GENERAL NOTES1.0
SUB GRADE PREPARATION AND BACKFILL
2.1
2.2
2.3
2.4
2.5
2.6
3.0 CONCRETE
3.1
3.2
3
3
3.3
3.4
3.5
3.6
3.7
3.8
3.9
3.10 BELOW GROUND PROTECTIVE COATINGS
3.10.1 FOUNDATIONS
3.10.2 SLAB ON GRADE
3.11 ABOVE GROUND PROTECTIVE COATINGS
PRIMER: SILANE-SILOXANE HYDROPHOBIC
INTERMEDIATE: ACRYLIC POLYMER (D.F.T. 200 MICRONS)
FINISH COAT: ACRYLIC POLYMER (D.F.T. 200 MICRONS)
4.0 REINFORCEMENT
4.1
4.2
4.3
4.4
4.5
4.6
4.7
5.0 ANCHOR BOLTS AND EMBEDDED ITEMS
5.1
5.2 MINIMUM COVER DISTANCE FROM CONCRETE EDGE SHALL BE AS FOLLOW:
TO BOLTS: 4.0 BOLT DIAMETER (125 mm MINIMUM)
TO SLEEVE OR PLATE: 75 mm
MINIMUM BOLT SPACING SHALL BE 7 BOLT DIAMETER.
5.3
5.4
5.5
5.6
5.7
5.8
6.0 GROUT
6.1
7.0 PAVING
7.1
7.2
7.3
7.4
7.5 PAVING ABBREVIATIONS:
7.6
8.0 REFERENCE STANDARDS AND SPECIFICATIONS
P.S. EARTHWORKS
P.S. EXCAVATION AND BACKFILL FOR UNDERGROUND INSTALLATIONS
P.S. CIVIL DESIGN BASIS
P.S. SPECIFICATION FOR CONCRETE SUPPLY
P.S. CONCRETE CONSTRUCTION
P.S. GROUTING
P.S. PAVING MATERIALS AND CONSTRUCTION
P.S. STRUCTURAL DESIGN BASIS
ANCHOR BOLT TYPE T
HPP:
LPP: LOW POINT OF PAVING
HIGH POINT OF PAVING
HPP ELEVATION EL.500.000 IS EQUAL TO EL.90.500 NEW ABU DHABI DATUM.
25
30FP 24 30 0.40 380
40 32 40
24 30
50
150 mm
200 mm
EQUIPMENT (GENERAL)
EQUIPMENT (PUMPS)
STRUCTURAL STEEL COLUMNS
300 mm
ALL SALIENT EDGES AND CORNERS OF CONCRETE (EXCEPT BOTTOM EDGES OF
FOUNDATIONS) SHALL HAVE 25 mm x 25 mm CHAMFER.
CLASS OF BOLT (SEE STD-1781-002-001)
STD-1781-002-001 ANCHOR BOLTS MATERIALS - FABRICATION - MARKING
STD-1781-002-002
STD-1781-002-003
STD-1781-002-004
STD-1781-002-005
ALL DIMENSIONS ARE IN MILLIMETERS. ALL LEVELS AND COORDINATES ARE IN METERS.
CONCRETE PLACEMENT AND CURING SHALL BE MADE IN ACCORDANCE
CONCRETE TESTING SHALL BE IN ACCORDANCE WITH SPECIFICATION
B1 20/12/10 FC
SCALE SIZE:
"COMPANY" DRG.NO.
"CONTRACTOR" DRG.NO.
EQUIPMENT DESCRIPTION
TAG/ITEM NOTES
REV.
DRAWING TITLE:
PROJECT :
CONTRACTOR:
COMPANY:
GF H IBA C ED K ML N PO
8
9
7
5
6
10
1
4
3
2
REV DATE STATUS DESCRIPTION BY CKD APP.
THI
S
DO
CU
ME
NT I
S
TH
E
PR
OP
ER
TY
OF
AB
U
DH
ABI
GA
S
DE
VE
LO
PM
EN
T
CO
MP
AN
Y
LI
MI
TE
D
AN
D
CO
NT
AI
NS I
NF
OR
MA
TI
ON
WHI
CH I
S
PR
OP
RI
ET
AR
Y.
THI
S I
NF
OR
MA
TI
ON I
S
TO
BE
HE
LD I
N
CO
NFI
DE
NC
E.
NO
DI
SC
LO
SU
RE
OR
OT
HE
R
US
E
OF
THI
S
DO
CU
ME
NT I
S
TO
BE
MA
DE
WI
TH
OU
T
TH
E
PRI
OR
WRI
TT
EN
CO
NS
EN
T
OF
AB
U
DH
ABI
GA
S
DE
VE
LO
PM
EN
T
CO
MP
AN
Y
LI
MI
TE
D.
A1
11
CAD FILE NO:
VAR. CLASS: SHEET: of3 11
PP05-0500-17-DTL-2915
ISSUED FOR INFORMATION FL AN
500-CE-B-12915
CONCRETE WORKS
GENERAL NOTES
THESE GENERAL NOTES SHALL BE READ IN CONJUNCTION WITH
SPECIFICATIONS PP05-0500-17-ADD-1108 AND PP05-0500-17-ADD-1109.
FOR CONCRETE TYPE AND MIX DESIGN REFER TO SPC. PP05-0500-17-ADD-1108.
PP05-0500-17-ADD-1108.
FORMED AND UNFORMED FINISHES SHALL BE IN ACCORDANCE WITH SPECIFICATION
PP05-0500-17-ADD-1109 AND SHALL FOLLOW THE INDICATIONS REPORTED ON
CONSTRUCTION DRAWINGS.
WITH PP05-0500-17-ADD-1109.
BELOW GROUND CONCRETE PROTECTION SHALL BE IN ACCORDANCE WITH STANDARD
DRAWING PP05-0500-17-ADD-2913 AND SPECIFICATION PP05-0500-17-ADD-1109,
IN PARTICULAR:
- ALL BELOW GROUND CONCRETE SHALL BE FULLY ENCAPSULATED WITH ONE LAYER OF
A MINIMUM 1.5 mm THICK SELF-ADHESIVE RUBBER/BITUMEN HIGH DENSITY POLYETHYLENE
LAMINATED WATERPROOF MEMBRANE.
- ALL FOUNDATIONS SHALL BE INSTALLED ON A SUPPORT/MEMBRANE SYSTEM CONSISTING
OF A 75 mm THICK LAYER OF BLINDING CONCRETE, A 1.5 mm MEMBRANE AS DESCRIBED
ABOVE, AND A 30 mm LAYER OF SCREED CONCRETE.
- ALL BELOW GROUND MEMBRANES AND COATING SHALL BE PROTECTED FROM DAMAGE DUE TO
CONSTRUCTION ACTIVITIES AND BACKFILLING BY COVERING WITH A PROTECTION BOARD OF
3.5 mm BITUMEN IMPREGNATED FIBREBOARD OR 12 mm THICK BITUMEN IMPREGNATED SOFT BOARD.
SMALL MISCELLANEOUS FOUNDATIONS (AS INDICATED ON DRAWINGS), SHALL BE COATED WITH
500 MICRONS DRY FILM THICKNESS (D.F.T.) NON-SOLVENTED COAL TAR EPOXY, WITH MINIMUM
PROPERTIES REPORTED IN DOCUMENT PP05-0500-17-ADD-1109.
POLYETHYLENE SHEET VAPOUR BARRIER, MINIMUM 0.25 mm THICK, SHALL BE PLACED BENEATH
THE SLAB ON GRADE.
VERTICAL SIDES OF ALL SLABS ON GRADE SHALL BE COATED WITH 1 mm D.F.T. NON-SOLVENTED
COAL TAR EPOXY, WITH MINIMUM PROPERTIES REPORTED IN DOCUMENT PP05-0500-17-ADD-1109.
ALL ABOVE GRADE CONCRETE MEMBERS SHALL HAVE A THREE COAT SYSTEM HAVING THE PROPERTIES
INDICATED IN DOCUMENT PP05-0500-17-ADD-1109, IN PARTICULAR:
PP05-0500-14-ADD-1103
PP05-0500-14-ADD-1104
PP05-0500-17-ADD-1107
PP05-0500-17-ADD-1108
PP05-0500-17-ADD-1109
PP05-0500-17-ADD-1111
PP05-0500-17-ADD-1112
PP05-0500-17-ADD-1113
PP05-0500-17-DTL-2913
PP05-0500-17-DTL-2912
FCFL AN00 14/01/11
00
PP05-0500-17-DTL-2915_00.dgn
NOMINAL
GRADE
STRENGTH APPLICATION MAXIMUM
FREE WATER/
CEMENTITIOUS
RATIO
MPa
CYLINDER CUBE
CEMENTITIOUS
CONTENT
KG/M
MPa MPa MAXIMUM MAXIMUM (mm) MINIMUM (KG/M )
20 25 0.50 250
FIREPROOFING
0.40 380
0.40 38030F
40 50 0.40 380
75 mm
60 mm
50 mm
CONCRETE
TYPE
FOLLOWING COMPLETION OF THE EXCAVATION AND PREPARATION OF THE
BOTTOM OF THE EXCAVATION TO RECEIVE THE PERMANENT WORKS,
THE BLINDING CONCRETE, MEMBRANE OR SUCH OTHER PROTECTION AS
CALLED FOR ON THE DRAWINGS SHALL BE PLACED AS SOON AS PRACTICAL.
PRECAUTIONS SHALL BE TAKEN TO PROTECT THE BOTTOM OF THE EXCAVATION.
ALL MATERIAL USED AS BACKFILL SHALL HAVE A MAXIMUM SALT CONTENT
AT 1% AND A MAXIMUM SULPHATE CONTENT OF 0.5%.
ALL BACKFILL WITHIN STRUCTURAL AREAS (AREAS SUPPORTING FOUNDATIONS,
CONCRETE SLABS, PAVEMENTS, ETC.) SHALL BE COMPACTED TO AT LEAST 95%
OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557.
BACKFILL IN NONSTRUCTURAL AREAS SHALL BE COMPACTED TO AT LEAST 90%
OF THE MAXIMUM DRY DENSITY AS DETERMINED BY ASTM D1557.
ALL BACKFILL SHALL BE PLACED AT A MOISTURE CONTENT OF -2 TO +2% OF
THE OPTIMUM MOISTURE CONTENT.
BACKFILL SHALL BE COMPACTED BY MECHANICAL TAMPING WHEREVER
POSSIBLE.
HAND-COMPACTED BACKFILL SHALL BE PLACED IN LOOSE LAYERS NOT
EXCEEDING 100 mm.
MACHINE-COMPACTED BACKFILL SHALL BE PLACED IN LOOSE LAYERS NOT
EXCEEDING 200 mm. MACHINE COMPACTORS SHALL BE SUITABLE ON THE TYPE
OF SOIL TO BE COMPACTED.
PAVING, SLABS, WALLS,
TRENCHES, DITCHES
EQUIPMENT
FOUNDATIONS,
STRUCTURES,
FOOTINGS,
PIPE SLEEPERS,
PITS, BASINS
BLINDING,
ELECTRICAL,
DUCT BANKS,
SCREED
PRESTRESSED
CONCRETE, PILE,
MARINE FACILITIES
OVER WATER,
STRUCTURES IN
CONTINUOUS CONTACT
WITH SEA WATER, WATER
RETAINING STRUCTURES
CONCRETE CAST AGAINST OR PERMANENTLY EXPOSED TO EARTH
(BELOW GRADE STRUCTURES)
CONCRETE EXPOSED TO WEATHER (ALL ABOVE GRADE
STRUCTURES NOT ENCLOSED BY A TEMPERATURE AND HUMIDITY
CONTROLLED BUILDING)
CONCRETE NOT EXPOSED TO WEATHER (LOCATED WITHIN A
TEMPERATURE AND HUMIDITY CONTROLLED BUILDING)
THE BOTTOM OF THE EXCAVATION SHALL BE LEVELLED AND TRIMMED
TO RECEIVE THE PERMANENT WORKS.
THE BOTTOM OF THE EXCAVATION SHALL BE MECHANICALLY COMPACTED
TO A DENSITY OF NOT LESS THAN 95% OF MAXIMUM DRY
DENSITY (ASTM D1557) FOR CONCRETE ITEMS; AND 85% OF DRY DENSITY
(ASTM D1557) FOR DRAINAGE STRUCTURES, UNDERGROUND PIPES AND ELECTRICAL
INSTALLATION AS PER PP05-0500-14-ADD-1104.
ANY SOFT SPOTS OR UNSUITABLE MATERIAL EXPOSED SHALL BE EXCAVATED
AND REPLACED IN ACCORDANCE WITH PP05-0500-14-ADD-1104.
BACKFILL MATERIAL SHALL BE TYPE A OR B IN ACCORDANCE WITH EARTHWORKS
SPECIFICATION PP05-0500-14-ADD-1103 EXCEPT AS NOTED, BACKFILL MATERIAL
SHALL CONSIST OF MATERIALS IMPORTED FROM BORROW PIT OR
EXCAVATED FROM THE CUT AREAS SUITABLE FOR USE IN CONSTRUCTING FILLS.
THE MATERIAL SHALL BE FREE FROM UNSUITABLE MATERIAL OR PARTICLES
LARGER THAN 75 mm IN LARGEST DIMENSION.
CONCRETE PREPARATION PROCEDURE AND MATERIALS (CEMENT, WATER, AGGREGATES,
ADDITIVES, ETC.) SHALL COMPLY WITH SPECIFICATION PP05-0500-17-ADD-1108.
ALL CONCRETE SHALL BE IN ACCORDANCE WITH SPECIFICATIONS PP05-0500-17-ADD-1108
AND PP05-0500-17-ADD-1109.
CONCRETE COMPRESSIVE STRENGTH SHALL BE AS FOLLOWS:
1.4 DRAWINGS SHALL NOT BE SCALED AND ONLY FIGURED DIMENSIONS SHALL BE FOLLOWED.00
TESTING TO VERIFY THE DEGREE OF COMPACTION WILL BE DONE ACCORDING
TO SPECIFICATION PP05-0500-14-ADD-1104,
IN ACCORDANCE WITH ASTM TEST METHOD D1556 (OR ASTM TEST METHOD D6938
AFTER VERIFICATION BY PARALLEL TESTING PERFORMED BY SAND CONE METHOD D1556).
00
MINIMUM CONCRETE COVER TO REINFORCEMENT (MEASURED TO THE OUTSIDE OF ALL
REINFORCEMENT) SHALL BE AS FOLLOWS:
MINIMUM PEDESTAL HEIGHT, REFERRED TO HPP (HIGH POINT OF PAVING) SHALL BE:
ALL CONCRETE FOUNDATIONS SHALL BE PLACED ON A 75 mm THICK BLINDING
LAYER WITH 75 PROJECTION ON EITHER SIDE OF FOUNDATION EDGE EXCEPT
OTHERWISE NOTED ON DRAWINGS. BLINDING CONCRETE LAYER IS NOT REQUIRED BELOW PAVING.
00
REINFORCING SPACERS, MANUFACTURED FROM AN INERT MATERIAL (SUCH AS uPVC) SHALL BE
USED TO INSURE THE CORRECT SPACING OF THE REINFORCING FROM THE OUTSIDE EDGE OF THE
STRUCTURAL DESIGNED SECTION.
REINFORCEMENT STEEL BARS, ANCHOR BOLTS OR OTHER STEEL EMBEDMENT SHALL NOT BE USED
FOR GROUNDING OF ELECTRICAL EQUIPMENT.
ANCHOR BOLTS, STEEL EMBEDMENTS AND EXTERNALLY MOUNTED STEELWORKS SHALL NOT BE
ELECTRICALLY CONNECTED TO THE REINFORCEMENTS.
BAR BENDING SCHEDULE SHALL BE PREPARED IN ACCORDANCE WITH BS 8666 OR ACI SP-66.
ALL BENDING AND CUTTING SHALL BE DONE COLD AND NO HEATING OR WELDING SHALL BE ALLOWED.
FABRIC REINFORCEMENT SHALL COMPLY WITH THE REQUIREMENTS OF BS 4483 OR ASTM A184 MADE
WITH COLD REDUCED STEEL WIRE COMPLYING WITH BS 4482.
ALL REINFORCEMENT SHALL BE IN ACCORDANCE WITH SPECIFICATION PP05-0500-17-ADD-1109.
REINFORCEMENT SHALL BE CONFORM TO BS4449 GRADE 460 OR ASTM A615 GRADE 60.
MANUFACTURE, FABRICATION, HANDLING, PLACEMENT AND STORAGE OF REINFORCEMENT SHALL BE
IN ACCORDANCE WITH PP05-0500-17-ADD-1109.
4.8
A.S. provided /
A.S.required
Equal to or greater than 2
Less than 2
Max. per cent of A.S. splices required lap lenght
class A
50
class B
100
class Bclass B
LAP SPLICE (Ld)
DI
A.
DI
A.
MINIMUM CLEAR SPACING OF BARS BEING SPLICED NOT LESS THAN 2 DIA. AND CLEAR COVER
NOT LESS THAN DIA.
SUBGRADE PREPARATION WILL BE CARRIED OUT AS PER 2.1
UNLESS OTHERWISE INDICATED ON DRAWINGS JOINTS SHALL BE PROVIDED AROUND
ALL PLINTHS AND FOUNDATIONS PROTRUDING THROUGH CONCRETE SLAB.
EXPANSION JOINTS SHALL BE PROVIDED BETWEEN TWO ADJACENT SLABS.
THEY SHALL BE FILLED WITH AN ELASTIC JOINT FILLER AND SEALED WITH A
CHEMICAL RESISTANT SEALANT AND SHALL COMPLY WITH THE DETAILS SHOWN
ON STANDARD DRAWING PP05-0500-17-DTL-2912. EXPANSION JOINT SPACING
WILL BE MAX 10 METERS.
CONTRACTION JOINTS SHALL BE PROVIDED IN CONCRETE PAVING SPACED
AT MAXIMUM 7 METERS (THE BEST WILL BE 5 METERS), AND SHALL COMPLY
WITH THE DETAILS REPORTED ON STANDARD DRAWING PP05-0500-17-DTL-2912.
REINFORCED CONCRETE PAVING SHALL COMPLY WITH SPECIFICATION
PP05-0500-17-ADD-1112 AND DRAWING PP05-0500-17-DTL-2912.
TYPE, THICKNESS AND AREA OF GROUT SHALL BE IN ACCORDANCE WITH THE
CONSTRUCTION DRAWINGS AND SPECIFICATION PP05-0500-17-ADD-1111.
- CEMENT BASED NONSHRINK GROUT SHALL BE PREMIXED, PREPORTIONED AND
FACTORY PACKAGED. CEMENT BASED NONSHRINK GROUT SHALL BE USED FOR
THE FOLLOWING ITEM:
- VESSELS AND HEAT EXCHANGERS.
- EQUIPMENT WITH CAST BASES.
- EQUIPMENT ON BASE FRAMES WITH COVER PLATES.
- STRUCTURAL COLUMN BASE PLATES.
- SMALL EQUIPMENT WITH FLAT BASE PLATES.
EPOXY NONSHRINK SHALL BE USED FOR THE FOLLOWING, PROVIDED THAT
SURFACE TEMPERATURES LOCAL TO THE GROUT IS LESS THAN 60 C:
- ALL MACHINERY AND PUMPS WITH DRIVES OF 750 kW AND ABOVE.
- ALL ENGINE DRIVES AND THEIR DRIVEN EQUIPMENT.
- ALL SOLE PLATE MOUNTED EQUIPMENT.
- ALL RECIPROCATING MACHINES.
- ALL SUPPORTS SUBJECT TO CYCLIC LOADING.
GROUT THICKNESS SHALL BE 25 mm OTHERWISE SPECIFIED IN THE DRAWINGS.
BOLT DESIGNATION:
T1 F1 33 150 400
NOMINAL SIZE
TYPE OF BOLT (T, R, S, Z)
ANCHOR BOLTS SHALL NOT COME IN CONTACT WITH REINFORCING STEEL.
PROJECTION OF BOLT ABOVE TOP OF CONCRETE
(DIMENSION "S" ON STANDARD DRAWINGS)
EMBEDDED LENGTH (DIMENSION "H" INDICATED
ON STANDARD DRAWINGS)
EXPOSED CAST-IN STEEL ITEMS (SUCH AS ANGLES, PLATES, ETC...) INCLUDING
ANCHOR RODS SHALL BE TREATED AS PER SPECIFICATION PP05-0500-17-ADD-1109.
BOLT PROJECTIONS SHALL BE MEASURED FROM THE TOP OF ROUGH CONCRETE.
ANCHOR BOLTS SHALL BE IN ACCORDANCE WITH STANDARD DRAWINGS 1781-002-001,
STD-1781-002-002, STD-1781-002-003, STD-1781-002-004, STD-1781-002-005.
BEFORE POURING OF CONCRETE, THE EXPOSED THREAD AND NUT OF ALL FOUNDATION BOLTS
SHALL BE WRAPPED IN AN APPROVED PROTECTIVE TAPE.
THIS TAPE SHALL BE MAINTAINED INTACT UNTIL THE EQUIPMENT IS PLACED IN POSITION.
BOLT SLEEVES AND POCKETS SHALL BE PROTECTED FROM FOREIGN MATTER AND WATER.
ALL SLEEVES AND POCKETS SHALL BE CLEARED OUT PRIOR TO PLACEMENT OF THE EQUIPMENT
AND SUBSEQUENT GROUTING.
ALL ANCHOR BOLTS AND SLEEVES FOR VERTICAL EQUIPMENTS WITH SKIRTS REQUIRING
CIRCUMFERENTIAL BOLTING SHALL BE RIGIDLY FIXED AND LEVELLED IN CORRECT POSITION
BY MEANS OF TEMPLATES BEFORE CASTING CONCRETE.
00
ANCHOR BOLT TYPE R
ANCHOR BOLT TYPE S
ANCHOR BOLT TYPE Z
ROAD AND PAVING DETAILS
MEMBRANE PROTECTION TO CONCRETE
FOUNDATIONS AND PEDESTALS
MINIMUM LENGHT OF LAP FOR LAP SPLICES SHALL BE AS FOLLOWS (BUT NOT LESS THAN 300 mm),
AS PER ACI 318M-08 SECTION 12.15:
class A SPLICE = 1.0 Ld
class B SPLICE = 1.3 Ld
A.S. = AREA OF STEEL
WHERE Ld IS THE TENSILE DEVELOPMENT LENGHT (INDICATED IN TABLE BELOW) WITHOUT ANY REDUCTION
FACTOR. THE FOLLOWING TABLE REPRESENTS THE SPLICE REQUIREMENT IN TABULAR FORMS:
FINAL ISSUE FOR CONSTRUCTION