Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770 • Contact: [email protected] • Website: www.bushrefrigeration.com Specifications subject to change without notice Model FS77GD Width 77” Depth 32” Height 74½” Volume 59³ft Doors 3 Shelves 4 HP 1/2 Voltage 115V Door Size 23” x 55” Shipping Weight 720 lbs Operating Temperature 38-42°F Features Save space and money with a sliding door cooler. Sliding door models fit into tight spaces where there isn’t enough aisle space for a door to swing open. Powers’ sliding door coolers are priced lower than swinging door models for added value. • Self contained - ready to plug in. • Black anodized aluminum double pane glass self-closing doors. • Automatic condensate evaporator. • Adjustable coated wire shelving. • Louvered motor covers. • Can be customized to suit individual needs. • Powder-coat exterior finish. • Heated PVC door jambs and tracks. • Switch controlled vertical fluorescent lamps. • Balanced refrigeration systems. • Stainless steel bottom pans. • Environmentally friendly refrigerants. • Low E and argon-filled double panel glass doors.

Transcript of Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral...

Page 1: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

Power’s Sliding Glass 3 Door FloralCoolers For Bush Refrigeration

Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770 • Contact: [email protected] • Website: www.bushrefrigeration.com

Specifications subject to change without notice

Model FS77GDWidth 77”

Depth 32”

Height 74½”

Volume 59³ft

Doors 3

Shelves 4

HP 1/2

Voltage 115V

Door Size 23” x 55”

Shipping Weight

720 lbs

Operating Temperature

38-42°F

FeaturesSave space and money with a sliding door cooler. Sliding door models fit into tight spaces where there isn’t enough aisle space for a door to swing open. Powers’ sliding door coolers are priced lower than swinging door models for added value.

• Self contained - ready to plug in.• Black anodized aluminum double pane glass self-closing doors.• Automatic condensate evaporator.• Adjustable coated wire shelving.• Louvered motor covers.• Can be customized to suit individual needs.• Powder-coat exterior finish.• Heated PVC door jambs and tracks.• Switch controlled vertical fluorescent lamps.• Balanced refrigeration systems.• Stainless steel bottom pans.• Environmentally friendly refrigerants.• Low E and argon-filled double panel glass doors.

Page 2: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

Power’s Sliding Glass 3 Door FloralCoolers For Bush Refrigeration

Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770 • Contact: [email protected] • Website: www.bushrefrigeration.com

Top View

Front View

77”

32”

55”

77”

74½23”

Page 3: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

MAKING MODERN LIVING POSSIBLE

EN-Instruction sheet ERC 102 kit

Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.B3.02/520H8601 1

Technical highlights

Dimensions mm

Technical specifications

y Save up to 52 % energy y Sleep/night mode detection y Smart fan control y Reliable & Advance defrost algorithm y Compressor protection against instable voltage y High condensing temperature protection y Real 16 A power relay - up to 2.5 HP compressors y Fully compatible with flammable refrigerants (R290) y Moisture protection (housing & coating) y Pre-programmed - ready to use

FEATURES DESCRIPTION

Power supply 100 VAC - 240 VAC 50-60 Hertz, automatic switch mode power supply

Rated power Less than 0.7 W

Inputs4 inputs: 3 analogue and 1 digital:- Air/evaporator/condenser- Door sensor: all types, user specific

Output compressor relay

1xCompressor relay: 16 (16A) EN60730; 16 (16A) CQC; 16A (16A FLA/72A LRA) UL60730 2xAux relay: total load: max 10 A Individual load: U60730: 8FLA/12LRA/TV1" EN60730: 8A resistive/2(2)A

Display LED display, 3 digits, decimal point and multi functionality icons; °C scale

Operating conditions 0 °C to 55 °C, 93% rHStorage conditions -40 °C to 85 °C, 93% rHMeasurement range -40 °C to 85 °C

ProtectionFront: IP65/Rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00

Environmental Pollution degree III (can be mounted inside a refrigerated cabinet), non-condensing

Resistance to heat & fire Category D (UL94-V0

EMC category Category I

Operating cycles Compressor relay: more than 175,000 at full load (16A (16A))

Approvals

R290/R600a: EN/IEC 60079-15:2005,Glow wire according to EN/IEC 60335-1,IEC/EN 60730, UL60730, NSF, CQC, GOST R 60730 Note: These approvals are only valid when using the accessories listed in this document

78.25

36.5

78.2582.25

28rear mounting

3071

front mounting

28.571

Input/output

100 - 240 VAC SMPS

L

1 2 3 4 5 DO’s AI/DI’sD(S1)

S1=t

empe

ratu

re c

ontr

ol

C(S2) B(S3) A(DI)

N

OR

com

pres

sor

DO1 DO2 DO3

defr

ost h

eate

r

fan lig

hts

ERC 102Ccontroller

Safety info

Risk of electrocution!For mounting: do not connect mains power until the controller is correctly mounted.For unmounting: disconnect the power supply before unmounting

Installation Changing the desired temperature setpoint

Turning ON/OFF the ECO and DEFROST function

Operation menu

Turning ON/OFF the light

y Insert the ERC 102 in to the cabinet y Attach the clips to each side of the ERC 102

Display/operation

Password protection

Press variable direct function,e.g. ECO/night mode.Sub function: BACK

Press temperaturesetpointSub function: UP

Press temperaturesetpointSub function: DOWN

Press variable direct function,e.g. defrost mode.Sub function: OK

Password protection on two levels:level 1: shop (daily use by shop personel)level 2: ser (service technician)

Press 5 sec both rightbuttons to access themenu

The display showsthe currenttemperature

current temperature

1Press: UP/DOWN toadjust setpointAfter 30 seconds, thedisplay automaticallyreverts to showing thecurrent temperaturetemperature setpoint

2

Press brie�y toentering inECO mode

Press brie�y toentering inDEFROST mode

ECO

The green ECO symbolappears in ECO mode

The DEFROST symbolappears in DEFROST mode

Press 5 sec both right buttonsto access the menu 1) Parameter

groups

2) Parameter name

3) Parameter value

Higher left button to exitLower left button to con�rm

Scroll through themenu group

Scroll through theparameters group

Higher left button to exitLower left button to con�rm

Press and hold for 5 sec LIGHT buttonTo turn OFF the Light press and hold the LIGHT button again

IMPORTANT NOTEThe inputs are not galvanic separated and are connected directly to the mains supply! For that reason, door-switches, sensors as well as the cables must fulfil the reinforced insulation requirements.

Page 4: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

MAKING MODERN LIVING POSSIBLE

EN-Instruction sheet ERC 102 kit

Produced by Danfoss A/S (EL-MSSM/AZ) | March 2014 DKRCC.EI.RL0.B3.02/520H8601 2

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifica-tions already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Parameters Problem solving

Menu Parameters Cod Description Min Max Unit Def

Setpoint Stp Setpoint -50 80 C 2

Thermostat tHE Thermostat settings

Setpoint adjustment ratio SPr Current setpoint adjustment value diF * SPr 0.0 1.0 - 0.0

Differential diF Thermostat differential 0.0 20.0 K 2.0

Air temperature adjust tAD Air Temperature Adjust 0.0 20.0 K 0.0

Alarm ALA Alarm setting

High alarm delay Htd Alarm delay on high temperature 0 240 min 30

Low alarm delay Ltd Alarm delay on low temperature 0 240 min 0

High temperature alarm HAt Alarm is activated above this temperature

(Celsius ) -50.0 80.0 C 15.0

Low temperature alarm LAt Alarm is activated below this temperature

(Celsius ) -50.0 80.0 C -50.0

Door open delay dod Alarm delay for door open (0-60 minutes) 0 60 min 2

Compressor CoP Compressor Setting

Min run time Crt Minimum time compressor must run 0-30 minutes 0 30 min 0

Min Stop time CSt Min time compressor must idle 0-30 minutes 0 30 min 0

Max OFF time Cot Max time compressor must idle 0-480 minutes 0 480 min 0

Error run time Ert Compressor run time if temperature sensor is not working (0-60 minutes) 0 60 min 0

Error stop time ESt Compressor stop time if temperature sensor is not working (0-60 minutes) 0 60 min 0

Minimum cut-in voltage uLi When compressor is OFF:

lowest compressor start voltage (0-270 V) 0 270 Vac 0

Minimum cut-out voltage uLo When compressor is ON:

lowest operation voltage (0-270 V) 0 270 Vac 0

Maximum voltage uHi When compressor is ON: highest operation voltage (0-270 V) 0 270 Vac 270

Power ON delay Pod Delay in seconds between power ON & compressor being activated 0 300 Sec 180

Defrost dEF Defrost Setting

Defrost type dFt No: defrost function is disabled, nat: Off-cycle defrost (natural defrost) no nat - EL

Terminating temp dtt Temp at which defrost stop (evap temp or cabinet temp) 0 25 C 7

Def Min Interval dii The minimum time in hours between the start of each defrost cycle 0 96 hours 6

Def Max Interval dAi The maximum time in hours between the start of each defrost cycle 0 96 hours 7

Def Min time dit The minimum duration of a defrost cycle in minutes 0 240 min 5

Def Max time dAt The maximum duration of a defrost cycle in minutes 0 480 min 30

Drip OFF time dot The duration in minutes of the drip-OFF time at the end of a defrost cycle 0 60 min 0

Fan delay after defrost Fdd The duaration in minutes before the fan starts after a defrost cycle 0 240 sec 0

Defrost fan ON dFA Whether the fan will run during a defrost cycle no yes - no

Initial defrost interval idi The number of hours after power-up before the first defrost cycle starts 0 96 hours 3

Initial defrost duration idd Defrost is deactivated 0 999 cycles 100

Fan FAn

Fan always ON FAo No: fan parameters below active. Yes: fan is always ON no yes - yes

Fans stop time on door open Fdt The maximum time the fan will be stopped

after the door has been opened 0 999 sec 0

Fan on cycle FoC The number of seconds the fan runs when the compressor is OFF 0 960 sec 0

Fan stop cycle FSC The number of seconds the fan does not run when the compressor is OFF 0 960 sec 0

Energy managment Eng

ECO activity delay EAdMinutes delay after last door opening until ECO mode is enabled; 0:disable

0 360 min 0

ECO temperature offset Eto Tempearture increase for ECO mode relative

to normal mode 0 10 K 2

Condenser Protection Con Condenser protection setting

Condenser Alarm Limit CAL If condenser sensor exceeds this temperature,

alarm is activated 0 85 C 75

Condenser Block Limit CbL If this temperature is exceeded, compressor will be stopped 0 85 C 85

Condenser OK limit CoL Temperature at which compressor may start after a stop due to exceeding "CbL" 0 85 C 60

Condenser Low Temp CLL Temperature below which the compressor is not allowed to start -50 20 C -5

Display diS Display setting

Lock-time After defrost dLt Display lock time after defrost [0-60 min] 0 60 min 5

Show economy state SECYes: display will show "eco" when in ECO mode. No: temperature will be shown

no yes - yes

Show defrost Sdf Yes: display will show "deF" during defrost; No: display will show temp no yes - yes

Assignments Assignment of inputs and outputs

S2 Application S2AApplication to be controlled with Sensor C(nC=Not Connected, Sco= Temp control, EuA= Evap temp, Con=Cond temp {condenser cleaning})

nC Con - EuA

S3 Application S3AApplication to be controlled with Sensor C(nC=Not Connected, Sco= Temp control, EuA= Evap temp, Con=Cond temp {condenser cleaning})

nC Con - nC

DI configuration diCdoC: Door contact, contact closed when door closed, doo: door contact, Contact open when door closed, buS:communication

doC doo - buS

DO1 configuration o1C Relay output 1. compressor (CoP) 2. Heater HeT CoP HeT - CoP

DO2 configuration 02CRelay output 2. No:not used; dEF:elec defr heater/hot gas valve; ALA:alarm output; FAn: fan control; Lig:light control

no Lig - dEF

DO3 configuration 03CRelay output 3. No:not used;dEF:elec defr heater/hot gas valve; ALA:alarm output; FAn: fan control; Lig:light control

Cop Het - FAn

Password level1 PS1 Shop owner most common parameters 0 999 - 0

Password level2 PS2Service technician all parameters with read permission and possibility to change a number of parameters

0 999 - 0

Cabinet light control source CLC "LEC": economy (and button if defined) only Lig LEC - Lig

Light OFF delay Lod Light OFF delay [sec] after door has been closed 0 300 sec 0

Service Service

Voltage value uAC Current main power supply voltage 0 270 Vac -

Relay 1 counter rL1 Thousands of cycles of compressor relay since manufacture 0 999 1000 -

Relay 2 counter rL2 Thousands of cycles of compressor relay since manufacture 0 999 1000 -

Relay 3 counter rL3 Thousands of cycles of compressor relay since manufacture 0 999 1000 -

Interval counter int Compressor run time since last defrost 0 999 min -

Defrost time counter dnt Duration of last defrost cycle [min] 0 999 min -

Door open counter ont ont/100=number of door openings since last reset 0 999 1 -

Firmware version Fir Danfoss software version number - - - -

Hardware version HAr Danfoss hardware version number - - - -

Problem Probable cause Remedy

Compressors does not start

Waiting for compressor delay timerCheck CoP -> CSt

Check CoP -> Pot/Pod

Defrost in progress Check DEF -> dit, dot

Line voltage to compressor too low or too high Check CoP -> uLi, uLo, uHi

Fan does not start Door is open or door contact is defectiveFan stops when door is opened

Check that door contact is OK

E01 or E02 or E03 is shown on display

E01: sensor "S1" defective

Replace sensorE02: sensor "S2" defective

E03: sensor "S3" defective

Display alternates between "Con" & temp. Condenser temperature exceed the temperature set in condenser settings menu

Clean condenser, check Con -> CAL, Cbl

Display alternates between "Hi" & temp. Temperature too high Check ALA -> HAt

Display alternates between "Lo" & temp. Temperature too low Check ALA -> LAt

Display show "dEF" Defrost in progress Check dis -> sdf

Display show "ECo" Economy mode Check dis -> SEC

Page 5: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

������ �������������� ������������������ ����������

Digital controller with off cycle defrost

XR30CCONTENTS1. GENERAL WARNING___________________________________________ 12. GENERAL DESCRIPTION _______________________________________ 13. CONTROLLING LOADS _________________________________________ 14. FRONT PANEL COMMANDS_____________________________________ 15. TEMPERATURE ALARM AND ITS DURATION RECORDING (HACCP) ___ 16. MAIN FUNCTIONS _____________________________________________ 17. PARAMETERS ________________________________________________ 28. DIGITAL INPUT________________________________________________ 29. INSTALLATION AND MOUNTING _________________________________ 310. ELECTRICAL CONNECTIONS ___________________________________ 311. HOW TO USE THE HOT KEY ____________________________________ 312. ALARM SIGNALS ______________________________________________ 313. TECHNICAL DATA _____________________________________________ 314. CONNECTIONS _______________________________________________ 415. DEFAULT SETTING VALUES ____________________________________ 4

1. GENERAL WARNING

1.1 PLEASE READ BEFORE USING THIS MANUAL• This manual is part of the product and should be kept near the instrument for

easy and quick reference.• The instrument shall not be used for purposes different from those described

hereunder. It cannot be used as a safety device.• Check the application limits before proceeding.

1.2 SAFETY PRECAUTIONS• Check the supply voltage is correct before connecting the instrument.• Do not expose to water or moisture: use the controller only within the operating

limits avoiding sudden temperature changes with high atmospheric humidity toprevent formation of condensation

• Warning: disconnect all electrical connections before any kind of maintenance.• Fit the probe where it is not accessible by the End User. The instrument must

not be opened.• In case of failure or faulty operation send the instrument back to the distributor

or to “Dixell s.r.l.” (see address) with a detailed description of the fault.• Consider the maximum current which can be applied to each relay (see

Technical Data).• Ensure that the wires for probes, loads and the power supply are separated

and far enough from each other, without crossing or intertwining.• In case of applications in industrial environments, the use of mains filters (our

mod. FT1) in parallel with inductive loads could be useful.

2. GENERAL DESCRIPTIONModel XR30C, format 32 x 74 mm, is a digital termostat with off cycle defrostdesigned for refrigeration applications at normal temperature. It provides two relayoutputs, one for the compressor, the other one can be used for alarm signalling oras auxiliary output. The probe input can be selected between PTC or NTC. Theinstrument has a digital input, for alarm signalling, for switching the auxiliary outputor for start a defrost cycle.

3. CONTROLLING LOADS

3.1 COMPRESSORThe regulation is performed according to the temperature measured by thethermostat probe with a positive differential from the set point: if the temperatureincreases and reaches set point plus differential the compressor is started and thenturned off when the temperature reaches the set point value again.

In case of fault in the thermostat probe the start and stop of the compressor aretimed through parameters “COn” and “COF”.

3.2 DEFROSTDefrost is performed through a simple stop of the compressor. Parameter “IdF”controls the interval between defrost cycles, while its length is controlled byparameter “MdF”.

4. FRONT PANEL COMMANDS

SET: To display target set point; in programming mode it selects a parameter orconfirm an operation.

(DEF) To start a manual defrost�� (UP): To see the last temperature alarm happened; in programming mode it

browses the parameter codes or increases the displayed value.�� (DOWN) To see the last temperature alarm happened; hold pressed it switches

the auxiliary output; in programming mode it browses the parameter codes ordecreases the displayed value.

KEY COMBINATIONS:

�� +�� To lock & unlock the keyboard.

SET +�� To enter in programming mode.SET + �� To return to the room temperature display.

4.1 USE OF LEDS

Each LED function is described in the following table.

LED MODE FUNCTIONON Compressor enabled

Flashing -Programming Phase (flashing with )- Anti-short cycle delay enabled

ON Defrost enabled

Flashing - Programming Phase (flashing with )

��� ON Second relay ONON An temperature alarm happened

5. TEMPERATURE ALARM AND ITS DURATIONRECORDING (HACCP)XR30C signals and records temperature alarms, together with their duration andmax value reached. See drawing:

Ex. High temperature alarm

Set

ALuH igh te mp . alarm

Tim e

Tem perature

ALLLow te mp . alarm

A la rm dura tion

M axTem perature

Safe food zone

5.1 HOW TO SEE THE ALARM DURATION AND MAX (MIN)TEMPERATUREIf the alarm LED is on, an alarm has taken place.To see the kind of alarm, the max (min) reached temperature and alarm duration doas follows:1. Push the Up or Down key.2. On the display the following message is shown::

“HAL” for high temperature alarm (“LAL” fot the minimum allarm), followed bythe Maximum (minimum) temperature.Then the “tiM” (tiMe) message is displayed, followed by the “Duration” inh.mm.

3. Then the instrument displays the temperature once again.

NOTE1: if an alarm is still occurring the “tim” shows the partial duration.NOTE2: the alarm is recorded when the temperature come back to normal values

5.2 HOW TO RESET A RECORDED ALARM OR ONE THAT ISSTILL OCCURRING1. Hold the SET key pressed for more than 3s, while the recorded alarm is

displayed. (the rSt message will be displayed)2. To confirm the operation, the “rSt” message starts blinking and the normal

temperature will be displayed.

6. MAIN FUNCTIONS

6.1 HOW TO SEE THE SETPOINT1. Push and immediately release the SET key: the display will

show the Set point value;

2. Push and immediately release the SET key or wait for 5 seconds to display theprobe value again.

Page 6: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

������ �������������� ������������������ ����������

6.2 HOW TO CHANGE THE SETPOINT1. Push the SET key for more than 2 seconds to change the Set point value;2. The value of the set point will be displayed and the LED starts blinking;3. To change the Set value push the �� or�� arrows within 10s.4. To memorise the new set point value push the SET key again or wait 10s.

6.3 HOW TO START A MANUAL DEFROSTPush the DEF key for more than 2 seconds and a manualdefrost will start.

6.4 HOW TO SWITCH ON OR OFF THE SECOND RELAY(OAC= LHt)

Hold pressed the �� key for some seconds, till the ��� LED isturned ON or OFF

6.5 HOW TO CHANGE A PARAMETER VALUETo change the parameter’s value operate as follows:

1. Enter the Programming mode by pressing the Set andDOWN key for 3s ( and start blinking).

2. Select the required parameter.3. Press the “SET” key to display its value (now only the

LED is blinking).4. Use “UP” or “DOWN” to change its value.

5. Press “SET” to store the new value and move to the following parameter.To exit: Press SET + UP or wait 15s without pressing a key.NOTE: the set value is stored even when the procedure is exited by waiting thetime-out to expire.

6.6 THE HIDDEN MENUThe hidden menu Includes all the parameters of the instrument.

6.6.1 HOW TO ENTER THE HIDDEN MENU1. Enter the Programming mode by pressing the Set + �� key

for 3s (LED 1 and start blinking).2. When a parameter is displayed keep pressed the Set+��

for more than 7s. The Pr2 label will be displayedimmediately followed from the HY parameter.NOW YOU ARE IN THE HIDDEN MENU.

3. Select the required parameter.4. Press the “SET” key to display its value (Now only the LED is blinking).5. Use �� or�� to change its value.6. Press “SET” to store the new value and move to the following parameter.To exit: Press SET + �� or wait 15s without pressing a key.NOTE: the set value is stored even when the procedure is exited by waiting thetime-out to expire.

6.6.2 HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THEFIRST LEVEL AND VICEVERSA.Each parameter present in the HIDDEN MENU can be removed or put into “THEFIRST LEVEL” (user level) by pressing “SET + ��”.In HIDDEN MENU when a parameter is present in First Level the decimal point ison.

6.7 HOW TO LOCK THE KEYBOARD

1. Keep pressed for more than 3 s the �� and�� keys.2. The “POF” message will be displayed and the keyboard will be locked. At this

point it will be possible only to see the set point or the MAX o Min temperaturestored

3. If a key is pressed more than 3s the “POF” message will be displayed.

6.8 TO UNLOCK THE KEYBOARDKeep pressed together for more than 3s the �� and�� keys, till the “Pon” messagewill be displayed.

6.9 THE CONTINUOUS CYCLEWhen defrost is not in progress, it can be activated by holdingthe “��” key pressed for about 3 seconds.

The compressor operates in continuous mode for the time set through the “CCt”parameter. The cycle can be terminated before the end of the set time using thesame activation key “��” for 3 seconds.

7. PARAMETERSNOTE: the parameters preceded by dots are in the Hidden Menu.REGULATIONHy Differential: (0,1 ÷ 25,5°C / 1÷255 °F) Intervention differential for set point.

Compressor Cut IN is Set Point Plus Differential (Hy). Compressor Cut OUT iswhen the temperature reaches the set point.

• LS Minimum set point: (- 50°C÷SET/-58°F÷SET): Sets the minimumacceptable value for the set point.

• US Maximum set point: (SET÷110°C/ SET÷230°F). Set the maximumacceptable value for set point.

Ot Thermostat probe calibration: (-12.0÷12.0°C;-120÷120°F) allows to adjust possible offset of the thermostat probe.

• OdS Outputs activation delay at start up: (0÷255min) This function isenabled at the initial start up of the instrument and inhibits any output activationfor the period of time set in the parameter.

AC Anti-short cycle delay: (0÷50 min) minimum interval between the compressorstop and the following restart.

• CCt Compressor ON time during continuous cycle: (0.0÷24.0h; res. 10min)Allows to set the length of the continuous cycle: compressor stays on withoutinterruption for the CCt time. Can be used, for instance, when the room is filledwith new products.

• COn Compressor ON time with faulty probe: (0÷255 min) time during whichthe compressor is active in case of faulty thermostat probe. With COn=0compressor is always OFF.

• COF Compressor OFF time with faulty probe: (0÷255 min) time during whichthe compressor is OFF in case of faulty thermostat probe. With COF=0compressor is always active.

CH Type of action: CL = cooling; Ht = heating.DISPLAY• CF Temperature measurement unit:

°C=Celsius; °F=Fahrenheit. WARNING: When the measurement unit ischanged the SET point and the values of the parameters Hy, LS, US, Ot, ALUand ALL have to be checked and modified if necessary).

rES Resolution (for °C): (in = 1°C; dE = 0.1 °C) allows decimal point display.DEFROSTIdF Interval between defrost cycles: (0÷120h) Determines the time interval

between the beginning of two defrost cycles.MdF (Maximum) length for defrost: (0÷255min) When P2P = n, (not evaporator

probe: timed defrost) it sets the defrost duration, when P2P = y (defrost endbased on temperature) it sets the maximum length for defrost.

• dFd Temperature displayed during defrost: (rt = real temperature; it =temperature at defrost start; SEt = set point; dEF = “dEF” label)

• dAd MAX display delay after defrost: (0÷255min). Sets the maximum timebetween the end of defrost and the restarting of the real room temperaturedisplay.

ALARMS• ALC Temperature alarms configuration: (Ab; rE)

Ab= absolute temperature: alarm temperature is given by the ALL or ALUvalues. rE = temperature alarms are referred to the set point. Temperaturealarm is enabled when the temperature exceeds the “SET+ALU” or “SET-ALL”values.

ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when thistemperature is reached the alarm is enabled, after the “ALd” delay time.

ALL Minimum temperature alarm: (-50.0 ÷ SET°C;-58÷230°F when this temperature is reached the alarm is enabled, after the“ALd” delay time.

• ALd Temperature alarm delay: (0÷255 min) time interval between thedetection of an alarm condition and alarm signalling.

• dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) timeinterval between the detection of the temperature alarm condition afterinstrument power on and alarm signalling.

SECOND RELAY AND DIGITAL INPUT• tbA Alarm relay silencing (with oAC=ALr):

(n= silencing disabled: alarm relay stays on till alarm condition lasts, y=silencing enabled: alarm relay is switched OFF by pressing a key during analarm).

OA1 Second relay configuration: ALr: alarm; LHt: auxiliary; onF: always on; dEF:do not select it!.; FAn: do not select it!.;

AoPAlarm relay polarity: it set if the alarm relay is open or closed when an alarmhappens. CL= the relay is closed; oP = the relay is open

i1P Digital input polarity: oP: the digital input is activated by opening the contact;CL: the digital input is activated by closing the contact.

i1F Digital input configuration:EAL = external alarm: “EA” message is displayed; bAL = serious alarm “CA”message is displayed. PAL = pressure switch alarm, “CA” message isdisplayed; dor = door switch function; dEF = activation of a defrost cycle; LHt=switch on the second relay if oA1=LHt; Htr = kind of action inversion (cooling– heating).

did: (0÷255 min)with i1F= EAL or i1F = bAL digital input alarm delay: delay between thedetection of the external alarm condition and its signalling.with i1F= dor: door open signalling delaywith i1F = PAL: time for pressure switch function: time interval to calculatethe number of the pressure switch activation.

nPS Pressure switch number: (0 ÷15) Number of activation of the pressureswitch, during the “did” interval, before signalling the alarm event (I2F= PAL).If the nPS activation in the did time is reached, switch off and on theinstrument to restart normal regulation.

• odc Compressor status when open door: no, Fan = normal; CPr, F_C =Compressor OFF

OTHERPbC Type of probe: it allows to set the kind of probe used by the instrument: PbC

= PBC probe, ntC = NTC probe.• rEL Software release for internal use.• Ptb Parameter table code: readable only.

8. DIGITAL INPUTThe free contact digital input is programmable in five different configurations by the“i1F” parameter.

Page 7: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

������ �������������� ������������������ ����������

8.1 DOOR SWITCH INPUT (i1F = dor)It signals the door status and the corresponding relay output status through the“odc” parameter:

no, Fan = normal (any change);CPr, F_C = Compressor OFF;

Since the door is opened, after the delay time set through parameter “did”, the dooralarm is enabled, the display shows the message “dA” and the regulation restarts.The alarm stops as soon as the external digital input is disabled again. With thedoor open, the high and low temperature alarms are disabled.

8.2 GENERIC ALARM (i1F = EAL)As soon as the digital input is activated the unit will wait for “did” time delay beforesignalling the “EAL” alarm message. The outputs status don’t change. The alarmstops just after the digital input is de-activated.

8.3 SERIOUS ALARM MODE (i1F = bAL)When the digital input is activated, the unit will wait for “did” delay before signallingthe “CA” alarm message. The relay outputs are switched OFF. The alarm will stopas soon as the digital input is de-activated.

8.4 PRESSURE SWITCH (i1F = PAL)If during the interval time set by “did” parameter, the pressure switch has reachedthe number of activation of the “nPS” parameter, the “CA” pressure alarm messagewill be displayed. The compressor and the regulation are stopped. When the digitalinput is ON the compressor is always OFF.If the nPS activation in the did time is reached, switch off and on theinstrument to restart normal regulation.

8.5 SWITCHING SECOND RELAY ON (i1F = LHt)With oA1= LHt it switches on and off the second relay.

8.6 START DEFROST (i1F = dFr)It starts a defrost if there are the right conditions. After the defrost is finished, thenormal regulation will restart only if the digital input is disabled otherwise theinstrument will wait until the “MdF” safety time is expired.

8.7 INVERSION OF THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)This function allows to invert the regulation of the controller: from cooling to heatingand viceversa.

8.8 DIGITAL INPUTS POLARITYThe digital input polarity depends on the “i1P” parameter.i1P=CL: the input is activated by closing the contact.i1P=OP: the input is activated by opening the contact

9. INSTALLATION AND MOUNTINGInstrument XR30C shall be mounted on verticalpanel, in a 29x71 mm hole, and fixed using thespecial bracket supplied.To obtain an IP65 protection grade use the frontpanel rubber gasket (mod. RG-C) as shown infigure.

The temperature range allowed for correct operation is 0÷60 °C. Avoid placessubject to strong vibrations, corrosive gases, excessive dirt or humidity. The samerecommendations apply to probes. Let air circulate by the cooling holes.

10. ELECTRICAL CONNECTIONSThe instrument is provided with screw terminal block to connect cables with a crosssection up to 2,5 mm2. Before connecting cables make sure the power supplycomplies with the instrument’s requirements. Separate the probe cables from thepower supply cables, from the outputs and the power connections. Do not exceedthe maximum current allowed on each relay, in case of heavier loads use a suitableexternal relay.

10.1 PROBE CONNECTIONThe probes shall be mounted with the bulb upwards to prevent damages due tocasual liquid infiltration. It is recommended to place the thermostat probe away fromair streams to correctly measure the average room temperature. Place the defrosttermination probe among the evaporator fins in the coldest place, where most ice is

formed, far from heaters or from the warmest place during defrost, to preventpremature defrost termination.

11. HOW TO USE THE HOT KEY

11.1 HOW TO PROGRAM A HOT KEY FROM THEINSTRUMENT (UPLOAD)1. Program one controller with the front keypad.2. When the controller is ON, insert the “Hot key” and push �� key; the "uPL"

message appears followed a by flashing “End”3. Push “SET” key and the End will stop flashing.4. Turn OFF the instrument remove the “Hot Key”, then turn it ON again.

NOTE: the “Err” message is displayed for failed programming. In this case pushagain �� key if you want to restart the upload again or remove the “Hot key” to abortthe operation.

11.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY(DOWNLOAD)1. Turn OFF the instrument.2. Insert a programmed “Hot Key” into the 5 PIN receptacle and then turn

the Controller ON.3. Automatically the parameter list of the “Hot Key” is downloaded into the

Controller memory, the “doL” message is blinking followed a by flashing“End”.

4. After 10 seconds the instrument will restart working with the new parameters.5. Remove the “Hot Key”..

NOTE the message “Err” is displayed for failed programming. In this case turn theunit off and then on if you want to restart the download again or remove the “Hotkey” to abort the operation.

12. ALARM SIGNALSMessage Cause Outputs“P1” Room probe failure Compressor output according

to par. “Con” and “COF”“HA” Maximum temperature alarm Outputs unchanged.“LA” Minimum temperature alarm Outputs unchanged.“dA” Door open Regulation restarts“EA” External alarm Output unchanged.“CA” Serious external alarm (i1F=bAL) All outputs OFF.“CA” Pressure switch alarm (i1F=PAL) All outputs OFF

12.1 ALARM RECOVERYProbe alarm “P1” starts some seconds after the fault in the related probe; itautomatically stops some seconds after the probe restarts normal operation. Checkconnections before replacing the probe.Temperature alarms “HA” and “LA” automatically stop as soon as the thermostattemperature returns to normal values and when defrost starts.Alarms “EA” and “CA” (with i1F=bAL) recover as soon as the digital input isdisabled.Alarm “CA” (with i1F=PAL) recovers only by switching off and on the instrument.

13. TECHNICAL DATAHousing: self extinguishing ABS.Case: XR30C frontal 32x74 mm; depth 60mm;Mounting: XR30C panel mounting in a 71x29mm panel cut-outProtection: IP20.Frontal protection: IP65 with frontal gasket RG-C (optional).Connections: Screw terminal block ≤ 2,5 mm2 wiring.Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac±10%, 50/60Hz, 110Vac ±10%, 50/60HzPower absorption: 3VA maxDisplay: 3 digits, red LED, 14,2 mm high.Inputs: 1 NTC or PTC probe.Digital input: free contactRelay outputs

compressor: SPST relay 8(3) A, 250Vac orSPST relay 20(8)A; 250Vac

second relay: SPDT relay 8(3) A, 250Vac orData storing: on the non-volatile memory (EEPROM).Kind of action: 1B; Pollution grade: normal; Software class: A.Operating temperature: 0÷60 °C.Storage temperature: -30÷85 °C.Relative humidity: 20÷85% (no condensing)Measuring and regulation range:

NTC probe: -40÷110°C (-40÷230°F)PTC probe: -50÷150°C (-58÷302°F)

Resolution: 0,1 °C or 1°C or 1 °F (selectable).Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit

Page 8: Power’s Sliding Glass 3 Door Floral Coolers For Bush ... · Power’s Sliding Glass 3 Door Floral Coolers For Bush Refrigeration Bush Refrigeration 1-877-907-8387 • Fax: 856-963-0770

������ �������������� ������������������ ����������

14. CONNECTIONS

14.1 XR30C: 8A COMPRESSOR

N.C .

� � � � � � �

� �� �� ��

CompAux/

Alarm

Roo

m

Hot Key

8(3)A250V 8(3)A250V

Line

12Vac/dc supply: connect to the terminals 7 and 8.24Vac/dc supply: connect to the terminals 7 and 8.120Vac supply: connect to the terminals 7 and 8.

14.2 XR30C: 20A COMPRESSOR

N.C .

� � � � � � �

� �� �� ��

Comp

Hot Key

8(3)A250V 20(8)A250V

Line

Aux/Alarm

Roo

m

12Vac/dc supply: connect to the terminals 7 and 8.24Vac/dc supply: connect to the terminals 7 and 8.120Vac supply: connect to the terminals 7 and 8.

15. DEFAULT SETTING VALUESLabel Name Range °C/°F

Set Set point LS÷US 3.0/37Hy Differential 0,1÷25.5°C/ 1÷ 255°F 2.0/4LS Minimum set point -50°C÷SET/-58°F÷SET -50,0/-58US Maximum set point SET÷110°C/ SET ÷ 230°F 110/230Ot Thermostat probe calibration -12÷12°C /-120÷120°F 0.0

OdS Outputs delay at start up 0÷255 min 0AC Anti-short cycle delay 0 ÷ 50 min 1CCt Continuos cycle duration 0.0÷24.0h 0.0

COn Compressor ON time with faultyprobe

0 ÷ 255 min 15

COF Compressor OFF time with faultyprobe

0 ÷ 255 min 30

CH Kind of action CL=cooling; Ht= heating CLCF Temperature measurement unit °C ÷ °F °C/°FrES Resolution in=integer; dE= dec.point dE/-IdF Interval between defrost cycles 1 ÷ 120 ore 8

MdF (Maximum) length for defrost 0 ÷ 255 min 20dFd Displaying during defrost rt, it, SEt, DEF itdAd MAX display delay after defrost 0 ÷ 255 min 30ALc Temperat. alarms configuration rE= related to set;

Ab = absoluteAb

ALU MAXIMUM temperature alarm Set÷110.0°C; Set÷230°F 110/230ALL Minimum temperature alarm -50.0°C÷Set/ -58°F÷Set -50/-58ALd Temperature alarm delay 0 ÷ 255 min 15dAO Delay of temperature alarm at

start up0 ÷ 23h e 50’ 1.3

tbA Alarm relay silencing n=no; y=yes YoA1 2nd relay configuration ALr= alarm; dEF=no select it;

LHt=auxiliary; onF=always on;Fan= no select it

LHt

AoP Second relay polarity (oA1=ALr) oP; cL cLi1P Digital input polarity oP=opening;CL=closing cLi1F Digital input configuration EAL=extern. alarm; bAL=lock

regulation; PAL=press. switch;dor=door switch; dEF=defrost;LHt=switch on 2nd relay; Htr=

cooling - heating

LHt

did Digital input alarm delay 0÷255min 5Nps Number of activation of pressure

switch0 ÷15 15

odc Compressor status with opendoor:

no, Fan = normal;CPr; F_C = Compr. OFF;

no

PbC Kind of probe Ptc; ntc ntc/PtcrEL Software release -- 4.0Ptb Map code -- -

Hidden parameters