POST – BID ADDENDUM #1 TO PLANS AND SPECIFICATIONS...
Transcript of POST – BID ADDENDUM #1 TO PLANS AND SPECIFICATIONS...
04/15/15
POST – BID ADDENDUM #1 TO PLANS AND SPECIFICATIONS FOR New Music Building Ft. Sam Houston Independent School District 04/15/15 NOTE: If you have questions about this project, please contact Edward J. Rodriguez, Senior Project Manager [email protected] 210.223.9588 Wanira Magaloni, Designer [email protected] 210.223.9588 This Post – Bid Addendum is generally separated into sections for convenience; however, all contractors, subcontractors, material suppliers and other involved parties shall be responsible for reading the entire Addendum. Failure to list an item(s) in all affected sections of this Addendum does not relieve any party affected from performing per instructions, provided the information is set forth one time anywhere in the Addendum. This document shall become attached to and part of the Construction Documents for the aforementioned project. BID DATE and TIME: Coordinate with D.L. Bandy Constructors, Inc. DELIVER PROPOSALS TO: D.L. Bandy Constructors, Inc. Attention: David Bandy
P.O. Box 1529 San Marcos TX 78667 512-754-6661 512-754-6662 fax GENERAL ITEMS: Where materials and manufacturers are deleted, clarified or added to the project via this post-
bid addendum, refer to and coordinate with, the applicable specification sections. LIST OF ATTACHMENTS: Architectural Sheets MEP Sheets A121R M11R A201R M301R A211R M302R A401R E111R A501R E211R A611R E501 A631R MEP Narrative A711R A801R A821R
SPECIFICATIONS
ITEM SECTION DESCRIPTION 1 08 03 85-Steel Acoustical Door
Assemblies Security Metal Products Model # AW50C-STC50 is an acceptable manufacturer;
2 02 25 00-Allowances Delete “Allowance No. 4”, in the amount of $100,000 from the project
DRAWINGS
ITEM SHEET NUMBER DESCRIPTION 3 A121R • Windows at upper level of building are deleted. 4 A201R • Windows at upper level of building are deleted.
• Metal Building panels are revised as indicated in the “Panel Profile Schedule” Coordinate the requirements of Specification Section
5 A211R • Windows at upper level of building are deleted. • The layout of the acoustical wall panels are revised
6 A401R • The ceramic tile indicated at the wall elevations is revised. • Refer to Room Finish Schedule
7 A501R • The “Window Types” schedule is revised. 8 A611R • The reflected ceiling plan is revised.
• Delete Wood Panel ceiling. • Add 2x2 acoustical panel ceiling system. • Refer to Room Finish Schedule
9 A631R • The ceiling system is revised. • Delete Wood Panel ceiling. • Add 2x2 acoustical panel ceiling system. • Refer to Room Finish Schedule.
10 A711R • B1-First Level Floor Plan is revised to show VCT flooring • A6-Corridor Floor and Wall Pattern AXO is revised to indicate
ceramic tile 11 A801R • The Room Finish Schedule is revised.
• The Material Schedule is revised. 12 A821R • The layout of the acoustical wall panels is revised. 13 MEP • Refer to attached MEP narrative for additional information. 14 MEP • Refer to attached MEP narrative for additional information.
END OF POST – BID ADDENDUM # 1
G1A811
26.19.15
6.8 22.4
CT2
CT4
6' -
0"C
T39'
- 0"
CT2
2' -
0"C
T31'
- 0"
CT4
11' -
0"
CT3
6' -
0"C
T23'
- 0"
CT3
1' -
0"
CT4
2' -
0"C
T32'
- 0"
CT2
2' -
0"C
T31'
- 0"
CT3
5' -
0"C
T23'
- 0"
CT3
1' -
0"
CT4
10' -
0"
CT3
2' -
0"
CT2
2' -
0"C
T31'
- 0"
CT4
6' -
0"C
T39'
- 0"
CT2
2' -
0"C
T31'
- 0"
CT4
11' -
0"
CT3
6' -
0"C
T23'
- 0"
CT3
1' -
0"
CT4
6' -
0"C
T39'
- 0"
CT2
2' -
0"C
T31'
- 0"
CT2
2' - 0" 6' - 0" 2' - 0" 6' - 0" 2' - 0" 6' - 0" 2' - 0" 6' - 0" 2' - 0" 6' - 0" 2' - 0" 6' - 0" 2' - 0" 3' - 5"4' - 9"
P3 P3
10.4
26.1
9.6
105A 115A114113
TYP
8' -
4"
TYP
8"
TYP
8' -
0"
TYP
1' -
4"
TYP
8' -
0"
TYP
8' -
4"
TYP
1' -
0"
TYP
2' -
10"
CLCLCLCL
.60"H x 24"W
.84"H x 36"W
.60"H x 24"W
.48"H x 36"W
.36"H x 24"W .
48"H x 36"W
.36"H x 24"W.
48"H x 36"W
.60 1/16"H x 24"W
.84 1/16"H x 36"W
.60 1/16"H x 24"W
10.18
9.6
9' - 4"8' - 4"
FIN FL
11' - 4"
.24 1/8"H x 72"W
.84"H x 36"W
.84"H x 36"W
9' - 4"8' - 4"
FIN FL
.84"H x 36"W
.24"H x 24"W
10.18
MKBD
3' -
0"4'
- 0"
.60"H x 24"W
.84"H x 36"W
.60"H x 24"W
.48"H x 36"W
.48"H x 36"W
.36"H x 24"W
.36"H x 24"W
.48"H x 36"W
.60"H x 24"W
.84"H x 36"W
.60"H x 24"W
9.6
9' - 4"8' - 4"
FIN FL
11' - 4"
9' - 4"8' - 4"
FIN FL
.84"H x 36"W
.46"H x 24"W
.84"H x 36"W
.46"H x 48"W
.84"H x 36"W
.46"H x 24"W
.70 5/16"H x 36"W
10.18
9.6
P2
9.6
AWP248"H x 36"W
AWP236"H x 24"W
AWP248"H x 36"W
AWP236"H x 24"W
AWP248"H x 36"W
AWP260"H x 24"W
AWP284"H x 36"W
AWP260"H x 24"W
AWP260"H x 24"W
AWP284"H x 36"W
AWP260"H x 24"W
10.18
9' - 4"8' - 4"
FIN FL
11' - 4"
AWP236"H x 24"W
AWP236"H x 24"W
AWP284"H x 36"W
AWP260"H x 24"W
AWP284"H x 36"W
AWP224"H x 72"W
AWP284"H x 36"W
AWP223"H x 24"W
AWP284"H x 36"W
AWP284"H x 36"W
AWP224"H x 72"W
AWP284"H x 36"W
AWP224"H x 24"W
AWP284"H x 36"W
AWP284"H x 36"W
10.18
9.6
9' - 4"8' - 4"
FIN FL
MKBD
3' -
0"4'
- 0"
10' - 4" 3' - 0" 1' - 6" 3' - 0" 4' - 7" 16' - 0" 4' - 7" 3' - 0" 1' - 6" 3' - 0"
AWP248"H x 36"W
AWP236"H x 24"W
AWP248"H x 36"W
AWP236"H x 24"W
AWP248"H x 36"W
AWP260"H x 24"W
AWP284"H x 36"W
AWP260"H x 24"W
AWP260"H x 24"W
AWP284"H x 36"W
AWP260"H x 24"W
9' - 4"8' - 4"
FIN FL
11' - 4"
AWP184"H x 36"W
AWP160"H x 24"W
AWP184"H x 36"W
AWP128"H x 72"W
AWP184"H x 36"W
AWP146"H x 24"W
AWP184"H x 36"W
AWP146"H x 48"W
AWP184"H x 36"W
AWP146"H x 24"W
AWP184"H x 36"W
AWP128"H x 72"W
AWP173 5/16"H x 36"W
AWP160"H x 24"W
AWP184"H x 36"W
9' - 4"8' - 4"
FIN FL
10.18
9.6
P2
4' -
0"4'
- 0"
4' - 0" 6' - 3" 1' - 8 1/2" 3' - 0" 2' - 0" 3' - 0" 2' - 0" 3' - 0" 1' - 7"
4' -
0"5'
- 0"
4' -
0"4'
- 0"
4' - 0" 12' - 0"
8' MKBD1' - 7" 3' - 0" 2' - 0" 3' - 0" 2' - 0" 3' - 0" 1' - 8 1/2"
4' -
0"5'
- 0"
1. REFER TO SHEETS A501 FOR DOOR SCHEDULE.
2. REFER TO SHEET A003 FOR LINTEL SCHEDULES AND DOORAND WINDOW JAMB STUD FRAMING SCHEDULE.
3. ALL DOORS TO BE 1 3/4" THICK (UON)
4. ALL STL FRAMES TO HAVE A 2" FACE DIMENSION UON, W/ 5/8"STOP. 3/4" STOP REQUIRED FOR FIRE RATED FRAMES.
5. STEEL FRAME DEPTHS INDICATED IN THE DETAILS ARENOMINAL. PROVIDE STANDARD WIDTH FRAME WITH THROATOPENING APPROPRIATE TO WALL TYPE.
6. COORDINATE WITH MECH DOCUMENTS FOR DOORUNDERCUTS AND DOOR LOUVERS, IF ANY.
7. ALL LIGHTS IN DOORS TO HAVE SAFETY GLAZING (UON).
8. EXTERIOR DOORS TO HAVE TINTED GLAZING (UON) ANDINTERIOR DOORS TO HAVE CLEAR GLAZING.
9. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATING FRAMES.
10. PROVIDE WD BLKG IN GYP BD WALLS BEHIND DOORSSCHEDULED TO HAVE WALL MOUNTED DOOR STOPS. (REFERHARDWARE SCHEDULE SUBMITTAL).
11. REFER TO A004 FOR TYP WINDOW AND DOOR CONTROLJOINTS IN MASONRY WALLS. REFER TO A004 FOR TYP WINDOWAND DOOR CONTROL JOINTS IN STEEL STUD FRAMED WALLS.
12. FLOOR MATERIAL CHANGES BETWEEN ROOMS TO OCCURUNDER DOOR.
13. PROVIDE TREATED WOOD BLOCKING AT WINDOWSURROUND MEMBERS AS REQUIRED FOR PROPER ATTACHMENTWHERE ALUMINUM WINDOWS ARE TO BE INSTALLED IN EXISTINGMASONRY OPENINGS.
14. FIELD VERIFY DIMENSIONS OF EXISTING FRAMES TO REMAIN.
15. PROVIDE 1: LOUVER BLINDS AT WINDOWS TYPE A7, TYP.
GENERAL DOOR & WINDOW NOTES:
1. REFER TO SHEETS A821 FOR ACOUSTICAL PANEL LAYOUT.
2. ACOUSTICAL PANELS MOUNTED BELOW 8'-0" AFF SHALL BEIMPACT RESISTANT, TYP.
3. ACOUSTICAL PANELS SHALL NOT BE FIELD CUT FORINSTALLATION OF OTHER WALL LOCATED EQUIPMENT,UTILITIES, ETC. NOTIFY ARCHITECT OF CONFLICTING WALLMOUNTED ITEMS.
4. ALL CORRIDOR INSTALLED ACOUSTICAL PANELS SHALL BE2" PANELS, TYP.
5. ABOVE CEILING SOUND ABSORPTION SHALL BE 50% OFCEILING AREA AT CHORAL ROOM.
6. GYP BD PANELS AND DUCTWORK ABOVE CEILING SHALL BEPAINTED BLACK.
GENERAL ACOUSTICAL PANEL NOTES:
ACOUSTICAL PANEL LEGEND
AWP1 - 2" ACOUSTICAL WALL PANELREF SPECS
AWP2 - 4" ACOUSTICAL WALL PANELREF SPECS
AWP3 - HIGH IMPACT ACOUSTICALWALL PANELREF SPECS
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
5:19
PM
As indicatedER
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
INTERIOR ELEVATIONS
A821R214000210
11/07/2014
3/16" = 1'-0"F1CORR 100 - EAST ELEV.
3/16" = 1'-0"D1CORR 100 - WEST ELEV.
3/16" = 1'-0"A1CHORAL HALL - NORTH ELEV.
3/16" = 1'-0"A7CHORAL HALL - EAST ELEV.
3/16" = 1'-0"A5CHORAL HALL - SOUTH ELEV.
3/16" = 1'-0"A3CHORAL HALL - WEST ELEV.
3/16" = 1'-0"C1BAND HALL - NORTH ELEV.
3/16" = 1'-0"C3BAND HALL - EAST ELEV.
3/16" = 1'-0"C7BAND HALL - SOUTH ELEV.
3/16" = 1'-0"D7BAND HALL - WEST ELEV.
KEYNOTESKEY DESCRIPTION
6.8 WOOD VENEER MILLWORK9.6 SCHEDULED BASE9.15 PORCELAIN WALL TILE10.4 FIRE EXTINGUISHER CABINET10.18 ACOUSTICAL WALL PANEL22.4 ELECTRIC WATER COOLER. SEE PLUMBING DWGS26.1 LIGHT FIXTURE AS SCHEDULED. SEE ELEC. DWGS
3/16" = 1'-0"H7ENSEMBLE RM - SOUTH ELEVATION
3/16" = 1'-0"H9ENSEMBLE RM - WEST ELEVATION
3/16" = 1'-0"F7ENSEMBLE RM - NORTH ELEVATION
3/16" = 1'-0"F9ENSEMBLE RM - EAST ELEVATION
1 12/10/2014 ADD #1
FSH BAND HALL MATERIAL SCHEDULE
EXTE
RIO
R
SEALED CONCRETESC1
INTE
RIO
R
MIS
CEL
LAN
EOU
S
TP
MB
TB
TOILET PARTITIONS
MARKERBOARD
TACKBOARD/TACKWALL
PL2
PL1
PLASTIC LAMINATE
PLASTIC LAMINATE
FLO
OR
S
WD1
RB1
WOOD
RUBBER BASE
VCT1 VINYL COMPOSITE TILE
WAL
LS
GROUTGT2
CT1 CERAMIC TILE
AWP1
AWP2
ACOUSTICAL WALL PANEL
ACOUSTICAL WALL PANEL
P2
P3
MRK
PAINT
PAINT
PAINT
MATERIAL
-
CLARIDGE/GENON
SANTANA
CLARIDGE
SELECTED BY ARCH
-
SELECTED BY ARCH
FORMICA
FORMICA
5877-58 SEED WEFT , FINISH: MATTE
3697-58 BELUGA , FINISH: MATTE
ROPPE
BLOCK MOTTLE MAKORE #NP01164
4" COVE, 114 LUNAR DUST
MANNINGTON
2"
4"
MANUFACTURER
BENJAMIN MOORE
BENJAMIN MOORE
BENJAMIN MOORE
SANDY HOOK GRAY HC-108
SWEET DAPHNE 529
CLOUD WHITE 967
STYLE / COLOR REMARKS
NATURE'S PALETTE
GROUTGT1 LATICRETE
BASE
MIL
LWO
RK
CEI
LIN
G APC1 ACOUSTICAL PANEL CEILING ARMSTRONG ULTIMA NRC .60 , 2424" SQUARE LAY-IN
SL1 SOUNDLOK 6'-8" x 9'-1", GENERAL COLOR: OYSTER, DOOR& FLOOR RAIL: CHARCOAL GREY
SOUND-ISOLATION ROOM WENGER
POLISHED CONCRETEPC1 FIELD
POLISHED CONCRETEPC2
PB1 PORCELAIN TILE BASE DALTILE KEYSTONES BULLNOSE 2"X4", ARCHITECTURAL GRAY D109
VCT2
ESSENTIALS - MINERAL GRAY 175
VCT3
FOR HORIZONTAL APPLICATIONS
FOR VERTICAL APPLICATIONS
CT6 PORCELAIN MOSAIC TILE DALTILE KEYSTONES 2"X4", ARCHITECTURAL GRAY D109 ([email protected])
P1
POLISHED CONCRETEPC2
BK1 BRICK ACME FIELD COLOR
BK2 BRICK ACME BLACK ACCENT
MP1 METAL PANEL MBC1 SHADOWRIB, SMOOTH / SIGNATURE 300 METALIC
MP2 METAL PANEL MBCI FW-120, SMOOTH / GREEN, NO BEADS
MP3 ALUM PERFORATED PANEL CENTRIA SUNSTORM - 3/4" ECONOLAP
44 BRIGHT WHITE (AT CT1)
AWP3 HIGH IMPACT WALL PANEL HIGH IMPACT
APF2
APF3
ACOUSTIC PANEL FABRICS
ACOUSTIC PANEL FABRICS
ACOUSTIC PANEL FABRICS CINEMA DESIGN GROUP
CINEMA DESIGN GROUP
CINEMA DESIGN GROUP
SELECTED BY ARCHITECT
SELECTED BY ARCHITECT
SELECTED BY ARCHITECTAPF1
WS
DALTILE WALL TILE 4"X4" WHITE K101, SEMI-GLOSS
WOOD STAIN SHERWIN WILLIAMS SELECTED BY ARCH
GYPSUM BOARD CEILING -GWB1 -
APC2 ACOUSTICAL PANEL CEILING ARMSTRONG OPTIMA NRC .90 ., 2424" SQUARE LAY-IN
CT2 CERAMIC TILE DALTILE PARKWAY 12"X24", CREAM PK95 MATTE FINISH
CT3 CERAMIC TILE DALTILE
CT4 CERAMIC TILE DALTILE
CT5 CERAMIC TILE DALTILE WALL TILE 3"X6" MATTE ARCHITECTURAL GRAY 0709
PARKWAY 12"X24", CREAM PK95 GLOSS FINISH
PARKWAY 12"X24", GRAY PK98 MATTE FINISH
LATICRETE 90 LIGHT PEWTER
VINYL COMPOSITE TILE MANNINGTON ESSENTIALS - PEWTER 112
VINYL COMPOSITE TILE MANNINGTON ESSENTIALS - MACAW 145
NATURAL CONCRETE COLOR
FOREST GREEN
BLACK
ACCENT
ACCENT
1. MODEL NUMBERS/MFR'S ARE LISTED ON CASEWORK ELEVATIONS SO THAT A MINIMUM DESIGN BASIS MAY BEESTABLISHED. THE DIMENSIONS SHOWN (WXHXD) MAY DIFFER FROM THE SELECTED MFR'S STANDARD DIMENSIONSFOR THE LISTED MODEL NUMBERS.
2. PROVIDE SIDE, TOP, AND BOTTOM FILLER PIECES AS REQ'D TO COMPLETE CASEWORK INDICATED ON PLANS.3. ALL FLOOR MOUNTED FIXTURES ARE TO HAVE THE SAME FINISH FACE MATERIAL AS THE ROOM IN WHICH THEY ARE
LOCATED.4. BLIND CABINETS, AT CORNERS, ARE TO BE LEFT OR RIGHT HAND AS REQ'D PER PLAN.5. ALL CABINETS TO HAVE PLASTIC LAMINATE THROUGHOUT, INCLUDING ALL EXPOSED SURFACES INSIDE AND OUT.6. PROVIDE PLASTIC LAMINATE FINISHED END PANELS AT EXPOSED CABINET ENDS INCLUDING KNEESPACES (TYP).7. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATION AND INSTALLATION OF ANY FIXTURES.8. BOOKCASES AND SHELVES TO HAVE FRONT FACING SURFACE OF BACK PANEL TO WATCH FINISH OF REMAINDER OF
BOOKCASE.9. COUNTERTOPS TO HAVE PLASTIC LAMINATE SURFACE W/ 4" HIGH BACKSPLASH (TERRILL, TYPE No. 2) TYP, UON.10. PROVIDE KEYED LOCKS AT CABINET DOORS AND DRAWERS, WHERE INDICATED.11. KNEESPACE UNITS NOT RECEIVING SINKS SHALL RECEIVE GROMMETS CENTERED ON THE UNIT, 3" FROM THE BACK
EDGE OF THE KNEESPACE UNIT (UON).12. SHELVES SHALL BE ADJUSTABLE (UON). SHELVES OVER 36" IN LENGTH SHALL BE 1" THICK.13. PROVIDE 7/8" WORK TOPS WITH PLASTIC LAMINATE FINISH AT CASEWORK SHELVING UNITS UNDER 48".14. PROVIDE 4' -0" TALL TACKBOARDS, AND MARKERBOARDS (UON). BOARDS SHALL BE IN THE SAME FRAME WHEN
ADJACENT.15. MKBDS, AND TKBDS TO HAVE CONT TACKSTRIPS AND PEN TROUGHS (UON). TACKSTRIPS TO HAVE MAP HOOKS (UON).16. PROJECTION SCREENS: REF TECHNOLOGY DOC.17. PROVIDE BUILT-IN RECESSED COMBINATION LOCKS AT LOCKERS (UON).18. PROVIDE HORIZONTAL LOUVER BLINDS AT EXTERIOR WINDOWS, EXCEPT WINDOWS SHARING A FRAME WITH A DOOR
(UON).
NOTE: COORDINATE ALL ELECTRICAL ITEMS W/ CASEWORK,DISPLAY BOARDS, MIRRORS & ACOUSTICAL MATERIAL ASINDICATED ON THE PLANS, CASEWORK ELEVATIONS &INTERIOR ELEVATIONS (TYP).
1. FIRE EXTINGUISHERS (MEASURED FLOOR TO T.O. CABINET)
A. ALL GRADES AND ADULTS =56"
2. CHBD, MKBD & TKBD (MEASURED FLR. TO BOTT. OF BOARD)
A. GRADES 7-12 & ADULTS =36"
3. DOOR HARDWARE (MEASURED FLR. TO CENTER OF HARDWARE)
A. GRADES 7-12 & ADULTS
1. PUSH PLATES =45"
2. PULL HANDLES =42"
3. KNOBS =40 5/16" TO CL OF STRIKE
4. PANIC EXIT =40 5/16" TO CL OF STRIKE
4. THERMOSTATS & CCMS SENSORS (VERIFY HT. W/ ARCHITECT)
A. ALL OCCUPIED SPACES =48" MAX. TO TOP OF BOX
5. CONVENIENCE RECEPTACLES
A. GENERAL AREAS =15" MIN. TO BOTT. OF BOX
B. SPECIAL AREAS AS REQ'D, VERIFY W/ ARCH.
6. CLOCK OUTLETS
A. GENERAL AREAS =96"
B. SPECIAL AREAS AS REQ'D, VERIFY W/ ARCH.
7. LIGHT SWITCHES
A. ALL AREAS =48" MAX. TO T.O. BOX
8. FIRE ALARM PULL STATIONS
A. ALL AREAS =44" TO BOT. OF BACKBOX
9. FIRE ALARM STROBES/HORN STROBES
A. ALL AREAS =80" TO BOT OF BACKBOXOR 6" BELOW CEILING,WHICHEVER IS LOWER
10. SMOKE AND/OR HEAT DETECTORS
A. GENERAL AREAS =CEILING HEIGHT
B. SPECIAL AREAS AS REQ'D, VERIFY W/ ARCH.
11. INTERCOM SPEAKERS
A. GENERAL AREAS =96" OR FLUSH W/CLG.
B. SPECIAL AREAS AS REQ'D, VERIFY W/ ARCH.
12. TELEPHONE OUTLETS
A. ALL AREAS =15" MIN. TO BOTT. OF BOX
13. SOUND SYSTEM CALL SWITCHES
A. ALL AREAS =48" MAX. TO TOP OF BOX
13. DATA CABLE OUTLETS
A. ALL AREAS =15" MIN. TO BOTT. OF BOX
14. PROJECTION SCREENS
A. ALL AREAS COORD W/ARCHITECT
15. COUNTERTOPS (BASE CABINETS FLOOR TO C. TOP)
A. GRADES 7-12 & ADULTS =34"
16. SHELF & ROD (MEASURED FLR TO T.O. SHELF)
A. ALL AREAS =72" U.O.N.
17. ROBE HOOKS
A. ADULT =72" A.F.F.
B. ACCESSIBLE =48" A.F.F.
XX1
EXTERIOR
INTERIOR
ALUMINUM STOREFRONT, ALUMINUM WINDOWS
COPING, AND FLASHING NOTED ON THE DRAWINGS.
ALL UNDESIGNATED PRE-FINISHED METAL
PRE-FINISHED LOUVERS
GUTTERS, DOWNSPOUTS, BRACKETS & D.S. BOOTS
ALUMINUM HANDRAILS.
HOLLOW METAL DOORS, FRAMES AND STEEL HANDRAILS.
ALL EXPOSED COUNTER FLASHING, PIPE SUPPORTS AND OTHER MISC. FLASHING (U.O.N.).
ALL METAL BUILDING SIGNAGE.
CLEAR ANNOD. -
PM -
PM -
PM -
PM -
CLEAR ANNOD. -
P2 -
MATCH ADJ. WALL -
PM -
1. ALL EXTERIOR STEEL LINTELS SHALL BE PAINTED TO MATCH ADJACENT BRICK.
2. ALL ALUM. WINDOWS & DOOR FRAMES SHALL BE CLEAR ANODIZED; EXTERIOR GLAZING TO BE ACCORDINGTO MANUFACTURER PPG "AZURIA" INSULATION GLASS, TYP.
3. ALL EXTERIOR METAL SHALL BE FINISHED AS FOLLOWS:
1. MANUFACTURERS NAMES AND IDENTIFICATION NUMBERS ARE LISTED AS A MEANS OF ESTABLISHING A STANDARDOF TYPE, FUNCTION, COLOR, AND QUALITY. REFER TO PROJECT MANUAL FOR ADDITIONAL MANUFACTURERS &PROCEDURES.
2. THE CONTRACTOR SHALL SUBMIT TO THE ARCHITECT A SAMPLE OF ALL FINISH MATERIALS FOR APPROVALBEFORE MATERIALS ARE APPLIED ON THE JOB.
3. VERIFY ALL GRAPHICS WITH THE ARCHITECT BEFORE PAINTING. GRAPHICS MAY NEED TO BE ADJUSTEDAFTER ENLARGING TO REFLECT THE SAME COMPOSITION AS ON THE DRAWINGS.
4. IF REQUESTED THE ARCHITECT WILL PROVIDE 8 1/2" X 11" CLEAR ACETATE OR MYLAR OF DETAILEDMURAL GRAPHICS FOR PROJECTION ON WALL.
5. TERMINATE ALL ACCENT PAINTS & VINYL WALL COVERING ON INSIDE CORNERS ONLY UNLESS OTHERWISE INDICATED.
6. PAINT ALL INTERIOR & EXTERIOR EXPOSED PIPING. VERIFY COLOR W/ ARCHITECT.
7. PAINT ANY VENTS, GRILLES, PIPING, FEC, ETC... SAME COLOR AS ADJACENT WALL.
COLORS WILL BE MARKED AS SHOWN. NOTE ALL COLORS MAY NOTBE MARKED ON PLANS. MATERIALS NOT NOTED WILL BE COVEREDUNDER GENERAL NOTES OR WILL BE PICKED ON THE JOB BY THE ARCHITECT.
1. UNDESIGNATED PAINTED GYPSUM BOARD WALLS TO BE MARK "P1".
2. ALL INTERIOR HOLLOW METAL DOOR AND WINDOW FRAMES SHALL BE PAINTED TO MATCH MARK "P2"(U.O.N.). ALL VISION PANEL FRAMES IN INTERIOR DOORS TO MATCH MARK "P2".
3. ALL INTERIOR HOLLOW METAL DOORS SHALL BE PAINTED TO MATCH MARK "P2".
4. ALL INTERIOR WOOD DOORS & UNASSIGNED WOOD TRIM PIECES SHALL BE MARK "WS".
5. METAL HANDRAILS (INTERIOR) SHALL BE PAINTED P1.
6. ALL BOY'S AND GIRL'S TOILET PARTITIONS SHALL BE AS SPECIFIED.
7. ALL BASE CABINETS, WALL CABINETS, AND MISC. CASE WORK SHALL BE MARK "PL1".
8. ALL COUNTERTOPS SHALL BE MARK "PL2", (U.O.N.).
9. ALL METAL LOCKERS SHALL BE FINISHED TO MATCH MARK "P2".
10. ALL EXPOSED STRUCTURAL STEEL INCLUDING ROOF DECK, JOISTS, GIRDERS, BEAMS AND ANY MISC. STEELSHALL BE PAINTED; COORD.W/ ARCH. DUCTS, DIFFUSERS AND AIR HANDLING UNITS SHALL BE GALVANIZED METAL.
11. PATTERNS AND COLORS FOR AREAS SCHEDULED TO RECEIVE MCT SHALL BE AS REPRESENTED ONSHEETS A711. UNDESIGNATED MCT TO BE MARK "MCT1".
12. PATTERNS FOR AREAS SCHEDULED TO RECEIVE POLISHED CONCRETE SHALL BE AS REPRESENTED ON SHEETS A711.
13. LOW PROFILE TRANSITION STRIPS TO BE PLACED AT ANY FLOORING MATERIAL CHANGE.
14.. METAL LOW PROFILE TRANSITION STRIPS TO BE PLACED AT ANY FLOORING MATERIAL CHANGE ADJACENT TO CT.
15. CERAMIC WALL/FLOOR TILE GROUT SHALL BE GT1.
16. PORCELAIN PAVER TILE GROUT SHALL BE GT2.
BRAIL TO MATCH COPYWOMEN
8"
1/2" 7" 1/2"
1/16" WIDE X 1/16" REVEAL
INTERNATIONAL SYMBOLFOR MEN/WOMEN
1/2" R.(TYP)
2"3/
4"
8"
NOTES:
1. ALL COPY TO BE HELVETICA BOLD CONDENSED.2. ALL COPY TO BE RAISED 1/32" MIN.3. COPY STROKE WIDTH TO BE 1/4" WIDE MIN.4. SIZE OF COPY MAY BE ADJUSTED; HOWEVER LETTERS MAY NOT BE LESS THAN 1" HIGH.5. SIGN FACE & BACK SHALL BE AS SPECIFIED.
60"A
.F.F
.
BRAIL TO MATCH COPY101
VERIFY ROOM NAME &NUMBER TYP.
1/2" R.(TYP)
1"3/
4"
8"
NOTES:
1. ALL COPY TO BE HELVETICA BOLD CONDENSED.2. ALL COPY TO BE RAISED 1/32" MIN.3. COPY STROKE WIDTH TO BE 1/4" WIDE MIN.4. SIZE OF COPY MAY BE ADJUSTED; HOWEVER LETTERS MAY NOT BE LESS THAN 1" HIGH.5. SIGN FACE & BACK SHALL BE AS SPECIFIED.
60"A
.F.F
.
1/2" 7" 1/2"
A101
8"
Kitchen
5/8"5/
8" 5/8"3/
4"
Supervisor
ARCHITECTURAL ROOMNUMBERCOLOR TO MATCHBACKGROUND
PROVIDE TWOSLOTS
BRAIL TO MATCH COPY
CONFIRM CLIENTSTANDARD FOR ACRYLICSLOT HEIGHT AND TOTALNUMBER OF SLOTS
Fort Sam Houston Cole HS Band HallFort Sam Houston Independent School District
Board of TrusteesDeborah E. Seabron
Dr. Eustace Lewis
Colonel Randall Anderson
Jeanne Warren
Jane Crow
Dr. Gail Siller
President
Vice President
Secretary
Member
Member
Superintendent
Contractor name
HelveticaNeue LT 45LTRegular 28PT
HelveticaNeue LT 45LTRegular 22PT
HelveticaNeue LT 45LTRegular 22PT
Line Stroke1PT
Line Stroke1PT
HelveticaNeue LT65MED 50PT
HelveticaNeue LT 45LTRegular 28PT
HelveticaNeue LT 45LTRegular 140PT
7" 1'-1
"
8" 1'-2
"
7"
8"
1'-1"
1'-2"
**VERIFY ALL TEXT WITH OWNER AND ARCHITECT PRIOR TO FABRICATION**
ARCHITECTURE FIRMLOGO
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
4:40
PM
As indicatedChecker
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
ROOM FINISH AND COLORSCHEDULE
A801R214000210
11/07/2014
FSH BAND HALL ROOM FINISH SCHEDULE
WT ROOM NAME FLOOR BASEWALLS CEILING
REMARKSNORTH EAST SOUTH WEST MATERIAL FINISH
GROUND LEVEL100 CORRIDOR PC RB1 P1 P3 / CT P1 P1 - EXP101 ELEC SC RB1 P1 P1 P1 P1 - EXP102 CUST SC RB1 P1 P1 P1 P1 - EXP103 MEN TLT CT CT P1/CT P2 P1/CT P1/CT GWB1104 WOMEN TLT CT CT P1/CT P2 P1/CT P1/CT GWB1105 BAND HALL VCT RB1 P1 P1 P1 P2 APC2106 OFFICE VCT RB1 P1 P1 P1 P1 APC1108 B PRACTICE VCT SL1 SL1 SL1 SL1 SL1 SL1109 B PRACTICE VCT SL1 SL1 SL1 SL1 SL1 SL1110 LIBRARY/STORAGE VCT RB1 P1 P1 P1 P1 APC1111 UNIFORM STOR VCT RB1 P1 P1 P1 P1 APC1112 ENSEMBLE VCT RB1 P1 P1 P1 P1 APC2113 STAFF TLT CT CT P1 / CT P1 / CT P1 / CT P1 GWB1114 IDF SC RB1 P1 P1 P1 P1 - EXP115 CHORAL HALL VCT RB1 P1 P1 P1 P2 APC2116 HALL VCT RB1 P1 P1 P1 P1 APC1117 C PRACTICE VCT SL1 SL1 SL1 SL1 SL1 SL1118 C PRACTICE VCT SL1 SL1 SL1 SL1 SL1 SL1119 LIBRARY VCT RB1 P1 P1 P1 P1 APC1120 OFFICE VCT RB1 P1 P1 P1 P1 APC1121 STORAGE VCT RB1 P1 P1 P1 P1 APC1123 RISER SC - P1 P1 P1 P1 - EXPMEZZANINE200 MECH PLATFORM CONC - P1 P1 P1 P1 - EXP201 MECH PLATFORM CONC - P1 P1 P1 P1 - EXP
MOUNTING HEIGHT LEGEND
FURNISHING AND EQUIP GENERAL NOTESGENERAL COLOR SCHEDULE NOTES
TYPICAL HANDICAP SIGNTYPICAL INTERIOR SIGN
2 04/07/2015 V.E. ITEMS
16' M
KBD
16' M
KBD
16' MKBD
J
J
J
2
22
A821R
A1
A7
A5
A3
A821RD1 F1
A821R
C7
C1
D7 C3
CORRIDOR100
ELEC101
CUST102
RISER123
WOMEN TLT104
IDF114
STAFF TLT113
ENSEMBLE112
UNIFORM STOR111
BAND HALL105
OFFICE106LIBRARY/STORAGE
110
B PRACTICE108
B PRACTICE109
CHORAL HALL115
STORAGE121
OFFICE120
LIBRARY119
C PRACTICE118
C PRACTICE117
HALL116
A811
G8
G4
MS1
10.17 10.17
10.1710.17
10.4
12.3
C6A711R
PROVIDE MUSICALNOTATION TO HALFOF MARKER BOARD.
A501R6
VCT3
VCT2
VCT3
VCT2
VCT3
VCT2
VCT1
VCT1
VCT1
A821R
H7
H9
F7
F9
A501R
9
PC1
A201R A9
VCT2
VCT3
VCT3
VCT1
VCT1 VCT1
VCT1
38T
1T
3' - 0"
VCT1 VCT1
CASEWORK KEY
MODEL#WIDTHxHEIGHTxDEPTH
REMARKSADDITIONAL REMARKS
MODEL#WIDTHxHEIGHTxDEPTH
REMARKSADDITIONAL REMARKS
NOTE: ALL CASEWORK MODEL NUMBERS DESIGNATED ONSHEETS AI 1.01-1.04 AND AI 2.01 ARE FROM "TERRILLMANUFACTURING CO." GENERAL CATALOG (UON). REFER TOSPECIFICATIONS FOR ADDITIONAL ACCEPTANCEMANUFACTURERS. - REF F&E GENERAL NOTE #1 SHT AF 6.01
NOTE: REF SHT AF 6.01 FOR COLOR SCHED, NOTES, ANDFINISHES, TYP.
CONT COUNTERAND BACK SPLASH
F G H J
5
6
10
11
12
14
15
16
5' -
2 3/
4"2'
- 0"
6' -
0"2'
- 0"
6' -
0"2'
- 0"
6' -
0"2'
- 0"
6' -
0"2'
- 0"
6' -
0"2'
- 3
3/4"
5' -
8 1/
4"2'
- 0"
5' -
11 1
/4"
ALIGN
ALIGN
PC1
PC2
PC1
PC2
PC1
PC2
PC1
PC2
PC1
PC2
PC1
PC2
PC1
PC2
PC1
PC2
PC1
NOTE:ALIGN FLOOR PATTERNWITH WALL TILE PATTERN
A1A811
CT43' - 0"
CT6
CT43' - 0"
CT6
7
8
9
13
PC3
PC3
PC3
PC3
PC3
PC3
PC3
PC3
(14
LOC
KER
S)R
EF. D
9/A8
11(1
4 LO
CKE
RS)
REF
. D9/
A811
12x1
8x72
12x1
8x72
6"
STAINED POLISHEDCONCRETE
POLISHED CONCRETE
TILE PATTERN WRAPSAROUND OUT SIDE CORNERS
DISPLAY CASE (SHEET A811)
CERAMIC TILE ACCENT -MATTE (CT4)
CERAMIC TILE ACCENT -SEMIGLOSS (CT3)
CERAMIC TILE FIELD -MATTE (CT2)
FINISH KEY
PC1
PC2
PC3
CT6
CT4
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
4:27
PM
As indicatedChecker
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
FIRST LEVELCASEWORK/MILLWORK,FLOOR PATTERN,EQUIPMENT PLAN
A711R214000210
11/07/2014
1/8" = 1'-0"B1FIRST LEVEL FLOOR PLAN
KEYNOTESKEY DESCRIPTION
10.4 FIRE EXTINGUISHER CABINET10.17 SOUND-ISOLATION ROOM12.3 WALK-OFF MAT
1/4" = 1'-0"C6ENLARGED FLOOR PATTERN
A6CORRIDOR FLOOR AND WALL PATTERN AXO
2 04/07/2015 V.E. ITEMS
SUSPENDED ACOUSTICALPANEL CEILING ASSCHEDULED (GYP BDWHERE NOTED)
CONTINUOUS BENT PLATEBETWEEN JOISTS
STUD FRAMING AT16" O.C.
SUSPENDED APC ASSCHEDULED
5/8" GYP BD (PT)
CORNER BEAD
SHEET METAL CLIPANGLES - TYP ATCORNERS
CONT RUNNER TRACKANCHOR TO B.O. STRUCT
STUD BRACE AT 4'-0" OC(ANCHOR TO STRUCTURE)
8" M
IN2"
1' - 2"
STUD FRAMINGAT 16" OC
5/8" GYP BD (PT)
CORNER BEAD(TYP)
SHEET METALCLIP ANGLES -TYP AT CORNERS
GYP BD CEILINGAS SCHEDULED
2"8"
STUD FRAME DIAGONALBRACE AT 4'-0" OC MAX.(ANCHOR TO STRUCTURE)
CONT. RUNNER TRACKANCHOR TO B.O. STRUCT
F7 Sim
A301
F4 Sim
A301
119' - 0"
F7 Sim
A301
F4 Sim
A301
119' - 0"
SUSPENDED APCAS SCHEDULED
6" STUD FRAMINGAT 16" OC
5/8" GYP BD (PT)
CORNER BEAD
REF
RC
P
SOUND-ISOLATIONROOM ASSEMBLY
CONTINUOUS BENTPLATE BETWEENJOISTS
CONT RUNNER TRACKANCHOR TO B.O. STRUCT
STUD BRACE AT 4'-0" OC(ANCHOR TO STRUCTURE)
2' -
0"
SOUND-ISOLATIONROOM FILL PANEL
STUD FRAMINGAT 16" OC
5/8" GYP BD (PT)
CORNER BEAD(TYP)
SHEET METALCLIP ANGLES -TYP AT CORNERS
STUD FRAME DIAGONALBRACE AT 4'-0" OC MAX.(ANCHOR TO STRUCTURE)
CONT. RUNNER TRACKANCHOR TO B.O. STRUCT
REF PLAN
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
3:49
PM
As indicatedER
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
CEILING DETAILS
A631R214000210
11/07/2014
1" = 1'-0"F1CEILING DETAIL
1" = 1'-0"F5CEILING DETAIL
1/2" = 1'-0"E1CEILING - LAYOUT 1 SECTION
1/2" = 1'-0"B1CEILING - LAYOUT 2 SECTION
1" = 1'-0"F3CEILING DETAIL
DUCT, REF MECH DOCS
DUCT, REF MECH DOCS
2 04/07/2015 V.E. ITEMS
1" = 1'-0"F7CEILING DETAIL
D3A401R
LIBRARY/STORAGE110 OFFICE
106
B PRACTICE108
B PRACTICE109
BAND HALL105
ENSEMBLE112
UNIFORM STOR111
IDF114
STAFF TLT113
CHORAL HALL115
CORRIDOR100
WOMEN TLT104
RISER123
CUST102
ELEC101
C PRACTICE117
C PRACTICE118
HALL116
LIBRARY119
OFFICE120
STORAGE121
9' - 6"APC1
E1A631R
B1A631R
9' - 6"GWB1
9' - 6"APC1 9' - 6"
APC1
11' - 0"APC1
8' - 6"SL1
9' - 6"APC1
8' - 6"SL1
9' - 6"APC1
60' -
11
1/2"
8' - 6"SL1
8' - 6"SL1
26.2
EQEQ
EQEQ
8' - 6 1/8"
E1Sim
A631R
B1Sim
A631R
A1A303
A1A301
F3A631R
F3A631R
EQEQ
A1A211R
A1A211R
10' - 0"APC2
12' - 0"GWB1
10' - 6"GWB1
10' - 6"GWB1
12' - 0"GWB1
8' - 0"GWB1
8' - 0"GWB1 12' - 0"
GWB1
8' -
0"G
WB1
F5A631R
F5A631R
F5A631R
F1A631R
5/8" GYP BOARD PANELS(PAINTED BLACK) SET ABOVE WOOD GRILLECEILING, REF SECTIONS. GYP BOARD PANELSSHOWN HERE IN RCP FOR QUANTITY ANDDISTRIBUTED LOCATION PURPOSES ONLY, TYP.
F7A631R
F7A631R
MEN TLT103
9' - 0"APC1
19' - 0"APC2
19' - 0"APC2
RCP GENERAL NOTES
REFER TO FLOOR PLANS & INTERIOR ELEVATIONS FOR WALLMOUNTED FIXTURES & DEVICES, ETC.
REFER TO MECHANICAL, ELECTRICAL & TECHNOLOGYDRAWINGS FOR QUANTITY & TYPE OF CEILING MOUNTEDFIXTURES & DEVICES, ETC.
ALL CEILING MOUNTED FIXTURES, DEVICES, ETC ARE TO BECENTERED WITHIN THE CEILING TILE UNLESS NOTEDOTHERWISE.
UNDESIGNATED PAINTED GYPSUM BOARD SOFFITS & CEILINGSUNLESS NOTED OTHERWISE TO BE PAINTED 'PT-X'.
EXACT LOCATIONS FOR PROJECTOR MOUNTS & CEILINGMOUNTED PROJECTION SCREENS ARE TO BE FIELD VERIFIEDTO ACHIEVE THE OPTIMUM PERFORMANCE. COORDINATE WITHTECHNOLOGY TRADE CONTRACTOR.
FIELD VERIFY ALL BULKHEAD DIMENSIONS PRIOR TOCONSTRUCTION.
PROVIDE CONTROL JOINTS AT 30' - 0" OC MAXIMUM AT ALLGYPSUM BOARD BULKHEADS
1.
2.
3.
4.
5.
6.
7.
CEILING LEGEND
SUSPENDED GYP BD CEILINGSYSTEM OR GYP BD BULKHEADREF DWGS.
2'-0" x 2'-0" ACOUSTIC PANELCEILING SYSTEM. PER FINISHSCHEDULE
10'-8"
SUSPENDED WOODGRILLE CEILING SYSTEM .PER FINISH SCHEDULE
RECESSED 2' X 4' LIGHTFIXTURE REF MEP DOC
ELEVATION HEIGHT SYMBOLINDICATES HEIGHT OF CEILINGABOVE FINISH FLOOR ANDCEILING TYPE. SEE FINISHSCHEDULE FOR MOREINFORMATION.
RECESSED LIGHTING FIXTUREREF MEP DOC
PENDANT MTD LIGHT FIXTUREREF MEP DOC
NOTE: EXIT LIGHTING FIXTURES- REF MEP DOCS
SUPPLY AND RETURN AIRGRILLS. REF MEP DOCS
PROJECTOR SCREEN (NIC)REF. TECHNOLOGY, TYP.
EXPOSED STRUCTUREOR OPEN TO BELOW
APC1
CEILING BY PRACTICEROOM MANUF
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
3:42
PM
As indicatedER
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
FIRST LEVEL CEILINGPLAN
A611R214000210
11/07/2014
1/8" = 1'-0"A5FIRST FLOOR RCP
KEYNOTESKEY DESCRIPTION
26.2 12' CEILING MOUNTED EXTERIOR FAN. SEE ELEC. DWGS
2 04/07/2015 V.E. ITEMS
FULL GLASSINTERMEDIATE RAIL
FGIRF NL
NARROW LIGHTFLUSH HALF LIGHTWOOD DOOR
HL
*NOTE: AT DOORS MARKED AS ACOUSTICAL DOORS,PROVIDE SOUND SEALS FOR AN EQUIVALENT STC 50 DOOR
FULL GLASS
FG1' -
0"
VE
RIF
Y W
/ HD
WR
MTG
HT
1' -
0"
6"6"
8"
6" 10"
8"3'
- 4"
8"3'
- 4"
8"
6"6" 6" 6"
DOOR LOUVERAS SCHED
1' -
0"
REMOVABLE MULLIONAT EXTERIOR DOORS
7' -
2"
7' -
2"
REF SCHEDS1
2"
REF SCHEDS2
2"
REF
SC
HED
REF
SC
HED
2" 2" 2" 2"
FFE
REF
SC
HED
2' -
6"
REF SCHEDS5
2" 2" 2"
2"
2' - 0" 4' - 0"
4"
2"
GLAZING KEYDESCRIPTIONSYMBOL
CLEAR SAFETY GLASS
TINTED INSUL SAFETY GLASS(BLAST MITIGATION)
A7
4' - 0"
6' -
0"3'
- 0"
EXT
G1A521
C1A521
E1A521
A4B
2' -
7"5'
- 5"
4"
8' -
0"
EXT
G7A521
E7A521
A1A521
C7/G7
C10A521
INT
A3B
2' -
7"5'
- 3"
2' -
10"
10' -
8"
4"
EXT
E7A521
A1A521
F6A304
C7/G7A521
INTA2B
5' -
3"1'
- 6"EXT
9' -
4"
2' -
7"
E7A521
A1A521
A3A521
F6A304
C7/G7A521
A5B
4' -
2"5'
- 3"
2' -
7"
4"
7' -
10"
12' -
0"
EXT
E7A521
A1A521
A3A521
F6A304
A4A321
EXTA6
12' - 10"
3' -
0"9'
- 0"
G7A521
E7A521
C7A521
1. REFER TO SHEETS A501 FOR DOOR SCHEDULE.
2. REFER TO SHEET A003 FOR LINTEL SCHEDULES AND DOORAND WINDOW JAMB STUD FRAMING SCHEDULE.
3. ALL DOORS TO BE 1 3/4" THICK (UON)
4. ALL STL FRAMES TO HAVE A 2" FACE DIMENSION UON, W/ 5/8"STOP. 3/4" STOP REQUIRED FOR FIRE RATED FRAMES.
5. STEEL FRAME DEPTHS INDICATED IN THE DETAILS ARENOMINAL. PROVIDE STANDARD WIDTH FRAME WITH THROATOPENING APPROPRIATE TO WALL TYPE.
6. COORDINATE WITH MECH DOCUMENTS FOR DOORUNDERCUTS AND DOOR LOUVERS, IF ANY.
7. ALL LIGHTS IN DOORS TO HAVE SAFETY GLAZING (UON).
8. EXTERIOR DOORS TO HAVE TINTED GLAZING (UON) ANDINTERIOR DOORS TO HAVE CLEAR GLAZING.
9. FIELD VERIFY DIMENSIONS PRIOR TO FABRICATING FRAMES.
10. PROVIDE WD BLKG IN GYP BD WALLS BEHIND DOORSSCHEDULED TO HAVE WALL MOUNTED DOOR STOPS. (REFERHARDWARE SCHEDULE SUBMITTAL).
11. REFER TO A004 FOR TYP WINDOW AND DOOR CONTROLJOINTS IN MASONRY WALLS. REFER TO A004 FOR TYP WINDOWAND DOOR CONTROL JOINTS IN STEEL STUD FRAMED WALLS.
12. FLOOR MATERIAL CHANGES BETWEEN ROOMS TO OCCURUNDER DOOR.
13. PROVIDE TREATED WOOD BLOCKING AT WINDOWSURROUND MEMBERS AS REQUIRED FOR PROPER ATTACHMENTWHERE ALUMINUM WINDOWS ARE TO BE INSTALLED IN EXISTINGMASONRY OPENINGS.
14. FIELD VERIFY DIMENSIONS OF EXISTING FRAMES TO REMAIN.
15. PROVIDE 1: LOUVER BLINDS AT WINDOWS TYPE A7, TYP.
GENERAL DOOR & WINDOW NOTES:
1. PROVIDE DRIP EDGE AT HEAD OF DOOR
2. PROVIDE 2" WIDE ADA COMPLIANT MARBLE THRESHOLD WITHCHAMFERED EDGES AT ENTRY DOOR.
3. PROVIDE COMPLETE DOOR, FRAME & HARDWARE SOUNDSEAL (STC 50) ASSEMBLY PER MANUFACTURER - REF SPECS.
4. PROVIDE 1/2" UNDERCUT AT DOOR - REF MEP.
5. PROVIDE REMOVABLE MULLION.
6. DOOR AS PART OF PRACTICE ROOM SYSTEM - REF SPECS.
SPECIFIC DOOR SCHEDULEREMARKS
STEEL (HM) FRAME TYPE
FRAME TYPE LEGEND
ALUMINUM (STOREFRONT) FRAME TYPE
S1
A1
A101A
WALL/FIXTURE WHERE OCCURS
TYP (UON) OR CENTERDOOR IN WALL (SEE PLAN)
SOUNDSEAL
MULTIPLE DOORDESIGNATION
CLR MIN (AT PUSHSIDE OF DOORWITH CLOSER)
AREA DESIGNATIONSEE KEY PLAN
DOOR/ROOM NO
DOOR MARK KEY
1' - 0"
1' - 6"
4"
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
3:28
PM
As indicatedER
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
DOOR SCHEDULE, INFO,AND FRAME TYPES
A501R214000210
11/07/2014
DOOR SCHEDULEDOOR FRAME DETAILS
FIRE RATING REMARKSNUMBER WIDTH HEIGHT TYPE MATERIAL GLAZING TYPE MATERIAL HEAD JAMB SILL
GROUND LEVEL100A 6' - 2" 7' - 10" FGIR ALUM SFTY A5B ALUM G1/A521 E1/A521 NA 5100B 3' - 6" 7' - 10" FGIR ALUM SFTY A2B ALUM G1/A521 E1/A521 NA100C 3' - 6" 7' - 10" FGIR ALUM SFTY A2B ALUM G1/A521 E1/A521 NA101 3' - 0" 7' - 0" F WD NA S1 STL A7/A521 A10/A521 - NA102 3' - 0" 7' - 0" F WD NA S1 STL A7/A521 A10/A521 - NA103 3' - 0" 7' - 0" F WD NA S1 STL A7/A521 A10/A521 - NA 2104 3' - 0" 7' - 0" F WD NA S1 STL A7/A521 A10/A521 - NA 2105A 4' - 0" 7' - 0" NL WD SFTY S1 STL G5/A521 E5//A521 - NA 3105B 4' - 0" 7' - 4" F STL NA S1 STL G3/A521 E3/A521 NA 1106 4' - 0" 7' - 0" NA A7/A521 A10/A521 - NA108 3' - 0" 7' - 0" MANUF MANUF MANUF MANUF MANUF MANUF MANUF NA 6109 3' - 0" 7' - 0" MANUF MANUF MANUF MANUF MANUF MANUF MANUF NA 6110 4' - 0" 7' - 0" NA A7/A521 A10/A521 - NA111 3' - 0" 7' - 0" F WD NA S1 STL G5/A521 E5/A521 NA112A 4' - 0" 7' - 0" HL WD SFTY S1 STL G5/A521 E5/A521 NA 3112B 3' - 6" 7' - 0" HL WD SFTY S1 STL G5/A521 E5/A521 NA 3113 3' - 0" 7' - 0" F WD NA S1 STL G5/A521 E5//A521 - NA 2114 3' - 0" 7' - 0" F WD NA S1 STL G5/A521 E5//A521 - NA115A 3' - 6" 7' - 0" NL WD SFTY S1 STL G5/A521 E5//A521 - NA 3115B 4' - 0" 7' - 4" F STL NA S1 STL G3/A521 E3/A521 NA 1117 3' - 0" 7' - 0" MANUF MANUF MANUF MANUF MANUF MANUF MANUF NA 6118 3' - 0" 7' - 0" MANUF MANUF MANUF MANUF MANUF MANUF MANUF NA 6119 4' - 0" 7' - 0" NA A7/A521 A10/A521 - NA120 4' - 0" 7' - 0" NA A7/A521 A10/A521 - NA121 4' - 0" 7' - 0" F WD NA S1 STL G5/A521 E5//A521 - NA123 4' - 0" 7' - 4" F STL NA S1 STL G3/A521 E3/A521 NA
DOOR FRAME TYPESDOOR TYPES
NOTE: WINDOW TYPES A2A, A3A & A8 SHALL BE HAVE BOTH EXTERIOR & INTERIOR APPLICATIONS AS FOLLOWS;- INTERIOR SHALL HAVE CLEAR SAFETY GLASS- EXTERIOR SHALL HAVE TINTED INSULATED SAFETY GLASS - BLAST MITIGATION
- ALL INTERIOR STOREFRONT FRAME TYPES SHALL BE: KAWNEER 451 WITH SINGLE GLAZING, BASIS OF DESIGN (TYP).- ALL EXTERIOR STOREFRONT FRAME TYPES SHALL BE: KAWNEER IR 501 BLAST MITIGATION, BASIS OF DESIGN(TYP), EXCEPT FRAMES A2B & A5B SHALL BE KAWNEER 1600 BLAST RESISTANT. ALL BLAST MITIGATION SYSTEM SHALL BE DOUBLE GLAZING SYSTEM WITH 1/2" AIR SPACE, BASIS OF DESIGN.
WINDOW TYPES
HLHL
HL
HL WD
WD
WDWD
S5
S5
S5S5
STL
STL
STLSTL
2 04/07/2015 V.E. ITEMS
F6/A304
G5/A521 E5 /A521
G5/A521 E5 /A521
A3 /A521
A3 /A521
IV2
WOMEN TLT104
7 1/
4"
5' -
0"EQ
.18
' - 0
"EQ
.5'
- 0"
1' -
1 7/
8"
5' - 0" 3' - 0" 2' - 6"103
104
A401R
B6
B5
B3
A401RA5
A3
A6
3' -
0"3'
- 3"
3' -
1"3'
- 6"
RISER123
CUST102
ELEC101
123
3' -
6"3'
- 1
1/2"
3' -
2 1/
2"3'
- 0"
101
102
B8
A8
1' -
4"
6"3'
- 0"
6"
3' - 4"
G
G
J
J
5
16
1' -
7"3'
- 0"
1' -
5"4'
- 5
3/4" 7
1/4"
A401RA2
A1
9
13
PONY WALL 7'-0"
MEN TLT103
5' - 0" 3' - 0 3/8" 2' - 5 3/4" 1' - 1 7/8"
6 1/
2"
1' - 4 3/4"
1' - 0 1/2"
5' - 3 1/4" 6' - 7"
1' -
4"
3' - 9 1/2"
A6
A6
2' -
3 1/
2"
1' - 2 3/8"
1' - 2 3/8"
2' - 9 1/8"1' - 0 3/8"
2' - 4 1/8" 5 1/4" 11' - 6"
2' -
10 7
/8"
3' -
1"6'
- 4"
5' -
1"6'
- 6
1/8"
5' -
1"
26B
24 24A
24A
24B
24
24B
24
24
24B26B
24A
24A
2626
26
26
24A
26
26
24A
26
24
26
26B
26B
26B
26
CT5
6' -
0"
EQ 12' - 0" EQ
CT4
3' -
0"C
T53'
- 0"
PB1C
T56'
- 0"
9.15
P2
PB1
WOMEN TLT104
CUST102
RISER123
ELEC101
G
G
H
H
J
J
5
16
8' - 0"GWB1
8' - 0"GWB1
12' - 0"GWB1
12' - 0"GWB1
8' - 0"GWB1
EQEQ
EQEQ
9
13
F5A631R
F5A631R
F5A631R
MEN TLT103
10' - 6"
10' - 6"
F7A631R
F7A631R
CT5
6' -
0"
9.15
EQ 12' - 0" EQ
CT5
3' -
0"C
T43'
- 0"
PB1
CT5
6' -
0"
PO
NY
WA
LL7'
- 0"9.15
P2
PB1
STAFF TLT113
A401RE8
E7
D7
D8
F
10
1' -
6"1'
- 8"
8
9
1' -
1 7/
8"2
7/8"CT4
3' - 0" CT6
(14 LOCKERS)
A6
9.15
P2
PB1
(14 LOCKERS)
A6
PO
NY
WA
LL7'
- 0"
9.15
PB1C
T56'
- 0"
CT4
3' -
0"C
T53'
- 0"
1' - 10 7/8" 6' - 0" 0"
6"
CT5
6' -
0"
4"
PB1
10.19
22.3
(CT1
)4'
- 0"
5.4
2' - 6"
22.3
10.19
5.4
(CT1
)4'
- 0"
4' - 6"
CEILING LEGEND
SUSPENDED GYP BD CEILINGSYSTEM OR GYP BD BULKHEADREF DWGS.
2'-0" x 4'-0" ACOUSTIC PANELCEILING SYSTEM. PER FINISHSCHEDULE
10'-8"
SUSPENDED WOODGRILLE CEILING SYSTEM .PER FINISH SCHEDULE
RECESSED 2' X 4' LIGHTFIXTURE REF MEP DOC
ELEVATION HEIGHT SYMBOLINDICATES HEIGHT OF CEILINGABOVE FINISH FLOOR ANDCEILING TYPE. SEE FINISHSCHEDULE FOR MOREINFORMATION.
RECESSED LIGHTING FIXTUREREF MEP DOC
PENDANT MTD LIGHT FIXTUREREF MEP DOC
NOTE: EXIT LIGHTING FIXTURES- REF MEP DOCS
SUPPLY AND RETURN AIRGRILLS. REF MEP DOCS
EXPOSED STRUCTUREOR OPEN TO BELOW
APC1
WALL MOUNTEDWATER CLOSET
WALL MOUNTED ACCWATER CLOSET
LAVATORY
ACC LAVATORY
ACC URINAL
MOP RACK
MOP BASIN
TOILET TISSUEDISPENSER (TTD)
SANITARY NAPKINDISPOSAL UNIT (SNDU)
FRAMED MIRROR(18"X36" UON) AT HS
ELECTRIC WATERCOOLER (EWC)
ACC ELECTRICWATER COOLER
TOILET ROOM LEGEND
TYPICAL WALL LAVATORY
WALL MOUNTEDLAVATORYFRAMED TEMPEREDGLASS MIRROR.REFER MOUNTINGHEIGHTS FORACCESSIBLE MIRRORELEVATION HT
TOILET PLANGENERAL NOTES1. REFER TO SHEETS A009 FOR WALL TYPES, UON.
2. ALL TOILET ROOM WALLS TO DECK, UON.
3. PROVIDE ACOUSTICAL BATT INSULATION IN STUDCONSTRUCTION WALLS SURROUNDING TOILETROOMS.
4. PROVIDE WALL MOUNTED DOOR STOPS INRESTROOMS.
5. REFER TO SHEET A801 FOR INTERIOR FINISHES.
6. REFER TO 'TOILET ROOM LEGEND' ON A401 FORFIXTURES AND ACCESSORY INFO, TYP.
7. PROVIDE THE SAME FIXTURES AND ACCESSORIESAT ALL SINGLE ACCESSIBLE TOILET ROOMS WHICHARE TO BE PROVIDED AT TYPICAL FIXTURES, ASINDICATED IN 'TOILET ROOM LEGEND.' PROVIDEACCESSORIES FOR ACCESSIBLE WATER CLOSETS ASINDICATED FOR A 'TYPICAL ACCESSIBLE STALL,'PROVIDE ACCESSORIES FOR ACCESSIBLELAVATORIES AS INDICATED FOR A 'TYPICALACCESSIBLE WALL LAVATORY.
8. REFER TO 'FIXTURE MOUNTING HEIGHT SCHEDULE'ON A401 FOR MOUNTING HEIGHT INFO, TYP ALLACCESSIBLE FIXTURES AND EQUIPMENT ARE TO BEMOUNTED AT SPECIFIED SCHOOL HEIGHTS, UON BY'ACF' (ADULT ACC FIXTURE), TYP.
9. COORDINATE INSTALLATION OF REQD BLOCKINGAND STABILIZING FOR FIXTURES.
10. THE STRUCTURAL STRENGTH OF GRAB BARS,SHOWER SEATS, FASTENERS AND MOUNTINGDEVICES AT ACCESSIBLE WATER CLOSETS ANDSHOWERS SHALL COMPLY WITH ADA AND TASREQUIREMENTS.
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
3:17
PM
As indicatedChecker
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
ENLARGED TOILETROOMS
A401R214000210
11/07/2014
1/4" = 1'-0"D5ENLARGED TOILET ROOMS PLAN
1/4" = 1'-0"B3WOMEN TLT - ELEVATION
1/4" = 1'-0"B5WOMEN TLT - ELEVATION
1/4" = 1'-0"B6WOMEN TLT - ELEVATION
1/4" = 1'-0"D3ENLARGED TOILET ROOMS RCP
1/4" = 1'-0"A3MEN TLT - ELEVATION
1/4" = 1'-0"A5MEN TLT - ELEVATION
1/4" = 1'-0"A6MEN TLT - ELEVATION
1/4" = 1'-0"G7STAFF TOILET ROOM PLAN
1/4" = 1'-0"B8WOMEN TLT - ELEVATION
1/4" = 1'-0"A8MEN TLT - ELEVATION
1/4" = 1'-0"E7STAFF TLT - ELEVATION 1/4" = 1'-0"E8
STAFF TLT - ELEVATION
1/4" = 1'-0"D7STAFF TLT - ELEVATION
1/4" = 1'-0"D8STAFF TLT - ELEVATION
1/4" = 1'-0"A1CUST - ELEVATION
1/4" = 1'-0"A2CUST - ELEVATION
KEYNOTESKEY DESCRIPTION
5.4 PAINTED STEEL SHIP'S LADDER9.1510.19 MOP & BROOM HOLDER RACK22.3 PLUMBING FIXTURE. SEE PLUMBING DWGS
2 04/07/2015 V.E. ITEMS
DOUBLE TIER LOCKER WITH BENCH
NOTE: ALL TLTS FIXTURES TO BE ADULT HEIGHT
TYPICAL TLT TILE LAYOUT
CT5CT5
CT4
CT4 CT6
GROUND LEVEL100' - 0"
LIBRARY/STORAGE110 BAND HALL
105
CHORAL HALL115
13101921 713
MECH PLATFORM201
ENSEMBLE112
LIBRARY119
105B
CRAWL SPACE
ACOUSTICAL PANEL
LIGHT FIXTURE, REFELECTRICAL DOCS
115B
GROUND LEVEL100' - 0"
BAND HALL105
CORRIDOR100
MECH PLATFORM200
B C F G J K
111 112A
MEN TLT103
CRAWL SPACE
8' -
8"
GROUND LEVEL100' - 0"
13101922 13
A7
105A113 114 115A 120
A7A5BCORRIDOR
100 OFFICE120
10.4
CRAWL SPACE
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
2:51
PM
1/8" = 1'-0"WM
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
BUILDING SECTIONS
A211R214000210
11/07/2014
1/8" = 1'-0"F1BUILDING SECTION
1/8" = 1'-0"D1BUILDING SECTION
1/8" = 1'-0"A1BUILDING SECTION
2 04/07/2015 V.E. ITEMS
EXTERIOR ENVELOPE NOTES1 FIRST FLOOR REFERENCE ELEVATION 100' - 0" = 674.30' (674.30'' DATUM, REFER TO CIVIL)
2 MAINTAIN WATERPROOFING FLUID CONTINUITY THROUGHOUT EXTERIOR ENVELOPE. SEAL ALL SEAMS, JOINTS, PENETRATIONS &
TERMINATIONS TO OTHER SUBSTRATES.
3 CURTAIN WALL / STOREFRONT SYSTEMS TO HAVE CLOSED HEAD, JAMB & SILL PROFILES.
4 FILL ALL VOIDS AROUND GLAZING SYSTEM PERIMETER WITH MINERAL WOOL INSULATION.
5 EXTERIOR STEEL (I. E. RELIEF ANGLES, PLATES, LINTELS, ETC), ARE TO BE GALVANIZED, UNLESS NOTED OTHERWISE.
6 EJ - INDICATES MASONRY EXPANSION JOINT LOCATIONS. FOR LOCATIONS NOT SHOWN, PROVIDE JOINTS 3' - 4" FROM OUTSIDE CORNERS AND SPACED MAXIMUM 20' - 0" OC.
7 CONTINUE MASONRY ACCENT SCHEME AT ALL EXTERIOR WALLS, INCLUDING AT ENTRIES, COLUMNS AND WALLS NOT SHOWN ON ELEVATIONS, UNLESS NOTED OTHERWISE.
EXTERIOR TINTED INSULATING & BLAST RESISTANT GLASS UNIT
ALL EXTERIOR GLAZING FOR THE FSHISD BAND HALL BUILDINGSHALL BE BLAST MITIGATION (BLAST RESISTANT) PER FT. SAMHOUSTON DESIGN STANDARDS.
GLASS THICKNESS DESIGNATION INDICATED ARE MINIMUMS &ARE FOR DETAILING ONLY. GLAZING TRADE CONTRACTOR TODETERMINE SAFETY GLAZING REQUIREMENTS & TO CONFIRMGLASS THICKNESS BY ANALYZING PROJECT LOADS, IN-SERVICECONDITIONS & GLASS LOCATIONS. PROVIDE GLASS LITES /UNITS IN THE THICKNESS DESIGNATIONS INDICATED ABOVE FORVARIOUS SIZE OPENINGS, BUT NOT LESS THAN THICKNESS & INSTRENGTH (ANNEALED, TEMPERED OR HEAT TREATED)REQUIRED TO MEET OR EXCEED CODE & PERFORMANCECRITERIA, RE: SPECIFICATION SECTION 08 8000.
ALL EXTERIOR GLAZING IS TINTED, INSULATING & BLASTRESISTANT, UNLESS OTHERWISE NOTED.
ALL EXTERIOR DOOR GLAZING IS TINTED, INSULATING & BLASTRESISTANT, UNLESS OTHERWISE NOTED.
EXTERIOR GLASS GENERAL NOTES
1.
2.
3.
4.
GROUND LEVEL100' - 0"
GROUND LEVEL100' - 0"
ABHJK
B.O
. FAN
(TYP
)21
' - 0
"
A7 A7
PRE-FINISHED MTL COPING- REF ROOFING DETAILS
PRE-FINISHED MTL FASCIA(TYP)
PRE-FINISHED ALUMINUMPERFORATED SCREEN
GALVANIZED STL FRAME -REF STRUCTURAL DWGS
PRE-FINISHED ALUMINUMPLATE PANELS
EXTERIOR CEILINGFAN BEYOND
MASONRY CJ(TYP)BK1/BK2
MP1PRE-FINISHED MTL GUTTER& DOWNSPOUTS
CONTINUOUS PRE-FINISHEDMTL FASCIA(TYP)
NOTE: ROOF PENETRATIONS -REF MEP & ROOFING DTLS(TYP)
CJ
EXTERIOR BENCHES BEYOND- REF SITE PLANS
CJ CJCJ
BK1/BK2
MP2
CJ
STEEL LADDER,REF ROOF PLAN
GROUND LEVEL100' - 0"
GROUND LEVEL100' - 0"
A B F G J K
B.O
. FAN
(TYP
)21
' - 0
"
A7 A7
A5B
100AMP2
PRE-FINISHED MTL COPING- REF ROOFING DETAILS
PRE-FINISHED MTLFASCIA(TYP)
PRE-FINISHED ALUMINUMPERFORATED SCREEN
GALVANIZED STL FRAME -REF STRUCTURAL DWGS
PRE-FINISHED ALUMINUMPLATE PANELS
EXTERIOR CEILINGFAN BEYOND
MASONRY CJ(TYP)BK1/BK2MP1BK1/BK2BK1/BK2
BK1/BK2
(TYP @ BENCHES)
MP1
PRE-FINISHED MTL GUTTER& DOWNSPOUTS
CONTINUOUS PRE-FINISHEDMTL FASCIA(TYP)
NOTE: ROOF PENETRATIONS -REF MEP & ROOFING DTLS(TYP)
CJ CJ CJ CJ
EXTERIOR BENCHES -REF SITE PLANS
GROUND LEVEL100' - 0"
GROUND LEVEL100' - 0"
135611151618192122
A7
A4BA3B
A2B
A6 A6
A4BA3B A2B A7
123100B 100C
CJCJ CJCJ
NOTE: EXTERIOR BENCHES IN FOREGROUNDNOT SHOWN - REF FLOOR PLANS
BK1/BK2
PRE-FINISHED MTL COPING- REF ROOFING DETAILS
PRE-FINISHED MTLFASCIA(TYP)
PRE-FINISHED ALUMINUMPERFORATED SCREEN
GALVANIZED STL FRAME -REF STRUCTURAL DWGS
PRE-FINISHED ALUMINUMPLATE PANELS
EXTERIOR CEILINGFAN BEYOND
PRE-FINISHED ALUMINUMPLATE PANELS
GALVANIZED STL FRAME -REF STRUCTURAL DWGS
EXTERIOR CEILING FANBEYOND
GALVANIZED STL FRAME -REF STRUCTURAL DWGSPRE-FINISHED
MTL FASCIA(TYP)
PRE-FINISHED ALUMINUMPERFORATED SCREEN
EXTERIOR BENCH ANDPLANTERS BEYOND -REF SITE PLAN
GALVANIZED STL FRAME -REF STRUCTURAL DWGS
STOREFRONT DOOR &WINDOW FRAME
PRE-FINISHED ALUMINUMPLATE PANELS
MASONRY CJ(TYP)MP1MP1
BK1/BK2
MP2
GROUND LEVEL100' - 0"
GROUND LEVEL100' - 0"
1 3 6 14 19 21 229
105B115B
CJ
CJ CJ CJ
CJ
BK1/BK2
PRE-FINISHED MTL COPING- REF ROOFING DETAILS
PRE-FINISHED MTL FASCIA(TYP)
PRE-FINISHED ALUMINUMPERFORATED SCREEN BEYOND
GALVANIZED STL FRAME BEYOND- REF STRUCTURAL DWGS
PRE-FINISHED ALUMINUMPLATE PANELS
EXTERIOR CEILINGFAN BEYOND
MASONRYCJ (TYP)
MP1MASONRYCJ (TYP)
SLOPING METAL ROOFBEYOND
PRE-FINISHED ALUMINUMPLATE PANELS
SLOPING METAL ROOF BEYOND PRE-FINISHED METALGUTTER & DOWNSPOUTS(DS)
DSDSDSDSDSDS
MECH YARD- REF MEP
WALL MOUNTED LIGHTFIXTURE - REF MEP
MP1MP1
BK1/BK2WALL MOUNTED LIGHTFIXTURE - REF MEP
MECH LOUVER- REF MEP
EXTERIOR BENCHESBEYOND - REF SITE PLAN
STEEL LADDER,REF ROOF PLAN
BK1/BK2BK1/BK2BK1/BK2 BK1/BK2
CH
AIN
LIN
K8'
- 0"
CJ
WALL MOUNTED LIGHTFIXTURE - REF MEP(TYP)
PRE-FINISHED MTL COPING
BK1: BRICK VENEERFIELD COLOR(TYP) -REF FINISH SCHED.
BK2: BRICK VENEERACCENT COLOR, BLACK(TYP) - REF FINISHSCHED.
NOTE: 'BK2' BRICK VENEER ACCENT COLOR, BLACKSHALL BE APPROXIMATELY 15% OF BRICK VENEER,RANDOM PATTERN AS SHOWN HERE. TYP AT ALLBRICK VENEER WALLS & MASONRY BENCHES.
MRK PANEL PROFILE
1 1/
2"
12"
1 1/
2" 16"
.
.
.MP2 - METALWALL PANEL
MBCI FW-120 / NO BEADS, SMOOTHCOLOR: GREEN
NOTE: REFER TO FINISH MATERIAL SCHEDULES FOR FURTHER PANEL DESCRIPTION
MP3 - ALUMINUMPERFORATEDPANEL
CENTRIA PERFORATED PANEL3/4" ECONOLAP
3/4"
MBCI SHADOWRIB SMOOTHCOLOR: SIGNATURE 300 METALIC
MP1 - METALWALL PANEL
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
2:38
PM
As indicatedER
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
EXTERIOR ELEVATIONS
A201R214000210
11/07/2014
REFERENCED ON /A1 A111 1/8" = 1'-0"G1EXTERIOR ELEVATION - NORTH
REFERENCED ON /A1 A111 1/8" = 1'-0"E1EXTERIOR ELEVATION - SOUTH
REFERENCED ON /A1 A111 1/8" = 1'-0"C1EXTERIOR ELEVATION - EAST
REFERENCED ON /A1 A111 1/8" = 1'-0"A1EXTERIOR ELEVATION - WEST
NTSE7SE PERSPECTIVE VIEW
2 04/07/2015 V.E. ITEMS
C1
A201
E1
A201
1/8" = 1'-0"A9TYPICAL BRICK PATTERN ELEVATION
NOTE: REFER TO A9/A201 'TYPICAL BRICK PATTERN ELEVATION' FOR BRICK VENEER DESIGN INTENT AT ALL BRICK VENEER WALLS.
NOTE: REFER TO A9/A201 'TYPICAL BRICK PATTERN ELEVATION' FOR BRICK VENEER DESIGN INTENT AT ALL BRICK VENEER WALLS.
NOTE: REFER TO A9/A201 'TYPICAL BRICK PATTERN ELEVATION' FOR BRICK VENEER DESIGN INTENT AT ALL BRICK VENEER WALLS.
NOTE: REFER TO A9/A201 'TYPICAL BRICK PATTERN ELEVATION' FOR BRICK VENEER DESIGN INTENT AT ALL BRICK VENEER WALLS.
A201R
E1
758 SF
MECH PLATFORM200
F1A211R
F1A211R
A201RC1A201R A1
A201R
G1
D1A211R
D1A211R
B C F G J
1
3
5
10
16
REF A611
REF A611
E1A631R
B1A631R
A1A304
A5A304
A7A303
A4A303
A1A303
A6A302
A4A302
A1A302
A1A301
A3A301
A5A301
A3Sim
A301
A1Sim
A301
A1Sim
A302
19
21
7
A1A211R
A1A211R
OPEN TOBELOW
14' - 0"
14' - 0"
723 SF
MECH PLATFORM201
46' - 5 3/8"
18' -
7 1
/4"
14' - 10 5/8"
5.4
57' -
7 1
/4"
ROOF BELOW
ROOF BELOW
SUN SHADE DEVICE, REF EXTERIOR ELEVATIONS
MECHANICAL DUCTS, REF MEP DOCUMENTS
ROOF LADDER,REF ROOF PLAN
A201R A9 5' - 0"
4' -
0"
2' - 6"
5' - 0"
4' -
0"
2' - 6"
5.4
REMOVABLE GUARDRAIL REFDET G4/A321
REMOVABLE GUARDRAIL REFDET G4/A321
REF DET D4/A005
REF DET D4/A005
BIG EXTERIOR FAN, REF MECH & ELEC DOCS
BIG EXTERIOR FAN, REF MECH & ELEC DOCS
ADD 2
ADD 2
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
Final Plans for Bidding and Construction
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/07/14
C:\U
sers
\Pub
lic\D
ocum
ents
\Loc
al_R
evit_
File
s\21
4000
210
FSH
Ban
d H
all A
14_v
sier
ra.rv
t4/
16/2
015
12:0
2:13
PM
1/8" = 1'-0"WM
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
COLE HIGH SCHOOLBAND HALL
SAN ANTONIO, TEXAS
MEZZANINE FLOOR PLAN
A121R214000210
11/07/2014
REFERENCED ON / 1/8" = 1'-0"A1MEZZANINE FLOOR PLAN
2 04/07/2015 V.E. ITEMS
V.E. Items
____________________________________________________________
Alderson & Associates, Inc.|Consulting Engineers|Firm No. F1008 7700 Torino, Suite 101 | San Antonio, TX 78229 |P: (210) 614-1110
Date: April 7, 2015 Client: Stantec Project Name: New Band Hall – Cole High School, Ft. Sam Houston ISD Project Number: 14-066 This addendum is generally separated into sections for convenience; however, all contractors, subcontractors, material men and other parties shall be responsible for reading the entire addendum. The failure to list an item or items in all affected sections of this addendum does not relieve any part affected from performing as per instructions, providing that the information is set forth one time any place in this addendum. These documents shall be attached to and become part of the Contract Documents for this project. PLAN ITEMS
RE: Plan Sheet M111:
Item 1: Replaced slot diffusers with 2’x2’ supply diffusers. Item 2: Added 2’x2’ return air grilles. Item 3: Changed round supply duct to rectangular duct and updated supply silencers S-1, S-2 and S-3 to
rectangular silencers.
RE: Plan Sheet M301: Item 1: Updated Air Device Schedule to reflect changes to air devices.
RE: Plan Sheet M302: Item 1: Updated Sound Attenuator Schedule to reflect changes to S-1, S-2 and S-3.
RE: Plan Sheet E111:
Item 1: Replaced decorative pendant light fixture types ‘P2’ and ‘P2E’ with dimmable 2x4 LED volumetric light fixture types ‘A2’ and ‘A2E’ in Choral Hall 115 and Band Hall 105.
RE: Plan Sheet E211:
Item 1: Removed power and switch for shades in Choral Hall 115 and Band Hall 105.
RE: Plan Sheet E501: Item 1: Removed decorative pendant light fixture types ‘P2’ and ‘P2E’. Item 2: Added dimmable 2x4 LED volumetric light fixture types ‘A2’ and ‘A2E’.
END OF ITEMS FOR V.E. xx
F-2
VFC-4
VCU-2
VCU-1
VCU-3
MS-CU-1
VFC-6
VFC-5
MS-1
A B C F G H J K
1
2
3
4
5
6
10
11
12
14
15
16
17
D E
1819
20
21
7
8
9
13
XA1390
SA7390
SA630
EA260
SA470
SA470
EA1150
EA1150
SA7360
SA2140
SA3280
SA2190
SA160
RA1140
RA1125
SA2145
GV-1SA2150
8"x10"
8"ø
6"ø
6"ø8"
ø
8"ø
12"x12"
12"x10"
6"x6
"
6"x6
"
12"x
6"
12"x
6"
12"x
10" 12"x10"
SA430
RA1225
VOA-1
RA1100
RA1185
12"x
6"
SA5185
8"ø
8"x8"
6"ø
6"ø
10"x10"
10"x10"
6"ø
10"x12"
10"ø
8"ø
12"x10"16"x
12"
16"ø
16"ø12"ø
VOA-3
30"x
14"
26"x
14"
GV-2
12"x10" 12"x10"
RA1275
12"x
6"
6"x6
"
6"x6
"
12"x
6"
RA1175
SA2195
8"ø6"
øSA21756"
ø
8"ø
SA2175
12"x12"8"x10"
6"x6"
6"x6"
12"x10"
12"x12"
8"ø
SA5185
26"x10"
24"x
14"
48"x18"
36"x10"
30"x
14"
16"ø
16"ø
1
2
1
1
1
1
3 3
4
4
5
6
7
7
7
7 3
8
8
9
3
3
9
3
3
3
3
3
10
T VFC-6
TVFC-1
TVFC-2AVFC-2B
T VFC-4
TVFC-3
TVFC-5
CORRIDOR100
LIBRARY/STORAGE110
C PRACTICE118
IDF114
CHORAL HALL115
RISER123
ENSEMBLE112
STAFF TLT113
HALL116
STORAGE121
MEN TLT103
CUST102
UNIFORM STOR111
OFFICE120
WOMEN TLT104
ELEC101
LIBRARY119
B PRACTICE109
B PRACTICE108
OFFICE106
BAND HALL105
F-3
F-4
F-5
6"ø
6"ø
11
TMS-1
16"x
12"
16"x
12"
20"x
14"
20"x
14"
S-3
S-1 S-2
10"x8"
12
20"x
14"
T
13
14 (TYP. 4)
14(TYP. 4)
15
1516
16
17
GV-38
10"x
10"
10"x10"
18
19
SA3285
SA3315
SA3320
SA3320
SA3315
SA3315
SA3285
SA3285
SA3285
SA3280
SA3315
SA3315
SA3320
SA3320
SA3315
10"ø 10"ø
10"ø
10"ø
10"ø 10"ø
10"ø
10"ø
10"ø
10"ø
10"ø
10"ø
10"ø
10"ø
10"ø
SA3320
SA3320
10"ø
10"ø
10"øSA3320
SA3315
SA3315
10"ø
10"ø
10"ø SA3315
SA3315
10"ø
10"ø
RA2RA2
RA2
RA2
RA2
RA2
SA3320
2
2
PR
OJEC
T #14 066
7700 Torino St, Suite 101San Antonio, TX 78229
Telephone: 210.614.1110© 2014 Alderson & Associates, Inc.
F-1008
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
C:\U
sers
\kel
ley\
Doc
umen
ts\1
4066
- M
echa
nica
l Cen
tral -
CF1
4_ke
lley.
rvt
4/7/
2015
3:3
0:46
PM
1/8" = 1'-0"DTA
COLE HIGH SCHOOLBAND HALL
MECHANICAL FLOORPLAN - LEVEL 1
M111R13-08
11-07-2014
SCALE: 1/8" = 1'-0"1 MECHANICAL FLOOR PLAN - LEVEL 1
(THIS SHEET ONLY)KEYED NOTES
GENERAL MECHANICAL NOTES1. ALL WORK SHALL BE IN ACCORDANCE WITH THE INTERNATIONAL
BUILDING CODE,THE INTERNATIONAL MECHANICAL CODE, AND THEOTHER CODES AND ORDINANCES OF THE AUTHORITY HAVINGJURISDICTION.
2. DUCT DIMENSIONS INDICATED ARE INSIDE DIMENSIONS CLEAR.
3. ALL RECTANGULAR SUPPLY AND RETURN DUCTS SHALL HAVE TURNINGVANES AT EACH 90 DEGREE ELBOW OR TEE.
4. ALL DUCT SHALL BE SHEETMETAL AND SHALL BE INSTALLED WITHINSULATION AS SPECIFIED.
5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED AS PER ASHRAEAND SMACNA STANDARDS.
6. MOUNT ALL THERMOSTATS AND SENSORS AT 3'-8" A.F.F.
7. PROVIDE AND INSTALL A SPIN-IN TYPE TAKE-OFF W/ VOLUMECONTROL DAMPER ON EACH ROUND SUPPLY BRANCH DUCT SERVING ASUPPLY DIFFUSER/REGISTER.
8. COORDINATE ALL DUCTWORK, GRILLES, AND EQUIPMENT WITH ALLTRADES BEFORE INSTALLING.
9. TRANSITION SUPPLY, RETURN AND EXHAUST DUCT FROM UNIT CONNECTIONSIZE TO DUCT SIZE SHOWN.
10. PROVIDE AND INSTALL VIBRATION ISOLATORS ON ANY EQUIPMENT WITHMOVING PARTS.
11. DUCT SMOKE DETECTORS TO BE PROVIDED AND INSTALLED BY THEFIRE ALARM SYSTEMS INSTALLER. COORDINATE WITH MECHANICALCONTRACTOR. INSTALL DETECTOR IN RETURN DUCT NEAR UNITCONNECTION. THE MECHANICAL CONTRACTOR SHALL BERESPONSIBLE FOR WIRING BETWEEN THE FIRE ALARM LOW VOLTAGERELAY AND THE HVAC CONTROL EQUIPMENT.
12. ALL UNITS MUST BE INSTALLED LEVEL.
13. PROVIDE CANVAS CONNECTION AT UN-ISOLATED FAN DUCTCONNECTIONS.
14. COORDINATE WITH ELECTRICAL TRADE FOR STARTERS ON EXHAUSTFANS; SEE NOTES IN FAN SCHEDULES AND ON PLANS. MECHANICALCONTRACTOR TO PROVIDE LAMINATED SIGN AT EACH SWITCH STATINGMARK NUMBER.
15. COORDINATE LOCATIONS OF NEW MECHANICAL EQUIPMENT WITHGENERAL CONTRACTOR AND STRUCTURE, TYPICAL. WHERE SIGNIFICANTCHANGES ARE REQUIRED, THE CONTRACTOR SHALL PRESENT POTENTIALMODIFICATIONS TO, AND OBTAIN APPROVAL FROM THE ENGINEER PRIORTO PROCEEDING WITH SAID WORK.
16. CAREFULLY PROTECT ALL EQUIPMENT AND MATERIAL PRIOR TOINSTALLATION. SEE SPECIFICATIONS.
17. ALL CONDENSATE DRAIN PIPING SHALL BE TYPE L COPPER, GRADEPIPING AT 1/8" PER FOOT. (MIN.).
18. PROVIDE MANUFACTURER'S RECOMMENDED CLEARANCES FOR ALLMECHANICAL EQUIPMENT.
19. SIZE AND ROUTE REFRIGERANT PIPING PER EQUIPMENTMANUFACTURER'S RECOMMENDATIONS.
20. PROVIDE SOUND CALCULATIONS FOR REVIEW FOR EACH SOUNDATTENUATOR.
21. FIRE ALARM CONTRACTOR MUST PROVIDE A SMOKE DETECTORNEAR EACH FIRE/SMOKE DAMPER. ELECTRICAL CONTRACTOR MUSTPROVIDE POWER TO EACH FSD. COORDINATE THESE REQUIREMENTSWITH OTHER TRADES.
22. CONSTRUCTION ACTIVITIES SHALL NOT IMPEDE OR OBSTRUCT THE MEANSOF EGRESS.
1 FAN-COIL UNIT TO BE SUSPENDED FROM STRUCTURE. LOCATE UNIT ABOVECEILING.
2 LOCATE MINI-SPLIT UNIT ABOVE DOOR, AS HIGH AS POSSIBLE.3 REFERENCE #1/M121 FOR CONTINUATION.4 16" DIA. OUTSIDE AIR DUCT UP TO MEZZANINE ABOVE. REFERENCE #1/M121
FOR CONTINUATION.5 6" DIA. EXHAUST DUCT UP THRU MEZZANINE ABOVE. REFERENCE #1/M121 FOR
CONTINUATION.6 LOCATE BOTTOM OF AIR DEVICE AT 13'-6" AFF.7 OUTDOOR UNITS TO BE LOCATED ON CONCRETE HOUSEKEEPING PAD.
REFERENCE STRUCTURAL DRAWINGS FOR HOUSEKEEPING PAD DETAIL.8 GRAVITY VENTILATOR LOCATED ON ROOF. COORDINATE ROOF PENETRATION
WITH STRUCTURE.9 LOCATE AIR DEVICE AT 14'-0" AFF.10 RETURN AIR DUCT OPEN TO PLENUM SPACE.11 REFERENCE DETAIL #8/M402 FOR RETURN AIR TRANSFER DETAIL.12 RETURN AIR TRANSFER DUCT LOCATED ABOVE CEILING. REFERENCE #7/M402
FOR RETURN AIR TRANSFER DETAIL.13 PROVIDE SECONDARY DRAIN PAN BELOW UNIT. DRAIN PAN SHALL EXTEND
BENEATH THE CONDENSATE RECEPTOR. REFERENCE PLUMBING DRAWINGSFOR LOCATION OF RECEPTOR.
14 CONNECT DUCT TO AIR DEVICE. AIR DEVICE PROVIDED BY MODULAR ROOMMANUFACTURER.
15 PROVIDE 24V MOTORIZED DAMPER EQUAL TO RUSKIN M# CDRS25 CONTROLDAMPER. DAMPER SHALL BE NORMALL CLOSED, SPRING RETURN, POWEREDOPEN WHEN ASSOCIATED AIR UNIT IS ENERGIZED. BALANCE DAMPER TOINDICATED AIRFLOW WHEN OPENED.
16 RETURN AIR SOUND BOOT. REFERENCE DETAIL #2/M403 FOR SOUND BOOTDETAIL.
17 PROPOSED LOCATION OF DAIKIN BACNET GATEWAY CONTROLLER.REFERENCE ELECTRICAL DRAWINGS FOR REQUIREMENTS.
18 10x10 OUTSIDE AIR DUCT SHALL PENETRATE FLOOR AND TEMRINATE 6"BELOW FLOOR IN CRAWL SPACE. CAULK AND SEAL FLOOR PENETRATION.PROVIDE MESH COVERING OVER OPEN DUCT IN CRAWL SPACE.
19 10x10 EXHAUST AIR DUCT SHALL PENETRATE FLOOR AND TEMRINATE 6"BELOW FLOOR IN CRAWL SPACE. CAULK AND SEAL FLOOR PENETRATION.PROVIDE MESH COVERING OVER OPEN EXHAUST DUCT IN CRAWL SPACE.
2 04/07/2015 V.E. ITEMS
PR
OJEC
T #14 066
7700 Torino St, Suite 101San Antonio, TX 78229
Telephone: 210.614.1110© 2014 Alderson & Associates, Inc.
F-1008
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
C:\U
sers
\kel
ley\
Doc
umen
ts\1
4066
- M
echa
nica
l Cen
tral -
CF1
4_ke
lley.
rvt
4/7/
2015
3:3
0:47
PM
DTA
COLE HIGH SCHOOLBAND HALL
MECHANICAL -SCHEDULES
M301R13-08
11-07-2014
AIR DEVICE SCHEDULE
MARK SERVICE FACE SIZETAP/DUCT
CONN. SIZEMIN.
FLOWMAX.FLOW MAX. NC
THROWPATTERN
MOUNTTYPE
TITUS*MODEL DAMPER FINISH REMARKS
EA1 EXHAUST 12x12 10x10 0 350 15 N/A SURFACE 50R NO WHITE 1/2"x1/2"x1/2" EGGCRATE; STEELEA2 EXHAUST 8x8 6x6 0 100 15 N/A SURFACE 350RL NO WHITE 3/4" BLADE SPACING; STEEL; 35 DEG. DEFLECTIONRA1 RETURN 24x12 22x10 0 600 15 N/A LAY-IN 50R NO WHITE 1/2"x1/2"x1/2" EGGCRATE; STEELRA2 RETURN 24x24 22x22 601 1400 15 N/A LAY-IN 50R NO WHITE 1/2"x1/2"x1/2" EGGCRATE; STEELRA3 RETURN 32x14 30x12 350 1150 15 N/A SURFACE 350RL NO WHITE 3/4" BLADE SPACING; STEEL; 35 DEG. DEFLECTIONSA1 SUPPLY 24x24 6" RND 0 100 20 4-WAY LAY-IN OMNI NO WHITE ARCH. SQUARE PLAQUE DIFFUSER; STEEL; THERMAL BACKPAN BLANKETSA2 SUPPLY 24x24 8" RND 101 220 20 4-WAY LAY-IN OMNI NO WHITE ARCH. SQUARE PLAQUE DIFFUSER; STEEL; THERMAL BACKPAN BLANKETSA3 SUPPLY 24x24 10" RND 221 380 20 4-WAY LAY-IN OMNI NO WHITE ARCH. SQUARE PLAQUE DIFFUSER; STEEL; THERMAL BACKPAN BLANKETSA4 SUPPLY 12x12 6" RND 0 100 20 4-WAY SURFACE OMNI NO WHITE ARCH. SQUARE PLAQUE DIFFUSER; STEEL; THERMAL BACKPAN BLANKETSA5 SUPPLY 14" DIA. 8" RND 0 250 25 360 DEG. HIGH BAY TMR NO WHITE ROUND INTLET; STEELSA6 SUPPLY 8x8 6x6 0 115 20 DOUBLE DEFLECT SURFACE 300RL NO WHITE 3/4" BLADE SPACING; STEEL; DOUBLE DEFLECTIONSA7 SUPPLY 14x12 12x10 115 400 20 DOUBLE DEFLECT SURFACE 300RL NO WHITE 3/4" BLADE SPACING; STEEL; DOUBLE DEFLECTIONXA1 TRANSFER 14x14 12x12 0 400 15 N/A SURFACE 350RL NO WHITE 3/4" BLADE SPACING; STEEL; 35 DEG. DEFLECTION
MINI-SPLIT FAN COIL UNIT SCHEDULE
MARK TYPE SERVICE
ELECTRICAL FAN COOLINGWEIGHT
(LBS) MFG MODEL NOTESVOLTS. PH.MAX AIRFLOW
(CFM)MIN AIRFLOW
(CFM)NOM. CAP.(BTU/HR)
MS-1 WALL MOUNT IDF 114 208 1 570 360 22000 30 DAIKIN FTXN24KVJU 1,2,3
MINI-SPLIT CONDENSING UNIT SCHEDULE
MARK SERVICE
ELECTRICAL COOLINGWEIGHT
(LBS) MFG MODEL NOTESVOLTS PH. MCA (A) MOCP (A)NOM. CAP.(BTU/HR) SEER
MS-CU-1 MS-1 208 1 15.0 20 22000 18.0 100 DAIKIN RKN24KEVJU 1,2
FAN SCHEDULE
MARK SERVICE TYPEWHEELTYPE
AIRFLOW(CFM)
STATICPRESSURE(IN. W.G.)
SOUNDLEVEL
DRIVETYPE
FANSPEED(RPM)
INPUT POWER(WATTS)
MOTORSIZE (HP)
MOTORSPEED (RPM) FAN CONTROL VOLTS. PH.
WEIGHT(LBS) MFG MODEL NOTES
F-1 RESTROOM/JANITOR SQ. IN-LINE BI 360 0.5 7.5 SONES DIRECT 1654 141 1/6 1550 DDC 115 1 100 COOK 90SQN15D 1,2,9F-2 STAFF RESTROOM CEILING/IN-LINE FC 75 0.25 1.6 SONES DIRECT 884 59 FRACTIONAL 884 SWITCH IN SPACE 115 1 40 COOK GC-124 1,2,3,4,5,6F-3 PATIO HVLS AIRFOIL N/A FREE AREA 35 DBA DIRECT 56 300 FRACTIONAL 56 SWITCH IN SPACE 115 1 100 BAF ESSENCE 14 FT 7,8F-4 PATIO HVLS AIRFOIL N/A FREE AREA 35 DBA DIRECT 56 300 FRACTIONAL 56 SWITCH IN SPACE 115 1 100 BAF ESSENCE 14 FT 7,8F-5 PATIO HVLS AIRFOIL N/A FREE AREA 35 DBA DIRECT 56 300 FRACTIONAL 56 SWITCH IN SPACE 115 1 100 BAF ESSENCE 14 FT 7,8F-6 CRAWL SPACE SQ. IN-LINE BI 300 0.5 6.8 SONES DIRECT 1570 137 1/6 1550 DDC 115 1 100 COOK 90SQN15D 1,2,5
GRAVITY VENTILATOR SCHEDULE
MARK SERVICEAIRFLOW
(CFM)THROAT SIZE
(DIA.)
MAX. STATICPRESSURE(IN. W.G.) MFR MODEL
WEIGHT(LBS) NOTES
GR-1 BUILDING RELIEF 2300 16x16 0.05 COOK 16X16 GR 160 1,2,3GV-1 VFC-5 115 8" 0.05 COOK 8 PR 50 1,2GV-2 VFC-6 115 8" 0.05 COOK 8 PR 50 1,2GV-3 CRAWL SPACE VENTILATION 300 12" 0.05 COOK 12 PR 50 1,2
*TITUS IS BASIS OF DESIGN; OTHER ACCEPTABLE MANUFACTURERS INCLUDE KRUEGER, METAL*AIRE, PRICE, NAILOR.GENERAL NOTES:1. FRAMES SHALL BE SUITABLE FOR CEILING OR FINISH TYPE. REFER TO ARCHITECTURAL DOCUMENTS.2. PROVIDE SQUARE TO ROUND ADAPTERS WHERE REQUIRED.3. SEE PLANS FOR ADDITIONAL NOTES ON SPECIFIC ACCESSORIES OR INSTALLATION REQUIREMENTS.
NOTES:1. PROVIDE WITH WIRED WALL-MOUNTED CONTROLLER.2. PROVIDE WITH FACTORY CONDENSATE PUMP.3. FEED THROUGH POWER FROM CONDENSING UNIT.
NOTES:1. PROVIDE WITH REFRIGERANT LINE SETS; CONFIRM SIZES/LENGTHS WITH MANUFACTURER. INSTALL PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.2. PROVIDE WITH 7 YEAR COMPRESSOR AND 5 YEAR PARTS WARRANTY.
NOTES:1. PROVIDE FACTORY DISCONNECT.2. PROVIDE FAN SPEED CONTROLLER FOR FAN BALANCING.3. PROVIDE FACTORY WHITE ALUMINUM GRILLE.4. PROVIDE FACTORY ROOF CAP.5. PROVIDE INTEGRAL GRAVITY BACKDRAFT DAMPER.6. PROVIDE TIME DELAY SWITCH.7. PROVDE GEARLESS DIRECT DRIVE MOTOR.8. PROVIDE WIRED WALL CONTROLLER.9. PROVIDE MOTORIZED DAMPER ON DISCHARGE OF FAN.
NOTES:1. PROVIDE FACTORY 14" HIGH ROOF CURB.2. PROVIDE BIRDSCREEN.3. PROVIDE BAROMETRIC DAMPER SET TO OPEN AT +0.05 IN. WG. BUILDING PRESSURE.
2
2 04/07/2015 V.E. ITEMS
PR
OJEC
T #14 066
7700 Torino St, Suite 101San Antonio, TX 78229
Telephone: 210.614.1110© 2014 Alderson & Associates, Inc.
F-1008
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
C:\U
sers
\kel
ley\
Doc
umen
ts\1
4066
- M
echa
nica
l Cen
tral -
CF1
4_ke
lley.
rvt
4/7/
2015
3:3
0:47
PM
DTA
COLE HIGH SCHOOLBAND HALL
MECHANICAL -SCHEDULES
M302R13-08
11-07-2014
VARIABLE REFRIGERANT FAN COIL SCHEDULE
MARK SYSTEM TYPE SERVICE
ELECTRICAL FAN COOLING HEATING AUXILIARY ELECTRIC HEAT
WEIGHT(LBS) MFG MODEL
BRANCH SELECTOR
NOTESVOLTS PH. MCA (A) MOCP (A)MAX FLOW
(CFM)MIN FLOW
(CFM)OUTSIDEAIR (CFM)
SOUNDRATING(DBA)
NOM. CAP.(BTU/HR)
NOM. CAP.(BTU/HR) KW MCA (A) MOCP (A) MARK MODEL VOLTAGE PHASE MCA (A) MOCP (A)
WEIGHT(LBS)
VFC-1 SYSTEM 1 DUCTED CORRIDOR/RESTROOMS 208 1 2.9 15 1130 810 N/A 43 36000 40000 N/A N/A N/A 110 DAIKIN FXMQ36PAVJU BS-1 BSVQ36PVJU 208 1 0.1 15 30 1,2,5,6VFC-3 SYSTEM 1 DUCTED CHORAL HALL 208 1 10.1 15 2540 2190 800 49 96000 108000 N/A N/A N/A 300 DAIKIN FXMQ96MVJU BS-3 BSVQ96PVJU 208 1 0.1 15 30 1,2,5
VFC-2A SYSTEM 2 DUCTED BAND HALL 208 1 9.0 15 2050 1780 1235 49 72000 81000 N/A N/A N/A 300 DAIKIN FXMQ72MVJU BS-2A BSVQ96PVJU 208 1 0.1 15 30 1,2,5VFC-2B SYSTEM 2 DUCTED BAND HALL 208 1 10.1 15 2540 2190 435 49 96000 108000 N/A N/A N/A 300 DAIKIN FXMQ96MVJU BS-2B BSVQ96PVJU 208 1 0.1 15 30 1,2,5VFC-4 SYSTEM 2 DUCTED UNIFORM STORAGE/ENSEMBLE 208 1 0.6 15 450 390 275 34 12000 13500 N/A N/A N/A 70 DAIKIN FXMQ12PAVJU BS-4 BSVQ36PVJU 208 1 0.1 15 30 1,2,5VFC-5 SYSTEM 2 DUCTED LIBRARY/OFFICE/CHORAL PRACTICE 208 1 1.5 15 635 530 115 41 18000 20000 N/A N/A N/A 80 DAIKIN FXMQ18PAVJU BS-5 BSVQ36PVJU 208 1 0.1 15 30 1,2,5VFC-6 SYSTEM 2 DUCTED LIBRARY/OFFICE/BAND PRACTICE 208 1 1.5 15 635 530 115 41 18000 20000 N/A N/A N/A 80 DAIKIN FXMQ18PAVJU BS-6 BSVQ36PVJU 208 1 0.1 15 30 1,2,5VOA-1 SYSTEM 3 DUCTED OUTSIDE AIR 208 1 3.8 15 1235 N/A 1235 47 96000 59000 7 42.06 45 270 DAIKIN FXMQ96MFVJU N/A N/A N/A N/A N/A N/A N/A 1,2,3,4,5VOA-2 SYSTEM 3 DUCTED OUTSIDE AIR 208 1 3.8 15 1235 N/A 1235 47 96000 59000 7 42.06 45 270 DAIKIN FXMQ96MFVJU N/A N/A N/A N/A N/A N/A N/A 1,2,3,4,5VOA-3 SYSTEM 3 DUCTED OUTSIDE AIR 208 1 1.9 15 635 N/A 635 42 48000 30000 5 30.05 35 200 DAIKIN FXMQ48MFVJU N/A N/A N/A N/A N/A N/A N/A 1,2,3,4,5
NOTES:1. PROVIDE FIELD OR FACTORY MOUNTED CONDENSATE PUMP ON ALL INDOOR UNITS CAPABLE OF MINIMUM 24" LIFT.2. PROVIDE DAIKIN BRC1E72 NAVIGATION STAT, OR EQUAL APPROVED BY ENGINEER FOR ALL FCU WITH AUTO CHANGE OVER AND DUAL HEAT AND COOL SETPOINTS, UNLESS NOTED OTHERWISE ON DRAWINGS.3. VRV SUPPLIER TO INCLUDE SCR STRIP HEAT FOR SUPPLY SIDE OF OA UNITS.4. SCR STRIP HEAT TO BE FIELD MOUNTED IN DUCTWORK & REQUIRES SEPERATE POWER SUPPLY FROM VRV INDOOR UNIT.5. PROVIDE BACNET/IP GATEWAY TO CONNECT VRV SYSTEM TO BAS.6. OUTSIDE AIR IS DUCTED DIRECTLY INTO SPACE FROM VOA-3, VOLUME EQUAL TO 360 CFM. OUTSIDE AIR IS PROVIDED TO SPACE, IT JUST IS NOT PROVIDED THROUGH UNIT VFC-1.
2
2 04/07/2015 V.E. ITEMS
JJ
JJ
J
J
J
IV2
OSOS
OS
OS
OS
OS OS
OSOS
IV1
A B C F G H J K
1
2
3
4
5
6
10
11
12
14
15
16
17
D E
1819
20
21
22
7
8
9
13
B1 B1
B1 B1
W1EW1E
D1
D1
D1W3
D1
D1E
D1
D1 D1
D1E D1D1E
B1 B1
B1B1 A1 A1
A1EA1A1 A1E
D1W3
D1
D1E
D1
D1 D1
D1E D1D1E
B1
B1
B1
B1E
A1A1
A1 A1
B1
B1E
B1
B1
B1E
B1
P1E
P1
P1
P1E
P1
P1E
P1
P1
P1E
P1
P1
P1E
W2E
W2E
W2E
W1E
C1E C1E
W2E
B1 B1
B1B1
B1B1
HA-31
HA-33
HA-35
HA-37
HA-39
HA-41
HA-2
(SC)HA-4
(SC)HA-4
(SC)HA-4
(SC)HA-4
S1
S1
S1
S1
S1
S1
S1S1S1S1 S1
S1
S1
K
K
(TYP)1
(TYP)2
33
LV
LV
3
K
K
LA-18
3
4
4
4
4
LV4
LA-77
LA-79
F1 F1
F1
F1
F1
F1
F1 F1
(SC)HA-8
(SC)HA-8
LA-14,16
LA-10,12
LA-28,30
T1
CORRIDOR100
LIBRARY/STORAGE110
C PRACTICE118
IDF114
CHORAL HALL115
RISER123
ENSEMBLE112
STAFF TLT113
HALL116
STORAGE121
MEN TLT103
CUST102
UNIFORM STOR111
OFFICE120
WOMEN TLT104
ELEC101
LIBRARY119
B PRACTICE109
B PRACTICE108
OFFICE106
BAND HALL105
LA-32
LA-34
(TOP)
(BOTTOM)
(2)
5
X1
X1
X1
X1
6
6
66
HA-16
5
5
5
3
3
3
3
3
3
C PRACTICE117
HA
X1
33
33
33
7
1
W4
W4
W4
HA-20
8
(TYP)9
10
10
W2
W2
W2
W2
W2E
LCP
W1E
3LV
433
(TYP)2
/2 E602
/2 E602
/2 E602 5
5 /2 E602
/2 E602
3 /2 E602
X1 1
X1
1
A2E A2 A2 A2 A2E
A2A2A2EA2A2
A2E A2 A2 A2 A2E
A2 A2E A2 A2E A2
A2A2A2A2A2
A2E A2 A2E A2 A2E
A2A2A2A2A2
A2 A2E A2 A2E A2
A2A2A2A2A2
A2E A2 A2E A2 A2E
a
a
a
a
a
a
a b
b
b
b
b
b
b c
c
c
c
c
c
c
D,aD,bD,c
,a
,b,c
a a
a a
a a
b
b
b
c
c
c
,a,b,c
D,aD,bD,c
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
a
2
2
2
PR
OJE
CT
#14
06
6
7700 Torino St, Suite 101
San Antonio, TX 78229Telephone: 210.614.1110
© 2014 Alderson & Associates, Inc.
F-1008
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
F:\
14066 -
Ele
ctr
ical C
en
tral -
CF
14_Jam
es.r
vt
4/7
/2015 3
:47:5
2 P
M
1/8" = 1'-0"
DTA
COLE HIGH SCHOOLBAND HALL
LIGHTING FLOOR PLAN -LEVEL 1
E1111307
11-07-2014
GENERAL LIGHTING NOTES (THIS SHEET ONLY)
1. ALL WORK TO BE COMPLETED IN ACCORDANCE WITH THE NATIONAL ELECTRICCODE AND THE AUTHORITY HAVING JURISDICTION.
2. COORDINATE ALL WORK WITH OTHER TRADES AS REQUIRED.
3. ALL NEW LIGHT SWITCHES TO BE MOUNTED AT 44" ABOVE FINISHED FLOOR.
4. SINGLE HOMERUNS ARE SHOWN FOR CIRCUIT IDENTIFICATION ONLY.CONTRACTOR MAY GROUP A MAXIMUM OF THREE (3) BRANCH CIRCUITS PERHOMERUN RACEWAY, UNLESS NOTED OTHERWISE. TYPICAL FOR ALLELECTRICAL FLOOR PLANS.
5. MULTI-WIRED (SHARED NEUTRAL) BRANCH CIRCUITS SHALL NOT BEINSTALLED. ALL 120- & 277- VOLT BRANCH CIRCUITS SHALL HAVE ADEDICATED INDIVIDUAL NEUTRAL CONDUCTOR.
6. ALL HOMERUNS AND RUNS BETWEEN JUNCTION BOXES TO BE A MINIMUM OF3/4" CONDUIT WITH #10 WIRE. NO MORE THAN THREE (3) CIRCUITS PERHOMERUN. ALL WIRING SHALL HAVE A SEPARATE INSULATED GREENGOUNDING CONDUCTOR. #10 CONDUCTORS SHALL EXTEND FROM OCPD TO AJUNCTION BOX IN THE AREA OF THE OUTLETS OR UTILIZATION EQUIPMENT. DROPS TO INDIVIDUAL 20A SWITCHES AND RECEPTACLES MAY BE #12 THHNCOPPER.
7. ALL ITEMS AND FIXTURES SHALL BE U.L. LISTED.
8. EXPOSED GRID CEILINGS: FLOURESCENT FIXTURES SHALL BE SUPPORTEDINDEPENDENTLY OF THE CEILING GRID BY A MINIMUM OF FOUR #9GALVANIZED WIRES ATTACHED TO THE FIXTURE AT EACH CORNER.
9. VOLTAGE DROP IN BRANCH CIRCUITS SHALL NOT EXCEED 3%.
10. ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OFELECTRICAL WORK ABOVE THE CEILING TO PROVIDE THE GREATEST POSSIBLECLEARANCE FOR PLUMBING AND MECHANICAL EQUIPMENT BOTH CURRENTAND FUTURE. CONDUITS SHALL BE KEPT TIGHT TO STRUCTURE OR ROUTEDTHROUGH STRUCTURAL TRUSSES WHEREVER POSSIBLE.
11. PROVIDE U.L. LISTED FIRE STOP SYSTEMS AT ALL PENETRATIONS THROUGHWALLS.
12. ALL JUNCTION BOX COVERS WILL BE MARKED USING "SHARPIE" OR"MARKSALOT" INDICATING THE PANEL AND CIRCUIT #'S CONTAINED WITHIN THEJUNCTION BOX.
13. ALL SWITCH COVER PLATES WILL BE MARKED TO INDICATE PANEL ANDCIRCUIT #'S USING APPROVED LABEL MAKER.
14. THERE SHALL BE NO JUNCTION BOXES LOCATED ABOVE A HARD CEILING. ALLCONNECTIONS TO FIXTURES IN A HARD CEILING WILL COME FROM A JUNCTIONBOX LOCATED IN AN ACCESSIBLE AREA OUTSIDE OF THE ROOM.
15. FIXTURES SHALL NOT BE DAISY CHAINED TOGETHER. EACH FIXTURE SHALLHAVE ONLY ONE FLEXIBLE CONDUIT CONNECTION FROM A JUNCTION BOXLOCATED WITHIN 6'.
16. FLEXIBLE CONDUIT (FMC) CAN BE USED ONLY FOR FINAL CONNECTIONS TOLIGHT FIXTURES. RUNS LONGER THAN 6' WILL NOT BE ALLOWED.
17. LIQUIDTIGHT FLEXIBLE CONDUIT (LFMC) SHALL BE USED FOR CONNECTIONS TOEQUIPMENT AND MOTORS.
KEYED NOTES (APPLIES TO THIS SHEET ONLY)
1 PROVIDE INVERTER WITH INTEGRAL TEST SWITCH IN ACCESSIBLE SPACE FOREMERGENCY LIGHT FIXTURES INDICATED ON PLAN. REFER TO LIGHTINGFIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
2 ROUTE ALL "P1E/P2E" FIXTURE THRU INVERTER INDICATED ON PLAN.
3 ROUTE EXTERIOR LIGHTING CIRCUIT THRU LIGHTING CONTROL PANEL VIA #8AWG WIRE MINIMUM. REFER TO DETAIL INDICATED ON PLAN.
4 PROVIDE LOW VOLTAGE OVERRIDE SWITCH PER IECC. SWITCH SHALLINTERFACE WITH LIGHTING CONTROL PANEL TO ALL LOCAL LIGHTINGCIRCUIT(S) REMAIN/TURN ON FOR 2 HOURS.
5 ROUTE INTERIOR LIGHTING CIRCUIT THRU LIGHTING CONTROL PANEL.CONNECT EMERGENCY EXIT AND/OR EGRESS LIGHT FIXTURE TO NORMALPOWER LIGHTING CIRCUIT SERVING THE SAME AREA AND CONNECTEMERGENCY BATTERY CONDUCTOR AHEAD OF LIGHTING CONTROL PANEL ANDANY SWITCHES OR PHOTOCELLS. EMERGENCY EGRESS LIGHTING SHALL BESWITCHED WITH NORMAL LIGHTING UNLESS NOTED OTHERWISE WITH"NL"(NIGHT LIGHT). REFER TO INTERIOR LIGHTING CONTROL DETAIL FORADDITIONAL INFORMATION.
7 ROUTE LIGHT SWITCH CIRCUIT DOWN TO LIGHT FIXTURE IN CRAWL SPACE.
8 PROVIDE LIGHT SWITCH TO CONTROL FLOOD LIGHTS MOUNT ON ROOF FORFIELD LIGHTING.
9 PROVIDE FLOOD LIGHTS MOUNTED ON ROOF FOR FIELD LIGHTING.
10 ROUTE LIGHT SWITCH CIRCUIT UP TO LIGHT FIXTURE IN MEZZANINE SPACE.
SCALE: 1/8" = 1'-0"1
LIGHTING AND CEILING FAN PLAN - LEVEL 1
1 12/11/2014 Addendum #1
2 04/07/2015 V.E. Items
J
J
J
J J
J J
J
J
A B C F G H J K
1
2
3
4
5
6
10
11
12
14
15
16
17
D E
1819
20
21
22
7
8
9
13
TLALA
HA
GFCI
GFCI/AC
1
GFCI
2
3
3
EWH-1
FACP
LA-1
LA-3
LA-5
LA-7
LA-9
LA-11
LA-13LA-15
LA-17
LA-19
LA-21
LA-23
LA-25
LA-27
LA-55
LA-57
LA-61LA-63
LA-65
LA-67
LA-73
LA-29,31
LA-33
LA-35
LA-37
LA-39
LA-20
LA-41
WP/GFCI/LOCKABLE
WP/GFCI/LOCKABLE
WP/GFCI/LOCKABLE
LA-81
REFER TO LIGHTINGPLAN FOR FAN POWER
REFER TO LIGHTINGPLAN FOR FAN POWER
REFER TO LIGHTINGPLAN FOR FAN POWER
LBLA-36
CORRIDOR100
LIBRARY/STORAGE110
C PRACTICE118
IDF114
CHORAL HALL115
RISER123
ENSEMBLE112
STAFF TLT113
HALL116
STORAGE121
MEN TLT103
CUST102
UNIFORM STOR111
OFFICE120
WOMEN TLT104
ELEC101
LIBRARY119
B PRACTICE109
B PRACTICE108
OFFICE106
BAND HALL105
EWH-2
72"LA-43
C PRACTICE117
GFCI/ACAC
LA-59
4
LCP
LA-44
LA-45
LA-46
56
AC AC
78
LA-47
LA-2
1
1
2
2
PR
OJE
CT
#14
06
6
7700 Torino St, Suite 101
San Antonio, TX 78229Telephone: 210.614.1110
© 2014 Alderson & Associates, Inc.
F-1008
N
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
KEY PLAN (NTS)
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
F:\
14066 -
Ele
ctr
ical C
en
tral -
CF
14_Jam
es.r
vt
4/7
/2015 3
:54:2
4 P
M
1/8" = 1'-0"
DTA
COLE HIGH SCHOOLBAND HALL
POWER FLOOR PLAN -LEVEL 1
E2111307
11-07-2014
KEYED NOTES (APPLIES TO THIS SHEET ONLY)
1 PROVIDE GFCI RECEPTACLE FOR DRINKING FOUNTAIN. RECEPTACLE SHALL BELOCATED INSIDE DRINKING FOUNTAIN ENCLOSURE. REFER TO ARCHITECTURALAND PLUMBING SHEETS FOR ADDITIONAL INFORMATION
2 PROVIDE COMPLETE CONNECTION TO SECURITY PANEL AND POWER FROMCIRCUIT INDICATED ON PLANS. REFER TO SPECIFICATIONS FOR ADDITIONALINFORMATION AND REQUIREMENTS. VERIFY EXACT LOCATION OF SECURITYPANEL ON TECHNOLOGY SHEET.
3 PROVIDE POWER TO CEILING MOUNTED PROJECTOR. VERIFY EXACTLOCATION/HEIGHT AND REQUIREMENTS WITH TECHNOLOGY SHEETS ANDARCHITECT PRIOR TO ROUGHIN.
4 PROVIDE POWER TO ELECTRONIC FLUSH VALVE TOILETS VIA LOW VOLTAGETRANSFORMER AS REQUIRED. PROVIDE TRANSFORMER IN ACCESSIBLECEILING SPACE. PROVIDE ACCESS DOOR IN GYPSUM WALL/CEILING IFADJACENT SPACE DOES NOT HAVE ACCESSIBLE CEILING. REFER TO PLAN FORLOCATION.
5 PROVIDE COMPLETE CONNECTION TO HVAC CONTROL PANEL.
6 PROVIDE SCHNEIDER ELECTRIC LIGHTING CONTROL PANEL. PROVIDEENCLOSURE TO HOUSE SMARTSTRUCTURE AUTOMATION SERVER AND OTHERREQUIRED MODULES. REFER TO INTERIOR AND EXTERIOR LIGHTING CONTROLDETAILS FOR ADDITIONAL INFORMATION.
7 PROVIDE NEMA L6-20R RECEPTACLE MOUNTED TO UNISTRUT ABOVE LADDERRACK. REFER TO TECHNOLOGY SHEETS FOR ADDITIONAL INFORMATION.
8 PROVIDE NEMA 5-20R RECEPTACLE MOUNTED TO UNISTRUT ABOVE LADDERRACK. REFER TO TECHNOLOGY SHEETS FOR ADDITIONAL INFORMATION.
GENERAL POWER NOTES (THIS SHEET ONLY)
1. ALL WORK TO BE COMPLETED IN ACCORDANCE WITH THE NATIONALELECTRIC CODE AND AUTHORITIES HAVING JURISDICTION.
2. ALL WALL MOUNTED RECEPTACLES TO BE LOCATED 18" A.F.F. TO BOTTOMOF BOX UNLESS OTHERWISE NOTED.
3. ALL OUTLETS SHOWN AS "AC" (ABOVE COUNTER) ARE TO BE INSTALLED 3"ABOVE COUNTER OR BACK SPLASH TO BOTTOM OF BOX.
4. SINGLE HOME RUNS ARE SHOWN FOR CIRCUIT IDENTIFICATION ONLY.CONTRACTOR MAY GROUP A MAXIMUM OF THREE (3) BRANCH CIRCUITSPER HOMERUN RACEWAY, UNLESS NOTED OTHERWISE. TYPICAL FOR ALLELECTRICAL FLOOR PLANS.
5. MULTI-WIRED (SHARED NEUTRAL) BRANCH CIRCUITS SHALL NOT BEINSTALLED. ALL 120- & 277- VOLT BRANCH CIRCUITS SHALL HAVE ADEDICATED INDIVIDUAL NEUTRAL CONDUCTOR.
6. ALL HOMERUNS AND RUNS BETWEEN JUNCTION BOXES TO BE A MINIMUMOF 3/4" CONDUIT WITH #10 WIRE. NO MORE THAN THREE (3) CIRCUITS PERHOMERUN. ALL WIRING SHALL HAVE A SEPARATE INSULATED GREENGROUNDING CONDUCTOR. #10 CONDUCTORS SHALL EXTEND FROM OCPDTO A JUNCTION BOX IN THE AREA OF THE OUTLETS OR UTILIZATIONEQUIPMENT. DROPS TO INDIVIDUAL 20A SWITCHES AND RECEPTACLES MAYBE #12 THHN COPPER.
7. COORDINATE LOCATIONS OF ALL POWER AND DATA OUTLETS WITHFURNITURE AND CASEWORK FOOTPRINTS PRIOR TO COMMENCING ANY DEVICE ROUGH-IN TO AVOID CONFLICTS OR LOCATING DEVICES BEHIND ORUNDER EQUIPMENT THAT WOULD RENDER THE DEVICE USELESS ORINACCESSIBLE.
8. PROVIDE U.L. LISTED FIRE STOP SYSTEMS AT ALL PENETRATIONSTHROUGH WALLS.
9. ELECTRICAL CONTRACTOR SHALL COORDINATE THE INSTALLATION OFELECTRICAL WORK ABOVE THE CEILING TO PROVIDE THE GREATESTPOSSIBLE CLEARANCE FOR PLUMBING AND MECHANICAL EQUIPMENTBOTH CURRENT AND FUTURE. CONDUITS SHALL BE KEPT TIGHT TOSTRUCTURE OR ROUTED THROUGH STRUCTURAL TRUSSES WHEREVERPOSSIBLE.
10. ALL SWITCHES AND RECEPTACLES SHALL BE U.L. LISTED AND SHALL BESPECIFICATION GRADE.
11. ALL FEEDER AND BRANCH CIRCUIT WIRING SHALL BE COPPER.
12. ALL JUNCTION BOX COVERS WILL BE MARKED USING "SHARPIE" OR"MARKSALOT" INDICATING THE PANEL AND CIRCUIT #'S CONTAINED WITHINTHE JUNCTION BOX.
13. ALL SWITCH AND RECEPTACLE COVER PLATES WILL BE MARKED TOINDICATE PANEL AND CIRCUIT #'S USING APPROVED LABEL MAKER.
14. IN ALL CASES VOLTAGE DROP TO LAST OUTLET MUST NOT EXCEED 3%.
15. FLEXIBLE METAL CONDUIT (FMC) CAN BE USED ONLY FOR FINALCONNECTIONS TO LIGHT FIXTURES. RUNS LONGER THAN 6' WILL NOT BEALLOWED.
16. LIQUIDTIGHT FLEXIBLE CONDUIT (LFMC) SHALL BE USED FORCONNECTIONS TO EQUIPMENT AND MOTORS.
17. ALL DATA CONDUITS, SLEEVES AND STUBS SHALL BE TERMINATED WITHPLASTIC BUSHINGS.
18. COORDINATE LOCATION OF ALL DISCONNECT SWITCHES TO ENSURE THATALL NEC MINIMUM WORKING CLEARANCES ARE MAINTAINED.
19. REFER TO BRANCH CIRCUIT SCHEDULES FOR CONDUCTOR SIZING.CIRCUITS FEEDING COMPUTERS SHALL CONSIST OF THE FOLLOWING: (1) CURRENT CARRYING CONDUCTOR (1) NEUTRAL CONDUCTOR (1) INSULATED GND. CONDUCTOR
(1) INSULATED ISOLATED GND. CONDUCTOR
20. PROVIDE CEILING ACCESS DOORS TO GAIN ACCESS TO EQUIPMENT ABOVEHARD CEILINGS.
SCALE: 1/8" = 1'-0"1
POWER FLOOR PLAN - LEVEL 1
1
1 12/11/2014 Addendum #1
2 04/07/2015 V.E. Items
PR
OJE
CT
#14
06
6
7700 Torino St, Suite 101
San Antonio, TX 78229Telephone: 210.614.1110
© 2014 Alderson & Associates, Inc.
F-1008
1
ISSUE:
CHECKED:
SCALE:
© 2014 Stantec
Stantec Project:
SHEET TITLE:
2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
H
G
F
E
D
C
B
A
H
G
F
E
D
C
B
A
FINAL PLANS FOR BIDDING ANDCONSTRUCTION
1344 SOUTH FLORESSUITE 201
SAN ANTONIO, TEXAS 78204
P 210.223.9588F 210.223.9589
11/7/2014
SAN ANTONIO, TEXAS
FORT SAM HOUSTONINDEPENDENT SCHOOL
DISTRICT
F:\
14066 -
Ele
ctr
ical C
en
tral -
CF
14_Jam
es.r
vt
4/7
/2015 3
:44:5
7 P
M
DTA
COLE HIGH SCHOOLBAND HALL
ELECTRICAL SCHEDULES
E5011307
11-07-2014
Lighting Fixture Schedule
KS Manufacturer Catalog Number Description Lamp Qty Lamp Type Ballast Qty Ballast Type Mounting Voltage Wattage
A1 LITHONIA 2VT8 3 32 ADP MVOLT 1/3 GEB10PS LP841 (DGA24FOR GYPSUM CEILING-REFER RCP)
2X4 VOLUMETRIC FLUORESCENT TROFFER, 3-LAMP PROGRAM START BALLAST.CONTRACTOR TO VERIFY EXACT MOUNTING REQUIREMENTS PERARCHITECTURAL RCP PRIOR TO ORDERING.
3 32W T8 4100K 1 ELECTRONIC RECESSED 277 V 93 VA
A1E LITHONIA 2VT8 3 32 ADP MVOLT 1/3 GEB10PS LP841 EL14(DGA24 FOR GYPSUM CEILING-REFER RCP)
SAME AS FIXTURE ABOVE EXCEPT WITH 90 MINUTE 1400 LUMEN MINIMUMEMERGENCY BATTERY BACKUP.
3 32W T8 4100K 1 ELECTRONIC RECESSED 277 V 93 VA
A2 LITHONIA 2VTL4 72L ADP EZ1 LP840 2x4 VOLUMETRIC LED TROFFER, 0-10 VOLT DIMMING DOWN TO 1%. CONTRACTORTO VERIFY EXACT MOUNTING REQUIREMENTS PER ARCHITECTURAL RCP PRIORTO ORDERING.
1 LED 1 LED DRIVER RECESSED 277 V 70 VA
A2E LITHONIA 2VTL4 72L ADP EZ1 LP840 EL14L SAME AS FIXTURE ABOVE EXCEPT WITH 90 MINUTE 1400 LUMEN MINIMUMEMERGENCY BATTERY BACKUP.
1 LED 1 LED DRIVER RECESSED 277 V 70 VA
B1 LITHONIA 2SP8 G 332 A12125 MVOLT GEB10PS LP741 (DGA24FOR GYPSUM CEILING-REFER RCP)
2x4 LENSED FLUORESCENT TROFFER, 3-LAMP PROGRAM START BALLAST.CONTRACTOR TO VERIFY EXACT MOUNTING REQUIREMENTS PERARCHITECTURAL RCP PRIOR TO ORDERING.
3 32W T8 4100K 1 ELECTRONIC RECESSED 277 V 93 VA
B1E LITHONIA 2SP8 G 332 A12125 MVOLT GEB10PS LP741 EL14(DGA24 FOR GYPSUM CEILING-REFER RCP)
SAME AS FIXTURE ABOVE EXCEPT WITH 90 MINUTE 1400 LUMEN MINIMUMEMERGENCY BATTERY BACKUP.
3 32W T8 4100K 1 ELECTRONIC RECESSED 277 V 93 VA
C1 LITHONIA C 2 32 MVOLT GEB10PS WGCUN NST (HC36 TALLCEILINGS)
GENERAL PURPOSE STRIP FIXTURE, 4' FOOT IN LENGTH WITH WIRE GUARD.CONTRACTOR TO VERIFY EXACT MOUNTING REQUIREMENTS PERARCHITECTURAL RCP AND ARCHITECT PRIOR TO ORDERING.
2 32W T8 4100K 1 ELECTRONIC CHAIN / SURFACE 277 V 62 VA
C1E LITHONIA C 2 32 MVOLT GEB10PS WGCUN NST EL SAME AS ABOVE, EXCEPT WITH EMERGENCY BATTERY PACK 2 32W T8 4100K 1 ELECTRONIC CHAIN / SURFACE 277 V 62 VA
D1 GOTHAM AF 1/42TRT 6AR MVOLT 6" DIA. RECESSED DOWNLIGHT. VERIFY TRIM FINISH WITH ARCHITECT PRIOR TOORDERING.
1 42W TRT 4100K 1 ELECTRONIC RECESSED 277 V 46 VA
D1E GOTHAM AF 1/42TRT 6AR MVOLT ELHL SAME AS ABOVE, EXCEPT WITH EMERGENCY 90 MINUTE HIGH LUMEN BATTERYPACK AND INTERGRAL TEST SWITCH.
1 42W TRT 4100K 1 ELECTRONIC RECESSED 277 V 46 VA
F1 LITHONIA FEM8 LED 9L IMAFL 277 DPMB 8' ENCLOSED AND GASKETED LINEAR LED. VERIFY MOUNTING HEIGHT WITHARCHITECT.
1 LED 1 LED DRIVER SUSPENDED 277 V 122 VA
IV1 LITHONIA EAC ISSM 125 RGM REGRESSED SURFACE MOUNT 125W EMERGENCY BATTERY BACKUP INVERTERWITH INTERGRAL TEST SWITCH. LOCATED OWNER ACCESSIBLE AREA FORFUTURE TESTING REQUIREMENTS.
IV2 LITHONIA EAC ISSM 375 SM WALL MOUNT 375W EMERGENCY BATTERY BACKUP INVERTER WITH INTERGRALTEST SWITCH. LOCATED OWNER ACCESSIBLE AREA FOR FUTURE TESTINGREQUIREMENTS.
P1 VISA LIGHTING CP5548 STM LCW5000DEDUCT ALT #2 - CP5548 STM 2FS54
4' LONG 12" SQUARE TUBE DIFFUSER LED PENDANT WITH STEM MOUNT TOCEILING/DECK.
1 LED 1 LED DRIVER SUSPENDED 277 V 70 VA
P1E VISA LIGHTING CP5548 STM LCW5000DEDUCT ALT #2 - CP5548 STM 2FS54
SAME AS ABOVE, EXCEPT WITH ROUTED THRU 375W INVTERTER "IV1". 1 LED 1 LED DRIVER SUSPENDED 277 V 70 VA
S1 120 V 11 VA
T1 ELITE LED TAPE: LB102-30F-65K, TRANSFORMER:EUM-LED-DRIVER-65W-24, MINI CHANNEL:LB100-BC-AL
17' LED TAPE LIGHT WITH ASSOCIATED TRANSFORMER, MINI CHANNEL,CONCEAL/MOUNT TRANSFORMER IN DISPLAY CASE. LED TAPE LIGHT MOUNTED INBOTH TOP AND BOTTOM COVES WITHIN DISPLAY CASE. SEE ARCHITECTURALSHEETS FOR MORE INFORMATION.
1 LED 6500K 1 LED DRIVER COVE 120 V
W1 LITHONIA WL4 D43 LP840 NX WALL BRACKET OR SURFACE MOUNT 4' LINEAR LED. 1 LED 1 LED DRIVER SURFACE/WALL 277 V 43 VA
W1E LITHONIA WL4 D43 LP840 NX EL14L WALL BRACKET OR SURFACE MOUNT 4' LINEAR LED WITH 90 MINUTE 1400 LUMENMINIMUM INTEGRAL EMERGENCY BATTERY BACKUP.
1 LED 1 LED DRIVER SURFACE/WALL 277 V 43 VA
W2 LITHONIA WSQLED 2 10A700/40K SR4 277 ELCW EXTERIOR WALL MOUNTED FULL CUT OFF LED FIXTURE, 3,851 LUMENS. VERIFYEXACT HEIGHT AND FINISH WITH ARCHITECT.
2 LED 1 LED DRIVER WALL 277 V 47 VA
W2E LITHONIA WSQLED 1 10A700/40K SR4 277 ELCW EXTERIOR WALL MOUNTED EMERGENCY FULL CUT OFF LED FIXTURE. VERIFYEXACT HEIGHT AND FINISH WITH ARCHITECT PRIOR TO ORDER AND ROUGHIN.
1 LED 1 LED DRIVER WALL 277 V 24 VA
W3 MARK LIGHTING S4LF 5FT GB H 40 AD 277 HT ABOVE SINK 5' LINEAR RECESSED SLOT FIXTURE. 1 LED 1 ELECTRONIC WALL 277 V 60 VA
W4 LITHONIA TFA 400M TA 277 FLOOD LIGHT MOUNTED TO ROOF STRUCTURE POINTING TOWARDPERFORMANCE AREA ON FIELD.
1 400W MH 1 PSMH STAND 277 V 461 VA
X1 LITHONIA EDG EL SINGLE/DOUBLE FACE BATTERY BACKUP SIDE LITE LED EXIT SIGN. REFER TOPLANS FOR REQUIRED NUMBER OF FACES, ARROWS AND MOUNTINGREQUIREMENTS(CEILING/WALL). VERIFY FINISH AND LED COLOR(RED/GREEN)WITH ARCHITECT PRIOR TO ORDERING.
1 LED 1 LED DRIVER WALL/CEILING 277 V 11 VA
Electrical Mechanical/Plumbing Equipment Schedule
HVAC UnitDesignation HP LML FLA
SubloadkW MCA MOCP Total kW Voltage Ph
HVAC UnitLocation
HVAC UnitLocation
Disconnect
FeederTag
PanelName
Circuit# Remarks
SpaceName Space #
CU-3 20.6 A 25.0 A 17.1 kW 480 V 3 EXTERIOR 30AF/3P/NF/N1
25
EWH-1 16.7 A 16.7 A 6.0 kW 20.8 A 40.0 A 7.5 kW 208 V 3 CUST 102 60AF/3P/NF/N1
50 LB 24,26,28
EWH-2 4.2 A 4.2 A 1.5 kW 5.2 A 15.0 A 1.9 kW 208 V 3 LIBRARY/STORAGE
110 30AF/3P/NF/N1
25 LB 30,32,34
F-1 15.0 A 0.0 kW 120 V 1 MECHPLATFORM
200 TOGGLE 25/1 N LB 18
F-2 15.0 A 0.0 kW 120 V 1 STAFF TLT 113 TOGGLE 25/1 N LB 41
F-6 15.0 A 0.0 kW 120 V 1 MECHPLATFORM
200 TOGGLE 25/1 N LB 40
MS-1 15.0 A 0.0 kW 208 V 1 IDF 114 30AF/2P/NF/N1
25/1 POWER FROM ASSOCIATED OUTDOOR HVACUNIT.
MS-CU-1 15.0 A 20.0 A 0.0 kW 208 V 1 EXTERIOR 30AF/2P/NF/N1
25/1 LB 5,7
SP-1 1/2 5.4 A 5.4 A 6.8 A 15.0 A 1.1 kW 208 V 1 CRAWL SPACE 30AF/2P/NF/N1
25/1 LA 40,42
VCU-1 20.5 A 25.0 A 17.0 kW 480 V 3 EXTERIOR 30AF/3P/NF/N1
25 HA 13,15,17
VCU-2 20.3 A 25.0 A 16.9 kW 480 V 3 EXTERIOR 30AF/3P/NF/N1
25 HA 19,21,23
VCU-3 20.6 A 25.0 A 17.1 kW 480 V 3 EXTERIOR 30AF/3P/NF/N1
25 HA 7,9,11
VFC-1 2.9 A 15.0 A 0.6 kW 208 V 1 MECHPLATFORM
200 30AF/2P/NF/N1
25/1 LB 6,8
VFC-2A 9.0 A 15.0 A 1.9 kW 208 V 1 MECHPLATFORM
201 30AF/2P/NF/N1
25/1 LB 2,4
VFC-2B 10.1 A 15.0 A 2.1 kW 208 V 1 MECHPLATFORM
201 30AF/2P/NF/N1
25/1 LB 21,23
VFC-3 10.1 A 15.0 A 2.1 kW 208 V 1 MECHPLATFORM
201 30AF/2P/NF/N1
25/1 LB 17,19
VFC-4 0.6 A 15.0 A 0.1 kW 208 V 1 UNIFORM STOR 111 30AF/2P/NF/N1
25/1 LB 9,11
VFC-5 1.5 A 15.0 A 0.3 kW 208 V 1 STORAGE 121 30AF/2P/NF/N1
25/1 LB 1,3
VFC-6 1.5 A 15.0 A 0.3 kW 208 V 1 LIBRARY/STORAGE
110 30AF/2P/NF/N1
25/1 LB 13,15
VOA-1(COIL) 3.8 A 15.0 A 0.8 kW 208 V 1 ENSEMBLE 112 30AF/2P/NF/N1
25/1 LB 25,27
VOA-1(HEAT) 42.1 A 45.0 A 8.7 kW 208 V 1 ENSEMBLE 112 60AF/2P/NF/N1
50/1 LB 29,31
VOA-2(COIL) 3.8 A 15.0 A 0.8 kW 208 V 1 UNIFORM STOR 111 30AF/2P/NF/N1
25/1 LB 33,35
VOA-2(HEAT) 42.1 A 45.0 A 8.7 kW 208 V 1 UNIFORM STOR 111 60AF/2P/NF/N1
50/1 LB 37,39
VOA-3(COIL) 1.9 A 15.0 A 0.4 kW 208 V 1 UNIFORM STOR 111 30AF/2P/NF/N1
25/1 LB 10,12
VOA-3(HEAT) 30.5 A 35.0 A 6.3 kW 208 V 1 UNIFORM STOR 111 60AF/2P/NF/N1
35/1 LB 14,16
Notes:
Receptacle 15480 VA 82.30% 12740 VA
Power 2580 VA 100.00% 2580 VA
Other 9965 VA 100.00% 9965 VA Total Demand(Amps): 155 A
Lighting 12574 VA 125.00% 15717 VA Total Demand(KVA): 128640 VA
Heating 9375 VA 100.00% 9375 VA Total Conn. Load(KVA): 137612 VA
Cooling 84638 VA 100.00% 84638 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 157 A 179 A 162 A
Total Load: 43537 VA 49380 VA 44679 VA
41 Lighting Lighting 20 A 1 2472 0 -- -- -- Space 42
39 Lighting Lighting 20 A 1 851 0 -- -- -- Space 40
37 Lighting Lighting 20 A 1 728 0 -- -- -- Space 38
35 Lighting Lightin... 20 A 1 981 0 -- -- -- Space 36
33 Lighting Lighting 20 A 1 1061 0 -- -- -- Space 34
31 Lighting Lighting 20 A 1 984 0 -- -- -- Space 32
29 Spare -- 20 A 1 0 0 -- -- -- -- 30
27 Spare -- 20 A 1 0 0 -- -- -- -- 28
25 Spare -- 20 A 1 0 0 3 25 A -- Spare 26
23 -- -- -- -- 5626 0 1 20 A -- Spare 24
21 -- -- -- -- 5626 0 1 20 A -- Spare 22
19 HVAC Unit(s) 'CU-2' Cooling 25 A 3 5626 1383 1 20 A Lighting Lighting 20
17 -- -- -- -- 5681 215 1 20 A Lighting Lighting 18
15 -- -- -- -- 5681 207 1 20 A Lighting Lighting 16
13 HVAC Unit(s) 'CU-1' Cooling 25 A 3 5681 0 1 20 A -- Spare 14
11 -- -- -- -- 5709 0 1 20 A -- Spare 12
9 -- -- -- -- 5709 0 1 20 A -- Spare 10
7 HVAC Unit(s) 'CU-3' Cooling 25 A 3 5709 976 1 20 A Lighting Lighting 8
5 -- -- -- -- 23375 620 1 20 A Lighting Lighting 6
3 -- -- -- -- 29937 308 1 20 A Lighting Lighting 4
1 XFMR "TLA" Lightin... 125 A 3 21591 860 1 20 A Lighting Lighting 2
CKT Circuit Description Type Trip Poles A B C Poles Trip Type Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 400 A
Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: MSB Phases: 3 Mains Type: MCB
Location: ELEC 101 Volts: 480/277 Wye A.I.C. Rating: 22000 A
Branch Panel: HA
Notes:
Receptacle 15480 VA 82.30% 12740 VA
Power 2580 VA 100.00% 2580 VA
Other 9965 VA 100.00% 9965 VA Total Demand(Amps): 175 A
Lighting 1411 VA 125.00% 1763 VA Total Demand(KVA): 63141 VA
Heating 9375 VA 100.00% 9375 VA Total Conn. Load(KVA): 74903 VA
Cooling 33593 VA 100.00% 33593 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 180 A 252 A 197 A
Total Load: 21591 VA 29937 VA 23375 VA
83 Spare -- 20 A 1 0 0 1 20 A -- Spare 84
81 FIRE ALARM CONTROL PANEL Other 20 A 1 120 0 1 20 A -- Spare 82
79 Practice Room Power Lighting 20 A 1 600 0 1 20 A -- Spare 80
77 Practice Room Power Lighting 20 A 1 600 0 1 20 A -- Spare 78
75 Heat Trace Power 20 A 1 1596 0 1 20 A -- Spare 76
73 Receptacles Recep... 20 A 1 180 0 1 20 A -- Spare 74
71 Spare -- 20 A 1 0 0 1 20 A -- Spare 72
69 Spare -- 20 A 1 0 0 1 20 A -- Spare 70
67 Receptacles - CUST 102 Recep... 20 A 1 180 0 1 20 A -- Spare 68
65 Receptacles Recep... 20 A 1 1080 0 1 20 A -- Spare 66
63 Practice Room Power - B PRACTICE 108 Miscell... 20 A 1 500 0 1 20 A -- Spare 64
61 Practice Room Power Miscell... 20 A 1 500 0 1 20 A -- Spare 62
59 Receptacles - LIBRARY/STORAGE 110 Recep... 20 A 1 1260 0 1 20 A -- Spare 60
57 Receptacles - OFFICE 106 Recep... 20 A 1 1260 0 1 20 A -- Spare 58
55 Projector - BAND HALL 105 Other 20 A 1 500 0 1 20 A -- Spare 56
53 Spare -- 20 A 1 0 0 1 20 A -- Spare 54
51 Spare -- 20 A 1 0 0 1 20 A -- Spare 52
49 Sump Pump Controller Other 20 A 1 1176 1200 1 20 A Other Window Shades 50
47 Receptacles - IDF 114 Recep... 20 A 1 180 600 1 20 A Other Window Shades - CHORAL HALL 115 48
45 FLUSH VALVE TRANSFORMER - CUST 102 Other 20 A 1 500 500 1 20 A Other HVAC CONTROLLER - ELEC 101 46
43 Receptacle for HWRP-1 Recep... 20 A 1 180 120 1 20 A Other - ELEC 101 44
41 Receptacles Recep... 20 A 1 540 562 -- -- -- -- 42
39 Receptacles Recep... 20 A 1 180 562 2 20 A Other Sump Pump 40
37 Receptacles - IDF 114 Recep... 20 A 1 360 984 1 20 A Power Heat Trace 38
35 Receptacles - IDF 114 Recep... 20 A 1 360 700 1 20 A Other Other CORRIDOR 100 36
33 Receptacles - IDF 114 Recep... 20 A 1 360 34 1 20 A Lighting Display Case Lighting 34
31 -- -- -- -- 90 34 1 20 A Lighting Display Case Lighting 32
29 Receptacles Other 20 A 2 90 0 -- -- -- -- 30
27 Receptacles - BAND HALL 105 Recep... 20 A 1 1260 915 2 20 A Other Outdoor Fan 28
25 Receptacles - BAND HALL 105 Recep... 20 A 1 360 10732 -- -- -- -- 26
23 Receptacles - BAND HALL 105 Recep... 20 A 1 1260 14020 -- -- -- -- 24
21 Receptacles - ENSEMBLE 112 Recep... 20 A 1 720 18216 3 150 A Heatin... PANEL "LB" 22
19 Projector - CHORAL HALL 115 Other 20 A 1 500 500 1 20 A Miscell... SECURITY PANEL - IDF 114 20
17 Receptacles - UNIFORM STOR 111 Recep... 20 A 1 720 143 1 20 A Lighting Exterior Step Lighting 18
15 Practice Room Power - C PRACTICE 118 Miscell... 20 A 1 500 0 -- -- -- -- 16
13 Practice Room Power - C PRACTICE 117 Miscell... 20 A 1 500 915 2 20 A Other Outdoor Fan 14
11 Receptacles - CHORAL HALL 115 Recep... 20 A 1 360 0 -- -- -- -- 12
9 Receptacles - CHORAL HALL 115 Recep... 20 A 1 720 915 2 20 A Other Outdoor Fan 10
7 Receptacles - CHORAL HALL 115 Recep... 20 A 1 900 0 1 20 A -- Spare 8
5 Receptacles - LIBRARY 119 Recep... 20 A 1 900 0 1 20 A -- Spare 6
3 Receptacles - OFFICE 120 Recep... 20 A 1 1080 0 1 20 A -- Spare 4
1 Receptacles - STORAGE 121 Recep... 20 A 1 720 360 1 20 A Recep... Receptacles 2
CKT Circuit Description Type Trip Poles A B C Poles Trip Type Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 250 A
Mounting: SURFACE Wires: 4 Mains Rating: 250 A
Supply From: TLA Phases: 3 Mains Type: MCB
Location: ELEC 101 Volts: 120/208 Wye A.I.C. Rating: 10000 A
Branch Panel: LA
Notes:
Total Demand(Amps): 93 A
Total Demand(KVA): 33593 VA
Heating 9375 VA 100.00% 9375 VA Total Conn. Load(KVA): 42968 VA
Cooling 33593 VA 100.00% 33593 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Amps: 156 A 121 A 89 A
Total Load: 18216 VA 14020 VA 10732 VA
41 HVAC Unit(s) 'F-2' - STAFF TLT 113 Cooling 15 A 1 0 0 -- -- -- Space 42
39 -- -- -- -- 4374 0 1 15 A Cooling HVAC Unit(s) 'F-6' - MECH PLATFORM 200 40
37 HVAC Unit(s) 'OAU-2(HEAT)' Cooling 45 A 2 4374 175 -- -- -- -- 38
35 -- -- -- -- 395 175 2 15 A Cooling HVAC Unit(s) "BS-X" 36
33 HVAC Unit(s) 'OAU-2(COIL)' Cooling 15 A 2 395 625 -- -- -- -- 34
31 -- -- -- -- 4374 625 -- -- -- -- 32
29 Cooling ENSEMBLE 112 Cooling 20 A 2 4374 625 3 20 A Heating EWH-2 30
27 -- -- -- -- 395 2500 -- -- -- -- 28
25 HVAC Unit(s) 'VOA-1(COIL)' - ENSEMBLE 112 Cooling 15 A 2 395 2500 -- -- -- -- 26
23 -- -- -- -- 1050 2500 3 20 A Heating EWH-1 24
21 HVAC Unit(s) 'FC-2B' Cooling 15 A 2 1050 0 -- -- -- -- 22
19 -- -- -- -- 1050 0 2 15 A -- Spare 20
17 HVAC Unit(s) 'FC-3' Cooling 15 A 2 1050 0 1 15 A Cooling HVAC Unit(s) 'F-1' - MECH PLATFORM 200 18
15 -- -- -- -- 156 3172 -- -- -- -- 16
13 HVAC Unit(s) 'FC-6' - LIBRARY/STORAGE 110 Cooling 15 A 2 156 3172 2 20 A Cooling Cooling UNIFORM STOR 111 14
11 -- -- -- -- 62 198 -- -- -- -- 12
9 HVAC Unit(s) 'FC-4' - UNIFORM STOR 111 Cooling 15 A 2 62 198 2 15 A Cooling HVAC Unit(s) 'OAU-3(COIL)' - UNIFORM STOR 111 10
7 -- -- -- -- 0 302 -- -- -- -- 8
5 HVAC Unit(s) 'MS-CU-1' Cooling 15 A 2 0 302 2 15 A Cooling HVAC Unit(s) 'FC-1' - MECH PLATFORM 200 6
3 -- -- -- -- 156 936 -- -- -- -- 4
1 HVAC Unit(s) 'FC-5' - STORAGE 121 Cooling 15 A 2 156 936 2 15 A Cooling HVAC Unit(s) 'FC-2A' 2
CKT Circuit Description Type Trip Poles A B C Poles Trip Type Circuit Description CKT
Enclosure: NEMA 1 MCB Rating: 0 A
Mounting: SURFACE Wires: 4 Mains Rating: 200 A
Supply From: LA Phases: 3 Mains Type: MLO
Location: ELEC 101 Volts: 120/208 Wye A.I.C. Rating: 10000 A
Branch Panel: LB
1
1
2
2
1 12/11/2014 Addendum #1
2 04/07/2015 V.E. Items