POWER SYSTEM PROTECTION SOLUTIONS FOR FUTURE …
Transcript of POWER SYSTEM PROTECTION SOLUTIONS FOR FUTURE …
POWER SYSTEM PROTECTION SOLUTIONS FOR FUTURE TRANSMISSION NETWORKS THE MIGRATE PROJECT 21st November, Tres Cantos
INDEX
1. PEIG: IMPACT ON PROTECTION ALGORITHMS
2. PRESENT PROTECTION SCHEMES IN TRANSITION AND HIGH PEIG PENETRATION SCENEARIOS
3. FUTURE PROTECTION SCHEMES: NEW TECHNOLOGIES AND APPROACHES IN PROTECTION
ALGORITHMS
1. PEIG: IMPACT ON PROTECTION ALGORITHMS
- Short circuit current contribution from Power Electronic
Interfaced Generation systems (PEIG) differs from classical
Synchronous Generation:
- The Short Circuit Current contribution is fixed by Power
Electronic Control Strategies and the type of converter.
- Grid Codes stablish the requirements to PEIG to be connected to
the Grid:
Protection of Future Power Systems. Challenges of the future! 3
Capability of PE-based
components to stay connected
in short periods after a
fault inception in the grid
Capability of
injection/comsume of reactive
power to reduce voltage dip
I2 INJECTION?
1. PEIG: IMPACT ON PROTECTION ALGORITHMS
Protection of Future Power Systems. Challenges of the future! 4
Source: CIRCE, MIGRATE D4.3 presentation
TYPE IV, PV, AND HVDC: Short Circuit
Current Contribution fully fixed by
Power Electronic control.
Source: “Negative sequence current injection by power electronics based generators and its impact on faulted phase selection algorithms of dist ance protection” presented in Western Protective Relay Conference October 2018, Spokane , US.
1. PEIG: IMPACT ON PROTECTION ALGORITHMS
Protection of Future Power Systems. Challenges of the future! 5
• Distance protection (21) is the most affected protection function in
transition and high pnetration scenarios of Type IV PV and HVDC
systems:
o Waveform currents are distorted during transition period and
differs from classical synchronous generator shortcircuit current
contribution.
o The control strategy of suppression of Negative Sequence Current
Injection (I2) makes that PEIG fed any type of fault in a balanced
way in the short circuit steady state.
o Consequences:
- Negative Impact on Direcionality Algorithms
- Negative impact on Faulty Phase Selection Algorithms :
- Superimposed currents.
- Angle between I2/I0
- Impedance phase loops.
- Negative impact on Impedance Phasor Estimation after fault
inception.
o Better performance expected with Negative Sequence Current
Injection (I2)
1. PEIG: IMPACT ON PROTECTION ALGORITHMS
Protection of Future Power Systems. Challenges of the future! 6
Short circuit contribution affected by Power Electronic Control:
o Great influence of Crowbar Control Strategy : (Example of Phase to
Phase Fault)
o Consequences on Distance Protection Funtion (21):
- Negative Impact on Fault Detection
- Negative Impact on Directionality
- Negative impact on Impedance Phasor Estimation.
2. PRESENT PROTECTION SCHEMES IN TRANSITION AND HIGH PENETRATION SCENEARIOS
Protection of Future Power Systems. Challenges of the future! 7
o SUMMARIZING THE PROBLEMS…..
DISTANCE PROTECTION IS THE MOST AFFECTED PROTECTION FUNCTIONS IN TRANSITION
AND HIGH PEIG PENETRATION SCENARIO.
FREQUENCY ISSUES RUNNING LOW INERTIA SYSTEMS ARE ALSO EXPECTED
PROBLEMS EXPECTED WITH DIRECTIONALITY DECLARATION AS PHASOR FREQUENCY DIFFERENCE OF
POLARIZING MEMORY VOLTAGE AND CURRENT PHASORS CAN LEAD WRONG DIRECTIONALITY DECLARATION
o SCENARIOS:
STRONG
SYNCHRONO
US BASED
GENERATIO
N GRID
FULL CONVERTER
DFIG
PV SYSTEM
FULL CONVERTER
DFIG
PV SYSTEM
WEAK
SYNCHRON
OUS BASE
GENERATI
ON GRID
FULL CONVERTER
PV SYSTEM
DFIG
TRANSITION SCENARIO HIGH PEIG PENETRATION SCENARIO
MIX
2. PRESENT PROTECTION SCHEMES IN TRANSITION AND HIGH PENETRATION SCENEARIOS
Protection of Future Power Systems. Challenges of the future! 8
STRONG
SYNCHRONO
US BASED
GENERATIO
N GRID
FULL CONVERTER
DFIG
PV SYSTEM
SYNCHRONOUS
GENERATION BASED NODE BB FAULT
LINE FAULT
PEIG BB FAULT
PROTECTION
SYSTEM
87L 21 67N
87L 21 67N
PRESENT PROTECTION SYSTEM SCHEMES :
OPTION 1 :
2x PROTECTION (PRIMARY
AND BACKUP)
2x OPTICAL FIBER
COMMUNICATION
21-TP SCHEEME
67N
87L 21 67N
OPTION 2:
2x PROTECTION (PRIMARY
AND BACKUP)
1x OPTICAL FIBER
COMMUNICATION
1X CARRIER WAVE
COMMUNICATION
FAULT PERFORMANCE OPTION 1 IN N-1 COMMENT OPTION 1 PERFORMANCE OPTION 2 IN N-1 COMMENT OPTION 2
LINE FAULT (N-1 = 1 x OPTICAL FIBER FAILLURE)
GOOD 87L EXPECTED TO WORK PROPERLY GOOD 21 – TP EXPECTED TO WORK PROPERLY IMPLEMETING WEAK
INFEED SCHEEME.
SGB NODE BB FAULT (N-1 = SGB NODE BBP FAILLURE)
GOOD PROTECTION SYSTEM OF FEEDERS CONNECTED TO SG GRID FAIL SYSTEM PROTECTION OF PEIG
Z2 PROTECTION SYSTEM OF SG GRIDS EXPECTED TO WORK PROPERLY
Z2/Z_REV PEIG DELAYED TRIPS OR MISSED TRIPS
GOOD PROTECTION SYSTEM OF FEEDERS CONNECTED TO SG GRID FAIL SYSTEM PROTECTION OF PEIG
Z2 FEEDERS SG GRIDS EXPECTED TO WORK PROPERLY
Z2/Z_REV PEIG DELAYED TRIPS OR MISSED TRIPS
PHASE PEIG BB FAULT (N-1 = PEIG NODE BBP FAILLURE )
GOOD Z2/Z_REV PROTECTION SYSTEM PEIG EXPECTED TO WORK PROPERLY
GOOD Z2/Z_REV PROTECTION SYSTEM PEIG EXPECTED TO WORK PROPERLY
TRANSITION SCENARIO
SGB NODE
PEIG NODE
TRANSITION SCENARIO PROTECTION SYSTEM PERFORMANCE:
2. PRESENT PROTECTION SCHEMES IN TRANSITION AND HIGH PENETRATION SCENEARIOS
Protection of Future Power Systems. Challenges of the future! 9
WEAK
SYNCHRONOUS
BASED
GENERATION
GRID
FULL CONVERTER
DFIG
PV SYSTEM
SGB NODE AND PEIG
BB FAULT
LINE FAULT
PEIG BB FAULT
PROTECTION
SYSTEM
87L 21 67N
87L 21 67N
PRESENT PROTECTION SYSTEM SCHEMES :
OPTION 1 :
2x PROTECTION (PRIMARY
AND BACKUP)
2x OPTICAL FIBER
COMMUNICATION
21-TP SCHEEME
67N
87L 21 67N OPTION 2:
2x PROTECTION
(PRIMARY AND BACKUP)
1x OPTICAL FIBER
COMMUNICATION
1X CARRIER WAVE
COMMUNICATION
FAULT PERFORMANCE OPTION 1 IN N-1 COMMENT OPTION 1 PERFORMANCE OPTION 2 IN N-1 COMMENT OPTION 2
PHASE LINE FAULT (N-1 = 1 x OPTICAL FIBER FAILLURE)
GOOD 87L EXPECTED TO WORK PROPERLY POTENTIAL FAIL 21 – TP COULD MALOPERATE , BOTH ENDS POTENTIAL WEAK INFEED AND
HIGH PEIG FEEDED
PHASE SG BB FAULT (N-1 = SGB NODE BBP FAILLURE)
POTENTIAL FAIL PROTECTION SYSTEM FEEDERS CONNECTED TO
PEIG + SGB NODE FAIL PEIG PROTECTION SYSTEM
PERFORMANCE DEPENDING ON GENERATION MIX OF SG AND PEIG Z2/Z_REV PEIG DELAYED TRIPS OR
MISSED TRIPS
POTENTIAL FAIL FEEDERS CONNECTED TO PEIG + SGB NODE
FAIL PEIG PROTECTION SYSTEM
PERFORMANCE DEPENDING ON GENERATION MIX OF SG AND PEIG Z2/Z_REV PEIG DELAYED TRIPS OR
MISSED TRIPS
PHASE PEIG BB FAULT (N-1 = PEIG NODE BBP FAILLURE )
POTENTIAL FAIL PROTECTION SYSTEM FEEDERS CONNECTED TO
PEIG + SGB NODE FAIL PEIG PROTECTION SYSTEM
PERFORMANCE DEPENDING ON GENERATION MIX OF SG AND PEIG Z2/Z_REV PEIG DELAYED TRIPS OR
MISSED TRIPS
POTENTIAL FAIL FEEDERS CONNECTED TO PEIG + SGB NODE
FAIL PEIG PROTECTION SYSTEM
PERFORMANCE DEPENDING ON GENERATION MIX OF SG AND PEIG Z2/Z_REV PEIG DELAYED TRIPS OR
MISSED TRIPS
HIGH PEIG PENETRATION SCENARIO
SGB AND PEIG
NODE PEIG NODE
FULL CONVERTER
DFIG
PV SYSTEM MIX
HIGH PEIG PENETRATION SCENARIO PROTECTION SYSTEM PERFORMANCE:
2. PRESENT PROTECTION SCHEMES IN TRANSITION AND HIGH PEIG PENETRATION SCENEARIOS
Protection of Future Power Systems. Challenges of the future! 10
• CONCLUSSIONS:
IN TRANSITION SCENARIO, PRESENT PROTECTION SCHEEMES ARE STILL RELIABLE:
PROBLEMS TO DETECT BUSBAR FAULTS IN N-1 FROM PEIG PROTECTION SYSTEMS, BUT DOES NOT
REPRESENT TRANSMISSION SYSTEM STABILITY RISKS.
IN HIGH PEIG PENETRATION SCENARIO, NEED FOR HIGHER LEVEL OF PROTECTION EQUIPMENT REQUIREMENTS:
PROBLEMS TO DETECT LINE FAULTS IN N-1
PROBLEMS TO DETECT BUSBAR FAULTS IN N-1, REPRESENTING TRANSMISSION SYSTEM STABILITY
RISKS FOR REMAINING SYNCHRONOUS GENERATION CONNECTED TO THE GRID RECOMMENDED 2 X 87B
FURTHER STUDIES MUST BE CARRIED OUT TO CHECK THE PERFORMANCE OF HIGH PEIG PENETRATION GRIDS:
NON HOMOGENEOUS GRID CODE IMPLEMENTATION ON PEIG I2 SHORT CIRCUIT CURRENTS LEVEL AND
IT’S IMPACT ON ALGORITHM ELEMENTS BASED ON I2
LOWER SHORTCIRCUIT CURRENTS EXPECTED IMPACT ON PROTECTION ALGORITHMS
OPTION 1 :
2x PROTECTION (PRIMARY AND BACKUP)
2x OPTICAL FIBER COMMUNICATION
3. FUTURE PROTECTION SCHEMES: NEW
TECHNOLOGIES AND APPROACHES IN PROTECTION
ALGORITHMS
Protection of Future Power Systems. Challenges of the future! 11
• ARE TRANSITION AND HIGH PEIG SCENARIOS REALISTIC?
• POWER ELECTRONICS INTRODUCES UNCERTAINTY IN PROTECTION ALGORITHMS
PERFORMANCE, SO THERE WILL BE A NEED OF NEW TECHNOLOGIES AND
APPROACHES TO PRESENT PROTECTION ALGORITHMS :
IMPROVEMENTS IN PHASOR BASED (FREQUENCY DOMAIN) ALGORITHMS IS IT POSSIBLE?
SUPPORT FROM DELTA QUANTITIES?
TRAVELLING WAVES ALGORITHM (TIME DOMAIN) STATE OF THE ART? PROBLEMS?
OTHER TECHNOLOGIES WAMS ? COMMUNICATION REQUIREMENTS? TIME SYNCHRONIZATION
AND TIME DISTRIBUTION BECAMES CRITICAL
Source: www.lainformacion.com
MIGRATE WP4. ROUNDTABLE 1: SHORT-CIRCUIT BEHAVIOR OF POWER ELECTRONICS BASED GENERATORS VS SYNCHRONOUS GENERATORS
M. Popov and J. Chavez
Madrid, November 20-21, 2019
ROUNDTABLE 1. DFIG SYSTEM
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 1 13
DC
DC AC
AC
DFIG
Interconnection
Transformer
Filter Crowbar
DC Chopper
is
ir
+
-
GSC Control
RSC Control
ROUNDTABLE 1. DFIG CONTROLS
CROWBAR AND CHOPPER PROTECTION
– CHOPPER
+ Voltage limit
– CROWBAR
+ Current limit, Time action, Impedance.
CONVERTERS: GRID FOLLOWING CONTROL
– GSC CONTROL STRATEGIES
+ Positive
– DC voltage,
– Reactive power supply.
+ Negative
– 2 minimization
– RSC CONTROL STRATEGIES
+ Positive
– Reactive power support,
– MPPT.
+ Negative
– 2 minimization
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 1 14
U(pu)
t(ms)
0 140-150140-250 450 2500-10000
HVDC-linkPE based unit
1500-3000
0-0.3
0.25-0.85
0.85-0.9
1
HVDCPE
DI/IN
DU/UN-10% 10%-50%
-100%
Reactive current static:k=(DI/IN)/(DU/UN)
Bus 10
Bus 11
DC
DC AC
AC
TR2H DFIG
[1] L. Xiu, “Coordinated control of DFIG’s Rotor and Grid Side Converters During Network Unbalance” IEEE Trans. Power Electronics, Vol 23, No 3, 2008.
ROUNDTABLE 1. DFIG CONTROL
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 1 15
–POSITIVE FRAME:
+ GSC reference:
– 𝐼𝑔𝑑+∗ by DC voltage regulator
– 𝐼𝑔𝑞+∗ by Grid Code at PCC
+ RSC reference: – 𝐼𝑟𝑑
+∗ by the Grid Code at PCC
– 𝐼𝑟𝑞+∗ by optimal power reference calculation
–NEGATIEVE FRAME:
+ GSC reference: – Stator and GSC active power harmonics
components equals.
– 𝐼𝑔𝑑−∗ Zero active power pulsation (𝑃𝑔𝑐𝑜𝑠2= 𝑃𝑒𝑐𝑜𝑠2)
– 𝐼𝑔𝑑−∗ Zero active power pulsation (𝑃𝑔𝑠𝑖𝑛2= 𝑃𝑒𝑠𝑖𝑛2)
+ RSC reference: – Harmonics components of active power set to
zero
– 𝐼𝑟𝑑−∗ Torque oscillation minimization (𝑃𝑒𝑐𝑜𝑠2= 0)
– 𝐼𝑟𝑞−∗ Torque oscillation minimization(𝑃𝑒𝑠𝑖𝑛2 = 0)
ROUNDTABLE 1. SIGNALS DURING A FAULT
LN FAULT LL FAULT LLL FAULT
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 1 16
CONTROL SYSTEMS FOR TYPE-4 WT AND PV SYSTEMS DURING SHORT CIRCUITS
CIRCE
Eduardo Martínez Carrasco et al.
November 20th – Madrid
MODELLING WT AND PV CONTROL SYSTEMS
18
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
FAULT APPEARS REACTIVE POWER
SUPPORT
ACTIVE AND REACTIVE POWER
CALCULATION
WHAT HAPPENS WITH NEGATIVE SEQUENCE CURRENT?
DC/AC
= =
Source: Power System Analysis. Grainger & Stevenson
𝑉𝑎(2)= 𝑍2 · 𝐼𝑎
(2)
MODELLING WT AND PV CONTROL SYSTEMS
19
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
EXTERNAL GRID
COMPARISON WITH SYNCHRONOUS GENERATION BASED ON SUPERIMPOSED QUANTITIES
20
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
SYNCHRONOUS GENERATOR TYPE 4 WIND TURBINE
Phase to phase
fault (AB)
Scalar Products: 𝑺𝑷𝑨𝑩,
𝑺𝑷𝑩𝑪, 𝑺𝑷𝑪𝑨
Phase to ground
fault (AG)
Scalar Products: 𝑺𝑷𝑨𝑩,
𝑺𝑷𝑩𝑪, 𝑺𝑷𝑪𝑨
SCALAR PRODUCT
DEFINITION
𝑆𝑃𝐴𝐵 = ∆𝑉𝐴𝐵 · ∆𝐼𝐴𝐵
DeltaA DeltaB DeltaC
t/s0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10 0,11
-600
-400
-200
0
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
DeltaA DeltaB DeltaC
t/s0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10 0,11
-150
-100
-50
0
50
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
DeltaA DeltaB DeltaC
t/s0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10 0,11
-2000
-1000
0
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
DeltaA DeltaB DeltaC
t/s0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10 0,11 0,12
-300
-200
-100
0
100
200
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
Fault type ∆𝑻𝑨𝑩 ∆𝑻𝑩𝑪 ∆𝑻𝑪𝑨
𝑨𝑮 ∆𝑇𝐴𝐵 < 0.1 · ∆𝑇𝐴𝐵 NC1
𝑩𝑮 NC ∆𝑇𝐵𝐶 < 0.1 · ∆𝑇𝐵𝐶
𝑪𝑮 < 0.1 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
𝑨𝑩,𝑨𝑩𝑮 ∆𝑇𝐴𝐵 > 0.25 · ∆𝑇𝐴𝐵
< 0.75 · ∆𝑇𝐴𝐵 NC
𝑩𝑪,𝑩𝑪𝑮 NC ∆𝑇𝐵𝐶 > 0.25 · ∆𝑇𝐵𝐶
< 0.75 · ∆𝑇𝐵𝐶
𝑪𝑨,𝑪𝑨𝑮 > 0.25 · ∆𝑇𝐶𝐴
< 0.75 · ∆𝑇𝐶𝐴 NC ∆𝑇𝐶𝐴
1 NC: Not Considered
𝑆𝑃𝐴𝐵 𝑆𝑃𝐵 𝑆𝑃 𝐴 𝑆𝑃𝐴𝐵 𝑆𝑃𝐵 𝑆𝑃 𝐴
𝑆𝑃𝐴𝐵 𝑆𝑃𝐵 𝑆𝑃 𝐴 𝑆𝑃𝐴𝐵 𝑆𝑃𝐵 𝑆𝑃 𝐴
MIGRATE WP4. ROUNDTABLE 2: IMPACT OF PE BASED GENERATORS IN PRESENT SHORT CIRCUIT PROTECTION SYSTEMS
M. Popov and J. Chavez
Madrid, November 20-21, 2019
ROUNDTABLE 2: SHORT CIRCUIT TRANSMISSION LINES
– Faults at Line 4-6, 5-7 and 5-4
– The Benchmark model developed reproduces potential problems for protections due to
high level of penetration of power electronics
+ Control systems of renewables acts over the fault current.
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 2 22
TRM
ROUNDTABLE 2: HARDWARE
IN LOOP
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 2 23
ROUNDTABLE 2: IMPEDANCE
TRAJECTORY AND RMS CURRENT
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 2 25
R/Ohm(secondary)
X/O
hm
(seco
ndary)
-2 -1 0 1 2
0.00
0.50
1.00
1.50
2.00
2.50 Z1 Z2
Z L12
R/Ohm(secondary) -2 -1 0 1 2
X/O
hm
(seco
nd
ary)
0.00
0.50
1.00
1.50
2.00
2.50
Z
Z
2 Z L
12
R/Ohm(secondary) -2 -1 0 1 2
0.00 X
/Ohm
(seco
nd
ary)
0.50
1.00
1.50
2.00
2.50 Z1 Z2
Z L12
LL FAULT at 70% TL 0Ω SG 40MW DFIG 40MW DFIG 200MW
EFFECTS OF TYPE-4 WT AND PV SYSTEMS ON DISTANCE PROTECTION BEHAVIOR
CIRCE
Samuel Borroy Vicente et al. ([email protected])
November 20th – Madrid
TESTING AND ANALYSIS: METHODOLOGY AND TOOLS
27
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
Manuf. A
Manuf. B
Manuf. C
Manuf. D
Each test is automatically performed,
recorded and evaluated according to
the obtained tripping times
Detailed oscillography analysis
Benchmark network
Accurate PE models
Scenarios & case studies
Faults characteristics & locations
IEC-60255:121 Standard for distance protection automated in RTDS
Developed tools: RTDS scripts
Conclusions
RESULTS
Statistics of obtained results for scenario 100% renewable
28
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
Distance protection: results for scenario 100% renewable (fault contribution
from wind turbine type 4 / PV)
% of faults resulting in missed trip % of faults resulting in delayed trip or overreach
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante A
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante B
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante C
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante D
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante A
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante B
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante C
0,00%
5,00%
10,00%
15,00%
20,00%
SLG LL LLG LLL
Fabricante D
Manufacturer A: 53.33% Manufacturer B: 38.33%
Manufacturer C: 35.00% Manufacturer D: 38.33%
Manufacturer A: 20.00% Manufacturer B: 30.83%
Manufacturer C: 25.00% Manufacturer D: 31.67%
ANALYSYS AND CONCLUSIONS
Detailed analysis of distance protection behavior
29
CIRCE – MIGRATE WP4 workshop - November 20th 2019 - Madrid
Distance protection
performance for type 4 wind
turbine contribution. Line to line
fault (A-B fault)
+ and – seq. Transition Only seq. +
I
V
Z
Reverse directionality
Fault selection phase A
Fault selection phase B
Fault selection phase C
Fault selection ground
o Directionality declaration
o Faulted phase identification
o Impedance calculation
Main issues found:
PRESENTATION
1. Power network model studied
2. Phase to ground fault
3. Phase to phase fault
4. Weak infeed
5. Conclusion
New common phase to ground fault:
Because of the connection of the PE through a power
transformer a single phase to ground fault creates faults on
all phases:
Example of a A phase to ground fault that leads to the
increase of the same 3 phase sinusoidal currents (as well as
in the neutral path).
33
2.- NEW COMMON FAULT SIGNATURES
NOV 2019
New phase to phase fault:
The PE controller impacts the
signature of the faulty current
Example of an AB fault seen as
AB until the PE control impacts
the current flow (8 to 10 ms
response time) and then is
wrongly seen as a AN fault if
currents are used.
34
3.- NEW FAULT SIGNATURES
NOV 2019
Weak infeeds:
For weak infeeds, the distance
protection impedance calculation
can be wrong (outside the
characteristic) in case of resistive
fault.
Example of a 1 Ω AB fault at 5% of
a 35km line from a 100MW power
plant.
35
4.- NEW FAULT SIGNATURES
NOV 2019
Conclusions:
New Algorithms are needed, either:
+ Improved algorithm based on current (and voltage)
+ New algorithm based on voltage
– Undervoltage faulty phase selection
The undervoltage faulty phase selection is based on the
measurement of the three phase voltages.
The algorithm replaces the existing faulty phase
selection based on currents for lines up to around 250 km.
Weak infeed protection needs to be run in parallel of the
distance protection for weak infeed lines.
36
5.- NEW FAULT DETECTION
NOV 2019
MIGRATE WP4. ROUNDTABLE 3:
NEW PROTECTION ENHANCEMENTS AND TECHNOLOGIES FOR A FUTURE SCENARIO WITH HIGH SHARES OF RENEWABLES
M. Popov and J. Chavez
Madrid, November 20-21, 2019
HYBRID RELAY BASED S-TRANSFORM
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 3 38
CASE 1: DFIG-40MW, STRONG GRID.
FAULT: LL, 70%, 0Ω, 0°
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 3 39
GSVSC1
GSVSC 2Sk=10 GW
X/R=3
Bus 13
Bus 1 Bus 2 Bus 3 Bus 4
Bus 5Bus 6
Bus 7 Bus 8
Bus 9
Bus 10
Bus 11
Bus 12
HVDC
DC
DC
DCAC
DC
DC AC
AC
DC
DC
ACAC
TR1H
TR3H
TR2H DFIG
PV
Load 1Load 2
FC
400 kV33 kV
14.5 kV13.8 kV0.69 kV0.48 kV
PERFORMANCE COMPARISON
Priority Variables
1 Number of lines 2 2 Scenarios 6 3 Generation Level 2 4 Point of the line 6 5 Type of fault 4 6 Fault Resistance 2 7 Repetition 3
TOTAL NUMBER OF CASES 3456
20th-21th November 2019, Madrid WP4: Dissemination event. Roundtable 3 40
0 fault 1 fault
RelayD SG
RelayD RW
RelayHybrid
RW
Error 0,00 34,09 0,00
Delay 4,55 25,00 2,27
Ok 95,45 50,00 97,73
0,0020,0040,0060,0080,00
100,00
%
RelaySG
RelayRW
HybridRW
Error 13,64 36,36 11,36
Delay 15,91 34,09 9,09
Ok 70,45 29,55 79,55
0,0020,0040,0060,0080,00
100,00
%
Presenter: Prof Vladimir Terzija
Research team: G. Liu, M. Sun, S. Azizi and V. Terzija
The University of Manchester
Madrid, 20-21 November 2019
Fast UFLS is vital in low inertia systems (extra decision variables)
Application of COI’s frequency to improving UFLS performance
Need of communication (latencies)
Motor loads not considered
An innovative technique for local estimation of COI’s ROCOF
UFLS with known system inertia (one-stage UFLS)
Generalized UFLS with unknown system inertia (two-stage UFLS)
PROPOSED COMMUNICATION-FREE UFLS FOR SYSTEMS WITH VOLATILE INERTIA
D D D2 COI
COI COI COI
d fH D f P
dt
UFLS RELAY MODELLING
43
Maximum available load to be shed in
the system
Maximum available load to be shed in
the system
One-stage UFLS used when system inertia is known
Two-stage UFLS used when system inertia is unknown
TRADE-OFF BETWEEN LOAD SHEDDING SIZE AND FREQUENCY NADIR
44
Proposed communication-free UFLS schemes can deliver higher nadir with less load shedding
Overshedding will be avoided at all cost (economic, frequency overshoot).
Due to fast event estimation, the scheme immediately sheds an appropriate amount of load:
Case 1 (β=0.83), same amount of load shed as conventional provides much higher nadir.
Case 2 (β=0.45), much less amount of load shed can deliver the same nadir.
Effective factor β=(load shedding amount) ÷ (estimated disturbance size)
PROPOSAL OF AN ENHANCED DISTANCE PROTECTION
CIRCE
Eduardo Martínez Carrasco et al.
November 21st – Madrid
INNOVATION
FOCUS IS ON FAULTED PHASE SELECTION. DESIGNING THE ALGORITHM
46
CIRCE – MIGRATE WP4 workshop - November 21s t 2019 - Madrid
ALGORITHM DEVELOPED BY CIRCE
Va, Vb, Vc
Ia, Ib, Ic
PHASOR ESTIMATION
I1, I2, I0
WAVEFORM
SAM
PLI
NG
FR
EQ
UE
NC
Y
CRITERION 3: MODIFIED
SUPERIMPOSED QUANTITIES
ADAPTIVE WINDOW
CRITERIA 1 (I1 vs I2) AND
CRITERIA 2 (I2 vs I0)
CRITERIACOMBINATION
FAULTED PHASE SELECTION
DIRECTIONALITY
Multicriteria algorithm
Adaptive window
S1) Bus7A S1) Bus7B S1) Bus7C
t/s0,000 0,025 0,050 0,075 0,100 0,125 0,150 0,175 0,200
U/kV
-400
-200
0
I5275A I5275B I5275C
t/s0,000 0,025 0,050 0,075 0,100 0,125 0,150 0,175 0,200
I/kA
-101
DeltaA_ini DeltaB_ini DeltaC_ini
t/s0,000 0,025 0,050 0,075 0,100 0,125 0,150 0,175 0,200
-200
-100
0
Criteria 1 and 2 are considered valid during this “adaptive window”
VALID CRITERIA APPLICATION
𝑆𝑃 𝐴𝑆𝑃𝐴𝐵 𝑆𝑃𝐵
METHODOLOGY FOR THE IMPLEMENTATION
47
CIRCE – MIGRATE WP4 workshop - November 21s t 2019 - Madrid
INPUTS FROM P544 - Voltage and current waveforms
- Fast Fourier Transform - Positive, negative and zero
sequence currents
OUTPUTS TO P544 - Faulted phase selector loops
- Directionality - Adaptive window activation
PROGRAMMING THE COMPLETE ALGORITHM
IN C-LANGUAGE
CODING THE ALGORITHM IN P544 COMMERCIAL RELAY
FIRMWARE UPDATE SENT BACK TO
CIRCE
DESING, TESTING AND DEBUGGING
IN RTDS
DELIVERY TO
SCHNEIDER
DEBUG PROCESS
AND FINAL VERSION
CIRCE – MIGRATE WP4 workshop - November 21s t 2019 - Madrid
FIRMWARE UPDATE AND TESTING
Validation of the model with renewables based on MIGRATE tests
Validation with comercial
standard IEC: 60255-121 Functional tests for distance protection Application for a patent
to the European Patent Office of The Hague
VA VB VC
t/s-0,01 0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10
U/kV
-400
-200
0
200
IA IB IC
t/s-0,01 0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10
I/kA
-1,0
0,0
t/s-0,01 0,00 0,01 0,02 0,03 0,04 0,05 0,06 0,07 0,08 0,09 0,10
Fault ReverseFault Forward
Sel Window ValidPhase Select NPhase Select CPhase Select BPhase Select A
Zone2 CA ElementZone2 BC ElementZone2 AB ElementZone2 CN ElementZone2 BN ElementZone2 AN ElementZone1 CA ElementZone1 BC ElementZone1 AB ElementZone1 CN ElementZone1 BN ElementZone1 AN Element
Zone 2 N StartZone 2 C StartZone 2 B StartZone 2 A StartZone 1 N StartZone 1 C StartZone 1 B StartZone 1 A StartZone 2 N TripZone 2 C TripZone 2 B TripZone 2 A Trip
Zone 2 TripZone 1 N TripZone 1 C TripZone 1 B TripZone 1 A Trip
Zone 1 TripAny Trip
CIRCE – MIGRATE WP4 workshop - November 21s t 2019 - Madrid
FIRMWARE UPDATE AND TESTING
FINAL IMPLEMENTED FIRMWARE – Z5 VERSION
‒ Lines 5-7, 4-5 and 4-6 to be tested
‒ Current signature is no longer reliable for phase selection
52
1.- POWER NETWORK MODEL
NOV 2019
Two directions have been studied.
1. An improved algorithm based on current (and voltage)
2. An algorithm based on voltage only
‒ The Circé algorithm:
‒ Fault detection based on an adaptive window applied to:
‒ Criterion 1. Positive vs Negative sequence currents
‒ Criterion 2. Negative vs zero sequence currents
‒ Plus:
‒ Criterion 3: Adaptation of superimposed quantities
theory
‒ Directionality
‒ It has been integrated into the distance protection in
MiCOM P54x and successfully tested (on line 5-7, 4-6 and
4-5 TBC)
53
2.- NEW ALGORITHMS
NOV 2019
Two directions have been studied.
1. An improved algorithm based on current (and voltage)
2. An algorithm based on voltage only
‒ The Schneider Electric algorithm:
‒ The U< algorithm faulty phase selection has replaced the
current based algorithm for lines up to around 250 km.
‒ The thresholds depend only on the line characteristic.
‒ It has been integrated into the distance protection in
MiCOM P54x
‒ It has been successfully tested on line 5-7, 4-6 and 4-5
with different lengths
54
3.- NEW ALGORITHMS
NOV 2019
Conclusions:
The distance protection algorithms based on conventional
generator faulty current signature can be updated with new
Algorithms.
Either:
+ Improved algorithm based on current (and voltage) or
+ Undervoltage faulty phase selection algorithm based on
voltage only
Note: Weak infeed protection needs to be run in parallel of
the distance protection for weak infeed lines.
55
4.- DISTANCE PROTECTION
NOV 2019
The information, documentation and figures in this presentation are written
by the MIGRATE project consortium under EC grant agreement No 691800
and do not necessarily reflect the views of the European Commission.
The European Commission is not liable for any use that may be made of
the information contained herein.