Power Quality Technical Faq
Transcript of Power Quality Technical Faq
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 1/21
© ABB
22/07/2009 | Slide 1
Technical FAQ for Transformers Horace Gay, Quality School, 17 August 2010
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 2/21
© ABB
22/07/2009 | Slide 2
Topics
Differences among normal, ACS and multi-tapped trafo
What are the different types of transformers and their
uses?
How does the tap changer work to regulate the HV input to
achieve desired LV output? Purpose of having a neutral ground resistor
How to determine the vector group required for our TFs
What is differential protection?
What are the different types of CT and their applications?
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 3/21
© ABB
22/07/2009 | Slide 3
Types of Transformers
3 phase
distribution
Converter TF Multi Tapping
Uses Residential /
commercial /
industrial use
Variable speed drive
systems are used,
e.g. industrial pumps,
paper, steel
production
Network adaptability
Vector Dyn11 Dd0y11 / Dd0y1 YNyn0 / Dyn11
Operating
Frequency
50 or 60 50 or 60 50 and 60
No. of windings 2 3, axially stacked 3, Single LV, Dual HV
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 4/21
© ABB
22/07/2009 | Slide 4
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 5/21
© ABB
22/07/2009 | Slide 5
Tap Changer
How does the tap changer work to regulate the HV input to
achieve desired LV output?
Device that faciliates voltage regulation for the transformer
The regulation of a transformer is defined as the drop in
secondary voltage from no load to full rated loadexpressed as a percent of the full load voltage.
How does tap changing maintains voltage regulation?
To help match the incoming primary voltage to your
equipment needs which is connected to the secondary
side. In other words, it works by adding or subtractingthe number of transformer windings and hence the
turns and voltage ratio.
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 6/21
© ABB
22/07/2009 | Slide 6
Tap Changer - Voltage Regulation Example
A huge 3-phase heating load was connected to the
secondary of a step-down transformer (nominal 433V p-p)
resulting in a 5% voltage drop. Now the voltmeter
measures 411V p-p. How to regulate back to the nominal
voltage?
Given, the transformer (Dyn11) has a voltage regulationcapability on the Primary ± 2 X 2.5%.
411 X 83.6 / 1.73 = 432.98 V p-p
The answer is to tap up from position 3 to position 5.
Tap Vpri Vsec Turns
Ratio
1 23100 : 433 92.4
2 22500 : 433 90.2
3 22000 : 433 88.04 21450 : 433 85.8
5 20900 : 433 83.6
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 7/21
© ABB
22/07/2009 | Slide 7
Vector Groups
What is the purpose of vector groups?
A Vector group is the IEC method of categorizing theprimary and secondary winding configurations of threephase. Within a polyphase system power transformer itindicates the windings configurations and the differencein phase angle between them.
Note in ANSI, vector diagram is given to show thephase relationship between the primary and thesecondary.
Features & Type of connections.
First symbol: HV winding connection Second and subsequent symbols: Intermediate and LV
winding.
Lastly, phase displacement ‘clock number’
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 8/21
© ABB
22/07/2009 | Slide 8
Vector Groups
Popular Connection: Delta on
Primary and Star on Secondary
This will produce a 30° phase shift
between the two windings. As our
Delta Connection (5 taps) is A0B6,
B0C6 and C0A6, which would resultin a phase displacement of 30°
anticlockwise to the 11 o’clock
position.
A B
C
A0, B6
B0, C6C0, A6
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 9/21
© ABB
22/07/2009 | Slide 9
Vector Groups
Common connection for distribution transformers: Dyn11
Delta connected windings eliminate / suppresses third
harmonics from feeding back into the primary network.
Also provides better current balance for the primary source
should there be large amount of unbalanced loads. The neutral point provides a neutral earthing for the
purpose of safety.
Due to large installed base of distribution transformers with
such vector group and for parallel operations of
transformers
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 10/21
© ABB
22/07/2009 | Slide 10
Vector Groups
Other vector groups
Generator step-up – Ynyn0, Ynd1, or Ynd11
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 11/21
© ABB
22/07/2009 | Slide 11
Neutral Ground Resistor
NGR’s limit the fault current when one phase of the system
shorts to ground. In the event that a ground fault condition
exists, the NGR typically limits the current to approx 300A.
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 12/21
© ABB
22/07/2009 | Slide 12
A very reliable method of protecting generators,transformers, buses, andtransmission lines from theeffects of internal faults.
Detection of faults is performed
primarily by CTs. The activation upon detection is
performed by relays.
The sum of all currents enteringand leaving the bus must beequal to zero under normalconditions or if the fault is outsidethe protected zone.
If there is a fault on the bus, therewill be a net flow of current to thebus and differential relay willoperate.
Differential Protection
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 13/21
© ABB
22/07/2009 | Slide 13
Current TransformersGeneral
A current transformer is used to transform a primary
current quantity in terms of its magnitude and phase to a
secondary value such that in normal conditions the
secondary value is substantially proportional to the primary
value.
Protection and Metering CTs
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 14/21
© ABB
22/07/2009 | Slide 14
Current TransformersBasics
IEC 60044
Ratio, Burden & Class
E.g. 3300/1A, Burden 10VA, Class 3
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 15/21
© ABB
22/07/2009 | Slide 15
Current Transformer Basics
Burden = Impedance of pilot wire between CT &
Relay/Instruments + Impedance of the Relay/Instrument
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 16/21
© ABB
22/07/2009 | Slide 16
Current Transformer Basics
Class
Accuracy Class Application
0.1 Precision Testing, Calibration of other CTs
0.2 Precision Metering
0.5 General Tarrif Metering
1.0 Non Revenue measurement incl. power and energy
3.0 General industrial measurements
5.0 Approximate measurements
5P Protection
10P Protection, lesser accuracy
X Protection - Restricted earth fault relay
Measurement
Protection
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 17/21
© ABB
22/07/2009 | Slide 17
Types of CTsProtection CT
Application: Neutral Earth, Differential Protection
Typical ratings: 1600/5 15 VA Class 5P10
1600/5 is the current ratio.
15 VA is the VA output at rated secondary current, Class
5P indicates that this is a protection (P) CT with acomposite error of < 5% at rated accuracy limit primary
current and 10 is the rated accuracy limit factor (RALF) for
the CT, i.e. overcurrent = 10 X rated normal current
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 18/21
© ABB
22/07/2009 | Slide 18
Protection Current Transformers- Selection
Protective System CT Secondary VA Class
PE current for phase &
earth fault
1A
5A
2.5
7.5
10P20 or 5P20
10P20 or 5P20
Unrestricted earth fault1A
5A
2.5
7.5
10P20 or 5P20
Sensitive earth fault 1A or 5A Class PX use relay manufacturers formulae
Distance protection 1A or 5A Class PX use relay manufacturers formulae
Differential protection 1A or 5A Class PX use relay manufacturers formulae
High impedancedifferential
impedance
1A or 5A Class PX use relay manufacturers formulae
High speed feeder
protection1A or 5A Class PX use relay manufacturers formulae
Motor protection 1A or 5A 5 5P10
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 19/21
© ABB
22/07/2009 | Slide 19
Types of CTsMetering / Measuring CT
Application: WTI
Example of rating on 2MVA 22/0.433kV, Dyn11
3300/1A Class 3 Burden 10VA
2666A
1A
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 20/21
© ABB
22/07/2009 | Slide 20
References
Differential Protection, NGR – Practical Power System,
Hewiston, Brown and Balakrishnan
NGR – Resistance Grounding System Basics, Michael
Seal
CT – ABB Protection Application Handbook
CT – Rudolf CT selection guide
CT – ITL selection guide
Neutral Earth – J & P Transformer Book,
The Basics of Delta-Wye Transformers, ecmweb.com
7/29/2019 Power Quality Technical Faq
http://slidepdf.com/reader/full/power-quality-technical-faq 21/21
© ABB
22/07/2009 | Slide 21