Power Quality

45
Power Quality, Harmonics & Transients By P.K.Agarwal DGM, NRLDC

description

Stop Plluting Power System. What is power quality.

Transcript of Power Quality

Page 1: Power Quality

Power Quality, Harmonics & Transients

By

P.K.Agarwal

DGM, NRLDC

Page 2: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 2

Agenda

Peculiarity of power What is quality power. Power quality defects. Who is responsible?. Reasons of bad power quality. Cost of bad power quality. Typical problems. Solutions.

Page 3: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 3

Peculiarity of Electric Power

Electric power is the most essential raw material.

It is unusual commodity as it requires continuous flow and can not be conveniently stored.

It is a typical example of “Just in Time” philosophy – Components are delivered to the production line at the point and time of use by a trusted supplier with no requirement of “goods in” inspection.

Page 4: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 4

Peculiarity of Electric Power (contd..)

In reality electricity is very different from any other product. It is generated far from the point of

consumption. Is fed to the grid together with output of many

other generators. And arrives at the point of use via several

transformers and many kilometers of overhead or possibly underground cabling.

The network is owned and maintained by different owners

Page 5: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 5

Peculiarity of Electric Power (contd..)

Assuring the quality of power is not a easy task.

These is no way that sub-standard electricity can be withdrawn from the supply chain or rejected by the consumer.

From the consumer point of view situation is even more difficult.

Acceptable quality level as perceived by the supplier is different then desired by the consumer.

Page 6: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 6

Quality of power

The perfect power supply will be one which is

Always available

Always with voltage and frequency within tolerances

Has pure noise free sinusoidal wave shape.

Page 7: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 7

Defects in Power

The most obvious defect in power is complete interruption for few seconds to several hours.

Voltage dips or sag where voltage drops to lower value for a short duration.

Voltage swells or surges where voltage raises to higher value for a short duration.

Long power interruption are problems to all users.

Many process are very sensitive to even a short duration of interruption.

Page 8: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 8

Defects in Power (contd…/-)

Continuous process industry where short outage of power may loss synchronizing of machinery and may result in large quantity of semi processed product – Paper making where clean up process is long and expensive

Outage in multistage batch process may destroy the value of previous process – Semiconductor industry – Production of wafer requires few dozen process over several days.

Page 9: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 9

Categories of Defects in Power

Power quality defects i.e. deviations from perfection falls in five categories:-

Under Voltage or Over Voltage Dips (or sags) and surges (or swells). Blackouts. Harmonic distortion. Transients.

Page 10: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 10

Under voltage or Over Voltage

Over voltage or under voltages means, supply voltage is more or less then the allowable tolerances.

These are the causes of unbalance of supply and consumption of reactive energy in network.

If generation of reactive power is more then the consumption supply voltage will be high.

If generation of reactive power is less then the consumption, voltage will be less.

Page 11: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 11

Under voltage or Over Voltage (contd..)

Sustained over voltage or under voltage stress the equipment.

It weakens the insulation of system and equipments.

By proper reactive power management the supply voltage can be maintained within the tolerance.

As far as possible reactive power compensation should be done locally by consumer.

Page 12: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 12

Voltage Dips (or Sags) and Surges

Voltage dips or sags are caused by abrupt increases in loads such as short circuits or faults, motors starting, or electric heaters turning on, or they are caused by abrupt increases in source impedance, typically caused by a loose connection.

Page 13: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 13

Voltage Dips

Page 14: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 14

Page 15: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 15

Voltage Dips

Page 16: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 16

Relative Cost of Voltage Dips Elimination

Page 17: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 17

Voltage Dips (or Sags) and Surges (contd..)

Voltage swells are almost always caused by an abrupt reduction in load on a circuit with a poor or damaged voltage regulator, although they can also be caused by a damaged or loose neutral connection.

Page 18: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 18

Blackouts (Power Outage)

Power outage disrupts more business that any other factor.

Power outage or blackout means energy is not available for work.

Power outages may be caused by generator maintenance outage, failure of equipment of any critical element.

The quality of sustained supply of power is known as reliability.

Reliability indices is used to track the performance of a utility.

Page 19: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 19

Harmonic Distortions

Electricity generation is normally produced at constant frequency of 50Hz and generated voltage can be considered practically sinusoidal.

However, when a source of sinusoidal voltage is applied to a nonlinear device or load the resulting current is not perfectly sinusoidal.

In the presence of system impendence of this causes a non-sinusoidal voltage drop causing voltage distortion at the load terminals known as Harmonic Distortion.

Page 20: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 20

Harmonic Distortions (contd…)

Circuits containing thyristor is when supplied a sinusoidal voltage produces the distortion.

Page 21: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 21

Harmonic Distortions (contd…)

Harmonics generated by microwave oven

Page 22: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 22

Harmonic Distortions (contd…)

Harmonics generated by SMPS of computer

Page 23: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 23

Harmonic Distortions (contd…)

Harmonics generated by variable speed drive

Page 24: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 24

Transients

Transients disturbances are high frequency events with durations much less than one cycle of supply.

Causes are switching, lightening strikes on the network, switching of reactive loads on consumer sites.

Transients can have magnitudes of several thousands volts and so can cause serious damage to both the installation and the equipment connected to it.

A good earthing greatly reduces the transients.

Page 25: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 25

Transients (contd…/-)

Majority of power system transients are due to switching action.

Page 26: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 26

Transients (contd…/-)

Voltage across the capacitor while Switching a RC circuit

Page 27: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 27

Transients (contd…/-)

Transients are triggered from capacitor switching.

Capacitor transients normally causes the highest peak magnitudes. If the capacitor is switches when the system voltage near its peak, the capacitor pulls the system voltage down (as the current ruches to capacitor to charges it). The system rebounds, the voltage overshoots, and oscillates about the system fundamental frequency wave forms. This transients normally decays quickly.

Capacitor Switching Transients

Page 28: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 28

Switching Transients

A restrike can occur when switching a capacitor off: the switch opens at current zero, trapping the peak voltage on capacitor. As the system voltage decreases from the peak, the voltage across the switch rapidly increases. By the time system voltage reaches opposite peak, the voltage across the switch is double. Switch may restrikes.

Restrike of a capacitor Bank

Page 29: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 29

Who is Responsible for Quality

Suppliers argue – Critical users must bear the cost of ensuring quality of supply.

Rather than expecting the supply industry to provide very high reliability to every customer everywhere on the network.

Page 30: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 30

Who is Responsible for Quality (Cond..)

Some quality problems are the result of shared infrastructure.

Fault on a one part of network may cause dip that will affect some customers.

Page 31: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 31

Who is Responsible for Quality (Cond..)

Higher the level of the fault, the greater will be the number of customers affected.

Problem on one customer’s site may cause a transient that affects all the customers on the same subsystem.

Harmonics, arise within the customer’s won installation may propagate onto the network and affect other customers.

Page 32: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 32

Reasons

Such a guaranteed quality supply would require a very substantial investment for the benefits of relatively few customers (in count, not in consumption) and would be uneconomic.

It may not be technical feasible with in the current social and legal frame work.

Any customer is normally entitled to be connected to the supply.

Utility providers has the right to excavate roadways with the risk of cable damage.

Page 33: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 33

Reasons (contd…)

Weather conditions, such as high winds and rains, snow fall, frequently cause damages overhead lines.

Repair of lines under the same conditions, are difficult and time consuming.

It is therefore the consumers responsibility to take steps to ensure that the quality of power delivered to his process is good enough.

This quality level may well be higher than that delivered to the plant by the supplier.

Page 34: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 34

Cost of Power Quality defects

It is difficult to attribute a business loss to a particular event.

The electricity supply industry tends to value an interruption in terms of the cost of the electricity that was not supplied as a result.

Consumer values it in terms of the revenue lost as a consequence of the break in production.

Electricity is relatively cheap and the supply interruption is relatively short.

Page 35: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 35

How much good is good enough

This question is impossible to answer. While it is relatively simple to quantify the

behavior of a particular piece of equipment to voltage dips.

Determining the likely incidence of voltage dips at a particular on supply system is difficult.

It will change over time as new consumers are added and assets replaced.

Page 36: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 36

How much good is good enough

There are some international standards available that set limit of voltage variation and harmonic voltage distortion below which the equipment should function without error.

Similarly, there are standard limits for voltage deviation and harmonic voltage distortion of the supply.

Page 37: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 37

Typical Problems

A study was performed by European Copper Institute in 2001, covering 1400 sites in 8 countries.

Any given site in Europe has 5-20% probability of suffering from one or more of the problem listed. Computer Lockups Flickering screens Flickering lights. Overheating of transformers at moderate load.

Page 38: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 38

Typical Problems (contd…)

Induction Motors Heating of conductors due to skin effects. Correct functioning of process control

equipments Data network congestion Problem with power factor correction

equipment. Problem with specific (long) lines or when

switching heavy loads. Overloaded neutrals.

Page 39: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 39

Typical Problems (contd…)

Nuisance tripping of protective devices. Utility claims resulting from harmonics

affecting supply.

Page 40: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 40

Typical Problems (contd…)

Page 41: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 41

Solutions

The list of possible solutions for power quality problems is long and non-complete. Solutions listed below are adopted according to a the survey:- Surge Protection UPS Back-up generator True RMS measurement Transformer derating Motor derating

Page 42: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 42

Solutions (contd…)

Dedicated circuit Multiple cables for harmonic loads. Complete rewiring of the installation. Zoning of electrical loads. Meshed Earth. Passive filters Active conditioners TN-S wiring Natural Upsizing

Page 43: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 43

Typical Problems (contd…)

Computer Lockups:

Page 44: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 44

Solutions (contd…)

Page 45: Power Quality

26-Apr-2007 Power Quality - By P.K.Agarwal 45

Thank You