PowerLogic® Active Pager Module Version 6.0

Instruction Bulletin 3080IB0801 April 2008

Page 2: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

This page is intentionally blank.

Page 3: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

Table of Contents

Table of Contents ...........................................................................................................................iii CHAPTER 1 – INTRODUCTION ..................................................................................................... 1

PowerLogic® Active Pager Module .............................................................................................................................. 1 About this Instruction Bulletin ....................................................................................................................................... 1 Assumptions and Guidelines ........................................................................................................................................ 2 Who to Go to Answer Technical Questions .................................................................................................................. 2

CHAPTER 2 – SAFETY PRECAUTION .......................................................................................... 3

CHAPTER 3 – INSTALLATION ....................................................................................................... 5

Prerequisites for Installing APM.................................................................................................................................... 5 Prerequisites for Installing SMS OPC Alarm and Event Server.................................................................................... 5 Installing the Product .................................................................................................................................................... 6

CHAPTER 4 – SETUP ..................................................................................................................... 7

Overview of Setup ........................................................................................................................................................ 7 Opening the APM Web Page ....................................................................................................................................... 7 Navigating to Setup ...................................................................................................................................................... 8 OPC Server ................................................................................................................................................................ 10 Remote Connection to OPC Using DCOM ................................................................................................................. 14 Filter ............................................................................................................................................................................ 15 Relay Templates ......................................................................................................................................................... 19 Relay & Recipient ....................................................................................................................................................... 22 Schedule ..................................................................................................................................................................... 25 Subscription ................................................................................................................................................................ 26 System Preference ..................................................................................................................................................... 29 Maintenance Mode Setup on PowerLogic® SMS ...................................................................................................... 31

CHAPTER 5 – DIAGNOSTICS .......................................................................................................33

Overview of Diagnostics ............................................................................................................................................. 33 Navigating to Diagnostics ........................................................................................................................................... 33 Real Time Monitoring of Diagnostic Alarms and Events............................................................................................. 33 Historical Viewing of Diagnostic Information............................................................................................................... 34 Diagnostic Options ..................................................................................................................................................... 37

CHAPTER 6 – MONITORING .........................................................................................................39

Overview of Monitoring ............................................................................................................................................... 39 Navigating to Monitoring ............................................................................................................................................. 39 Real Time Monitoring of Alarms and Events .............................................................................................................. 39 Historical Viewing of Diagnostic Alarms and Events .................................................................................................. 40 Monitoring Options ..................................................................................................................................................... 43

APPENDIX A – ISSUES & TROUBLESHOOTING ........................................................................45

APPENDIX B –INSTALLING APM ON MICROSOFT VISTA .........................................................47

Prerequisites before Installing APM ........................................................................................................................... 47 Configuring IIS after APM Install................................................................................................................................. 50

APPENDIX C – Remote Connection to OPC AE Server using DCOM .......................................55

Remote OPC AE Server Settings ............................................................................................................................... 55 APM Machine Settings ............................................................................................................................................... 59 Troubleshooting .......................................................................................................................................................... 63

APPENDIX D – RELY ATTRIBUTE DEFINITIONS ........................................................................65

Table 5, Acronyms and Definitions ............................................................................................................................. 65 Table 6, Relay Attributes for “Dial-up TAP” ................................................................................................................ 66 Table 7, Relay Attributes for “Email” ........................................................................................................................... 67 Table 8, Relay Attributes for “GsmOut” ...................................................................................................................... 68 Table 9, Relay Attributes for “Smpp” .......................................................................................................................... 68

Page 4: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Table of Contents 04/2008

iv © 2008 Schneider Electric. All Rights Reserved.

Table 10, Relay Attributes for “Snpp” ......................................................................................................................... 69

APPENDIX E – MAINTENANCE MODE SETUP IN SMS ..............................................................71

SMS Device Setup for Maintenance Mode Device ..................................................................................................... 71 Setup for Maintenance Mode GFX Control in SMS .................................................................................................... 76 Define Maintenance Mode for SMS Devices .............................................................................................................. 78

APPENDIX F – CD CONTENTS .....................................................................................................79

Electrical equipment should be installed, operated, serviced, and maintained only by.................................................................................................................80

Page 5: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Chapter 1 – Introduction

© 2008 Schneider Electric. All Rights Reserved. 1

CHAPTER 1 – INTRODUCTION

PowerLogic® Active Pager Module

PowerLogic® Active Pager Module (APM) e-mails, text or pages plant, facility, or campus personnel on alarms and events captured by PowerLogic® monitoring system(s) or third party monitoring systems, notifying them of power or energy anomalies that may occur within their systems. For more information on PowerLogic® monitoring system, including monitors, meters, specialized data network equipment, and system monitoring / reporting software, refer to the web site…

http://www.PowerLogic.com PowerLogic® APM has an OPC alarm and event client that receives alarms and events from OPC alarm and event servers. Upon receipt, APM e-mails and pages alarms and events to designated recipients, such as plant engineers and facility administrators. PowerLogic® APM relies on OPC alarm and event servers to transmit alarms and events to the APM’s OPC alarm and event client. The SMS OPC Alarm and Event Server, included with this installation, transmits alarms and events from PowerLogic® System Manager Software (SMS), version 4.02 or greater, to APM’s OPC alarm and event client. PowerLogic® SER 7.x is likewise equipped with an OPC Alarm and Event server and can provide alarms to PowerLogic® APM.

About this Instruction Bulletin

This instruction bulletin focuses on the APM application software components. It covers...

• Installation o APM (OPC Alarm & Event Client) o OPC Alarm & Event Server Add-on to PowerLogic® Monitoring

System(s)

• Setup o OPC Alarm & Event Server Connections to Client o Definition of Alarm and Event Filters o Definition of Relay Templates o Recipients and Relays (or Notification Channels) o Schedules o System Preferences

• Diagnostics o Live Viewing of APM Application Alarms and Events o Historical Viewing of APM Application Alarms and Events o Diagnostic Options to Display or to Hide Data Columns for Either

Live or Historical Viewing

Page 6: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Chapter 1 - Introduction 04/2008

2 © 2008 Schneider Electric. All Rights Reserved.

• Monitoring o Live Viewing of OPC Server Alarms and Events o Historical Viewing of OPC Server Alarms and Events o Monitoring Options to Display or to Hide Data Columns for Either

Live or Historical Viewing

Assumptions and Guidelines

The following assumptions and guidelines are presumed...

• Readers of this document are familiar with Microsoft Windows and how to use Microsoft Windows controls, such as text edit boxes, buttons, pull-down menus, etc.

• Readers of this document have some degree of familiarity with telecommunications and telecommunication devices and how to setup such devices and systems.

• Readers of this document are familiar with PowerLogic® system, including…

o PowerLogic® monitors and meters identified in this document o PowerLogic® Software Manager System (SMS) o PowerLogic® data network equipment o Modicon® Momentum Programmable Logic Controller (PLC)

• Readers of this document have working knowledge about their facilities’ electrical and operational systems, including severity levels of alarms and events

• There is no guarantee that the PowerLogic® APM OPC Alarm and Event Client will communicate with every 3

rd party OPC Alarm and Event

Server that is or has been available on the market.

Who to Go to Answer Technical Questions

To answer technical questions about APM, call PowerLogic® technical support at 1-615-287-3400.

Page 7: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Chapter 4 – Installation

© 2008 Schneider Electric. All Rights Reserved. 3

CHAPTER 2 – SAFETY PRECAUTION

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

NGER •Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. •This equipment must only be installed and serviced by qualified electrical personnel.

•Turn off all power supplying this equipment before working on or inside equipment. •Always use a properly rated voltage sensing device to confirm power is off. • Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result in death or serious injury.

Page 8: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Chapter 3 – Installation 04/2008

4 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 9: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Chapter 4 – Installation

© 2008 Schneider Electric. All Rights Reserved. 5

CHAPTER 3 – INSTALLATION

The APM compact disc (CD) allows for the installation of the APM application and the SMS OPC Alarm and Event Server. SMS OPC Alarm and Event Server automatically installs with PowerLogic® APM, if SMS version 4.02 or greater is detected on the machine.

Important!

There is no guarantee that the PowerLogic® APM OPC Alarm and Event Client will successfully communicate with every 3

rd party OPC Alarm and Event Server.

Prerequisites for Installing APM

The following table defines the prerequisites for installing APM. Table 1, Prerequisites for Installing APM

Applications or Components to Install

Versions

Microsoft (MS) Windows • Windows 2000 Server, Service Pack 4

• Windows 2003 Server, Service Pack 1

• Windows XP Professional, Service Pack 2

• Windows Vista (See Appendix B)

Prerequisites for Installing SMS OPC Alarm and Event Server

The following table defines the prerequisites for installing the SMS OPC Alarm and Event Server.

Page 10: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Chapter 3 – Installation 04/2008

6 © 2008 Schneider Electric. All Rights Reserved.

Table 2, Prerequisites for Installing the SMS OPC Alarm and Event Server

Applications or Components to Install

Versions

Microsoft (MS) Windows • Windows 2000 Server, Service Pack 4

• Windows 2003 Server, Service Pack 1

• Windows XP Professional, Service Pack 2

• Windows Vista

PowerLogic® System Manger Software (SMS)

• System Manager Software (SMS), version 4.02 or greater

Installing the Product

Insert CD into PC drive, and follow instructions as they appear on your computer screen.

Note!

Administrator rights are mandatory to install APM.

Page 11: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 7

CHAPTER 4 – SETUP

Overview of Setup

This chapter describes how to set up PowerLogic® APM (APM) to receive alarms and events and to transmit them to recipients via e-mail, pagers, etc. The setup of an APM application involves the following series of steps…

• Add users to APM roles

• Setup OPC alarm and event server connections

• Setup filtering of the receipt of alarms and events from various OPC alarm and event servers

• Optionally, create templates to define message transmission characteristics for relays, such as e-mail servers or pagers

• Identify recipients and define relay attributes, optionally using relay templates

• Create the schedule for each recipient, defining when alarms may be sent

• Subscribe recipients to receive alarms

Opening the APM Web Page

Note!

Skip this subsection if APM web page is already opened.

If APM web page is not open, then click on the following to activate web page…

Start > All Programs > PowerLogic eSolutions > APM > APM

Web

Upon opening APM web page, the main or home page appears, as illustrated by following example…

Page 12: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

8 © 2008 Schneider Electric. All Rights Reserved.

Figure 1, Example of Main or Home Page

Navigating to Setup

From the home page, the user can click on the “Setup” button. Upon activation, the setup page appears, as illustrated by the following example…

Page 13: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 9

Figure 2, Example of Setup Page

On the left-hand side of the setup page, the following options are available... Clicking on the icon expands to allow access to link(s)… The following sub-sections discuss each option and how it can be used to configure APM.

Page 14: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

10 © 2008 Schneider Electric. All Rights Reserved.

OPC Server

The “OPC Server” page sets up communication between the APM component and the various OPC Alarm and Event Servers accessible on the data network. Upon clicking the icon, adjacent to the “OPC Server” label, on the setup page, the “Edit” option appears, as illustrated below, and the icon, adjacent, to the “OPC Server” label changes to . Figure 3, Example of Setup Menu, “OPC Server” Selected and Expanded

Page 15: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 11

Click the “Edit” link to configure OPC servers. Clicking on the link opens the “OPC Server Configuration” page, similar to the following illustrated example. If there are OPC servers available on the local host, then they will be displayed in the “Available Servers” list.

Figure 4, Example of “OPC Server Configuration” Page

Page 16: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

12 © 2008 Schneider Electric. All Rights Reserved.

Auto-detect OPC Alarm and Event Servers To auto-detect OPC alarm and event servers in a server machine and list them in the “Available Servers” list box, move the cursor to the “Available OPC Servers” group box and …

• Key in the machine name in the “Machine” text edit box (See figure below) Figure 5, Example of Controls to Auto-detect OPC Servers for a Specified

Server Machine

• Click the “Auto-detect OPC Servers” button. If OPC alarm and event servers are registered on the specified machine, then the server names will appear in the “Available OPC Servers” list box (See figure below)

Figure 6, Example of Available Servers / Selected Servers

• Click the “>” button to move a single server from “Available Servers” list to “Selected Servers” list or click the “>>” button to move all servers from “Available Servers” list to “Selected Servers” list (Figure below)

Page 17: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 13

• Click the “Apply Changes” button to register the OPC alarm and event server(s) listed in the list of “Selected Servers” (See figure below)

Figure 7, Example of Available Servers / Selected Servers Control

Manual Entry and Assignment of OPC Alarm and Event Server To manually register an OPC alarm and event server, do the following…

• Enter the host name or IP address in the “Machine” text edit box (Figure below)

• Enter the OPC alarm and event server name in the “OPC Server” text edit box

• (Optional) Click on the “Verify” button to verify availability of OPC alarm and event server on the data network. If the OPC alarm and event server is available, then a dialog box will confirm connection.

Figure 8, Example of Manual Entry Control

• Click the “Add” button to insert OPC alarm and event server into the list of “Selected Servers” (Figure on next page)

Page 18: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

14 © 2008 Schneider Electric. All Rights Reserved.

Figure 9, Example of Available Servers / Selected Servers Controls

• Click the “Apply Changes” button to apply or register the OPC alarm and event server listed in the list of “Selected Servers” (See figure below)

Figure 10, Example of Available Servers / Selected Servers Control with a

Selected Server

Important!

If the settings on a selected OPC server change, they will not be reflected in APM until the user re-imports the OPC server by clicking on the “Apply Changes” button. For example, if an alarm in SMS is disabled, and the SMS OPC Server is selected as one of the servers to page on, once the alarm is enabled, it will not be visible to APM until the user clicks the “Apply Changes” button.

Remote Connection to OPC Using DCOM

See Appendix C.

Page 19: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 15

Filter

The “Filter Configuration” page allows for the creation of an alarm and event filter that defines groups of alarms for relay. To navigate to the configuration page, click the “Edit” link under the “Filter” menu. (See figure below) There is a default filter, “ALL”, assigned to each OPC alarm and event server that includes all alarms. (See figure below)

Figure 11, Example of Setup Menu, “Filter” Selected and Expanded

Figure 12, Example of “Filter Configuration” Page

Page 20: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

16 © 2008 Schneider Electric. All Rights Reserved.

Adding an Alarm and Event Filter To add a filter, click the “Add New Filter” button. In the “Filter Configuration” group box, do the following…

• Select server in the “Servers” list box (Select first figure on next page)

• Enter the name of the filter in the “Name” text edit box (See figures on next page)

• Enter the severity range of alarms and events to be received

Important!

If the reader is unfamiliar with the alarm severity level, please contact the system administrator.

• (Optional) Enter an integer value in the “Delay in Seconds” text edit box. (See figures on next pages) This option prevents a flood of notifications in an avalanche alarm scenario. Upon receipt of alarms matching the filter with the specified delay, the following will happen…

o A notification is sent, indicating alarm compression has begun, and identifying which alarm triggered the compression. If text is entered into the “Delay Start Message” text edit box, it will be included in the notification.

o At the end of the delay, another notification is sent, summarizing the alarms APM received

• Select the nodes from the area tree for inclusion in the filter (Checking alarms defines what gets paged on) (See figures on next pages)

• Click the “Save Filter” button to save filter, and respond to notification dialog (See figures on next pages)

Important!

When the user clicks the Add New Filter button, a new filter is created and saved with the name “New Filter”.

Selecting/Deselecting nodes from the area tree automatically adds or removes nodes from the filter. However, changes to the other

filter attributes such as filter name or severity are not made until the Save Filter button is clicked.

Page 21: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 17

Figure 13, Example of “Filter Configuration” Page with Newly Added Filter with Web Controls Unmodified

Page 22: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

18 © 2008 Schneider Electric. All Rights Reserved.

Figure 14, Example of “Filter Configuration” Page with Newly Added Filter with Web Controls Modified

Removing an Alarm and Event Filter To remove an alarm and event filter, …

• Select server in the “Servers” selection box

• Select filter in the “Filters” selection box

• Click on “Remove Filter” button and respond to notification dialog

Page 23: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 19

Relay Templates

The “Relay Templates Configuration” page permits creation of templates that define the data network parameters for messages sent from APM to a recipient. Upon clicking the icon, adjacent to the “Relay Templates” label, on the setup page, the “Edit” option appears, as illustrated below, and the icon, adjacent, to the “Relay Templates” label changes to .

Figure 15, Example Setup Menu, Relay Templates Selected Click the “Edit” link” to add, edit, or remove a relay template. Clicking on the link opens the “Relay Templates Configuration” page, similar to the diagram below.

Figure 16, Example of “Relay Templates Configuration” Page

Page 24: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

20 © 2008 Schneider Electric. All Rights Reserved.

Adding Relay Template and Creating the Template Name To add a relay template and create the template name, do the following…

• Select one of the following relay types via the “Relay” selection box… o “Email” (e-mail) o “Dialup-TAP” o “GSM Out” (Global Systems for Mobile Communications) o “SMPP” (Short Message Peer-to-Peer Protocol) o “SNPP” (Simple Network Paging Protocol)

• Click “Add” button. A dialog box prompts for entry of text. Enter text into text box and click the OK button (See figure on next page)

Editing Relay Template Name To edit a relay template name, move cursor to “Template” group box and do the following…

• Click “Edit” button. A dialog box prompts for entry of text. Enter text into text box and click the OK button (See Figure on next page)

Deleting Relay Template To delete a relay template, move cursor to “Template” group box and do the following…

• Click “Delete” button. Reply to notification dialog (See following illustration)

Page 25: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 21

Figure 17, Example of “Relay Templates Configuration” Page, Template Group Box

Modifying Attributes in a Relay Template To modify attributes in a relay template, do the following…

• Select one of the following relay types via the “Relay” selection box in the “Template” group box…

o “Email” (e-mail) o “Dialup-TAP” o “GSM Out” (Global Systems for Mobile Communications) o “SMPP” (Short Message Peer-to-Peer Protocol) o “SNPP” (Simple Network Paging Protocol)

• Select a template from the “Template” selection box (Refer to previous illustration)

• Click on the data field of the appropriate attribute, found in the list of attributes of the “Configuration” group box. Respond to dialog box, such as entering text in a text box or selecting an option in a selection box (See figure below)

Figure 18, Example of “Relay Templates Configuration” Page, List of

Attributes Relay Attributes See Appendix D.

Attribute Data Fields

Attributes

Page 26: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

22 © 2008 Schneider Electric. All Rights Reserved.

Relay & Recipient

The “Relay and Recipient Configuration” page…

• Enables identification of new recipients (communicational devices)

• Configures the communicational relay between the APM and the recipients, using relay templates to establish initial values in the various attribute data fields

Upon clicking the icon, adjacent to the “Relay Templates” label, on the setup page, the “Edit” option appears, as illustrated below, and the icon, adjacent, to the “Relay Templates” label changes to .

Figure 19, Example Setup Menu, Relay & Recipient Selected Click the “Edit” link to add, edit, or remove a relay template. Clicking on the link opens the “Relay and Recipient Configuration” page, similar to the following illustrated example.

Page 27: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 23

Figure 20, Example of “Relay and Recipient Configuration” Page

Adding a Recipient To add a recipient, move cursor to “Recipient” group box and do the following… “

• Click the “Add” button. Enter the Recipient's name, description and then click the “Apply” button to save the new recipient. (See figure on next page)

Editing a Recipient (or Recipient’s Name) To edit a recipient (or changing recipient’s name), move cursor to “Recipient” group box and do the following…

• Click “Edit” button. A dialog box prompts for entry of text. Enter text into text box and click the OK button (See figure on next page)

Deleting a Recipient To delete a recipient, move cursor to “Recipient” group box and do the following…

• Click “Delete” button. Reply to notification dialog (See figure on next page)

Page 28: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

24 © 2008 Schneider Electric. All Rights Reserved.

Figure 21, Example of “Relay Templates Configuration” Page, Template

Group Box Modifying Communicational Attributes for a Recipient via Template To modify communicational attributes of a recipient, do the following…

• Select a recipient from the “Name” selection box in the “Recipient” group box (Refer to previous illustration)

• Select one of the following relay types via the “Relay Name” selection box in the “Configuration” group box…

o “Email” (e-mail) o “Dialup-TAP” o “GsmOut” (Global Systems for Mobile Communications) o “Smpp” (Short Message Peer-to-Peer Protocol) o “Snpp” (Simple Network Paging Protocol)

• Select a template from the “Relay Template” selection box (Refer to following illustration)

• (Optional) Click on any of the attribute fields and custom modify any of the values (See figure below)

Figure 22, Example of “Relay and Recipient Configuration” Page, List of

Attributes Relay Attributes See Appendix D.

Attributes

Attribute Data Fields

Page 29: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 25

Schedule

The “Schedule” page defines the times during a seven-day week period when recipients can receive messages from APM. Upon clicking the icon, adjacent to the “Schedule” label, on the setup page, the “Edit” option appears, as illustrated below, and the icon, adjacent, to the “Schedule” label changes to .

Figure 23, Example Setup Menu, Schedule Selected Upon clicking “Edit” under Schedule, the Schedules web page appears. The following figure illustrates the Schedules web page. Select the recipient in the “Recipients” list box and click the add button to add a schedule. Click the appropriate check boxes for the days of the week that applied to the start and end times that are to the right. Multiple schedule boxes may be added for the recipient to reflect different time schedules and when they apply on what days of the week. Combining different time schedules for a single recipient allows for greater flexibility in defining the overall paging schedule for the recipient.

Page 30: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

26 © 2008 Schneider Electric. All Rights Reserved.

Figure 24, Example of a Schedules Page

Subscription

The “Subscription” page assigns recipients to messaging services provided by the APM. Upon clicking the icon, adjacent to the “Subscription” label, on the setup page, the “Edit” option appears, as illustrated below, and the icon, adjacent, to the “Relay Templates” label changes to .

Figure 25, Example Setup Menu, Subscription Selected Click the “Edit” link to add, edit, or remove a relay template. Clicking on the link opens the “Subscription” page, similar to Fig 24.

Page 31: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 27

Figure 26, Example of “Subscription” Page

Subscribing a New Recipient To subscribe a recipient to a relay, do the following… “

• Click the “Add” button. (New row with blank data fields should appear in data grid.)

• Click button adjacent to newly added row. A dialog box should appear (See Fig x). Select options presented from the following controls and click “OK” button…

o Recipient Name o OPC Server o Relay Name o (Alarm and Event) Filter Name o Get Server Pings (Heartbeat Alarm)

Note… “Get Server Pings” is a heartbeat alarm, transmitted during a period of alarm inactivity of one hour or greater.

Page 32: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

28 © 2008 Schneider Electric. All Rights Reserved.

Figure 27, Example of Subscription Dialog Editing a Subscription in Data Grid To edit a subscription (data row) in data grid, do the following…

• Click button adjacent to desired row and edit data fields. A dialog box should appear. Select options presented from the following controls and click “OK” button…

o Recipient Name o OPC Server o Relay Name o (Alarm and Event) Filter Name

Deleting Subscription in Data Grid To delete subscription of a recipient (data row) from data grid, do the following…

• Click button adjacent to desired row.

Page 33: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 29

System Preference

The “System” page allows for administrative changes to APM. Upon clicking the icon, adjacent to the “Schedule” label, on the setup page, the “Preference” option appears, as illustrated below, and the icon, adjacent, to the “System” label changes to .

Figure 28, Example Setup Menu, System Preference Selected Upon clicking “Preferences” under “System”, the “Preference” page appears, as illustrated in the following.

Figure 29, Example of a System Preference Page

Page 34: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

30 © 2008 Schneider Electric. All Rights Reserved.

Service Controls Controls on the page allow for the setting of various server options for either SMS OPC Server Options or APM Service Options. Controls consist of check boxes or text-edit boxes. Simply check the appropriate box for the appropriate service option or modify the appropriate text-edit box for a specific change in value. Click the “Save Settings” to save. Refer to tables on the next page for details on SMS OPC Server Options and APM Service Options. Table 3, SMS OPC Server Options Following four options are applicable only if SMS OPC AE server is configured to run with APM.

1 Include SMS System description in message

The name of the online SMS system is included in the message notification sent to the recipient.

2 Include device description in message.

The name of the device is included in the message notification sent to the recipient.

3 Include alarm description in message

The name of the alarm is included in the message notification sent to the recipient.

4 Include alarm value in message

The value of the alarm is included in the message notification sent to the recipient.

Following options are applicable in all scenarios:

5 Logger Memory cache duration (in Milliseconds)

The PowerLogic© OPC AE Historian (A component of APM, installed with the standard APM 6.0 setup) caches log entries in memory before writing to the database to optimize data throughput. Administrators can change this value if they want to fine-tune their system. In most cases, there would be no need to change the default value.

6 Logger OPC Server Health Check ( in Milliseconds)

The PowerLogic© OPC AE Historian periodically checks the health of all configured OPC servers. If a connection is lost, it attempts to reconnect to the server until it succeeds. This value indicates the frequency of that health check.

Page 35: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 31

Table 4, APM Service Options 1 Log Events in

Diagnostic Log Enable basic logging of events in the diagnostic log. Only the description of the event is logged. No custom or standard attributes are saved in the diagnostic log. The primary purpose of this option is to help with the initial configuration of the system.

2 Check for Logged event ID

Ensures that the event is logged (with all custom and standard attributes) in the historical log before sending the message notification to the recipient.

3 Generate extra diagnostics

Log verbose information in the diagnostic log.

4 Check Schedules A way to bypass the schedules. If this is unchecked, message notifications will be sent to all subscribed recipients without checking their schedules.

5 Check Maintenance mode

A way to bypass maintenance mode check. This should be enabled if the maintenance mode feature is used.

6 APM Health check frequency ( in milliseconds)

The APM service periodically checks the health of all configured OPC servers. If a connection is lost, it attempts to reconnect to the server until it succeeds. This value indicates the frequency of that health check.

7 Delay between message transmission (in milliseconds)

Add a short delay between notifications sent to a recipient. This is useful if the recipient’s device or service/modem cannot handle too many requests in a short time.

Restart Services The “Preference Page” provides services controls to start, to stop, and to restart SMS OPC service of APM, and to start, to stop, and to restart APM Service Status. The following figure illustrates the control buttons.

Figure 30, Example of Preference Page Control Buttons To restart both SMS OPC Service and APM Service, click the “Restart Services” button.

Maintenance Mode Setup on PowerLogic® SMS

See Appendix E.

Start Service

Stop Service Restart Service

Page 36: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

32 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 37: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 33

CHAPTER 5 – DIAGNOSTICS

Overview of Diagnostics

The diagnostics page provides real time and historical viewing of activity relating to the Active Pager Module (APM). It does not provide information on events transmitted from OPC alarm and event servers.

Navigating to Diagnostics

Click on the “Diagnostics” button, located on the gray bar of control buttons, below the blue product banner. Afterwards, click on one of the following links…

• Live – viewing of current diagnostic information as it happens – page refreshed every 5 seconds

• Historical – viewing of historical diagnostic information with filtering and sorting

• Options – display or hide information attributes

Real Time Monitoring of Diagnostic Alarms and Events

Upon clicking on the “Live” link, associated with the “Diagnostics” button, the “live” diagnostics page appears, as illustrated by the following example…

Figure 31, Example of Live Diagnostics Page

Page 38: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

34 © 2008 Schneider Electric. All Rights Reserved.

Historical Viewing of Diagnostic Information

Upon clicking the “Historical” link, associated with the “Diagnostics” button, the “historical” diagnostics page appears, as illustrated by the following example…

Figure 32, Example of Historical Diagnostics Page

Date Time Filter Use the date / time filter control to define the time span of alarms and events to display. (Refer to the following illustration.)

Figure 33, Date Time Filter

Page 39: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 35

Auto Filter Click on the Auto Filter radio button to auto-filter data columns. Click on to select topic(s) to be filtered. (Refer to the following illustration.)

Figure 34, Auto Filter

Page 40: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

36 © 2008 Schneider Electric. All Rights Reserved.

Advanced Filter Click on the Advanced Filter radio button to perform advanced filtering of data columns. Click on (“filter mode” symbol) to select type of filtering, and double click area adjacent to “filter mode” symbol to invoke display of text edit box, and enter target on which to filter on. (Refer to the following illustration.)

Figure 35, Advanced Filter

Page 41: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 37

Export of Historical Data to Microsoft Excel File Click on “Excel” link to export historical data Microsoft Excel File. (Refer to the following illustration.)

Figure 36, Excel Export

Diagnostic Options

Upon clicking on the “Options” link, associated with the “Diagnostics” button, the “diagnostic options” page appears, as illustrated by the following example…

Figure 37, Example of Diagnostics Options Page

The options page allows for the selection of data columns to be displayed on the live and historical pages. The page provides for a series of checkboxes to display or to hide data columns. The page also allows for the definition of rows per page.

Page 42: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

38 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 43: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 39

CHAPTER 6 – MONITORING

Overview of Monitoring

The monitoring page provides live and historical viewing of alarms and events received from the OPC alarm and event servers.

Navigating to Monitoring

From the currently displayed APM page, the user can click on the “Monitoring” button, located on the gray bar of control buttons, below the blue product banner, and then click on one of the following links…

• Live (Viewing of Alarms and Events)

• Historical (Viewing of Alarms and Events)

• Options (Display or Hide Alarm and Event Attributes)

Real Time Monitoring of Alarms and Events

Upon clicking on the “Live” link, associated with the “Monitoring” button, the “live events” page appears, as illustrated by the following example…

Figure 38, Example of Live Events Page

Click on (located in the columnar headers) to auto-filter on target.

Page 44: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

40 © 2008 Schneider Electric. All Rights Reserved.

Historical Viewing of Diagnostic Alarms and Events

Upon clicking on the “Historical” link, associated with the “Monitoring” button, the “historical events” page appears, as illustrated by the following example…

Figure 39, Example of Historical Events Page

Date Time Filter Use the date / time filter control to define the time span of alarms and events to display. (Refer to the following illustration.)

Figure 40, Date Time Filter

Page 45: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 41

Auto Filter Click on the Auto Filter radio button to auto-filter data columns. Click on to select topic(s) to be filtered. (Refer to the following illustration.)

Figure 41, Auto Filter

Page 46: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

42 © 2008 Schneider Electric. All Rights Reserved.

Advanced Filter Click on the Advanced Filter radio button to perform advanced filtering of data columns. Click on (“filter mode” symbol) to select type of filtering, and double click area adjacent to “filter mode” symbol to invoke display of text edit box, and enter target on which to filter on. (Refer to the following illustration.)

Figure 42, Advanced Filter

Page 47: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 43

Export of Historical Data to Microsoft Excel File Click on “Excel” link to export historical data Microsoft Excel File. (Refer to the following illustration.)

Figure 43, Excel Export

Monitoring Options

Upon clicking on the “Options” link, associated with the “Monitoring” button, the “diagnostic options” page appears, as illustrated by the following example…

Figure 44, Example of Monitoring Options Page

The options page allows for the selection of what data columns are displayed on the live and historical pages. The page provides for a series of checkboxes to display or to hide data columns. The page also allows for the definition of rows per page.

Page 48: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

44 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 49: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix A – Issues & Troubleshooting

© 2008 Schneider Electric. All Rights Reserved. 45

APPENDIX A – ISSUES & TROUBLESHOOTING

If symptoms exists and do not match with the ones listed below or if the attempt to implement prescribed solution does not resolve the issue, then please contact Tech Support at 615-287-3400.

• After installing Active Pager Module (APM), the APM service and the OPCAELogger Service will not be started automatically. The user will have to go through the configuration of APM and, then, start the services manually from the preferences page. Alternatively, the user can restart the machine after configuring APM to start the services.

• If a new Windows user profile is created after installing APM, then logging into the machine as the new user will cause the APM install to restart. To workaround this issue, create additional local Windows user profiles before installing APM.

• The user might see the statement, "The page cannot be displayed”, when accessing the APM website. This is caused when another install overwrites the IIS setting of “HTTP Keep-Alives Enabled” and sets it to false. For APM to properly function, this must be set to true. This is required for integrated Windows authentication which the APM website uses. The illustration, below, shows the proper setting to resolve this issue.

Figure 45, Default Web Site Properties

Page 50: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix A – Issues & Troubleshooting 04/2008

46 © 2008 Schneider Electric. All Rights Reserved.

• After navigating to the Subscriptions page, occasionally, the user will be taken to a blank screen. This is a known issue in a third party control. To workaround this problem, click on the Edit link again, located under “Subscription”, in the Setup controls on the left side of the Setup web page. The figure, below, illustrates the link.

Figure 46, Subscription Link

• SMS device events do not show up in filtering: This is a known issue with SMS. The work around to this is to…

o Open SMS Setup->Setup->Devices/Routing o Click on the device planned for use in APM o Click the configure button o Repeat the last two previous steps for each device planned for use in APM o When completed, restart the APM services.

• If installing with SER 7.1, prior to installing APM 6.0, the user must install the latest service update, minimum version SER Service Update 2.1. If the user has a previously installed update for SER 7.1, the SER Service Update 2.1 will not install until the previous update is uninstalled using the Control Panel, Add Remove programs. Once the previous update has been removed, the SER 2.1 update should install normally.

• When installed with SER 7.1, the error “Permission Denied” may appear when moving events. Simply ignore this error as it does not cause any problems.

• Any value entered for an attribute in the Relay Templates and Relay Recipients grids must not exceed a 500 character limit – this includes spaces.

• In order to show up in all of the drop-down boxes in the APM web site, the filter name must not exceed 40 characters – this include spaces. During migration, 5 characters are appended to the name of the filter being migrated from APM 5.n. This means that if the filter name in APM 5.n is longer than 35 characters, then the whole filter name may not show up in the drop-down boxes in APM 6.0.

• The minimum recommended screen size for APM is 1024 by 768. If the user interface looks skewed, please try changing the screen size. Otherwise, try to maximize the browser window and refresh the page.

• If changes made in configuration are not reflected in the actual functionality, then make sure to restart the ActivePagerModule and PLOpcAELogger services either from the System -> Preferences page, or from the Windows Service Controller.

Page 51: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix B – Installing on Vista

© 2008 Schneider Electric. All Rights Reserved. 47

APPENDIX B –INSTALLING APM ON MICROSOFT VISTA

Prerequisites before Installing APM

Before installing APM on Microsoft Vista, configure Internet Information Services (IIS) as follows…

1. Click on Control Panel > Programs and Features a. Click on “Turn Windows features on or off”, invoking the

“Windows Features” dialog box, as illustrated below.

Figure 47, “Windows Features” Dialog Box

b. Expand “Internet Information Services”, as illustrated in the previous figure.

c. Select “Web Management Tools” and expand. d. Check all boxes under “Web Management Tools”, except for “IIS

Management Services”, as illustrated in the following figure.

Page 52: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix B – Installing on Vista 04/2008

48 © 2008 Schneider Electric. All Rights Reserved.

Figure 48, “Windows Features” Dialog Box with “Web Management Tools” Expanded

e. Select “World Wide Web Services”, under “Internet Information Services”, and expand.

f. Check all boxes under “Application Development Features”, a child of “World Wide Web Services”, except for “Server Side Includes”, as illustrated in the following figure.

Figure 49, “Windows Features” Dialog Box with “Application Development

Features” Expanded

Page 53: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix B – Installing on Vista

© 2008 Schneider Electric. All Rights Reserved. 49

g. Select “Common Http Features”, under “Internet Information Services”, and expand.

h. Check all boxes under “Common Http Features”, as illustrated in the following figure. Make sure that “Common Http Features” box is checked as well.

Figure 50, “Windows Feature” Dialog Box with “Common Http Features”

Expanded

i. Select “Security”, under “Internet Information Services”, and expand.

j. Check boxes “Basic Authentication”, “Request Filtering”, and “Windows Authentication” under “Security”, as illustrated in the following figure. Make sure that “Security” box is checked as well.

Page 54: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix B – Installing on Vista 04/2008

50 © 2008 Schneider Electric. All Rights Reserved.

Figure 51, “Windows Feature” Dialog Box with “Security Features” Expanded

2. Click the OK button to apply changes

Configuring IIS after APM Install

After installing APM on Vista, do the following…

1. Click on “My Computer” > “Manage” to bring up the management console.

2. Expand the “Services and Applications” and click on “Internet Information Services”.

3. In the second column of the “Computer Management” window, expand root node of tree control and expand its child node “Web Sites”.

4. From “Web Sites”, expand “Default Web Site” to view “PLeSolutionsWeb” virtual directory. Refer to the following figure.

Page 55: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix B – Installing on Vista

© 2008 Schneider Electric. All Rights Reserved. 51

Figure 52, “Computer Management” Window with “PLeSolutionsWeb” Virtual Directory

5. Right-click on the virtual directory “PLeSolutionsWeb” and select “Advanced Settings”. This action brings up the “Advanced Settings” dialog box, as illustrated in the following figure.

a. Under “Behavior”, change “Application Pool” to “Classic .NET AppPool”

b. Click the “OK” button to apply changes

Page 56: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix B – Installing on Vista 04/2008

52 © 2008 Schneider Electric. All Rights Reserved.

Figure 53, “PLeSolutionsWeb” Virtual Directory’s Advanced Settings

Dialog Box

6. Make sure the “PLeSolutionsWeb” virtual directory is selected. Refer to the following figure.

Figure 54, “Authentication” Icon

Page 57: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix B – Installing on Vista

© 2008 Schneider Electric. All Rights Reserved. 53

7. Double-click Authentication icon to bring up Authentication settings, then right click on “Windows Authentication” and enable. Refer to the following figure.

Figure 55, “Authentication”, “Computer Management” Dialog Box

Page 58: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix B – Installing on Vista 04/2008

54 © 2008 Schneider Electric. All Rights Reserved.

This is intentionally blank.

Page 59: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix C – Remote Connection to OPC using DCOM

© 2008 Schneider Electric. All Rights Reserved. 55

APPENDIX C – Remote Connection to OPC AE Server using DCOM

The OPC AE server uses COM/DCOM to communicate with APM. When the OPC AE server and APM are installed on the same machine, no additional configuration is required. However, when the OPC AE server and APM are on separate machines, DCOM and IIS need to be configured.

Remote OPC AE Server Settings

Note

This procedure is specific to Windows Server 2003. However, the general principle of this procedure can be applied to other Windows operating systems.

To setup a remote machine with an OPC AE Server, using DCOM, do the following…

1. Click on Start > Settings > Control Panel > Administrative Tools > Computer Management > Local Users and Groups

a. In “Users”, create a user called “DCOMUser” b. In “Groups”, add “DCOMUser” to the Administrative group c. In “Groups”, create a group called “OPCDCOM” d. Add the following to “OCPDCOM” group…

i. DCOMUser ii. Administrator iii. ASPNET iv. INTERACTIVE v. NETWORK SERVICES vi. SYSTEM

2. Run DCOM configuration utility by clicking Start > Run > DComCnfg.exe. 3. In the “Component Services” window, expand the “Component Services” node,

“Computers” node, and “My Computer” node in the tree, located to the left of the window. Refer to the following figure.

Page 60: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix C – Remote Connection to OPC using DCOM 04/2008

56 © 2008 Schneider Electric. All Rights Reserved.

Figure 56, “Component Services” Window

4. Right-click on “My Computer” and select “Properties”. 5. Select the “Default Properties” tab, as illustrated in the following figure.

Figure 57, “My Computer Properties” Dialog Box, “Default Properties” Tab

Page 61: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix C – Remote Connection to OPC using DCOM

© 2008 Schneider Electric. All Rights Reserved. 57

6. As illustrated in the previous figure, set the options in the Default Properties Tab as

follows… a. Check box entitled “Enable distributed COM on this computer” b. Select “Connect” in the drop down list box, “Default Authentication Level” c. Select “Identify” in the drop down list box, “Default Impersonation Level”

7. Select the “COM Security” tab, as illustrated in the following figure.

Figure 58, “My Computer Properties” Dialog Box, “COM Security” Tab

8. As illustrated in the preceding figure, set options in the “COM Security” tab as follows… a. Click “Edit Default…” button under “Access Permissions” group box and do the

following… i. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Access Permissions” dialog box

ii. Check the boxes for all permissions for each group and user listed in the “Access Permission” dialog box

iii. Click on the “OK” button to apply changes b. Click “Edit Default…” button under “Launch and Activation Permissions” group

box and do the following… i. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Launch Permissions” dialog box

ii. Check the boxes for all permissions for each group and user listed in the “Launch Permissions” dialog box

iii. Click on the “OK” button to apply changes c. Click “Edit Limits…” button under “Access Permissions” group box and do the

following… i. Check box for “Remote Access” for each user and group listed in the “Access Permission” dialog box

Page 62: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix C – Remote Connection to OPC using DCOM 04/2008

58 © 2008 Schneider Electric. All Rights Reserved.

ii. Click on the “OK” button to apply changes d. Click “Edit Limits…” button under “Launch and Activation Permissions” group

box and do the following… i. Check boxes for “Remote Launch” and “Remote Activation” for each user and group listed in the “”Launch Permissions” dialog box

ii. Click on the “OK” to apply changes 9. Expand “My Computer”, select and expand on “DCOM Config”, and do the following…

a. Select “OPCEnum” server, a child node of “DCOM Config”, and right-click. Note… this action may induce the addition of several registry keys. Be sure to click “OK” on the dialog boxes requesting acknowledgement.

i. In the “Properties” dialog box, select the “General” tab, and select “Connect” in the “Authentication Level” drop down list box.

ii. In the “Properties” dialog box, select the “Security” tab and do the following…

1. Click “Edit Default…” button under “Access Permissions” group box and do the following…

a. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Access Permissions” dialog box

b. Check the boxes for all permissions for each group and user listed in the “Access Permissions” dialog box

c. Click on the “OK” button to apply changes 2. Click “Edit Default…” button under “Launch and Activation

Permissions” group box and do the following… a. Add the group “OPCDCOM”, created in Step 1,

by clicking on the “Add…” button in the “Launch Permissions” dialog box

b. Check the boxes for all permissions for each group and user listed in the “Launch Permissions” dialog box

c. Click on the “OK” button to apply changes b. The following OPC servers may need to be configured for DCOM access on

the remote machine…

• PowerLogic SMS AE server

• PLSEROPC AE/DA server

• Other OPC AE servers Select the appropriate OPC AE server, a child node of “DCOM Config”, and right-click. Note… this action may induce the addition of several registry keys. Be sure to click “OK” on the dialog boxes requesting acknowledgement.

i. In the “Properties” dialog box, select the “General” tab, and select “Connect” in the “Authentication Level” drop down list box.

ii. In the “Properties” dialog box, select the “Security” tab and do the following…

1. Click “Edit Default…” button under “Access Permissions” group box and do the following…

a. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Access Permissions” dialog box

b. Check the boxes for all permissions for each group and user listed in the “Access Permissions” dialog box

c. Click on the “OK” button to apply changes 2. Click “Edit Default…” button under “Launch and Activation

Permissions” group box and do the following…

Page 63: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix C – Remote Connection to OPC using DCOM

© 2008 Schneider Electric. All Rights Reserved. 59

a. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Launch Permissions” dialog box

b. Check the boxes for all permissions for each group and user listed in the “Launch Permissions” dialog box

c. Click on the “OK” button to apply changes iii. In the “Properties” dialog box, select the “Identity” tab, and do the

following… 3. Select “This User” and set the starting user to “DCOMUser” 4. Enter password for DCOMUser. 5. Click on the “OK’ button to apply changes

APM Machine Settings

To configure the APM machine for DCOM, do the following…

1. Click on Start > Settings > Control Panel > Administrative Tools > Computer Management > Local Users and Groups

c. In “Users”, create a user called “DCOMUser” d. In “Groups”, add “DCOMUser” to the Administrative group e. In “Groups”, create a group called “OPCDCOM” f. Add the following to “OCPDCOM” group…

i. DCOMUser ii. Administrator iii. ASPNET iv. INTERACTIVE v. NETWORK SERVICES vi. SYSTEM

2. Run DCOM configuration utility by clicking Start > Run > DComCnfg.exe. 3. In the “Component Services” window, expand the “Component Services” node,

“Computers” node, and “My Computer” node in the tree, located to the left of the window. Refer to the following figure.

Page 64: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix C – Remote Connection to OPC using DCOM 04/2008

60 © 2008 Schneider Electric. All Rights Reserved.

Figure 59, “Component Services” Window

4. Right-click on “My Computer” and select “Properties”. 5. Select the “Default Properties” tab, as illustrated in the following figure.

Figure 60, “My Computer Properties” Dialog Box, “Default Properties” Tab

Page 65: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix C – Remote Connection to OPC using DCOM

© 2008 Schneider Electric. All Rights Reserved. 61

6. As illustrated in the previous figure, set the options in the Default Properties Tab as

follows… a. Check box entitled “Enable distributed COM on this computer” b. Select “Connect” in the drop down list box, “Default Authentication Level” c. Select “Identify” in the drop down list box, “Default Impersonation Level”

7. Select the “COM Security” tab, as illustrated in the following figure.

Figure 61, “My Computer Properties” Dialog Box, “COM Security” Tab

8. As illustrated the in preceding figure, set options in the “COM Security” tab as follows. a. Click “Edit Default…” button under “Access Permissions” group box and do the

following… i. Add the group “OPCDCOM”, created in Step 1, by clicking on the

“Add…” button in the “Access Permissions” dialog box ii. Check the boxes for all permissions for each group and user listed

in the “Access Permission” dialog box iii. Click on the “OK” button to apply changes

b. Click “Edit Default…” button under “Launch and Activation Permissions” group box and do the following…

i. Add the group “OPCDCOM”, created in Step 1, by clicking on the “Add…” button in the “Launch Permissions” dialog box

ii. Check the boxes for all permissions for each group and user listed in the “Launch Permissions” dialog box

iii. Click on the “OK” button to apply changes c. Click “Edit Limits…” button under “Access Permissions” group box and do the

following… i. Check box for “Remote Access” for each user and group listed in

the “Access Permission” dialog box

Page 66: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix C – Remote Connection to OPC using DCOM 04/2008

62 © 2008 Schneider Electric. All Rights Reserved.

ii. Click on the “OK” button to apply changes d. Click “Edit Limits…” button under “Launch and Activation Permissions” group

box and do the following… i. Check boxes for “Remote Launch” and “Remote Activation” for

each user and group listed in the “”Launch Permissions” dialog box ii. Click on the “OK” to apply changes

9. Click on Control Panel > Administrative Tools > Computer Management and do the following…

a. Expand the “Services and Application” node, a child node of “Computer Management”

b. Select “Services” node, a child node of “Services and Application” c. Under “Services” list box, right-click on “PLActivePagerModule” and select

“Properties” and do the following, referring to following figure… i. Click on the “Log On” tab in the “Properties” dialog ii. Click the radio button, “This Account” iii. Enter “.\DCOMUser” in text box adjacent to “This Account” label iv. Enter password v. Click on “Apply” button vi. Click on “OK” button

d. Under “Services” list box, right-click on “PLOPCAELogger”, select “Properties” and do the following, referring to following figure…

i. Click on the “Log On” tab in the “Properties” dialog ii. Click the radio button, “This Account” iii. Enter “.\DCOMUser” in text box adjacent to “This Account” label iv. Enter password v. Click on “OK” button vi. Reboot the machine

Figure 62, “PLActivePagerModule Properties” Dialog Box, “Log On” Tab

Page 67: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix C – Remote Connection to OPC using DCOM

© 2008 Schneider Electric. All Rights Reserved. 63

Troubleshooting

Symptom An “access denied” error is reported in the event log when the client attempts to establish an IOPCShutdown or IOPCDataCallback connection point callback. Problem The .NET framework uses the default DCOM security settings for the machine, since the client application does not call CoInitializeSecurity(). Resolution It is not possible to call CoInitializeSecurity() in a .NET client application. However, DCOM security can be configured in the registry for each client application, by creating the following registry values… HKCR\AppID\APMService.exe\AppID = {426AF718-0B46-423B-8DC8-

833E7A944F11} HKCR\AppID\{426AF718-0B46-423B-8DC8-

833E7A944F11}\AuthenticationLevel = 1

…, where the GUID should be unique for each OPC client application, and the “APMService.exe” key should be replaced with the name of the client application. To automatically create these keys, browse to the CD content’s “Utility” folder and import the APM_DCOM.reg file to the registry, by double-clicking it.

Page 68: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix C – Remote Connection to OPC using DCOM 04/2008

64 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 69: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 65

APPENDIX D – RELY ATTRIBUTE DEFINITIONS This section uses many acronyms that may seem ambiguous to the user. Below, is a table that provides definitions of the acronyms introduced in this section.

Table 5, Acronyms and Definitions

Acronym Descriptions

GSM (Global System for Mobile communications). This is a communications standard used by many mobile phones. SMS is defined in the GSM standard, allowing messages of up to 160 characters.

OTA (Over-the-Air activation system). This is a category of the type of device that is connecting to the SMSC – used in the SMPP standard.

PL SMS PowerLogic System Manager Software (SMS in all other sections)

SIM card (Subscriber Identity Module). This is a chip that is placed into a mobile phone and securely stores the service-subscriber key of a user, allowing the user to switch phones by replacing the SIM card. This card is mandatory in all devices that communicate using GSM.

SMPP (Short Message Peer to Peer) . This is an open standard that sends and SMS by connecting directly to an SMSC. Often used to submit messages in bulk.

SMS (Short Message Service) . This is a communications protocol that allows the exchange of short text messages (160 7-bit characters, including spaces) between mobile phones. More information about SMS, including other protocols can be found here: www.smsforum.net

SMSC (Short Message Service Centre). Routes an SMS sent by a user, to the specified destination.

SNPP (Simple Network Paging Protocol). This is a standard protocol for sending messages to SMS and paging devices.

TAP (Telocator Alphanumeric Protocol). This protocol can be used to send SMS messages using a standard modem and telephone landline.

UCP (Universal Computer Protocol). This is a protocol that is used by mobile phones to connect to an SMSC.

VMS (Voice Mail System). This is a category of the type of device that is connecting to the SMSC – used in the SMPP standard.

Page 70: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

66 © 2008 Schneider Electric. All Rights Reserved.

The following tables identify the attributes of the available relay types, selectable from the “Relay” selection box, located in the “Relay and Recipient Configuration” Web Page of APM.

Table 6, Relay Attributes for “Dial-up TAP”

Relay Attributes Descriptions

Dialup Device Name of the device for sending APM messages.

Dialup Speed The baud rate of the communication session.

Data Format A string indicating the data bits / parity / stop bits Contact your provider to get this. The following link may also be useful… www.activexperts.com/activsms/smsclist

Protocol Type of provider. This is either the TAP or UCP.

Password Provider password (if required)

Sender Number The number listed as the reply-to number in the SMS.

Recipient Number SMS number of the recipient.

Provider Dial String Number to dial to access provider.

Prefix Text Text to append before the message body of the SMS.

Postfix Text Text to append after the message body of the SMS.

Retries This number determines how many unsuccessful send attempts are made before the SMS is aborted.

Log File Path This is the full path (including name) of the log file. All device commands and responses are written to this file.

Page 71: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 67

Table 7, Relay Attributes for “Email”

Relay Attributes Descriptions

“From” Appears in the “From” field of the sent email.

“To” Addresses of e-mail recipients, comma separated.

SMTP Server Host This can be a server name or an IP address of the provider. Usually obtained from the IT department.

Credential User Name Login for SMTP Server, if required.

Credential Password Password for SMTP Server, if required.

Retries This number determines how many unsuccessful send attempts are made before the email is aborted.

Prefix Text Text to append before the subject of the email.

Postfix Text Text to append after the subject of the email.

Enable SSL True or False – indicates whether the email is sent using Secure Sockets.

Subject The text that will appear in the subject line of the sent email.

Pickup Directory Location Left blank by default. Path to the folder where email messages are to be placed in order to be processed by the SMTP server.

Delivery Method Left blank by default. Indicates how email messages are delivered:

• An SMTP server.

• Moving the email into the pickup directory for IIS, which then delivers the message.

• Moving the email to a directory specified by PickupDirectoryLocation for later delivery by another application.

SMTP Service Port An integer that represents the port number on the SMTP host. The default value is 25.

SMTP Timeout An integer that specifies the time-out value in seconds. The default value is 60 seconds.

Page 72: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

68 © 2008 Schneider Electric. All Rights Reserved.

Table 8, Relay Attributes for “GsmOut”

Relay Attributes Descriptions

Gsm Device Name of the device to use for sending SMS messages.

Gsm Sim Pin Required if SIM card is pin protected

Gsm Prefix Text Text to append before the subject of the SMS.

Gsm Postfix Text Text to append after the subject of the SMS.

Gsm Retries This number determines how many unsuccessful send attempts are made before the SMS is aborted.

Gsm Recipient SMS number of the recipient.

Log File Path This is the full path (including name) of the log file. All device commands and responses are written to this file.

Table 9, Relay Attributes for “Smpp”

Relay Attributes Descriptions

Smpp Server This can be a server name or an IP address of the provider.

Smpp Server Port TCP port used for connection to SMPP provider.

Smpp System ID Account used to login to the SMSC provider’s system.

Smpp Password Password used to login to the SMSC provider’s system.

Smpp System Type Type of SMSC provider (e.g. SMPP, VMS, OTA)

Smpp Keep Alive (Seconds) Integer representing the number of seconds to keep a communication channel open.

Smpp Timeout (Milliseconds) Integer representing the server timeout in milliseconds – used for all network operations such as Connect or Send.

Smpp Prefix Text Text to append before the subject of the SMS.

Smpp Postfix Text Text to append after the subject of the SMS.

Smpp Retries This number determines how many unsuccessful send attempts are made before the SMS is aborted.

Smpp Recipient SMS number of the recipient.

Log File This is the full path (including name) of the log file. All device commands and responses are written to this file.

Page 73: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 69

Table 10, Relay Attributes for “Snpp”

Relay Attributes Descriptions

Snpp Server This can be a server name or an IP address of the provider.

Snpp Server Port TCP port used for connection to SMPP provider.

Snpp Password Password used to login to the SMSC provider’s system.

Snpp Timeout (Milliseconds) Integer representing the server timeout in milliseconds – used for all network operations such as Connect or Send.

Snpp Prefix Text Text to append before the subject of the SMS.

Snpp Postfix Text Text to append after the subject of the SMS.

Snpp Retries This number determines how many unsuccessful send attempts are made before the SMS is aborted.

Snpp Recipient SMS number of the recipient.

Log File This is the full path (including name) of the log file. All device commands and responses are written to this file.

Page 74: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

70 © 2008 Schneider Electric. All Rights Reserved.

This page is intentionally blank.

Page 75: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 71

APPENDIX E – MAINTENANCE MODE SETUP IN SMS

PowerLogic® physical and logical SMS devices may be put into maintenance mode. A device “in maintenance mode” indicates that some type of maintenance is occurring with devices that have the potential to emit alarms. A device “in maintenance mode” indicates to APM that it should log the information, but not send an alarm notification to recipients.

Note…

The following assumes that the user has a degree of familiarity with PowerLogic® SMS to comprehend and perform the procedures given in this appendix.

To incorporate the maintenance mode device and GFX control object into SMS and define which devices are in maintenance mode, the following must be accomplished…

SMS Device Setup for Maintenance Mode Device

• Install the database device driver from the installation CD, “.\Utilities” directory

• Launch SMS setup client

• Add a communication connection for the database device driver, where communication driver is “Database Driver”

Page 76: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

72 © 2008 Schneider Electric. All Rights Reserved.

• Add maintenance mode device, where… o Device Type = Generic_DBDrv o Connection Name = Newly Added Communication Connection o Device ID = 1 o Protocol = Modbus

• Add custom quantity for maintenance mode GFX control object

Page 77: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 73

• Set custom quantity attributes as… o Digital Function o No Units for Units Code o Digital Function for Format Code

Page 78: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

74 © 2008 Schneider Electric. All Rights Reserved.

• Assign custom quantity such that… o Set bitmap mask such that status names is “ON/OFF”

Page 79: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 75

• Configure digital function (custom quantity) by editing the set points such that the attributes are…

o Delay = 1 o Poll Interval = 1 Second o Equal

� Name = On � Severity = Level 1 � No Tasks

o Non-equal � Name = Off � Severity = Level 9 � No Tasks

Page 80: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

76 © 2008 Schneider Electric. All Rights Reserved.

Setup for Maintenance Mode GFX Control in SMS

• Add OLE Control (or GFX Control Object), “PL_GFX_MaintMainModeCtrl, to GFX Diagram

Page 81: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 77

• Set the following attributes for the maintenance mode GFX Control o ODBC (name of SMS system database currently installed) o Caption (as displayed on GFX Diagram) o Position of Control o Name of Control o Maintenance Mode Device o Login Timeout (in seconds) o Match Timeout (in seconds)

Page 82: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

78 © 2008 Schneider Electric. All Rights Reserved.

Define Maintenance Mode for SMS Devices

• Bring up the GFX diagram with the maintenance mode GFX control

• Open GFX control

• Select the name of the control

• Select the name of the maintenance mode device

• Select the name of the maintenance mode digital function (or custom quantity)

• Make sure that the “OFF” button is clicked to de-activate control

• Assign devices to maintenance mode or put them out of maintenance mode

• Click “ON” button to activate control

• Click “Exit” button to exit control.

Page 83: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

04/2008 Appendix D – Attributes of Relay Types

© 2008 Schneider Electric. All Rights Reserved. 79

APPENDIX F – CD CONTENTS

The following items are included on the CD:

Component Description Path on Disk

1 APM 6.0 Install This will install the APM OPC Client and UI.

\APM6\setup.exe

2 SMS OPC Server Install

This will install the SMS OPC Alarm and Events server. Without this component, APM cannot receive alarms from SMS.

\SMSOPC\setup.exe

3 Readme file Contains important warnings and user information.

\README.txt

4 APM 6.0 Manual Contains comprehensive guide to using APM.

\APMUserGuide.pdf

5 Utilities Folder These are extra files and applications that may be needed for troubleshooting and diagnostics.

\Utilities

5a. Microsoft SQL Server 2005 Management Studio Express Install

(Install Optional) This will install a Microsoft tool that provides a graphical interface through which the user can interact with SQL Server Databases. Recommended only for advanced users.

\Utilities\ sqlexpr32.exe

5b. APM_DCOM.reg A registry file that inserts the key missing on some systems.

\Utilities\APM_DCOM.reg

5c. SMS DBDRV Device Type Install

This will install the SMS DBDRV Device Type that is used for Maintenance Mode

SMS v3.3.2: \Utilities\ 33_2Generic_DB_Driver.exe SMS v4: \Utilities\ 40v2Generic_DBDrv.exe

6 Training Material Contains training simulation \Training Material

Page 84: PowerLogic® Active Pager Module Version 6 · PowerLogic® Active Pager Module Version 6.0 Instruction Bulletin 3080IB0801 April 2008

PowerLogic® Active Pager Module

Appendix D – Attributes of Relay Types 04/2008

80 © 2008 Schneider Electric. All Rights Reserved.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any

consequences arising out of the use of this material.