOGICALCORPORATIONLTD.

Fire Suppression System;FireAlarmSystem;FireDoors

ChandanKShahManagerProjects

+8801755579825 [email protected]

31 Ace Controls Limited Fire Suppression System;FireAlarmSystem;FireDoors

Md.AbdurRahmanSales Engineer

+8801915360345 [email protected];http://www.acecontrolsltd.com

32 MeghnaFireFightingand Equipments

Fire Suppression System;FireAlarmSystem;FireDoors

NurEAlam-ManagingDirector

+8801711234762 [email protected]

33 Pran RFL Group Fire Suppression System;FireAlarmSystem;FireDoors

Md.RashedulRahman

+8801912257271 [email protected];[email protected];www.pranrflgroup.com

Page 7: Practical Remediation Guidance

7|16

34 NewGenLtd. Fire Suppression System;FireAlarmSystem;FireDoors

Engr. Sheehab Quadir

+880186222222 [email protected];[email protected]

35 Atlantech Fire Suppression System;FireAlarmSystem;FireDoors

Shaklayen Shaheed (Joy)-CEO

+8801841504773;+8801747504773

[email protected]

36 ETAFIREALARM&SECURITYSYSTEM

Fire Suppression System;FireAlarmSystem;FireDoors

AbuSakerShohel-CEO

+8801736277433;+8801681524889.

[email protected]

37 Luminous Associates Fire Suppression System;FireAlarmSystem;FireDoors

Mohd.NoorNabi-Owner

+880189223168 [email protected]

38 Eastern Fire Solution Fire Suppression System;FireAlarmSystem;FireDoors

HMBulbulAhmed-MD

+8801726567062 [email protected]

39 MAMSAutomationSystems

Fire Suppression System;FireAlarmSystem;FireDoors

Fazlur Rahman Jewel;AssistantManager

+8801766676615 www.mamsbd.com

40 MechanismTrade&Engineering

Fire Suppression System;FireAlarmSystem;FireDoors

MDSAKHAWATHOSSAIN

+8801713273033;+8801712513770

[email protected],[email protected];[email protected], [email protected],

41 M/SSIGMAGROUP Fire Suppression System;FireAlarmSystem;

Preetam Basu +880-2-9122165,9128395

www.sigma-bd.com

42 Binary Signature Fire Suppression System;FireAlarmSystem;

Md.RafiqulIslam 01678629555-57 [email protected]

43 Soyeb Enterprise Fire Suppression System;FireAlarmSystem;

S.M.EzazShamim +8801711536235;+8801611536235;

[email protected]

44 ATCL Pvt. Ltd Fire Suppression System;FireAlarmSystem;

Md.AsrafulAlam +8801983603860 [email protected];[email protected]

45 Techno Apogee Fire Suppression System;FireAlarmSystem;

Md.MosaddiqueHossain

+8801714378008 [email protected]

46 MEPEngineeringConsultancy Firm

Fire Suppression System;FireAlarmSystem;

Engr.Md.MasudKawsar

+8801613837902;+8801710189680

[email protected];[email protected] (Office)

47 EMACOENGINEERING&TECHNOLOGYLimited

Fire Suppression System;FireAlarmSystem;

MohammadOmarFaruque

+8801817-181-250/+8801823-072-560

[email protected]

48 BAFFESCO Fire Suppression System;FireAlarmSystem;

ArickNikolasRecardo

[email protected]

49 Bangladesh Safety and Security Service

Fire Suppression System;FireAlarmand Security System

----- 029841405 [email protected]

50 Ezzy Automations Fire Suppression System;FireAlarmand Security System

MohammadShakilur Rahaman

+8801777757961 [email protected]

51 A3 Associates Ltd Building safety consultant(FireandElectrical)

Sakib Sarker +8801731 804030 [email protected]

Page 8: Practical Remediation Guidance

8|16

52 A4S Solution Fire Suppression System;FireAlarmand Security System

Md.SalimMiah +8801924100952 [email protected]

53 SothernMultiProducts Ltd.

FireAlarmSystem;Fire Doors

Md.MehediHasan +8801723888273 [email protected]

54 Aipro Engineering and Consultancy Services

Fire Suppression System;FireAlarmand Security System

Imran Udding Ahmed

+8801988181920 [email protected]

55 KuulmerchantLtd FireAlarmSystem;Fire Doors

Md.SalahUddin +8801611540455 [email protected]

56 NEWTECHBANGLADESHLTD.

Building Safety Consultant and supplier(Electrical&Fire)

CNQuader,CEO 01711546934, 01680005500.

[email protected]

57 ZipsEngineering Fire Suppression System;FireAlarmand Security System

ZiaulHaque 01911523911 [email protected]

58 HiTechErectionLtd AllKindofElectromechanical System Solution

M.A.Jalil 01752987423 [email protected]

59 Critical Stop Ltd Fire Doors Sumana Pervin 01191010832 [email protected]

60 New-TechInternational Ltd

AllKindofElectromechanical System Solution

Md.BalayetHossen +8801715113358 [email protected]

61 ModernErection(IS)Limited.

Fire Suppression System;

Engr.RafiqulAlam;Director

+8801711522928 [email protected]@melbd.com

62 Fire Pac Engineering Fire Suppression System;FireAlarmSystem

Engr.HemonKumarSaha;CEO

+8801717583339 [email protected]

63 NEOSafetySolutionsLtd.

Fire Suppression System;FireAlarmSystem;CCTVSystem;FireDoor;Floor marking

Engr.AwalHossain;Director

+8801916928963 [email protected]

64 MACRONFIRESAFETY&SECURITY

The Fire Protection Specialist.

A.K.MZobairAnsari;CEO

+8801713017646 [email protected]

65 Riant-techGroup Fire Suppression System with HydraulicCalculation;FireAlarmSystem;FireDoors;

Engr.Md.KaisarRijvi;ManagingDirector

+8801711105208 [email protected]

66 HazratAhmmadUllah Trading Company;

ITALLAFIREFIGHTIGSOLUTION

S.MShafiulbasherRipon;CEO

+8801711028580 [email protected]

67 VALUEEngineering FireSuppression System;FireAlarmSystem;CCTVSystem;

Engr.MamunChoudhury;Proprietor;

+8801199845753 [email protected]

68 MicroAutomation Md.AbuBakerSiddque;ManagingDirector

+8801716-242550 [email protected]

69 RECL-RoktechConsulting Engineering Ltd

Fire Suppression System;FireAlarmSystem;FireDoors

Engr. A Ahsan +8801713066403+8801713018292

[email protected]

Page 9: Practical Remediation Guidance

9|16

70 Safety First Pvt Ltd Supply and installation of all kindoffiresafetyappliances

M.HaqueMNI 031-2528170,+8801775771100+8801715070546

[email protected];[email protected]

71 Ixony Engineering Limited

Fire Suppression System;FireAlarmSystem;

MosfequrRahman +8801713 632703 [email protected]

72 Aces Corporate Solutions

Fire Suppression System;FireAlarmSystem;FireDoors

MohammedEakubAli

+8801714165846 [email protected];[email protected];www.acesbd.com

73 CEL Engineering Ltd Fire Suppression System;FireAlarmSystem;FireDoors

AkmolHossein +8801713069151 [email protected];[email protected]

74 The Alpha Engineering

Fire Suppression System;FireAlarmSystem;FireDoors

Md.KaosarUddin +8801712174597 [email protected];[email protected]

75 GURABA Engineering Ltd

Fire Suppression System;FireAlarmSystem;FireDoors

Engr.Md.MahaburRahman

+8801670886738 [email protected];[email protected]

76 SHAMAInternational Fire Suppression System;FireAlarmSystem;FireDoors

ShahidMahboob +8801711529515 [email protected];[email protected]

77 SPERRY INTERNATIONAL

Fire Suppression System;FireAlarmSystem;FireDoors

M.SHAHZADNAFEES

+8801911360565 [email protected];

78 Re-GreenBangla Fire Suppression System;FireAlarmSystem;FireDoors

MustaeemBChowdhury(Ratin)

+88 01717828450 [email protected]

79 VEGATech Fire Suppression System;FireAlarmSystem;

Shakiluzzahan Khan

+8801713194303 [email protected]

80 ElectronService(Pvt.)Ltd.

Fire Suppression System;FireAlarmSystem;

Sanaur Rahman +8801712869934 [email protected]

81 Star Tech Engineering Fire Suppression System;FireAlarmSystem;

MAHannan +8801731844024 [email protected]

82 ATCL Pvt. Ltd. Fire Suppression System;FireAlarmSystem;

Md.AbulHasanSobuz

+8801777192551+8801983603860

[email protected]

83 ElectroMechanicalServices

Fire Suppression System;FireAlarmSystem;

MD.MoshiurRahaman

+8801711828018+8801971828018

[email protected]

84 Genuine Technology Fire Suppression System;FireAlarmSystem;

Sayed KamruzzamanRussel

+8801714165188 [email protected]

85 FnG International Fire Suppression System;FireAlarmSystem;FireDoors

Engr.Md.KamalUddin

+8801927242066+8801716378297

[email protected][email protected]

86 OSL Engineering Co. (BD)Ltd

Fire Suppression System;FireAlarmSystem;FireDoors

MohammedMahbubHasan

+8801716851888+8801913428261

[email protected];[email protected]

87 ABG Interlinks Ltd Fire Suppression System;FireAlarmSystem;FireDoors

S.M.GofranulHoque

+8801713453249 [email protected]@gmail.com

88 FnGEngineering&Co.

Fire Suppression System;FireAlarmSystem;FireDoors

Md.KamalUddin +8801716378297 [email protected]

Page 10: Practical Remediation Guidance

10|16

89 Banmech Ltd. Fire Suppression System;FireAlarmSystem;

Md.ShayfulIslam +880165600900 [email protected];[email protected]

90 Shadhin Design and Development Ltd

Fire Suppression System;FireAlarmSystem;FireDoors

Md.SharifulIslam +8801713315155 [email protected]

91 PacificTrade&Technology Ltd.

Fire Suppression System;FireAlarmSystem;FireDoors

Sharfuddin Ahmed +8801713 [email protected]

92 BGTICGmbH UL Fire Doors, Fire-RatedRollingShutters,Fire-Rated Loading Bays

Ian Green,

RafiqHassan

+88 01787664771,+8801766497036;+49(0)17641600468

[email protected], [email protected]

93 MMSafety&SecurityLtd.

Fire Suppression System;FireAlarmSystem;FireDoors

Md.AbdulMatin +8801610007704 [email protected]

94 Amaze Corporation Ltd

Fire Suppression System, Fire Alarm &SecuritySystem,FireDoors&SafetyAppliances, Fire Pumps&Automation systems

Mr.MehdiHaroonSalesCo-ordinator

+8801766669911 [email protected]

95 Z3Corporation Fire Suppression System, Fire Alarm &SecuritySystem,FireDoors&SafetyAppliances, Fire Pumps&Automation systems

ZubayrShahidManagingDirector

Mob:+8801670990904Tel:+880(0)28835297Fax:+880(0)28835297

[email protected], [email protected];

96 Eastern Fire Fighting &CoLtd.

Fire Suppression System, Fire Alarm System

Md.MahmudulHassan

+8801715957949 [email protected]

97 DynSoL Fire Safety and Risk Assessment, Fire Suppression System, Fire Alarm System and Fire Doors

Engr.Md.BorhanulAkhtar

+8801717574145 [email protected]@dynsolonline.com

98 Environment, Compliance&Engineering Solutions (ECES)

Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

MohammadAktaruzzaman-CEO

+8801979883650 [email protected]

99 ZassGlobalLimited Fire Safety and Risk Assessment, Fire Suppression System, Fire Alarm System and Fire Doors

MD.TOWFIQUEMALEK-ManagingDirector

+8801822999097, +88 01977777357

[email protected]

100 ADROITTECHBANGLADESH

Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

Engr.MonsuruzZaman

+8801858361955, +8801625669782

[email protected]

Page 11: Practical Remediation Guidance

11|16

101 Fashion Accessories Fire Doors MuhammadAshiqur Rahman, Chief Executive

+8801711985551, +8801713372875

[email protected], [email protected]

102 UniversalMultiEngineering and Technology Company Limited(UMEC)

Fire Suppression System, Fire Alarm, Fire Doors, Hydrant&Sprinkler System, Safety Security System,CCTV&Access Control

MuhammadMostafizurRahman

+8801716096836, +8801924400279

[email protected],www.umec-bd.com

103 Shams Engineering Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

Engr.Md.Shamsuzzoha,Engr.Md.ShafiulAlam

+8801711111236 +8801777735301

[email protected];[email protected]

104 TASHAInternational Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

K.M.ShamsulHuq(Tareque)

+8801730704118 [email protected]

105 M-TechIntegratedSolutions Ltd.

Fire Safety, Fire Suppression System,HVACSystems, Steel Structure Solutions

Md.YousufAli +8801751593339 [email protected]

106 Prime Power Engineering

Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

NazmulHassanKhan

+8801816288772+8801674792841

[email protected]@gmail.com

107 Excel Technologies Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

AKMMostafizurRahman

+8801727 369678, 01911-332222,017070223333

[email protected]@yahoo.com

108 Compliance BD Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

Md.Al-Amin-CEO +88029358875, 01766670693, 01911643816

[email protected]@gmail.comwww.compliancebd.com

109 GREENLIGHT Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

ZahedOmar 01799626261-65 [email protected], [email protected] www.greenlightbd.org

110 Smriti Trading Corporation

Fire Alarm System andVoiceEvacuation System

Md.MuhaimeenAshraf

+8801755627982, +88029570556, +88029570561

[email protected], [email protected]

111 AB Technology Corporation Ltd.

Fire Safety, Fire Suppression System, Fire Alarm System and Fire Doors

Engr.Md.BabulAkhter

01865002388/01711117180,0447811780

[email protected]

The list will be updated frequently.

Page 12: Practical Remediation Guidance

12|16

APPENDIX B

FIRE ALARM SYSTEM

Each submittal shall include two sets of complete plans on minimum A2 size paper with Factory Stamp&Signatureandproductcatalog.Thefollowingitemsarealsorequired(2010NFPA72Section10.18.1.2)

1. Factory Forwarding Letter with factory name, address and contacts.2. The drawing’s cover page shall include Factory name, address, Accord ID.3. The drawing shall include the site plan with all necessary information if applicable.4. Thedrawingshallincludedetailonthesystem-AddressableorConventional.5. FireAlarmPaneldetailshallbeincluded-Howmanylooporzone6. Ifthesystemisaddressable,drawingshallcontainthedevicenumberwithloopnumber(eg:

L1S1=Loop1;Smoke1);forconventionalsystemclearindicationonzonesshallbeoutlined.7. The Fire Alarm Design shall include a Schematic Diagram/line Diagram containing the loops

starttoendandalsodevicesshallincludethedevicenumberandlocation.(ifaddressable)8. ThecableforDetectorsshallbeminimum2-core-1.5mm2certifiedcableforFireAlarm

System.9. ThecableforBellsandsoundersshallbeminimum2-core-2.5mm2certifiedcableforFire

Alarm System.10. FloorHeight,beamdepthshouldbementionedonthedrawing.Architecturalelevationis

required in case of shed building.11. Please include a catalogue of the Fire Alarm System.12. If the same floor is provided with sprinklers also, detectors can be eliminated.13. Multisensordetectorsarerecommendedontheswing,cutting,iron&finishingandother

areas where there is a possibility of floating fabric dust, threads and cottons etc. to avoid false alarm.

14. Beam detectors are recommended if the ceiling height is more than 6.00 meter from the finished floor level.

15. Ifthefactorywantstokeepthefiredooropen“DoorHoldOpendevice”tobeusedwhichshall be interfaced with fire alarm system in such a way that in case of fire the door will be closed automatically getting the signal from Fire Alarm Panel. It should be clearly shown on the drawing.

Re-Submittals:Submittalsrequiringadditionalinformationwillbeplaced“OnHold”untilrequired information has been submitted. Plan information revisions shall be submitted with changes clouded. Changes in other documents shall be clearly identified.

FIRE FIGHTING SYSTEM

Each submittal shall include two sets of complete plans on minimum A2 size paper with Factory Stamp&Signature.Thefollowingitemsarealsorequired:

1. Factory Forwarding Letter with factory name address and contacts.2. The drawing’s cover page shall include Factory name, address, Accord ID.3. The drawing shall include the site plan with all necessary information.4. The drawing shall be complete with legends, floor area and area title/name.5. Completedataonsprinklersshallbeprovidedliketypeofsprinkler,sprinklerKfactor,

temperature rating and type of response.6. Complete data on stand pipes shall be included in the drawing.7. Complete data on Fire Brigade/Siamese Connection shall be included in the drawing.8. Riser Diagram is mandatory. 9. The pipe network shall include riser location, zone control valve, pipe diameters and

dimensions.10. The drawing shall include fire pump location and pump capacity11. HydraulicCalculationforthesystemshallbesubmittedforthesystem.12. Top floor and Ground floor stairwells shall be covered by sprinkler.Sprinklers will not be

required in floors in between.13. All the toilets and kitchen areas shall be covered by sprinkler.14. Any room or open space in the working floor shall be covered by sprinklers if it is not

currently covered.

Page 13: Practical Remediation Guidance

13|16

Re-Submittals:Submittalsrequiringadditionalinformationwillbeplaced“OnHold”untilrequired information has been submitted. Plan information revisions shall be submitted with changes clouded. Changes in other documents shall be clearly identified.

Page 14: Practical Remediation Guidance

14|16

APPENDIX C

WHAT FIRE DOORS DO?

• Fire doors save lives and property• Theyarepartofabuilding’spassivefireprotectionsystemandarefundamentaltomost

firestrategiesforbuildings• Theyprovidecriticalprotectionwithinabuildingsuchasescaperoutes(stairsand

corridors)andinprotectingfromfirehazardsinabuilding.

WHAT’S IMPORTANT ABOUT FIRE DOORS?

• DoorsshallbecertifiedbyUL,FMorotherrecognizedthirdpartycertificationagency.ThedoorsmustcomplywiththestandardsmentionedintheAccordstandard-NFPA252;BS476part22,EN1634-1,GB12955-2008etc.Thespecificstandardshallbementionedinthecertificateprovidedbythecertificationagencyandthedoorassemblymustbemanufacturedinaccordancewiththecertificationagencyterms.

• Thefiredoorsandframesshallhavepermanentlabelingwiththeinformationofthemanufacturer,thecertificationagencyandthefirerating(seeexamplebelow).

• Ifthedoorscontainglass,thethirdpartycertificationshallindicatetheacceptableconfiguration.

• Thedoorhardwarewillalsobelistedasfireratedorbetestedaspartoftheassembly.• All components such as the doorframe, hinges, closers, seals and glazing systems make

upthefiredoorassemblyandmustbecertified.

EXAMPLE OF FIRE DOOR RATING LABEL

DO’S & DON’TS TO STAY SAFE

DO• Specifyandusethird-partycertifiedfiredoorsandcomponents• Makesureyouhavethecorrectcertificationforthedoor’sintendeduse• Makesurethetestiscarriedoutonacompleteinstalledassembly–thedoorleaf,door

frame and essential hardware• Install the door and frame as per manufacturer’s instructions

Page 15: Practical Remediation Guidance

15|16

DON’T• Fitafiredoorlikeanyotherdoor–it’snot,it’sanengineeredsafetydevice• Cut vision panels and other holes on site• Patchupafiredoor• Takerisksbyreducingthespecification• Disconnectafiredoorcloser• Proporwedgeopenafiredoor

WHAT IS A THIRD PARTY CERTIFICATION?

• It is the process of certifying that a manufacturer of a product has undergone an appropriateindependentappraisaltoconfirmtheircompliancewiththeperformanceaspectsofaspecificationforaparticularproductanditsinstallationandmaintenance.

• Toachievethirdpartycertification,amanufacturerandtheirproductwillhavetoundergo a rigorous audit and testing process, ensuring that they have in place documentedproductspecifications,installationinstructions,andafactoryproductioncontrolsystem,allofwhichintegratewithanapprovedQualityManagementScheme.

REQUIRED FIRE PROTECTION RATING OF FIRE DOORS

• Stairwells(ifthebuildingis4storiesorgreater):1.5hour• Stairwells(ifthebuildingis3storiesorless):1hour• Generator Rooms: 1.5 hour• Transformer rooms: 1.5 hour• Warehouse and Storage rooms: 45 minutes

Page 16: Practical Remediation Guidance

16|16

COLOPHON

Date: March 2015 - Updated November 2016Author: Accord Fire Safety TeamGraphic Design: JUSTAR .nlLayout: Iwan Fokin